0212 BU-SB11645 Page 1 of 11 Data Sheet: 1171 Quik-SpecCoordination Panelboard - Data Sheet 600A - 1200A Fusible Panelboards Contents Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2 Enclosure Types and Voltages/Systems . . . . . . . . . . . . . . . . . .3 Main, Sub-Feed & Feed Through Lug Specifications . . . . . . . .4 Neutral and Ground Assemblies . . . . . . . . . . . . . . . . . . . . . . .5 Typical Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .6 Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .7-8 Replacement Parts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .9-10 Fuse & Disconnect Performance Data . . . . . . . . . . . . . . . . . .11 Low-Peak CUBEFuse Fuse Specifications . . . . . . . . . . . . . . .11

Transcript of Quik-Spec Coordination Panelboard - Data Sheet€¦ · ccpb-2-15cf 2 1-15 15 tcf6rn, tcf10rn,...

Page 1: Quik-Spec Coordination Panelboard - Data Sheet€¦ · ccpb-2-15cf 2 1-15 15 tcf6rn, tcf10rn, tcf10, fcf6rn, fcf10rn, ccpb-3-15cf 3 tcf15rn tcf15 fcf15rn ccpb-1-20cf 1 tcf17-1⁄

0212 BU-SB11645 Page 1 of 11 Data Sheet: 1171

Quik-Spec™ Coordination Panelboard - Data Sheet600A - 1200A Fusible Panelboards

Contents

Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2

Enclosure Types and Voltages/Systems . . . . . . . . . . . . . . . . . .3

Main, Sub-Feed & Feed Through Lug Specifications . . . . . . . .4

Neutral and Ground Assemblies . . . . . . . . . . . . . . . . . . . . . . .5

Typical Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .6

Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .7-8

Replacement Parts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .9-10

Fuse & Disconnect Performance Data . . . . . . . . . . . . . . . . . .11

Low-Peak CUBEFuse Fuse Specifications . . . . . . . . . . . . . . .11

Page 2: Quik-Spec Coordination Panelboard - Data Sheet€¦ · ccpb-2-15cf 2 1-15 15 tcf6rn, tcf10rn, tcf10, fcf6rn, fcf10rn, ccpb-3-15cf 3 tcf15rn tcf15 fcf15rn ccpb-1-20cf 1 tcf17-1⁄

0212 BU-SB11645 Page 2 of 11 Data Sheet: 1171

Catalog Symbol: QSCP12Description:

Fuseible panelboards for commercial/industrial branch or service entranceapplications on systems up through 600Vac.

The QSCP is specifically designed to address the NEC® Selective CoordinationRequirements for Emergency, Legally Required Standby, Healthcare EssentialElectrical and Critical Operation Power Systems (COPS) per NEC® 700.27,701.18, 517.26 and 708.54. Not for applications requiring AFCI protected circuits. The QSCP is configured to order for the application. To confirm availability of options and constructions, contact your Cooper Bussmann distributor.Ratings:

Volts: 600Vac (or less), 125VdcAmps: 600, 800, 1200ASCCR: 20kA or 100kA @125Vdc - See Panelboard

Short-Circuit Current Ratings table for AC ratings

Agency Information:• UL 67 – Standard for panelboards• UL 50/UL 50E – Enclosures for electrical equipment• CSA 22.2, No. 29-M1989 – Panelboards and enclosed panelboards• UL Listed, Class CTL panelboard (meets 2002 NEC® 408.15 limit of

42 overcurrent devices per panel)• U.B.C. and C.B.C. Seismic Qualified, and I.B.C. Approved

Main Options:• Main Lug Only (MLO)

Branch Disconnect Options:• 1-, 2- and 3-Pole 15, 20, 30, 40, 50, 60, 70, 90, 100, 200, 400

and 600A rejecting branch disconnects (see table for details).Branch ampacity on 125Vdc panels limited to CCPB 80A or less.

