Raycap - Transient Voltage Surge Suppressor_4006895_02

download Raycap - Transient Voltage Surge Suppressor_4006895_02

of 20

Transcript of Raycap - Transient Voltage Surge Suppressor_4006895_02

  • 7/25/2019 Raycap - Transient Voltage Surge Suppressor_4006895_02

    1/20

    SchlumbergerPrivate

    Issue Date: 11/22/2004 Rev. Date: 00/00/0000 Revision: # / 01

    Author: Chris Salmas Page 1 of 20 Content ID:

    TVSS Transient Voltage Surge SuppressorsWhen Should A TVSS be used in a system? 2

    Over Voltages - What Causes Them and What are They? 2

    How does a TVSS reduce the over voltage levels on a system? 2Figure 1.01 Wave form before TVSS 3

    Figure 1.02 - Ideal Wave form after TVSS 3

    Configurations and Ratings of MOVs for use in TVSS equipment 31.1

    Design methods 3

    Figure 1.03 Conventional MOV Construction 4

    Figure 1.04 Cross Section of Raycap Strikesorb TVSS Construction 4

    1.2 Design ratings 4

    Figure 1.05 Parallel MOV Circuit Board 5

    Figure 1.06 Basic side view and Typical Ratings for Raycap TVSS 5

    1.3

    Lead Length to MOV Connection Point 6

    Figure 1.07 Raycap Strikesorb TVSS connected in-line with equipment 7

    Figure 1.08 Raycap Strikesorb TVSS connected in-line with 815 kVA SpeedStar SineWave Drive 8

    Figure 1.09 3-Phase 3-Wire Connection Block Diagram Using a Conventional TVSS 9

    Figure 1.10 3-Phase 3-Wire Connection Block Diagram Using a Raycap (in line) Strikesorb TVSS 10

    Appendix a 40/80-380 UL Approval For Use Behind An 800 Amp Breaker 11

    Appendix B Ferraz Shawmut I

    2

    T Destructive Test on Raycap Strikesorb TVSS Engine

    12Appendix C - 40-380 Module Test Acceptance Summary 15

    Appendix D 80-380 Module Test Acceptance Summary 17

    Appendix E Raycap Warranty Document 19

    Appendix F Raycap Legal Name Changes for Strikesorb and Rayvoss 20

    Copyright Statement This document remains the property of Schlumberger and is Confidential and Trade Secret.

    Do not disclose, use, or reproduce without written approval from Schlumberger

  • 7/25/2019 Raycap - Transient Voltage Surge Suppressor_4006895_02

    2/20

    SchlumbergerPrivate

    Page 2 of 20

    When Should A TVSS be used in a system?

    A TVSS is used to protect against lightning strikes, power line surges, and other transients that may be

    present on the system. The TVSS achieves this by providing voltage suppression when over voltage conditions

    appear on an electrical system. There are two main causes of over voltages, voltage spikes and systems transients.

    These over voltages could cause the immediate loss of equipment and/or reduce the reliability (MTBF-mean time

    before failures) of equipment; therefore, a TVSS should be installed into a system whenever there is the chance that

    over voltages may occur. In some cases a power system study may be required to determine whether the use of a

    TVSS is warranted. Proper selection should be the result of a thorough diagnostic evaluation of the customer

    systems and environment. Schlumberger EPC Power Systems Group offers diagnostic expertise.

    Over Voltages - What Causes Them and What are They?

    The causes of over voltages can be grouped into four categories:

    1. Lightning a natural phenomenon that produces severe and/or destructive levels of over voltage.2. Local Electrical Utilities can introduce transients and over voltages depending on the quality of the

    utility service.

    3. In-house systems Electrical equipment that introduces over voltages due to the operation of

    equipment (e.g. Variable Speed Drives, rectifiers, etc.)

    4. Adjacent facilities Introduction of the over voltages may be caused by equipment in an adjacent

    facility down stream.

    Over voltages are voltage levels that exceed the insulation rating of electrical equipment which will causes

    degradation of insulation. This degradation of insulation will result in a reduction of reliability and possibly the

    destruction of the equipment. If the voltage rises into the reliability impairment zone, the MTBF will be reduced

    proportionally. The result will be that equipment will have to be replaced more often, increasing net operating costs.

    If the voltage rises above the impairment zone then immediate destruction will occur, again increasing net operatingcosts. Most of these over voltages can be reduced or even eliminated with the installation of a TVSS.

    How does a TVSS reduce the over voltage levels on a system?

