PERHITUNGAN SETTING RELE PROTEKSI TRAFO DISTRIBUSI
SINGLE LINE DIAGRAM TRAFO 3 BELITAN
Gbr.1 Diagram rele proteksi Trafo
Definisi
PERHITUNGAN SETELAN RELAI TRAFO DISTRIBUSI
1. Data-data
1.1 Data Trafo-1
Kapasitas
Vektor group ; YNyn(d)
Impedansi :
%
Hubungan belitan trafo : Pilih Yyd=1, Yy shell type = 2 atau Yy core type 3
Isikan hubungan belitan 1,2 atau 3
1.2 Data CT
CT sisi 150 kV CT netral 20 kV
CT sisi 20 kV CT penyulang
CT netral 150 kV CT NGR
k 2
360
E 1
j 1 i 0 20
zb2020
2
100 zb20 4 pu ib20
100
20 310
3 ib20 2.887 10
3 A
zb150150
2
100 zb150 225 pu ib150
100
150 310
3 ib150 384.9 A
S 60 MVA
%reaktansi 12.312
Xt%reaktansi
100 Xt1 Xt
100
S Xt1 0.205 pu
Xt2 Xt1 Xto Xt1
Belitan 1
ACT150
300
5 A CTN20
2000
5
CT202000
5 A CTp
400
5 A
CTN150300
5 A CTNGRS
1000
5 A
CTNGRP 0 A
Arus nominal trafo
sisi 150 kV
sisi 20 kV
1.3 Data NGR
Resistansi NGR Ohm
Ohm
Arus maksimum Amp
Arus kontinyu Amp
Waktu Imaks detik
1.4 Impedansi sumber di bus 150 kV
Imp. urutan positif
Imp. urutan negatif
Imp. urutan nol
1.5 Data penyulang 20 kV
a. SUTM asumsi ohm/km
Panjang
b. asumsi u/ SKTM henry
ohm/km
In150S 10
3
150 3 In150 230.94 A primer( )
In20S 10
3
20 3 In20 1.732 10
3 A primer( )
RNGRP 0
RNGRS 11.6
ImNGR 1000
INGR 60 InNGR20 1000
3 RNGRS InNGR 995.431 A
tNGR 10
R1 0.0329 X1 0.0857 Zs1 R1 j X1
R2 0.0329 X2 0.0857 Zs2 R2 j X2
Ro 0.013 Xo 0.1329 Zso Ro j Xo
Zline 0.2 45 2
360 rad
p 0 20 ZL1 0.2 cos j 0.2 sin
ZL1 0.141 0.141i ZL1 0.2 ZL1p
ZL1p
zb20
ZL2p
ZL1p
ZLop
3 ZL1p
ZLp
ZL1p
ZL2p
ZLop
R 0.075 L 0.31 103
XL 2 50 L
Zk R j XL Zk 0.075 0.097i Zk 0.123
1.6 Impedansi Trafo
Impedansi trafo :
Pemilihan hubungan belitanakan merubah nilai Xtt0
1.7 Data SUTT 150 kV
urutan positif urutan negatif
urutan nol
2. Perhitungan hubung singkat
2.1 Hubung singkat 3 fasa dan 2 fasa di bus 20 kV
Gbr.2 Rangkaian pengganti hubung singkat 3 fasa
Xtp1 0.5 Xt1 Xts1 0.5 Xt1 Xtt1 0.5 Xt1
Xtp2 0.5 Xt1 Xts2 0.5 Xt1 Xtt2 0.5 Xt1
Xtp0 0.5 Xt1 Xts0 0.5 Xt1 Xt1 0.205
Xtt0 0.5 Xt1 Belitan 1if
5000000Xt1 Belitan 2if
10 Xt1 Belitan 3if
Xtt0 0.103
Zsutt10.0397 j 0.272
zb150 Zsutt2
0.0397 j 0.272
zb150
Zsutt0 3Zsutt1
zb150 Insutt 600
Gbr.3 Rangkaian pengganti hubung singkat 2 fasa
Arus gangguan 3-ph 20 kV
Arus gangguan 3-ph 150 kV
I3f20p
E
Zs1 j Xtp1 j Xts1 ZL1p
ib20
I3f200
9.861 103
A Primer( )
I2f20p
0.867I3f20p
I2f200
8.549 103
A Primer( )
I3f150p
E
Zs1 j Xtp1 j Xts1 ZL1p
ib150
I3f1500
1.315 103
A primer( )
I2f150p
0.867I3f150p
I2f1500
1.14 103
A Primer( )
I3f200
9.861 103
A Primer( )
0 2 4 6 8 10 12 14 16 18 200
