SERVICE MANUAL
220-240V 50Hz
PORTABLE AIR CONDITIONER
NEW WIDETECHR
WIDETECHWIDETECH
This manual is for the use of technical personnel entrusted
with maintenance.
Widetech reserves the right to change this dehumidifier's
casing, circuit and parts without notice.
PAC-10000DB
Important points on service, and flow chart for
inspecting and repairing the unit......................... 1
Appearance(out ward)........................................ 2
Troubleshooting.................................................. 3
Functions and control panel................................. 4
Technical specifications................................. 5 - 6
Refrigerator system diagram and schematic wiring
diagram.............................................................. 7
Exploded view.................................................... 8
Parts list....................................................... 9 -11
1
PLUG AND SOCKETARE LOOSE
RE-PLUGING THEPOWER SUPPLY CORD
AIR CONDITIONERWON'T COOLPROPERLY
AIR CONDITIONERWON'T START
COMPRESSOR WON'TSTART
TIMER FAILURE
CHANGE THEPROTECTOR
RUNNING TEST
RE-CONNECTING
NO POWER
PROTECTOR FAILURE
USE OXYACETYLENE AND PLUS 5%SILVER SOLDER TO WELD THECRACKED POINTS
WIRING IS LOOSE
CAPACITOR FAILURE
CHANGE THE SWITCH
CHANGE THECAPACITOR
TESTING BYELECTROSCOPE
POWER TRIPPEDCHECK THE POWERSWITCH
REFRIGERANTLEAKAGE
TROUBLE SHOOTINGTHE SYSTEM
RUNNING THE VACUUMEVACUATION FOR MORETHAN 15 MINUTES
CHANGE COOLANT ANDPROCEED RUNNING TEST
CHANGE THE AIR CONDITIONER WITH 15KG/CM2
NITROGEN GAS FROM LOW-PRESSURE SIDE ANDDETECT THE LEAKING POINT BY SOAP
Please follow these instructions carefully:Unplug the unit to avoid any danger from electric shock before disassembling the unit for repair.If there is any sound of the refrigerant circulating when in operation, avoid touching the cooling coils.If you need to perform any welding or soldering, be sure you are in a well ventilated area.
Only a qualified professional should perform any welding on the unit.When repairing the unit, the specifications listed in this manual must be strictly adheredto when replacing any components.When replacing any electrical components they should be factory approved units.
Be sure that any electrical components are properly wired and in place.
FLOW CHART FOR INSPECTING AND REPAIRING THE UNIT
IMPORTANT POINTS ON SERVICE OPERATING SAFETY
APPEARANCE(OUT WARD)
ACCESSORIESACCESSORIES
AIR FILTER
FIX TURE
APPEARANCE(OUT WARD)
FRONT SIDEFRONT SIDE
DISCHARGE GRILLE(COMPLETE)
POWER SUPPLY CORDDRAINAGE PIPE
BACK SIDEBACK SIDE
REAR COVER
HEAT EXHAUST HOSE CONNECTOR
FIX TURE
CAP
FIX TURE
control panel
Handle hole
Front panel
Caster
Air outlet
2
TROUBLESHOOTING
PROBLEM POSSIBLE CAUSE REMEDIES
The air conditionerdoesn't work
The air conditionerworks but it doesnot cool the room
The appliance is very noisy and vibrates violently
The air conditionerworks for short period only
The air conditionerswitches are off constantly
-Malfunction
-Decrease the setting temperature
-Remove any obstacles
-Provide repairment
-There is a window opened-There is a source of heat operating in the room (burner, lamp, etc.), or the room is crowded-The air filter is clogged
-The capacity of the air conditioner is not suitable for the conditions or size of the room-The evaporator is frozen
-The compressor blocking device has been loosen or the copper pipe is getting in touch with the body of the set
-The set temperature is too close to the room's temperature-There is something blocking the suction vent on the back of condenser-The fan on the condenser is blocked
-There is a power failure-The plug is not connected-The timer is unable to work-The main switch has not been pressed
-Close the window -Remove/switch off the source of heat
-Decrease the set temperature-Clean the filter
-Clean the air filter-Change the purifier filter, if necessary-Do not make the appliance operating at too low temperature(below22
-Provide repairment
-Wait for the power return-Connect the plug-Provide repairment-Press the main switch
-Turn off the appliance remove the plug and contact the service center
3
C
Fan Speed Key
: lamp is on when in cooling mode
Set-up of Function key Temperature & Timer set-up keyTemperature & Timer set-up key
. Time on or Time off mode:
Timer setting.(1-12 Hours)
. Cooling or Dehumidification mode:
Temperature setting.(16~32 )
Power Key
On / Off
On / Off Timer KeyOn / Off Timer Key
In running mode : Auto switch offIn standby mode: Auto switch on
Full-Tank Indicator
See the troubleshooting
when the lamp is on.
