PVDGIntegration Barker

download PVDGIntegration Barker

of 41

Transcript of PVDGIntegration Barker

  • 8/18/2019 PVDGIntegration Barker

    1/41

    Experiences in Integrating PV and

    Other DG to the Power System(Radial Distribution Systems) 

    Prepared by:

    Philip Barker

    Founder and Principal EngineerNova Energy Specialists, LLC

    Schenectady, NY

    Phone (518) 346-9770

    Website: novaenergyspecialists.com

    E-Mail: [email protected] 

    Presented at:

    Utility Wind Interest Group (UWIG)

    6th Annual Distributed Wind/Solar Interconnection Workshop

    February 22-24, 2012

    Golden, CO1Prepared by Nova Energy Specialists, LLC

  • 8/18/2019 PVDGIntegration Barker

    2/41

     Topics

    • Discussion of Distribution and Subtransmission

    Factors Considered in Basic DG integration Studies

    • Useful Ratios for Screening Analysis of DG Impacts

    • Review of Some System Impacts:

     – Voltage Issues

     – Fault Current Issues

     – Islanding Issues

     – Ground Fault Overvoltage Issues

    • Summary and Conclusions of PV Experiences

    Prepared by Nova Energy Specialists, LLC 2

  • 8/18/2019 PVDGIntegration Barker

    3/41

    Prepared by Nova Energy Specialists, LLC 3

    12.47 kV

    Subtransmission Line

    Substation

    Transformer

    LTC

    DG

    Distribution

    Feeder

    Rotating Machine orInverter based DG

    Step Up

    Transformer

    Subtransmission

    Source

    Bulk

    System

    Reclosing and

    Relay Settings

    Primary Feeder

    Point of Connection

    (POC)

    Other Substations

    with Load and DG

    Customer

    Site Load

     Adjacent

    Feeders

    Voltage Regulator

    Discussion of

    Some Factors to

    Consider in DG

    Integration

    Regulator andLTC Settings

    Capacitor

     Alt. Feed

     Alt. Feed

    Other load and

    DG scattered onfeeder

    Type of

    Grounding

    Prime mover or

    energy source

    characteristics

  • 8/18/2019 PVDGIntegration Barker

    4/41

    Some Useful Penetration Ratios

    for Screening Analysis

    • Minimum Load to Generation Ratio(this is the annual minimum load on the relevant power system section

    divided by the aggregate DG capacity on the power system section)

    • Stiffness Factor (the available utility fault current divided by DGrated output current in the affected area)

    • Fault Ratio Factor (also called SCCR)(available utility fault current divided by DG fault contribution in the

    affected area) (Note: also called Short Circuit Contribution Ratio: SCCR)

    • Ground Source Impedance Ratio (ratio of zerosequence impedance of DG ground source relative to utility ground source

    impedance at point of connection)

    NREL Workshop on High Penetration PV: Defining High Penetration PV  – Multiple Definitions and Where to Apply Them Phil Barker, Nova Energy Specialists, LLC

    Note: all ratios above are based on the aggregate DG sources on the system area of interest where appropriate

    Prepared by Nova Energy Specialists, LLC 4

  • 8/18/2019 PVDGIntegration Barker

    5/41

    Minimum Load to Generation Ratio

    (MLGR)

    • Try to use the annual minimum load (don’t

     just assume 1 week of measurements gives

    the minimum)

    Prepared by Nova Energy Specialists, LLC 5

    Time (up to 1 year is ideal)

    Minimum

    Load

    Peak Load

    Weekend

    Weekdays

     Annual Minimum Load

    False Minimum

  • 8/18/2019 PVDGIntegration Barker

    6/41

    Name of

    Ratio What is Ratio useful for?(Note: these ratios are intended for distribution and

    subtransmission system impacts of DG for the types of impacts

    described below.) 

    Suggested Penetration Level Ratios(1) 

    Very Low

    Penetration(Very low probability

    of any issues)

    Moderate

    Penetration(Low to minor probability

    of issues)

    Higher

    Penetration(4) (Increased probability

    of serious issues.

    Minimum

    Load to

    Generation

    Ratio

    [MLGR](2)

    • MLGR used for Ground Fault

    Overvoltage Suppression Analysis(use ratios shown when DG is not effectively

    grounded) 

    >10Synchronous Gen.

    10 to 5Synchronous Gen.

    Less than 5Synchronous Gen.

    >6Inverters(3)

    6 to 3Inverters(3)

    Less than 3Inverters(3)

    • MLGR used for Islanding Analysis(use ratios 50% larger than shown when

    minimum load characteristics are not well

    defined or if significant load dropout is a

    concern during sags.)

