Reflected Ceiling Plan & Details

download Reflected Ceiling Plan & Details

of 1

description

Reflected Ceiling Plan & Details

Transcript of Reflected Ceiling Plan & Details

  • METAL STUD BRACING

    TO STRUCTURE ABOVE

    SEE REFLECTED CLG. PLAN

    SEE REFLECTED CLG. PLAN

    3 5/8" X 25 GA

    FINISH SCHEDULE

    FIN. CLG., SEE

    METAL STUDS @ 16" O.C.

    3 5/8" X 25 GA

    GWB, 5/8"

    3 5/8" X 25 GA

    METAL STUDS @ 16" O.C.

    @ 48" O.C.

    FACE OF WALL CABINET

    FINISH SCHEDULE

    FIN. CLG., SEE ROOM

    CLG. PLAN

    SEE REFL.

    GWB, 5/8"

    SEE REFLECTED CLG. PLAN

    STUDS @ 16" O.C.

    3 5/8" X 25 GA MTL.

    TO STRUCT. ABOVE

    GWB, 5/8"

    3 5/8" X 25 GA

    METAL STUDS

    FIN. CLG., SEESEE FLOOR PLAN &

    PARTITION SCHED.

    SEE REFLECTED CLG. PLAN

    @ 16" O.C.

    6"

    6"

    SEE REFLECTED CEILING PLAN

    6"

    6"

    ALIGN WITH ADJACENT PART.

    UNLESS DIMENSIONED IN PLAN

    6"6"

    FINISH SCHEDULE

    1" MINIMUM UNLESS

    DIMENSIONED

    OTHERWISE IN PLAN

    FLUORESCENT

    COVE LIGHT

    4"

    FLUORESCENT STRIP

    LIGHT FIXTURE

    3"

    5"

    8"

    6"

    5"5"

    4"

    3'-2" 5"

    2"

    6"

    6"

    SEE REFELCTED CLG. PLAN

    6"

    6"

    5"

    9"

    6"

    4" 6"

    SEE REFELCTED CLG. PLAN5"

    SCHEDULED

    PARTITION

    SEE REFLECTED CEILING

    PLAN

    FOR HEIGHT ABOVE

    FINISHED

    FLOOR

    3 5/8" X 25 GA

    METAL STUDS @ 16" O.C.

    TO STRUCTURE ABOVE

    WITH 5/8" GWB, PTD

    DECORATIVE FIXTURE

    AS SCHEDULED

    8'-0" A.F.F.

    SEE REFLECTED CLG. PLAN

    5/8" PAINTED GYP. BD.

    ON METAL STUD (22 GA)

    SCHEDULED ACT

    3 5/8" X 25 GA

    METAL STUDS @ 16" O.C.

    TO STRUCTURE ABOVE

    WITH 5/8" GWB, PTD

    SCHEDULED ACT

    SEE REFLECTED CLG. PLAN

    SCHEDULED

    ACT

    8'-0" A.F.F.

    3 5/8" X 25 GA

    METAL STUDS @ 16" O.C.

    TO STRUCTURE ABOVE

    WITH 5/8" GWB, PTD

    8'-0" A.F.F.

    7'-4" A.F.F.

    3 5/8" X 25 GA

    METAL STUDS @ 16" O.C.

    TO STRUCTURE ABOVE

    WITH 5/8" GWB, PTD

    SCHEDULED ACT

    8'-8" AFF

    5/8" PAINTED GYP. BD.

    ON 2 1/2" METAL STUD (22 GA)

    SEE REFLECTED CLG. PLAN

    FIN. CLG.

    3 5/8" X 25 GA MTL.

    STUDS @ 16" O.C.

    TO STRUCT. ABOVE

    5/8" GYP. BD.

    SEE FLOOR PLAN &

    PARTITION SCHED.

    3 5/8" X 25 GA

    METAL STUDS

    @ 16" O.C.

    SEE REFLECTED CLG. PLAN

    3 5/8" X 25 GA

    METAL STUDS @ 16" O.C.

    TO STRUCT. ABOVE

    TYPE A TYPE B TYPE C

    TYPE D

    TYPE H

    TYPE F

    TYPE G

    TYPE E

    PER SCHEDULE

    FIN. WALL

    MOULDING

    METAL WALLEXPOSED CROSS

    TEE

    EXPOSED MAIN

    TEE

    WIRE HANGER

    BEYOND

    TILE UNITS

    LAY-IN ACOUST.

    5/8" GYP. BD.

    HANGERS AT

    4'-0" O.C. MAX.

    FIN. WALL

    METAL TRIM

    CHANNEL

    METAL RUNNER

    JOINT

    1-1/2" METAL CHANNELS

    @ 4'-0" O.C. MAX.

    FURRING CHANNELS

    @ 24" O.C. MAX.

    CONTROL

    CLIPS OR WIRE

    FURRING CHANNEL

    GWB

    8' - 0" A.F.F.