1200
2400
3600
4800
6000
7200
8400
9600
1.08 104
1.2 104
I3f150p
I3f20p
p
I3f2020
2.323 103
I3f15020
309.797
Gbr.4 Grafik hubung singkat 3 pasa sisi 150 kV dan 20 kV
2.2 Hubung singkat 1 fasa
Gbr.5 Rangkaian pengganti hubung singkat 1 fasa
2.3. Untuk gangguan di bus 20 kV
Arus yang melalui netral trafo sisi 20 kV pada I base 20 kV
Kontribusi arus urutan nol yang melalui belitan primer trafo sisi 150 kV pada I base 20 kV :
RNGRP3 RNGRP
zb150 RNGR
3 RNGRS
zb20 RNGRS 11.6
If20p
3 E
Zso RNGRP Xtp0 j( ) Xtt0 j
Zso RNGRP Xtp0 j( ) Xtt0 j
Xts0 j RNGR Zs2 Xtp2 j Xts2 j Zs1 Xtp1 j Xts1 j 5 ZL1p
ib20
If200
984.173 A Primer( )
If120pXtt0 j
Zso RNGRP Xtp0 j Xtt0 j
If20p
If1200 298.437 A Primer( )
Arus yang melalui netral trafo sisi 20 kV pada I base 150 kV
Kontribusi arus urutan nol yang melalui belitan primer trafo sisi 150 kV pada I base 150 kV :
2.4. Untuk gangguan di bus 150 kV
Gbr.6 Rangkaian pengganti hubung singkat 1 fasa di bus 150 kV dengan memperhitungkan trafo
Arus yang melalui netral SUTT sisi 150 kV memperhitungkan trafo :
If20150p
3 E
Zso RNGRP Xtp0 j( ) Xtt0 j
Zso RNGRP Xtp0 j( ) Xtt0 j
Xts0 j RNGR Zs2 Xtp2 j Xts2 j Zs1 Xtp1 j Xts1 j 5 ZL1p
ib150
If201500
131.223 A Primer( )
If120150pXtt0 j
Zso RNGRP Xtp0 j Xtt0 j
If20150p
If1201500 39.792 A Primer( )
If150p
3 E
Zso Zsutt0 p( ) RNGRP Xtp0 j Xtt0 j( )
Zso Zsutt0 p( ) RNGRP Xtp0 j Xtt0 j( )
Zs1 Zsutt1 p Zs2 Zsutt2 p
ib150
If1500
4.408 103
A Primer( )
If150sutttrfp
RNGRP Xtp0 j Xtt0 j
Zso Zsutt0 p( ) RNGRP Xtp0 j Xtt0 j( )
If150p
If150sutttrf0
2.674 103
Arus yang melalui netral trafo sisi 150 kV :
3. Setelan OCR dan GFR
3.1 Setelan Penyulang 20 kV
3.1.1 OCR Penyulang 20 kV SIEMENS tipe ARGUS
Setelan arus
atau CCC penyulang Amp
waktu kerja yang diinginkan
pilih
waktu kerja aktual :
If150trfp
Zso Zsutt0 p
Zso Zsutt0 p( ) RNGRP Xtp0 j Xtt0 j( )
If150p
If150trf0
1.74 103
In6 5 A Primer I2f20m I2f200
CTp 80 Iset6 420 1.2 Iset6 504
Is6Iset6
CTp Is6 6.3 A Sekunder
Tap6Is6
In6 Tap6 1.26 pilih Tap6 1.2
tof20 0.1 dt
td6
I2f20m
Iset6
0.02
1
0.14tof20 td6 0.042
Iset6 504 A primer( )
td6 0.20
tof200.14
I2f20m
Iset6
0.02
1
td6 tof20 0.481
3.1.2 GFR Penyulang 20 kV SIEMENS tipe ARGUS
Setelan arus
waktu kerja yang diinginkan
pilih
waktu kerja aktual :
3.2 Setelan Incoming 20 kV atau sisi TM Trafo3.2.1 OCR sisi 20 kV NARI tipe PCS 9611
Setelan arus
setelan aktual :
In7 5 A
Iset7 0.2 400 A Primer
Is7Iset7
CTp
Is7 1 A Sekunder
Tap7Is7
In7 Tap7 0.2 pilih Tap7 0.2
tgf20 0.5 dt If20m If200
If20m 984.173
td7
If20m
