Data Bulletin 8000DB0701 10/2009 Raleigh, NC, USA Altivar ® 61 Variable Speed Drive PID Function Setup Retain for future use. © 2009 Schneider Electric All Rights Reserved Overview This bulletin covers only the configuration of the parameters required to set up the PID function; it assumes that all other motor parameters are set by qualified personnel before the steps described in this example are performed. Due to the multitude of possible PID control configurations, this document covers only the basic proportional-integral-derivative (PID) configuration on a stand-alone Altivar ® 61 variable speed drive (ATV61) using an analog input for control of the ATV61. This document does not describe an actual configuration and is not a training document for PID control and configuration. The values used are examples provided solely to illustrate the PID function of the ATV61. PID Control The ATV61 offers proportional-integral-derivative (PID) control. When programmed, the PID function compares the value of an analog input signal (AI1 or AI2) to a set point. The PID loop adjusts the output frequency as needed to correct the input signal, so that it equals the set point. Presumption This bulletin is written for individuals familiar with PowerSuite software user and assumes familiarity with this software. If you are not familiar with this software or ATV61 drive operation, please consult your system administrator before attempting to set the parameters for the PID function on an ATV61 drive. Requirements The following hardware and software is required: Hardware Altivar ® 61 variable speed drive with HMI V1.5 Software PowerSuite software V2.5 or higher (optional) Safety Information Notice Read these instructions carefully, and look at the equipment to become familiar with the device before trying to install, operate, or maintain it. The following special messages may appear throughout this documentation or on the equipment to warn of potential hazards, or to call attention to information that clarifies or simplifies a procedure.

Transcript of REGULADOR PID ALTIVAR.pdf

Page 1: REGULADOR PID ALTIVAR.pdf

Data Bulletin

8000DB070110/2009

Raleigh, NC, USA

Altivar® 61 Variable Speed Drive PID Function SetupRetain for future use.

© 2009 Schneider Electric All Rights Reserved

Overview This bulletin covers only the configuration of the parameters required to set up the PID function; it assumes that all other motor parameters are set by qualified personnel before the steps described in this example are performed.

Due to the multitude of possible PID control configurations, this document covers only the basic proportional-integral-derivative (PID) configuration on a stand-alone Altivar® 61 variable speed drive (ATV61) using an analog input for control of the ATV61. This document does not describe an actual configuration and is not a training document for PID control and configuration. The values used are examples provided solely to illustrate the PID function of the ATV61.

PID Control

The ATV61 offers proportional-integral-derivative (PID) control. When programmed, the PID function compares the value of an analog input signal (AI1 or AI2) to a set point. The PID loop adjusts the output frequency as needed to correct the input signal, so that it equals the set point.

Presumption This bulletin is written for individuals familiar with PowerSuite software user and assumes familiarity with this software. If you are not familiar with this software or ATV61 drive operation, please consult your system administrator before attempting to set the parameters for the PID function on an ATV61 drive.

Requirements The following hardware and software is required:

Hardware

• Altivar® 61 variable speed drive with HMI V1.5

Software

• PowerSuite™ software V2.5 or higher (optional)

Safety Information

Notice Read these instructions carefully, and look at the equipment to become familiar with the device before trying to install, operate, or maintain it. The following special messages may appear throughout this documentation or on the equipment to warn of potential hazards, or to call attention to information that clarifies or simplifies a procedure.

Page 2: REGULADOR PID ALTIVAR.pdf

Altivar® 61 Variable Speed Drive PID Function Setup 8000DB0701Safety Information 10/2009

© 2009 Schneider Electric All Rights Reserved2

A lightning bolt or ANSI man symbol in a “Danger” or “Warning” safety label on the equipment indicates an electrical hazard which, as indicated below, can or will result in personal injury if the instructions are not followed.

The exclamation point symbol in a safety message in a bulletin indicates potential personal injury hazards. Obey all safety messages introduced by this symbol to avoid possible injury or death.

Qualified Personnel For the protection of personnel and equipment, a qualified person must perform the procedures detailed in this bulletin.

A qualified person is one who has skills and knowledge related to the construction and operation of this electrical equipment and the installation, and has received safety training to recognize and avoid the hazards involved. Refer to the most current release of NFPA 70E®, “Standard for Electrical Safety in the Workplace®,” for safety training requirements.