    Almost all TVSS manufactures use MOVs (Metal Oxide Varistors) in their design. MOVs are composed of a

    thin disk wafer of material (metal oxide) that has a known voltage breakdown characteristic. At low voltages, the

    MOV conducts very little current (micro-amperes). As the voltage approaches breakdown, the MOV then begins to

    conduct current. At voltages slightly above the break down, large currents flow, effectively clamping the output

    voltage. This clamping feature allows the higher voltage levels to be shunted to ground preventing over voltages onequipment. Refer to Figures 1.01 and 1.02 for examples on waveform clamping.

    Copyright Statement: This document remains the property of Schlumberger. It is Confidential and Trade Secret

    and not to be disclosed, used, or reproduced without written approval from Schlumberger.

  • 7/25/2019 Raycap - Transient Voltage Surge Suppressor_4006895_02

    3/20

    Schl

    berg

    Private

    Page 3 of 20

    umum

    er

    - VClamping

    er

    - VClamping

    +VClamping

    +VClamping

    berg

    Private

    - VClamping

    - VClamping

    Figure 1.01 Wave form before TVSSFigure 1.01 Wave form before TVSS

    Voltage Spikes

    +VClamping

    +VClamping

    Figure 1.02 - Ideal Wave form after TVSSFigure 1.02 - Ideal Wave form after TVSS

    Configurations and Ratings of MOVs for use in TVSS equipmentConfigurations and Ratings of MOVs for use in TVSS equipment

    Design methodsDesign methods

    The conventional connection method used by most manufacturers for MOV construction is a soldered

    connection of the conductor onto a thin coating of conductive material on the face of the MOV, as illustrated in

    Figure 1.03.

    The conventional connection method used by most manufacturers for MOV construction is a soldered

    connection of the conductor onto a thin coating of conductive material on the face of the MOV, as illustrated in

    Figure 1.03.

    Copyright Statement: This document remains the property of Schlumberger. It is Confidential and Trade Secret

    and not to be disclosed, used, or reproduced without written approval from Schlumberger.

  • 7/25/2019 Raycap - Transient Voltage Surge Suppressor_4006895_02

    4/20

    SchlumbergerPrivate

    Page 4 of 20

    Figure 1.03 Conventional MOV Construction

    A problem with this type of construction becomes apparent when a high-energy surge is applied to the

    MOV-connection-conductor. When a fast rising surge exceeds the capacity of the assembly (not the wafer disk), itpunches through the wafer between the connecting wires. Because the energy is not spread evenly across the

    MOV face, the connection becomes its weakest link and when several MOVs are placed in parallel this can create

    a domino effect where the TVSS fails catastrophically.

    The Raycap Strikesorb TVSS design solves the problem of using multiple conventional MOVs by creating

    one single MOV capable of handling the high-energy surges. The design also allows the energy of the surge to be

    equally dispersed throughout the varistor surface. The varistor is also held in place with 1500+ pounds of pressure.

    This design encourages the rapid dispersion of energy across the whole surface of the MOV, which removes the

    problem of weak links and increases the energy handling capabilities of the device. Refer to Figure 1.04.

    Figure 1.04 Cross Section of Raycap Strikesorb TVSS Construction

    Design ratings

    Most TVSS designs use multiple MOVs in parallel on a circuit board. The module rating or energy handling

    is calculatedby multiplying the rating of one MOV by the number of MOVs in the circuit; the assumption being that

    the surge will be shared equally by all MOVs and that each MOV has exactly the same operating characteristics as

    depicted in figure 1.05.

    Copyright Statement: This document remains the property of Schlumberger. It is Confidential and Trade Secret

    and not to be disclosed, used, or reproduced without written approval from Schlumberger.

  • 7/25/2019 Raycap - Transient Voltage Surge Suppressor_4006895_02

    5/20

    SchlumbergerPrivate

    umbergerPrivate

    Page 5 of 20

    Figure 1.05 Parallel MOV Circuit BoardFigure 1.05 Parallel MOV Circuit Board

    Testing of parallel MOV modules does not support this assumption: they fail at a much lower value. It is

    impossible for all the parallel MOVs to clamp at the exact same voltage: thus, when subjected to a surge the lowest

    clamping MOVs will clamp first and take on most of the surge energy; hence, this causes further degradation within

    the MOVs and eventually leads to failure at its weakest link as described in Section 4.1 - Design Methods. Whenthe MOVs fail it could explode and/or cause a chain reaction of events leading to a destructive breakdown and

    debris contamination, even when encased in epoxy.

    Testing of parallel MOV modules does not support this assumption: they fail at a much lower value. It is

    impossible for all the parallel MOVs to clamp at the exact same voltage: thus, when subjected to a surge the lowest

    clamping MOVs will clamp first and take on most of the surge energy; hence, this causes further degradation within

    the MOVs and eventually leads to failure at its weakest link as described in Section 4.1 - Design Methods. Whenthe MOVs fail it could explode and/or cause a chain reaction of events leading to a destructive breakdown and

    debris contamination, even when encased in epoxy.

