PUSHING THE ENVELOPE · ‐10 (14) 0 (32) 10 (50) 20 (68) 30 (86) 0. dlb associates | confidential...
Transcript of PUSHING THE ENVELOPE · ‐10 (14) 0 (32) 10 (50) 20 (68) 30 (86) 0. dlb associates | confidential...
This image cannot currently be displayed.
Don Beaty, PE, ASHRAE FellowPresident, DLB Associates Consulting Engineers
PUSHING THE ENVELOPE: The impact of increasing the environmental range on IT equipment reliability
2dlb associates | confidential and proprietaryPrinted: 1/16/2013 4:51 PM
s:\dlb 1\a presentation\archive public\2013\bcs ‐ 2013 london ‐ beaty ‐ published version.pptx
Opening Comments
Before ASHRAE first published the Thermal Guidelines Book in 2004, there were no vendor neutral standards for data center temperature and humidity
Common temperatures were 18 – 20 °C.
ASHRAE’s Thermal Guidelines recommended temperatures up to 27 °C with allowable temperatures even higher.
Although there are a number of data centers operating above 20 °C, often those operating temperatures are in the range of 22 – 24 °C
A minority of the data centers are operating above 24 °C
Today’s presentation shares some case studies and experiences about operating at higher temperatures and / or using chiller‐less approaches
We hope this will encourage more companies to take advantage of the ASHRAE Recommended and Allowable Envelopes.
3dlb associates | confidential and proprietaryPrinted: 1/16/2013 4:51 PM
s:\dlb 1\a presentation\archive public\2013\bcs ‐ 2013 london ‐ beaty ‐ published version.pptx
Agenda
PART 1: ASHRAE 2011 THERMAL GUIDELINES OVERVIEW
PART 2: CASE STUDIES
1) Greenfield Mega Internet Data Center (Europe)
2) Existing Colocation Data Center (Europe)
3) Greenfield Colocation Data Center (Asia)
4) Greenfield Mega Internet Data Center (Europe)
CLOSING COMMENTS
GOAL: Demonstrate capital & operational savings through design aligned with ASHRAE Thermal Guidelines
4dlb associates | confidential and proprietaryPrinted: 1/16/2013 4:51 PM
s:\dlb 1\a presentation\archive public\2013\bcs ‐ 2013 london ‐ beaty ‐ published version.pptx
Part 1: ASHRAE 2011 Thermal Guidelines Overview
5dlb associates | confidential and proprietaryPrinted: 1/16/2013 4:51 PM
s:\dlb 1\a presentation\archive public\2013\bcs ‐ 2013 london ‐ beaty ‐ published version.pptx
New Thermal Guidelines – Introduction
Reluctance to operate at higher temperature / humidity ranges include a perceived higher risks of outages, lower resilience, voiding IT equipment warranties, etc.
In 2004, IT OEMs from ASHRAE TC 9.9 published the first VENDOR NEUTRAL temperature and humidity ranges that did NOT void legacy IT equipment warranties.
In 2008, the ranges were further expanded without voiding warranties and in 2011, new groundbreaking data was provided by IT OEMs to help guide greater energy efficiency.
THE OPPORTUNITIES FOR COMPRESSORLESS COOLING (NO REFRIGERATION) ARE HIGH
6dlb associates | confidential and proprietaryPrinted: 1/16/2013 4:51 PM
s:\dlb 1\a presentation\archive public\2013\bcs ‐ 2013 london ‐ beaty ‐ published version.pptx
2011 Equipment Environment Specifications Table (Partial)
7dlb associates | confidential and proprietaryPrinted: 1/16/2013 4:51 PM
s:\dlb 1\a presentation\archive public\2013\bcs ‐ 2013 london ‐ beaty ‐ published version.pptx
Thermal Guidelines – ALLOWABLE Environmental Envelopes
New Classes A1 and A2 are EXACTLY the SAME as previous Classes 1 & 2
Classes A1 and A2 apply to new and legacy equipment.
New Classes A3 and A4 do NOT include legacy equipment.
