Reference IEC Fault

download Reference IEC Fault

of 37

Transcript of Reference IEC Fault

  • 8/9/2019 Reference IEC Fault

    1/37

    SKM Power*Tools for Windows

    Power*Tools

    for Windows

    IEC 60909_FAULT Reference

    Manual

    Electrical Engineering Analysis Software

    for Windows

    Copyright 2006, SKM Systems Analysis, Inc

    All Rights Reserved

  • 8/9/2019 Reference IEC Fault

    2/37

    12/4/2006

    Information in this document is subject to change without notice. No part of this document may be reproduced or

    transmitted in any form or by any means, electronic or mechanical, without the express written consent of SKM

    Systems Analysis, Inc. No patent liability is assumed with respect to the use of the information contained herein.

    Although every precaution has been taken in the preparation of this manual, the publisher and author assume no

    responsibility for errors or omissions. Neither is any liability assumed for damages resulting from the use of

    information contained herein. For information, address SKM Systems Analysis, Inc., PO Box 3376, Manhattan

    Beach, CA 90266-1376, USA.

    2006 SKM Systems Analysis, Inc. All rights reserved.

    Power*Tools, CAPTOR and DAPPER are registered trademarks and HI_WAVE and I*SIM are trademarks of

    SKM Systems Analysis, Inc.

    Microsoft is a registered trademark and Windows is a trademark of Microsoft Corporation.

    Intel is a registered trademark and Pentium is a trademark of Intel Corporation.

    ACAD and AutoCAD are registered trademarks of AUTODESK, Inc.

    WordPerfect is a registered trademark of Novell, Inc.

    Lotus and 1-2-3 are registered trademarks of Lotus Development Corporation.

    Arial is a registered trademark of The Monotype Corporation, PLC.

    PIXymbols is a trademark of Page Studio Graphics

    ImageStream Graphics Filters is a registered trademark and ImageStream is a trademark of ImageMark Software

    Labs, Inc.

    PIXymbols Extended Character Set. Copyright 1995. Page Studio Graphics. All rights reserved.For information, address Page Studio Graphics, 3175 North Price Road, Suite 150, Chandler, AZ 85224.

    Phone/Fax: (602) 839-2763.

    ImageStream Graphics & Presentation Filters. Copyright 1991-1995. ImageMark Software Labs, Inc. All

    rights reserved.

    Various definitions reprinted from IEEE Std 100-1992, IEEE Standard Dictionary of Electrical and Electronics

    Terms, copyright 1992 by the Institute of Electrical and Electronics Engineers, Inc. The IEEE takes no

    responsibility or will assume no liability for the reader's misinterpretation of said information resulting from its

    placement and context in this publication. Information is reproduced with the permission of the IEEE.

    MathType math equation editing fonts are licensed from Design Science, Inc.

    1987-1996 by Design Science, Inc. All rights reserved.

  • 8/9/2019 Reference IEC Fault

    3/37

    SKM Power*Tools for Windows

    Contents

    1 IEC_FAULT STUDY 1-1

    1.1 What is the IEC_FAULT Study?....................................................................1-2

    1.2 Engineering Methodology................................................................................1-31.2.1 IEC Standard 909 .......................................................................................1-31.2.2 Comparing the ANSI and IEC Short Circuit Standards .............................1-3

    1.2.3 Initial Symmetrical Short Circuit Current ..................................................1-4dc Current...............................................................................................................1-5Peak Current...........................................................................................................1-5

    Breaking Current ....................................................................................................1-5

    Steady State Current...............................................................................................1-5

    1.2.4 IEC Standard 909 Terms ............................................................................1-61.2.5 Conventional Methodology........................................................................1-61.2.6 Requirements for Computer Solutions .......................................................1-71.2.7 Equations....................................................................................................1-71.2.8 IEC Standard 909 Unbalanced Short Circuit Calculations.........................1-9

    1.3 PTW Applied Methodology...........................................................................1-111.3.1 Before Running the IEC_FAULT Study..................................................1-111.3.2 Running the IEC_FAULT Study..............................................................1-111.3.3 IEC_FAULT Study Options.....................................................................1-11

    Report and Study Options ....................................................................................1-12

    Report Type......................................................................................................1-12

    Short Circuit Type............................................................................................1-12

    All or Selected..................................................................................................1-12

    Faulted Bus.......................................................................................................1-12

    System Modeling..................................................................................................1-12

    Use Sequence Network or Three-Phase Factors ..............................................1-13

    Pre-Fault Voltage .............................................................................................1-13

    Calculate max. or min. Short Circuit................................................................1-13

    System Frequency ............................................................................................1-13

    Tmin(.02 to 99 Sec.) for Iband Idc ...................................................................1-13

    Model Primary Transformer Tap (Ignore Secondary)......................................1-13

    Time Varying Report............................................................................................1-13Voltage Factors ....................................................................................................1-13

    1.3.4 Assumptions of the IEC_FAULT Study ..................................................1-141.3.5 Component Modeling...............................................................................1-14

    Contribution Data.................................................................................................1-14

    Network Feeders ..............................................................................................1-14

    Synchronous Generators and Motors ...............................................................1-15

    Asynchronous Induction Motors......................................................................1-16

    Cables and Transformers......................................................................................1-17

  • 8/9/2019 Reference IEC Fault

    4/37

    IEC_FAULT ii Reference Manual

    12/4/2006

    1.3.6 Error Messages ........................................................................................ 1-181.3.7 Reports..................................................................................................... 1-19

    1.4 Application Examples.................................................................................... 1-191.4.1 Generator and Network Feeders .............................................................. 1-191.4.2 Meshed Network Considerations............................................................. 1-221.4.3 Far Versus Near Considerations .............................................................. 1-24

    1.4.4 Example from Plant ................................................................................. 1-25

    Index IEC_FAULT i

  • 8/9/2019 Reference IEC Fault

    5/37

    SKM Power*Tools for Windows

    1 IEC 6 9 9_FAULT Study

    This chapter examines the short-circuit current calculation procedures used in the

    IEC_FAULT Short Circuit Study. The chapter includes a systematic methodology and

    applies the methodology to numerous practical examples. You can also run a

    Comprehensive Short Circuit Study (in PTW-DAPPER) or an ANSI Short Circuit Study

    (in A_FAULT). The A_FAULT Short Circuit Study and Comprehensive Short Circuit

    Study chapters discuss the Short Circuit Methodology applied by each Study, and the

    standards followed by each; the A_FAULT Study is based on the American National

    Standards Institute (ANSI), while the Comprehensive Short Circuit Study is based onThevenin equivalent circuit representation and Ohms Law.

    The IEC_FAULT Study follows the specifications of theInternational Electrotechnical

    Commission (IEC) International Standard 909: Short-circuit current calculation in three-

    phase a.c. systems.

    This chapter discusses:

    Engineering Methodology.

    PTW Applied Methodology.

    Examples.

    IN

    T

    H

    IS

    C

    H

    A

    P

    T

    E

    R

    What is the IEC_FAULT Study?........................................................ IEC_FAULT 1-2

    Engineering Methodology .................................................................. IEC_FAULT 1-3

    PTW Applied Methodology ............................................................. IEC_FAULT 1-11

    Application Examples....................................................................... IEC_FAULT 1-19

  • 8/9/2019 Reference IEC Fault

    6/37

    IEC 60909_FAULT 1-2 Reference Manual

    12/4/2006

    1.1 What is the IEC_FAULT Study?

    The IEC_FAULT Short Circuit Study (referred to hereafter as IEC_FAULT) models the

    current that flows in the power system under abnormal conditions and determines the

    prospective fault currents in an electrical power system. These currents must becalculated in order to adequately specify electrical apparatus withstand and interrupting

    ratings. The Study results are also used to selectively coordinate time current

    characteristics of electrical protective devices.

    Electrical equipment manufactured in Europe is predominately tested and rated against the

    IEC equipment standards; therefore, IEC Standard 909 is the preferred method for

    calculating fault duties when specifying European equipment. Equipment must withstand

    the thermal and mechanical stresses of short circuit currents as described in the Standard.

    Both rms and peak short circuit withstand and interrupting duties (referred to as making

    and breaking short circuit current duties, respectively) must be calculated and then

    compared to the protective device and electrical apparatus ratings. Both maximum and

    minimum short circuit currents are available for specifying equipment in accordance with

    IEC Standard 909.

    Define System Data

    Define system topology and connections

    Define feeder and transformer sizes

    Define fault contribution data

    Run IEC_FAULT Study

    Saved in DatabaseThree-phase fault currents

    Unbalanced fault currents

    Calculated IEC fault currents

    Reports

    Study Setup

    Cable Library

    Transformer Library

    Study Setup

    Used by Time Current

    Coordination (CAPTOR)

    Datablocks

  • 8/9/2019 Reference IEC Fault

    7/37

    IEC 60909_FAULT Study IEC_FAULT 1-3

    SKM Power*Tools for Windows

    1.2 Engineering Methodology

    IEC Standard 909 describes a detailed method for calculating three-phase and unbalanced

    short circuit duties to compare to electrical apparatus ratings. The Standard contains 14

    chapters and an appendix. Individual paragraphs are referred to as articles or clauses, and

    sub-paragraphs are referred to as sub-clauses. The Standard is divided into two majorsections: far-from-generator short circuits and near-to-generator short circuits.