    The Raycap TVSS rating is not based on calculation but rather on actual lab testing on a single MOV module

    as illustrated in Figures 1.04 & 1.06. Refer to Appendices C & D for actual lab test certifications.

    The Raycap TVSS rating is not based on calculation but rather on actual lab testing on a single MOV module

    as illustrated in Figures 1.04 & 1.06. Refer to Appendices C & D for actual lab test certifications.

    Figure 1.06 Basic side view and Typical Ratings for Raycap TVSS

    Copyright Statement: This document remains the property of Schlumberger. It is Confidential and Trade Secret

    and not to be disclosed, used, or reproduced without written approval from Schlumberger.

  • 7/25/2019 Raycap - Transient Voltage Surge Suppressor_4006895_02

    6/20

    SchlumbergerPrivate

    Page 6 of 20

    Lead Length to MOV Connection Point

    The lead length to the MOV plays a very important role in the value of clamping that will be offered by the

    device. The conventional TVSS requires the use of leads and fusing to connect in parallel to the load side breaker

    and cannot be mounted inside equipment due to the catastrophic failure condition of the device if it fails during ahigh-energy event. The length of the leads adds inductance to the circuit and increases the clamping voltage of the

    TVSS. This results in clamping voltages that are higher than desired and may not protect equipment effectively.

    The Raycap TVSS is installed in-line with the load (TVSS is installed in-line in the Toshiba plant for

    all SS2K and SWD models), minimizing unnecessary connection leads and maximizing the level of protection by

    keeping the lead length no more than 8-10 away from the TVSS as illustrated in Figure 1.07, 1.08 and 1.10. The

    reduced lead length is made possible due to the fact that the Raycap Strikesorb TVSS does not fail catastrophically

    and contains the energy within itself; this allows the TVSS to be installed on the load side of the breaker as depicted

    in Figure 1.08. Refer to Appendix B for destructive test results and descriptions/pictures of the Raycap Strikesorb

    TVSS that has operated to a short. Typical connection block diagrams for ESP applications of both types of TVSS

    can be found in Figures 1.09 & 1.10.

    The connection point also plays a large role in the way in which the protection to the device is offered. As

    part of the requirement when connecting a conventional TVSS to the line side of the breaker, a fuse must be placed

    in series with the TVSS to protect TVSS against a high inrush of current, which could lead to the catastrophic failure

    of the TVSS. When the fuse is blown all protection is lost and any transients that are entering the system, after the

    fuse has blown, is now entering the unprotected equipment. The Raycap 40/80-380 Strikesorb TVSS can be

    connected on the load side of the breaker without any additional fusing up to its UL rating of 800 Amps (refer to UL

    rating in Appendix A) or behind a fuse rating of 1200A at 100kA of available short circuit. The I2T rating of the Raycap

    Strikesorb TVSS can handle much higher levels (approximately 500 times more) of inrush when compared to the I2T of

    a breaker as depicted in by the Ferraz Shaumat test results in Appendix B. In the rare case that the TVSS rating is

    exceeding during a high-energy event the TVSS will short to ground thereby tripping the breaker and isolating the

    load from damaging energy. The event is contained within the TVSS enclosure and no external damage occurs.

    This, in turn, ensures that the breaker will trip during an extremely high I2T and will isolate the system from any other

    transients that may follow. Refer to Appendix B for a cut-away picture of a TVSS unit that has operated to a short.

    Copyright Statement: This document remains the property of Schlumberger. It is Confidential and Trade Secret

    and not to be disclosed, used, or reproduced without written approval from Schlumberger.

  • 7/25/2019 Raycap - Transient Voltage Surge Suppressor_4006895_02

    7/20

    SchlumbergerPrivate

    Page 7 of 20

    Figure 1.07 Raycap Strikesorb TVSS connected in-line with equipment

    Copyright Statement: This document remains the property of Schlumberger. It is Confidential and Trade Secret

    and not to be disclosed, used, or reproduced without written approval from Schlumberger.

  • 7/25/2019 Raycap - Transient Voltage Surge Suppressor_4006895_02

    8/20

    SchlumbergerPrivate

    Page 8 of 20

    Figure 1.08 Raycap Strikesorb TVSS connected in-line with 815 kVA SpeedStar SineWave Drive

    Copyright Statement: This document remains the property of Schlumberger. It is Confidential and Trade Secret

    and not to be disclosed, used, or reproduced without written approval from Schlumberger.

