Raritan PX Model Number: PX2-1190R Line Drawing Features · Input Plug IEC60309 2P3W 16A (L1/L2/E)...
Transcript of Raritan PX Model Number: PX2-1190R Line Drawing Features · Input Plug IEC60309 2P3W 16A (L1/L2/E)...
-
Line Drawing
Features
Input
Model Number: PX2-1190R1
Raritan PXModel Number: PX2-1190R
Energy Metering Voltage (V), Current (A), Active Power (kW), Real Power (kVA), Energy (kWh), PowerFactor
Metering Accuracy ISO/IEC 62053-21 1%
Metering per Input Line Yes
Metering per Branch Circuit Breaker Yes
Metering per Output Receptacle No
Remote Outlet Switching No
Environmental Sensor Ready Yes
Networking 10/100 BaseT Ethernet. Optional WiFi (802.11a/b/g/n)
Remote Management HTTP(s); SSH; Telnet; RS-232 (Serial); Power IQ; SNMP version v2/v3; SMTP; JSON-RPC
Cascading Yesup to (4) PDUs in a single cabinet can share a single Ethernet connection
Onboard Display3-digit user-selectable display (can be selected between Manual and Auto DisplayMode).Can display Line voltage, Line current, CB Current (if IPDU supports CBs) and Unitactive power
Compatible SensorsTemperature, Humidity, Air Flow, Static PressureSingle cable connection provides temp/humidity monitoringat three points in cabinet (with a single sensor assembly)
Input Plug IEC60309 2P3W 16A (L1/L2/E) IP44("splashproof")(230V, Single phase)
Cord Length 3 meters (9.84 feet) standard
Cord Entry Terminal block
Cable Type 2P 3W
Number of Power Cords 1
Maximum Input Current 16A (per line)
Nominal Input Voltage 230V, Single phase
Rated Input Voltage 200 - 240V, Single phase
Input Frequency 50/60Hz
Power Capacity 3.2kVA at 200V, 3.8kVA at 240V
-
Output
Physical
Environmental
Conformance
Model Number: PX2-1190R2
Nominal Output Voltage 230V
Rated Output Voltage 200 - 240V
Output Connections (8) IEC 60320 C13 2-pole, 3-wire; 10A
Overload Protection N/A
Cable Retention Raritan SecureLockTM Ready Optional retention clips are also available
Dimensions (W x D x H) 17.3" x 5.2" x 1.7" ; 440.00mm x 133.00mm x 44.00mm
Color Black powder coat
Mounting Tool-less button mount
Operating Environment 5 - 50°C (41 - 122°F)
Operating Relative Humidity 5-95%
Operating Elevation 0-10000ft
Regulatory ApprovalsCanada ICES-003, Class APart 15 Class A of the FCC rulesRoHS compliant
-
Control Panel Detail
Electrical Drawing Detail
Model Number: PX2-1190R3
-
Mechanical Diagram
Model Number: PX2-1190R4
-
Compatiable Sensors
Model Number: PX2-1190R5
Environmental
DPX-T1 : single temperature nodeDPX-T2H2 : 2 nodes: each providing both temp + humidityDPX-T3H1 : 3 temperature nodes; one also with humidityDPX-TDP1 : temperature + differential air pressureDPX-T1AF1 : temperature + air flow sensorDPX-CC2-TR : Dual contact closure sensor
©2013 Raritan Inc. All rights reserved. Raritan®, Know More. Manage Smarter.TM, Dominion® and PX® are registered trademarks ortrademarks of Raritan Inc. or its wholly owned subsidiaries. All others are registered trademarks or trademarks of their respective owners.For more information, please visit www.raritan.com
-
Line Drawing
Features
Input
Model Number: PX2-14861
Raritan PXModel Number: PX2-1486
Energy Metering Voltage (V), Current (A), Active Power (kW), Real Power (kVA), Energy (kWh), PowerFactor
Metering Accuracy ISO/IEC 62053-21 1%
Metering per Input Line Yes
Metering per Branch Circuit Breaker Yes
Metering per Output Receptacle No
Remote Outlet Switching No
Environmental Sensor Ready Yes
Networking 10/100 BaseT Ethernet. Optional WiFi (802.11a/b/g/n)
Remote Management HTTP(s); SSH; Telnet; RS-232 (Serial); Power IQ; SNMP version v2/v3; SMTP; JSON-RPC
Cascading Yesup to (4) PDUs in a single cabinet can share a single Ethernet connection
Onboard Display3-digit user-selectable display (can be selected between Manual and Auto DisplayMode).Can display Line voltage, Line current, CB Current (if IPDU supports CBs) and Unitactive power
Compatible SensorsTemperature, Humidity, Air Flow, Static PressureSingle cable connection provides temp/humidity monitoringat three points in cabinet (with a single sensor assembly)
Input Plug IEC60309 2P3W 16A (L1/L2/E) IP44("splashproof")(230V, Single phase)
Cord Length 3 meters (9.84 feet) standard
Cord Entry Terminal block
Cable Type 2P 3W
Number of Power Cords 1
Maximum Input Current 16A (per line)
Nominal Input Voltage 230V, Single phase
Rated Input Voltage 200 - 240V, Single phase
Input Frequency 50/60Hz
Power Capacity 3.2kVA at 200V, 3.8kVA at 240V
-
Output
Physical
Environmental
Conformance
Model Number: PX2-14862
Nominal Output Voltage 230V
Rated Output Voltage 200 - 240V
Output Connections (24) IEC 60320 C13 2-pole, 3-wire; 10A
Overload Protection N/A