    1.2.1 IEC Standard 909Section One of the Standard, Systems with Short Circuit Currents Having No A.C.

    Component Decay (Far-From-Generator Short Circuits), defines the short circuit currents

    that are expected at a fault location, assuming that active sources (machines and network

    feeders) have no ac decrement. The Standard calls these machines far-from-the-fault-

    location. The Standard defines no ac decrement as a symmetrical short circuit current that

    has no time-varying change from peak to peak during the fault. The terms near and far are

    defined in Section 1.3.4, Assumptions of the IEC_FAULT Study.

    Section Two of the Standard, Systems With Short Circuit Currents Having Decaying

    A.C. Components (Near-To-Generator Short Circuits), examines machines that are

    considered near the fault; they exhibit an ac decrement throughout the duration of the fault

    condition. Different source types (network feeders, synchronous motors and generators,

    and asynchronous motors) are defined differently based on how their ac decrement is

    modeled.

    Both Sections One and Two discuss the implications of how the short circuit current

    arrives at the fault location, and the impact of the dc decay on the short circuit current.

    The Standard defines a contribution as coming from a meshed topology if a contribution

    current flow splits into two or more currents between the source of supply and the fault

    location. The concept of a meshed network is more complex than merely defining the

    system as having loops or parallel connections; special procedures are required when

    modeling meshed contributions. In addition, careful attention must be paid when

    calculating their dc decay currents, regardless of whether the source of the short circuit

    contribution is near or far from the fault location.

    IEC Standard 909 is a derivative of the German VDE Short Circuit Standard. As such,

    both standards were developed to assist engineers with hand calculations. Some of the

    simplifying assumptions necessary for practical hand calculations are not necessarily well-

    suited for computerized methods. The computer allows for removal of many of the

    limiting assumptions in the hand calculation methods. Whenever PTW identifies a

    simplifying assumption in the IEC Standard 909, or if the Standard uses the term may be

    considered, the IEC_FAULT Study evaluates the assumption and takes the most

    conservative implementation approachthat is, the Study calculates a larger short circuit

    current.

    1.2.2 Comparing the ANSI and IEC Short Circuit StandardsThere are three significant differences between the IEC methodology and ANSI

    methodology.

    The first major difference involves calculating the dc decay component. ANSI requires

    calculation of a Thevenin equivalent fault point X/R ratio, based on separately derived R

  • 8/9/2019 Reference IEC Fault

    8/37

    IEC 60909_FAULT 1-4 Reference Manual

    12/4/2006

    and X values at the fault point. From that X/R ratio, a single equivalent dc decay can be

    determined for multiple sources at the fault location. The IEC Standard uses a unique R/X

    ratio, calculated from the complex form of the R and X values at the fault location for

    each contribution, and uses this unique ratio for calculating the asymmetrical fault currents

    from each machine to the fault point. It could be argued that the IEC Standard is current

    based, while the ANSI Standard is impedancebased.

    The second major difference involves the dc offset current. Both standards recognize that

    calculating the dc offset (the transient solution to the short circuit current calculation) must

    be uniquely accomplished when parallel or meshed paths are involved. Both standards

    consider the nature of meshed or parallel paths when concerned with the dc offset;

    however, the two standards use completely different procedures for calculating this dc

    offset current when meshed or parallel paths are involved.

    The third major difference involves the ac decrement. The ANSI method globally adjusts

    the machine sub-transient impedances when considering different moments of time during

    the fault. The IEC method modifies the prospective short circuit currents available from

    each machine based on the transfer impedance between the active source and the specific

    fault location in question. Clearly, the IEC methodology is more computationally

    intensive than the ANSI methodology.

    Both short circuit methodologies can be considered as quasi-steady-state solutions to the

    fault current problem, and both standards acknowledge that a more dynamic solution

    method might yield more accurate results. They do, however, claim sufficient accuracy

    for specifying electrical equipment.

    The results from IEC and ANSI calculations cannot be directly compared. While both

    calculate a withstand duty, the IEC and ANSI methodologies are fundamentally different.

    In sample projects, the ANSI closing and latching duty can, at times, be larger than the

    IEC peak current duty. However, in other sections of the same project, the opposite is

    true. A similar disparity can be found between the IECs breaking current and the ANSIs

    symmetrical current interrupting duty. Thus, it can be concluded that when equipment is

    rated in accordance with the IEC Standard, then the IEC methodology must be used tocalculate the fault duties; and when equipment is rated in accordance with the ANSI

    Standard, then the ANSI methodology must be used to calculate the fault duties.

    1.2.3 Initial Symmetrical Short Circuit CurrentIEC Standard 909 calls for calculating the initial symmetrical rms short circuit current

    duty at the fault location ( Ik ). It is important to understand that referring to a short circuit

    duty means that you must include the necessary multipliers as dictated by the Standard

    when calculating short circuit currents. This differs from associated published electrical

    apparatus short circuit currents which define these currents as equipment ratings.

    Remember that the short circuit duties calculated by the Study must be compared to the

    equipment ratings published by the manufacturer. Also, when no special multipliers areused in the short circuit calculations (such as in PTWs Comprehensive Short Circuit

    Study), then these values are known as short circuit currents.

    The initial symmetrical short circuit current duty is the ratio of the driving point line-to-

    neutral voltage to the system impedance at the fault point. Special consideration is given

    to defining driving point voltages. A voltage factor (c) is introduced in the Standard,

    which is intended to take into account the uncertainties associated with transformer

    voltage taps, line capacitance, and so on. Additionally, the network feeder or the source

    generator impedances, or both, are specially modified.

  • 8/9/2019 Reference IEC Fault

    9/37

    IEC 60909_FAULT Study IEC_FAULT 1-5

    SKM Power*Tools for Windows

    dc Current

    An aperiodic dc current duty (Idc ) is not necessarily required in the calculation in order to

    specify electrical equipment, but knowledge of the dc decay is critical to determining the

    other short circuit current duties specified in the Standard. As stated above, the dc current

    is influenced by the R/X ratio seen between each contribution and the fault location.

    Conceivably, each contribution can have a unique R/X ratio and hence its own unique dc

    decay component. The Standard allows superposition in order to form the Thevenin

    equivalent impedance at the fault location, but the dc current contributions are

    individually calculated for each source of fault current and those dc fault currents are then

    added together at the fault location. This means that any computerized modeling must

    calculate and retain the fault point R/X ratio for each source to each fault location.

    Peak Current

    Given knowledge of the initial symmetrical and Idc duties, a peak or crest one-half cycle

    short circuit duty can be defined. The theoretical maximum peak current of a fully offset

    waveform is 2 2 Ik (X/R ratio approaching infinity).

    When calculating the peak current duty ( Ip ) in meshed networks, the Standard providesthree methods: Method A, Method B, and Method C. While Method A is simple, it is

    also the least accurate procedure; it uses the R/X of the smallest meshed branch. Method

    B uses the R/X ratio from a meshed network formulated by using the complex (vector)

    impedances, and adds a 15% safety factor to allow for inaccuracies. Method C uses

    equivalent frequencies to calculate the special multiplying factor used. The IEC_FAULT

    Study uses Method B.

    The peak current also takes into account any dc decay that exists at one-half cycle into the

    onset of the fault condition.

    Breaking Current

    The IEC Standard 909 breaking current duty ( Ib ) depends on the time for contact partingof the protective device. This is roughly equivalent to the interrupting duties in the ANSI

    Standard. If far contributions are considered, the breaking duty equals the initial

    symmetrical duty. If near contributions are considered, special multipliers are required to

    define the ac decrement component of the short circuit duty. Ib does not include dc offset

    or decay. Ib asym includes both ac and dc decay.

    Steady State Current

    Finally, the IEC Standard 909 calls for calculating a steady state current duty ( Ik ). It

    assumes that asynchronous motors have ceased to contribute short circuit current, and that

    generation (with static exciters) does not contribute to the steady state current. For far

    network feeders, the steady state duty equals the initial symmetrical duty. Both minimum

    and maximum steady state currents are calculated. When a minimum steady state duty is

    calculated, a minimum driving point voltage is used.

  • 8/9/2019 Reference IEC Fault

    10/37

    IEC 60909_FAULT 1-6 Reference Manual

    12/4/2006

    1.2.4 IEC Standard 909 TermsPTWs Reports conform to IEC Standard 909 notation, including:

    c Voltage factor;

    cUn

    Equivalent voltage source (rms);

    f Frequency (Hz);

    Ib Symmetrical short circuit breaking current (rms) voltage;

    Ib asym Asymmetrical short circuit breaking current;

    Ik Steady-state short circuit current (rms);

    Ik Initial symmetrical short circuit current (rms);

    IkG Initial symmetrical short circuit current at synchronous machine;

    IkM Initial symmetrical short circuit current at asynchronous motor;

    IG rated Rated current of synchronous machine;

    IM rated Rated current of asynchronous motor;

    ILR Locked-rotor current of an asynchronous motor;

    Idc Decaying aperiodic component of short circuit current;

    Ip Peak short circuit current;

    KG Correction factor for synchronous machines;

    Factor of the calculation of breaking currents;

    q Factor for the calculation of breaking currents of asynchronous motors;

    Sk Steady state symmetrical short circuit power (apparent power);

    Sk Initial symmetrical short circuit power (apparent power);

    tmin Minimum time delay;

    Un Nominal system voltage, line-to-line (rms);

    U rG Rated machine voltage;

    Xd Direct axis sub-transient reactance (saturated) of synchronous machine;Xq Quadrature axis sub-transient reactance (saturated) of synchronous machine;

    Xd sat Reciprocal of the short circuit ratio;

    Factor for the calculation of the steady-state short circuit current;

    rG Rated machine power factor angle in degrees.