    >4 4 to 2 Less than 2

    Notes:1. Ratios are meant as guides for radial 4-wire multigrounded neutral distribution system DG applications and are calculated based on aggregate DG on relevant power system sections

    2. “Minimum load” is the lowest annual load on the line section of interest (up to the nearest applicable protective device). Presence of power factor correction banks that result in a surplus

    of VARs on the “islanded line section of interest” may require slightly higher ratios than shown to be sure overvoltage is sufficiently suppressed.

    3. Inverters are inherently weaker sources than rotating machines therefore this is why a smaller ratio is shown for them than rotating machines4. If DG application falls in this “higher penetration” category it means some system upgrades/adjustments are likely needed to avoid power system issues.

    NREL Workshop on High Penetration PV: Defining High Penetration PV  – Multiple Definitions and Where to Apply Them Phil Barker, Nova Energy Specialists, LLC

    Some Helpful Screening Thresholds

    the Author Uses in His Studies 

    Prepared by Nova Energy Specialists, LLC 6

  • 8/18/2019 PVDGIntegration Barker

    7/41

    Type of

    Ratio What is it useful for?(Note: these ratios are intended for distribution and

    subtransmission system impacts of DG for the types of

    impacts described below.) 

    Suggested Penetration Level Ratios(1) 

    Very Low

    Penetration(Very low probability

    of any issues)

    Moderate

    Penetration(Low to minor probability

    of issues)

    Higher

    Penetration(3) (Increased probability

    of serious issues.

    Fault RatioFactor

    (ISCUtility/ISCDG)

    • Overcurrent device coordination

    • Overcurrent device ratings >100 100 to 20

    Less than

    20

    Ground Source

    Impedance

    Ratio(2)

    • Ground fault desensitization 

    • Overcurrent device coordination

    and ratings>100 100 to 20

    Less than

    20

    StiffnessFactor

    (ISCUtililty/IRatedDG)

    • Voltage Regulation

    (this ratio is a good indicator of voltageinfluence. Wind/PV have higher ratios

    due to their fluctuations. Besides this

    ratio, may need to check for current

    reversal at upstream regulator devices.) 

    >100PV/Wind

    100 to 50PV/Wind

    Less than 50PV/Wind

    > 50Steady Source

    50 to 25Steady Source

    Less than 25Steady Source

    Notes:1. Ratios are meant as guides for radial 4-wire multigrounded neutral distribution system DG applications and are calculated based on aggregate DG on relevant power system sections

    2. Useful when DG or it’s interface transformer provides a ground source contribution. Must include effect of grounding step -up transformer and/or accessory ground banks if present.

    3. If DG application falls in this “higher penetration” category it means some system upgrades/adjustments are likely needed to avoid power system issues.

    NREL Workshop on High Penetration PV: Defining High Penetration PV  – Multiple Definitions and Where to Apply Them Phil Barker, Nova Energy Specialists, LLC

    Screening Ratios (Continued) 

    Prepared by Nova Energy Specialists, LLC 7

  • 8/18/2019 PVDGIntegration Barker

    8/41NREL Workshop on High Penetration PV: Defining High Penetration PV  – Multiple Definitions and Where to Apply Them Phil Barker, Nova Energy Specialists, LLC

    What Does it Mean if it Falls

    Into the Higher Penetration Category? 

    • If the DG application falls into these higher penetration

    categories , then a detailed study is generally recommended

    and may lead to the need for mitigation

    Prepared by Nova Energy Specialists, LLC 8

  • 8/18/2019 PVDGIntegration Barker

    9/41

    In addition to the ratios discussed in the prior

    slides, also check for:

    • Reverse power flow at any voltage regulator or transformer LTC bank: if

     present, check compatibility of the controls and settings of regulator

    controls.

    • Check line drop compensation interaction: if employed by any upstream

    regulator, do a screening calculation of the voltage change seen at theregulator with the R and X impedance settings actually employed at the

    regulator. Generally, if  ΔV < 1% seen by the regulator controller

    calculated for the full rated power change of DG, then line drop

    compensation effects and LTC cycling is not usually an issue.

    • Capacitor Banks: if significant VAR surplus on a possible islanded area

    study for potential impact

    • Fast Reclosing Dead Times: if less than 5 seconds (especially those less

    than 2 seconds) consider the danger of reclosing into live island.