8dlb associates | confidential and proprietaryPrinted: 1/16/2013 4:51 PM
s:\dlb 1\a presentation\archive public\2013\bcs ‐ 2013 london ‐ beaty ‐ published version.pptx
2008 Recommended Envelope Operating Points
2008 ASHRAE Thermal Guidelines Recommended Envelope – Many Operating Points (171)Dry Bulb
% Relative Humidity
40 41 42 43 44 45 46 47 48 49 50 51 52 53 54 55 56 57 58 59 60
18 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 =17
19 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 =19
20 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 =21
21 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 =21
22 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 =21
23 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 =21
24 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 =18
25 1 1 1 1 1 1 1 1 1 1 1 1 1 1 =14
26 1 1 1 1 1 1 1 1 1 1 1 =11
27 1 1 1 1 1 1 1 1 =8
=8 =8 =9 =9 =10 =10 =10 =10 =9 =9 =9 =8 =8 =8 =7 =7 =7 =7 =6 =6 =6 =171
9dlb associates | confidential and proprietaryPrinted: 1/16/2013 4:51 PM
s:\dlb 1\a presentation\archive public\2013\bcs ‐ 2013 london ‐ beaty ‐ published version.pptx
London Time at Temperature Histogram
Average yearly dry bulb temperatures for airside economizer for London with air mixing to maintain 15°C (59°F) minimum and mechanical cooling to maintain 35°C (95°F) maximum.
ASHRAE Weather Data Viewer provides statistical averages based on the most recent 25 years of data
10dlb associates | confidential and proprietaryPrinted: 1/16/2013 4:51 PM
s:\dlb 1\a presentation\archive public\2013\bcs ‐ 2013 london ‐ beaty ‐ published version.pptx
Volume Server Failure Rate versus Ambient Temperature
Volume Server Failure Rate Versus Ambient Temperature
Dry Bulb Temperature
Average Relative Failure Rate (Notes 2 and 3)
Annual Server Failure Rate
CommentsBaseline (Note 1)
Adjusted Due To Temperature
A B C D = B x C
15°C (59°F) 0.72 4% 3% Less Failures
20°C (68°F) 1.00 4% 4% Baseline
40°C (104°F) 1.66 4% 7% More Failures
NOTES
1) Table uses the conservative upper bound of typical server failure rates of 2 to 4%.2) Assumes continuous (7 x 24 x 365) operation with Dry Bulb Temperature at ITE inlet. 3) Based on years of Server Manufacturers’ actual failures, Component Manufacturers’
failure data, and modeling (published by ASHRAE TC 9.9).
CONCLUSION: Temperature has minimal impact on Server Failure
11dlb associates | confidential and proprietaryPrinted: 1/16/2013 4:51 PM
s:\dlb 1\a presentation\archive public\2013\bcs ‐ 2013 london ‐ beaty ‐ published version.pptx
Volume Server Failure Rate versus Ambient Temperature
Lower bound, average, and upper bound are included since there is variation in server configuration and utilization
12dlb associates | confidential and proprietaryPrinted: 1/16/2013 4:51 PM
s:\dlb 1\a presentation\archive public\2013\bcs ‐ 2013 london ‐ beaty ‐ published version.pptx
London Net X‐Factor Across The Whole Year
IT hardware failure in London with a variable data center temperature is actually LOWER than if the data center was operating at a tightly controlled temperature of 20°C (68°F).
