Reference ArcFlash

101
Power*Tools for Windows Arc Flash Reference Manual Electrical Engineering Analysis Software for Windows Copyright © 2008, SKM Systems Analysis, Inc. All Rights Reserved.

Transcript of Reference ArcFlash

Page 1: Reference ArcFlash

Power*Tools

for Windows™

Arc Flash Reference Manual

Electrical Engineering Analysis Software

for Windows

Copyright © 2008, SKM Systems Analysis, Inc.

All Rights Reserved.

Page 2: Reference ArcFlash

Arc Flash Reference Manual 1 - 1

SKM Power*Tools for Windows

Arc FlashArc FlashArc FlashArc Flash Users Guide Users Guide Users Guide Users Guide

This chapter examines the calculation procedures used in the PTW Arc Flash Study.

The Arc Flash Study module follows the guidelines and procedures outlined in the NFPA 70E-2004 and IEEE 1584-2002. It is recommended that you purchase and reference the NFPA 70E and IEEE 1584 Standards prior to performing and interpreting Arc Flash Calculations.

This guide includes:

- Engineering Methodology

- Terminology and Symbols

- Assumptions and Equations

- PTW Applied Methodology

- Examples

Page 3: Reference ArcFlash

7/15/2008

TABLE OF CONTENTS

ARC FLASH USERS GUIDE

1.1 Cautions and Disclaimers 3

1.2 What is an Arc Flash Study? 4

1.3 Introduction to Arc Flash Studies 5 1.3.1 Causes of Electrical Arc Flash Events 5 1.3.2 Why Perform Arc Flash Studies? 5

1.4 Engineering Methodology 5

1.4.1 IEEE Standard 1584 5 1.4.2 Arc Flash Report Definitions 6 1.4.3 Arc Flash Menu Options 12 1.4.4 Arc Flash Study Procedure 14 1.4.5 Arc Flash Modeling Assumptions 14 1.4.6 Arc Flash Equations 16

IEEE 1584 Standard – 2002 16 NFPA 70E - 2004 18 NESC - 2007 19

1.4.7 Default Values 28 1.4.8 Determination of Grounded/Ungrounded Bus 28 1.4.9 Relationship Between 3-Phase Fault and Arcing Fault 28

1.5 PTW Applied Methodology 29 1.5.1 Running the Arc Flash Study 29 1.5.2 Arc Flash Study Options 30 1.5.3 Determining Trip Time 57 1.5.4 Current-Limiting Devices 59 1.5.5 Reports 65 1.5.6 Selecting Buses for Arc Flash Report 80 1.5.7 PPE Table 81 1.5.8 Long Trip Times 83 1.5.9 Differential Protection 85 1.5.10 Arcing Fault Tolerances 87 1.5.11 Reducing Incident Energy 88

1.6 Application Example 89

1.6.1 Sample Arc Flash Study 89

Page 4: Reference ArcFlash

Arc Flash Reference Manual 1 - 3

SKM Power*Tools for Windows

1.1 Cautions and Disclaimers This Users Guide outlines methods for conducting an arc-flash hazard analysis. Following the suggestions contained in this guide does not guarantee worker safety from arc flash events. Professional judgment must be used in the development of the system model, interpretation of the results and the selection of adequate PPE.

The information contained herein should be used in conjunction with the IEEE 1584 standard and NFPA 70E guidelines regarding Arc Flash Analysis.

This guide does not imply that work on energized equipment with exposure to live parts is an acceptable practice. OSHA 29 CRF Subpart S.1910.333 limits the situations in which work is performed near energized equipment or circuits.

“Live parts to which an employee may be exposed shall be de-energized before the employee works on or near them, unless the employer can demonstrate that de-energizing introduces additional or increased hazards or is infeasible due to equipment design or operational limitations.”

Incident Energy is the result of short circuit current and clearing time under arcing fault conditions. Small changes in arcing fault current and trip settings can significantly affect the amount of incident energy.

This guide is based on technical data documented in the IEEE 1584-2002 standard and is intended for use by qualified personnel experienced in power system studies. The equations documented in the IEEE 1584-2002 and referenced in this guide were generated from tests performed at multiple test labs. Differences in environmental conditions between your facility and the test labs may affect the results. These equations may not produce conservative results when applied to your facility. SKM Systems Analysis, Inc. makes no warranty concerning the accuracy or application of the study results.

Page 5: Reference ArcFlash

7/15/2008

1.2 What is an Arc Flash Study? Arc Flash Studies estimate incident energy exposure from potential arc sources. To understand the purpose of an Arc Flash Study, it is important to understand the difference between a traditional fault and an arcing fault. A bolted 3-phase, phase to phase, or phase to ground fault creates high current that flows through the network and the current is contained within the network. Traditional fault studies are used to select equipment that can withstand and interrupt these short circuit currents. Arcing faults occur when the current passes through vapor between two conducting materials. These high-temperature arcs can cause fatal burns even when standing several feet from the arc. The electrical arcs also shower droplets of molten material in the surrounding area, causing further hazard. The arcing fault current is smaller than a traditional bolted fault current because the vapor acts as impedance between the conducting materials.

por

The PTW Arc Flash Study, herein referred to as Arc Flash, follows the NFPA 70E 2004 and IEEE 1584 2002 methods for determining the arc-flash hazard distance and the incident energy that workers may be exposed to when working on or near electrical equipment. Electrical arc burns account for a large percentage of electrical injuries.

An arc flash study combines short circuit

calculations, empirical equations and protective device operating times to estimate incident energy and protective clothing requirements at typical working distances.

Page 6: Reference ArcFlash

Arc Flash Reference Manual 1 - 5

SKM Power*Tools for Windows

1.3 Introduction to Arc Flash Studies

1.3.1 Causes of Electrical Arc Flash Events - Contact with live parts typically from dropping tools or loose parts.

- Insulation failure

- Over-voltages

- Dust

- Corrosion

- Condensation

1.3.2 Why Perform Arc Flash Studies? - Prevent worker injury or death

- Avoid litigation expense

- Minimize equipment damage

- Minimize system down time

- Comply with codes and safety regulations (OSHA, NFPA, NEC).

- Insurance requirements

1.4 Engineering Methodology For Arc Flash calculations, a thorough understanding of the IEEE 1584 standard, fault analysis principles and protective coordination is required.

1.4.1 IEEE Standard 1584 The IEEE 1584 standard provides a procedure to determine incident energy to which a worker may be exposed. The equations used in the 1584 standard were developed from tests of arc flash incidents initiated in a lab environment. While it’s not feasible to include every combination of environmental factors in the tests, the tests and resulting empirical equations provide the best means of estimating arc flash hazard levels available today. It’s still important to understand the limitations of the tests and use engineering judgment when interpreting the calculations. Significant variations in incident energy can result from relatively small changes in the power system model. It’s important to understand where these sensitive areas exit and how to make changes that will provide more conservative results. Refer to the IEEE 1584 standard and the following chapters to gain a better understanding of the assumptions, limitations and application guidelines for arc flash analysis.

You should think of Arc Flash calculations as a sensitivity study rather than a single fixed calculation. Since the incident energy is based on a combination fault current and trip time, it is not possible to predict whether a higher fault current or a lower fault current will produce the worst-case incident energy. The arcing fault current is often below the instantaneous trip setting and for these cases a lower fault current will result in a longer trip time and more energy release.

The intent of this guide is to describe how the PTW Arc Flash module calculates and reports the incident energy and flash boundary values, and to understand the terminology and assumptions used in the software. This guide is a supplement and not a substitute for a complete understanding of the IEEE 1584 standard.

Page 7: Reference ArcFlash

7/15/2008

1.4.2 Arc Flash Report Definitions

From the above table, reading from left to right, the columns have the following definitions:

Bus Name Fault location for bus report. For line side and load side report options the bus refers to the equipment where the line side and load side protective devices are connected.

Protective Device Name Refers to the protective device that clears the arcing fault or portion of the total arcing fault current.

Bus kV Bus voltage at the fault location.

Bus Bolted Fault Current (kA) The current flowing to a bus fault that occurs between two or more conductors or bus bars, where the impedance between the conductors is zero.

Bus Arcing Fault The calculated arcing current on the faulted bus

Protective Device Bolted Fault Current (kA) The portion of the total bolted fault current, that flows through a given protective device.

Protective Device Arcing Fault Current (kA) The arc current flowing through each protective device feeding the electric arc fault. Note that the total arc fault current may flow through several parallel sources to the arc location.

Trip / Delay Time The time required for the protective device to operate for the given fault condition. In the case of a relay, the breaker opening time is entered separately from the relay trip time. For low voltage breakers and fuses, the trip time is assumed to be the total clearing curve or high tolerance of the published trip curve. Breaker Opening Time The time required for a breaker to open after receiving a signal from the trip unit to operate. The combination of the Trip/Delay time and the Breaker Opening time determines the total time required to clear the fault. For low voltage circuit breakers, the total clearing time displayed on the Manufacturer’s drawing is assumed to include the breaker opening time.

Ground Indicates whether the fault location includes a path to ground. Systems with high-resistance grounds are assumed to be ungrounded in the Arc Flash calculations. (Available for IEEE 1584 only) Equip Type Used only in the IEEE 1584 method to indicate whether the equipment is Switchgear, Panel, Cable or Open Air. The equipment type provides a default Gap value and a distance exponent used in the IEEE incident energy equations. The equipment type provides a default Gap value and a distance exponent used in the IEEE incident energy equations.

Page 8: Reference ArcFlash

Arc Flash Reference Manual 1 - 7

SKM Power*Tools for Windows

Gap Used only in the IEEE 1584 method to define the spacing between bus bars or conductors at the arc location. Duration of Arc The summation of Trip/Delay Time and Breaker Opening Time. Arc Type Identifies whether the fault location is in an enclosure or in open air. In open air the arc energy will radiate in all directions whereas an enclosure will focus the energy toward the enclosure opening. The In Box / Air selection is available when the NFPA 70E study option is selected. For the IEEE 1584 study selection the In Box or In Air is determined automatically from the Equipment Type specification.

Arc Flash Boundary The distance from exposed live parts within which a person could receive a 2nd degree burn. Working Distance The distance between the arc source and the worker’s face or chest.

Incident Energy The amount of energy on a surface at a specific distance from a flash.

Required Protective FR Clothing Category (PPE) Indicates the Personal Protective Equipment (PPE) required to prevent an incurable burn at the working distance during an arcing fault.

Label # This allows the user to specify the prefix character that will go on the "Label #" column in the Arc Flash spreadsheet report. This field can help in sorting out (organizing) the label when they printed out.

Cable Length From Trip Device Reports the total cable length from the protective device that trips to clear the fault to the faulted bus. If there is no cable in between, nothing will be reported.

Incident Energy at Low Marginal This will report an incident energy value of the bus, if the incident energy on the bus meets the low marginal criteria value entered in the PPE.

Incident Energy at High Marginal This will report an incident energy value of the bus, if the incident energy on the bus meets the high marginal criteria value entered in the PPE.

Page 9: Reference ArcFlash

7/15/2008

If NESC 2007 method is selected, the following column headers also appear:

SLG Bolted Fault Initial Symmetrical RMS single-line-to-ground fault current. (Reported by Comprehensive Short Circuit Study.)

Duration of Arc (sec.) The sum of the Trip/Delay Time and the Breaker Opening Time.

Altitude (feet or meter) Altitude of the worksite where the arcing fault could potentially occur. The unit is in feet or meter depending on the unit selection (English or Metric) in the arc flash study option window. This will affect the minimum approach distance.

Max Over Voltage Factor (T) The maximum anticipated per-unit over voltage factor (T) at the worksite determined by an engineering analysis.

3-Phase Multiplier Specify here the 3-phase multiplier. This will affect the calculated incident energy. The calculated incident energy from Table 410-1 and Table 410-2 of NESC 2007 is based single-phase system.

Gap Distance of the arc gap

Type of Work Specify here the type of work: Com (for communications) or Sup (for supply). This will affect the minimum approach distance.

LL/LG Specify here whether the work being done is on a line to line (phase-to-phase) or line to ground (phase-to-ground) system. This will affect the minimum approach distance for supply type of work

Separation Distance The distance at which the calculated incident energy from Table 410-1 and Table 410-2 of NESC 2007 is based on.

Minimum Approach Distance The distance from any exposed energized part within which an employee could approach.

Rubber Insulating Equipment Class The class of rubber insulating sleeves the employee shall wear, in addition to the rubber insulating gloves.

Page 10: Reference ArcFlash

Arc Flash Reference Manual 1 - 9

SKM Power*Tools for Windows

Detail View versus Summary View The detail view in the arc flash report lists all parallel contributions and the accumulated energy as each contribution is cleared. The summary view lists only the last branch that clears the significant contribution as defined by the "Cleared Fault Threshold" percentage specified.

In the Detail View, the program traces each connected branches to find the protective device that trips first in the branch and lists it under the faulted bus. If the directly connected branch doesn’t have a protective device, the program walks the branch until it finds one.

If standard NFPA is followed, the incident energy is calculated using the bolted bus fault current for all protective devices listed under the bus without consider the reduction of fault current after some of the devices have been tripped. If IEEE 1584 is followed, the incident energy is calculated by using the arcing bus fault current left at the bus which consider the fact that some devices have tripped already and the one that trips later doesn’t see as much current.

In the Summary View, only one device under each bus is listed, and that is the one after it’s tripping a user defined percentage (ie… 80%) of the total fault current would have been cleared. The user can define the percentage in the Arc Flash Study Options dialog (see section 1.5.2).

The data associated with the device listed in the summary view will be used in the Bus Detail report and Arc Flash Label.

Scenarios… This button brings up a window where the user can specify to report Arc Flash results based on the current scenario opened; or if the project has multiple scenarios, the user can select Arc Flash results to report the worst case (the one with the highest incident energy) out all of all the selected scenarios. Furthermore, the user can also select Arc Flash result to report the "Best Case Scenario". The "Best Case Scenario" is the one with the lowest incident energy out of all the selected scenarios.

Page 11: Reference ArcFlash

7/15/2008

For instance, if a project has four scenarios, in this window the user can select all of the scenarios and select the "Worse Scenario" option button. When the user clicks on the "OK" button, what will be reported by Arc Flash spreadsheet report for each bus is the incident energy from the scenario with the highest value.

Similarly, if a project has four scenarios, in this window the user can select all of the scenarios and select the "Best Scenario" option button. When the user clicks on the "OK" button, what will be reported by Arc Flash spreadsheet report for each bus is the incident energy from the scenario with the lowest value.

Selecting worst case will greatly help in printing out the arc flash label for the worst case situation for those scenarios selected.

In the Arc Flash Report, the scenario where the incident energy being reported came from is indicated by (*S0), (*S1), (*S3), etc. depending on the scenario number.

Custom Label.. This button will bring up the custom label window where the user can specify the Page Size, Label Size, Page Margins, Orientation, Rows and Columns of the labels and Spacing between labels (See section 1.5.5 for more information on custom label).

Work Permit This button brings up the window to generates a work permit required for working on energized equipment per NFPA 70E 2004

Re-Run Study This button refreshes the Arc Flash display to reflect updated short circuit values caused by system changes made since the last arc flash study was run.

Page 12: Reference ArcFlash

Arc Flash Reference Manual 1 - 11

SKM Power*Tools for Windows

Options… This button will display Option menu for Arc Flash Study

PPE Table This button will display PPE Table where Personal Protective Equipment descriptions are assigned to ranges of incident energy. The PPE classes, descriptions and label color for each class are user-definable.

Notes Section

(*N1) - Out of IEEE 1584 or NFPA 70E Ranges. LEE equation is used in this case and applicable for Open Air only.

(*N2) - Percentage of fault current cleared is less than the Cleared Fault Threshold specified in the study options

(*N3) - Arcing Fault Current Low Tolerances Used.

(*N4) - Equipment Specific Incident Energy and Flash Boundary Equations Used.

(*N5) - Mis-coordinated, Upstream Device Tripped.

(*N6) - Special Instantaneous Protection in Use. Refer to Bus Equipment & Arc Flash subview.

(*N7) - Trip Time Unlinked with TCC.

(*N8) - Fault Current Unlinked with Fault Study results.

(*N9) - Max. Arcing Duration Reached. The time taken for the protective device to clear the fault is longer than the Max. Arcing Duration is specified in the study options.

(*N10) - Fuse Cable Protector Modeled. Fuse Cable Protector Modeled is when the fuse is connected to a cable with multiple conductors in parallel. The fault current and arcing fault through the fuse is divided by the #parallel to read the trip time.

(*N11) - Out of IEEE 1584 Range, Lee Equation Used. Applicable for Open Air only. Existing Equipment type is not Open Air. This shows only if data at the bus is out of the IEEE 1584 Range and the selected equipment is not an Open Air type.

(*N12) - Out of IEEE 1584 Gap Range

(*N13) - PPE up one Category.