Iset7
0.02
1
0.14tgf20 td7 0.184
Iset7 80 A primer( )
td7 0.175
tgf200.14
If20m
Iset7
0.02
1
td7tgf20 0.476
In2 5 A
Iset2 1.2 In20 Iset2 2.078 103
A primer( )
Is2Iset2
CT20
Is2 5.196 A sekunder( )
Tap3Is2
In2 Tap3 1.039 pilih Tap2 1.0
Iset20 Tap3 In2 CT20
Iset20 2.078 103
A primer( )
waktu kerja yang diinginkan
pilih
waktu kerja aktual :
3.2.2 GFR trafo sisi 20 kV NARI PCS 9611
Setelan arus
setelan aktual :
waktu kerja yang diinginkan
pilih
toi20 1 dt I2f20m I2f200
I2f20m 8.549 103
A primer( )
td2
I2f20m
Iset20
0.02
1
0.14toi20 td2 0.205
Iset20 2.078 103
A primer( )
td2 0.24 Tap3 1.039
toi200.14
I2f20m
Iset20
0.02
1
td2toi20 1.171 dt
In4 5 A In20 1.732 103
Iset4 0.2 InNGR Iset4 199.086 A primer( )
Is4Iset4
CT20 Is4 0.498 A sekunder( )
Tap5Is4
In4 Tap5 0.1 pilih Tap5 0.17
Isetg20 Tap5 In4 CT20
Isetg20 340 A primer( )
tgi20 1 dt If20m If200
If20m 984.173
td4
If20m
Isetg20
0.02
1
0.14tgi20 td4 0.153
Isetg20 340 A primer( )
td4 0.153 Tap5 0.17
waktu kerja aktual :
3.2.3 SBEF sisi netral 20 kV NARI tipe RCS 9671C
Setelan arus
setelan aktual
waktu kerja yang diinginkan
pilih
(LTI)
waktu kerja aktual :
tgi200.14
If20m
Isetg20
0.02
1
td4
tgi20 1 dt
In8 5 A
IsetN 0.15 In20 IsetN 259.808 Primer
Iset8b 0.3 InNGR Iset8b 298.629 Primer
Iset8 IsetN IsetN Iset8b( ) Iset8b Iset8b IsetN( ) IsetN 259.808
Is8Iset8
CTNGRS Is8 1.299 A Sekunder
Tap8Is8
In8 Tap8 0.26 pilih Tap8 0.15
Iset8 Tap8 In8 CTNGRS Iset8 150 Primer
t8 5.0 dt If20m If200
If20m 984.173
td8
If20m
Iset8
1
120t8 td8 0.232
Iset8 150 A primer( )
td8 0.35
t8120
If20m
Iset8
1
td8
t8 7.552 dt
Koordinasi Rele Pengaman Untuk Gangguan Tanah
Kemampuan arus :
Nilai tahanan :
Batas waktu :
Kurva ketahanan termis :
Kurva SBEF (LTI) :
Kurva incoming trafo ; (SI)
Kurva Feeder 20 kV ; SKTM (SI)
3.3 Setelan Trafo sisi Tegangan Tinggi 150 kV3.3.1 OCR sisi 150 kV NARI tipe RCS 9671 C
Setelan arus
setelan aktual :
ImNGR 1 103
A x 1 1000
RNGRS 11.6
tNGR 10 detik
c ImNGR2
RNGRS tNGR
tnx
c
x2
RNGRS tn1
xc .5
x2
RNGRS
tLx
x
Iset81
120
x
Iset8
1
td8
x
Iset8 150 A
td8 0.35
Iset4 Isetg20 Iset4 340 At2
xx
Iset41
0.14
x
Iset4
0.02
1
td4
x td4 0.153
Iset7 80 At3
xx
Iset71
0.14
x
Iset7
0.02
1
td7
x td7 0.175
In1 1 A
Iset1 1.2 In150 Iset1 277.128 A primer( )
Is1Iset1
CT150
Is1 4.619 A sekunder( )
Tap1Is1
In1 Tap1 4.619 pilih Tap1 0.95
Iset150 Tap1 In1 CT150 Iset150 57 A primer( )
waktu kerja yang diinginkan
A
pilih
waktu kerja aktual :
Setelan arus moment OCR
untuk 1/I2 cycle
(Primer)
atau,
Pilih
tot150 1.5 dt I2f150m I2f1500
I2f150m 1.14 103