ASHRAE Weather Data Viewer provides statistical averages based on the most recent 25 years of data
13dlb associates | confidential and proprietaryPrinted: 1/16/2013 4:51 PM
s:\dlb 1\a presentation\archive public\2013\bcs ‐ 2013 london ‐ beaty ‐ published version.pptx
Average Net Failure Rate Projections for Air‐side Economization (EU Cities)
ASHRAE Weather Data Viewer provides statistical averages based on the most recent 25 years of data
14dlb associates | confidential and proprietaryPrinted: 1/16/2013 4:51 PM
s:\dlb 1\a presentation\archive public\2013\bcs ‐ 2013 london ‐ beaty ‐ published version.pptx
Chiller Hours Per Year for Air‐side Economization (Europe Cities)
* Assumes 1.5°C (2.7°F) approach between outdoor air dry bulb and supply air due to fan friction
ASHRAE Weather Data Viewer provides statistical averages based on the most recent 25 years of data
15dlb associates | confidential and proprietaryPrinted: 1/16/2013 4:51 PM
s:\dlb 1\a presentation\archive public\2013\bcs ‐ 2013 london ‐ beaty ‐ published version.pptx
Use & Application Guidance for New ASHRAE Data Center Classes
16dlb associates | confidential and proprietaryPrinted: 1/16/2013 4:51 PM
s:\dlb 1\a presentation\archive public\2013\bcs ‐ 2013 london ‐ beaty ‐ published version.pptx
Part 2: Case Studies
17dlb associates | confidential and proprietaryPrinted: 1/16/2013 4:51 PM
s:\dlb 1\a presentation\archive public\2013\bcs ‐ 2013 london ‐ beaty ‐ published version.pptx
Case Study Overview
Case Study
DetailsEmphasis
Site Location Type
1 Greenfield Europe Mega IDCIncrease Setpoint, Increase Free Cooling Hours, Reduced Mechanical Cooling Plant, Climate Analysis, X‐factor Analysis
2 Existing DC Europe Colocation Increase Setpoint, Increase Free Cooling Hours
3 Greenfield Asia ColocationIncrease Setpoint, Increase Free Cooling Hours, Improve Chiller Efficiency, Reduced Mechanical Cooling Plant, Climate Analysis, X‐factor Analysis
4 Greenfield Europe Mega IDCIncrease Setpoint, Increase Free Cooling Hours,Reduced Mechanical Cooling Plant, Climate Analysis
18dlb associates | confidential and proprietaryPrinted: 1/16/2013 4:51 PM
s:\dlb 1\a presentation\archive public\2013\bcs ‐ 2013 london ‐ beaty ‐ published version.pptx
Case Study 1:Greenfield Mega Internet Data Center (Europe)
19dlb associates | confidential and proprietaryPrinted: 1/16/2013 4:51 PM
s:\dlb 1\a presentation\archive public\2013\bcs ‐ 2013 london ‐ beaty ‐ published version.pptx
Case Study 1: Overview
A European greenfield site was designed without chillers.
This was achieved through:
1) Climate and cooling analysis
2) Application of the ASHRAE Thermal Guidelines
3) Alignment with the client’s value system
By raising the temperature and operating in the upper end of the Recommended range AND to accept excursions beyond that range on occasion, a CHILLERLESS design was achieved.
20dlb associates | confidential and proprietaryPrinted: 1/16/2013 4:51 PM
s:\dlb 1\a presentation\archive public\2013\bcs ‐ 2013 london ‐ beaty ‐ published version.pptx
Raised Floor Area: 20,000m2 (215,000 ft2)
Raised Floor Height: 122cm (48”)
Cooling System: Waterside Economizer feeding in‐row cooling units
Total IT load: UNDISCLOSED
Case Study 1: Floor Plan & Metrics
Cooling Cooling
Power Power
Server Space Server Space Support Space
21dlb associates | confidential and proprietaryPrinted: 1/16/2013 4:51 PM
s:\dlb 1\a presentation\archive public\2013\bcs ‐ 2013 london ‐ beaty ‐ published version.pptx
Case Study 1: Energy Efficiency Measures (EEM) Implemented (Airflow Mgmt.)
The best practice of isolating the hot aisle from the cold aisle ensures mixing does not occur and was key to pushing the temperature limits of energy efficiency in the facilities.
The servers exhaust heat to an enclosed hot‐aisle where air is drawn by fans across a chilled water coil and back into the room. The room acts as one big cold‐aisle.