    Prepared by Nova Energy Specialists, LLC 9

  • 8/18/2019 PVDGIntegration Barker

    10/41

    Caveats for Use of the Ratios & Checks

    • Ratios we have discussed on preceding slides are only guides

    for establishing when distribution and subtransmission system

    effects of DG become “significant” to the point of requiring

    more detailed studies and/or potential mitigation options.

    • They must be applied by knowledgeable engineers that

    understand the context of the situation and the exceptions

    where the ratios don’t work 

    • It requires a lot more than just these slides here to do this topic

     justice. We have omitted a lot of details due to the short

    presentation format so this is just meant as a brief illustration

    of these issues.

    NREL Workshop on High Penetration PV: Defining High Penetration PV  – Multiple Definitions and Where to Apply Them Phil Barker, Nova Energy Specialists, LLCPrepared by Nova Energy Specialists, LLC 10

  • 8/18/2019 PVDGIntegration Barker

    11/41

    Voltage Regulation & Variation Issues

    • Steady State Voltage (ANSI C84.1 voltage

    limits)

    • Voltage Excursions and LTC Cycling

    • Voltage Flicker

    • Line Drop Compensator Interactions

    • Reverse Power Interactions

    • Regulation Mode Compatibility Interactions

    Prepared by Nova Energy Specialists, LLC 11

  • 8/18/2019 PVDGIntegration Barker

    12/41

    High Voltage Caused by Too Much

    DG at End of Regulation Zone

    SUBSTATION

    Voltage

    Distance

    Heavy Load No DG

    Heavy Load

    (DG High Output)

    End

    ANSI C84.1 Lower

    Limit (114 volts)

    Light Load

    (DG at High Output)ANSI C84.1 UpperLimit (126 volts)

           Cos RSin X  I V  DG

     

    LTC Large DG exports

    large amounts of

    power up feeder

     I  DG

    Feeder (with R and X)

    IEEE 1547 trip Limit (132 Volts)

    Prepared by Nova Energy Specialists, LLC 12

    DG current

    at angle  

  • 8/18/2019 PVDGIntegration Barker

    13/41

    Impact of Distributed Generation

    on Line Drop Compensation

       V   o    l   t   a

       g   e

    Distance

    Heavy Load No DG

    Heavy Load with DG

    End

    ANSI C84.1 Lower Limit (114 volts)

    Light Load No DG

    SUBSTATIONLTC

    Large DG(many MW)

    DG Supports most of

    feeder load

    Exporting DG “shields” the

    substation LTC controller

    from seeing the feeder

    current. The LTC sees less

    current than there is and

    does not boost voltage

    adequately.

    CT

    Line drop

    compensator

    LTC Controller

    Prepared by Nova Energy Specialists, LLC 13

    ANSI C84.1 Upper Limit (114 volts)

  • 8/18/2019 PVDGIntegration Barker

    14/41

    Voltage Regulator Reverse Mode

    Confused by DG Reverse Power

    SUBSTATION

    LTC

    Reverse

    Power Flow

    Due to DG

    Supplementary

    Regulator with Bi-

    Directional controls

    Normally

    Closed

    Recloser

    R

    R

    Normally

    Open

    Recloser

    DG

    Supplementary regulator senses reverse power and

    erroneously assumes that auto-loop has operated – it

    attempts to regulate voltage on the substation side of

    the supplementary regulator

    What happens?  Since the feeder is still connected to the substation, the line regulator once it isforced into the reverse mode will be attempting to regulate the front section of the feeder. To do

    this can cause the supplementary regulator to “runaway” to either its maximum or minimum tap

    setting to attempt to achieve the desired set voltage. This in turn could cause dangerously high or

    low voltage on the DG side of the regulator. This occurs because the source on DG side of regulator

    is voltage following (not aiming to a particular voltage set point) and is weak compared to the

    substation source.

    Prepared by Nova Energy Specialists, LLC 14

  • 8/18/2019 PVDGIntegration Barker

    15/41

    Fluctuating Output of aPhotovoltaic Power Plant

    Prepared by Nova Energy Specialists, LLC 15

    1 2 3 4 5 6 7 8 9

    Days

  • 8/18/2019 PVDGIntegration Barker

    16/41

         Cos RSin X  I V  DG

     

    System Impedance

    DG Starting Current

    and DG Running current

    fluctuations DG

     ΔIDG

    Infinite

    Source R X

    V  Flicker Voltage Example

    The GE Flicker Curve

    (IEEE Standard 141-1993 and 519-1992)Flicker

    Screening:Using the voltage drop screeningformula to estimate the ΔV for a

    given DG current change (ΔIDG).