td1
I2f150m
Iset150
0.02
1
0.14tot150 td1 0.662
Iset150 57 A primer( )
td1 0.3 Tap1 0.95
tot1500.14
I2f150m
Iset150
0.02
1
td1 tot150 0.68 dt
n 1 6
Kn
1 2 e
4
n
2
X1 Xt1R1
K1
1.408 Pilih K1
1.5
Im1In150
Xt CT150K
1 Im1 46.893 A sekunder( )
Tap2Im1
In1 Tap2 46.893 pilih Tap2 9
Im150 Tap2 In1 CT150 Im150 540 A
Im2In150
XtK
1 Im2 2.814 10
3
ImsetIm2
Iset150 Imset 49.361
Imset 9.5 xIset150
3.3.2 GFR sisi 150 kV NARI tipe PCS 9611
Setelan arus GFR :
Pilih
Setelan waktu GFR SUTT untuk gangguan di bus 150 kV :
waktu kerja aktual GFR SUTT untuk gangguan di Bus 150 kV :
pilih :
3.3.3 GFR trafo sisi 150 kV NARI tipe RCS 9671
Setelan arus :
Setelan arus GFR Trafo :
Setelan aktual :
Isgbs 0.2 Insutt Isgbs 120 A primer( )
IsgIsgbs
Insutt
Isg 0.2
Isg 0.2 Isgbs Isg Insutt
Isgbs 120 A
tgsutt 1 dt
td32
If150sutttrf0
Isgbs
0.02
1
0.14tgsutt td32 0.457
Isetgfr150 Isgbs Isetgfr150 120 td32 0.45
tgsutt0.14
If150sutttrf0
Isgbs
0.02
1
td32 tgsutt 0.984
In3 1 A In150 230.94 A primer( )
Iset3 0.5 In150 Iset3 115.47 A primer( )
Is3Iset3
CT150
Is3 1.925 A sekunder( )
Tap4Is3
In3 Tap4 1.925 pilih Tap4 0.4
Isetg150 Tap4 In3 CT150 Isetg150 24 A primer( )
3.3.3 (a) SETTING GFR TT TRAFO DIKOORDINASIKAN DENGAN GFR SUTT Waktu kerja GFR Trafo 150 kVyang diinginkan untuk gangguan di Bus 150 kV
pilih
waktu kerja aktual :
waktu kerja aktual GFR Trafo. sisi 150 kV untuk gangguan di Bus 20 kV :
waktu kerja aktual GFR SUTT untuk gangguan di Bus 20 kV :
Untuk 1 pht sutt
Untuk 2 pht sutt
tgt150150 1.5 dt
Dengan satu sutt
If1150m If150trf0
If1150m 1.74 103
A primer( )
td3
If1150m
Isetg150
0.02
1
0.14tgt150150 td3 0.958
Isetg150 24 A primer( ) td3 0.6
tgt1501500.14
If1150m
Isetg150
0.02
1
td3 tgt150150 0.939 dt
tgt150200.14
If1201500
Isetg150
0.02
1
td3 tgt15020 8.265 dt
tgsutt200.14
If1201500
Isgbs
0.02
1
td32tgsutt20 2.885 dt
tgsutt200.14
If1201500
Isgbs 2
0.02
1
td32
tgsutt20 1.785 dt
3.3.3 (b) SETTING GFR TRAFO SISI 150 KV DIKOORDINASIKAN DENGAN 20 KV
waktu yang diinginkan :
Arus gangguan di bus 20 kV :
waktu kerja aktual GFR Trf. sisi 150 kV untuk gangguan di Bus 20 kV :
waktu kerja aktual GFR SUTT untuk gangguan di Bus 20 kV :
Jika terjadi gangguan disisi Bus 150 kV, maka GFR Trf. akan kerja pada t :
tgt150 1.5 dt
If1201500 39.792
td33
If1201500
Isetg150
0.02
1
0.14tgt150 td33 0.109
tgt1500.14
If1201500
Isetg150
0.02
1
td33 tgt150 1.5 dt
tgsutt200.14
If1201500
Isgbs
0.02
1
td32 tgsutt20 2.885 dt
tgt150150a0.14
If150trf0
Isetg150
0.02
1
td3 tgt150150a 0.939 dt
4. Koordinasi Setting Relai