Neutral Options:• Unbonded & Bonded 600, 800, 1200, 1600 and 2400A

Ground Options:• Isolated & Non-isolated

Enclosures:• NEMA 1

Spare Fuse Compartment:• Standard on all models

CCPB Horsepower Ratings:

FFuussee MMaaxx TTiimmee--DDeellaayy TTiimmee--DDeellaayy FFaasstt--AAccttiinnggBranch* Part Amp CCPB Non-Indicating Indicating Non-IndicatingNumber Poles Range Ampacity Fuses Fuses** FusesCCPB-1-15CF 1 TCF1RN, TCF3RN, TCF6 FCF1RN, FCF3RN,CCPB-2-15CF 2 1-15 15 TCF6RN, TCF10RN, TCF10, FCF6RN, FCF10RN,CCPB-3-15CF 3 TCF15RN TCF15 FCF15RNCCPB-1-20CF 1 TCF17-1⁄2RN, TCF17-1⁄2,CCPB-2-20CF 2 171⁄2-20 20 TCF20RN TCF20 FCF20CCPB-3-20CF 3CCPB-1-30CF 1 TCF25RN, TCF25, FCF25RN,CCPB-2-30CF 2 25-30 30 TCF30RN TCF30 FCF30RNCCPB-3-30CF 3CCPB-1-40CF 1 TCF35RN, TCF35, FCF35RN,CCPB-2-40CF 2 35-40 40 TCF40RN TCF40 FCF40RNCCPB-3-40CF 3CCPB-1-50CF 1 TCF45RN, TCF45, FCF45RN,CCPB-2-50CF 2 45-50 50 TCF50RN TCF50 FCF50RNCCPB-3-50CF 3CCPB-1-60CF 1CCPB-2-60CF 2 60 60 TCF60RN TCF60 FCF60RNCCPB-3-60CF 3CCPB-1-70CF 1CCPB-2-70CF 2 70 70 TCF70RN TCF70 FCF70RNCCPB-3-70CF 3CCPB-1-90CF 1

TCF80RN TCF80 FCF80RNCCPB-2-90CF 2 80-90 90

TCF90RN TCF90 FCF90RNCCPB-3-90CF 3CCPB-1-100CF 1CCPB-2-100CF 2 100 100 TCF100RN TCF100 FCF100RNCCPB-3-100CF 3

LPJ-110SP, LPJ-125SP, LPJ-110SPI, LPJ-125SPI, JKS-110, JKS-125,CFD200J03 3*** 110-200 200 LPJ-150SP, LPJ-175SP, LPJ-150SPI, LPJ-175SPI, JKS-150, JKS-175,

LPJ-200SP LPJ-200SPI JKS-200LPJ-225SP, LPJ-250SP, LPJ-225SPI, LPJ-250SPI, JKS-225, JKS-250,

CFD400J03 3*** 225-400 400 LPJ-300SP, LPJ-350SP, LPJ-300SPI, LPJ-350SPI, JKS-300, JKS-350,LPJ-400SP LPJ-200SPI JKS-400

LPJ-450SP, LPJ-500SP, LPJ-450SPI, LPJ-500SPI, JKS-450, JKS-500,CFD600J03 3*** 450-600 600LPJ-600SP LPJ-600SPI JKS-600

*CCPB disconnect can accept CUBEFuses with amp ratings less than or equal to the amp rating of the CCPB disconnect.**Correct fit with CCPB disconnect requires time-delay CUBEFuses with date code R38 or later.*** 3-Pole switch used for 1 and 2-pole applications

Panelboard Short-Circuit Current Ratings:

Amp Hp Rating @ VacCCPB Disconnect Rating 120 240 480 600CCPB-(Poles)-15CF 15 0.5 3 5 7.5CCPB-(Poles)-20CF 20 0.75 3 7.5 10CCPB-(Poles)-30CF 30 1.5 5 15 10CCPB-(Poles)-40CF 40 2 7.5 20 10CCPB-(Poles)-50CF 50 3 7.5 20 10CCPB-(Poles)-60CF 60 3 7.5 20 10CCPB-(Poles)-70CF 70 3 15 30 40CCPB-(Poles)-90CF 80 5 20 40 50CCPB-(Poles)-100CF 100 5 20 50 50CFD200J03 200 – 60 125 150CFD400J03 400 – 125 250 350CFD600J03 600 – 200 400 500

Branch Disconnects:

Panelboard Short-Circuit Current RatingsAC Main Options DC

Main MainLug Only Lug Only

SCCR (MLO)* (MLO)*High 200kA 100kAStd. 50kA 20kA

* For panelboards with subfeed main lugs, or panelboards withoptional feed-through lugs, Class J, T or R fuses are required upstream – max amps = panel amps.