    1.2.5 Conventional MethodologyThe Conventional or Comprehensive short circuit analysis procedure involves reducing

    the network at the short circuit location to a single Thevenin equivalent impedance,

    determining the associated fault point R/X ratio calculated using complex vector algebra,

    and defining a driving point voltage (assuming the effect of transformer taps on bus

    voltage). The initial symmetrical short circuit current can be calculated and, given thefault location R/X ratios, the asymmetrical short circuit current at various times during the

    onset of the fault can be calculated.

    Conventional short circuit analysis techniques do not satisfy IEC Standard 909

    methodology. First, IEC Standard 909 disallows complete network reduction techniques

    (that is, calculating a single Thevenin equivalent impedance) for determining the peak

    short circuit current because the meshed/non-meshed information between each

    contributing source and each fault location must be retained. Second, the methodology is

  • 8/9/2019 Reference IEC Fault

    11/37

    IEC 60909_FAULT Study IEC_FAULT 1-7

    SKM Power*Tools for Windows

    aimed at adjusting contribution currents at the fault point location, and not simply

    adjusting the contribution impedances at the machine buses. IEC Standard 909 is further

    complicated by the requirement to model transformers whose turns ratios may not be the

    same as the system base voltages, as illustrated in examples A1, A2, and A3 in the IEC

    Standard 909 Appendix.

    1.2.6 Requirements for Computer SolutionsIn order to attain the necessary data for calculating various short circuit current duties

    using computer solutions and in accordance with the IEC Standard 909, it is necessary to

    solve multiple networks associated with each specific short circuit location. For example,

    at each short circuit location it is necessary to determine:

    1. The ac decrement characteristic (far or near) for each machine;

    2. Whether each machine or network feeder contributes through a non-meshed or

    meshed topology;

    3. The R/X ratio each machine or network feeder sees at each fault location;

    4. The initial symmetrical short-circuit current which flows through each network feederand machine.

    1.2.7 EquationsA summary of the important equations and associated graphs applied in IEC_FAULT

    follows. Note that all of the numbered equations used in this section refer to the equations

    as numbered in the IEC Standard 909, 1988 edition.

    For each short circuit location, IEC_FAULT calculates the Thevenin equivalent and total

    initial symmetrical short circuit duty ( Ik). Also, each individual machines IkG

    contribution to the fault location is calculated.

    For network feeders, the defining equation is:

    ZcU

    SQ

    nQ2

    kQ

    =

    Eq. 5a

    Asynchronous machines are represented by:

    Z1

    M II

    LR

    M rated

    = Eq. 34

    Motor impedance and synchronous generators are represented by:

    Z K R XGk G G d = + jb g Eq. 35where

    KU

    U

    c

    XG

    n

    rG

    MAX

    d rG

    = + 1 sin

    Eq. 36

  • 8/9/2019 Reference IEC Fault

    12/37

    IEC 60909_FAULT 1-8 Reference Manual

    12/4/2006

    The Standard calculates each machines contribution ( Ik , Idc , Ip , Ib , Ik ) using the

    following standard equations:

    Ik calculated as in Section 1, Article 9, taking into account the voltage factor and the

    synchronous machine KG factor:

    =

    +

    IcU

    3 R Xk

    n

    k2

    k2

    Eq. 14

    =IcU

    3Zk

    n

    k

    Idc is calculated as:

    I 2 I edc k2 f tmin

    RX=

    Eq. 1

    where R/X is calculated knowing the complex (vector) form of the Thevenin equivalent

    impedance.

    Ip is calculated for non-meshed networks as:

    I I 1.02 0.98ep k3RX= +

    2 e j Eq. 16

    For meshed contributions, Idc and Ip are corrected using Method B:

    I 2 I edc MESH k 2 f tmin

    RX=

    115.

    e j Eq. 21

    I I 1.02 0.98ep MESH k3RX= +

    115 2. e j

    For contributions considered far from the fault location:

    I = I = Ik b k Eq. 15

    For near contributions of synchronous machines:

    I = Ib k Eq. 46

    where:

    = e0.26IkG IrG0 84 0 26. .+

    for t .02smin= 0 Eq. 47

    = 0.51e 0.30IkG

    IrG0 71. +

    for t = 0.05smin

    = +

    0.62 0.72e0.32IkG IrG for t .10smin= 0

    = +

    0 56 0 94. . e0.38IkG IrG for t .25smin= 0

    If the tmin is not as explicitly defined above, interpolation is used between equations.

  • 8/9/2019 Reference IEC Fault

    13/37

    IEC 60909_FAULT Study IEC_FAULT 1-9

    SKM Power*Tools for Windows

    For near contributions of asynchronous machines:

    I = q Ib k Eq. 71

    where is defined as above, and q is calculated as:

    q = 1.03 + 0.12 n MWPole Pairl d i for t = 0.02smin Eq. 67

    q = 0.79 + 0.12 n MWPole Pair

    l d i for t = 0.05smin

    q = 0.57 + 0.12 n MWPole Pair

    l d i for t = 0.10smin

    q = 0.26 + 0.12 n MWPole Pair

    l d i for t = 0.25smin

    The asymmetrical breaking current is calculated as:

    2

    dc

    2

    bbasym III += Eq. A2.4

    Calculation of short circuit current duties of asynchronous motors in the case of a short

    circuit at the terminals is defined in Sub-Clause 13.2.1, Table II.

    Calculations of short circuit current breaking duties of near synchronous and

    asynchronous machines contributing through meshed networks are based on Equations 60,

    61, and 62 in Sub-Clause 12.2.4.3.

    Asynchronous machines do not contribute to the steady state duty (I )k .

    The steady state contribution for synchronous machines assumes that the fault current

    contribution is considered (as entered in the synchronous generator or motor data boxes of

    the Component Editors IEC Contribution subview). Calculation is as follows:

    I = Ik max G rated max Eq. 48

    I = Ik min G rated min Eq. 49

    where:

    Imax and Imin are taken from Figures 17 and 18 of Sub-Clause 12.2.1.4, and depend on

    whether the machines are turbine generators (round rotor) or salient pole generators.

    1.2.8 IEC Standard 909 Unbalanced Short Circuit CalculationsGenerally, the current-based IEC Standard 909 procedure for calculating three-phase

    balanced short circuits does not lend itself directly to calculating unbalanced short

    circuitsthe process is impedance-based, involving network reduction. It should be noted

    that reduced sequence networks do not retain information regarding individual

    contributions, which are necessary when contributions through meshed networks must be

    analyzed. Therefore, the technique allowed by the IEC Standard 909 uses factors

    calculated in the balanced procedure for application in the unbalanced short circuit

    calculations. Further, it is important to note that there is no recognition of near-to-

    generator/motor-type calculations for unbalanced short circuits; the assumption

  • 8/9/2019 Reference IEC Fault

    14/37

    IEC 60909_FAULT 1-10 Reference Manual

    12/4/2006

    I = I = Ik b k appears to be valid. IEC_FAULT automatically calculates line-to-earth, line-

    to-line and line-to-line-to-earth short circuit duties.

    Positive- and zero-sequence impedances can be entered for all branch elements.

    Transformer neutral impedances also can be entered. It is important to correctly identify

    the transformer winding connections for proper modeling of the zero-sequence network.

    Except for synchronous motors and generators, the negative-sequence impedance is

    always assumed to be equal to the positive-sequence impedance.

    In the case of synchronous motors and generators, the negative-sequence reactance is

    equal to:

    = +

    XX X

    22

    d q

    If Xq data is missing or zero, then = X Xd q is assumed and Z 2 = ZG Gb g b g1 . Refer toIEC Standard 909, Section 11.5.3.6.

    The negative- and zero-sequence impedance of synchronous motors and generators, like

    the positive-sequence impedance, is multiplied by the correction factor KG . Refer to

    Equations 37 and 38 in Section 11.5.3.6.

    Thus, the positive-, negative-, and zero-sequence machine impedances are:

    Z 1 = K R + jXG G G d b g b g

    Z 2 = K R X X

    2G G G

    d qb g + + F

    HG I

    KJj

    Z 0 = K (R + jX )G G 0 0b g For asynchronous motors, Z 1 = Z 2M Mb g b g , as defined in Section 11.5.3.5, and Z 0M b g isassumed to be infinite, and not user-definable. Finally, unbalanced short circuits near-to-

    generator are treated as far ( = =I I Ik b k), as defined in Sections 11.3 and 12.3.

    Line capacitances and parallel admittances of non-rotating loads are neglected.

    The zero-sequence impedance is considered for network feeders. It is calculated

    internally from user-defined line-to-earth current, kVA or MVA network contribution

    data.

    Two options are provided for calculating the unbalanced short circuit components: Idc and

    Ip .