4.1. Koordinasi OCR
sisi 150 kV trafosisi 150 kV trafo
incoming 20 kV
sisi incoming
penyulang
penyulang 20 kv
Gbr. 7 Koordinasi setting relai OCR penyulang, incoming trafo dan sisi 150 kV trafo
DATA WAKTU KERJA RELE PROTEKSI GFR PADA KOORDINASI SETTING SISI 150 KV TRAFO DENGAN SUTT DAN REL 20 KV UNTUK TRAFO Yyd
KoordinasiSetting GFR
LokasiGangguan
GFR TrafoSisi 20 kV
GFR TrafoSisi 150 kV
GFR SUTT
Gangguandi rel 20 kV
Sisi 150 kVTrafo denganSUTT Gangguan
di bus 150 kV Tidak kerja
Gangguandi rel 20 kV
Sisi 150 kVTrafo dengansisi 20 kV Gangguan
di bus 150 kV Tidak kerja
tgf20 0.476 tgt15020 8.265 tgsutt20 2.885
tgt150150 0.939 tgsutt 0.984
tgf20 0.476 tgt150 1.5 tgsutt20 2.885
tgt150150a 0.939 tgsutt 0.984
t1p
0.14
I2f150p
Iset150
0.02
1
td1 t2p
0.14
I2f20p
Iset20
0.02
1
td2 t3p
0.14
I2f20p
Iset6
0.02
1
td6
Iset150 57 A Iset20 2.078 103
Iset6 504
td1 0.3 td2 0.24 td6 0.2
0 1 2 3 4 5 6 7 8 9 100
0.5
1
1.5
2
2.5
3
3.5
4
4.5
5
Iset OCR sisi 150 kV = 277.5 A, TMS = 0.3 (SI)Iset OCR sisi 20 kV = 2000 A, TMS = 0.2 (SI)Iset OCR penyulang 480 A, TMS = 0.2 (SI)
t1 p
t2 p
t3 p
p
t110
1.002 detikt1
00.68 detik
t20
1.171 detikt2
103.546 detik
t30
0.481detik
t310
0.727 detik
4.2. Koordinasi GFR
(SI) (SI)
(SI) (SI)
sisi Trf. 150 kV sisi 150 kV Trf.
incoming 20 kVsisi incoming
penyulangpenyulang 20 kv
sisi SUTTsisi SUTT
Gbr. 8 Koordinasi setting relai GFR penyulang, trf. sisi 20 kV, trf. sisi 150 kV dan SUTT
I2f200
8.549 103
I2f1500
1.14 103
I2f2010
3.331 103
I2f15010
444.09
t1p
0.14
If120150p
Isetg150
0.02
1
td3t2
p0.14
If20p
Isetg20
0.02
1
td4
Isetg150 24 A Isetg20 340 A
td3 0.6 td4 0.153
t3p
0.14
If20p
Iset7
0.02
1
td7 t4p
0.14
If120150p
Isgbs
0.02
1
td32
Iset7 80 A Isgbs 120 A
td7 0.175 td32 0.45
0 1 2 3 4 5 6 7 8 9 100
0.5
1
1.5
2
2.5
3
3.5
4
4.5
5
IsetGFR Trafo sisi 150 kV 180 A, TMS 0.3 (SI)Iset GFR Trafo sisi 20 kV 400 A, TMS 0.125 (SI)Iser GFR penyulang 80 A, TMS 0.175 A (SI)Iset GFR SUTT 150 kV 120 A, TMS 0.45 (SI)
t1 p
t2 p
t3 p
t4 p
p
t10
8.265 detik t15
10.484
t20
1 detikt2
101.246
t30
0.476 detikt3
100.52
t40
2.885 detikt4
52.634
4.3. Koordinasi GFR 150 Trafo dengan SUTT
(SI) (SI)
Trafo
Trafo
SUTTSUTT
Gb.3. Koordinasi setting relai GFR sisi 150 kV Trafo dan SUTT 150 kV
5. Setelan Setting REF Trafo sisi TT
5.1. REF sisi 150 kV NARI tipe RCS 9671 C
5.1.1 Data Resistansi
Resistansi phase CT sekunder
Resistansi netral CT sekunder
Resistansi lead
Resistansi auxiliary trafo
Tegangan knee Volt
tSUp
0.14
If150sutttrfp
Isgbs
0.02
1
td32 tTRp
0.14
If150trfp
Isetg150
0.02