    Then plot ΔV on the flicker curve

    using expected time period

    between fluctuations

    Realize that this is a basic screening concept. For situationswhere there might be more significant dynamic interactionswith other loads, or utility system equipment, a dynamicsimulation with a program such as EMTP or PSS/E may berequired to verify if flicker will be visible.

    Prepared by Nova Energy Specialists, LLC 16

  • 8/18/2019 PVDGIntegration Barker

    17/41

    A Conservative Quick Screen for PV Flicker(Not as accurate as IEEE 1453 method but easy and quick for PV)

    Prepared by Nova Energy Specialists, LLC 17

       P  e  r  c  e  n   t   V  o   l   t  a  g  e   C   h  a  n  g  e   (         V   %   )

    Adjusted Borderline of Visibility Curves for PV: This

    curve used/developed by NES represents a conservativemodification to the regular IEEE flicker visibility curve. This

    curve for PV is meant to capture the fact that PV is not

    square modulation, and is based on cloud ramping rates,

    and possible LTC interactions causing flicker.

    IEEE 519-1992 Borderline of Irritation Curve

    519 Visibility

    Curve x 2.0

    519 Irritation

    Curve x

    1.25X

    Adjusted Borderline of Irritation Curve for PV: This curve used/developed by

    NES represents a conservative modification to the regular IEEE flicker irritation

    curve. This curve for PV is meant to capture the fact that PV is not squaremodulation, and is based on cloud ramping rates, and possible LTC interactions

    causing flicker.

    IEEE 519-1992 Borderline

    of Visibility Curve

    This is the IEEE 519-1992 flicker

    curve, but with two new adjusted

    curves added by NES to

    conservatively  approximate PV

    flicker thresholds.

    While the IEEE 1453 method basedon Pst, Plt is still the most

    technically robust approach and

    should allow best results in tight

    situations, it is the author’s view that

    this adjusted IEEE 519-1992 curve

    approach shown here can serve as

    a cruder but easier alternative

    method to facilitate quick screens.

    Note that for PV, the regular IEEE

    519-1992 curves are generally too

    conservative from a flicker visibility

    perspective due to the fact that PV

    fluctuations are more rounded rather

    than square.

  • 8/18/2019 PVDGIntegration Barker

    18/41

    PV Flicker Experiences

    • Use of IEEE 1453 method is a technically very robust

    screening methodology for flicker when very accurate

    threshold levels need to be determined

    • However, a suggested modified GE flicker curve canwork well for PV as a conservative tool for simple

    screening when less accuracy is required

    • It is the author’s experience that other voltageproblems (LTC cycling, ANSI limits, etc.) related to PV

    become problematic at lower capacity thresholds

    than flicker – flicker is one of the last concerns to arise

    Prepared by Nova Energy Specialists, LLC 18

  • 8/18/2019 PVDGIntegration Barker

    19/41

    Some DG Fault Current Issues

    • Impact of current on breaker, fuse, recloser,

    coordination. Affect on directional devices and

    impedance sensing devices.

    • Increase in fault levels (interrupting capacity of

    breakers on the utility system)

    • Nuisance trips due to “backfeed” fault current 

    • Distribution transformer rupture issues

    • Impact on temporary fault clearing/deionization

    Prepared by Nova Energy Specialists, LLC 19

  • 8/18/2019 PVDGIntegration Barker

    20/41

    Fault Currents of Rotating Machines

    Separately-ExcitedSynchronous Generator

    2 to 4 times rated current

       F   a   u   l   t    C   u   r   r   e   n

       t

    Time

    Subtransient Period

    Envelope

    Transient Period

    Envelope Steady State Period

    Envelope

       F   a   u   l   t    C   u   r   r   e   n

       t

    Time

    Subtransient Period

    Envelope

    Transient Period

    Envelope Steady State Period

    Envelope

    4-10 times rated current

    Induction Machine

    Current decays toessentially zero

    Current Decay Envelope

    37%

    Transient Time Constant

    Time

    100%

       F   a   u    l   t   C   u   r   r   e   n   t

    4-10 timesrated current

    Prepared by Nova Energy Specialists, LLC 20

  • 8/18/2019 PVDGIntegration Barker

    21/41

    Pre-fault Fault Current Worst casei

    t

    Fault Current Contributions of Inverters

    Note: The exact nature and duration of the fault contribution from aninverter is much more difficult to predict than a rotating machine. It is afunction of the inverter controller design, the thermal protection functionsfor the IGBT and the depth of voltage sag at the inverter terminals. Inthe worst case if fault contributions do continue for more than ½ cycle,they are typically no more than 1 to 2 times the inverter steady statecurrent rating.