Room as a Cold Aisle
Room as a Cold Aisle (27°C [80°F])
Plan View Elevation
Enclosed Hot Aisle(>41oCF [105°])
Servers
Servers
Enclosed Hot Aisle (>41oC [105°F])
Servers
Servers
Enclosed
Hot Aisle
Servers
Servers
FansCooling Coil
22dlb associates | confidential and proprietaryPrinted: 1/16/2013 4:51 PM
s:\dlb 1\a presentation\archive public\2013\bcs ‐ 2013 london ‐ beaty ‐ published version.pptx
Case Study 1: Details (Specific European City Wet Bulb Temp. Information)
Annual Wet Bulb Temperature Frequency
Freq
uency (Percentage)
35
30
15
10
5
25
20
Wet Bulb Temperature, °C (°F)
‐30(‐22)
‐20(‐4)
‐10(14)
0(32)
10(50)
20(68)
30(86)
0
23dlb associates | confidential and proprietaryPrinted: 1/16/2013 4:51 PM
s:\dlb 1\a presentation\archive public\2013\bcs ‐ 2013 london ‐ beaty ‐ published version.pptx
Case Study 2:Existing Colocation Data Center (Europe)
24dlb associates | confidential and proprietaryPrinted: 1/16/2013 4:51 PM
s:\dlb 1\a presentation\archive public\2013\bcs ‐ 2013 london ‐ beaty ‐ published version.pptx
An existing European Data center was examined for opportunities to reduce PUE and decrease energy costs.
The data center consists of two data halls (plus one future hall).
The cooling system consists of air‐cooled chillers which supply chilled water to the CRAC units in the server area.
A total PUE of 1.70 was calculated with current PUE contributions from the various systems as follows:
Case Study 2: Overview
Component(s) PUE Contribution
Chiller (with Primary Pumps) 0.40
Secondary Pumps & CRACs 0.15
Electrical (Transformers, UPS) 0.15
25dlb associates | confidential and proprietaryPrinted: 1/16/2013 4:51 PM
s:\dlb 1\a presentation\archive public\2013\bcs ‐ 2013 london ‐ beaty ‐ published version.pptx
Case Study 2: Energy Efficiency Measures (EEM) Implemented
The following best practices were implemented and their impact on PUE and energy costs were analyzed.
1) Partial containment of cold aisle & installation of blanking panels
Prevents mixing of air streams
2) Increase temperature in data halls
Reduces fan energy in CRAC units (utilize their VFDs)
Increases number of hours of both partial and full free cooling in integrated free cooling mode
Reduces or eliminates cooling load in compressors
3) Control CRAC units on cold aisle temperature (instead of return air temperature)
Required installation of cold aisle temperature sensors
4) Control CRAC units as a whole instead of individually
Prevents “fighting” units
Reduces pump energy
5) Balance floor tiles to equalize loads on CRAC units
Reduces fan energy in CRAC units
26dlb associates | confidential and proprietaryPrinted: 1/16/2013 4:51 PM
s:\dlb 1\a presentation\archive public\2013\bcs ‐ 2013 london ‐ beaty ‐ published version.pptx
Case Study 2: Energy Efficiency Measures (EEM) Implemented
Cold Aisle Containment at End of Aisle
CRAC Unit Control Scheme Before (left) & After (right)
Reduced Compressor Load on Air‐Cooled Chiller Plant
27dlb associates | confidential and proprietaryPrinted: 1/16/2013 4:51 PM
s:\dlb 1\a presentation\archive public\2013\bcs ‐ 2013 london ‐ beaty ‐ published version.pptx
7(44.6)
Case Study 2: Details (Supply Water Temperature Impact on Chiller Efficiency)
0.000
0.100
0.200
0.300
0.400
0.500
0.600
0.700
Chiller PUE
Chilled Water Supply Temperature, °C (°F)
Chiller PUE vs. Chilled Water Supply Temperature At 8.5°C (47.3°F) OAT
Chiller PUE Decreases With Increased Supply Water Temperature Due To Increased Partial Free Cooling
16(60.8)
8(46.4)
9(48.2)
10(50)
11(51.8)
12(53.6)
13(55.4)
14(57.2)
15(59)
28dlb associates | confidential and proprietaryPrinted: 1/16/2013 4:51 PM
s:\dlb 1\a presentation\archive public\2013\bcs ‐ 2013 london ‐ beaty ‐ published version.pptx
Case Study 2: Overall Results (PUE Energy Savings Projection)
The changes were expected to reduce the PUE by 0.10 purely from MECHANICAL changes to the existing system.
