Quality install testing procedures for forced air systems

32
Quality Install Testing Procedures for Forced Air Systems

Transcript of Quality install testing procedures for forced air systems

Page 1: Quality install testing procedures for forced air systems

Quality Install Testing Procedures for Forced Air

Systems

Page 2: Quality install testing procedures for forced air systems

Quality Installation: Outcomes

• Installation practices have links to • Comfort• Humidity Levels (dehumidification)• Reduced Utility Consumption • Reduced Utility Consumption • Indoor Air Quality

Page 3: Quality install testing procedures for forced air systems

Why Test?

• SEER reduced when airflow not correct• High Static = more power draw on ECMs• ECMs start to draw more power at .8” wc• Must know system performance to • Must know system performance to

consider ECM upgrade

Page 4: Quality install testing procedures for forced air systems

Why Test?

• Coils, filters, ductwork (flexible lines worst), registers all add to Total External Static Pressure (TESP)

• High static pressure makes more noise• High static pressure makes more noise• Flow directly effects comfort• No test is just a guess

Page 5: Quality install testing procedures for forced air systems

Two Main Tests

• Total External Static Pressure• Air Flow CFM

Page 6: Quality install testing procedures for forced air systems

What is Rated TESP?

Page 7: Quality install testing procedures for forced air systems

What is TESP?

All components add resistance. Too much

restricts flow.

Page 8: Quality install testing procedures for forced air systems

Testing TESPStatic Pressure Tube and Manometer

Page 9: Quality install testing procedures for forced air systems

Testing TESPPitot Tube and Manometer

Page 10: Quality install testing procedures for forced air systems

Testing TESP (Heat Only)

• TESP = top of heat exchanger to bottom of blower (after filter)

• Pressure Drop = • Pressure Drop = change over a distance (AC coil, filter, etc.

• Check rating (includes coil? Filter?)

Page 11: Quality install testing procedures for forced air systems

Testing TESP Rooftop units

• TESP = Supply and return

• Pressure Drop = change over a distance change over a distance (AC coil, filter, etc.

• Rated TESP, coil included in package units.

Page 12: Quality install testing procedures for forced air systems

Testing TESP

• TESP = Add two numbers together

• Pressure Drop = subtract numbers subtract numbers (ignore ± sign)

Page 13: Quality install testing procedures for forced air systems

TESP Results

• Think Golf and Blood Pressure• Lower is better• High numbers indicate a problem• And a need for…more practice, exercise • And a need for…more practice, exercise

and tweaking the system

Page 14: Quality install testing procedures for forced air systems

Example w/no and dirty filter

• 10 After coil • 4 Before Filter• 10 After Filter• 70 Before Coil

• 6 After coil • 4 Before Filter• 52 After Filter• 43 Before Coil • 70 Before Coil

• **TESP = 80• **∆P Coil = 62• ∆P Filter = 2

• 43 Before Coil • ***TESP total = 95• ∆P Coil = 38• **∆P Filter = 48

Page 15: Quality install testing procedures for forced air systems

Testing Air Flow (CFM)

• Static Pressure affects air flow• Air flow determines efficiency• Need air flow to set refrigerant• Need 400~ cfm per ton of cooling• Need 400~ cfm per ton of cooling• Need to know # of tons

Page 16: Quality install testing procedures for forced air systems

Testing Air FlowTrue Flow Meter®

Page 17: Quality install testing procedures for forced air systems

True Flow Meter®

• Energy Conservatory, MN Manufacturer• Advantages: very accurate, fairly easy to

set up• Disadvantages: Equipment can be • Disadvantages: Equipment can be

expensive, needs filter slot that fits plates, can be effected by poor duct design

Page 18: Quality install testing procedures for forced air systems

True Flow Meter®

• Install in filter slot• Meter automatically averages flow rates• Needs manometer (pressure gauge)

Page 19: Quality install testing procedures for forced air systems

Testing Air FlowHot Wire or Mini-Vane Anenometer

Page 20: Quality install testing procedures for forced air systems

Hot Wire or Mini Vane

• Advantages: Fast and east to use, accurate (when compared to True Flow meter)

• Disadvantages: Cost, need linear section • Disadvantages: Cost, need linear section of duct

Page 21: Quality install testing procedures for forced air systems

Hot Wire or Mini Vane

• Drill holes in duct• Take readings• Meter automatically calculates flow rates

Page 22: Quality install testing procedures for forced air systems

Testing Air FlowHotwire or Mini-Vane Anenometer

Page 23: Quality install testing procedures for forced air systems

TESP

• Advantages: Low cost, Quick and easy (if table available), good for troubleshooting

• Disadvantages: Fan tables sometimes not available (can use generic), duct available (can use generic), duct configurations may cause turbulence

Page 24: Quality install testing procedures for forced air systems

TESP

• Take readings• Know fan speed setting, rated TESP• Match readings off fan table to find CFM

Page 25: Quality install testing procedures for forced air systems

Fan Table

Page 26: Quality install testing procedures for forced air systems

Potential Problems Found

Restrictive filter (up to 50% drop in flow) Restrictive designer registers

Page 27: Quality install testing procedures for forced air systems

Potential Problems Found

Dirty AC Coils Owner did not know it existed

Page 28: Quality install testing procedures for forced air systems

Potential Problems Found

Dirty Fan Blades Leaky Ductwork

Page 29: Quality install testing procedures for forced air systems

Possible Solutions

• Less restrictive filters• Regular filter changes, maintenance • Curved ductwork, turning vanes• Registers with free air • Registers with free air • Smooth ductwork, not flex duct• Proper sizing of ductwork• Sealing ductwork

Page 30: Quality install testing procedures for forced air systems

Challenges

• Additional testing often means more cost• Additions to ductwork can add cost to

proposal• “Low Bid” vs. most responsible bid• “Low Bid” vs. most responsible bid• Customer education• Contractor education

Page 31: Quality install testing procedures for forced air systems

Benefits

• Energy Savings (that is expected and predicted)

• Increased Comfort• Better customer service• Better customer service

Page 32: Quality install testing procedures for forced air systems

Thank You