    Best Case: May last only a fewmilliseconds (less than ½ cycle) for manytypical PV, MT and fuel cell inverters

    Typical Worst Case: may last forup to the IEEE 1547 limits and be upto 200% of rated current

    Irated

    Prepared by Nova Energy Specialists, LLC 21

  • 8/18/2019 PVDGIntegration Barker

    22/41

    Fault Current Impacts:Nuisance trips, fuse

    coordination issues,transformer rupture issues, etc.

    Recloser B

    13.2 kV

    115 kV

    Recloser A

    DG

    Adjacent

    Feeder

    FaultCase 1

    Fault Contribution

    from DG Might

    Trip The Feeder

    Breaker and

    Recloser

    (Nuisance trip)

    Iutility

    IDG

    Prepared by Nova Energy Specialists, LLC 22

    Fault

    Case 2

       U   t   i   l   i   t  y

    DG

       U   t   i   l   i   t  y

       D   G

    Fault

    Case 3

    The good news is that PV is

    much less likely than

    conventional rotating DG to

    cause issues since inverter faultcontributions are smaller!Fault Contribution from

    DG Might Interfere with

    Fuse Saving or Exceed

    Limits of a DeviceTransformer Rupture

    Limits (fault magnitude)

  • 8/18/2019 PVDGIntegration Barker

    23/41

    The Author’s Experiences

    Related to PV Fault Levels 

    • In doing many projects, I have observed that fault current

    problems associated with PV in most cases are not an issue

    due to the low currents injected by the inverter (about 1-2

    per unit of rating).

    • In general, only the largest PV (or large PV aggregations) can

    cause enough fault current to even begin to worry current

    impacts (there are some special exceptions).

    • As PV capacity grows on a circuit, voltage problems usually

    arise well before fault currents become an issue. A circuit

    without voltage problems is not likely to have fault current

     problems due to PV.

    Prepared by Nova Energy Specialists, LLC 23

  • 8/18/2019 PVDGIntegration Barker

    24/41

    Unintentional DG

    Islanding Issues

    Recloser B

    (Normally Open)

    13.2 kV

    115 kV

    Recloser A

    DG

    Adjacent

    Feeder

    The recloser has

    tripped on its first

    instantaneous shot,

    now the DG must trip

    before a fast reclose is

    attempted by the utility

    Islanded Area

    • Incidents of energizeddowned conductorscan increase (safety)

    • Utility system reclosinginto live island may

    damage switchgearand loads

    • Service restoration canbe delayed and willbecome moredangerous for crews

    • Islands may notmaintain suitablepower quality

    • Damaging overvoltagescan occur during some

    conditionsPrepared by Nova Energy Specialists, LLC 24

  • 8/18/2019 PVDGIntegration Barker

    25/41

    Islanding Protection Methods of DG

    Passive Relaying Approach (Voltage and frequencywindowing relay functions: 81o, 81u, 27, 59 – ifconditions leave window then unit trips)

    Active Approach (instability induced voltage orfrequency drift coupled and/or actively perturbedsystem impedance measurement or other activeparameter measurement)

    (UL-1741 utility interactive inverters) 

    Communication Link Based Approach (use of directtransfer trip [DTT] or other communications means)

    Prepared by Nova Energy Specialists, LLC 25

  • 8/18/2019 PVDGIntegration Barker

    26/41

    Islanding and PV Inverters

    • Inverters typically have very effective active anti-

    islanding protection.

    • Unfortunately, the IEEE 1547 and UL-1741 islanding

    protection requirements (2 second response time)are not compatible with high speed utility reclosing

    practices used at many utilities

    • If minimum load is nearly matched to generationthen provisions such as DTT and/or live line reclose

    blocking may be needed, especially with high

    speed reclosing situations.

    Prepared by Nova Energy Specialists, LLC 26

  • 8/18/2019 PVDGIntegration Barker

    27/41

    Screening

    for

    Islanding

    Issues

    Prepared by Nova Energy Specialists, LLC 27

    Start

    Is the annual minimum load on any

    “Islandable” section at least twice the rated DG

    capacity?

    Is the DG an Inverter Based

    Technology Certified Per

    UL1741 Non-IslandingTest?

    Islanding Protection May Need

    Careful Examination and

    Possible Enhancement

    Islanding Protection is

     Adequate

     Yes

    No

     Yes

     Yes

    No

    No Is the reclosing dead time on the “Islandable”

    section ≥ 5 seconds?

    Is the DG equipped with at least passive relaying-

    based islanding protection?