    2'x2' ACOUSTIC CEILING TILE. ALL CEILING GRIDS ARE CENTERED IN ROOM UNLESS

    OTHERWISE DIMENSIONED IN PLAN

    2'x4' ACOUSTIC CEILING TILE. ALL CEILING GRIDS ARE CENTERED IN ROOM UNLESS

    OTHERWISE DIMENSIONED IN PLAN

    GYPSUM WALLBOARD CEILING - ALIGN WITH ADJACENT PARTITION UNLESS

    OTHERWISE DIRECTED IN PLAN

    DENOTES CEILING HEIGHT ABOVE FINISHED FLOOR. ALL CEILING HEIGHTS ARE

    8'-0" UNLESS OTHERWISE NOTED IN PLAN.

    MECHANICAL SYSTEMS PER ENGINEERING DRAWINGS

    1'x4' FLUORESCENT LIGHT FIXTURE

    2'x2' FLUORESCENT LIGHT FIXTURE

    2'x4' FLUORESCENT LIGHT FIXTURE

    RECESSED INCANDESCENT OR FLUORESCENT CAN LIGHT FIXTURE

    WALL MOUNTED LIGHT FIXTURE - SEE INTERIOR ELEVATIONS FOR MORE INFORMATION

    '1x4' 'BASKET' FLUORESCENT INDIRECT LIGHT FIXTURE

    FLUORESCENT COVE LIGHT FIXTURE

    SURFACE MOUNTED DECORATIVE FIXTURE

    WALL MOUNTED FLUORESCENT LIGHT FIXTURE

    2'x2' 'BASKET' FLUORESCENT LIGHT FIXTURE.

    SECURITY CAMERA

    SYMBOL DESCRIPTION

    REFLECTED CEILING PLAN SYMBOLS KEY

    C

    DECORATIVE PENDANT LIGHT FIXTURE PER ELECTRICAL DRAWINGS

    WALL MOUNTED LIGHT FIXURE PER ELECTRICAL DRAWINGS

    INGROUND LIGHT FIXTURE PER ELECTRICAL DRAWINGS

    GROUND MOUNTED SPOTLIGHT FIXTURE PER ELECTRICAL DRAWINGS

    2' - 3"

    2' - 0"2' - 0"

    2' - 3"

    2' - 0"

    2' - 0"

    2' - 0"

    2' - 0"

    A.F.F.

    2' x 4' ACT

    9' - 0"

    A.F.F.

    TYPE B

    8' - 8"

    A.F.F.

    TYPE A

    8' - 8"

    A.F.F.

    TYPE B

    8' - 8"

    A.F.F.

    2' x 2' ACT

    9' - 0"

    A.F.F.

    2' x 2' ACT

    9' - 0"

    A.F.F.

    2' x 2' ACT

    9' - 0"A.F.F.

    2' x 2' ACT

    9' - 0"

    A.F.F.

    2' x 2' ACT

    9' - 0"

    A.F.F.

    2' x 2' ACT

    9' - 0"

    A.F.F.

    2' x 2' ACT

    9' - 0"

    A.F.F.

    TYPE B

    8' - 8"

    A.F.F.

    TYPE B

    8' - 8"

    RC4 RC4 RC4 RC4

    RC4 RC4 RC4 RC4

    RC4

    RC4

    RC4

    RC4

    RC4

    RC4

    RC2

    RC2

    RC2

    RC2

    A.F.F.

    GWB

    11' - 4"

    A.F.F.

    GWB

    11' - 4"

    RC5 RC5

    RC5 RC5

    RC5 RC5

    RC6 RC6

    RC6 RC6

    2' - 0"

    2' - 0"2' - 0"

    2' - 0"

    RC3RC3

    SB

    SB

    SB

    SB

    SB

    SB

    SB

    SB

    SB

    SB

    SB

    SB

    SB

    SB

    SB

    RC1 RC1

    RC1

    RC1

    RC1

    RC1

    3

    A. ALL FIXTURES UNLESS NOTED OTHERWISE SHALL BE

    LOCATED WITHIN THE CETNER OF THE APPROPRIATE

    CEILING TILE, OR SHALL BE SPREAD EVENLY AND

    SYMMETRICALLY WITHIN THE GYPSUM BOARD CEILING

    UNLESS NOTED OTHERWISE.

    B. CEILING TILES WITHIN EACH ROOM SHALL BE CENTERED

    WITHIN THE MAJOR RECTANGULAR SPACE, UNLESS NOTED

    OTHERWISE. DO NOT CUT CEILING TILES LESS THAN 4"

    WIDE.

    C. ALL SPRINKLER HEADS SHALL BE WITHIN THE

    APPROPRIATE CEILING TILES OR SHALL BE IN A

    SYMMETRIC PATTERN IN A DRYWALL CEILING.

    D. PARTIAL REMOVAL/DEMOLITION OF EXISTING

    CEILINGS TO REMAIN NECESSARY AS A RESULT OF MEP

    INSTALLATION SHALL BE COORDINATED WITH THE MEP

    DRAWINGS. CONTRACTOR TO REPLACE ALL CEILINGS

    DAMAGED AS A RESULT OF REQUIRED MEP INSTALLATION.

