Protection of Generators

download Protection of Generators

of 50

description

generators are high investment assets and are to be protected against damages due to electrical faults

Transcript of Protection of Generators

  • 5/28/2018 Protection of Generators

    1/50

    rotection of generators

    A Mini Project Report Submitted in the partial fulfillment

    Of the requirement for the award of

    BACHELOR OF TECHNOLOGY IN

    ELECTRICAL & ELECTRONICS ENGINEERING

    Submitted by

    R.Venkatesh - 096Q1A0213

    K.V.S.Kishore - 096Q1A0252

    S.Dorababu - 106Q5A0205

    A.V.V.Vikas - 096Q1A0201J.Ashok - 096Q1A0212

    K.N.V.Prasad - 096Q1A0220

    Under Esteemed guidance of

    Mr. SURESH

    (External guide)

    M r .P. Koteswararao

    (I nternal guide)

    DEPARTMENT OF ELECTRICAL AND ELECTRONICS ENGINEERING

    KAKINADA INSTITUTE OF ENGINEERING AND TECHNOLOGY II

    KORANGI

    2009-2013

  • 5/28/2018 Protection of Generators

    2/50

    ABSTRACT

    Generators and auxiliary transformers are subjected to a number of

    possible hazards for which protection should be provided. The main objective of

    generator protection is to detect faults and abnormal conditions as fast as possible

    and in case of fault to avoid extending the damage to a minimum. Protection

    scheme for Generator depend on many factors, such as size and importance of the

    machine, type of prime mover, grounding, protection philosophy etc

    This report is aimed to study the Protection of Generators in a Combined

    Cycle Power Plant (GVK-Jegurupadu). GVK is using the combined cycle principle

    for generation of power. Here air and gas combustion mixture is used to drive the gas

    turbine which in turn drives the gas turbine generator(GTG). In order to avoid

    wastage of energy of flue gases they are used for converting water in to steam and

    this is used to drive the steam turbine. Steam turbine acts as a governor to steam

    turbine generator(STG). The plant consist of two phases. Total capacity of plant is

    463MW (235MW of phase -1 and 228MW of phase-2).

    This plant is using the latest technology that is available for the

    operation. This plant is completely automated using the concept of digital control

    system (DCS)

    Signature of the internal guide: Signature of the HOD:

    Submitted by: R.Venkatesh (096Q1A0213)

    K.V.S.Kishore (096Q1A0252)S.Dorababu (106Q5A0205)

    A.V.V.Vikas (096Q1A0201)

    J.Ashok (096Q1A0212)

    K.N.V.Prasad (096Q1A0220)

  • 5/28/2018 Protection of Generators

    3/50

    ACKNOWLEDGEMENT

    We express our deep sense of gratitude to Ch. Vinod Kumar, Head

    of the Department of Electrical and Electronics Engineering, KIET+ for havingkeen interest at every stage of development of our project work and to

    P.Koteswara rao for guiding us in every aspect.

    We are also deeply indebted to C.V.S MURTHY,Principal, KIET+

    for providing the necessary facilities during the execution of this mini project.

    We thank Mr. N. Srinivasarao (GM) and HR team of GVK

    JEGURUPADU POWER GENERATION LIMITED for their help in completion

    of this project.

  • 5/28/2018 Protection of Generators

    4/50

    CONTENTS

    1. Introduction to power plants in india2. Introduction to GVK power plant3. Introduction to combined cycle power plant4. Operation and operating modes5.Need for protection of generators6. Protection schemes of generators7. Conclusion

  • 5/28/2018 Protection of Generators

    5/50

    INTRODUCTION TO POWER PLANTS IN INDIA

    The electricity sector in India supplies the world's 6th largest energy

    consumer, accounting for 3.4% of global energy consumption by more than 17%of global population. The Energy policy of India is predominantly controlled by

    the Government of India's, Ministry of Power, Ministry of Coal and Ministry of

    New Renewable Energy and administered locally by Public Sector

    Undertakings (PSU s).

    About 64.75% of the electricity consumed in India is generated by

    thermal power plants, 21.73% by hydroelectric power plants, and 2.78 % by

    nuclear power plants and by Renewable Energy Sources. More than 50% of India'scommercial energy demand is met through the country's vast coal reserves.

    INTRODUCTION ON GVK ENERGY POWER PLANT

    INTRODUCTION:

    GVK is 235MW of phase -1 and 228MW of phase-2 combined cyclepower plant located at Jegurupadu, east Godavari district. The combined cycle unit

    is multi- shaft power train with three gas turbine,one steam turbine of phase-1 and

    one gas turbine,one steam turbine of phase-2. The basic operation mode of the

    plant is to supply electrical power to grid. The facility operates with natural gas

    and is suitable for fuel oil as back-up. The plant is capable of running at maximum

    continuous rating (MCR) and a part load as well as continuous and in two shift

    operation. In a daily ambient temperature the minimum is 13.9C and the

    maximum is 49C. The design ambient air temperature is 29C. The performanceguarantee for the combined cycle plant is based on the gross electrical output.