    No

    Is the mix of (number of and

    capacity) inverters and other

    converters and capacitors on the

    “Islandable” section within

    comfortable limits of the UL1741

    algorithms?

    No

     Yes

     Yes

  • 8/18/2019 PVDGIntegration Barker

    28/41

    Ground Fault Overvoltage

    Ground Fault Overvoltage

    can result in seriousdamaging overvoltage on theunfaulted phases. It can beup to roughly 1.73 per unit ofthe pre-fault voltage level.

    Neutral

    Vcn

    Van

    Vbn

    Before the Fault

    Neutral

    Voltage

    Increases

    on Van, Vbn

    Vbn

    Van

    Vcn

    During the Fault

    Neutral and earth return path

    Phase A

    Phase B

    Phase C

    Source

    Transformer

    (output side)

    Fault V bn

    V an

    V cn

    X1, X2 R1, R2

    X0 R0

    Voltage swell during

    ground fault

    V(t)

    (t)

    Prepared by Nova Energy Specialists, LLC 28

    X1, X2

    X1, X2 R1, R2

    R1, R2

  • 8/18/2019 PVDGIntegration Barker

    29/41

    IEEE Effective Grounding

    • Effective grounding is

    achieved when the source

    impedance has the following

    ratios:

    Ro/X1 < 1Xo/X1 < 3

    • Effective grounding limits the

    L-G voltage on the unfaulted

    phases to roughly about

    1.25-1.35 per unit of nominal

    during the fault

    • With ungrounded source, the

    voltage could be as high as

    1.82 per unit.

    ideally

    grounded

    system

    Vbn

    Van

    Vcn

    Effectively

    grounded

    system

    Ungrounded

    system

    N

    N

    N

    1.82 VLN

    Prepared by Nova Energy Specialists, LLC 29

    Voltage

    includes 5%

    regulation

    factor

  • 8/18/2019 PVDGIntegration Barker

    30/41

    Generator Step-Up Transformer

    Grounding Issues

    deltaNeutral

    Neutral

    Low Voltage Side (DG facility)

    wye

    wye wye

    Neutral grounding of

    generator on low side of

    transformer does not impact

    grounding condition on high

    side

    *IMPORTANT: Generator

    neutral must be

    connected to the

    neutral/ground of the

    transformer to establish

    zero sequence path to

    high side

    Neutral wye*neutral is not connected

    then the source acts as

    an ungrounded source

    even though transformer

    is grounded-wye to

    grounded-wye

     Acts as grounded

    source feeding out to

    system only if

    generator neutral istied to the transformer

    grounded neutral

     Acts as ungrounded

    source feeding out to

    system only if generator

    neutral is not connectedto transformer grounded

    neutral*

     Acts as grounded

    source feeding out

    to system

    C N

    A

    B

    Gen.

    C

    C N

    A

    B

    Gen.

    C

    C N

    A

    B

    Gen.

    C

    Distribution

    Transformer

    wye

    High Voltage Side(to Utility Distribution System Primary)

    Prepared by Nova Energy Specialists, LLC 30

    G t St U T f

  • 8/18/2019 PVDGIntegration Barker

    31/41

    Generator Step-Up Transformer

    Grounding Issues – Continued

    deltaNeutral

    Low Voltage Side (DG facility)

    wye

    Neutral grounding of

    generator on low side of

    transformer does not impact

    grounding condition on high

    side

     Acts as ungrounded 

    source feeding out

    to system

    C N

    A

    B

    Gen.

    C

    Distribution

    Transformer

    High Voltage Side(to Utility Distribution System Primary)

    delta

     Acts as

    ungrounded

    source feeding out

    to system

    Neutral grounding of

    generator on low side of

    transformer does not impact

    grounding condition on high

    side

    C N

    A

    B

    Gen.

    Cdelta

    delta wye Neutral grounding at generator

    on low side of transformer does

    not impact grounding condition

    on high side

     Acts as

    ungrounded

    source feeding out

    to system

    C N

    A

    B

    Gen.