(*N14) - Zone Selective Interlock (ZSI) in Use. If one of the protective device directly connected to the bus has a ZSI function, the bus is considered having instantaneous protection and the trip time become user-definable in the Arc Flash main window.

(*N15) - Bolted Fault < 10 kA or Transformer Size < 125 kVA, Report as Category 0

(*N20) - Out of NESC Voltage Range.

(*N21) - Out of NESC Fault Current Range.

Page 13: Reference ArcFlash

7/15/2008

(*N22) - Out of NESC Max Clearing Range.

(*N23) - Out of NESC Voltage Range.

(*N24) - Out of NESC Altitude Range.

(*N25) - Out of NESC Max Over Voltage Factor Range.

(*N26) - NESC SLG Fault is Zero

(*S0), (*S1),(*S2),..etc – Indicates which scenario the incident energy being reported came from.

1.4.3 Arc Flash Menu Options The Arc Flash study module has several menu options. With the Arc Flash application window active, the following menu items are available:

Bus Detail Generates a detailed label including the protective device settings, arcing fault current, incident energy at multiple working distances, and clothing class for the primary working distance. You can also enter the client information and job #, etc. Bus Detail can be used on a single bus or for a selected group of buses. The description information entered will be re-used for all buses.

Standard Label The Bus Label provides a summary of the flash boundary, incident energy and PPE classification at each bus. The NFPA shock hazard Limited, Restricted and Prohibited Approach boundaries are also listed based on the nominal system voltage at the bus.

Custom Label Displays the custom label window where the user can specify the Page Size, Label Size, Page Margins, Orientation, Rows and Columns of the labels and Spacing between labels

Work Permit Generates a work permit required for working on energized equipment per NFPA 70E 2004.

Re-run Studies Refreshes the Arc Flash display to reflect updated short circuit values caused by system changes made since the last arc flash study was run.

Page 14: Reference ArcFlash

Arc Flash Reference Manual 1 - 13

SKM Power*Tools for Windows

PPE Table Displays PPE Table where Personal Protective Equipment descriptions are assigned to ranges of incident energy. The PPE classes, descriptions and label color for each class are user-definable.

Auto Update Arc Flash Result When this is checked, the software will automatically update the arc flash results whenever there is a change in the system model. For instance, when user open up a tie-breaker or change the size of a motor in the system model, the software will automatically update the arc flash results based on those changes. The user would not need to re-run the arc flash study.

Link/Unlink with Fault Study You can highlight a bus or multiple buses from the Arc Flash table and select the Unlink with Fault Study option to allow you to enter user-defined values for bolted fault current. Remember to re-link the rows if you want fault currents to be updated from the project database.

Link/Unlink with TCC You can highlight a bus or multiple buses from the Arc Flash table and select the Unlink with TCC option to allow you to enter user-defined Trip Times for the protective device. Remember to re-link the rows if you want the trip times to be updated from the project database.

Link/Unlink with Ground You can highlight a bus or multiple buses from the Arc Flash table and

select the Unlink Ground option to allow you to enter “yes” or “no” in Ground column.

Link/Unlink Gap You can highlight a bus or multiple buses from the Arc Flash table and

select the Unlink Gap option to allow you to enter user-defined values for Gap.

Link/Unlink Equipment Type You can highlight a bus or multiple buses from the Arc Flash table and

select the Unlink Equipment Type option to allow you to select your own equipment type from the list.

Link/Unlink Working Distance You can highlight a bus or multiple buses from the Arc Flash table and

select the working distance to allow you to enter user-defined values for working distance.

Export to This selection allows users to export the result into excel, *.htm, or

*.ss3 file formats. User defined Arc Flash Table This option selection displays the user “User defined Arc Flash Table”

where the user can enter any user-defined bus voltage, fault current, and arcing duration and it will calculate the incident energy and flash boundary results. You can also click on the “Custom Label” button it will produce arc flash label based on those results.

Page 15: Reference ArcFlash

7/15/2008

Include non 3-phase system Includes non 3-phase system buses to the Arc Flash display and report Study Options This option selection will display Option menu for Arc Flash Study Study Options Report This option selection will display a window where the user can print the

options that have been selected in the Option menu for Arc Flash Study Font, Page Margin This option selection will display a window where the user can select

the type of font to use for the arc flash report Print/Export Option This option selection will display a window where the user can change

page margin, and page number display for printing.

The same menu items are available by clicking the Right Mouse button.

1.4.4 Arc Flash Study Procedure The Arc Flash study requires an accurate short circuit and coordination study for the different modes in which the system may operate.

The general arc flash study procedure outlined in the IEEE 1584 standard includes:

1. Collect field data sufficient to perform a short-circuit and coordination study.

2. Identify the possible system operating modes including tie-breaker positions, parallel generation, etc.

3. Calculate the bolted fault current at each fault location.

4. Calculate the arcing fault current flowing through each branch for each fault location.

5. Determine the time required to clear the arcing fault current using the protective device settings and associated trip curves.

6. Select the working distances based on system voltage and equipment class.

7. Calculate the incident energy at each fault location.

8. Calculate the flash protection boundary at each fault location.

1.4.5 Arc Flash Modeling Assumptions It’s important to understand the assumptions made by the PTW Arc Flash module.

The following assumptions are applied

Page 16: Reference ArcFlash

Arc Flash Reference Manual 1 - 15

SKM Power*Tools for Windows

- Arc Flash searches the entire system topology, starting from the faulted bus out, to find the first protective device with an over-current trip curve. When the first device is located, the search is discontinued (i.e. assumes coordination with upstream branches). The next upstream protective device may be included in the search by selecting the “Check upstream devices for mis-coordination” option. If there are multiple contributions to the faulted bus, the search process will be repeated until each contribution is cleared by it’s protective device, or the search reaches the end of the topology. Protection functions with a name of “Ground”, “Earth”, or “AF_EX” will be excluded from the protective device search and the next upstream device is used instead. Upstream refers to the flow of power from the primary sources of power to the faulted location from the perspective of standing at the fault location.

- The trip time is determined for all protective devices located in the branch that contains the first trip device and the device with the fastest trip time for the given arcing fault current is used.

- Worker is stationary during the entire arc flash incident (constant working distance).

- Induction motors contribute continuous sub-transient current until removed at user specified time ‘x’, unless they are specifically excluded from the arc flash study.

- When applying generic current-limiting fuse representation, the current-limiting range is assumed to start where fuse clearing curve drops below 0.01 sec.

- When applying generic current-limiting fuse representation, fuses operating in the current limiting range are assumed to clear in ½ cycle for currents 1 to 2 times the current where the current-limiting range begins, and ¼ cycle for currents higher than 2 times the current where the current-limiting range begins.

- Interrupting device is rated for the available short circuit current (no equipment damage is considered).

- Upstream branch devices are properly coordinated with downstream branch devices. The next upstream protective device may be included in the search by selecting the “Check upstream devices for mis-coordination” option. The device that clears the arcing fault fastest is used.

- Ground fault and motor over load devices are not included.

- For multi-function protective devices, only the first f unction is used to determine the trip time.

- Reports only the larger incident energy based on low or high tolerances applied to the calculated arcing fault current.

- When the total fault current cleared is less than the threshold percent specified in the study setup, or no protective device is found, the bus is labeled as Dangerous and the incident energy and flash boundary are not reported.

- If the trip time obtained from the time current curve is larger than the maximum protection trip time defined in the study setup, the maximum protection trip time is used.

- Any equations where 600V and below is used in the NFPA 70E standard, it is applied to 1 kV and below as well in the software. This is because in IEC standard, there is no 600V. IEC standard classifies any voltage below 1 kV as low voltage.

Page 17: Reference ArcFlash

7/15/2008

1.4.6 Arc Flash Equations

IEEE 1584 Standard – 2002 Arcing Fault Current at the bus (Ia) and through each protective device (Ia br) for bus voltages less than 1 kV and bolted fault current between 700Amps and 106,000 Amps.

lg (Ia) = K + 0.662 lg (IB) + 0.0966 V + 0.000526 G + 0.5588 V lg (IB) - 0.00304 G lg (IB)

lg is log10

Ia is arcing fault current at the bus in kA

K is -0.153 for open configuration and

is -0.097 for box configuration

IB is bolted fault current – 3phase sym rms kA at the bus

V is bus voltage in kV

G is bus bar gap between conductors in mm

Arcing Fault Current at the bus (Ia) and through each protective device (Ia br) for bus voltages greater than or equal to 1 kV and bolted fault current between 700Amps and 106,000 Amps.

lg (Ia) =0.00402 + 0.983 lg (IB)

Therefore, Ia = 10 lg (Ia)

Ia br = Ia * IB br / IB

IB br is the Bolted Fault Current through each protective device in kA. Ia br is the arcing fault current through each protective device in kA.

*Note: For IEEE 1584-2002 - Section 5.2, a second arcing fault current is calculated at 85% of the original. The Trip Time and Incident Energy at both the 85% and 100% arcing fault currents are calculated and the larger of the two Incident Energy values is displayed with the associated Trip Time. PTW allows a user-defined arc fault tolerance. The default tolerance is -15% as described in the IEEE 1584 - 2002 standard. For additional information refer to section 1.5.9.

Normalized Incident Energy

lg (En) = K1 + K2 + 1.081 lg (Ia) + 0.0011 G

En is incident energy (J/cm2) normalized for a arcing duration of 0.2s and working distance of 610mm K1 is -0.792 for open configuration and is -0.555 for box configuration (switchgear, panel, cable) K2 is 0 for ungrounded and high resistance grounded systems and is -0.113 for grounded systems G is the gap between bus bar conductors in mm solve En = 10 ^ lg En

Page 18: Reference ArcFlash

Arc Flash Reference Manual 1 - 17

SKM Power*Tools for Windows

Incident Energy converted from normalized:

E = 4.184 Cf En (t/0.2) (610^X / D^X) E is incident energy (J/cm2) Cf is 1.0 for voltage above 1 kV and is 1.5 for voltage at or below 1 kV t is arcing duration in seconds D is the working distance in mm x is the distance exponent Default distance exponent x based on the voltage level and equipment type x Equipment Type kV 1.473 Switchgear < 1 1.641 Panel < 1 0.973 Switchgear > 1 2 all others

Arc Flash Boundary (DB) DB = [ 4.184 Cf En (t/0.2) (610^X / EB) ] ^ 1/x

DB is the arc flash boundary in mm at incident energy of EB EB is the limit for a second-degree bare skin burn. EB = 5.0 (J/cm2)

x is the distance exponent

Default distance exponent x based on the voltage level and equipment type x Equipment Type kV 1.473 Switchgear < 1 1.641 Panel < 1 0.973 Switchgear > 1 2 all others

Page 19: Reference ArcFlash

7/15/2008

NFPA 70E - 2004 The NFPA 7E – 2004 follows the same procedure as IEEE 1584 – 2002 with the following exceptions: Flash Protection Boundary for buses less than 600 Volts: Dc = [2.65 x MVAbf x t] ½ Dc = [53 x MVA x t] ½ Where

Dc = distance in feet from an arc source for a second-degree burn MVA bf = bolted fault capacity available at bus in MVA MVA = capacity rating of transformer. For transformers less than 0 .75 MVA, multiply

the transformer MVA by 1.25. t = arc exposure in seconds. Flash Protection Boundary for buses above 600 volts: for Clearing Time of 0.1 second or less, calculate boundary distance where incident energy = 1.5 cal/cm2 for Clearing Time longer than 0.1 second, calculate boundary distance where incident energy = 1.2 cal/cms2

Page 20: Reference ArcFlash

Arc Flash Reference Manual 1 - 19

SKM Power*Tools for Windows

NESC – 2007

When the user selects NESC 2007 as the standard, the software will do arc flash hazard analysis based on the tables specified by NESC 2007.

The following tables are reprinted with permission from 2007 National Electrical Safety Code.

Table 410-1: Clothing and clothing systems—voltage, fault current, and maximum clearing time for voltages 1 to 46 kV 1 (See Rule 410A3.)

4-cal system 8-cal system 12-cal system

Phase-to-phase voltage (kV) Fault current (kA)

Maximum clearing time (cycles)

Maximum clearing time (cycles)

Maximum clearing time (cycles)

1 to 15 5 46.5 93.0 139.5

10 18.0 36.1 54.1

15 10.0 20.1 30.1

20 6.5 13.0 19.5

15.1 to 25 5 27.6 55.2 82.8

10 11.4 22.7 34.1

15 6.6 13.2 19.8

20 4.4 8.8 13.2

25.1 to 36 5 20.9 41.7 62.6

10 8.8 17.6 26.5

15 5.2 10.4 15.7

20 3.5 7.1 10.6

36.1 to 46 5 16.2 32.4 48.6

10 7.0 13.9 20.9

15 4.3 8.5 12.8

20 3.0 6.1 0.1

Copyright 2006 IEEE All rights reserved.

1These calculations are based on open air phase-to-ground arc. This table is not intended for phase-to-phase arcs or enclosed arcs (arc in a box). These calculations are based on a 15-in separation distance from the arc to the employee and arc gaps as follows: 1 to 15 kV = 2 in, 15.1 to 25 kV = 4 in, 25.1 to 36 kV = 6 in, 36.1 to 46 kV = 9 in. See IEEE Std 4-1995. These calculations were derived using a commercially available computer software program. Other methods are available to estimate arc exposure values and may yield slightly different but equally acceptable results. The use of the table in the selection of clothing is intended to reduce the amount or degree of injury but may not prevent all burns.

Page 21: Reference ArcFlash

7/15/2008

Table 410-2: Live-line tool work clothing and cloth ing systems—voltage, fault current, and maximum clearing time for voltages 46.1 to 800 kV 1

(See Rule 410A3.)

4-cal system 8-cal system 12-cal system

Phase-to-phase voltage (kV)

Fault current (kA)

Maximum clearing time (cycles)

Maximum clearing time (cycles) Maximum clearing time (cycles)

46.1 to 72.5 20 8.5 17.0 25.5

30 5.3 10.5 15.8

40 3.7 7.3 11.0

50 2.8 5.5 8.3

72.6 to 121 20 8.2 16.5 24.7

30 4.7 9.4 14.1

40 3.1 6.2 9.3

50 2.2 4.4 6.6

138 to 145 20 9.8 19.5 29.3

30 5.6 11.2 16.8

40 3.7 7.4 11.1

50 2.6 5.3 7.9

161 to 169 20 9.3 18.6 27.9

30 5.7 11.5 17.2

40 4.0 8.0 12.0

50 3.0 6.0 9.0

230 to 242 20 10.4 20.9 31.3

30 6.4 12.9 19.3

40 4.5 9.0 13.5

50 3.4 6.8 10.1

345 to 362 20 22.6 45.3 67.9

30 14.0 28.1 42.1

40 9.8 19.6 29.4

50 7.4 14.7 22.1

500 to 550 20 18.9 37.8 56.7

30 11.7 23.3 35.0

40 8.1 16.3 24.4

50 6.1 12.2 18.3

765 to 800 20 43.6 87.3 130.9

30 27.0 53.9 80.9

40 18.9 37.8 56.7

50 14.2 28.4 42.6

1Arc gap—calculated by using the phase-to-ground voltage of the circuit and dividing by 10. The dielectric strength of air is taken at 10 kV per inch. See IEEE Std 4-1995. Distance from arc—calculated by using the minimum approach distance from Table 441-2 and subtracting two times the assumed arc gap length. These calculations were derived using a commercially available computer software program. Other methods are available to estimate arc exposure values and may yield slightly different, but equally acceptable results. The use of the table in the selection of clothing is intended to reduce the amount or degree of injury but may not prevent all burns.

Page 22: Reference ArcFlash

Arc Flash Reference Manual 1 - 21

SKM Power*Tools for Windows

Table 431-1: Communication work minimum approach di stances (in meters) (See Rule 431 in its entirety.)

Copyright © 2006 IEEE. All rights reserved.

1For single-phase lines off three-phase systems, use the phase-to-phase voltage of that system. 2For single-phase systems, use the highest voltage available. 3The data used to calculate Table 431-1(m) was derived from test data taken under standard atmospheric conditions for dry and clean insulators. Standard atmospheric conditions are defined as temperatures above freezing, wind less than 24 km per hr, and normal barometric pressure with unsaturated and uncontaminated air.

Voltage range phase-to-phase (rms)1 Distance to employee at altitudes from sea level to 3600 m

0 to 50 V 2 Not specified

51 to 300 V 2 Avoid contact

301 to 750 V 2 0.31 m

751 V to 15 kV 0.65 m

15.1 kV to 36 kV 0.91 m

36.1 kV to 46 kV 1.06 m

46.1 kV to 72.5 kV 1.22 m

At altitudes from Voltage range

phase-to-phase (rms)1 0 to 900 m 90 to 1800 m 1801 to 3600 m

72.6 to 121 kV 1.43 m 1.50 m 1.64 m

121.1 to 169 kV 1.75 m 1.85 m 2.04 m

169.1 to 362 kV 3.70 m 3.95 m 4.48 m

362.1 to 800 kV 7.19 m 7.72 m 8.84 m

Page 23: Reference ArcFlash

7/15/2008

Table 431-1: Communication work minimum approach di stances (in feet) (See Rule 431 in its entirety.)