The cost savings from the reduced PUE was projected over time (assumes increased load over time):
Post‐implementation PUE Reduction
System Component Post‐implementation PUE Reduction
Chillers 0.05CRAC Units 0.04Pumps 0.01Total 0.10
Per Annum Cost Savings
Year Per Annum Saved Cumulative Saved
2012 $250k $250k
2013 $325k $575k
2014 $450k $1.0M
2015+ $550k $1.6M
29dlb associates | confidential and proprietaryPrinted: 1/16/2013 4:51 PM
s:\dlb 1\a presentation\archive public\2013\bcs ‐ 2013 london ‐ beaty ‐ published version.pptx
Case Study 3:Greenfield Colocation Data Center (Asia)
30dlb associates | confidential and proprietaryPrinted: 1/16/2013 4:51 PM
s:\dlb 1\a presentation\archive public\2013\bcs ‐ 2013 london ‐ beaty ‐ published version.pptx
Raised Floor Area: 13,000m² (140,000 ft2)
Raised Floor Height: 91cm (36”)
Cooling System: Modular Chilled Water Plants with Waterside Economizer Feeding CRAH Units
Total IT Load: 10MW
Case Study 3 – Floor Plan & Metrics
Server Area
Power Plant
Office
Cooling Plant (Above)
31dlb associates | confidential and proprietaryPrinted: 1/16/2013 4:51 PM
s:\dlb 1\a presentation\archive public\2013\bcs ‐ 2013 london ‐ beaty ‐ published version.pptx
Case Study 3: Energy Efficiency Measures (EEM) Implemented (Cooling Analysis)Hou
rs Per Year B
in
0
50
100
150
200
250
300
‐20 0 20 40 60 80 1000
50
100
150
200
250
300
‐20 0 20 40 60 80 100 120
A Cooling System Analysis was performed for a Greenfield data center located in Asia to understand the tradeoffs in terms of TCO & reliability.
The analysis was applied to 3 different cooling system types to understand:
1) Amount of available free cooling at differing supply air temperature(higher supply air temperatures mean MORE free cooling)
2) Magnitude of MECHANICAL cooling capacity needed (when outdoor conditions mean that free cooling is NOT suitable)
3) Annual average relative PUE for each cooling system (directly related to relative operating cost)
Wet Bulb Temperature, °C (°F)
‐29(‐20)
Dry Bulb Temperature, °C (°F)
38(100)
27(80)
16(60)
4(40)
‐7(20)
‐18(0)
‐29(‐20)
49(120)
27(80)
16(60)
4(40)
‐7(20)
‐18(0)
38(100)
32dlb associates | confidential and proprietaryPrinted: 1/16/2013 4:51 PM
s:\dlb 1\a presentation\archive public\2013\bcs ‐ 2013 london ‐ beaty ‐ published version.pptx
Case Study 3: Details (Climate Analysis)
Climate Analysis Results
ScenarioNumber System Type Air Flow Approach IT Envelope
Free CoolingPUE
Hours % Of Year
1 Direct Air‐Side Economizer Open 1.7°C(3°F)
Recommended 2,223 25.4 1.275
A1 Allowable 5,632 64.3 1.207
2 Chillers And CRAHs(Water‐Side Economizer) Closed 8.3°C
(15°F)Recommended 5,950 67.9 1.167
A1 Allowable 8,298 94.7 1.153
3 Indirect Adiabatic Cooling Closed 1.7°C (3°F) 70% WBDE
Recommended 7,318 83.5 1.152
A1 Allowable 8,758 100 1.145
The Climate Analysis maps the statistical weather data and the desired operating temperature range inside the data center (IT Envelope) to the defined Cooling System type to build a theoretical ANNUAL performance in terms of economizer hours and mechanical system PUE.
1) For each system type the approach temperature represents the differential between outdoor air conditions and IT inlet conditions.