Page 3: Quik-Spec Coordination Panelboard - Data Sheet€¦ · ccpb-2-15cf 2 1-15 15 tcf6rn, tcf10rn, tcf10, fcf6rn, fcf10rn, ccpb-3-15cf 3 tcf15rn tcf15 fcf15rn ccpb-1-20cf 1 tcf17-1⁄

0212 BU-SB11645 Page 3 of 11 Data Sheet: 1171

Enclosure Types

NEMA 1

• Floor mount

• Galvanized steel with blank end walls

• Box sizes: 27” W x 15” D x 65”/ 38˝ W x 15˝ D x 65˝ or 89˝ H

• Enclosure and chassis mounting instructions are found in literaturesupplied with unit

• Chassis mounts directly onto studs in the enclosure

• Trim finished with gray powder coat paint over phosphatized steel (ANSI 61)

• Circuit directory card is located on the inside of the door

AC & DC Voltages & System Types

Three-PhaseSingle-Phase

Busing

Tin-plated copper with sufficient cross section to meet UL 67 temperature riserequirements.

Distributed 1- & 3-Phase Busing

All CCPB branch disconnects can be mounted in any branch circuit position.

1-Phase, 3 Wire• 120/240V 1-Phase, 3 Wire

1-Phase, 2 Wire• 120V 1-Phase, 2 Wire• 240V 1-Phase, 2 Wire

1-Phase, 2 Wire, Wye• 277V 1-Phase, 2 Wire

1-Phase, 2 Wire, Delta• 480V 1-Phase, 2 Wire

1-Phase, 3 Wire, Delta• 240/480V 1-Phase, 3 Wire

3-Phase, 4 Wire, Wye• 208Y/120V 3-Phase, 4 Wire• 480Y/277V 3-Phase, 4 Wire• 600Y/347V 3-Phase, 4 Wire

1-Phase, 3 Wire, Wye• 208Y/120V 1-Phase, 3 Wire• 480Y/277V 1-Phase, 3 Wire

3-Phase, 4 Wire, Delta• 240/120V 3-Phase, 4 Wire• 480/240V 3-Phase, 4 Wire

3-Phase, 3 Wire, Delta• 240V 3-Phase, 3 Wire• 480V 3-Phase, 3 Wire• 600V 3-Phase, 3 Wire• 240V 3-Phase, 3 Wire, Grounded B• 480V 3-Phase, 3 Wire, Grounded B• 600V 3-Phase, 3 Wire, Grounded B

A B

N

C

A

BC

AN

BC

AB

N

C

A

BNC

A

BC

B

N

C

A

DC Voltage1-Phase, 2 Wire

• 125Vdc, 2 Wire

(Up to 125Vdc, MLO optiononly, CCPB 80A or less)

AC Voltages

N +125Vdc

Page 4: Quik-Spec Coordination Panelboard - Data Sheet€¦ · ccpb-2-15cf 2 1-15 15 tcf6rn, tcf10rn, tcf10, fcf6rn, fcf10rn, ccpb-3-15cf 3 tcf15rn tcf15 fcf15rn ccpb-1-20cf 1 tcf17-1⁄

0212 BU-SB11645 Page 4 of 11 Data Sheet: 1171

Main Sub-Feed Mechanical LugsWWiirree RRaannggee // TToorrqquuee LLbb--IInn ((NN••mm))

• 300kcmil - 6AWG / 275 (31)WWiirree RRaattiinngg:: 60/75°C, Cu-Al

Main Sub-Feed Mechanical LugsMain Barrier Cover OpenWWiirree RRaannggee // TToorrqquuee LLbb--IInn ((NN••mm))• 600kcmil-2AWG/375(42)WWiirree RRaattiinngg:: 60/75°C, Cu-Al

Main Compression (Crimp) Lugs*WWiirree RRaannggee

• 300kcmil-4AWGWWiirree RRaattiinngg:: 60/75°C, Cu-Al

Main Compression (Crimp) Lugs*Main Barrier Cover OpenWWiirree RRaannggee• 600-250kcmilWWiirree RRaattiinngg:: 60/75°C, Cu-Al

Main Mechanical LugsWWiirree RRaannggee // TToorrqquuee LLbb--IInn ((NN••mm))

• 300kcmil-1AWG / 375 (42)• 2-6AWG / 275 (31)

WWiirree RRaattiinngg:: 60/75°C, Cu-Al

Main Mechanical LugsMain Barrier Cover OpenWWiirree RRaannggee // TToorrqquuee LLbb--IInn ((NN••mm))• 600kcmil-4AWG / 500 (56)WWiirree RRaattiinngg:: 60/75°C, Cu-Al

800-1200 Amp Main Lugs600 Amp Main Lugs

Feed-Through Lugs

Compression, mechanical and double (sub-feed) lugs are allavailable as feed-through lugs. Lug ampacity ratings will bebased upon panelboard ampacity rating.