Voltage range phase-to-phase (rms) 1 Distance to employee at altitudes from sea level to 12 000 ft

0 to 50 V 2 Not specified

51 to 300 V 2 Avoid contact

301 to 750 V 2 1 ft-0 in

751 V to 15 kV 2 ft-2 in

15.1 kV to 36 kV 3 ft-0 in

36.1 kV to 46 kV 3 ft-6 in

46.1 kV to 72.5 kV 4 ft-0 in

At altitudes from Voltage range

phase-to-phase (rms)1 0 to 3000 ft 3001 to 6000 ft 6001 to 12 000 ft

72.6 kV to 121 kV 4 ft-9 in 4 ft-11 in 5 ft-5 in

121.1 kV to 169 kV 5 ft-10 in 6 ft-1 in 6 ft-9 in

169.1 kV to 362 kV 12 ft-3 in 13 ft-0 in 14 ft-9 in

362.1 kV to 800 kV 23 ft-8 in 25 ft-4 in 29 ft-0 in

1 For single-phase lines off three-phase systems, use the phase-to-phase voltage of that system.

2 For single-phase systems, use the highest voltage available. 3 The data used to calculate Table 431-1(ft) was derived from test data taken under standard atmospheric conditions for dry and clean insulators. Standard atmospheric conditions are defined as temperatures above freezing, wind less than 15 miles per hour, and normal barometric pressure with unsaturated and uncontaminated air.

Table 441-1: AC Live Work Minimum Approach Distance 4 (See Rule 441 in its entirety.)

Distance to employee

Phase-to-ground Phase-to-phase Voltage in kilovolts phase to phase1,2

(m) (ft–in) (m) (ft–in)

0 to 0.0501 not specified not specified

0.051 to 0.3001 avoid contact avoid contact

0.301 to 0.7501 0.31 1–0 0.31 1–0

0.751 to 15 0.65 2–2 0.67 2–3

15.1 to 36.0 0.77 2–7 0.86 2–10

36.1 to 46.0 0.84 2–9 0.96 3–2

46.1 to 72.5 1.003 3–33 1.20 3–11

1 For single-phase systems, use the highest voltage available. 2 For single-phase lines off three phase systems, use the phase-to-phase voltage of the system. 3 The 46.1 to 72.5 kV phase-to-ground 3-3 distance contains a 1-3 electrical component and a 2-0 inadvertent movement component . 4 Distances listed are for standard atmospheric conditions. The data used to formulate this table was obtained from test data taken with standard atmospheric conditions. Standard atmospheric conditions are defined as temperatures above freezing, wind less than 15 mi per hr or 24 km per hr, unsaturated air, normal barometer, uncontaminated air, and clean and dry insulators. If standard atmospheric conditions do not exist, extra care must be taken.

Page 24: Reference ArcFlash

Arc Flash Reference Manual 1 - 23

SKM Power*Tools for Windows

Table 441-2 (in feet) AC Live Work Minimum Approach Distances for Altitud es Less Than 3000 ft Above Sea Level, Where T Has Been Determined According to Rule 441A5 1, 2 (See Rule 441 in its entirety.)

Distance to employee: phase-to-ground work, in air, barehand, and clear live-line tool

Maximum phase-to-phase voltage in kilovolts Maximum anticipated per unit overvoltage

factor T 72.5 to 121.0

121.1 to 145.0

145.1 to 169.0

169.1 to 242.0

242.1 to 362.0

362.1 to 550.0

550.1 to 800.0

1.5 2 ft 2 in 2 ft 5 in 2 ft 8 in 3 ft 4 in 4 ft 6 in 6 ft 6 in 10 ft 5 in

1.6 2 ft 3 in 2 ft 6 in 2 ft 9 in 3 ft 6 in 4 ft 9 in 7 ft 11 ft 5 in

1.7 2 ft 4 in 2 ft 7 in 2 ft 10 in 3 ft 8 in 4 ft 11 in 7 ft 6 in 12 ft 5 in

1.8 2 ft 5 in 2 ft 8 in 3 ft 3 ft 10 in 5 ft 2 in 8 ft 1 in 13 ft 6 in

1.9 2 ft 6 in 2 ft 9 in 3 ft 1 in 4 ft 5 ft 5 in 8 ft 8 in 14 ft 8 in

2.0 2 ft 7 in 2 ft 11 in 3 ft 2 in 4 ft 1 in 5 ft 8 in 9 ft 4 in 15 ft 11 in 3

2.1 2 ft 8 in 3 ft 3 ft 4 in 4 ft 3 in 5 ft 10 in 9 ft 11 in 17 ft 2 in

2.2 2 ft 9 in 3 ft 1 in 3 ft 5 in 4 ft 5 in 6 ft 2 in 10 ft 7 in 18 ft 5 in

2.3 2 ft 10 in 3 ft 2 in 3 ft 6 in 4 ft 7 in 6 ft 6 in 11 ft 2 in 19 ft 9 in

2.4 2 ft 11 in 3 ft 3 in 3 ft 7 in 4 ft 9 in 6 ft 10 in 11 ft 10 in 3 21 ft 3 in

2.5 3 ft 3 ft 4 in 3 ft 9 in 4 ft 11 in 7 ft 3 in 12 ft 8 in 22 ft 8 in

2.6 3 ft 3 ft 5 in 3 ft 10 in 5 ft 7 ft 7 in 13 ft 4 in

2.7 3 ft 1 in 3 ft 6 in 3 ft 11 in 5 ft 2 in 7 ft 11 in 14 ft 2 in

2.8 3 ft 2 in 3 ft 7 in 4 ft 1 in 5 ft 4 in 8 ft 4 in 15 ft

2.9 3 ft 3 in 3 ft 9 in 4 ft 2 in 5 ft 6 in 8 ft 9 in 15 ft 9 in

3.0 3 3 ft 4 in 3 ft 10 in 4 ft 3 in 5 ft 8 in 9 ft 2 in 16 ft 8 in

3.1 3 ft 5 in 3 ft 11 in 4 ft 4 in 5 ft 10 in 9 ft 6 in

3.2 3 ft 6 in 4 ft 4 ft 6 in 6 ft 9 ft 11 in

3.3 3 ft 7 in 4 ft 1 in 4 ft 7 in 6 ft 3 in 10 ft 4 in

3.4 3 ft 8 in 4 ft 2 in 4 ft 8 in 6 ft 5 in 10 ft 9 in

3.5 3 ft 9 in 4 ft 3 in 4 ft 10 in 6 ft 8 in 11 ft 3 in

1Distances listed are for standard atmospheric conditions. The data used to formulate this table was obtained from test data taken with standard atmospheric conditions. Standard atmospheric conditions are defined as temperatures above freezing, wind less than 15 miles per hour (24 km per hr), unsaturated air, normal barometer, uncontaminated air, and clean and dry insulators. If standard atmospheric conditions do not exist, extra care must be taken. 2 Distances are based on altitudes below 3000 ft above sea level. For altitudes above 3000 ft, Rule 441A6 applies. 3 See Rule 441A4a.

Page 25: Reference ArcFlash

7/15/2008

Table 441-2 (in meters) AC Live Work Minimum Approach Distances for Altitud es Less Than 900 m Above Sea Level, Where T Has Been Determined According to Rule 441A5 1, 2 (See Rule 441 in its entirety.)

Distance to employee: phase-to-ground work, in air, barehand, and clear live-line tool

Maximum phase-to-phase voltage in kilovolts

Maximum anticipated per unit overvoltage

factor T 72.5 to 121.0

121.1 to 145.0

145.1 to 169.0

169.1 to 242.0

242.1 to 362.0

362.1 to 550.0

550.1 to 800.0

1.5 0.72 0.73 0.80 1.01 1.36 1.96 3.16

1.6 0.79 0.76 0.83 1.05 1.43 2.12 3.46

1.7 0.86 0.78 0.86 1.10 1.50 2.28 3.78

1.8 0.93 0.81 0.90 1.15 1.57 2.45 4.11

1.9 1.01 0.84 0.93 1.20 1.64 2.62 4.45

2.0 1.07 0.87 0.96 1.24 1.71 2.82 4.84 3

2.1 1.10 0.90 0.99 1.29 1.78 3.01 5.22

2.2 1.12 0.92 1.03 1.34 1.88 3.20 5.60

2.3 1.14 0.95 1.06 1.38 1.98 3.40 6.00

2.4 1.16 0.98 1.09 1.43 2.08 3.61 3 6.46

2.5 1.18 1.01 1.12 1.48 2.19 3.84 6.89

2.6 1.20 1.04 1.16 1.52 2.30 4.06

2.7 1.23 1.06 1.19 1.57 2.41 4.30

2.8 1.25 1.09 1.22 1.62 2.54 4.56

2.9 1.27 1.12 1.26 1.66 2.65 4.80

3.0 3 1.29 1.15 1.29 1.71 2.77 5.07

3.1 1.31 1.18 1.32 1.76 2.89

3.2 1.33 1.20 1.35 1.76 2.89

3.3 1.36 1.23 1.39 1.88 3.15

3.4 1.37 1.26 1.42 1.94 3.27

3.5 1.39 1.29 1.45 2.02 3.40

1Distances listed are for standard atmospheric conditions. The data used to formulate this table was obtained from test data taken with standard atmospheric conditions. Standard atmospheric conditions are defined as temperatures above freezing, wind less than 24 km per hr, unsaturated air, normal barometer, uncontaminated air, and clean and dry insulators. If standard atmospheric conditions do not exist, extra care must be taken. 2 Distances are based on altitudes below 900 m above sea level. For altitudes above 900 m, Rule 441A6 applies. 3 See Rule 441A4a.

Page 26: Reference ArcFlash

Arc Flash Reference Manual 1 - 25

SKM Power*Tools for Windows

Table 441-3 (in feet)

AC Live Work Minimum Approach Distances for Altitud es Less Than 3000 ft Above Sea Level, Where T Has Been Determined According to Rule 441A5 1, 2 (See Rule 441 in its entirety.)

Distance to employee: phase-to-ground work, in air, barehand, and clear live-line tool

Maximum phase-to-phase voltage in kilovolts

Maximum anticipated per

unit overvoltage factor T

72.5 to 121.0 121.1 to 145.0

145.1 to 169.0

169.1 to 242.0

242.1 to 362.0

362.1 to 550.0

550.1 to 800.0

1.5 2 ft 6 in 2 ft 10 in 3 ft 1 in 4 ft 5 ft 6 in 8 ft 13 ft

1.6 2 ft 9 in 3 ft 2 in 3 ft 6 in 4 ft 6 in 6 ft 3 in 9 ft 5 in 15 ft 8 in

1.7 3 ft 1 in 3 ft 5 in 3 ft 10 in 5 ft 1 in 7 ft 11 ft 18 ft 6 in

1.8 3 ft 4 in 3 ft 9 in 4 ft 3 in 5 ft 7 in 7 ft 9 in 12 ft 6 in 21 ft 5 in

1.9 3 ft 7 in 4 ft 1 in 4 ft 7 in 6 ft 1 in 8 ft 7 in 14 ft 3 in 24 ft 7 in

2.0 3 ft 10 in 4 ft 4 in 4 ft 11 in 6 ft 7 in 9 ft 4 in 15 ft 11 in 27 ft 10 in 3

2.1 3 ft 11 in 4 ft 6 in 5 ft 1 in 6 ft 9 in 9 ft 7 in 16 ft 9 in 29 ft 7 in

2.2 4 ft 4 ft 7 in 5 ft 2 in 6 ft 11 in 10 ft 17 ft 6 in 31 ft 1 in

2.3 4 ft 1 in 4 ft 8 in 5 ft 3 in 7 ft 1 in 10 ft 5 in 18 ft 4 in 32 ft 10 in

2.4 4 ft 2 in 4 ft 9 in 5 ft 4 in 7 ft 3 in 10 ft 9 in 19 ft 2 in 3 34 ft 9 in

2.5 4 ft 3 in 4 ft 10 in 5 ft 6 in 7 ft 4 in 11 ft 2 in 20 ft 1 in 36 ft 6 in

2.6 4 ft 3 in 4 ft 11 in 5 ft 7 in 7 ft 6 in 11 ft 7 in 21 ft

2.7 4 ft 4 in 5 ft 5 ft 8 in 7 ft 8 in 12 ft 1 in 22 ft

2.8 4 ft 6 in 5 ft 1 in 5 ft 10 in 7 ft 10 in 12 ft 7 in 23 ft 1 in

2.9 4 ft 6 in 5 ft 3 in 5 ft 11 in 8 ft 13 ft 1 in 24 ft

3.0 3 4 ft 7 in 5 ft 4 in 6 ft 8 ft 2 in 13 ft 6 in 25 ft 1 in

3.1 4 ft 8 in 5 ft 5 in 6 ft 1 in 8 ft 4 in 13 ft 11 in

3.2 4 ft 9 in 5 ft 6 in 6 ft 2 in 8 ft 6 in 14 ft 5 in

3.3 4 ft 10 in 5 ft 7 in 6 ft 4 in 8 ft 9 in 14 ft 11 in

3.4 4 ft 11 in 5 ft 8 in 6 ft 5 in 8 ft 11 in 15 ft 4 in

3.5 5 ft 5 ft 9 in 6 ft 6 in 9 ft 3 in 15 ft 9 in

1Distances listed are for standard atmospheric conditions. The data used to formulate this table was obtained from test data taken with standard atmospheric conditions. Standard atmospheric conditions are defined as temperatures above freezing, wind less than 15 miles per hour (24 km per hr), unsaturated air, normal barometer, uncontaminated air, and clean and dry insulators. If standard atmospheric conditions do not exist, extra care must be taken. 2 Distances are based on altitudes below 3000 ft above sea level. For altitudes above 3000 ft, Rule 441A6 applies. 3 See Rule 441A4a

Page 27: Reference ArcFlash

7/15/2008

Table 441-3 (in meters)

AC Live Work Minimum Approach Distances for Altitud es Less Than 900 m Above Sea Level, Where T Has Been Determined According to Rule 441A5 1, 2 (See Rule 441 in its entirety.)

1Distances listed are for standard atmospheric conditions. The data used to formulate this table was obtained from test data taken with standard atmospheric conditions. Standard atmospheric conditions are defined as temperatures above freezing, wind less than 24 km per hr, unsaturated air, normal barometer, uncontaminated air, and clean and dry insulators. If standard atmospheric conditions do not exist, extra care must be taken. 2 Distances are based on altitudes below 900 m above sea level. For altitudes above 900 m, Rule 441A6 applies. 3 See Rule 441A4a.

Distance to employee: phase-to-ground work, in air, barehand, and clear live-line tool

Maximum phase-to-phase voltage in kilovolts Maximum

anticipated per unit overvoltage

factor T 72.5 to 121.0 121.1 to 145.0

145.1 to 169.0

169.1 to 242.0

242.1 to 362.0

362.1 to 550.0

550.1 to 800.0

1.5 0.76 0.85 0.94 1.21 1.65 2.43 3.96

1.6 0.84 0.94 1.05 1.36 1.89 2.86 4.76

1.7 0.92 1.04 1.16 1.53 2.13 3.33 5.62

1.8 1.00 1.13 1.27 1.68 2.36 3.80 6.51

1.9 1.08 1.23 1.38 1.85 2.61 4.32 7.48

2.0 1.15 1.32 1.48 2.00 2.83 4.84 8.47 3

2.1 1.18 1.35 1.53 2.05 2.91 5.09 9.00

2.2 1.20 1.38 1.56 2.09 3.03 5.32 9.47

2.3 1.22 1.41 1.59 2.14 3.15 5.57 9.99

2.4 1.25 1.44 1.62 2.19 3.27 5.82 3 10.58

2.5 1.27 1.46 1.65 2.23 3.39 6.11 11.10

2.6 1.29 1.49 1.69 2.28 3.53 6.39

2.7 1.32 1.52 1.72 2.33 3.67 6.71

2.8 1.35 1.55 1.76 2.38 3.83 7.03

2.9 1.37 1.58 1.79 2.43 3.97 7.32

3.0 3 1.39 1.61 1.82 2.48 4.10 4.64

3.1 1.41 1.63 1.85 2.52 4.24

3.2 1.43 1.66 1.88 2.58 4.37

3.3 1.46 1.69 1.92 2.66 4.54

3.4 1.48 1.71 1.94 2.71 4.67

3.5 1.50 1.73 1.97 2.80 4.80

Page 28: Reference ArcFlash

Arc Flash Reference Manual 1 - 27

SKM Power*Tools for Windows

Table 441-5: Altitude Correction Factor (See Rule 441 in its entirety.)