    Water which is required for the plant is available from two sources; supplies such

    as tube wells. This report is aimed to study the operation of combined cycle power

    plant (ccpp). GVK is using the combined cycle principle for the generation of

    power. In this plant gas from GAIL is being used as the fuel input. Here this input

  • 5/28/2018 Protection of Generators

    6/50

    is combining chamber. Here this input is combining with atmospheric air and

    combustion these places inside the combustion chamber. Here flue gases are

    produced and wastage of flues are used to drive the gas turbine generator (GTG).

    In order to avoid wastage of flue gases they are using these flues for converting

    water in to steam and this is used the drive the steam turbine generator (STG).

    The power supplied by is in the form of three-phase 50-hertz AC current, at a

    nominal voltage 220kv of phase-1 and 400kv of phase-2.They power is generated

    power as per the power contracts and is supplied to the APTRANSCO department.

    This plant is using the latest technology that is available for operation. This plant is

    completely automated using the concept of digital control systems.

    SALIENT FEATURES:

    Capacity : 235MW of phase-1

    228MW of phase-2

    Location : Jegurupadu, East Godavaridistrict

    Type of station : combined cycle power plant

    Gas supply : GAIL

    PROCESS DESCRIPTION:

    The power plant uses natural gas as primary fuel and naphtha as alternative fuel

    with HSD as start-up fuel to produce power. Gas authority of India Limited

    (GAIL) supplies Natural gas. Raw water is drawn from reservoir.

    The exhaust gas from the turbine is led to heat recovery steam generator. The dual

    pressure steam generated is the steam turbineThe air water-cooled generator is

    coupled on the cold end side of the GT and ST generator at high-pressure side of

    ST and are arranged in parallel feeding two step up transformers. The gas turbine

    equipped with duel fuel hybrid burner i.e. capable of firing either Natural gas,

    liquid fuel (Naphtha/HSD) or Mix fuel operation. For natural gas operation with

  • 5/28/2018 Protection of Generators

    7/50

    premix burner no water injection is repudiation to match the required emission

    level. However liquid fuel operation will require water injection to reduce the

    NOX emission levels.

    The ambient air shall be filtered in three stages and led to the compressor ofthe gas Turbine. Gas Turbine is provided with two silo combustion chambers

    (inconal alloy) respectively. The compressed air enters the combustion chambers

    through the annular space provided on the outer side of the casing cone. The air

    and fuel mixture is burnt in silo combustion chambers. The hot gases then flow

    through the turbine with its four stages.

    After expanding in the turbine the flue gases shall be directly led in to the

    HRSG. Steam is generated in the HRSG by heat transfer from the water the flue

    gases to the water/steam. From the HRSG the super heated steam is expands. Thesuperheated LP steam is also led to the steam turbine as well. The expanded steam

    is condensed in a water cooled condenser and returned by the condensate pump to

    Deaerator via condensate preheater thus completing the cycle.

    In order to make best use of the thermal energy of the steam; the pressure at

    the exhaust end shall be optimized. For this purpose a surface type water-cooled

    condenser is provided and cooling is achieved by cooling water circulated through

    a forced cooling tower. The air as well as the non-condensable gases entering the

    ST and the circuit is extracted from the steam space of the condenser by the

    vacuum pump.

    The condensate is preheated to extract residual heat in the condensate

    preheater. It also equipped with circulation pumps and LP heater for maintaining

    desired inlet temperature to mitigate cold end corrosion (Dew point corrosion).

    From the feed water storage tank (Deaerator) the feed water is delivered to

    HP and LP drum using 2*100% HP and LP feed water pumps respectively. One

    pump is in operation at full load.

    The HP&LP bypass operation shall be in operation when the steam is not

    utilized in the steam turbine.The power generated by the gas turbine and the steam

    turbine generators are stepped up to 220KV& 400KV level and evacuated by

    APTRANSCO through overhead transmission lines.

  • 5/28/2018 Protection of Generators

    8/50

    INTRODUCTION TO CCPP

    The most efficient way for utilities to use gas or oils is in a combined-cycle

    system, which combines two means of producing electricity. Hot gases from the

    combustion chamber spin the gas turbine and the generator to make electricity. The

    system then pipes the still-hot exhaust gases leaving the combustion turbine to a

    'waste heat' steam boiler where their heat produces steam. The steam turns a

    turbine, connected to a second generator, to produce electricity. Condensers

    convert the steam to water that returns to the boiler to repeat the cycle.