    C

    Floating Neutral

    No connection toTransformer Neutral

    Prepared by Nova Energy Specialists, LLC 31

    PV Inverter Neutral Is Typically Not

  • 8/18/2019 PVDGIntegration Barker

    32/41

    PV Inverter – Neutral Is Typically Not

    Effectively Grounded

    Prepared by Nova Energy Specialists, LLC 32

    Building Neutral

    A

    A

    B

    C

    Utility

    Distribution

    Transformer 480V

    277V

    Delta

    12,470V

    Wye

    B

    C

    Wye has high resistance neutral

    grounding or is essentially ungrounded

    Three Phase Inverter with Internal Isolation Transformer all inside an enclosure – a typical arrangement

    Safety Ground

    Enclosure bond

    to safety

    ground

    Neutral

    Neutral Terminal

    Usually bonded to earth ground at main service panel

    per NEC but this does not make it effectively

    grounded if inverter transformer is not so

  • 8/18/2019 PVDGIntegration Barker

    33/41

    Ground Fault Overvoltage Issues

    Prepared by Nova Energy Specialists, LLC 33

    Need enough load on this island with respect aggregate

    DG at all connected distribution substations to suppress

    overvoltage –

    otherwise special solutions are needed!

    12.47 kV Line

    DG Site 1

    Ground

    Fault

    Feeder

    Breaker

    Utility System

    Bulk Source

    Load Load Load

    Need enough load on this island with respect aggregate DG

    at distribution level to suppress overvoltage – otherwise

    effective grounding or other solutions are needed!

    Transformer Acts as

    ungrounded source

    (not effectively

    grounded)

    Substation transformer acts as grounded source with respect to 12.47

    feeder suppressing ground fault overvoltage on distribution until feeder

    breaker opens. But it acts as an ungrounded source when feeding

    backwards into subtransmission!

    Neutral is Ungrounded

    or High Z Grounded

    Transformer acts as

    ungrounded source or acts as

    high Z grounded source (if

    generator neutral is not

    grounded or high z grounded)DG Site 2

    Subtransmission

    (46kV)

    Subtransmission source transformer acts as grounded source

    suppressing ground fault overvoltage on subtransmission until

    subtransmission breaker opens.

    Ground

    Fault

    Distribution

    SubstationDG

    DG

    Distribution

    Substation

    Load

    Load

    Distribution

    Substation

    Subtransmission

    Breaker

  • 8/18/2019 PVDGIntegration Barker

    34/41

    Solutions to Ground Fault Overvoltage(any one of these alone will work)

    • Effectively ground the DG if possible(But be careful since too much effectively grounded DG can desensitize relaying and cause

    other issues. Also, see note 1 with regard to subtransmission impacts of distribution effective

    grounding of DG.)

    • If DG is not effectively grounded make sure to maintain a minimum loadto aggregate generation ratio >5 for rotating DG and >3 for inverter

    generation

    • Don’t separate the feeder from the substation grounding source

    transformer until sufficient non-effectively grounded DG is “cleared” from

    the feeder (e.g. use a time coordinated DTT method.)

    • Use grounding transformer banks at strategic point(s) on feeder.

    Prepared by Nova Energy Specialists, LLC 34

    Note 1: On subtransmission since the distribution substations usually feed in through delta (high-side)

    windings, effective grounding of DG at the distribution level does not make it effectively grounded with

    respect to subtransmission level.

    H L d R d

  • 8/18/2019 PVDGIntegration Barker

    35/41

    How Load Reduces

    Ground Fault Overvoltage

    Neutral

    Vcg

    Vag

    Vbg

    Before the

    Fault

    12.47 kV Feeder

    Load

     Impedance of DG

    Source, its transformerand connecting leads 

    Ground Fault

    (phase C)Open

    BreakerUtility Source

    Neutral

    Voltage

    Increases

    on Vag, Vbg

    VbgVcg=0

    During Ground Fault

    (light load)

    Neutral

    Voltage does not rise much on Vag, Vbg because the overall size of the

    triangle has been reduced (phase to phase voltage has dropped)

    Vbg

    During Ground Fault

    (heavy load)

    X

    R

    Vag

    Vcg=0

    Vag

    Prepared by Nova Energy Specialists, LLC 35

    For inverters theexcessive load will

    also trigger fast

    shutdown to protect

    transistors

  • 8/18/2019 PVDGIntegration Barker

    36/41

    Grounding Transformer Impedance Sizing

    Prepared by Nova Energy Specialists, LLC 36

    1

    3

    1

    0

    1

    0

     pv

     groundbank 

     pv

     groundbank 

     X 

     R

     X 

     X 

    IEEE Effective Grounding Definition

    7.0

    2

    1

    0

    1

    0

     pv

     groundbank 

     pv

     groundbank 

     X 

     R

     X 

     X 

    Engineering Targets to Provide Effective

    Grounding with Reasonable MarginAssume inverter X1 is 30% for generic worst case30% is not the actual impedance since the inverter

    impedance varies due to controller dynamics and operating

    state. But 30% is a conservative number that factors worst

    case conditions whether the inverter is a current controlled

    or voltage controlled PV source. A higher number can be

    used for some inverters, but care should be exercised if using

    a higher value (especially if it exceeds 50%).