Altitude

(m) (ft)

Correction factor

Sea level to 900 Sea level to 3000 1.00

901 to 1200 3001 to 4000 1.02

1201 to 1500 4001 to 5000 1.05

1501 to 1800 5001 to 6000 1.08

1801 to 2100 6001 to 7000 1.11

2101 to 2400 7001 to 8000 1.14

2401 to 2700 8001 to 9000 1.17

2701 to 3000 9001 to 10 000 1.20

3001 to 3600 10 001 to 12 000 1.25

3601 to 4200 12 001 to 14 000 1.30

Table 441-6: Maximum Use Voltage for Rubber Insulat ing Equipment

Class of Equipment Maximum Use Voltage1

00 500

0 1 000

1 7 500

2 17 000

3 26 500

4 36 000

Page 29: Reference ArcFlash

7/15/2008

1.4.7 Default Values

Equipment Categories and Gap

Equipment Category contains Gap (mm) Equip Type kV Switchgear 32 Panel < 1 Cable 13 Cable < 1 Air 32 Open Air < 1 * all others 25 Panel < 1 Cable 13 Cable 1-5 Air 102 Open Air 1-5 * all others 25 Switchgear 1-5 Cable 13 Cable > 5 Air 153 Open Air > 5 * all others 153 Switchgear > 5

Working Distances

Default the working distance based on the voltage level and equipment type Working Distance Equipment Type kV 24 inches (610mm) Switchgear <= 1 18 inches (455mm) Panel <=1 36 inches (910mm) Switchgear > 1 & < 35 72 inches (1829mm) Switchgear > 35 18 inches (455mm) all others

1.4.8 Determination of Grounded/Ungrounded Bus

The PTW Arc Flash study performs a calculation for both 3 phase and single-line-to-earth faults. The single-line-to-earth fault is only used to determine whether the bus should be considered as grounded or ungrounded. Since the IEEE 1584 standard includes resistance grounded conditions as ungrounded, the PTW arc flash module compares the single-line-to-earth value with the three-phase value to determine the grounded/ungrounded state. If the single-line-to-earth fault value is less than 5% of the three-phase value, the fault bus is considered to be ungrounded. The 5% threshold is a default value that can be adjusted.

1.4.9 Relationship Between 3-Phase Fault and Arcing Fault

The equations used to calculate the magnitude of an arcing fault are relative to the available 3-phase bolted fault current. Single-line to ground and line-to-line faults are not directly considered when calculating arcing fault or incident energy. While it’s recognized that many arcing faults are initiated by a line to ground fault, the arc flash equations in the IEEE 1584 standard are relative to the available bolted-3-phase fault current for the following reasons:

a) 3-phase faults give the highest possible short circuit energy in AC equipment. b) Arcing faults that begin as line-to-line or line-to-ground faults quickly escalate into 3-phase faults

as the air ionizes across the phases. The high-speed video photography of arc flash tests show the arc rotating between the phases and the metal box. The tests were performed on grounded and ungrounded systems and the arc fault equation includes a grounded/ungrounded variable.

Page 30: Reference ArcFlash

Arc Flash Reference Manual 1 - 29

SKM Power*Tools for Windows

1.5 PTW Applied Methodology

1.5.1 Running the Arc Flash Study You can run the Study from any screen in PTW, and it always runs on the active project.

To run the Arc Flash Study

1. From the Run menu, choose Arc Flash Evaluation.

The Arc Flash Study produces a display that the typically lists each bus in the system, protective devices that clear the arcing fault, trip times, incident energy, flash boundary and PPE clothing class. The items listed in this report are user-defined. They change be changed in the arc flash study options window.

Page 31: Reference ArcFlash

7/15/2008

1.5.2 Arc Flash Study Options The Arc Flash Options dialog box lets you select options for running the Study.

The Arc Flash Options dialog box is divided into 3 options tabs: Standard and Units, Fault Current, and Report Options.

The descriptions of the options of each tab follows: Standard and Units

Standard allows the choice of NFPA 70E, IEEE 1584, or NESC 2007 methods. If NFPA 70E method is selected, the equations published in NFPA 70E – 2004 Annex D.6 will be used to calculate the incident energy and flash boundary. If the IEEE 1584 method is selected, the equations published in the IEEE 1584 2002 and NFPA 70E – 2004 Annex D.8 will be used to calculate the arcing fault current, incident energy, and flash boundary. The IEEE 1584 method is based on more recent and expanded test data, and is the preferred method. Since IEEE 1584 method is also part of the NFPA 70E 2004, using the IEEE 1584 method could be considered as comply with NFPA 70E as well. If NESC 2007 method is selected, the tables from NESC 2007 are used to calculate the incident energy and minimum approach distance.

Page 32: Reference ArcFlash

Arc Flash Reference Manual 1 - 31

SKM Power*Tools for Windows

Flash Boundary Calculation Adjustments - The Flash Boundary is normally calculated by setting the incident energy to 1.2 cal/cm^2 and use the incident energy equation to reverse calculate the flash boundary. An option to use 1.5 cal/cm^2 for equipments above 1 kV and trip time < 0.1 seconds is provided here. This is recommended by NFPA 70E – 2004 (section 130.3 (a) page 70E-25).

An option to use equation: sqrt (2.65 * 3-Phase MVA * t) to calculate the flash boundary when the voltage level is equal or below 1 kV is also provided. Refer to NFPA 70E – 2004 Article 130.3 for more detail.

Equipment Below 240 Volts Options: Two separate list boxes are provided due to the difference in applicable voltage criteria to the location of the arcing fault in addition to Bolted Fault magnitude or upstream Transformer Size presented in IEEE 1584 and NFPA 70E standards.

- The first list box represents the Equipment Voltage range and the choices are "<= 240 V" (equal to 240 V or below) referred to NFPA 70E Std Table 130.7.(C)(9)(a), or "< 240 V" ( less than 240 V) referred to IEEE 1584-2002 Std.

- The second list box provides the following options:

- Option1: Report as Category 0 if Bolted Fault < 10 kA. Referred to Note 3 in Table 130.7.(C)(9)(a) of NFPA 70E-2004 Std.

- Option2: Report as Category 0 if Transformer Size < 125 kVA. Referred to IEEE 1584-2002 Std.

- Option3: Report as Category 0 if Bolted Fault < 10 kA or Transformer Size < 125 kVA.

- Option4: Report as Category 0 if Bolted Fault < 10 kA and Transformer Size < 125 kVA.

- Option5: Report Calculated Values From Equations. Use normal incident energy calculation methodology.

If option 1, 2, 3, or 4 is selected, and the calculated incident energy is smaller than 1.2 cal/cm^2, the calculated value will be reported and used to calculate the flash boundary. If the calculated incident energy is greater than 1.2 cal/cm^2, it will be reported as 1.2 cal/cm^2.

English or Metric Units – For NFPA 70E – 2004, IEEE 1584 - 2002 standards, or NESC 2007, we allow the choice of English or Metric units.

If the English units option is selected, the incident energy is in Calories/cm2. The working distance and flash boundary can then be in inches or feet.

If the Metric units option is selected the incident energy can then be in Joules/cm2 or Calories/cm2. The working distances and flash boundary can then be in mm, cm, or m.

Page 33: Reference ArcFlash

7/15/2008

Fault Current

Maximum Arcing Time Duration allows you to specify a maximum (Trip Time + Breaker Time) for the incident energy and flash boundary calculations. IEEE 1584 Annex B.1.2 stated that “If the time is longer than two seconds, consider how long a person is likely to remain in the location of the arc flash. It is likely that the person exposed to arc flash will move away quickly if it is physically possible and two seconds is a reasonable maximum time for calculations. A person in a bucket truck or a person who has crawled into equipment will need more time to move away.”

The default for the Maximum Arcing Duration in PTW is set to 2 seconds, if the Trip Time read from the TCC plus the Breaker Time is bigger than the Maximum Arcing Duration, the Trip Time will be set to the Maximum Arcing Duration – Breaker Time. Sound engineering judgment is always required when making reasonable arc flash energy estimates.

- Use Global Max Arcing Time: Allow user to enter different maximum arcing during for system voltage > 240 Volts and system voltage <= 240 Volts.

- Enter for each bus: When this option is selected, the user can click on the “Max Arcing Time for Each Bus” button, and “Maximum Arcing Duration for Each Bus” window will come up. See picture below.

Page 34: Reference ArcFlash

Arc Flash Reference Manual 1 - 33

SKM Power*Tools for Windows

In this window, the user can specify the maximum arcing duration for each buses in the system modeled. For convenience, the user can also sort the window by bus name, bus voltage, or maximum arcing duration by selection one of the available options button. Furthermore, user can change the maximum arcing duration of all the buses globally by clicking on the “Global Change” button. This helps in modeling your system accurately for arc flash study, since each bus location you are analyzing may have different maximum arcing duration depending on the situation.

Arcing Fault Tolerances… - For the IEEE 1584 standard, specify a low and high tolerance for arcing fault current calculations. For example, enter a –15% low and +10% high tolerances means the program will calculate two incident energies one at 0.85* arcing fault current, and another at 1.1* arcing fault current. For the NFPA 70E standard, specify the percentage of bolted fault current used to calculate the second incident energy. For example, enter a 38% bolted fault current means the program will calculate two incident energies one at 100% of the bolted fault current and another at 38% of the bolted fault current.

The arcing fault current magnitude is a function of the voltage and arc impedance. Since a small change in arcing fault current can produce substantially different trip times and incident energy, it is prudent to account for arcing fault current variability through reasonable tolerances. The IEEE 1584

Page 35: Reference ArcFlash

7/15/2008

standard uses a 15% low tolerance for arcing fault current calculations, and the NFPA 70E suggests using a 38% bolted fault current. The incident energy is calculated at the low and high tolerance specified and the largest incident energy is reported. For cases where both the low and high tolerance values result in the same trip time, the high tolerance will always produce the highest incident energy. For cases where the low tolerance results in longer trip times, which is often the case, the incident energy is typically higher at the longer trip time. In the arc flash table, the value is labeled with (*3) when the low tolerance arc fault value is used

Pre-Fault Voltage options… This button allows the user to specify the pre-fault voltage options for the short circuit study.

Load Flow Results If the Load Flow option is selected, the load flow voltage at each bus will be used to calculate the bus and branch fault current when apply a fault to the bus.

PU Voltage for All Buses If the PU Voltage for All Buses option is selected, the user can enter one single value for the per unit pre-fault voltage to be used for all bus in the system.

PU Voltage Enter for Each Bus If the PU Voltage Enter for Each Bus option is selected, the user can enter the per unit pre-fault voltage to be used at each individual bus and the per unit voltage will be used to calculate the bus and branch fault current when apply a fault to that bus. No Load with Tap If the No Load with Tap option is selected, the per unit pre-fault voltage is calculated by the program starting from the Initial Operating Voltage from the utility or Swing Bus generator. Transformer Tap and Phase Shift will be included in the calculation of the pre-fault voltage if the options are checked in the Calculation Model. This is the default option.

Fixed or Movable for Each Bus… This button brings up a window where the user can specify for each bus whether it is defined as "Fixed" circuit part or "Movable" conductor. The will affect the shock limited approach boundary reported by the arc flash label. A bus defined as "Movable" will have a higher limited approach boundary than a "Fixed" bus. For convenience, the user can also sort the window by bus name, bus voltage, or by "Fixed/Movable" selection options. Furthermore, the user can change the Fixed/Movable" selection of all the buses globally by clicking on the "Global Change" button.

Page 36: Reference ArcFlash

Arc Flash Reference Manual 1 - 35

SKM Power*Tools for Windows

Transformer Tap If this box is unchecked, all transformers appear without the effect on any taps, and the pre-fault voltage is relative to the swing bus voltage. By selecting Transformer Tap, PTW calculates the system pre-fault no load voltage profile based on the swing bus voltage and transformer tap settings. You must check this box to analyze transformer off nominal voltages properly.

Transformer Phase Shift By default, PTW does not include Transformer Phase Shift, the transformer phase shift angle remains at 0°, and the pre-fault voltage angles in each isolated area of the power system remain at the swing bus voltage angle. To report unbalanced circuit branch flows, select the Transformer Phase Shift check box. This option calculates each transformer phase shift in degrees based on the transformer connection type; the pre-fault voltage angle includes all transformer phase shifting relative to the swing bus.

Defined Ground as SLG/3P Fault in % - enter the single line to ground fault current / 3-phase fault current at the bus in percentage. If the calculated SLG / 3P fault current at the bus is higher than the value specified by the user, the bus is considered grounded. IEEE 1584 recommended different incident energy equation parameters based on whether a bus is grounded or not.

Reduce Generator / Synchronous Motor Fault Contribution To – Generators and synchronous motors do not supply the same amount of fault current after a certain number of cycles following the fault. For example, the fault current may be reduced from the initial 1000% of the Rated Current (10 per unit) to 300% after 10 cycles. Enter the percentage of the Rated Current and the number of cycles after which to reduce the fault current to. PTW assumes a step change from the initial fault current to the reduced value and incident energy will be calculated using the initial fault current and the number of cycles specified, then accumulated with rest of the incident energy calculated using the reduced fault current and the duration at which the protective device trips. The Apply To Generator check box controls whether the reduction of contribution should be applied to generators. If unchecked, generator contribution will be the same as the initial fault for the entire arcing duration. Similarly, the Apply To Synchronous Motors check box controls whether synchronous motor contribution should be reduced after the number of cycles.

Recalculate Trip Time using Reduced Current – use the decayed fault current from the Generators and synchronous after the number of cycles to recalculate the trip time and calculate the incident energy.

Below is description on how "Apply to Generators/Synchronous Motor” check boxes works in conjunction with “Recalculate Trip Time Using Reduced Current” checkbox.

If "Apply to Generators/Synchronous Motor” check box is checked and the “Recalculate Trip Time Using Reduced Current” is unchecked

� PTW uses the initial arcing fault current up to the specified number of cycles to determine the first accumulation of incident energy.

� If the protective device protecting the generator did not operate, the current is reduced

using the new bolted fault current value that corresponds to 300% of the generators FLAs.

� From that, a new arcing fault current is calculated and is used to determine the second

accumulation of the incident energy. Note that for this option, the assumption is that protective device protecting the generator will start to operate at the first current it sees. So the time used for the second portion of the accumulation is the calculated trip time from the initial current minus the number of cycles specified.

Page 37: Reference ArcFlash

7/15/2008

� PTW adds the two incident energy values to get a total accumulated energy.

If " Apply to Generators/Synchronous Motor” check box is checked and the “Recalculate Trip Time Using Reduced Current” is checked

� PTW uses the initial arcing fault current up to the specified number of cycles to determine the first accumulation of incident energy.

� If the protective device protecting the generator did not operate, the current is reduced using the new bolted fault current value that corresponds to 300% of the generators FLAs.

� From that, a new arcing fault current is calculated and is used to determine the new tripping time. To determine the second accumulation of the incident energy, the new arcing current is used along with the remaining time (new tripping time minus the number of cycles specified).

� PTW adds the two incident energy values to get a total accumulated energy.

� This option assumes that the protective device protecting the generator did not operate on the initial current.

Note also the following:

o Arc Flash Study Option "Apply To Generators" option is enabled only if there are energized generators in the system.

o Arc Flash Study Option "Apply To Synchronous Motors" option is enabled only if there are energized Synchronous Motors in the system.

o "Recalculate Trip Time Using Reduced Current" option will be enabled only if the "Apply To Generators" and/or "Apply To Synchronous Motors" options are checked.

Induction Motor Fault Contribution – Specify the number of cycles to include the induction motor contributions. PTW assumes a step change from the initial fault current with induction motor contributions to the reduced fault current without induction motor contributions. To include induction motors all the time, enter a large value as the cycles. To ignores all induction motor fault contributions from the arcing fault current and the incident energy calculations, enter 0 cycles. You can enter a specific induction motor hp size and check or uncheck the Exclude if <??? hp independently to exclude motors less than the given hp.

Notice that while ignoring motor contributions reduces the fault current value, it may increase the trip time and result in higher incident energy.

Page 38: Reference ArcFlash

Arc Flash Reference Manual 1 - 37

SKM Power*Tools for Windows

Fuses treated as "All Current Limiting, All Standard Fuses, or Specified in Library" When "All Standard Fuses" is selected, the arc duration is read from the total clearing curve at the arcing fault current for all fuses in the project. If the fault current is above the 0.01sec crossing point then 0.01 seconds is used as the trip time. The IEEE 1584 or NFPA 70E standard equation and calculated tripping time are used to calculate incident energy.