In addition, the person must be:

• Able to read, interpret, and follow the instructions and precautions in this data bulletin and the other documentation referenced.

• Able to use the required tools listed in this data bulletin in a safe and correct manner.

Symbol Name

Lightning Bolt

ANSI Man

Exclamation Point

DANGERDANGER indicates an imminently hazardous situation which, if not avoided, will result in death or serious injury.

WARNINGWARNING indicates a potentially hazardous situation which, if not avoided, can result in death or serious injury.

CAUTIONCAUTION indicates a potentially hazardous situation which, if not avoided, can result in minor or moderate injury.

CAUTIONCAUTION, used without the safety alert symbol, indicates a potentially hazardous situation which, if not avoided, can result in property damage.

Page 3: REGULADOR PID ALTIVAR.pdf

8000DB0701 Altivar® 61 Variable Speed Drive PID Function Setup10/2009 Safety Information

© 2009 Schneider Electric All Rights Reserved 3

Before You Begin Do not use this product on machinery lacking effective point-of-operation guarding. Lack of effective point-of-operation guards on a machine can result in serious injury to the operator of that machine..

This automation equipment and related software is used to control a variety of industrial processes. The type or model of automation equipment suitable for each application will vary depending on factors such as the control function required, degree of protection required, production methods, unusual conditions, and government regulations. In some applications, more than one processor may be required, as when backup redundancy is needed.

Only the user can be aware of all the conditions and factors present during setup, operation, and maintenance of the machine; therefore, only the user can determine the automation equipment and the related safeties and interlocks which can be properly used. When selecting automation and control equipment and related software for a particular application, the user should refer to the applicable local and national standards and regulations. The National Safety Council’s Accident Prevention Manual (nationally recognized in the United States of America) also provides much useful information.

In some applications, such as packaging machinery, additional operator protection such as point-of-operation guarding must be provided. This is necessary if the operator’s hands and other parts of the body are free to enter the pinch points or other hazardous areas and serious injury can occur. Software products alone cannot protect an operator from injury. For this reason, the software cannot be substituted for or take the place of point-of-operation protection.

Ensure that the appropriate safeties and mechanical/electrical interlocks related to point-of-operation protection have been installed and are operational before placing the equipment into service. All interlocks and safeties related to point-of-operation protection must be coordinated with the related automation equipment and software programming.

NOTE: Coordination of safeties and mechanical/electrical interlocks for point-of-operation protection is outside the scope of the Function Block Library, System User Guide, or other implementation referenced in this documentation.

Start-up and Test Before using electrical control and automation equipment for regular operation after installation, the system should be given a start-up test by qualified personnel to verify correct operation of the equipment. It is important that arrangements for such a check be made and that enough time is allowed to perform complete and satisfactory testing.

WARNINGUNGUARDED MACHINERY CAN CAUSE SERIOUS INJURY

• Do not use this software and related automation equipment on equipment which does not have point-of-operation protection.

• Do not reach into machinery during operation.

Failure to follow these instructions can result in death, serious injury, or equipment damage.

Page 4: REGULADOR PID ALTIVAR.pdf

Altivar® 61 Variable Speed Drive PID Function Setup 8000DB0701Safety Information 10/2009

© 2009 Schneider Electric All Rights Reserved4

Follow all start-up tests recommended in the equipment documentation. Store all equipment documentation for future references.

Software testing must be done in both simulated and real environments.

Verify that the completed system is free from all short circuits and grounds, except those grounds installed according to local regulations (according to the National Electrical Code® in the USA, for instance). If high-potential voltage testing is necessary, follow recommendations in the equipment documentation to prevent accidental equipment damage.

Before energizing equipment:

• Remove tools, meters, and debris from equipment.

• Close the equipment enclosure door.

• Remove ground from incoming power lines.

• Perform all start-up tests recommended by the manufacturer.

Operation and Adjustments The following precautions are from the NEMA Standards Publication ICS 7.1-1995 (English version prevails):

• “Regardless of the care exercised in the design and manufacture of equipment or in the selection and rating of components, there are hazards that can be encountered if such equipment is improperly operated.”