Operation of PAC-10000DB(10000 B.T.U.)
OperationOperation
1. Make sure power cord is properly connected.
(Standby)
2. Press " On / Off " key.
3. Setup function key to " Fan "
4. Select proper fan speed by actual situation.
A. Auto switch off
1) To be operated in cooling or fan mode.
2) Press " Auto on / off " key for machine's
stopping operation after 1,2,3,......,12 hours .
B. Auto switch on
1) Be sure that machine is in standby mode.
( power cord is securely plugged )
2) Press " Auto on / off " key for machine's
starting operation after 1,2,3,.....,12 hours.
Air conditioning
NAME OF THE PARTSNAME OF THE PARTS
Symbols Operation procedure
Easy operation
1. Make sure power cord is properly connected.
(Standby)
2. Press " On / Off " key .
3. Setup function key to " air conditioning " if necessary.
4. Select proper fan speed by actual situation if necessary.
Fan mode
Operation procedure for auto switch on/off
:HIGH :MED :LOW
: lamp is on when in fan mode
: lamp is on when in dehumidification mode
3 42
4
TECHNICAL SPECIFICATIONS
AIR CONDITIONER
ITEM UNIT
OUTER DIMENSION
RATED VOLTAGE
RUNNING VOLTAGE
COOLING CAPACITY
DEHUMIDIFYINGCAPACITY
RUNNING CURRENT
POWERCONSUMPTION
INDOOR AIR VOLUME
COMPRESSOR
MODEL
OUTPUTPOWER
OPERATINGCYCLE
PROTECTOR
MODEL
INPUTPOWER
TURBINEFAN MOTOR
CAPILLARY
CONDENSER
REFRIGERANT
WEIGHT
REFERENTIAL USINGAREA
2
mm
m
V/Hz
V
B.T.U.
L/H
A
W
m/hr
W
uF/V
A
mm
uF/V
R22/g
3
APPLICABLE AMBIENTTEMPERATURE
524W*897H*347D
220~240/50
198 264
1035
420
18 35
KETC154ELBABA
950~975
25/450
16.5
WA90S2
12
1.5/450
2.6(O.D.)*1.4(I.D.)*950(L)
2R13S16FPI
PAC-10000DB
10000
Kg
13 19
1.8
440
MRA90255-9079
32
OPERATINGCYCLE
MODEL
OUTPUTPOWER
INDOORMOTOR
W
uF/V
WTC-13G
30
1/400OPERATINGCYCLE
MODEL
OUTPUTPOWER
OUTDOORMOTOR W
WTC-43G
43
EVAPORATOR 2R11S17FPI
W
LOCKEDROTOR AMPS
4.71
5
TECHNICAL SPECIFICATIONS
AIR CONDITIONER
ITEM UNIT
OUTER DIMENSION
RATED VOLTAGE
RUNNING VOLTAGE
COOLING CAPACITY
DEHUMIDIFYINGCAPACITY
RUNNING CURRENT
POWERCONSUMPTION
INDOOR AIR VOLUME
COMPRESSOR
MODEL
OUTPUTPOWER
OPERATINGCYCLE
PROTECTOR
MODEL
INPUTPOWER
TURBINEFAN MOTOR
CAPILLARY
CONDENSER
REFRIGERANT
WEIGHT
REFERENTIAL USINGAREA
2
mm
m
V/Hz
V
B.T.U.