Cable Retention Raritan SecureLockTM Ready Optional retention clips are also available
Dimensions (W x D x H) 2.1" x 1.7" x 51.1" ; 52.00mm x 43.00mm x 1298.00mm
Color Black powder coat
Mounting Tool-less button mount
Operating Environment 5 - 50°C (41 - 122°F)
Operating Relative Humidity 5-95%
Operating Elevation 0-10000ft
Regulatory ApprovalsCanada ICES-003, Class APart 15 Class A of the FCC rulesRoHS compliant
-
Control Panel Detail
Electrical Drawing Detail
Model Number: PX2-14863
-
Mechanical Diagram
Model Number: PX2-14864
-
Compatiable Sensors
Model Number: PX2-14865
Environmental
DPX-T1 : single temperature nodeDPX-T2H2 : 2 nodes: each providing both temp + humidityDPX-T3H1 : 3 temperature nodes; one also with humidityDPX-TDP1 : temperature + differential air pressureDPX-T1AF1 : temperature + air flow sensorDPX-CC2-TR : Dual contact closure sensor
©2013 Raritan Inc. All rights reserved. Raritan®, Know More. Manage Smarter.TM, Dominion® and PX® are registered trademarks ortrademarks of Raritan Inc. or its wholly owned subsidiaries. All others are registered trademarks or trademarks of their respective owners.For more information, please visit www.raritan.com
-
Line Drawing
Features
Input
Model Number: PX2-14931
Raritan PXModel Number: PX2-1493
Energy Metering Voltage (V), Current (A), Active Power (kW), Real Power (kVA), Energy (kWh), PowerFactor
Metering Accuracy ISO/IEC 62053-21 1%
Metering per Input Line Yes
Metering per Branch Circuit Breaker Yes
Metering per Output Receptacle No
Remote Outlet Switching No
Environmental Sensor Ready Yes
Networking 10/100 BaseT Ethernet. Optional WiFi (802.11a/b/g/n)
Remote Management HTTP(s); SSH; Telnet; RS-232 (Serial); Power IQ; SNMP version v2/v3; SMTP; JSON-RPC
Cascading Yesup to (4) PDUs in a single cabinet can share a single Ethernet connection
Onboard Display3-digit user-selectable display (can be selected between Manual and Auto DisplayMode).Can display Line voltage, Line current, CB Current (if IPDU supports CBs) and Unitactive power
Compatible SensorsTemperature, Humidity, Air Flow, Static PressureSingle cable connection provides temp/humidity monitoringat three points in cabinet (with a single sensor assembly)
Input PlugIEC60309 2P3W 32A (L1/L2/E) IP44("splashproof")(230V, Single phase)
Cord Length 3 meters (9.84 feet) standard
Cord Entry Terminal block
Cable Type 2P 3W
Number of Power Cords 1
Maximum Input Current 32A (per line)
Nominal Input Voltage 230V, Single phase
Rated Input Voltage 200 - 240V, Single phase
Input Frequency 50/60Hz
Power Capacity 6.4kVA at 200V, 7.7kVA at 240V
-
Output
Physical
Environmental
Conformance
Model Number: PX2-14932
Nominal Output Voltage 230V
Rated Output Voltage 200 - 240V
Output Connections a. (20) IEC 60320 C13 2-pole, 3-wire; 10Ab. (4) IEC 60320 C19 2-pole, 3-wire; 16A
Overload Protection (2) 20A 1-pole [Moeller] FAZ-C20/1-NA circuit breaker
Cable Retention Raritan SecureLockTM Ready Optional retention clips are also available
Dimensions (W x D x H) 2.1" x 2.1" x 60.6" ; 52.00mm x 53.00mm x 1539.00mm
Color Black powder coat
Mounting Tool-less button mount
Operating Environment 5 - 50°C (41 - 122°F)
Operating Relative Humidity 5-95%
Operating Elevation 0-10000ft
Regulatory ApprovalsCanada ICES-003, Class APart 15 Class A of the FCC rulesRoHS compliant
-
Control Panel Detail
Electrical Drawing Detail
Model Number: PX2-14933
-
Mechanical Diagram
Model Number: PX2-14934
-
Compatiable Sensors
Trip Curve of Circuit Breaker
Model Number: PX2-14935
Environmental
DPX-T1 : single temperature nodeDPX-T2H2 : 2 nodes: each providing both temp + humidityDPX-T3H1 : 3 temperature nodes; one also with humidityDPX-TDP1 : temperature + differential air pressureDPX-T1AF1 : temperature + air flow sensorDPX-CC2-TR : Dual contact closure sensor
0.0005
rTgni
ppi
timt
e]ces[
7200
3600
1200
600
300
120
60
30
10
5
2
1
0.5
0.2
0.1
0.05
0.02
0.005
0.01
0.002
0.001
504030201510987654321
acc. to IEC 60898-1instantaneous tripping
5454
3
12
N
N
1
2
t
nt
N
N
N
N
4
6
N3
I = 1.0 I (T=40 °C )
I = 1.35 I : t < 1 h (T=25 °C )
2.0 I : t = 12- 120 s (T=25 °C )
10 I : t < 0.1 s
20 I : t < 0.1 s
conventional non-tripping current
conventional tripping current
type C: 5 I : t > 0.1 s
type D: 10 I : t > 0.1 s
tripping characteristicacc. to UL 489 / CSA 22.2 No. 235
3
DC
Multiples of In
©2013 Raritan Inc. All rights reserved. Raritan®, Know More. Manage Smarter.TM, Dominion® and PX® are registered trademarks ortrademarks of Raritan Inc. or its wholly owned subsidiaries. All others are registered trademarks or trademarks of their respective owners.For more information, please visit www.raritan.com