33dlb associates | confidential and proprietaryPrinted: 1/16/2013 4:51 PM
s:\dlb 1\a presentation\archive public\2013\bcs ‐ 2013 london ‐ beaty ‐ published version.pptx
If the Maximum MECHANICAL cooling capacity (e.g. chiller tonnage) is UNDERSIZED, then EXCURSIONS occur. The occurrences of the excursions are directly related to the Outdoor conditions.
The EXCURSIONS can be considered in terms of annual DURATION (number of hours per year), or essentially how often they will occur and MAGNITUDE (what IT inlet temperature can be expected during the excursion).
0
100
200
300
400
500
600
Case Study 3: Details (Intentional Undersizing and Excursions)
Excursion Temperature, °C (°F)
Cumulative Excursion Freq
uency
(Hou
rs per Year)
At full IT load, sizing a chiller plant at 65% of the max tonnage (e.g., 0.65 x 325‐tons per 1MW) will result in ~520‐hours ABOVE 24°C (75.2°F) and a MAX temp of 29°C (84.2°F).
~150‐hours above 25.5°C (78°F)
~10‐hours above 27°C (80.6°F)
24(75.2)
30(86)
65% Chiller Capacity (Max. Temp. 29°C [84.2°F])
25(77)
26(78.8)
27(80.6)
28(82.4)
29(84.2)
34dlb associates | confidential and proprietaryPrinted: 1/16/2013 4:51 PM
s:\dlb 1\a presentation\archive public\2013\bcs ‐ 2013 london ‐ beaty ‐ published version.pptx
Mechanical Cooling Capacity
20 ≤ T ≤ 25°C68 ≤ T ≤ 77°F
25 < T ≤ 30°C77 < T ≤ 86°F
30 < T ≤ 35°C86 < T ≤ 95°F Net X‐
factor% hours Avg. X‐
Factor % hours Avg. X‐Factor % hours Avg. X‐
Factor
Chillers & CRAHs (Waterside Economizer)
100% 325 Tons 100 1.13 0.0 1.34 0.0 1.48 1.13
65% 210 Tons 98.3 1.13 1.7 1.34 0.0 1.48 1.13
Indirect Adiabatic Cooling
100% 200 Tons 100 1.13 0.0 1.34 0.0 1.48 1.13
‐ Chillerless 83.5 1.13 15.6 1.34 0.9 1.48 1.29
Case Study 3: Details (Excursions and Impact on Failure Rate)
From an IT Equipment perspective, provided that the Maximum Temperature remains within the ALLOWABLE envelope then the IMPACT of each excursion is NOT significant.
The impact of the DURATION of the excursions can be mapped to annual X‐factors to understand the impact on server failures.
The table below identifies that having a 65% Capacity Chiller Plant translates to a NEGLIGIBLE increase in temperature related IT equipment failures per year.
35dlb associates | confidential and proprietaryPrinted: 1/16/2013 4:51 PM
s:\dlb 1\a presentation\archive public\2013\bcs ‐ 2013 london ‐ beaty ‐ published version.pptx
Case Study 3: Overall Results (Summary of Cooling Options)
Allowing elevated temperatures within a data center provides the opportunity to REDUCE or ELIMINATE the amount of MECHANICAL COOLING that is installed.This example shows that even in a location that may experience fairly high ambient temperatures and a fairly humid environment for a significant portion of the year, SIGNIFICANT first cost savings are achievable which will result in a NEGLIGIBLE impact on ITE performance or longevity.
1) Direct Airside Cooling
An efficient solution BUT will require supplement mechanical cooling if supply air temperatures are to be maintained below the ASHRAE allowable thresholds.
In order to control HIGH HUMIDITY a fully‐sized mechanical cooling plant is required –otherwise high humidity conditions would occur (problematic for the facility).
2) Chilled Water CRAHs with Waterside Economizer
Reasonable efficiency especially if the operated at elevated supply air temperatures
Chillers may be intentionally undersized to achieve good Capex savings (~$500,000 / MW) and negligible impact to ITE reliability.