1
td3
Isgbs 120 Isetg150 24
td32 0.45 td3 0.6
0 1 2 3 4 5 6 7 8 9 100
0.2
0.4
0.6
0.8
1
1.2
1.4
1.6
1.8
2
tTR p
tSUp
p
tTR0
0.939
detiktTR
200.979
tSU0
0.984
tSU20
1.043 detik
Rct 1.0
RctN 0.90
Rl0.85
2
Rt 0
Vkp 275
5.1.2 Perhitungan setting
5.1.2.1 Setting Tegangan
a. Tegangan phasa
Volt
b. Tegangan netral
Volt
Tegangan relai minimum adalah harga terbesar antara tegangan phasa dan netral
Setelan tegangan relai Volt
5.1.2.2. Setting Arus
Arus nominal
Range arus dari 0.1 x In s/d 1,5 x In
Setting Arus
5.1.2.3. Arus Operasi Minimum
CT's number
Arus magnetisasi pada Vr
Arus operasi minimum
Sensitivitas pengamanan
CTref CTN150 A
If150trf0
1.74 103
A Primer( )
VrIf150trf
0
CTrefRct 2 Rl Rt Vr 53.645
VrNIf150trf
0
CTrefRctN 2 Rl( ) VrN 50.745
Vr 1.0 Vr Vr 53.645
Vr 15
in1 5 A In150 230.94
Isetr1 0.2 in1 Isetr1 1 A
n 4
im 0.01 A
iop Isetr1 n im( ) iop 1.04 A Sekunder( )
Iop iop CTref Iop 62.4 A Primer( )
sIop
In150100
s 27.02 %
5.2. Setelan REF Trafo sisi TT 20 kVSisi 20 kV REF sisi 20 kV NARI tipe RCS 9671 C
5.2.1 Data Resistansi
Resistansi phase CT sekunder
Resistansi netral CT sekunder
Resistansi lead
Resistansi auxiliary trafo
Tegangan knee Volt
5.2.2 Perhitungan setting
5.1.2.1 Setting Tegangan
Rasio CT untuk REF 20 kV
a. Tegangan phasa
volt
b. Tegangan netral
volt
Tegangan relai minimum adalah harga terbesar antara tegangan phasa dan netral
Setelan tegangan relai Volt
5.2.2.2. Setting Arus
Arus nominal rele
Range arus dari 0.1 x In s/d 1,5 x In
Setting Arus
5.2.2.3. Arus Operasi Minimum
CT's number
Arus magnetisasi pada Vr
Arus operasi minimum
Rct 8.15
RctN 5.5
Rl 0.8
Rt 0
Vks 285
If200
984.173
CTref20 CTN20 CTref20 400
VrIf20
0
CTref20Rct Rl 2 Rt Vr 23.989
VrNIf20
0
CTref20RctN 2 Rl( ) VrN 17.469
Vr 1.0 Vr Vr 23.989
Vr 20
in2 5 A
Isetr2 0.2 in2 Isetr2 1 A
n 4
im 0.01 A
Sensitivitas pengamanan
6. Setelan Differential Protection NARI tipe RCS 9671 C
I1n_CT_S1 = 0,3 kA Range 0.00 - 20.00 kA step 0.01 kAI2n_CT_S1 = 5 A Range 5A / 1A
I1n_CT_S2 = 2 kA Range 0.00 - 20.00 kA step 0.01 kAI2n_CT_S2 = 5 A Range 5A / 1A
I1n_CT_NP_S2 = 1 kA Range 0.00 - 20.00 kA step 0.01 kAI2n_CT_NP_S2 = 5 A Range 5A / 1A
I_Pkp_PcntDiff = 0,3 Range 0,2 - 1,5 Ie
Slope_PcntDiff = 0,3 Range 0,3 - 0,75
Opt_InrustBlk = 2 Range 0 - 3
I_Pkp_PcntREF_S1 = 0.1 Range 0.1 - 0.5Slope_PcntREF_S1 = 0.3 Range 0.3 - 0.75
I_Pkp_PcntREF_S2 = 0.1 Range 0.1 - 0.5Slope_PcntREF_S2 = 0.3 Range 0.3 - 0.75
iop Isetr2 n im( ) iop 1.04 A Sekunder( )
Iop iop CTref20 Iop 416 A Primer( )
sIop
In20100 s 24.018 %