  • 7/25/2019 Raycap - Transient Voltage Surge Suppressor_4006895_02

    9/20

    Page 9 of 20

    SchlumbergerPrivate

    umbergerPrivate

    Note: TVSS connection could be from load or line side of breaker. Load side connection depicted in this

    diagram.

    Figure 1.09 3-Phase 3-Wire Connection Block Diagram Using a Conventional TVSS

    Copyright Statement: This document remains the property of Schlumberger. It is Confidential and Trade Secret

    and not to be disclosed, used, or reproduced without written approval from Schlumberger.

  • 7/25/2019 Raycap - Transient Voltage Surge Suppressor_4006895_02

    10/20

    SchlumbergerPrivate

    Page 10 of 20

    Figure 1.10 3-Phase 3-Wire Connection Block Diagram Using a Raycap (in line) Strikesorb TVSS

    Copyright Statement: This document remains the property of Schlumberger. It is Confidential and Trade Secret

    and not to be disclosed, used, or reproduced without written approval from Schlumberger.

  • 7/25/2019 Raycap - Transient Voltage Surge Suppressor_4006895_02

    11/20

    SchlumbergerPrivate

    Page 11 of 20

    Appendix A 40/80-380 UL Approval For Use Behind An 800 Amp Breaker

    Copyright Statement: This document remains the property of Schlumberger. It is Confidential and Trade Secret

    and not to be disclosed, used, or reproduced without written approval from Schlumberger.

  • 7/25/2019 Raycap - Transient Voltage Surge Suppressor_4006895_02

    12/20

    SchlumbergerPrivate

    Page 12 of 20

    Appendix B Ferraz Shawmut I2T Destructive Test on Raycap Strikesorb TVSS Engine

    Copyright Statement: This document remains the property of Schlumberger. It is Confidential and Trade Secret

    and not to be disclosed, used, or reproduced without written approval from Schlumberger.

  • 7/25/2019 Raycap - Transient Voltage Surge Suppressor_4006895_02

    13/20

    SchlumbergerPrivate

    Page 13 of 20

    Copyright Statement: This document remains the property of Schlumberger. It is Confidential and Trade Secret

    and not to be disclosed, used, or reproduced without written approval from Schlumberger.

  • 7/25/2019 Raycap - Transient Voltage Surge Suppressor_4006895_02

    14/20

    SchlumbergerPrivate

    Page 14 of 20

    Copyright Statement: This document remains the property of Schlumberger. It is Confidential and Trade Secret

    and not to be disclosed, used, or reproduced without written approval from Schlumberger.

  • 7/25/2019 Raycap - Transient Voltage Surge Suppressor_4006895_02

    15/20

    SchlumbergerPrivate

    Page 15 of 20

    Appendix C - 40-380 Module Test Acceptance & Summary

    Copyright Statement: This document remains the property of Schlumberger. It is Confidential and Trade Secret

    and not to be disclosed, used, or reproduced without written approval from Schlumberger.

  • 7/25/2019 Raycap - Transient Voltage Surge Suppressor_4006895_02

    16/20

    SchlumbergerPrivate

    Page 16 of 20

    Copyright Statement: This document remains the property of Schlumberger. It is Confidential and Trade Secret

    and not to be disclosed, used, or reproduced without written approval from Schlumberger.

  • 7/25/2019 Raycap - Transient Voltage Surge Suppressor_4006895_02

    17/20

    SchlumbergerPrivate

    Page 17 of 20

    Appendix D 80-380 Module Test Acceptance & Summary

    Copyright Statement: This document remains the property of Schlumberger. It is Confidential and Trade Secret

    and not to be disclosed, used, or reproduced without written approval from Schlumberger.

  • 7/25/2019 Raycap - Transient Voltage Surge Suppressor_4006895_02

    18/20

    SchlumbergerPrivate

    Page 18 of 20

    Copyright Statement: This document remains the property of Schlumberger. It is Confidential and Trade Secret

    and not to be disclosed, used, or reproduced without written approval from Schlumberger.

  • 7/25/2019 Raycap - Transient Voltage Surge Suppressor_4006895_02

    19/20

    SchlumbergerPrivate

    Page 19 of 20

    Appendix E Raycap Warranty Document

    Copyright Statement: This document remains the property of Schlumberger. It is Confidential and Trade Secret

    and not to be disclosed, used, or reproduced without written approval from Schlumberger.

  • 7/25/2019 Raycap - Transient Voltage Surge Suppressor_4006895_02

    20/20

    SchlumbergerPrivate

    Page 20 of 20

    Appendix F Raycap Legal Name Changes for Strikesorb and Rayvoss

    Copyright Statement: This document remains the property of Schlumberger. It is Confidential and Trade Secret