• “It is sometimes possible to misadjust the equipment and thus produce unsatisfactory or unsafe operation. Always use the manufacturer’s instructions as a guide for functional adjustments. Personnel who have access to these adjustments should be familiar with the equipment manufacturer’s instructions and the machinery used with the electrical equipment.”

• “Only those operational adjustments actually required by the operator should be accessible to the operator. Access to other controls should be restricted to prevent unauthorized changes in operating characteristics.”

Related Documents If there are no documents recommended, this subsection can be removed.

You can download these technical publications and other technical information from our website at www.schneider-electric.us.

CAUTIONEQUIPMENT OPERATION HAZARD

• Verify that all installation and set up procedures have been completed.

• Before operational tests are performed, remove all blocks or other temporary holding means used for shipment from all component devices.

• Remove tools, meters, and debris from equipment.

Failure to follow these instructions can result in injury, or equipment damage.

Title of Documentation Reference Number

Altivar 61 Programming Manual, Sections 1.5, “Inputs/Outputs Cfg” and 1.7, “Application Funct.”

1760649

Addendum to Altivar 61 Variable Speed Drives Programming Manual,

30072-451-55

Altivar 61 Variable Speed Drive Controllers, High Horsepower, Simplified Guide,

30072-451-59

Altivar 61 Variable Speed Drive Controllers, Low Horsepower, Simplified Guide,

30072-451-60

Page 5: REGULADOR PID ALTIVAR.pdf

8000DB0701 Altivar® 61 Variable Speed Drive PID Function Setup10/2009 Safety Information

© 2009 Schneider Electric All Rights Reserved 5

Product Related Information

1. For additional information refer to NEMA ICS 1.1 (latest edition), “Safety Guidelines for the Application, Installation, and Maintenance of Solid State Control” and to NEMA ICS 7.1 (latest edition), “Safety Standards for Construction and Guide for Selection, Installation and Operation of Adjustable-Speed Drive Systems.”

User Comments We welcome your comments about this bulletin. You can reach us by e-mail at [email protected].

DANGERHAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH

• Apply appropriate personal protective equipment (PPE) and follow safe electrical work practices. See NFPA 70E.

• This equipment must be installed and serviced only by qualified electrical personnel.

• Turn off all power supplying this equipment before working on or inside equipment. Disconnect the power at the processor and at the power source.

• Always use a properly rated voltage sensing device to confirm power is off.

• Replace all devices, doors and covers before turning on power to this equipment.

• Confirm that a proper ground connection exists before applying power to the unit.

• Use only the specified voltage when operating this equipment and any associated products.

Failure to follow these instructions will result in death or serious injury.

WARNINGLOSS OF CONTROL

• The designer of any control scheme must consider the potential failure modes of control paths and, for certain critical control functions, provide a means to achieve a safe state during and after a path failure.Examples of critical control functions are emergency stop and overtravel stop.

• Separate or redundant control paths must be provided for critical control functions.

• System control paths may include communication links. Consideration must be given to the implications of unanticipated transmission delays or failures of the link. 1

• Each implementation of an Altivar 31C drive must be individually and thoroughly tested for proper operation before being placed into service.

Failure to follow these instructions can result in death, serious injury, or equipment damage.

Page 6: REGULADOR PID ALTIVAR.pdf

Altivar® 61 Variable Speed Drive PID Function Setup 8000DB0701Using the Drive Controller HMI 10/2009

© 2009 Schneider Electric All Rights Reserved6

Using the Drive Controller HMI

For instructions on using the drive controller HMI, refer to the Altivar® 61 Programming Manual, bulletin 1760649 . Be sure to press the navigation button (Enter) to do the following:

Select the highlighted menu or parameter

Save the displayed value

Factory Default Settings Table 1 shows the factory default settings. Ensure that these parameters are set according to the configuration of your drive controller and motor.