When "All Current Limiting Fuses" is selected, the arc duration is read from the total clearing curve when the arcing current is below the current-limiting threshold (below the 0.01sec crossing point). When the arcing current exceeds the current-limiting threshold (above the 0.01sec crossing point) the trip time is reduced to either ½ or ¼ cycle based on the amount of current.

When "Specified in Library" is selected, (recommended option) the software will check the “Current Limiting” checkbox and “Use Arc Flash Equation” checkbox in the library to determine if a device is current limiting or not. The incident energy calculation will be based on its findings. If the "Use Equipment Specific Arc Flash Equation in Protective Device Library" check box is not checked and/or no equation is entered in the Arc Flash page, then the IEEE 1584 or NFPA 70E standard equation will be used with the trip time reduced to ½ or ¼ cycles.

Arc Flash Equations for Breakers and Fuses. "Use Equipment Specific Arc Flash Equation in Protective Device Library"

If this check box is checked, all the devices that have:

• The " Use Arc Flash Equation " check box checked

• Manufacturer’s/tested equations entered in the Arc Flash tab of the specific library file

• Fault current is in the range of the equations

The software will calculate the incident energy based on these equations. Otherwise, for the case of breakers, the IEEE 1584 or NFPA 70E standard equation will be used and calculated tripping time are used to calculate incident energy. For the case of Fuses, the trip time will be reduced to ½ or ¼ cycles if current limiting conditions are satisfied. This option is not available if ‘All Standard’ is chosen in the option above (Treat fuses as).

Page 39: Reference ArcFlash

7/15/2008

If the manufacturer’s equations are entered in the Arc Flash page, PTW will use these equations instead of the standard incident energy equations from the IEEE 1584 or NFPA 70E. If no manufacturer’s equipment-specific equations are entered or could be matched with the cartridge and bolted fault current range, the fuse will be treated as a current limiting fuse without using the manufacturer’s equations.

If the "Current Limiting…" check box in the library is unchecked and the "Specified in Library" option is selected, the fuses will be treated as standard fuses without having the current limiting feature.

For breakers, manufacturers could also provide equipment-specific equations to represent faster trip time when the fault current reach a certain level, but they are not current limiting in nature.

For all current limiting fuses and breakers, if the trip time of the TCC clearing curve at the branch arcing fault current is less than ½ cycles, and the curve is defined below 0.01 seconds, the defined clearing time is used. Otherwise, the arcing fault current (Ia) is compared to the current (IL) where the total clearing curve drops below 0.01 seconds, and the trip time is based on the following table:

Trip/Delay Time (Tr) Condition

Read from clearing curve Ia < IL

1/2 cycle IL < Ia < 2 IL 1/4 cycle Ia > 2 IL

Page 40: Reference ArcFlash

Arc Flash Reference Manual 1 - 39

SKM Power*Tools for Windows

For fuses with only the average melting time curve available, and the time read from the average melting curve at the arcing fault current Trips less or equal to 0.03 seconds, add 15% to Tr. If Tr is above 0.03 seconds, add 10% to determine the total clearing time. If the arcing fault current is above the total clearing time at the bottom of the curve (0.01 seconds), use 0.01 seconds for the time. (IEEE_P1584/ 4.6 Step5)

The protective device library alternatively allows you to enter current limiting equations for fuses at each bolted fault current range. Arc Flash uses these equations to calculate the Incident Energy and Flash Boundary instead of the standard IEEE1584 equations.

Equipment-Specific Incident Energy Equations on the Arc Flash Tab - If manufacturers of low voltage breakers have their equipment-specific incident energy equations published, these equations can be entered in the Arc Flash tab of the Protective Device Library. The user must check the "Use Equipment-Specific Incident Energy Equations on the Arc Flash Tab" check box in order for the equations to be used in the Arc Flash calculations.

If the "Use Equipment-Specific Incident Energy Equations on the Arc Flash Tab" check box is checked, but no equation on the Arc Flash tab has a bolted fault current range that covers the calculated bolted fault current through the device, the Equipment-Specific equation will not be used. Instead, the device will be treated as current limiting a the following way:

If the trip time of the TCC clearing curve at the branch arcing fault current is less than ½ cycles and the curve is defined below 0.01 seconds, the defined clearing time is used. Otherwise, the arcing fault current (Ia) is compared to the current (IL) where the total clearing curve drops below 0.01 seconds, and the trip time is based on the following table:

Trip/Delay Time Condition Read from clearing curve Ia < IL

1/2 cycle IL < Ia < 2 IL 1/4 cycle Ia > 2 IL

Page 41: Reference ArcFlash

7/15/2008

Report Option

Three different report options are available. The report options are named Bus, Protective Load Side, and Protective Line Side. The Bus report is the normal selection however the load side and line side reports may be useful in specific situations. Refer to the following diagram and descriptions.

MCC

Line Side

Load Side

XXXX

XXXX

MCC

M1-Bus

T1

UTIL-0001

C1

Main Bkr

B1

M1

M2 M3 M4 M5

B2 B3 B4 B5

R1

Page 42: Reference ArcFlash

Arc Flash Reference Manual 1 - 41

SKM Power*Tools for Windows

- Bus option – The bus report assumes that the fault occurs at the equipment bus. If the bus has multiple contributions, the devices that trip each branch contribution will be listed in the order they trip, and incident energy will be accumulated until a significant percentage of the fault current has tripped. The significant portion is defined by the “Cleared Fault Threshold” percentage you specify.

- Protective Device Load Side option – The load side report applies a fault at the load side (To End) of each protective device whose line side (From End) is connected directly to a bus without having an impedance device between the bus and the protective device. The protective device being evaluated is the one that clears the fault. The fault current through the device will be used to calculate the arcing fault current and obtain the trip time from the TCC. You can then select to include Line + Load Sides Contributions (to represent both ends hot) in calculating the incident energy, or to include Line Side Contributions only in which case the load side contributions are not included (now working as if the load side is disconnected).

- Protective Device Line Side option – The line side report applies a fault at the line side (From End) of each protective device whose load side (To End) is connected directly to a bus without having an impedance device between the bus and the protective device. You can then selected to include Line + Load Sides Contributions or to include Line Side Contributions only. The first case represent both ends hot, this occur if the main breaker failed to open, and the next upstream device is the one that must clear the fault. If there is more than one contribution when there is a fault at the line side, incident energy will be accumulated up to the fault contribution percentage specified. If Line Side Contributions Only is selected, the load side contributions are not included and it is now working as if the load side is disconnected.

Note: In the above discussion of Load Side (To End) and Line Side (From End),we assumed that the power flows from the From End to the To End. If the direction of power is opposite to our assumption, the devices that would be listed in the Load Side report under normal power flow direction will be listed in the Line Side report instead.

- Bus + Line Side option – This option combines the bus report option and the line side report option into one report. Calculated result for the bus and line side will be listed next to each other for easier comparison of worse case scenario. A special custom label is supplied by PTW to put both bus and line side results in one single label.

Include Line + Load Sides Contributions

- If you select “Include Line + Load Sides Contributions”, software will then include Line + Load Sides Contributions (to represent both ends hot) in calculating the incident energy.

- If you select “Include Line Side Only”, the software will include Line Side Contributions only in which case the load side contributions are not included (now working as if the load side is disconnected).

Page 43: Reference ArcFlash

7/15/2008

Report Last Trip Device vs. Report Main Device – This option is applicable for the Bus Report option only and it affects the device reported in the Summary View, Bus Detail and Bus Label. The last trip device is defined as the protective device that would trip last, when the percentage of fault current cleared reaches the Cleared Fault Threshold. The “Main Device” is the one that carries the biggest percentage of the fault current contributing to the bus.

• Report Last Trip Device If this option is selected, in Detailed View, the highlighted device is the one that meets the percent threshold (Last Trip Device). In Summary View, Bus Detail, and Bus Label, this device, along with its corresponding values in the Detailed View will be reported.

• Report Main Device If this option is selected, in Detailed View, the highlighted device is the one that carries the biggest percentage of the fault current contribute to the bus (Main Device). In the Summary View, Bus Detail, and Label this “Main Device” will be reported. However note that the incident energy, flash boundary, and other fields from the detailed view will be reported based on the last trip device.

Check Upstream devices for mis-coordination, evaluates trip times for backup protective devices beyond the branch containing the first protective device. Two conditions must be satisfied for the upstream backup protective device to be reported instead of the immediate protective device:

Condition 1: The immediate protective device must carry 5% or more of the Cleared Fault Threshold value (default as 80%) multiplied by the total bus fault current.

Condition 2: The upstream backup protective device must trip faster and carry a fault current that is bigger or equal to the Cleared Fault Threshold value multiplied by the fault current through the immediate device.

Upstream mis-coordination is checked by branch, all devices within the branch containing the immediate protective device will be evaluated and the fastest one will be used to compare with the fastest device in the upstream branch. If the first valid protective device is found in an upstream branch and the trip time is slower than the immediate device, the search stops there and the immediate device will be reported.

The definition of a valid device is one with a trip curve that is not a Ground Fault type and the protection function name does not include "Ground", "Earth", "Neutral" or "AF_EX".

If the upstream mis-coordination is not checked, all devices within the branch containing the first protective device will still be evaluated, and the one with the fastest trip time will be used in the Arc Flash calculation.

Upstream Levels to Search The number entered here determines the number of additional branches, consisting of a protective device or a set of protective devices that are away from the first protective device protecting the faulted bus, that the software will search for mis-coordination. This will greatly help when doing coordination and arc flash study to see if any of the protective devices several braches away from the fault are mis-coordinated with the protective device next to the faulted bus.

Label Options Default Label # Prefix - This allows the user to specify the default prefix character that will go on the "Label #" column in the Arc Flash spreadsheet report. This field can help in sorting out (organizing) the label when they printed out. Note that if a bus already has a label prefix assigned, changing the default label prefix will not change the label prefix already assigned to that bus. The Default Label # Prefix will only be assigned to buses newly created in the project.

Page 44: Reference ArcFlash

Arc Flash Reference Manual 1 - 43

SKM Power*Tools for Windows

Cleared Fault Threshold determines the portion of the Total Arcing Fault current at the Bus that needs to be interrupted by protective devices to extinguish the arc. Therefore the remaining portion of Arcing Fault current, if any, can not sustain the arc and will not be considered in the accumulated incident energy. Enter a value in percent of the total bus fault current, the default value is 80%, which means that the final arc fault trip time is based on when 80% or more of the total fault current at the bus has been cleared. In the Summary View, the last device to trip that reaches the cleared fault threshold is the only protective device that will be listed under the bus, and the data from the device will be used in the Bus Detail report and Bus Label. The cleared fault threshold value is also used to determine which branches are searched for mis-coordination.

There isn't any recommendation in the NFPA or IEEE1584 for the "Fault Clear Threshold". But the assumption comes from the fact that when certain percentage of fault (like 80%) is interrupted by the protective devices then the remaining bolted/arcing fault percentage/current can not sustain the arc and naturally can not be added to the accumulated energy. Since the last 5% - 15% of the contribution may take a very long time to trip (a small current takes a long delay time), then it is not practical to accumulate the energy up to 100%, because the calculated incident energy would be much bigger than reality. If the user is setting a "Maximum Protection Trip Time" in the Arc Flash Options to a realistic number (2 second for example), then the "Fault Clear Threshold" becomes less of an issue, the user could set it to 100% and we will only accumulate the energy up to 2 seconds anyway.

Auto Update Arc Flash Results When this checkbox is checked, the software will automatically update the arc flash results whenever there is a change in the system model. For instance, when user open up a tie-breaker or change the size of a motor in the system model, the software will automatically update the arc flash results based on those changes. The user would not need to re-run the arc flash study.

Increase PPE Category by 1 for high marginal IE When this checkbox is checked, the software will automatically increase the arc flash PEE category results by 1 whenever the incident energy calculate is greater than the high marginal value set in the PPE table.

Additional Incident Energy and Flash Boundary… This button brings up a dialog box that allows the users to enter additional working distances for PTW to calculate the incident energies.

Page 45: Reference ArcFlash

7/15/2008

This information could be used to determine the PPE required at the given additional working distance. You can also specify five incident energies for PTW to calculate the flash boundaries. This information could be used to determine the distance from exposed live parts within which a person could receive a 2nd degree burn for the given additional incident energy. The additional working distances and the calculated incident energies and PPE at each bus could be displayed in the datablock and the data fields are available in the Custom Label Designer. The incident energies entered and the calculated flash boundaries are also available in the datablock and Arc Flash Label.

The Custom Label Designer allows individual data fields to be selected and placed in the desired locations.

Page 46: Reference ArcFlash

Arc Flash Reference Manual 1 - 45

SKM Power*Tools for Windows

Shock Approach Boundary… This button brings up a window that will allow the user to customize the Shock approach boundary table.

Page 47: Reference ArcFlash

7/15/2008

This window allows the user to customize the Shock approach boundary table. Note that the voltage range is in unit of voltage and boundaries are in units of inches.

The Shock Approach Boundaries Table information is project specific. (It will look in the information from the “ShockBoundary.ss6” file located in the project's directory).

For new projects created, it will copy and use the “ShockBoundary.ss6” file information from the LIB directory (specified in the miscellaneous files options group).

If there is no “ShockBoundary.ss6” file existing in the project directory currently opened, it will copy and use the ShockBoundary.ss6 information from the LIB directory (specified in the miscellaneous files options group).

If there is no “ShockBoundary.ss6” file existing in the LIB directory, it will copy and use the “ShockBoundary.ss6” file in the Bin directory of PTW32.

Add Row This button lets you insert a row in the table.

Save As Default If you had customized this table and want to keep the changes as your default, use the "Save As User Default" button. This will save the changes you’ve made to the “ShockBoundary.ss6” file in the LIB directory (specified in the miscellaneous files options group).

Reset Default If you make changes to this table and don’t want to keep them, use the Reset button to re-store the defaults from ShockBoundary.ss6 file in the LIB directory (specified in the miscellaneous files options group).

Report Data and Order… This button brings up a window that will allow the user to specify which of the twenty available fields will be displayed in the Arc Flash spreadsheet report. Furthermore, the user can also specify the order in which they will appear in the Arc Flash spreadsheet report.

Page 48: Reference ArcFlash

Arc Flash Reference Manual 1 - 47

SKM Power*Tools for Windows

For instance, if you don’t want to show the equipment type, you can simply uncheck the display checkbox next to that field. If you want the “Bus kV” field to show up on the first column, you can just type in the number “1” in the column order next to that field and the bus voltage will them show up on the first column of the report.

The following are the meaning of those fields:

Bus Name: Fault location for bus report. For line side and load side report options the bus refers to the equipment where the line side and load side protective devices are connected.

Protective Device Name: Refers to the protective device that clears portion or total of the arcing fault current.

Bus kV: Bus voltage at the fault location.

Bus Bolted Fault: The current flowing to a bus fault that occurs between two or more conductors or bus bars, where the impedance between the conductors is zero.

Bus Arcing Fault: The calculated arcing current on the bus.

Prot Dev Bolted Fault: The portion or total of the bolted fault current, that flows through a given protective device.

Prot Dev Arcing Fault: The portion or total of arcing current flowing through each protective device feeding the electric arc fault. Note that the total arc fault current may flow through several parallel sources to the arc location.

Trip/Delay Time: The time required for the protective device to operate for the given arcing fault condition. In the case of a relay, the breaker opening time is entered separately from the relay trip time. For

Page 49: Reference ArcFlash

7/15/2008

low voltage breakers and fuses, the trip time is assumed to be the total clearing curve or high tolerance of the published trip curve.

Breaker Opening Time: The time required for a breaker to open after receiving a signal from the trip unit to operate. The combination of the Trip/Delay time and the Breaker Opening time determines the total time required to clear the fault. For low voltage circuit breakers, the total clearing time displayed on the Manufacturer’s drawing is assumed to include the breaker opening time.

Ground: Indicates whether the fault location includes a path to ground. Systems with high-resistance grounds are assumed to be ungrounded in the Arc Flash calculations.

In Box: Identifies whether the fault location is in an enclosure or in open air. In open air the arc energy will radiate in all directions whereas an enclosure will focus the energy toward the enclosure opening. The In Box / Air selection is available when the NFPA 70E study option is selected. For the IEEE 1584 study selection the In Box or In Air is determined automatically from the Equipment Type specification.

Equip Type: Used only in the IEEE 1584 method to indicate whether the equipment is Switchgear, Panel, Cable or Open Air. The equipment type provides a default Gap value and a distance exponent used in the IEEE incident energy equations.

Gap: Defines the spacing between bus bars or conductors at the arc location.

Arc Flash Boundary: The distance from exposed live parts within which a person could receive a 2nd degree burn.

Working Distance: The distance between the arc source and the worker’s face or chest.

Incident Energy: The amount of heat energy on a unit of surface at a specific distance from the location of arc flash.

Required FR Clothing Category: Indicates the Personal Protective Equipment (PPE) required to prevent an incurable burn at the working distance during an arcing fault.