    The first option uses equivalent three-phase factors. The equivalent is derived by

    dividing the sum of individual contribution components by the absolute value of the

    total initial symmetrical short circuit current Ikb g . Refer to Sections 9.2.1.2 and9.2.3.2.

  • 8/9/2019 Reference IEC Fault

    15/37

    IEC 60909_FAULT Study IEC_FAULT 1-11

    SKM Power*Tools for Windows

    The second option uses factors developed from short circuit-type dependent

    combinations of reduced sequence networks to establish a short circuit equivalent

    R/X. If any three-phase contribution contributes through a meshed network, the

    Method B 15% safety factor is applied to the total short circuit current.

    Depending on the option selected, the minimum or maximum voltage factor (c) is applied

    to the single equivalent positive-sequence voltage used in determining unbalanced shortcircuit currents.

    1.3 PTW Applied Methodology

    PTW applies the methodology described in Section 1.2. Section 1.3 describes how to run

    the IEC_FAULT Study, including explanations of the various options associated with the

    Study.

    1.3.1 Before Running the IEC_FAULT StudyBefore running the IEC_FAULT Study, you must:

    Define the system topology and connections.

    Define feeder and transformer sizes.

    Define fault contribution data.

    1.3.2 Running the IEC_FAULT StudyYou can run the Study from any screen in PTW, and it always runs on the active project.

    To run the IEC_FAULT Study

    1. From the Run menu, choose Analysis.

    2. Select the check box next to Short Circuit and choose the IEC_FAULT option button.

    3. To change the Study options, choose the Setup button.

    4. Choose the OK button to return to the Study dialog box, and choose the Run button.

    The Short Circuit Study runs, writes the results to the database, and creates a report.

    1.3.3 IEC_FAULT Study OptionsThe IEC_FAULT Study dialog box lets you select options for running the Study.

  • 8/9/2019 Reference IEC Fault

    16/37

    IEC 60909_FAULT 1-12 Reference Manual

    12/4/2006

    Following is a list of the available Study options.

    Report and Study Options

    These boxes allow you to customize the breadth of the Study and its Report.

    Report Type

    There are three report types. Both the Standard Report With Calculation Details and the

    Time Varying Report options produce extensive reports. If the Time Varying Report

    option is selected, then you need to define the specific times at which you want to studythe Idc and Ib duties. Typically, you will want to see the duty at specific times, such as

    1/2 cycle, and at specific breaker opening times, such as 5 cycles. Time varying entries

    are in cycles. The Standard Report, No Calculation Details option, which is the default, is

    more concise.

    Short Circuit Type

    The default is to report both the Balanced & Unbalanced Isc, but you can choose to report

    the three-phase Balanced Isc only or the three-phase Unbalanced Isc only.

    All or Selected

    You can study a fault at a single bus or all buses. If a fault is to be studied at a single bus,

    then the faulted bus must be specified. The default is to study the fault currents at allbuses.

    Faulted Bus

    If Selected Bus is selected in the previous box, use this box to specify the faulted bus.

    System Modeling

    These options further customize the Study.

  • 8/9/2019 Reference IEC Fault

    17/37

    IEC 60909_FAULT Study IEC_FAULT 1-13

    SKM Power*Tools for Windows

    Use Sequence Network or Three-Phase Factors

    Two options are provided for calculating the unbalanced short circuit Idc and Ipeak

    values. The default option, Use Sequence Network to Calc Ip & Idc Factors, uses factors

    developed based on the equivalent positive-, negative-, and zero-sequence network

    combination for the type of unbalanced fault studied. If a meshed network is detected, the

    Method B safety factor is applied to the unbalanced short circuit current.

    The second option uses equivalent three-phase factors. The equivalent is derived by

    dividing the sum of the individual positive-, negative-, and zero-sequence contribution

    components by the absolute value of the total initial symmetrical current, in accordance

    with Sub-Clause 9.2.

    Pre-Fault Voltage

    The driving point voltage established by the network feeder connection will be modified

    by the voltage factors established in the Study setup. The default is to use the c factor.

    Otherwise, you may select the driving point voltage calculated as the load flow voltage.

    The driving point impedance is not affected by the utility (swing bus) voltage if thevoltage factors are selected.

    Calculate max. or min. Short Circuit

    You can model the minimum (lk min) or maximum (lk max) steady state short circuit

    current duty. PTW automatically ignores asynchronous motor contributions to the steady

    state current. Synchronous motors are modeled or not modeled based on their excitation

    and whether the Included in Steady State check box in the IEC Contribution subview for

    synchronous motors is selected or cleared. Cable resistance changes, due to fault

    temperature increases, are not modeled in IEC_FAULT.

    System Frequency

    The system frequency must be defined, along with tmin , in order to calculate the breaking

    current. The system frequency must be specified because the tmin is expressed in the

    Standard in seconds. The IEC fault frequency default is 50 hz.

    Tmin(.02 to 99 Sec.) for Iband Idc

    Tmin is the user-defined time in seconds for reporting Idc , Ib , and Ib (asym) values. The

    default is 0.02 seconds.

    Model Primary Transformer Tap (Ignore Secondary)

    You may model the primary transformer taps by selecting this check box. Secondary taps,

    if modeled, are ignored in the IEC_FAULT calculation.

    Time Varying ReportThe time varying report boxes allow Idc , Ib , and Ib (asym) values to be reported at four

    user-specified times on a single report.

    Voltage Factors

    Voltage factors are used to define system pre-fault voltages used for fault current

    calculations. The voltages can be entered as a range and for specific voltages. Specific

  • 8/9/2019 Reference IEC Fault

    18/37

    IEC 60909_FAULT 1-14 Reference Manual

    12/4/2006

    voltage values override voltage range values. The voltage factors are used only if the pre-

    fault voltage was selected as Use Voltage Factor (c).

    1.3.4 Assumptions of the IEC_FAULT StudyThe IEC_FAULT Study implements IEC Standard 909 with the following assumptions.

    When determining the near/far status of each machine, IEC_FAULT determines the

    following:

    1. Network feeders are always modeled as far from the short circuit location, as

    suggested by Section 1, Clause 7. Network feeders are always defined by the utility

    component in PTW. In general, if the network feeders transformer reactance

    referenced on its low side X tlvb g is less than twice the equivalent reactance of thenetwork feeder Xqd i , then the network feeder is considered near the fault; thus itrequires that more of the network feeder system be modeled.

    2. Any machine directly connected to a fault location is considered a near contribution.

    3. A synchronous machine whose IkG contribution at the fault location is greater than

    twice its rated current is considered a near contribution.

    4. If the sum of all motors (synchronous and asynchronous) Ik contribution at the fault

    location is greater than 5% of the total Ik combination at the fault location excluding

    all motors, then all motor contribution (as a group) at the fault location is considered

    near.

    5. Any machine which has not been determined to be near the above is then considered

    far, and thus no ac decrement is considered.

    1.3.5 Component ModelingIt is best to set the engineering standard to IEC before beginning a new project. See

    Setting Application Options in Chapter 3, Getting Started of the Users Guideto

    change the engineering standard from ANSI to IEC. The IEC_FAULT Study assumes that

    you have entered machine fault characteristics with PTW set to the IEC engineering

    standard. However, if data is entered with PTW set to the ANSI engineering standard,

    PTW will automatically convert ANSI fault contribution data to equivalent IEC fault data.

    The following sections describe the minimum data required for the IEC_FAULT Study to

    run.

    Contribution Data

    Contribution data must be defined for network feeders, synchronous generators,

    synchronous motors, and asynchronous motors.

    Network Feeders

    Network feeders are modeled as Utility components. The driving point voltage and

    voltage angle may be specified, but are not used in the IEC_FAULT calculation. The

    short circuit contribution data must be specified for this component. It is important to note

    that the utility driving point voltage and the equivalent generator source driving point

    voltage, if the generator is modeled as a swing bus generator, are not used in the

    IEC_FAULT Study. The driving point voltage is controlled only by the c factor identified

  • 8/9/2019 Reference IEC Fault

    19/37

    IEC 60909_FAULT Study IEC_FAULT 1-15

    SKM Power*Tools for Windows

    in the IEC_FAULT Study setup for the voltage range of the bus which is faulted. Refer to

    Table 1 of the Standard for recommended voltage ranges. The short circuit contribution

    can be entered in amperes, or apparent power in units of kVA or MVA. Three-phase and

    single-line-to-earth short circuit contribution values may be entered. A zero single-line-

    to-earth short circuit contribution is acceptable, as PTW will assume an infinite zero

    sequence impedance if the single-line-to-earth fault current is zero. The default values are

    zero for the short circuit contribution magnitude, and 0.067 for the X/R ratio (X/R of 15).

    You can also model the driving point voltages as calculated from the Load Flow Study.

    When so modeled, no c factors are used.

    Synchronous Generators and Motors

    Synchronous generator and motor short circuit current contributions are defined in the

    Component Editor as shown in the following figure:

    Enter the Xd and Xq values; PTW assumes the machine is a salient pole machine if the

    two values are not equal. Unique machine stator resistance for the positive- and negative-

    sequence, and the zero-sequence component must be entered. You must define these

    resistance values; they are notestablished as a percentage of the machine Xd values. The

    default values for Xd , Xq and X0 are 0.15 pu on the machine base, and both rg and r0

    have a default of 0.01 pu on the same machine base. Thus, synchronous machines are bydefault star-earthed.