* Versa-Crimp® VC-6 crimp tool recommended for wire crimping.

Main Mechanical Lugs Main Sub-Feed Mechanical Lugs Main Compression (Crimp) Lugs*

Page 5: Quik-Spec Coordination Panelboard - Data Sheet€¦ · ccpb-2-15cf 2 1-15 15 tcf6rn, tcf10rn, tcf10, fcf6rn, fcf10rn, ccpb-3-15cf 3 tcf15rn tcf15 fcf15rn ccpb-1-20cf 1 tcf17-1⁄

0212 BU-SB11645 Page 5 of 11 Data Sheet: 1171

600A UnbondedWWiirree RRaannggee // TToorrqquuee LLbb--IInn ((NN••mm))• Main Terminal 600kcmil-2 AWG / 275 (31)• Branch Connections - See table belowWWiirree RRaattiinngg:: 60/75°C, Cu-AlBBaarr MMaatteerriiaall:: Copper, Tin-platedLLuugg MMaatteerriiaall:: Aluminum, Tin-plated

600A BondedWWiirree RRaannggee // TToorrqquuee LLbb--IInn ((NN••mm))• Main Terminal 600kcmil-2 AWG / 275 (31)• Branch Connections - See table belowWWiirree RRaattiinngg:: 60/75°C, Cu-AlBBaarr MMaatteerriiaall:: Copper, Tin-platedLLuugg MMaatteerriiaall:: Aluminum, Tin-plated

Isolated / Non-isolatedWWiirree RRaannggee // TToorrqquuee LLbb--IInn ((NN••mm))• Main Terminal 600kcmil-2 AWG / 275 (31)• Branch Connections - See table belowWWiirree RRaattiinngg:: 60/75°C, Cu-AlBBaarr MMaatteerriiaall:: Copper, Tin-platedLLuugg MMaatteerriiaall:: Aluminum, Tin-plated

Neutral Assemblies

Ground Assemblies

WWiirree** TToorrqquuee MMaaxx.. NNoo.. WWiirreess PPeerr OOppeenniinnggAAWWGG LLbb--IInn ((NN••mm)) NNeeuutt.. GGNNDD

≤≤110000AA BBrraanncchh14 AWG - 4 AWG 20-35 (2.3-3.9) 2 23 AWG - 2/0 AWG 35-80 (4.5-9.0) 1 1

111100 -- 220000AA BBrraanncchh6 AWG - 1/0 AWG 35-200 (3.9-22.6) 2 2

2/0 AWG - 350 kcmil 200-375 (22.6-42.0) 1 1222255 -- 440000AA BBrraanncchh

4 AWG - 3/0 AWG 35-200 (3.9-22.6) 2 24/0 AWG 200 (22.6) 1 1

250 kcmil - 600 kcmil 275-500 (31.0-56.5) 1 1445500 -- 660000AA BBrraanncchh

2 AWG - 3/0 AWG 35-200 (3.9-22.6) 2 24/0 AWG 200 (22.6) 1 1

250 kcmil - 600 kcmil 275-500 (31.0-56.5) 1 1*60/75ºC, Cu-Al.

Ground and Neutral Bars Connection Wire Torques

Page 6: Quik-Spec Coordination Panelboard - Data Sheet€¦ · ccpb-2-15cf 2 1-15 15 tcf6rn, tcf10rn, tcf10, fcf6rn, fcf10rn, ccpb-3-15cf 3 tcf15rn tcf15 fcf15rn ccpb-1-20cf 1 tcf17-1⁄

0212 BU-SB11645 Page 6 of 11 Data Sheet: 1171

Single-Phase, 2 WireMain Lug Only

NE

UTR

AL

GR

OU

ND

GR

OU

ND

NE

UTR

AL

Main Lug OnlySingle-Phase, 3 Wire

GR

OU

ND

Three-Phase, 3 WireMain Lug Only

NE

UTR

AL

GR

OU

ND

Three-Phase, 4 WireMain Lug Only

Typical Wiring

Single-Phase, 2 WireMain Lug Only

Page 7: Quik-Spec Coordination Panelboard - Data Sheet€¦ · ccpb-2-15cf 2 1-15 15 tcf6rn, tcf10rn, tcf10, fcf6rn, fcf10rn, ccpb-3-15cf 3 tcf15rn tcf15 fcf15rn ccpb-1-20cf 1 tcf17-1⁄

