PT. Sinar Surya Komindo - Internal resistance and …...Work for 8 hours continuously. Build-in...
Transcript of PT. Sinar Surya Komindo - Internal resistance and …...Work for 8 hours continuously. Build-in...
www.aitelong.com Aitelong Technology Co.,Ltd.
SAT-AR03Battery internal resistance tester
Keeping your system safe and running!
TM
Internal resistance and Voltage out of
range alarm
User-exchangeable probes and Clamp
High precision online testing
Powerful data management function
As a digital memoryable and muitifunction test equipment
which can analysis the battery according to the history record.
AT-AR03 Stationary battery internal resistance tester quick and accurate measurement of battery running status. It can show and
record multi group battery voltage resistance etc.It also can precisely repart battery's condition by powerful PC and Data analyzing
software.
S
Full automatically switch the testing range and great capacity data storage.
Automatically switch the testing range between 0.00m -99.99m .
store up to 999 groups battery parameter and 200 groups battery parameter setting.
USB flash memory or RS232 for Data transfer
Enhanced over voltage protection function.
Self over recovery current protecting function.
Use the SOC chip to improve the tester stability.
Big capacity Lithium cell and AC 100V-240V
power supply
Low battery indication.
Automatic testing mode make user to test
expediently.
Technical indicator
PC software management
Regarding the conclusion about Conductance and Capacity
Keeping your system safe and running!
TM
www.aitelong.com Aitelong Technology Co.,Ltd.
A301 Qinfeng Pavilion, Xi'an Software Park, No.68, 2nd Keji Road, Xi'an, Shaanxi, P.R.China 710075
SAT-AR03Battery internal resistance tester
Automatically analysis battery's condition (Good,Suspect, Fail,Unserviceable).
Building the history record database, describe the battery state curve.
Batteries contrastive analysis in the same battery pack.
All batteries are administrated by conditions
t present, Lead acid stationary battery maintenance is applied for the check of Float voltage of battery, However it has been found that
Voltage is irrelevance with Capacity of battery, because Voltage is only to show battery s basic parameters.
In fact, Resistance test is widely applied in daily battery maintenance instead of Voltage check,In world wide because Resistance is reflection
to internal parameters of battery with high precision.
Regarding the conclusion about internal resistance and Capacity: when battery conductance is lower than 25% of Initial Value (basic value),
battery can't be passed by the test of Capacity. When battery's internal resistance is higher than 2 times of initial value, battery capacity will be lower 80%
of nonimal capacity.
A
Internal resistance 1 Voltage 1mV
Internal resistance 1%rdg 2dgt Voltage 0.2%rdg 6dgt
10.8V,1900mAh, Rechargeable Lithium battery
Work for 8 hours continuously.
Build-in 16Mbit Flash memory
320 x 240 LCD
280 x 105 x 83 mm
1.2Kg
-5 --60
90%RH
Tests individual lead acid cells or monoblocs(up to 16 Volts) in any common configuration
Auto-reset disconnect Reverse polarity protected
Min. measurement resolution
Measurement precision
Power supply
Working time
Memory space
Display
Size
N.W
Working temperature
Humidity
APPLICATIONS
Over Voltage Protection
Phone: +86 (29) 87669465 Fax: +86 (29) 87669645 Email: [email protected]
Testing range Internal resistance 0.00m - 99.99m Voltage 0.000V - 25V Capacity 0 - 6000Ah