    PTW calculates the machine kVA and voltage base using the data you enter in the first

    subview of the Component Editor. The motor rated size is in mechanical units of work

    (output) when entered as horsepower, but in equivalent electrical units of work (input)

    when entered as electrical quantities of kVA, MVA or kW. Motor efficiency is used to

    convert horsepower to electrical units of work, and power factor is used to convert kW to

    kVA. If the rated kVA base in the IEC Contribution subview is zero, then PTW calculates

  • 8/9/2019 Reference IEC Fault

    20/37

    IEC 60909_FAULT 1-16 Reference Manual

    12/4/2006

    the equivalent kVA base from the machine rated size shown in the first subview of the

    Component Editor. If the rated kVA base is not zero, PTW will not change it, even if you

    enter a revised rated size in the motors first subview. Also, if the rated voltage is not zero,

    PTW will not change it. Therefore, you may want to modify the rated machine kVA and

    kVA base together; if you do modify them together, the kVA base will remain unchanged,

    even if you change the rated size on the first subview of the Component Editor.

    IEC_FAULT assumes the machine is salient pole if the Xq does not equal the Xd . Also,

    the machine is defined as having a Series One or Series Two excitation characteristic as

    follows:

    Exciter Type Excitation Limit

    Turbine Generator Salient Pole Generator

    Series One 1.3 1.6

    Series Two 1.6 2.0

    The preceding table of Excitation Limits and machine types (turbine generator or salient

    pole generator) is used along with Figures 17 and 18 in the Standard for calculating thesteady state contribution from synchronous machines. Fault current calculations for

    unbalanced fault conditions follow the same procedures as for three-phase fault currents.

    All three sequence impedance models (positive-sequence or Z1 , negative-sequence or

    Z2 ,and zero-sequence or Z0 ) are modeled.

    The synchronous machine or motor can be grounded through an earthing impedance, and

    this value is entered in ohms. PTW automatically multiplies the impedance value by three

    when calculating the zero-sequence currents. Do not enter the earthing impedance as

    three-times the actual impedance selected, since PTW will perform that calculation. The

    default is no earthing impedance.

    The positive-, negative-, and zero-sequence impedances of synchronous machines are

    modified by the KG factor, as defined in Sub-Clause 11.5.3.6, Equation 36.

    When calculating the steady-state short circuit current, you should identify whether or not

    the machine should be considered a fault current contribution; by default, PTW does

    consider the machine in the Ik calculation. Also, the steady-state current is based on the

    saturated reactance (Xd-sat) and the ratio of the Ik to the machine rated current. The

    default transient reactance is 1.6 pu on the machine base. Finally, the steady-state current

    contribution of the machine is dependent on the type of excitation and the type of

    machine, either turbine generator (round rotor) or salient pole generator; the default

    assumes a Series One machine with a turbine generator. Thus, the excitation limit of 1.3

    times the rated field voltage is used.

    In order to fully model a synchronous machine, the rated size of the machine must be

    defined, along with the power factor. Motors can be defined in the Component Editor as

    either a single motor (the default) or as multiple motors. PTW will calculate the power for

    multiple motors modeled at the bus.

    Asynchronous Induction Motors

    Asynchronous motor short circuit currents must also be modeled in PTW. The

    Component Editor IEC contribution data boxes are shown in the following figure:

  • 8/9/2019 Reference IEC Fault

    21/37

    IEC 60909_FAULT Study IEC_FAULT 1-17

    SKM Power*Tools for Windows

    The rated current to lock rotor current ratio must be defined; the default is 0.17 pu on the

    machine base. This is an impedance (vice reactance) value. The associated motor R/X

    ratio must be defined; the default is 0.067.

    The motor rated size is in mechanical units of work (output) when entered as horsepower,

    but is in equivalent electrical units of work (input) when entered as electrical quantities of

    kVA, MVA or kW. Motor efficiency is used to convert horsepower to electrical units of

    work, and power factor is used to convert kW to kVA. If the rated kVA base is zero, then

    PTW calculates the equivalent kVA base using the machine rated size as defined in thefirst subview of the Component Editor. The number of pole pairs, combined with the rated

    kW of asynchronous machines, is used to calculate the breaking current duty. If multiple

    motors are modeled in a single motor object, PTW will model the MW/pp of each of the

    individual motors which comprise the group. Asynchronous motors are modeled as delta-

    connected.

    IEC_FAULT calculates the Thevenin equivalent positive-, negative- and zero-sequence

    impedance components independently, and lists these values in the input Report for the

    associated contribution. The values may be modified by special factors as specified in the

    Standard.

    Cables and Transformers

    Cables are modeled with a series resistance and reactance in both the positive- and zero-

    sequence components. PTW assumes that the negative-sequence impedance is equal to

    the positive-sequence value. No zero-sequence shunt capacitance is modeled in

    IEC_FAULT.

    Transformers also are modeled with a positive- and zero-sequence impedance value. The

    zero-sequence impedance path is dependent on the transformer connection. Only shell-

    wound three-phase and single-phase transformers modeled in three-phase banks are

    modeled in PTW.

  • 8/9/2019 Reference IEC Fault

    22/37

    IEC 60909_FAULT 1-18 Reference Manual

    12/4/2006

    The transformer may be earthed through an earthing impedance, and this value must be

    entered in ohms. PTW automatically multiplies the impedance value by three when

    calculating the zero-sequence currents. Do not enter the earthing impedance as three-

    times the actual impedance selected, since PTW performs that calculation. The default is

    no earthing impedance.The earthing impedance is modeled only on the star-connection.

    A warning message is shown on the status bar if an earthing impedance is entered for a

    non-star (delta connection). If the transformer is connected star-star, an earthingimpedance may be modeled on either or both sides of the transformer, unless the load flow

    voltages are used instead of the Voltage Factors.

    Transformer primary taps may be modeled. A negative primary tap raises the secondary

    voltage. Secondary transformer taps are not modeled in IEC_FAULT. Taps will only be

    considered if the IEC_FAULT Study Setup dialog box is set to model them. The driving

    point voltages are defined by the Voltage Factors and are not modified by the transformer

    tap settings.

    Transformer off-nominal voltage ratios, as compared to the primary and secondary bus

    system nominal voltages, are modeled when the Model Transformer Taps check box is

    selected in the Study setup dialog box. Essentially, PTW will create a fictitious primary

    and/or secondary tap to ensure that the voltage ratios are properly matched.

    1.3.6 Error MessagesPTW examines the entered data for the IEC_FAULT Study. If PTW finds missing or

    incomplete information, it sends an error message to the Study Message dialog box. The

    Study Messages dialog box will report both fatal and warning messages. The Study will

    attempt to run to completion even if fatal errors are detected, in order to identify any other

    errors.

    A somewhat common error is:

    The cal cul at ed zer o sequence i mpedance i s negat i ve.

    It involves the entry of single-line-to-easrth short circuit contribution data. PTW uses the

    three-phase fault data and the single-line-to-earth fault data to calculate the positive-,

    negative- and zero-sequence impedances from the following per-unit equations:

    Z Z

    Z1.0

    I

    I3 1.0

    Z Z Z

    Z3

    I

    Z Z

    1 2

    1f

    f1 2 0

    0f

    1 2

    3

    sle

    sle

    =

    =

    =

    + +

    =

    b gb g

    Utilities often report available single-line-to-earth fault duties on an equivalent three-

    phase rating apparent power basis, using the equation:

    kVA 3 I kV3 f LLsle=

    However, the actual apparent power of a single-line-to-ground fault is:

  • 8/9/2019 Reference IEC Fault

    23/37

    IEC 60909_FAULT Study IEC_FAULT 1-19

    SKM Power*Tools for Windows

    kVA = IkV

    31 fsle

    where

    kV line-to-line voltage.

    You cannot use the three-phase equivalent rating of a single-line-to-ground short circuitcontribution. If you do, PTW may attempt to calculate the zero-sequence impedance as a

    negative value. The actual apparent power to be entered into PTW is the utility equivalent

    single-line-to-earth duty divided by three. Enter the single-line-to-ground fault current

    X/R ratio, not the zero sequence impedance X/R ratio.

    1.3.7 ReportsFor each fault location, IEC_FAULT reports:

    Ik ;

    IkG of each machine;

    Near/far status of each machine;

    Transfer impedance and R/X ratio for each contributing machine.

    1.4 Application Examples

    The examples that follow illustrate how the IEC_FAULT Study runs on various system

    topologies. Unless otherwise specified, all pu values are expressed on a 100 MVA base at

    the bus system nominal voltage.

    1.4.1 Generator and Network FeedersIn this first example, a network feeder and two generators are modeled in order to

    understand how IEC_FAULT models these contributions. The equivalent short circuit

    capacity is the same for all the three contributions. The one-line diagram for the system is

    as shown:

    NETWORK BUS

    Ik" 20.86 kAIp 58.13 kAIb 20.86 kAIk 14.86 kA

    NETWORK FDRGEN 1 GEN 2

    95% PF 75% PF

    A portion of the output report is shown:

  • 8/9/2019 Reference IEC Fault

    24/37

    IEC 60909_FAULT 1-20 Reference Manual

    12/4/2006

    T H R E E P H A S E I E C 9 0 9 F A U L T R E P O R TMODEL TRANSFORMER TAPS: NOFREQUENCY ( HZ): 50.CALC. MAX. FAULT CURRENTS

    ============================================================================== NETWORK BUS 11. 000 kV Vol t age ( PU) : 1. 1000 Tmi n: 0. 02 Sec.