0212 BU-SB11645 Page 7 of 11 Data Sheet: 1171

NEMA 1 Enclosures & Interior

Page 8: Quik-Spec Coordination Panelboard - Data Sheet€¦ · ccpb-2-15cf 2 1-15 15 tcf6rn, tcf10rn, tcf10, fcf6rn, fcf10rn, ccpb-3-15cf 3 tcf15rn tcf15 fcf15rn ccpb-1-20cf 1 tcf17-1⁄

0212 BU-SB11645 Page 8 of 11 Data Sheet: 1171

NEMA 1 Enclosure Dimensions

Panel Ampacity Branch Configuration DimensionsBase Unit H W D

(18) 1-100A 65 27 15(18) 1-100A + 200A single(18) 1-100A + 200A twin

600A 200A single + 200A single 65 38 15200A single + 200A twin200A twin + 200A twin(2) 300A single 89 38 15(18) 1-100A + 200A single(18) 1-100A + 200A twin 65 38 15

800A (2) 200A twin(18) 1-100A + 400A single200A twin + 400A single 89 38 15(2) 400A single(18) 1-100A + 600A single(3) 200A twin 89 38 15200A twin + 600A single

1200A (2) 200A twin + 400A single(3) 400A single600A single + 400A single + 200A single 102 38 15600A single + 400A single + 200A twin(2) 600A single

Page 9: Quik-Spec Coordination Panelboard - Data Sheet€¦ · ccpb-2-15cf 2 1-15 15 tcf6rn, tcf10rn, tcf10, fcf6rn, fcf10rn, ccpb-3-15cf 3 tcf15rn tcf15 fcf15rn ccpb-1-20cf 1 tcf17-1⁄

0212 BU-SB11645 Page 9 of 11 Data Sheet: 1171

Quik-Spec Coordination Panelboard Replacement Parts

See list on following page for part numbers.

E

F

C

D

A

G

IB

Page 10: Quik-Spec Coordination Panelboard - Data Sheet€¦ · ccpb-2-15cf 2 1-15 15 tcf6rn, tcf10rn, tcf10, fcf6rn, fcf10rn, ccpb-3-15cf 3 tcf15rn tcf15 fcf15rn ccpb-1-20cf 1 tcf17-1⁄

0212 BU-SB11645 Page 10 of 11 Data Sheet: 1171

Replacement PartsA & B - Main Devices and Feed-Through Lugs

2A2575-1 Kit, compression lug 3 phase 600A2A2575-2 Kit, mechanical lug 3 phase 600A2A2575-3 Kit, double/sub-feed lug 3 phase 600A2A2575-4 Kit, compression lug 1 phase, 3 wire 600A2A2575-5 Kit, mechanical lug 1 phase, 3 wire 600A2A2575-6 Kit, double/sub-feed lug 1 phase, 3 wire 600A2A2575-7 Kit, compression lug 1 phase, 2 wire 600A2A2575-8 Kit, mechanical lug 1 phase, 2 wire 600A2A2575-9 Kit, double/sub-feed lug 1 phase, 2 wire 600A2A2575-10 Kit, compression lug 3 phase 800A & 1200A2A2575-11 Kit, mechanical lug 3 phase 800A & 1200A2A2575-12 Kit, double/sub-feed lug 3 phase 800A & 1200A2A2575-13 Kit, compression lug 1 phase, 3 wire 800A & 1200A2A2575-14 Kit, mechanical lug 1 phase, 3 wire 800A & 1200A2A2575-15 Kit, double/sub-feed lug 1 phase, 3 wire 800A & 1200A2A2575-16 Kit, compression lug 1 phase, 2 wire 800A & 1200A2A2575-17 Kit, mechanical lug 1 phase, 2 wire 800A & 1200A2A2575-18 Kit, double/sub-feed lug 1 phase, 2 wire 800A & 1200A