Label #: This allows the user to specify the prefix character that will go on the “Label #” column in the Arc Flash spreadsheet report. This field can help in sorting out (organizing) the label when they printed out.

Cable Length From Trip Device: Reports the total cable length from the protective device that trips to clear the fault to the faulted bus. If there is no cable in between, nothing will be reported.

Incident Energy at Low Marginal: This will report an incident energy value of the bus, if the incident energy on the bus meets the low marginal criteria value entered in the PPE.

Page 50: Reference ArcFlash

Arc Flash Reference Manual 1 - 49

SKM Power*Tools for Windows

Incident Energy at High Marginal: This will report an incident energy value of the bus, if the incident energy on the bus meets the high marginal criteria value entered in the PPE.

Re-arrange The purpose of this button is to prevent user from having duplicate column number when they are re-ordering the fields manually. Furthermore, it there is any missing columns (columns chose not to be displayed) it will use the number after the missing column.

Reset The purpose of this button is to reset the order of the table to its default setting.

Page 51: Reference ArcFlash

7/15/2008

Accumulated Energy The concept of accumulated energy is based on conditions where parallel contributions feed a single fault location. Referring to the following diagram, a fault at Bus MCC1 is fed from three parallel contributions (Utility, Generator, Motor). Each contribution will trip at a different time and the worker will be exposed to a varying amount of energy as each branch trips.

Trips in 0.5 Sec.

(6kA Arcing Fault)

Fault

Location

Trips in 0.07 Sec

(14kA Arcing Fault)

Trips in 39 Seconds

(0.9 kA Arcing Fault)

Motor Contribution

Decays within first

6 cycles

MCC1 Bus

C1

U1 G1

C2

C3

M1

Utility Fuse

LVB3

Generator Fuse

LVB1 LVB2

For this example, the worker is exposed to all three contributions for the first 0.07 seconds, the motor and generator for the next 0.03 seconds, and the generator contribution by itself for another 0.4 sec.

Page 52: Reference ArcFlash

Arc Flash Reference Manual 1 - 51

SKM Power*Tools for Windows

The Arc Flash study reports the accumulated energy from all three contributions. If the Utility had been the only significant contribution, the energy would have been accumulated only for the first 0.07 seconds, the time when the utility contribution was cleared. In this case, the utility is 67% of the total and the generator contribution was 28% of the total. Therefore both the utility and generator were both determined to be significant contributions as defined by the 80% “Cleared Fault Threshold” percentage specified. Both the Utility and the Generator must trip before the 80% Cleared Fault Threshold is reached.

Page 53: Reference ArcFlash

7/15/2008

Detail View versus Summary View

The detail view in the arc flash report lists all parallel contributions and the accumulated energy as each contribution is cleared. The summary view lists only the last branch that clears the significant contribution as defined by the “Cleared Fault Threshold” percentage specified. In the following example, 3 parallel branches contribute current to the fault.

Arcing Fault7.76 kA

Arcing Fault2.24 kA

Arcing Fault0.67 kA

Gen-Bus

UTIL

TX1

GEN

C1

M1

R-Util

R-Gen

R-M1

The Detail View for the bus report lists all 3 contributions, the trip time for each branch, and the cumulative energy when each branch clears. For this example, the Utility Contribution clears in 0.234 seconds, the Generator Contribution clears in 1.12 seconds, and the Synchronous Motor clears in 5.57 seconds (assuming no AC decay), but displays the 2 second maximum time specified in the study setup. When the Utility branch clears, the incident energy is 2.83 cal/cm2 (Class 1). When the Generator Branch clears 0.68 seconds later, the accumulated energy is 4.91 cal/cm2 (Class 1).

The Utility contribution is 73% and the generator is 21% of the total arcing fault current at Gen-Bus. With the Cleared Fault Threshold option set to 80%, the Summary display and Labels will report the energy accumulated up to the time when at least 80% of the total fault current is cleared. This occurs when the Generator contribution is cleared. The Summary View lists only the generator branch since when the generator trips, 94% of the fault current has cleared.

Page 54: Reference ArcFlash

Arc Flash Reference Manual 1 - 53

SKM Power*Tools for Windows

Selecting Buses for Display in Arc Flash Report

By default, all buses are displayed in the arc flash report. To display only selected buses, use the Query or Go-To functions as described below:

Go-To-Arc Flash

From the one-line diagram, select the buses you want to display and use the Window > Go-To-Arc Flash menu item (or use the Right Mouse Button menu). The Go-To-Arc Flash option will open the Arc Flash report and list only the bus or buses selected on the one-line.

Query

Alternatively, you can display selected buses by using a query. For example, you can query on buses where the voltage is equal to 480 Volts. To run a query, select the Run Query Menu. Refer to the on-line help, PTW Tutorial or PTW Users Guide for more information on creating new queries.

Page 55: Reference ArcFlash

7/15/2008

Minimum and Maximum Faults

It’s important to consider both minimum and maximum fault conditions when performing arc flash calculations. The reason why both are important is illustrated below:

0 .5 1 1 0 1 0 0 1 K 1 0 K 1 0 0 K0 .0 1

0 .1 0

1

1 0

1 0 0

1 0 0 0

C U R R E N T IN A M P E R E S

tc c 3 . t c c R e f . V o lta g e : 4 8 0 V C u r r e n t in A m p s x 1 @ 4 8 0 V t c c 3 .d rw

TIM

E IN

SE

CO

ND

S

P a n e l M a inP a n e l M a in

Notice on the TCC drawing above that for a maximum arcing fault that the trip time remains in the instantaneous trip region (0.05 seconds). Using a smaller minimum fault current and lower pre-fault voltage results in a lower fault current that takes slightly more than one second to trip (4.195 seconds). Using the maximum fault current, the incident energy is 1.6 J/cm2 resulting in a Class 0 FR Clothing Class. Using the minimum fault current, the incident energy is 110 J/cm2 resulting in a Class 4 FR Clothing Class. For this case, the lower fault current results in a longer trip time producing higher incident energy exposure to the worker. Making conservative assumptions regarding both the minimum and maximum fault currents will provide higher certainty in specifying the proper clothing class and selecting conservative protective device settings.

Trip time of 4.195 seconds for Min Fault

Minimum arcing fault current

Trip time of 0.05 seconds for Max Fault

Maximum arcing fault current

Page 56: Reference ArcFlash

Arc Flash Reference Manual 1 - 55

SKM Power*Tools for Windows

In the Arc Flash Module, users have the ability to show both the minimum and maximum fault conditions current. To do this the users could select on the device they are interested in on the TCC and then right-mouse click, and then select “Selected Device Setting” option. Select the Arcing Fault and UDF Flags tab and a similar window will appear.

In this window, the user has two options to show the arcing fault flag on the TCC.

The first option is to show user-defined arcing fault current flags on the TCC by checking the “Show User Defined Flags” check box and filling in current 1 and current 2 fields.

The second option is let the software automatically use the calculated arcing current from the study based on a selected bus. Here, the user can check on the “Show Arcing Fault current for Worse case Incident energy” and/or ”Show None-Worse Case Arcing Fault Current ” check boxes. Also make sure to select a bus that will be faulted for the calculation of the arcing fault currents.

If user-defined option is selected, the arcing fault current flags are represented by vertical dotted lines.

If study result is selected as the flag, the fault arcing current for worse case incident energy (normally 85% of calculated arcing current) is represented by a solid vertical line.

The other arcing fault current (normally 100% of the calculated arcing current) is represented by dot-dashed line on the TCC.

User Defined Arcing Fault

Arcing Fault Flag based on calculations

Page 57: Reference ArcFlash

7/15/2008

0 .5 1 1 0 1 0 0 1 K 1 0 K 1 0 0 K0 .0 1

0 .1 0

1

1 0

1 0 0

1 0 0 0

C U R R E N T IN A M P E R E S

tc c 3 . tc c R e f . V o lta g e : 4 8 0 V C u r re n t in A m p s x 1 @ 4 8 0 V t c c 3 .d rw

TIM

E IN

SE

CO

ND

SP a n e l M a inP a n e l M a in

In the “Arcing Fault UDF Flag” tab, the user could also chose to plot the constant incident energy line (C-Line) on the TCC. Constant incident energy line (C-Line) is a sloped line on a TCC that describes the relationship of a finite series of time and current combinations for which energy remains constant. For buses or system with single source of contribution, this C-Line can then be used as an aid in overcurrent device coordination to demonstrate visually which setting regions might be adjusted to reduce the arc flash hazard.

Worst Case (85%) arcing fault current

Other (100%) arcing fault current

Page 58: Reference ArcFlash

Arc Flash Reference Manual 1 - 57

SKM Power*Tools for Windows

In this window, the user has two options to show constant incident energy line (C-Line) on the TCC.

The first option is to show a user-defined C-line on the TCC by checking the “Show User Constant Category Line or User Define C-line” check box. Here, the user can then enter in two line and current points, and the software will plot the line between these two points to represent a C-line.

The second option is to let the software automatically draw C-lines representing PEE Category 0 to Category 5. To do this, the user can simply check the “Category C-lines” check box.

C a te g o r y 0

C a te g o r y 1

C a te g o r y 2

C a te g o r y 3

C a te g o r y 4

0 .5 1 1 0 1 0 0 1 K 1 0 K 1 0 0 K0 .0 1

0 .1 0

1

1 0

1 0 0

1 0 0 0

C U R R E N T IN A M P E R E S

tc c 3 . t c c R e f . V o lta g e : 4 8 0 V C u r r e n t in A m p s x 1 @ 4 8 0 V tc c 3 .d r w

TIM

E IN

SE

CO

ND

S

P a n e l M a inP a n e l M a in

The C-lines on the example above represents the top incident energy range of each PPE category per NFPA 70E standard PPE table. As can be seen from the plot above, the 4.195 seconds time at the minimum fault current is above the Category 3 C-line. It falls between the Category 3 and Category 4 C-line. Therefore, we can tell visually from the TCC that the resulting incident energy will be in the PPE Category 4 region. Note that the constant category lines are accurate for buses or system with single contribution only.

Worst Case (85%) arcing fault current @ 4.195 seconds.

Page 59: Reference ArcFlash

7/15/2008

1.5.3 Determining Trip Time The protective device arcing fault current is used to determine the trip time for both IEEE 1584 and NFPA 70E Methods within the specified range of voltage and available fault current.

Ground Fault devices are not included. For multi-function devices, only the trip time of the first function is checked. Functions named Ground, Earth and AF_EX are excluded.

The clearing time is used for trip curves that have a tolerance.

R-Main

F-Util

R-Main

Arcing Fault

Trip TimeFor Fuse

Trip TimeFor Relay

0.5 1 10 100 1K 10K0.01

0.10

1

10

100

1000

CURRENT IN AMPERES

TIM

E IN

SE

CO

ND

S

The trip time for all devices in a branch are checked. The device with the fastest trip time for the arcing fault current is used.

Page 60: Reference ArcFlash

Arc Flash Reference Manual 1 - 59

SKM Power*Tools for Windows

Relay R3,

Breaker CB3,

and Fuse FTXC

are in the

Same Branch and

are All Checked

for Trip Time.

Ground Fault

Relay is Not

Checked

C1

CB3

R3

F TX C

R3-G

003-HV SWGR

004-TX B PRI

The trip time for the first upstream backup device is checked for primary contributions. Only the first backup device is checked and only if the branch fault current is significant.

Arcing Fault0.67 kA

Arcing Fault2.24 kA

Arcing Fault7.76 kA

XFault Location

Primary Protection

Backup Protection Trip Time for Upstream Backup Protection is checked when the arcing fault current through the backup device is at least the Cleared Fault Threshold % of the current through the primary device, and the arcing fault current through the main protective device is at least 50% of the Cleared Fault Threshold % of the bus fault current.

For a Cleared Fault Threshold of 80%, R-Main sees 7.76 kA (72% of the total) and F-Util sees 7.76 kA (100% of R-Main). F-Util is checked for mis-coordination with R-Main, since R-Main sees more than 40% (80%/2) of the total and F-Util sees more than 80% of the current in R-Main.

Gen-BusArc Fault 10.7 kA3.9 Cal/cm^2@ 36 inchesClass 1 PPE

UTIL

TX1

Util-Bus

GEN

C1

M1

R-Main

R-Gen

R-M1

F-Util

Note: In the above discussion, the checkbox “Check Upstream devices for mis-coordination” is assumed unchecked, which is the default. If the checkbox “Check Upstream devices for mis-coordination” is checked, the software will valuates trip times for backup protective devices beyond the branch containing the first protective device. How far beyond is determine by the number entered in the “Upstream Levels to Search” field.

Page 61: Reference ArcFlash

7/15/2008

1.5.4 Current-Limiting Devices There are two common methods to approximate current-limiting devices in Arc Flash calculations:

1) Use faster clearing times to conservatively simulate current-limiting devices when the arcing fault current is in the current-limiting range;

2) Use empirical equations from equipment tests to calculate incident energy and flash boundaries.

Note that it is difficult to determine where the current-limiting range begins. Published data assumes a specific X/R ratio, whereas your system X/R may be different. The dynamic X/R seen under an Arcing Fault condition further complicates the issue. PTW assumes that the current limiting range begins at X, where the clearing curve of the protective device crosses 0.01 seconds.

Fuse

0.5 1 10 100 1K 10K0.01

0.10

1

10

100

1000

CURRENT IN AMPERES

TIM

E IN

SE

CO

ND

S

0.5 1 10 100 1K0.01

0.10

For arcing fault currents greater than X but less than 2X, the ½ cycle clearing time is used. For arcing fault currents 2X and larger, a ¼ cycle clearing time is used.

Alternatively, the trip curves can be extended below the 0.01 second when data is published.

Current Limiting Range

X 2X

Clear in ¼ cycle

Clear in ½ cycle

Page 62: Reference ArcFlash

Arc Flash Reference Manual 1 - 61

SKM Power*Tools for Windows

For current-limiting devices with published empirical equations for incident energy and flash boundary calculations, the equation parameters can be defined in the library as a function of bolted fault current.

Note that in this window, the “Current From” column could be a function of kA, multiple of Frame Size, or Multiple of Sensor/Trip size.

The Arc Flash Study Options menu controls how current-limiting fuses are treated in the calculations. Current-limiting effects for circuit breakers must be defined in the library by extending the clearing times below 0.01 seconds, or by entering the empirical equations for the current-limiting device. A choice to represent all fuses as current-limiting, standard, or as specified in the library is available.

Page 63: Reference ArcFlash

7/15/2008

0.5 1

1

10

10

100

100

1K

1K

10K

10K

0.01 0.01

0.10 0.10

1 1

10 10

100 100

1000 1000

CURRENT IN AMPERES

TIME IN SECONDS

PD-0001PD-0001

UTIL-0001Isc 3P 1000 A

CBL-0001Isc 3P 1000 A

PD-0001

BUS-0002

Isc 3P 1000 A

TCC: tcc1 Current Scale Ref. Voltage: 480V Current in Amps x 1 Reference Voltage: 480 May 7, 2008

Using the one-line and TCC above as an example, let us run Arc Flash with “Specified in Library” options selected and checkbox “Use Equipment-Specific Arc Flash Equation in Protective Library”.

Page 64: Reference ArcFlash

Arc Flash Reference Manual 1 - 63

SKM Power*Tools for Windows

Also, for simplicity, for this example, the data entered in the Arc Flash tab for the fuse is the following:

From the TCC above, a fault current of 1000 Amp seen by the fuse would produce 0.92 kA arcing current. Also, by visual inspection, the current limiting range (the current that crosses 0.01 seconds on the fuse curve) would start at around 3.0 kA. Since the arcing current for this case is below the current limiting range, the trip time that would be used will be the one from the fuse curve at around 46 seconds. The software will used 2.0 seconds, since 2.0 seconds is what is set as the maximum arcing duration for this example. This would then result in 6.5 cal/cm^2 incident energy. See arc flash result below.

Page 65: Reference ArcFlash

7/15/2008

Now, for the same case above if we increase the fault current on “Bus-0002” to 8.0 kA. The new TCC and arc flash are now below.

0.5 1

1

10

10

100

100

1K

1K

10K

10K

0.01 0.01

0.10 0.10

1 1

10 10

100 100

1000 1000

CURRENT IN AMPERES

TIME IN SECONDSPD-0001PD-0001

UTIL-0001Isc 3P 8000 A

CBL-0001Isc 3P 8000 A

PD-0001

BUS-0002

Isc 3P 8000 A

TCC: tcc1 Current Scale Ref. Voltage: 480V Current in Amps x 1 Reference Voltage: 480 May 7, 2008

For this case, at 8.0 kA bolted fault on “Bus-0002”, we are now above the current limiting range. Since we are now above the current limiting range the tripping time for this fuse is now ½ cycle (.0083 sec). Also, to calculate the incident energy we now have to use the equation defined in the library.