    Sk": 397354. kVA Sk: 283064. kVA I b asym. : 28. 610 kAI k"(kA) i dc(kA) i p(kA) I b(kA) I k(kA)

    COMPLEX TOTALS 20. 856 27. 698 58. 134 20. 856 14. 857BRANCH CONTRI BUTI ONS- - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -

    GEN 1 6. 887 9. 147 19. 198 6. 887 6. 464NETWORK FEEDER 5. 249 6. 971 14. 630 5. 249 5. 249GEN 2 8. 720 11. 581 24. 306 8. 720 7. 383

    CONTRI BUTI ONS AT SOURCES- - - - - - - r efer r ed t o 11000. vol t age-- - - - - - - -NETWORK FEEDER 5. 249 6. 971 14. 630 5. 249 5. 249GEN 1 6. 887 9. 147 19. 198 6. 887 6. 464GEN 2 8. 720 11. 581 24. 306 8. 720 7. 383

    DETAI LED SOURCE I NFORMATI ON- - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -NETWORK FEEDER NETWORK FEEDER STATUS: FAR, NON-MESHED

    R/ X: 0. 010GEN 1 GENERATOR STATUS: NEAR, NON-MESHED

    R/ X: 0. 010I "kG/ I G rat ed: 1. 31u: 1. 000LAMBDA: 1. 32

    GEN 2 GENERATOR STATUS: NEAR, NON-MESHEDR/ X: 0. 010I "kG/ I G rat ed: 1. 66u: 1. 000LAMBDA: 1. 46

    Examine the short circuit current contribution from the network feeder. The short circuit

    contribution is 100 MVA with an R/X ratio of 0.01. The network is serviced from

    11 kVtherefore the voltage factor is 1.1., based on Table 1 of the Standard. Using the

    impedance of the network feeder from Equation 5a of the Standard:

    ZcU

    S

    =1.111 kV

    100 MVA

    =1.331

    QnQ2

    kQ

    =

    b g2

    The initial symmetrical short circuit current available from the network feeder is from Eq.14, and is:

    I =cU

    3Z

    1.1 11 kV

    3 1.331

    = 5.2486 kA

    k

    q

    q

    =

    b g

    The network feeder is defined as far from the network bus, thus Ik , Ib and Ik are the

    same value since there is no ac decrement.

    Incidentally, if you run the Comprehensive Short Circuit Study on this example, assuming

    a driving point voltage at the source of 1.0 pu voltage, the network feeder produces the

    same short circuit current as calculated by the IEC_FAULT Study.

    However, note that the magnitude of fault current generated by the two generators is

    different than the fault current produced by the network feeder; each of the two generators

    produces a different Ik . Following are the reasons this occurs.

  • 8/9/2019 Reference IEC Fault

    25/37

    IEC 60909_FAULT Study IEC_FAULT 1-21

    SKM Power*Tools for Windows

    First, examine generator GEN 1. Note that the rated power factor of the machine is 95%

    lagging. Using Equation 36, the generator KG factor is calculated as:

    K =U

    U

    c

    1+ X sin

    1111

    1.11+ 1.0 sin cos 0.95

    = 0.83825

    Gn

    rG

    max

    d rg

    -1

    =

    b ge j

    Thus, the short circuit current contribution from this machine is:

    I =cU

    K X

    1.11.0

    0.83825 1.0

    = 1.3122 pu A

    KN

    G d

    =

    b g

    But you know the base current is:

    I =100,000 kVA

    311 kV

    = 5248.63 A

    base

    Thus, the generator produces an initial symmetrical short circuit of:

    I = 5248.63 1.3122 pu

    = 6887.53 A

    k

    The generator is directly assigned to the network feeder bus; thus, the generator is

    considered near the fault location and the ac decrement must be considered. Note that for

    this generator, Ib is smaller than

    Ik and Ik is smaller than either Ib or

    Ik .

    Because generator GEN 2 has a different power factor than generator GEN 1, the KG for

    generator GEN 2 is different than that of generator GEN 1. This is why generator GEN 2

    has a different (and larger) short-current current contribution to the network bus.The rated

    current of generators GEN 1 and GEN 2 is:

    I =100,000 kVA

    3 11 kV

    = 5248.63 A

    r G

    Thus the ratio of Ik to Irfor generator GEN 1 is:

    =

    II

    6887.53 A

    5248.63 A

    =1.3122

    k

    r

    This matches the calculated value in the preceding Report.

  • 8/9/2019 Reference IEC Fault

    26/37

    IEC 60909_FAULT 1-22 Reference Manual

    12/4/2006

    This value is used to determine the breaking current, using Figure 16 of the Standard. The

    factor is 1.0, since the ratio is less than 2. Therefore the breaking current is equal to

    the Ik .

    I = I

    =1.0 6887.53 A

    = 6887.53 A

    b k

    The scalar sum of the three initial symmetrical short circuit currents is:

    =I 6.887 + 5.249 + 8.720 kA

    = 20.865 kA

    k Bus

    This matches the reported complex value because the three contributions are nearly in

    phase with one another.

    The prospective initial power is:

    = S 3 20,865 A 11 kV= 397.6 MVA

    k b g

    Again, this matches the value in the Report.

    1.4.2 Meshed Network ConsiderationsThe second example analyzes meshed versus non-meshed characteristics. It demonstrates

    how in Method B a 15% safety factor is used when meshed networks are modeled.

    Consider the following one-line diagram:

    NETWORK BUS

    NETWORK FDR

    TX1

    TX 1 SEC BUS

    TX2

    TX2 SEC BUS

    CBL-0001

    A portion of the Report is shown for a fault at transformer TX1 SEC BUS:

    TX 1 SEC BUS 0. 400 kV Vol t age ( PU) : 1. 0000 Tmi n: 0. 02 Sec.Sk": 58062. kVA Sk: 58062. kVA I b asym. : 85. 105 kA

    I k"(kA) i dc(kA) i p(kA) I b(kA) I k(kA)COMPLEX TOTALS 83. 806 20. 951 193. 648 83. 806 83. 806BRANCH CONTRI BUTI ONS- - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -

  • 8/9/2019 Reference IEC Fault

    27/37

  • 8/9/2019 Reference IEC Fault

    28/37

    IEC 60909_FAULT 1-24 Reference Manual

    12/4/2006

    1.4.3 Far Versus Near ConsiderationsIn this example the network feeder is replaced with a single generator. The near/far status

    of the generator will be examined. The one-line is:

    NETWORK BU

    TX1

    TX 1 SEC BUS

    TX2

    TX2 SEC BUS

    CBL-0001

    GEN 1

    The generator sub-transient reactance is set at 0.5 pu on its own base of 100 MVA. The

    impedances of the branch impedance components are 0.5 pu on a 100 MVA base. The

    Report for this case is:

  • 8/9/2019 Reference IEC Fault

    29/37

    IEC 60909_FAULT Study IEC_FAULT 1-25

    SKM Power*Tools for Windows

    TX 1 SEC BUS 0. 400 kV Vol t age ( PU) : 1. 0000 Tmi n: 0. 02 Sec.Sk": 183472. kVA Sk: 183472. kVA I b asym. : 380. 269 kA

    I k"(kA) i dc(kA) i p(kA) I b(kA) I k(kA)COMPLEX TOTALS 264. 820 385. 941 749. 023 264. 820 264. 820BRANCH CONTRI BUTI ONS- - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -

    NETWORK BUS 183. 337 267. 190 518. 554 183. 337 183. 337TX2 SEC BUS 81. 483 118. 751 230. 469 81. 483 81. 483

    CONTRI BUTI ONS AT SOURCES- - - - - - - r efer r ed t o 400. vol t age-- - - - - - - -GEN 1 264. 820 385. 941 749. 023 264. 820 264. 820

    DETAI LED SOURCE I NFORMATI ON- - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -

    GEN 1 GENERATOR STATUS: FAR, MESHEDR/ X: 0. 017I "kG/ I G rat ed: 1. 83u: 1. 000LAMBDA: 1. 46

    The I"I

    kG

    G

    ratio is less than 2; therefore, the generator is considered electrically far from

    the fault location. The breaking current and steady state current equal the initial

    symmetrical current.

    The machines Xd is reduced to 0.3 pu, thereby increasing its short circuit capacity. A

    portion of the Report is shown:

    TX 1 SEC BUS 0. 400 kV Vol t age ( PU) : 1. 0000 Tmi n: 0. 02 Sec.