C - Ground Assemblies2A2576-1 Kit, ground non-isolated 600A2A2576-2 Kit, ground isolated 600A2A2576-3 Kit, ground non-isolated 800A2A2576-4 Kit, ground isolated 800A2A2576-5 Kit, ground non-isolated 800A2A2576-6 Kit, ground isolated 800A2A2576-7 Kit, ground non-isolated 800A2A2576-8 Kit, ground isolated 800A2A2576-9 Kit, ground non-isolated 1200A2A2576-10 Kit, ground isolated 1200A2A2576-11 Kit, ground non-isolated 1200A2A2576-12 Kit, ground isolated 1200A

D - Neutral Assemblies2A2577-1 Kit, neutral unbonded 600A for 600A panel2A2577-2 Kit, neutral bonded 600A for 600A panel2A2577-3 Kit, neutral unbonded 1200A for 600A panel2A2577-4 Kit, neutral bonded 1200A for 600A panel2A2577-5 Kit, neutral unbonded 800A for 800A panel2A2577-6 Kit, neutral bonded 800A for 800A panel2A2577-7 Kit, neutral unbonded 1600A for 800A panel2A2577-8 Kit, neutral bonded 1600A for 800A panel2A2577-9 Kit, neutral unbonded 800A for 800A panel2A2577-10 Kit, neutral bonded 800A for 800A panel2A2577-11 Kit, neutral unbonded 1600A for 800A panel2A2577-12 Kit, neutral bonded 1600A for 800A panel2A2577-13 Kit, neutral unbonded 800A for 800A panel2A2577-14 Kit, neutral bonded 800A for 800A panel2A2577-15 Kit, neutral unbonded 1600A for 800A panel2A2577-16 Kit, neutral bonded 1600A for 800A panel2A2577-17 Kit, neutral unbonded 1200A for 1200A panel2A2577-18 Kit, neutral bonded 1200A for 1200A panel2A2577-19 Kit, neutral unbonded 2400A for 1200A panel2A2577-20 Kit, neutral bonded 2400A for 1200A panel

D - Neutral Assemblies - (continued)2A2577-21 Kit, neutral unbonded 1200A for 1200A panel2A2577-22 Kit, neutral bonded 1200A for 1200A panel2A2577-23 Kit, neutral unbonded 2400A for 1200A panel2A2577-24 Kit, neutral bonded 2400A for 1200A panel2A2577-25 Kit, neutral unbonded 600A for 600A panel2A2577-26 Kit, neutral bonded 600A for 600A panel2A2577-27 Kit, neutral unbonded 1200A for 600A panel2A2577-28 Kit, neutral bonded 1200A for 600A panel

E - Enclosures (Box only, does not include doors)2A2400-1 NEMA 1, 38x65x152A2400-2 NEMA 1, 38x89x152A2400-3 NEMA 1, 27x65x152A2400-4 NEMA 1, 38x102x15

F - Dead Fronts - Branch Enclosure (1-100A Branches)2A2578-1 Kit, branch enclosure 38" wide panels2A2578-2 Kit, branch enclosure 27" wide panels

G - Latch for Spare Fuse Compartment2A1910-5 Kit, Spare Fuse Compartment Latch

Lockout/Tagout Devices2A1912-1 Kit, lockout 200A - 400A branch2A1912-3 Kit, lockout 1-100A branch

Miscellaneous2A1914 Kit, circuit directory card and sleeve2A1915 Kit, circuit number and fuse rating labels (1-100A

branches)2A1917-2 Kit, CCPB hardware (10 screws)2A1917-3 Kit, panelboard hardware2A1918-1 Kit, branch filler plates 1-60A2A1918-2 Kit, branch filler plates 70-100A2A1919 Kit, touch up paint2A1961-1 Kit, Spare Fuse Compartment TCF1-100A

Page 11: Quik-Spec Coordination Panelboard - Data Sheet€¦ · ccpb-2-15cf 2 1-15 15 tcf6rn, tcf10rn, tcf10, fcf6rn, fcf10rn, ccpb-3-15cf 3 tcf15rn tcf15 fcf15rn ccpb-1-20cf 1 tcf17-1⁄

0212 BU-SB11645 Page 11 of 11 Data Sheet: 1171

J - Branch Fuses for CCPB Disconnects

PPoolleess AApppplliiccaabbllee FFuussee AAmmppaacciittiieess PPaarrtt NNuummbbeerr1-Pole CCPB-1-(amp)CF2-Pole 15A, 20A, 30A, 40A, CCPB-2-(amp)CF3-Pole 50A, 60A, 70A, 90A, 100A CCPB-3-(amp)CF