Table 1: Factory Default Settings

Macro-configuration Pumps/fans

Motor frequency 50 Hz

Motor control type Energy-saving, variable torque applications

Stop mode, normal On deceleration ramp

Stop mode, in the event of a fault Freewheel

Linear, acceleration, and deceleration ramps 3 s

Low speed 0 Hz

High speed 50 Hz

Motor thermal current Rated drive current

Standstill injection braking current 0.7 x rated drive current, for 0.5 s

Automatic starts after a fault No

Switching frequency 2.5 kHz or 4 kHz, depending on the drive controller rating

Logic inputs

LI1Forward (one operating direction), 2-wire control on transition

LI2 Inactive (not assigned)

LI3 Switching of the 2nd speed reference

LI4 Fault reset

LI5, LI6 Inactive (not assigned)

Analog inputsAI1 1st speed reference, 0–10 Vdc

AI2 2nd speed reference, 0–20 mA

Relay outputs

R1The contact opens upon error detection (drive off).

R2The contact closes when the drive is operating (drive running).

Analog output AO1 0–20 mA, inactive (not assigned)

Page 7: REGULADOR PID ALTIVAR.pdf

8000DB0701 Altivar® 61 Variable Speed Drive PID Function Setup10/2009 Setting the Access Level

© 2009 Schneider Electric All Rights Reserved 7

Setting the Access Level Set the access level to the drive configuration to either Advanced or Expert.

Using the HMI:

a. From the Main Menu, select ACCESS LEVEL.

b. Select ADVANCED or EXPERT, then press Enter.

Using PowerSuite™ software:

a. From the navigation pane on the left side of the screen, under ATV61, select Access Level.

b. Select either Advanced access or Expert access from the drop-down menu.

Figure 1: Setting the Access Level Using the HMI

Figure 2: Setting the Access Level Using the PowerSuite Software

Access Level

Navigation Pane>ATV61>Access Level

Drop-down Menu

Page 8: REGULADOR PID ALTIVAR.pdf

Altivar® 61 Variable Speed Drive PID Function Setup 8000DB0701Setting the Drive Configuration Parameters 10/2009

© 2009 Schneider Electric All Rights Reserved8

Setting the Drive Configuration Parameters

Refer to Sections 1.5, “Inputs/Outputs Cfg” and 1.7, “Application Funct.” of the Altivar® 61 Programming Manual, Software Version 1.5, for detailed descriptions and additional options available for configuring the ATV61.

Input Configuration

Setting the Wire Control Set the wire control to two wire or three wire. The factory default setting is 2 wire [2C].

Using the HMI:

a. From the Main Menu, select DRIVE MENT > INPUTS/OUTPUTS CFG > 2/3 WIRE CONTROL.

b. Select either 2 WIRE TYPE or 3 WIRE TYPE, then press Enter.

c. Press the Esc button.

Using PowerSuite™ software:

a. Using the navigation pane on the left side of the screen, expand Inputs/Outputs Configuration, then select Logical Inputs.

b. From the TCC 2 / 3 wire control drop-down menu, select the appropriate wire control setting.

Figure 3: Setting the Wire Control Using the HMI

Figure 4: Setting the Wire Control Using PowerSuite Software

Page 9: REGULADOR PID ALTIVAR.pdf

8000DB0701 Altivar® 61 Variable Speed Drive PID Function Setup10/2009 Setting the Drive Configuration Parameters

© 2009 Schneider Electric All Rights Reserved 9

Logic Inputs Configure logic inputs LI1 through LI6 according to the requirements of your application.

Analog Inputs Configure the analog input signal type as required (for example, 0–10 Vdc or 4–20 mA).

NOTE: AI1 is a voltage only input; AI2 is configurable for voltage or current.

To set the AI1 parameters, follow the steps below. (To set the AI2 parameters, follow the same steps but select AI2 Configuration.)

Using the HMI:

a. From the Main Menu, select: DRIVE MENU > 1.5 INPUTS/OUTPUTS CFG > AI1 CONFIGURATION.

Adjust the AI1 MIN VALUE and AI1 MAX VALUE as required for your device.

Using PowerSuite™ software:

a. Using the navigation pane on the left side of the screen, expand Inputs/Outputs configuration, then select Analogue inputs. Refer to Figure 7 on page 10.

b. Under Configuration AI1, set the AI1 minimum value and AI1 maximum value.

Example—If your device is a 2–10 Vdc input, set the AI1 minimum value to 2 Vdc and the AI1 maximum value to 10 Vdc.

The values for the operating range are set in the PID function. See Table 2 on page 10.