    Utility

    Primary

    Feeder

    X1PV = 30% X

    t=5% 

    Utility Source

    Grounding

    Transformer

    Bank

    X0groundbank, R0groundbank

    Open

    Inverter

  • 8/18/2019 PVDGIntegration Barker

    37/41

    Ground Transformer Sizing/Rating

    • Must be sized such that:

     – X0/X1 and R0/X1 ratios are

    satisfied with some margin (see

    the targets prior slide)

     – Bank must be able to handle fault

    currents and steady state zero

    sequence currents without

    exceeding damage limits

     – Bank must not desensitize the

    utility ground fault relaying or

    impact ground flow currents too

    much

     – Bank may need alarming or

    interlock trip of DG if bank trips off.

    Prepared by Nova Energy Specialists, LLC 37

    Zero Sequence Current Divider

    GroundingTransformer

    Path

    UtilitySource

    Path

    I0 utility

    I0 Total

    I0 Ground transformer

    d L d

  • 8/18/2019 PVDGIntegration Barker

    38/41

    Ferroresonance and Load

    Rejection Overvoltage with DG

    Conditions to Avoid: Islanded State (Feeder Breaker open)

    Generator Rating > minimum load on island

    Excessive Capacitance on island

    Reliable and fast anti-islanding protection that

    clears DG from line before island forms is a

    good defense against this type of ferroresonant

    condition! Reasonably high MLGR avoids it too.

    EMTP Simulation of Ferroresonant

    OvervoltageUnfaulted Phase Voltage

    Load rejection, ground fault and

    resonance related overvoltage

    Breaker Opens (island forms)

    Normal Voltage

    Prepared by Nova Energy Specialists, LLC 38

    Waveform shown is Rotating

    Machine Type Overvoltage

  • 8/18/2019 PVDGIntegration Barker

    39/41

    Outcomes of PV Projects (0.1 to 5 MW) the Author Has

    Been Involved With in Various Locations

    Prepared by Nova Energy Specialists, LLC 39

    Type of Issue Typical Experience (over 30 projects studied)

    Voltage

    Regulation

    Interactions

    Most have not required changes to the regulator or regulation settings and no

    special mitigation. A few projects have required regulator setting changes to

    reduce the chance of LTC cycling or ANSI C84.1 voltage violations. The largest

    sites studied are considering reactive compensation to mitigate LTC cycling and

    voltage variations.

    Fault CurrentInteractions

    No sites except one caused enough additional fault current to impactcoordination or device ratings in a significant manner.

    Islanding

    Interactions

    For islanding protection, roughly 1/3rd of the sites have required something

    special beyond the standard UL-1741 inverter with default settings. Some

    required more sensitive inverter settings or adjustments to utility reclosing

    dead time. A few have needed a radio based or hardwired DTT and/or live line

    reclose blocking added.

    Ground Fault

    Overvoltage

    About 1/3rd of the sites need some form of mitigation – usually a grounding

    transformer bank, a grounded inverter interface, or a time coordinated DTT

    Harmonics No sites have required any special provisions for harmonics yet

    OtherSome sites are considering operating in power factor mode producing VARs to

    provide reactive power support. One site had a capacitor concern.

  • 8/18/2019 PVDGIntegration Barker

    40/41

    Conclusions

    • PV and other types of DG today are being successfully

    interconnected on distribution feeders all over the country.

    In many cases the impacts are not enough to cause

    worrisome effects.

    • However, the size of projects is growing, especially now that

    many large commercial and FIT type projects are being

    considered at the distribution level. Also, the ongoing

    aggregation effects as PV becomes more widely adopted is

    leading to more substantial impacts.

    • Many projects can still be screened using simple methods,

    but increasingly, more detailed analytical methods are

    becoming necessary.Prepared by Nova Energy Specialists, LLC 40

  • 8/18/2019 PVDGIntegration Barker

    41/41

    Conclusions (continued)

    • The “relative size” of the PV (or DG) compared to the power

    system to which it is connected plays the key role in system

    impact effects. Key factors that gauge the relative size include:

     – The MLGR, FRF (SCCR), Stiffness Factor, and GSIR

     – The ratios will usually need to be gauged based on aggregate DG in a

    zone or region of concern

    • The settings of utility voltage regulation equipment and feeder

    overcurrent devices and system designs also play a key role.

    • The “absolute size” and “project class” (e.g. FIT, net metered)

    play a role only in that this impacts the scope and criticality of

    the project and may trigger certain regulatory requirements.