Radon and earth tubesCRIIRAD / J. SYREN
CRIIRAD – ROOMS 2016 – 06/10/2016
Julien SYRENGeological engineer
Radon department manager, CRIIRAD [email protected]
Study carried out with the financial support of the Rhône-Alpes region
Radon andearth tubes
Radon etpuits canadiens

Radon and earth tubesCRIIRAD / J. SYREN
CRIIRAD – ROOMS 2016 – 06/10/2016
Operating principle of earth tube
Outsideair
Temperate air after passing
through the floor(connected to a
ventilation system)
Condensate drainHeat/Cold transferbetween ground and air
2 000 earth tubes installedin France in 2008
(LOYAU Frédéric, « Puits canadien et ventilation basse énergie », L’inédite,
2009)

Radon and earth tubesCRIIRAD / J. SYREN
CRIIRAD – ROOMS 2016 – 06/10/2016
1/ Case study : office building

Radon and earth tubesCRIIRAD / J. SYREN
CRIIRAD – ROOMS 2016 – 06/10/2016
1/ Case study : office building
a/ Preliminary surveys (march-april 2009)
First floor office : 339 Bq/m3
Double flux air handling unit (downstream earth tube and dust filter) : 684 Bq/m3

Radon and earth tubesCRIIRAD / J. SYREN
CRIIRAD – ROOMS 2016 – 06/10/2016
1/ Case study : office building
b/ Study of the ventilation system influence (summer 2009)

Radon and earth tubesCRIIRAD / J. SYREN
CRIIRAD – ROOMS 2016 – 06/10/2016
1/ Case study : office building
c/ Looking for radon sources (summer 2009)

Radon and earth tubesCRIIRAD / J. SYREN
CRIIRAD – ROOMS 2016 – 06/10/2016
1/ Case study : office building
d/ Remediation (winter-summer 2011)

Radon and earth tubesCRIIRAD / J. SYREN
CRIIRAD – ROOMS 2016 – 06/10/20162/ Tests in 11 buildings (2009-2011)
7 individual houses3 office buildings1 day nursery / leisure center
Earth tube causesradon accumulation in the building
Earth tube doesn’t causeradon accumulation in the building

Radon and earth tubesCRIIRAD / J. SYREN
CRIIRAD – ROOMS 2016 – 06/10/20162/ Tests in 11 buildings (2009-2011)
Solutions
• Seal the air leaksDrôme (building 1) : -60% (340 Bq/m3
140 Bq/m3)
• Prefer overpressure to depressionLot-et-Garonne : -70% (150/200 Bq/m3
50 Bq/m3)
• And… think to radon risk before constructingDrôme (building 1) : 1000 Bq/m3 (after earth tube) / 340 Bq/m3 (floor office)Drôme (building 2) : 80 Bq/m3 (after earth tube) / 52 Bq/m3 (floor office)Distance between 2 buildings : 150 meters

Radon and earth tubesCRIIRAD / J. SYREN
CRIIRAD – ROOMS 2016 – 06/10/2016Conclusion
PROBLEM :Depression + air leaks radon accumulationRadon sources : tubes, gaskets between tubes, condensate drain, dry wellEarth tubes can cause radon accumulation even in places where radon potential is low
SOLUTIONS :After constructing : difficult but possibleBefore constructing : betterThe most important : raise awareness of radon risk to all earth-tube stakeholders (manufacturers, professionnal or « do-it-yourself » installers)

Radon and earth tubesCRIIRAD / J. SYREN
CRIIRAD – ROOMS 2016 – 06/10/2016