3-Pole 110A, 125A, 150A, 175A, CFD200J03*200A

3-Pole 225A, 250A, 300A, 250A, CFD400J03*400A

3-Pole 450A, 500A, 600A CFD600J03**3-pole switch for 1- and 2-pole applications

NNoonn--IInnddiiccaattiinngg IInnddiiccaattiinngg** FFaasstt--AAccttiinnggTTiimmee--DDeellaayy TTiimmee--DDeellaayy NNoonn--IInnddiiccaattiinngg

FFoorr CCCCPPBB**** PPaarrtt NNuummbbeerr TTCCFF((aammppss))RRNN TTCCFF((aammppss)) FFCCFF((aammppss))RRNNTCF1RN, TCF3RN, TCF6 FCF1RN, FCF3RN,

CCPB-(# of Poles)-15CF TCF6RN, TCF10RN TCF10 FCF6RN, FCF10RNTCF15RN TCF15 FCF15RN

CCPB-(# of Poles)-20CF TCF17-1/2RN TCF17-1/2TCF20RN TCF20 FCF20RN

CCPB-(# of Poles)-30CF TCF25RN TCF25 FCF25RNTCF30RN TCF30 FCF30RN

CCPB-(# of Poles)-40CF TCF35RN TCF35 FCF35RNTCF40RN TCF40 FCF40RN

CCPB-(# of Poles)-50CF TCF45RN TCF45 FCF45RNTCF50RN TCF50 FCF50RN

CCPB-(# of Poles)-60CF TCF60RN TCF60 FCF60RNCCPB-(# of Poles)-70CF TCF70RN TCF70 FCF70RN

CCPB-(# of Poles)-90CF TCF80RN TCF80 FCF80RNTCF90RN TCF90 FCF90RN

CCPB-(# of Poles)-100CF TCF100RN TCF100 FCF100RN* Correct fit with CCPB disconnect requires indicating CUBEFuse with date code R38 or later.

CCllaassss JJ DDiissccoonnnneecctt NNoonn--IInnddiiccaattiinngg IInnddiiccaattiinngg NNoonn--IInnddiiccaattiinnggPPaarrtt NNuummbbeerr TTiimmee--DDeellaayy TTiimmee--DDeellaayy FFaasstt--AAccttiinngg

LPJ-110SP, LPJ-110SPI, JKS-110,LPJ-125SP, LPJ-125SPI, JKS-125,

CFD200J03* LPJ-150SP. LPJ-150SPI, JKS-150,LPJ-175SP, LPJ-175SPI, JKS-175,LPJ-200SP LPJ-200SPI JKS-200LPJ-225SP, LPJ-225SPI, JKS-225,LPJ-250SP, LPJ-250SPI, JKS-250,

CFD400J03* LPJ-300SP. LPJ-300SPI, JKS-300,LPJ-350SP, LPJ-350SPI, JKS-350,LPJ-400SP LPJ-400SPI JKS-400LPJ-450SP, LPJ-450SPI, JKS-450,

CFD600J03* LPJ-500SP, LPJ-500SPI, JKS-500,LPJ-600SP. LPJ-600SPI, JKS-600,

*3-Pole switch used for 1- and 2-pole applications.

I - CCPB Branch Disconnects

Branch Disconnects and Fuse Replacement Parts Fuse & Disconnect Performance Data

For details and specifications, access the following data sheets online atwww.cooperbussmann.com/DatasheetsEle.

DDaattaa SShheeeettPPrroodduucctt NNuummbbeerr

Low-Peak Time-Delay CUBEFuse 9000

Fast-Acting CUBEFuse 2147

Low-Peak LPJ-_SPI Class J fuses 1063

Limitron JKS Class J Fuses 1026 & 1027

CCPB Branch Disconnect 1161

Additional Reference

Additional information is available online at:• Selective Coordination (www.cooperbussmann.com/SelectiveCoordination)

The only controlled copy of this Data Sheet is the electronic read-only version located on the Cooper Bussmann Network Drive. All other copies of this documentare by definition uncontrolled. This bulletin is intended to clearly present comprehensive product data and provide technical information that will help the end userwith design applications. Cooper Bussmann reserves the right, without notice, to change design or construction of any products and to discontinue or limit distribution of any products. Cooper Bussmann also reserves the right to change or update, without notice, any technical information contained in this bulletin.Once a product has been selected, it should be tested by the user in all possible applications.

J - Branch Fuses for Class J Disconnects