    E. DO NOT CUT TILES IN A "U" SHAPE TO FIT AROUND

    PARTITION EDN CAPS AND OTHER PROTRUSIONS. CUT

    TILES ON AN "L" AND PROVIDE AN ADDITIONAL SUPPORT

    BAR AS NECESSARY.

    F. ALL CEILING HEIGHTS TO BE 8'-0" UNLESS NOTED

    OTHERWISE.

    G. DRAWING LOCATES CEILING MOUNTED LIGHTS. OTHER

    CEILING MOUNTED ITEMS OTHER THAN LIGHTS SHALL BE

    LOCATED 12" FROM BOTH ADJACENT EDGES OF A CEILING

    TILE TO THE CENTER OF THE ITEM, UNLESS OTHERWISE

    NOTED. CEILING MOUNTED ITEMS TO BE CENTERED ON

    SHORT DIMENSION OF MAIN CORRIDOR, UNLESS NOTED

    OTHERWISE.

    H. REFER TO M.E.P. DRAWINGS FOR ADDITIONAL CEILING

    MOUNTED ITEMS.

    I. ALL GYPSUM BULKHEADS AND CEILINGS TO BE P-5 UNLESS

    NOTED OTHERWISE.

    GENERAL REFLECTING CEILING PLAN NOTES

    NO FINISHED CEILING - OPEN TO

    STRUCTURE ABOVE

    WALL MOUNTED LIGHT FIXTURE PER

    ELECTRICAL PLANS.

    OPEN TO ABOVE - SEE SECOND FLOOR

    REFLECTED CEILING PLAN FOR MORE

    INFORMATION.

    EXTERIOR WALL MOUNTED LIGHT

    FIXTURE PER ELECTRICAL PLANS.

    INGORUND LIGHT FIXTURE PER

    ELECTRICAL DRAWINGS.

    GROUND MOUNTED SPOTLIGHT FIXTURE

    PER ELECTRICAL DRAWINGS.

    RC1

    RC2

    RC3

    RC4

    RC5

    REFLECTING CEILING PLAN NOTES

    RC6

    3 NOT USED

    TYPICAL GWB BULKHEAD DETAILS - SCALE: 1-1/2" = 1'-0"

    3

    NOT USED

    DRAWING NUMBER

    8

    a

    DRAWING TITLE

    CRGA PROJECT NUMBER

    DATE

    PROJECT TITLE

    CLIENT

    PROJECT KEY PLAN

    CONSULTANTS

    SEAL

    STATE OF MARYLAND LICENSE NUMBER:14696

    2008 CR GOODMAN ASSOCIATES, LLC

    THESE DRAWINGS ARE THE PROPERTY OF THE ARCHITECT,

    CR GOODMAN ASSOCIATES, LLC. UNAUTHORIZED

    REPRODUCTION FOR ANY PURPOSE IS AN INFRINGEMENT

    UPON COPYRIGHT LAWS. VIOLATORS WILL BE SUBJECT TO

    PROSECUTION TO THE FULLEST EXTENT OF THE LAW.

    ISSUE NUMBERDATE

    912 COMMERCE ROAD

    ANNAPOLIS, MD 21401

    V - 410-841-2570

    F - 410-841-2575

    b

    c

    d

    e

    f

    g

    7654321

    87654321

    FAX: 301-475-8705

    A151

    FIRST FLOOR

    REFLECTED

    CEILING PLAN &

    DETAILS

    08.056.A

    12/09/2008

    MEDICAL OFFICE

    BUILDING

    ST. MARY'S

    HOSPITAL

    SITE ENGINEER

    N.G & O ENGINEERING INC.

    23725 THREE NOTCH ROAD, SUITE 200

    HOLYWOOD, MARYLAND 20636

    PHONE: 301-475-8700

    STRUCTURAL ENGINEER

    MORABITO CONSULTANTS, INC

    952 RIDGEBROOK ROAD, SUITE 1700

    SPARKS, MARYLAND 21152

    PHONE: 410-467-2377

    MECHANICAL & ELECTRICAL ENGINEER

    LEACH WALLACE ASSOCIATES, INC

    6522 MEADOWRIDGE ROAD

    ELKRIDGE, MARYLAND 21075

    PHONE: 410-579-8100

    FAX: 410-467-4132

    FAX: 410-540-9041

    SCALE: 1/8" = 1'-0"A151

    C1FIRST FLOOR

    REFLECTED CEILING PLAN

    SCALE: 3" = 1'-0"A151

    E5TYPICAL

    ACOUSTICAL TILE CEILING

    SCALE: 3" = 1'-0"A151

    D5TYPICAL

    SUSPENDED GYP. BD. CEILING

    0' 2' 4' 8' 16'1/8" = 1'-0"

    PERMIT SET 12/09/08 1

    BID ISSUE 12/22/08 2

    ADDENDUM #1 01/09/09 3

    NOTE: FOR EMERGENCY ELECTRICAL CLOSET, ELECTRICAL

    ROOM, IT CLOSET, WATER ROOM AND SHELL SPACES SEE

    ELECTRICAL PLANS.