From the fuse library, IE (cal/cm^2) = A2*Ibf^2 + A*Ibf + B with A2 = 0, A = 0.5, B = 0.5, Ibf, = 8.0 kA

Therefore IE = 4.5 cal/cm^2. This matches PTW32 result.

Page 66: Reference ArcFlash

Arc Flash Reference Manual 1 - 65

SKM Power*Tools for Windows

Now to demonstrate how the software handles current limiting fuse with incident energy accumulation, let us add a 300hp motor on the previous sample system.

In the example, the total bolted fault current on the bus is now 10.12 kA. The first portion coming from the utility seen by the fuse is 8.0 kA. The rest of the current (2.12 kA) is from the motor. For the first portion, the current seen by the fuse is 8.0 kA. Since this is in the current limiting range, the tripping time is ½ cycle (.0083 sec), which would produce 4.5 cal/cm^2 of incident energy.

The second portion (2.12 kA) is from the motor. This current would last until the motor decays for 5 cycles (.083 seconds). Therefore, the second portion would last for a time difference of (0.083 - 0.0083) 0.075 seconds. Base on this remaining current and time difference, this second portion would produce an incident energy of 0.49 cal/cm^2. Below is the incident energy result of the second portion using the user-defined arc flash table.

Summing up the incident energy from each portion of the source current, we get a total incident energy of IE = 4.5 + 0.49 = 5.0 cal/cm^2.

Page 67: Reference ArcFlash

7/15/2008

Reports

The arc flash report options include a standard spreadsheet report, datablock report, Crystal report, detailed label, summary label, and datablock display on one-line:

Standard Report: The standard report is generated directly from the main arc flash application screen. You can use the Document>Print, or Document>Save-As menu functions.

Also, the field shown in the standard report above can also be modified. To do this the user can click on the “Report Data and Order…” button in the Arc Flash report options screen and it will bring up a window that will allow the user to specify which of the twenty available fields will be displayed in the Arc Flash spreadsheet report. Furthermore, the user can also specify the order in which they will appear in the Arc Flash spreadsheet report.

Page 68: Reference ArcFlash

Arc Flash Reference Manual 1 - 67

SKM Power*Tools for Windows

For instance, if you don’t want to show the equipment type, you can simply uncheck the display checkbox next to that field. If you want the “Bus kV” field to show up on the first column, you can just type in the number “1” in the column order next to that field and the bus voltage will them show up on the first column of the report.

With the settings above, once you click on the “OK” button you will see a window similar to the one below. Here, notice that the equipment column is gone and the “Bus kV” field is on the first column.

Page 69: Reference ArcFlash

7/15/2008

Bus Detail: The Bus Detail option generates a detailed label including a listing of the protective device settings and energy at several different working distances. The Bus Detail label is generated by clicking on the or Arc Flash>Bus Detail menu functions

In the Bus Detail, users can also type in different working distances and the software will calculate the corresponding incident energy,

Page 70: Reference ArcFlash

Arc Flash Reference Manual 1 - 69

SKM Power*Tools for Windows

Work Permit: The work permit button generates a work permit form required by NFPA 70E 2004. Standard tasks may be selected from the task list and the equipment location and flash hazard study results are automatically displayed on the form.

Page 71: Reference ArcFlash

7/15/2008

Arc Flash Custom Label

PTW provides an Arc Flash Custom Label Designer for you to specify the Page Size, Label Size, Page Margins, Orientation, Rows and Columns of the labels and Spacing between labels. The available fields could be selected from the list, and the size and position of each field is defined in the Field Layout Settings. You can also create your own Text field, Date field, or place a picture anywhere in the label and specify the background color and font size for the user defined text fields and input in your own local language.

Click on the “Custom Label” button on top of the Arc Flash spread sheet table to defined custom label configurations.

The following window will appear:

Bus List - allows you to select or scroll through (using the arrow Up or Down keys) to preview the final look of the label specific to the selected bus.

Style List - all custom labels created by SKM or by your own are listed here. The SKM labels have a Style name of "_SKM Sample …" for those that are completely defined. The ones with "… - Template" at the end of the style name only define the width and height of the label and leave the rest for your customization.

Page 72: Reference ArcFlash

Arc Flash Reference Manual 1 - 71

SKM Power*Tools for Windows

Print - allows you to select the buses to be printed. When the user clicks on the “Print” button a “Group Print” window similar to the one below will show up.

In this window, the user will be able pick and choose which bus to print. By clicking on the “Check Print” or “Uncheck Print” buttons, the user will be able to check all or uncheck all the buses to print. Also, here the user will also be able to print multiple copies of the same label when multiple labels are selected to print. Furthermore, “Sort” button will allow the user to sort the “Bus Name”, “Bus kV”, etc. columns. The “Export” button allows the user to export the contents of the “Group Print” window to an Excel file. A common practice is to print to plain paper and laminate.

Preview - allows you to select to preview the buses to be printed. (See the print description above)

Designer - allows you modify and existing label or create and design a new one.

Keyword Table - allows you to map the standard keywords displayed on the label to your own preference, or your own local language.

Single Label - allows you to pick label style that has arc flash bus report option result information. If you pick a label that has both bus and line information, the label will not show any results on the line side.

Dual Label (Bus and Bus + Line) – This option becomes available if the “Bus + Protective Device Line Side” option is selected in the arc flash report options window. This allows the user to pick a label style with both bus and line side information.

If you pick a bus from the bus list has both bus and line side report information; and you pick a label that could show both the bus and line side report information, the label will show the corresponding bus and line side report information.

If you then pick a bus with just a bus result and you pick a label that could show both the bus and line side report information, the label will show just the corresponding bus report information. The line side report of the label will not be filled in.

Dual Label Default Print Style – This options allow users to select as default their preferred single or dual label from the style list.

To select a default single label, users need to select a single label from the style list and then click on the “Bus” option button. Now, whenever the user selects a bus from the bus list drop-down menu that has a bus report only result, the label style that will be selected will be the label style that was selected as the default for the “bus” option.

Page 73: Reference ArcFlash

7/15/2008

To select a default dual label, users need to select a dual label from the style list then click on the “bus + line” option button. Now, whenever the user selects a bus from the bus list drop-down menu that has a bus and line report result, the label style that will be selected will be the one that was selected as the default for the “bus + line” option.

Custom Label Sheet Design

Click on the “Designer” button show the “Custom Label Sheet Design” window.

The Arc Flash Custom Label layout page allow you to specify the Page Size, Label Size, Page Margins, Orientation, Rows and Columns of labels and Spacing between labels.

The “Select” button allows you to select an existing custom label design.

The “Save” button allows you to save what you have modified to the same Style name, or overwrite an existing Style, or save as an new Style name.

The “New” button allows you to create a new label style.

Page 74: Reference ArcFlash

Arc Flash Reference Manual 1 - 73

SKM Power*Tools for Windows

Label Design Detail

Press the “Label Design Detail” button to view/modify the detail of a label.

The available fields are selected from the list on the left, and the size and position of each field is defined in the Field Layout Settings. You can select any existing Arc Flash data field listed on the left by clicking on the field. Check the box next to the field to display the field on the Label. In order to see the field show up on the view area at the right hand side, make sure the field coordinate is within the label area, and either of the width or height is not zero.

You can create you own Text field, Date field, or place a picture anywhere in the label. Enter the X, Y positions and the width and height for the field, you can also specify the background color and font size for the user defined text fields and input in your own local language.

Show Label Border - Display a thin line of rectangle border around the label area.

Show Unit - Select to display the unit along with the result value or not. This selection is only available in some fields that have a unit to display.

X - The coordinate X of the top-left corner of the field

Y - The coordinate Y of the top-left corner of the field

Width - The width of the field

Height - The height of the field

Show Field Border - Draw a thin line of rectangle border around the field area.

Background Opaque - Select to apply background color to the field. If the user’s printer is B&W, this function will not generate a good result.

Clothing Category Color - Background color use the pre-defined SKM Clothing Category Color Table and it will be changed dynamically according to the result warning level. (Note: Red for the dangerous Category and orange for the warning classes)

Page 75: Reference ArcFlash

7/15/2008

Copy & Paste button – This buttons allow users to copy and paste the X coordinate, Y coordinate, and other parameters from the selected field. to another field.

Bus Side & Line Side button – These buttons filter the available fields that the user can pick to show on the label.

Text Format

Font - Click the font button to bring up a font select dialog. Choose the font, font style, font size, font effects, and the font color. Vertical Alignment - Choose to display the text to locate on the top, center or bottom of the field area. Horizontal Alignment - choose to display the text to align on the left side, right side, or in the horizontal center of the field area. Text Wrapping - Wrap the text to next line when it hits the right end of the field area. Text - The content of the text field. (This is only available to the regular text field.)

Picture Format - Available in picture field only.

Scale - The scaling of the picture.

Best Fit - the picture will be scratched to the exact size of the field area, in order to fit both of the height and the width.

Actual Size - The picture will be shown in the exact number of pixels.

Fit to Width - The picture will be scratched to fit the width.

Fit to Height - The picture will be scratched to fit the height.

Path: the path of the picture file (BMP file only). User can use the browse button to select from a file dialog, or type in manually. If a user chooses to type in manually, make sure the path is correct.

Page 76: Reference ArcFlash

Arc Flash Reference Manual 1 - 75

SKM Power*Tools for Windows

Custom Field Selections and Descriptions

Page 77: Reference ArcFlash

7/15/2008

Choose the fields from the left-hand-side field list to modified the specific field. Check the box next to the field to display the field. In order to see the field show up on the view area at the right hand side, make sure the field coordinate is within the label area, and either of the width or height is not zero.

Bus Name The name of the equipment

Bus Name + (Desc) This is the name of the equipment bus and the bus description entered in the component editor.

Prot Dev Name The name of the protective device after its tripping, the "Fault Clear Threshold" percentage will be cleared (if the Arc Flash Option is set to Report Last Trip Device, or the name of the protective device that trips the largest percentage of the fault contribution at the bus (if the Report Main Device is the selected option).

Bus Name + Prot Dev Name The name of the equipment bus and the name of the protective device.

Bus Name + (Desc) + Prot Dev Name The name of the equipment bus, the bus description, and the name of the protective device.

PPE Category Indicates the Personal Protective Equipment (PPE) required to prevent an incurable burn at the working distance during an arcing fault.

Clothing Category Provides a description of the clothing required to meet the reported Clothing Category.

Flash Hazard / Incident Energy The amount of energy on a surface at a specific distance from a flash

Flash Hazard Distance The distance between the arc source and the worker’s face or chest

Flash Hazard + Flash Hazard Distance The amount of energy on a surface and the flash hazard distance

Flash Hazard Boundary The distance from an arcing fault within which unprotected skin could receive a 2nd degree burn. Generally considered the distance where the incident energy equals 1.2 cal/cm2.

Glove Class Provides the glove class required based on the design voltage at the fault location.Glover Class

Limited Approach An approach limit at a distance from an exposed live part within which a shock hazard exists. Defined in NFPA 70E based on design voltage at the fault location.

Prohibited Approach An approach limit at a distance from an exposed live part within which work is considered the same as making contact with the live part. Defined in NFPA 70E based on design voltage at the fault location.

Page 78: Reference ArcFlash

Arc Flash Reference Manual 1 - 77

SKM Power*Tools for Windows

Restricted Approach A shock protection boundary to be crossed by only qualified persons (at a distance from a live part) which, due to its proximity to a shock hazard, requires the use of shock protection techniques and equipment when crossed. Defined in NFPA 70E based on design voltage at the fault location.

Bus Bolted Fault The current flowing to a bus fault that occurs between two or more conductors or bus bars, where the impedance between the conductors is zero.

Bus Arcing Fault The calculated arcing current on the faulted bus

Arcing Duration Time that the arcing fault persisted

Bus Bar Gap Used only in the IEEE 1584 method to define the spacing between bus bars or conductors at the arc location

SKM Label Exlamation SKM supplied picture/sign for “Warning” or “Danger”. Note that the “Warning” can be modified in the PPE and the “Danger” text can be modified in the Keyword table.

SKM Label Title 1 SKM supplied text "WARNING" or "DANGER" can be displayed on the printed labels.

SKM Label Title 2 SKM supplied text "Arc Flash and Shock Hazard" or "NO PPE AVAILABLE" can be displayed on the printed labels.

SKM Label Title 3 SKM supplied text "Appropriate PPE Required" or "ENERGGIZED WORK PROHIBITED" can be displayed on the printed labels.

Today’s Date A smart field that reads the system date from the computer and displays it on the printed label.

Head & Eye & Hearing Protection Head & Eye & Hearing Protection from the PPE table

Hand & Arm Protection Hand & Arm Protection from the PPE table

Foot Protection Foot Protection from the PPE table

PPE Others 1 - PPE Others 5 Other notes or descriptions that can be associated with a PPE category. These can be defined in the PPE table.

PPE notes Notes from the PPE table

Label # Arc Flash label #

Project Title 1 – Project Title 5 Project Title fields are define from the Project Options menu (menu Project >options)

Text1 – Text20 20 user-defined text fields that can be displayed on the printed labels.

Page 79: Reference ArcFlash

7/15/2008

Picture1 – Picture3 3 user-defined bit-map pictures that can be displayed on the printed labels.

Additional Distance 1 – 4 User-define additional working distance. These fields comes from the data entered in Arc Flash reports options window (Additional Incident Energy and Flash Boundary button)

Flash Hazard at Distance 1 – 4 Calculated incident energy at user-define flash hazard distance

PPE Category at Distance 1 – 4 PPE Category required at calculated incident energy based on the user-defined distance.

PPE Description at Distance 1 – 4 PPE Description required at calculated incident energy based on the user-defined distance.

Hazard Range at Distance 1 – 4 Hazard Range for the PPE category required at calculated incident energy based on the user-defined distance.

Additional Flash Hazard 1 – 4 Additional user-defined flash hazard specified in the study options

Flash Hazard Boundary 1 – 4 Flash Boundary at user-defined flash hazard incident energy

PPE Picture 1 - 4 These fields are defined in the PPE table. In the PPE table, there are four picture columns where the user can specify different pictures or logos for each PPE Category.

ProtDev Feeds This field will show component that is fed or feeding by the protective device that is tripping. For instance, if the protective device tripping feeds a motor then it will show the name of the motor. If the protective device that is tripping is fed by a generator, then it will show the name of the generator. If there is no protective device on the bus or if the device tripping is fed by or is feeding multiple then the bus name will be show. If the bus is connect to a load schedule component, it will show the component name of the schedule.

ProtDev Manufacturer These fields are defined in the PPE table. In the PPE table, there are four picture columns where the user can specify different pictures or logos for each PPE Category.

Page 80: Reference ArcFlash

Arc Flash Reference Manual 1 - 79

SKM Power*Tools for Windows

ProtDev Type This is the type description of the protective device that is tripping.

ProtDev Description This is the description of the protective device that is tripping.

ProtDev Frame/Rating This is the frame/rating of the protective device that is tripping

ProtDev Sensor/Trip This is the frame/rating of the protective device that is tripping

ProtDev LTPU This is the long time pick up setting of the protective device that is tripping

ProtDev LTD This is the long time delay setting of the protective device that is tripping

ProtDev STPU This is the short time pick up setting of the protective device that is tripping

ProtDev STD This is the short time delay setting of the protective device that is tripping

ProtDev INST This is the instantaneous setting of the protective device that is tripping

ProtDev INST_Delay This is the instantaneous delay setting of the protective device that is tripping

ProtDev GFPU This is the ground fault pick up setting of the protective device that is tripping

ProtDev GFD This is the ground fault delay setting of the protective device that is tripping

Page 81: Reference ArcFlash

7/15/2008

Datablock Display: The datablock display is activated from the Run>Datablock Format menu item. You can modify the datablock formats to include any combination of data fields including: Incident Energy, Working Distance, PPE Class, Flash Boundary (as shown below), Arcing Fault, Breaker Time, Gap, Grounded Indicator, PPE Description, Trip time, and Shock Boundaries. The Arc Flash datablock, like any other datablock, can be applied to One-lines, TCCs and the Component Editor.

009-TX C PRI

0.5 Cal/cm^2@ 18 inchesClass 0 PPEFB 8 inches

TX3

LV DISTRIB

3.5 Cal/cm^2@ 18 inchesClass 2 PPEFB 35 inches

C14

015-MCC 1A

0.6 Cal/cm^2@ 18 inchesClass 0 PPEFB 12 inches

Subfeed #1

018-RA

0.5 Cal/cm^2@ 18 inchesClass 0 PPEFB 11 inches

PANEL S1

MCC 15A

SWBD 1

F TX 3

B-SWBD1

LVP1

Page 82: Reference ArcFlash

Arc Flash Reference Manual 1 - 81

SKM Power*Tools for Windows

Datablock Report: The datablock report can be generated from the Component Editor or the One-line diagrams. As with a datablock display, any combination of fields can be reported. The Datablock report may be printed, saved as a text file or saved as an Excel file.