    Sk": 269468. kVA Sk: 163173. kVA I b asym. : 534. 882 kAI k"(kA) i dc(kA) i p(kA) I b(kA) I k(kA)COMPLEX TOTALS 388. 943 533. 477 1100. 097 379. 210 235. 520BRANCH CONTRI BUTI ONS- - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -

    NETWORK BUS 269. 268 369. 330 761. 606 262. 530 163. 052TX2 SEC BUS 119. 675 164. 147 338. 491 116. 680 72. 468

    CONTRI BUTI ONS AT SOURCES- - - - - - - r efer r ed t o 400. vol t age-- - - - - - - -GEN 1 388. 943 533. 477 1100. 097 379. 210 235. 520

    DETAI LED SOURCE I NFORMATI ON- - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -GEN 1 GENERATOR STATUS: NEAR, MESHED

    R/ X: 0. 027I "kG/ I G rat ed: 2. 69u: 0. 969LAMBDA: 1. 63

    Now the I"I

    kG

    G

    ratio is greater than 2 and the machine is considered electrically near the

    fault location. The breaking and steady-state current are less than the initial symmetrical

    current.

    1.4.4 Example from PlantThe following figure is a one-line diagram for the Plant project. The Plant project is

    included on the PTW diskettes.

  • 8/9/2019 Reference IEC Fault

    30/37

    IEC 60909_FAULT 1-26 Reference Manual

    12/4/2006

    002-TXAPRI

    TXA

    C1

    C2

    C3

    M8

    M10

    RI

    005-TXDPRI

    006-TX3PRI

    007-TXEPRI

    024-MVSWG

    C10

    C19

    026-TXGPRI

    025-MTR25

    029-TXDSEC

    TXG

    027-DSB3

    C13A

    L3

    028-MTR28

    M28#1&2

    011-TX3SEC

    012-TX3TER

    C7

    013-DSSWG2

    C8

    020-DSSWG3

    C9

    M3

    G2

    0

    21-TXFPRI

    TX6

    022-DSB2

    C12

    0

    23-MTR23

    M7

    L1

    M4

    TX4

    TXC

    G1

    C5

    C6G

    1

    RI

    010-MTR10

    TX3

    M5

    C14

    C16

    C17

    016-H2A

    017-H1A

    Subfeed#1

    Subfeed#2A

    L10

    G3

    T

    XL1

    PANELS1

    MCC15A

    PANELS3

    TX3WND

    POWER*TOOLSFORWINDOWS

    SWBD1

    CB3

    R3

    FTXC

    F5

    FTX3

    PD-0011

    LVP1

    CB6R

    6

    RG2

    CBG2

    RG3

    CBG3

    RG1

    CBG1 M

    CP5

    F2

    LVP2

    LVP3

    CB5

    R5

    CB1

    CB2

    R2

    CBM8

    RM8

    CBM10

    RM10

    SW1

    CAP#1

    F4

    C13B

    LVP5

    028-MTR28B

    LVP4

    M28#3M

    CPM28#3

    MC

    M28#4

    MCPM28#1&2

    The following figure shows a portion of the Plant project, including IEC_FAULT results.

  • 8/9/2019 Reference IEC Fault

    31/37

    IEC 60909_FAULT Study IEC_FAULT 1-27

    SKM Power*Tools for Windows

    BLDG 115 SERV

    Ik" 8.14 kA

    I peak 19.81 kA

    Ib (asym) 8.61 kA10 C11

    26-TX G PRI

    Ik" 7.78 kA

    I peak 18.26 kA

    Ib (asym) 7.98 kA

    025-MTR 25

    Ik" 7.80 kA

    I peak 18.16 kA

    Ib (asym) 8.12 kA

    SW M25

    F M25

    MCP M25

    M25

    4

    X G

    027-DSB 3

    IEC SHORT CIRCUIT STUDY

    FAULT ALL BUSES

    BUILDING 115 SERVICE

  • 8/9/2019 Reference IEC Fault

    32/37

    IEC 60909_FAULT 1-28 Reference Manual

    12/4/2006

    A segment of the IEC_FAULT Report follows. The Standard Report, No Calculation

    Details option is first presented. For a fault at Bus 28, the Report is:

    T H R E E P H A S E I E C 9 0 9 F A U L T R E P O R TMODEL TRANSFORMER TAPS: NOFREQUENCY ( HZ): 50.CALC. MAX. FAULT CURRENTS

    ==============================================================================027-DSB 3 0. 400 kV Vol t age ( PU) : 1. 0000 Tmi n: 0. 02 Sec.

    Sk": 20786. kVA Sk: 6819. kVA I b asym. : 29. 218 kAI k"(kA) i DC(kA) i p(kA) I b(kA) I k(kA)

    COMPLEX TOTALS 30. 002 15. 197 69. 606 27. 171 9. 842BRANCH CONTRI BUTI ONS- - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -

    026- TX G PRI 21. 704 10. 356 50. 126 21. 663 9. 842028- MTR 28 A 4. 154 2. 016 9. 446 2. 686 0. 000028- MTR 28 B 4. 154 2. 827 10. 051 2. 828 0. 000

    The total bus initial symmetrical short circuit current is 21.867 kA, with the majority of

    the current flowing from the network feeder. The motors connected in MCC 28 contribute

    5.229 kA in short circuit current.

    More details are provided if the Standard Report with Calculation Details Report format is

    selected, as shown below:

    T H R E E P H A S E I E C 9 0 9 F A U L T R E P O R TMODEL TRANSFORMER TAPS: NOFREQUENCY ( HZ): 50.CALC. MAX. FAULT CURRENTS

    ==============================================================================027-DSB 3 0. 400 kV Vol t age ( PU) : 1. 0000 Tmi n: 0. 02 Sec.

    Sk": 20786. kVA Sk: 6819. kVA I b asym. : 29. 218 kA

    I k"(kA) i DC(kA) i p(kA) I b(kA) I k(kA)COMPLEX TOTALS 30. 002 15. 197 69. 606 27. 171 9. 842BRANCH CONTRI BUTI ONS- - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -

    026- TX G PRI 21. 704 10. 356 50. 126 21. 663 9. 842028- MTR 28 A 4. 154 2. 016 9. 446 2. 686 0. 000028- MTR 28 B 4. 154 2. 827 10. 051 2. 828 0. 000

    CONTRI BUTI ONS AT SOURCES- - - - - - - r efer r ed t o 400. vol t age-- - - - - - - -U1 9. 842 3. 085 20. 841 9. 842 9. 842M8 1. 461 0. 815 3. 407 1. 461 0. 000G1 0. 386 0. 232 0. 913 0. 386 0. 000

    M25 4. 595 2. 831 10. 911 4. 595 0. 000M 28 # 1&2 4. 154 2. 016 9. 446 2. 686 0. 000M28 #4 2. 077 1. 413 5. 026 1. 414 0. 000M28 #3 2. 077 1. 413 5. 026 1. 414 0. 000

    DETAI LED SOURCE I NFORMATI ON- - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -U1 NETWORK FEEDER STATUS: FAR, NON-MESHED

    R/ X: 0. 240M8 SYNC. MOTOR STATUS: NEAR, NON-MESHED

    R/ X: 0. 148I "kG/ I G rat ed: 0. 26u: 1. 000LAMBDA: 0. 24

  • 8/9/2019 Reference IEC Fault

    33/37

    IEC 60909_FAULT Study IEC_FAULT 1-29

    SKM Power*Tools for Windows

    G1 GENERATOR STATUS: FAR, NON-MESHEDR/ X: 0. 137I "kG/ I G rat ed: 0. 36u: 1. 000LAMBDA: 0. 34

    M25 ASYNC. MTR. STATUS: NEAR, NON-MESHEDR/ X: 0. 132I "kM/ I M rated: 1. 59MW/ ( pol e pai r ) : 0. 802

    uq: 1. 000

    M 28 # 1&2 ASYNC. MTR. STATUS: NEAR, NON- MESHEDR/ X: 0. 170I "kM/ I M rated: 11. 51MW/ ( pol e pai r ) : 0. 104uq: 0. 647

    M28 #4 ASYNC. MTR. STATUS: NEAR, NON-MESHEDR/ X: 0. 116I "kM/ I M rated: 5. 76MW/ ( pol e pai r ) : 0. 104uq: 0. 681

    M28 #3 ASYNC. MTR. STATUS: NEAR, NON-MESHEDR/ X: 0. 116I "kM/ I M rated: 5. 76MW/ ( pol e pai r ) : 0. 104uq: 0. 681

    The third Report format, Time Varying Balanced Report, depicts the time varying nature

    of the fault current at the bus, and the contributions in each branch. For a fault at Bus 27the report is:

    T H R E E P H A S E I E C 9 0 9 F A U L T R E P O R TMODEL TRANSFORMER TAPS: NOFREQUENCY ( HZ): 50.CALC. MAX. FAULT CURRENTS

    ==============================================================================( A) TOTAL SHORT- CI RCUI T CURRENT

    FAULT BUS NOMI NAL R/ X OF V I k" ( SYM. RMS) i p( PEAK) I k( RMS)027-DSB 3 V. ( kV) EQUI V. Z ( PU) ( kA) ( kA) ( kA)

    0. 400 0. 213 1. 0000 30. 002 69. 606 9. 842

    TI ME ( CYCLES) 0. 5 2. 0 5. 0 12. 5

    I b( ASYM. RMS) ( KA) 33. 701 25. 200 21. 134 18. 119I b( SYM. RMS) ( KA) 28. 524 24. 870 21. 132 18. 119

    i ( DC) ( KA) 25. 384 5. 752 0. 413 0. 001I b(ASYM) / I b(SYM) 1. 182 1. 013 1. 000 1. 000

    ( B) BRANCH CURRENT

    BRANCH NAME R/X OF I k" ( SYM. RMS) i p( PEAK) I k( RMS)EQUI V. Z ( kA) ( kA) ( kA)