L/H
A
W
m/hr
W
uF/V
A
mm
uF/V
3
APPLICABLE AMBIENTTEMPERATURE
460W*780H*320D
220~240/50
207 253
900
320
18 35
WA90S2
12
1.5/450
2R13S16FPI
PAC-10000DB
9000
Kg
13 19
1.6
440
AIR CONDITIONER
32
OPERATINGCYCLE
MODEL
OUTPUTPOWER
INDOORMOTOR
W
uF/V
WTC-13G
30
1/400OPERATINGCYCLE
MODEL
OUTPUTPOWER
OUTDOORMOTOR W
WTC-43G
43
EVAPORATOR 2R11S17FPI
W
NK134PL12C
738/762
25/370
19
2.6(O.D.)*1.4(I.D.)*600(L)
MRA12012-12026
R407c/g
LOCKEDROTOR AMPS
5.0
6
EVAPORATOR
INDOORRADIATOR DRUM
INDOOR MOTOR
INDOORRADIATOR FAN
OUTDOORRADIATOR DRUM
OUTDOORMOTOR
OUTDOORRADIATOR FAN
STRIKE WATER MOTOR
WATER PADDIE
AIR FILTER
CONDENSOR
CAPILLARY
LIQUIDACCUMULATOR
COMPRESSOR
SCHEMATIC WIRING DIAGRAM
REFRIGERATOR SYSTEM DIAGRAM
PAC-10000DB
7
T01(NATURE)
63
4942 37 3635 30 5928
27
32
34
41
46
38
29
23
20
26
22
21
19
25
24
15
17
31
141121311
4
6
5
7
3
53
52
55
33
56
6160
47
42
16
ACCESSOR
10
40 51
41
69
EXPLODED VIEW PAC-10000DB
62
57
58
64 68 67
44
45
65
66
43
2
70
72
74
71
75
73
39
48
54
18
9
8
50
OPTION
8
PARTS LIST
MATERIAL CODE PARTS NAME QUANTITYNO
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
BASE PAN ASS'Y
TURING WHEEL
DRAIN BUCKET
DRAIN BUCKET COVER
RENK
FLOAT
MICRO SWITCH
DRAINAGE PIPE
SOFT CAP
DRAINAGE PAN
FAN MOTOR
BLADE
STRIKE
COMPRESSOR ASS'Y
CONDENSER
STRAINER COMPLETE
SERVICE TUBE
DISCHARGE PIPE
SUCTION PIPE
STRIKE
STRIKE
FAN MOTOR
FAN CASING
FAN CASING
BLOWER WHEEL
CAPACITOR
PLATE
DRAINAGE PAN
TERMINAL BLOCK
EVAPORATOR
CAPILLARY TUBE
STRIKE
STRIKE
FAN MOTOR
FAN CASING
A4802-010
A7402-010
A5401-010-A-11
A5408-010-H-11
A5410-010-A-11
A5404-010
A2506-020
V02P11-100
A7307-010
A5001-070-A-11
A3000-430
A5311-030-A-22
A5802-410
A3202-080
A3404-140
A3408-010
A6202-010
A6208-390
A6227-510
A5802-070
A5802-080
A3000-360
A5301-070-A-22
A5301-090-A-22
A5304-050-A-22
A2509-320
A5700-010
A5001-110-P-22
A2525-010
A3400-130
A6204-220
A5802-030
A5802-040
A3000-330
A5301-110-A-22
1
2
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
PRICE
9
NO
36
37
38
39
40
41
42
43
44
45
46
47
48
49
50
51
52
53
54
55
56
57
58
59
60
61
62
63
64
65
66
67
68
69
70
PARTS LIST
1
1
1
1
1
2
2
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
2
2
1
1
1
1
1
1
1
1
A5301-130-A-22
A5304-070-A-22
A2509-060
A2525-020
A5900-010
A5802-020
A5802-010
A4254-150-A-BS
A6931-190-Z
A2520-120
A2516-160
A3700-200
A6102-050-A-BS
A2509-080
A5700-020
A4211-130-A-BS
A4211-150-A-BS
A4238-090-A-BS
A4201-130-A-BS
A6102-070-A-BS
A5805-030-A-BS
A4219-130-A-BS
A7301-070-A-BS
A7315-010-A-BS
A6101-090-A-BS
A7402-030
A4206-110-A-BS
A6200-010
A5812-010-H-BS
A5700-100
A5700-110
A5815-050-A-BS
A6101-010-H-BS
A2529-080
A7010-090
FAN CASING
BLOWER WHEEL
CAPACITOR
TERMINAL BLOCK
TOP BOARD
STRIKE
STRIKE
CONTROL PLATE
PC BOARD
CONTROL BOARD
POWER SUPPLY CORD COMPLETE
SCREW TOP COVER
CONTROL PANEL
CAPACITOR
PLATE
SIDE PLATE
SIDE PLATE
DISCHARGE GRILLE
FRONT PANEL
SCREW TOP COVER
FIX TURE
REAR COVER
AIR FILTER
FILTER FRAME
CAP
TURING WHEEL
TOP COVER PLATE
HEAT EXHAUST HOSE CONNECTOR
FIX TURE
PLATE
PLATE
FIX TURE
CAP
REMOTE CONTROL
CARTON
MATERIAL CODE PARTS NAME QUANTITY PRICE
10
PARTS LIST
1
1
1
1
1
A7012-580
A7107-250
A7107-260
A7107-270
A7105-120
CARTON
SHOCK ABSORBER
SHOCK ABSORBER
SCREW TOP COVER
CARTON BASE
NO
71
72
73
74
75
MATERIAL CODE PARTS NAME QUANTITY PRICE
11