Figure 5: Setting the Analog Inputs Using the HMI

Figure 6: Setting the Analog Inputs Min and Max Value

Page 10: REGULADOR PID ALTIVAR.pdf

Altivar® 61 Variable Speed Drive PID Function Setup 8000DB0701Setting the Drive Configuration Parameters 10/2009

© 2009 Schneider Electric All Rights Reserved10

Figure 7: Setting the Analog Inputs Using PowerSuite™ Software

Table 2: PID Regulator Parameter Assignments

HMI PowerSuite™ Software Description

PID Feedback Assignment PIF PI fdbk assignment Specify which analog input to set as the reference, either AI1 or AI2.

Min PID Feedback PIF1 Minimum PID feedback Specify the range of your input device. Among the possibilities are a range of: pressure (0 – 20 psig), flow (0 – 500 gpm), or temperature (–100 °F – 300 °F).

For example, if an input device is scaled at 0 – 30 psig to 0 – 10 Vdc, set the Min PID feedback to 0 and the Max PID feedback to 30.

Max PID Feedback PIF2 Maximum PID feedback

Min PID Reference PIP1 Minimum PID reference Establish the limits to which the operator can adjust the setpoint.

In the above example, to limit the setpoints to a range of 12 – 16 psig, set the Min PID reference to 12 and the Max PID reference to 16.Max PID Reference PIP2 Maximum PID reference

Act. Internal PID Ref. PII Internal reference PISet the value to Yes. This enables the operator to enter a setpoint value directly into the drive controller.

Internal PI Ref. RPI Internal PI reference Set the value to the desired setpoint.

PID Proportional Gain RPG PI Proportional gainThese values are relative to the loop characteristics; therefore, an experienced operator should provide these values.

PID Integral Gain RIG Integral gain PI regulator

PID Derivative Gain RDG PID derivative gain

PID Correct Reverse PIC PID correction reverse

If you set this value to No, the speed of the motor increases when the error is positive (for example, pressure control with a compressor).

If you set this value to Yes, the speed of the motor decreases when the error is positive (for example, temperature controls using a cooling tower fan).

Page 11: REGULADOR PID ALTIVAR.pdf

8000DB0701 Altivar® 61 Variable Speed Drive PID Function Setup10/2009 Setting the Drive Configuration Parameters

© 2009 Schneider Electric All Rights Reserved 11

PID Function Configuration Configure the PID function as described in “PID Regulator” below.

NOTE: While configuring the PID loop, keep in mind that the PID Regulator function does not allow negative values in the Internal PID Reference setpoint. So when using negative values, configure your control as a percentage.

If a temperature device is scaled at -100 to +300 °F, enter the Minimum PID Feedback as 0 (corresponding to -100 °F) and the Maximum PID Feedback as 100 (corresponding to +300 °F). Then, calculate the Internal PID Reference or setpoint as a percentage of the range. For example, an 80 °F setpoint is 45%; therefore, set the Internal PID Reference to 45.

PID Regulator Using the HMI:

a. From the Main Menu, select:DRIVE MENU > APPLICATION FUNCT. > PID REGULATOR

b. From the PID REGULATOR menu, select the parameters shown in Table 2 on page 10 and set the values according to the description.

Figure 8: Setting the PID Regulator Parameters

Page 12: REGULADOR PID ALTIVAR.pdf

Altivar® 61 Variable Speed Drive PID Function Setup 8000DB0701Data Bulletin 10/2009

Electrical equipment should be installed, operated, serviced, and maintained only by qualified personnel. No responsibility is assumed by Schneider Electric for any consequences arising out of the use of this material.

Schneider Electric8001 Knightdale BlvdKnightdale, NC 27545 USA([email protected])www.schneider-electric.us

© 2009 Schneider Electric All Rights Reserved12

Altivar® is a registered trademark of Schneider Electric. Other trademarks used herein are the property of their respective owners.

Using PowerSuite™ software:

a. Using the navigation pane on the left side of the screen, expand the Applicative functions menu. Refer to Figure 9.

b. Select PID regulator and set the values of the parameters shown in Table 2 on page 10 according to the description.

Figure 9: Configuring the PID Function Using PowerSuite™ Software