    026- TX G PRI 0. 230 21. 704 50. 126 9. 842

    TI ME ( CYCLES) 0. 5 2. 0 5. 0 12. 5

    I b( ASYM. RMS) ( KA) 25. 098 21. 060 19. 437 17. 947I b( SYM. RMS) ( KA) 21. 684 20. 896 19. 437 17. 947i ( DC) ( KA) 17. 873 3. 701 0. 233 0. 000I b(ASYM) / I b(SYM) 1. 157 1. 008 1. 000 1. 000

    BRANCH NAME R/X OF I k" ( SYM. RMS) i p( PEAK) I k( RMS)EQUI V. Z ( kA) ( kA) ( kA)

    028- MTR 28 A 0. 170 4. 154 9. 446 0. 000

    TI ME ( CYCLES) 0. 5 2. 0 5. 0 12. 5

    I b(ASYM. RMS) ( KA) 4. 167 1. 971 0. 790 0. 079I b(SYM. RMS) ( KA) 3. 383 1. 909 0. 790 0. 079i ( DC) ( KA) 3. 441 0. 692 0. 028 0. 000I b(ASYM) / I b(SYM) 1. 232 1. 032 1. 000 1. 000

    ( B) BRANCH CURRENT

    BRANCH NAME R/X OF I k" ( SYM. RMS) i p( PEAK) I k( RMS)EQUI V. Z ( kA) ( kA) ( kA)

    028- MTR 28 B 0. 170 4. 154 10. 051 0. 000

  • 8/9/2019 Reference IEC Fault

    34/37

    IEC 60909_FAULT 1-30 Reference Manual

    12/4/2006

    TI ME ( CYCLES) 0. 5 2. 0 5. 0 12. 5

    I b(ASYM. RMS) ( KA) 4. 507 2. 283 0. 915 0. 092I b(SYM. RMS) ( KA) 3. 466 2. 070 0. 909 0. 092i ( DC) ( KA) 4. 075 1. 360 0. 152 0. 001I b(ASYM) / I b(SYM) 1. 300 1. 103 1. 007 1. 000

  • 8/9/2019 Reference IEC Fault

    35/37

    SKM Power*Tools for Windows

    Index

    A

    ac Decrement, 1-3, 1-4

    required in computer solutions, 1-7

    ANSI Methodology

    compared to IEC methodology, 1-3

    Aperiodic dc Current Duty. SeeDecaying Aperiodic Component

    of Short Circuit Current

    Assumptions of the IEC_FAULT Study, 1-14

    Asymmetrical Short Circuit Breaking Current, 1-9

    IEC Standard 909 notation of, 1-6

    B

    Breaking Current, 1-5

    C

    Computer Requirements

    when solving short circuit current duties, 1-7

    Contribution Data, 1-14

    Conventional Short Circuit Methodology, 1-6

    Correction Factor for Synchronous Machines

    IEC Standard 909 notation of, 1-6

    D

    dc Current, 1-5

    dc Decay, 1-3, 1-4

    dc Offset Current, 1-4

    Decaying Aperiodic Component of Short Circuit Current, 1-5

    IEC Standard 909 notation of, 1-6

    Direct Axis Sub-Transient Reactance (Saturated) of Synchronous

    Machine

    IEC Standard 909 notation of, 1-6

    E

    Equations

    for aynchronous machines, 1-7

    for motor impedance, 1-7

    for network feeders, 1-7

    for synchronous generators, 1-7

    used by IEC_FAULT, 1-7

    Equivalent Voltage Source (rms)

    IEC Standard 909 notation of, 1-6

    Error Messages

    IEC_FAULT Study, 1-18

    Exciter Type

    for machines, 1-16

    F

    Factor for the Calculation of Breaking Currents of Asynchronous

    Motors

    IEC Standard 909 notation of, 1-6

    Factor for the Calculation of the Steady-State Short Circuit

    Current

    IEC Standard 909 notation of, 1-6

    Factor of the Calculation of Breaking Currents

    IEC Standard 909 notation of, 1-6Far Status of Machines

    in IEC_FAULT Study, 1-14

    Frequency (Hz)

    IEC Standard 909 notation of, 1-6

    I

    IEC Methodology

    compared to ANSI methodology, 1-3

    IEC Standard 909, 1-1, 1-2, 1-3, 1-4, 1-7

    calculating unbalanced short circuits using, 1-9

    methods A, B, & C in, 1-5

    terms, 1-6

    IEC_FAULT Study

    assumptions of, 1-14

    contribution data, 1-14

    definition of, 1-2

    equations used by, 1-7

    error messages, 1-18

    examples, 1-19

    far versus near considerations, 1-24

    generator and network feeders, 1-19

    meshed network considerations, 1-22

    Plant project, 1-25

    far status of machines, 1-14

    line-to-earth, line-to-line, and line-to-line-to-earth calculations,

    1-10

    methodology, 1-3

    near status of machines, 1-14network feeder modeling, 1-14

    running the Study, 1-11

    Study options, 1-11

    Initial Symmetrical Short Circuit Current (rms), 1-4

    IEC Standard 909 notation of, 1-6

    required in computer solutions, 1-7

    Initial Symmetrical Short Circuit Current at Asynchronous Motor

    IEC Standard 909 notation of, 1-6

  • 8/9/2019 Reference IEC Fault

    36/37

    IEC_FAULT ii Reference Manual

    12/4/2006

    Initial Symmetrical Short Circuit Current at Synchronous

    Machine

    IEC Standard 909 notation of, 1-6

    Initial symmetrical Short Circuit Duty, 1-7

    Initial Symmetrical Short Circuit Power (Apparent Power)

    IEC Standard 909 notation of, 1-6

    Interrupting Fault Duty, 1-2

    L

    Locked-Rotor current of an Asynchronous Motor

    IEC Standard 909 notation of, 1-6

    M

    Machine

    exciter type, 1-16

    Meshed Network. SeeMeshed Topology

    Meshed Topology, 1-3

    required in computer solutions, 1-7

    Methodology

    IEC_FAULT Study, 1-3Methods A, B, & C. SeeIEC Standard 909

    Minimum Time Delay

    IEC Standard 909 notation of, 1-6

    N

    Near Status of Machines

    in IEC_FAULT Study, 1-14

    Negative-Sequence Impedance. SeeSymmetrical Component

    Impedance Network

    Network Feeders

    modeling in IEC_FAULT Study, 1-14

    Nominal System Voltage, Line-to-Line (rms)

    IEC Standard 909 notation of, 1-6

    Non-Meshed Network. SeeNon-Meshed Topology

    Non-Meshed Topology, 1-8

    required in computer solutions, 1-7

    P

    Peak Short Circuit Current, 1-5

    IEC Standard 909 notation of, 1-6

    Positive-Sequence Impedance. SeeSymmetrical Component

    Impedance Network

    Q

    Quadrature Axis Sub-Transient Reactance (Saturated) of

    Synchronous MachineIEC Standard 909 notation of, 1-6

    R

    R/X Ratio, 1-5, 1-19

    required in computer solutions, 1-7

    Rated Current of Asynchronous Motor

    IEC Standard 909 notation of, 1-6

    Rated Current of Synchronous Machine

    IEC Standard 909 notation of, 1-6

    Rated Machine Power Factor Angle in Degrees

    IEC Standard 909 notation of, 1-6

    Rated Machine Voltage

    IEC Standard 909 notation of, 1-6

    Reciprocal of the Short Circuit Ratio

    IEC Standard 909 notation of, 1-6

    S

    Salient Pole Generators, 1-9

    in IEC_FAULT Study, 1-16

    Short Circuit Current Breaking Duties, 1-9

    Short Circuit Current Duty

    computer requirements in solving, 1-7

    of asynchronous motors, 1-9

    Standard Terms. SeeIEC Standard 909

    Steady State Contribution

    for synchronous motors, 1-9

    Steady State Current, 1-5

    Steady State Short Circuit Current

    calculating properly, 1-16Steady State Symmetrical Short Circuit Power (Apparent Power)

    IEC Standard 909 notation of, 1-6

    Steady-State Short Circuit Current (rms)

    IEC Standard 909 notation of, 1-6

    Symmetrical Component Impedance Networks

    positive-, negative-, and zero-sequence, 1-10

    Symmetrical Short Circuit Breaking Current (rms) Voltage

    IEC Standard 909 notation of, 1-6

    T

    Terms. SeeIEC Standard 909

    Thevenin equivalent, 1-7

    Thevenin Equivalent Fault Point X/R Ratio, 1-4

    Thevenin Equivalent Impedance, 1-8Transformer

    turns ratios, 1-7

    Turbine Generators (Round Rotor), 1-9

    Turns Ratios, 1-7

    U

    Unbalanced Short Circuits Calculation

    using IEC Standard 909, 1-9

    V

    Variables. SeeIEC Standard 909: terms

    Voltage FactorIEC Standard 909 notation of, 1-6

    minimum and maximum, 1-11

    W

    Withstand Fault Duty, 1-2

  • 8/9/2019 Reference IEC Fault

    37/37

    Z Zero-Sequence Impedance. SeeSymmetrical ComponentImpedance Network