3) Indirect Adiabatic Cooling
MOST efficient solution / provides the MOST free‐cooling hours and the lowest PUE.
Mechanical cooling can be ELIMINATED if supply air temperatures are allowed to rise up to the ASHRAE A1 Allowable threshold for the warmest days of the year.
36dlb associates | confidential and proprietaryPrinted: 1/16/2013 4:51 PM
s:\dlb 1\a presentation\archive public\2013\bcs ‐ 2013 london ‐ beaty ‐ published version.pptx
Case Study 4: Greenfield Mega Internet Data Center (Europe)
37dlb associates | confidential and proprietaryPrinted: 1/16/2013 4:51 PM
s:\dlb 1\a presentation\archive public\2013\bcs ‐ 2013 london ‐ beaty ‐ published version.pptx
A European greenfield site was designed with a unique cooling system.
Some unique features include:
1) Seawater as the primary method of cooling
2) Tempering the outlet seawater to minimize environmental impact
3) Chillerless design
4) Modular design with multiple failsafes
Case Study 4 Introduction
38dlb associates | confidential and proprietaryPrinted: 1/16/2013 4:51 PM
s:\dlb 1\a presentation\archive public\2013\bcs ‐ 2013 london ‐ beaty ‐ published version.pptx
Raised Floor Area: 2 x 100,000+ ft2 (2 x 9,290 m2)
Raised Floor Height: 48” (122cm)
Cooling System: Chillerless Seawater Cooling
Total IT Load: UNDISCLOSED
Case Study 4 Floor Plan & Metrics
39dlb associates | confidential and proprietaryPrinted: 1/16/2013 4:51 PM
s:\dlb 1\a presentation\archive public\2013\bcs ‐ 2013 london ‐ beaty ‐ published version.pptx
The seawater intake temperature was investigated using data taken over several years.
The temperature for an existing intake tunnel was compared with a new proposed location at a lower elevation.
This elevation had significantly less excursion time (Baseline = 20°C [68°F]) than the existing intake.
Case Study 4 Seawater Intake Temperature Investigation
Year 1
Year 2
Year 3
40dlb associates | confidential and proprietaryPrinted: 1/16/2013 4:51 PM
s:\dlb 1\a presentation\archive public\2013\bcs ‐ 2013 london ‐ beaty ‐ published version.pptx
Case Study 4 Overall Results
A closed water‐side cooling system was designed to minimize humidification and contamination concerns.
This was a chillerless design with a theoretical PUE significantly below 1.1.
Seawater provided an economical and environmentally conscious cooling solution that was reliable and exceed industry trends for cutting edge PUE.
41dlb associates | confidential and proprietaryPrinted: 1/16/2013 4:51 PM
s:\dlb 1\a presentation\archive public\2013\bcs ‐ 2013 london ‐ beaty ‐ published version.pptx
Case Study Overview – Techniques
TechniqueCase Studies
1 2 3 4
General
CFD modeling to predict outcomes X X X
Increase supply air temperature X X X X
CHILLERLESS design X X
Reduced fan speed (VFDs) X
Optimize Controls
CRAH Units & Chiller Plants X
Temp. / Humidity sensor locations X X
Improve Air Distribution
Balance tiles / increase floor pressure X
CFD model to review results X
Improve Airstream Separation
Hot / Cold Aisle Containment X X X X
Blanking Panels X X X X
42dlb associates | confidential and proprietaryPrinted: 1/16/2013 4:51 PM
s:\dlb 1\a presentation\archive public\2013\bcs ‐ 2013 london ‐ beaty ‐ published version.pptx
Closing CommentsThere are many ways to use the information presented in the ASHRAE Thermal Guidelines to save energy, capex and opex on your data center.
The examples presented today are all operational data centers that are benefiting from implementing higher operating temperatures & / or accepting excursions outside of their setpoints.
Having design professionals that have ASHRAE expertise eliminate the risk of balancing capex, opexand energy efficiency with mission critical operation.
We hope this will encourage more companies to take advantage of the ASHRAE Recommended and Allowable Envelopes.
This image cannot currently be displayed.
END OF SLIDES