1.5.5 Selecting Buses for Arc Flash Report By default, all buses are included in the arc flash report. To limit the buses displayed in the arc flash report, any of the following methods may be used:

- Bus Nodes versus Buses. Bus Nodes are excluded from the Arc Flash report automatically.

- Query: A query can be used to customize the bus list. For example, you can query to only display only above Class 2 PPE, above 208 Volts, or any other user-defined criteria.

- Go-To Selection: From the one-line, you can select the area of interest and use the Go-To-Arc Flash option. Only the items selected on the one-line will be displayed in the Arc Flash Table. The Go-To function is also available from TCC drawings and the Component Editor. From the TCC, only the buses attached to the components on the TCC will be displayed in the Arc Flash table. From the Component Editor, only the selected bus will be displayed in the Arc Flash table.

Page 83: Reference ArcFlash

7/15/2008

1.5.6 PPE Table The PPE table defines the Personal Protective Equipment Categories and clothing descriptions used in the reports and labels. Different label colors may be assigned for each PPE Category, the Bus Detail and Arc Flash Label will apply the colors based on the PPE Categories calculated.

The PPE table defines the Personal Protective Equipment Categories and clothing descriptions used in the reports and labels. Different label colors may be assigned for each PPE Category; the Bus Detail and Arc Flash Label will apply the colors based on the PPE Categories calculated.

The data supplied as default is taken from NFPA 70E, 2004 edition, Page-61. Four default Categories of FR Clothing are defined based on the applicable range of the incident energy. Modify these values or add new Categories to this table if needed.

The Notes, Head & Eye Protection, Hand & Arm Protection, Foot Protection, PPE Others 1 to 5 provides user defined additional protections for each category. The Warning Label Text could be user defined as well. All user defined additional protection fields are available in the Custom Label.

You can also choose a background and a foreground color for each of the PPE Category. These colors will be used as the background and foreground color for the SKM Label Title 1, 2, and 3 in the Arc Flash Label.

A row is reserved in the PPE table for the Dangerous category. This allows the users the flexibility to add descriptions for the Notes, Head & Eye Protection, Hand & Arm Protection, Foot Protection, and other columns for the PPE Dangerous category.

The PPE Table information is project specific. (It will look in the information from the FR_Clothing.ss3 or FR_Clothing_Metric.ss3 file located in the project's directory).

For new projects created, it will copy and use the PPE table file(s) information from the LIB directory (specified in the miscellaneous files options group).

If there is no PPE table file(s) existing in the project directory currently opened, it will copy and use the PPE table file information from the LIB directory (specified in the miscellaneous files options group).

Page 84: Reference ArcFlash

Arc Flash Reference Manual 1 - 83

SKM Power*Tools for Windows

If there is no PPE table file(s) existing in the LIB directory, it will copy and use the PPE table file(s) in the Bin directory of PTW32.

Four dynamic pictures for each PPE Category can also be specified. Switching pictures among the categories is done automatically.

In the PPE table, there are now four new picture columns where the user can specify different pictures or logos for each PPE Category. This allows the users the flexibility to add up to four different pictures or logos for each PPE category in their custom arc flash label.

Add Row This button lets you insert a row in the PPE table.

Save If you had customized a PPE table and want to keep the changes to a file for future use, or to use the file on a different project, use the "Save" button. This will save the changes you’ve made to a *.ppe file in a directory chosen by the user (by default it is save in the directory of the project that is currently open).

Load If you had a customized PPE table and had saved it to *.ppe file and want to use it for the existing project, use the "Load" button. This will load the contents of the selected *.ppe file to the current PPE table.

Save As Default If you had customized this table and want to keep the changes as your default, use the “Save As User Default” button. This will save the changes you’ve made to the FR_Clothing.ss3 or FR_Clothing_Metric.ss3 file in the LIB directory (specified in the miscellaneous files options group).

Reset Default If you make changes to this table and don’t want to keep them, use the Reset button to re-store the defaults from the FR_Clothing.ss3 or FR_Clothing_Metric.ss3 file in the LIB directory (specified in the miscellaneous files options group).

Print Use the Print button to print out this table.

Page 85: Reference ArcFlash

7/15/2008

1.5.7 Long Trip Times Long trip times will result in high incident energy values. The IEEE 1584-2002 equations do not include a time limit or variable working distance. It’s important to understand why the trip time is long and the behavior of the fault source. Often the trip time is long when the fault current is relatively small. For these cases, if the workers are properly clothed to withstand the initial few seconds of flash energy, it is likely they will be able to move further away from the arc source than the stated working distance. To evaluate the effect of faster trip times or limited arc duration for an existing system, use the Maximum Arcing Duration field in the Arc Flash Study Options dialog.

The default for the Maximum Arcing Duration in PTW is set to 2 seconds, if the Trip Time read from the TCC plus the Breaker Time is bigger than the Maximum Arcing Duration, the Trip Time will be set to the Maximum Arcing Duration – Breaker Time. Sound engineering judgment is always required when making reasonable arc flash energy estimates.

- Use Global Max Arcing Time: Allow user to enter different maximum arcing during for system voltage > 240 Volts and system voltage <= 240 Volts.

- Enter for each bus: When this option is selected, the user can click on the “Max Arcing Time for Each Bus” button, and “Maximum Arcing Duration for Each Bus” window will come up. See picture below.

Page 86: Reference ArcFlash

Arc Flash Reference Manual 1 - 85

SKM Power*Tools for Windows

In this window, the user can specify the maximum arcing duration for each buses in the system modeled. For convenience, the user can also sort the window by bus name, bus voltage, or maximum arcing duration by selection one of the available options button. Furthermore, user can change the maximum arcing duration of all the buses globally by clicking on the “Global Change” button. This helps in modeling your system accurately for arc flash study, since each bus location you are analyzing may have different maximum arcing duration depending on the situation.

Page 87: Reference ArcFlash

7/15/2008

1.5.8 Differential Protection Differential Protection, and other special protection schemes, can be represented by entering a Protection Category description for the Bus and checking the available check box.

The trip time for the Differential protection is entered directly in the Arc Flash table

The Special Instantaneous Protection specification can be used for differential, zone interlocking, optical sensors, and other protection methods. If special protection is not defined for the bus, the traditional time-over current protection method is used.

Page 88: Reference ArcFlash

Arc Flash Reference Manual 1 - 87

SKM Power*Tools for Windows

The same method could also be applied to 2 winding and 3 winding transformers transformer instantaneous protection for protective device Line Side calculations.

In the 2 and 3 winding transformer component editor, there is now an option checkbox to model special instantaneous protection for protective device Line Side calculations. If the “INST Protection” checkbox is checked, the report would then show the transformer name (INST Protection) on the report, indicating that the transformer is being protective by a special device. Also, the trip delay line field will be user-defined for the user to enter in their own tripping time.

Page 89: Reference ArcFlash

7/15/2008

1.5.9 Arcing Fault Tolerances There is on-going discussion regarding the use of arcing fault tolerance in determining trip times during an arcing fault. The IEEE 1584 2002 standard uses a 15% low tolerance for arcing fault current due to variations found in the test results. We know that the arc current is greater than zero and less than the bolted 3-phase fault, however variations in arc impedance due to temperature, humidity, dust content, altitude or other factors may create some variability beyond what was documented in the test results. To follow the IEEE 1584-2002 standard, a 15% low tolerance should be used. If a higher degree of safety is desired, larger tolerances may be specified. The low tolerance values may result in longer trip times and higher incident energy. If both the low tolerance and high tolerance values result in the same trip time, the high tolerance value will produce the highest incident energy. Separate tolerance values for low voltage and medium voltage are available since variations in arc impedance will have more effect on arcing fault current at lower voltages.

Page 90: Reference ArcFlash

Arc Flash Reference Manual 1 - 89

SKM Power*Tools for Windows

1.5.10 Reducing Incident Energy The following design modifications may be used to reduce incident energy from arc flash events:

1) Clear the arcing fault faster a) Reduce Existing Pickup and Delay Settings wherever possible. b) Enable Instantaneous Functions or Retro-fit with Instantaneous Functions c) Reduce Fuse Sizes wherever possible. d) Use Current-limiting breakers or fuses for high arcing fault currents e) Add Differential Protection f) Use Temporary Instantaneous Trip Settings when work is being performed g) Add optical sensors to trip when flash occurs

2) Reduce the fault level* a) Use Current-limiting breakers or fuses b) Use Current-limiting reactors c) Block paralleling capabilities

*Note that reducing the fault level results in reduced incident energy only when the reduced current does not increase the trip time.

Page 91: Reference ArcFlash

7/15/2008

1.6 Application Example

1.6.1 Sample Arc Flash Study

The following example highlights the steps required for an arc flash study.

Step 1: Enter data sufficient to perform Short Circuit study. The required data includes component connections, bus voltages, transformer impedance, cable impedance, and utility, generator, and motor fault contributions.

Page 92: Reference ArcFlash

Arc Flash Reference Manual 1 - 91

SKM Power*Tools for Windows

Step 2: Enter data sufficient to perform a time over-current coordination study. The required information includes protective devices and their associated trip settings.

C1-A

R1-AR-Util

TX Inrush

TX 1ATX 1A

C1-A

M1A

R1-A

R-Util

LVB 1A

BM1A

0.5 1 10 100 1K 10K0.01

0.10

1

10

100

1000

CURRENT IN AMPERES

tcc1.tcc Ref. Voltage: 4160 Current Scale x10^0 1Line001.drw

TIM

E IN

SE

CO

ND

S

Page 93: Reference ArcFlash

7/15/2008

Step 3: Identify Operating Modes. For this example, the operating modes include:

1) Maximum Utility fault of 300 MVA at a pre-fault voltage of 1.02 per unit. 2) Minimum Utility fault of 200 MVA at a pre-fault voltage of 0.98 per unit. 3) Tie breaker open and closed. Using the Scenario Manager in PTW, the Base Project can be duplicated and the different operating modes can be saved for comparison.

Page 94: Reference ArcFlash

Arc Flash Reference Manual 1 - 93

SKM Power*Tools for Windows

A summary table comparing the 4 scenarios in the PTW Version Manager Data Visualizer follows:

From the summary table, the highest incident energy for each bus follows:

LV SWB A Minimum Fault with Closed Tie LV SWB B Minimum Fault with Closed Tie MCC 1A Maximum Fault with Closed Tie MCC 1B Minimum Fault with Closed Tie MV SWGR Maximum Fault The important thing to note is that you can’t predict which operating scenario will result in the highest incident energy without evaluating all of the scenarios. The highest incident energy at some locations occurs with minimum fault and others with maximum fault, some with the tie closed and others with the tie open. The incident energy is affected by both the fault current and the trip time. The trip time is fixed for some levels of fault current and varies inversely at others. Using the arcing fault current rather than the bolted fault current also makes general predictions difficult. In the software, the user can chose to make the arc flash report show worst-case condition out of all the scenarios. To do this, the user can click on the “Scenarios…” button as show below.

When the user clicks on this button, a window similar to the one below will come up.

Page 95: Reference ArcFlash

7/15/2008

Here, the user can specify to report Arc Flash results based on the current scenario opened; or if the project has multiple scenarios, the user can select the Arc Flash result to report the worst case (the one with the highest incident energy) out all of all the selected scenarios.

The arc flash report based on the worst-case scenario should look like the window below.

Notice that now the arc flash spreadsheet report for each bus is the incident energy from the scenario with the highest value. In the “Required Protective FR Clothing Category” column, the (*S0), (*S1), (*S2), etc., indicate which scenario did the result come from. For a better understanding, lets look at why the results are higher for MCC 1B than they are for MCC 1A using the Maximum Fault with Bus Tie Open scenario.

Page 96: Reference ArcFlash

Arc Flash Reference Manual 1 - 95

SKM Power*Tools for Windows

Utility

MV-SWGR

LV SWB A

MCC 1A

480 VIsc 3P 8891 AAF_ArcingFault 5.931 kAAF_IncidentEnergy 1.13 Cal/cm^2AF_TripTime 0.060 s

P

S

TX 1A

LVB 1A

SQUARE D NT08N1 Sensor/Trip 800.0 ASettings LTPU (A);LTD 0.4 (320A); 8 STPU 5 (1600A) STD 0.4 (I^2t Out) INST 4 (3200A)

C1-AInitSymRMS 3P Bus2 8401.25 ALength 100.0 ft

BM1A

M1A

R-Util

R1-A

LV SWB B

MCC 1B480 VIsc 3P 4748 AAF_ArcingFault 3.471 kAAF_IncidentEnergy 4.94 Cal/cm^2AF_TripTime 0.500 s

P

S

TX 1A0

LVB 1BSQUARE D NT08N1 Sensor/Trip 800.0 ASettings LTPU (A);LTD 0.4 (320A); 8 STPU 5 (1600A) STD 0.4 (I^2t Out) INST 4 (3200A)

C1-B InitSymRMS 3P Bus2 4343.97 ALength 350.0 ft

BM1B

M1B

R1-B

OpenTie Breaker

Reviewing the datablock display on the one-line, you can see that the primary protection has the same settings for MCC 1A and MCC 1B. The only input difference is that cable C1-A is 100 feet long, whereas cable C1-B is 350 feet long. The cable length difference results in a smaller fault current at bus MCC 1B. Although the fault current is smaller, the incident energy is higher. To understand this situation, review of the coordination drawing is required.

Viewing the arcing fault current values on the following coordination drawing indicates the associated trip time for MCC 1A and MCC 1B. MCC 1A trips in 0.06 seconds, whereas MCC 1B trip in 0.5 seconds. MCC 1B has less fault current but the longer trip time results in the release of more energy.

Notice that the TCC curve identifies 5600 Amps which is the calculated arcing fault current through breaker LVB 1A for a fault at MCC 1A. It also identifies 3180 Amps, which is the arcing fault current through breaker LVB 1B for a fault at MCC 1B. 5600 Amps results in a trip time of 0.06 seconds, whereas 3480 Amps results in a trip time of 0.5 seconds. Due to variations in the test data for arcing faults, the IEEE 1584 also recommends calculating the trip time and incident energy using both 100% and 85% of the calculated arcing fault current. In this case the 100% value produces a higher incident energy since the trip time for both 100% and 85% are the same. Quite often, the 85% arc fault produces higher incident energy if the trip time is longer for the lower fault current.

Page 97: Reference ArcFlash

7/15/2008

The incident energy at bus MCC 1A is calculated to be about 1.2 Calories/cm2 whereas the incident energy at bus MCC 1B is calculated to be 4.9 Calories/cm2. MCC1B has a lower arcing fault current (3.18 kA versus 5.6 kA) but the longer trip time (0.5sec. versus 0.06 sec.) results in higher incident energy.

Arcing Fault

Trip Time

Incident Energy

Page 98: Reference ArcFlash

Arc Flash Reference Manual 1 - 97

SKM Power*Tools for Windows

The next step is to improve safety wherever possible. This means to clear the arcing faults as fast as possible and to document appropriate clothing requirements.

By reducing the instantaneous settings for breakers LVB 1A and LVB 2A, and by reducing the instantaneous time delay for relays R1-A and R1-B, as shown on the following TCC drawing, the trip times for the arcing fault currents are reduced significantly.

Arc Flash summary results after adjustments to protective device settings.

Comparison of protective device settings before and after changes.

Page 99: Reference ArcFlash

7/15/2008

BEFORE AFTER

Comparison of Arc Flash Results for all scenarios using the PTW Scenario Data Visualizer.

BEFORE

AFTER

Summary of Worst Case Before and After Protection Setting Changes BEFORE AFTER ------------------------------------------------------------------------------------------- LV SWB A 57.4 cal/cm2 11.7 cal/cm2

LV SWB B 57.4 cal/cm2 11.7 cal/cm2

MCC 1A 1.6 cal/cm2 1.6 cal/cm2

MCC 1B 5.4 cal/cm2 0.7 cal/cm2

MV SWGR 29.1 cal/cm2 13.4 cal/cm2

Page 100: Reference ArcFlash

Arc Flash Reference Manual 1 - 99

SKM Power*Tools for Windows

After adjusting the protective device settings so that all of the devices operate in the instantaneous region for all configurations, the largest incident energy now occurs for the Maximum Fault with the Tie Closed, as expected.

Given the same arcing fault current, the faster you can clear the fault, the lower your incident energy will be. This is why small changes in protective device settings can have a significant impact on the incident energy values, and a tolerance is recommended for available fault current and the estimated arcing fault values.

Page 101: Reference ArcFlash

7/15/2008

Once you’re satisfied with the study results, you can print reports and labels.

You can print labels to plain paper or to label sheets in a variety of sizes. You can also print multiple copies of the same label when multiple labels are selected to print in Custom Label Group Print.

A common practice is to print to plain paper and laminate.