    Combined cycle power plants are highly efficient, flexible, reliable, cost-effective

    and environmentally friendly solutions to generate electrical power.

    In combined cycle power plants (CCPPs) a gas turbine generator generates

    electricity while the waste heat from the gas turbine is used to make steam to

    generate additional electricity via a steam turbine.

    In other words: The output heat of the gas turbine flue gas is utilized to generate

    steam by passing it through a heat recovery steam generator (HRSG), so it can be

    used as input heat to the steam turbine power plant. This combination of two power

    generation cycles enhances the efficiency of the plant. While the electrical

    efficiency of a simple cycle plant power plant without waste heat utilizationtypically ranges between 25% and 40%, a CCPP can achieve electrical efficiencies

    of 60% and more. Supplementary firing further enhances the overall efficiency.

    The high fuel utilization factor of the plant contributes to low lifecycle costs.

    Together with an outstanding operational flexibility, CCPPs can provide a tailor-

    made solution for your power needs.

  • 5/28/2018 Protection of Generators

    9/50

    OPERATION AND OPERATING MODES

    The Combined cycle power plant (ccpp) is basically designed to produce

    electric power for the grid. In normal operation mode, the GT and ST are in

    operation.The GT should be running at 100% load for best efficiency.

    POWER GENERATION:

    The overall plant output is controlled by means of gas turbine.The steam

    turbine always generates the power, which is made available by the waste heat

    from the gas turbine. Therefore, control simplify involves varying the quantity of

    fuel supplied to the gas turbine and changing the gas turbine combustion airflow

    rate in the upper load range by variable inlet guide vanes.

    The steam cycle of power plant operates with sliding steam pressure. The

    pressure of the HP steam decreases proportionally to the combined cycle load

  • 5/28/2018 Protection of Generators

    10/50

    down to approximately 50%. At combined cycle loads above 50%,the steam

    turbine opens are fully open. At loads below 50%, the steam turbine control valves

    throttle to maintain a constant steam pressure. The result is an optimum efficiency

    of combined cycle power plant.

    NORMAL OPERATION:

    In normal operation,the set point of the by-pass valves is slightly above

    the actual live steam pressure.with combined cycle loads over 50%,the set point

    will automatically be raised. However, the speed of the set point adjustment is

    limited. Thus the pressure gradient is always kept with in the allowable limits for

    the HRSG drums even with fast loads increases of the gas turbine.

    The pressure of the LP/HP steam decreases proportionally to the combined

    cycle load down to approximately 80% of combined cycle load, the IP and LP

    control valves of the steam turbine maintains a constant pressure.

    BASE LOAD (FULL LOAD OPERATION):

    The load of the GT is limited to 100%, which is accomplished through the

    gas turbine control system. Combined cycle plant operation at 100% is defined

    with the GT running at 100% load (=base load) and the whole steam led through

    the ST. Base load operation of the GT is given by turbine inlet temperature at the

    pre-set base load temperature and the variable inlet guide vanes fully

    opened(max.flow). This definition applies toall ambient conditions.

    PART LOAD OPERATION:

    For high block efficiency at GT part load, the VIGV and fuel flow control

    keep the turbine exhaust temperature at a high level, down to approximately 60%

    GT load.

  • 5/28/2018 Protection of Generators

    11/50

    For low load operation, HP,IP&LP steam pressure are kept at their

    respective fixed pressure levels. If these pressure levels are exceeded, the

    steamturbine is operated in sliding pressure mode.

    The electrical output of the power plant is controlled only by means of thegas turbine. The GT gross load is controlled by the operator by entering manually a

    GT active gross load set point from the DCS in the control room.

    CONTROL SYSTEM

    GENERAL DESCRIPTION:

    The facility is equipped with an overall plant process control system basedon decentralised control system technology. This system enables safe and reliable

    operation, control and supervision of the process with a high degree of automation.

    The DCS system provides functions such as:

    - Signal conditioning, annunciation, recording- Operation, monitoring and supervision- Open and closed loop control, sequence logic, protection-

    Data communication, plant management applications

    CONTROL LOCATIONS:

    The plant will be operated and supervised from the main control room.

    All information required for remote operation and supervision of the GT, the ST

    and the other remote operable equipment is available in the main control room.

    The gas turbine is provided with its own safety system and governor, based

    on EGATROL technology. Necessary information for remote operation, control

    and monitoring are transferred to the overall plant control system.

    The steam turbine is provided with its own safety system and governor.

    Necessary information for remote operation, control and monitoring is transferred

    to the overall plant control system.

  • 5/28/2018 Protection of Generators

    12/50

    Autonomous systems are equipped with their own local control

    systems.These systems are provided with local control panels allowing for full

    local operation, control and monitoring.The necessary information for remote

    monitoring and/or control is transferred to the overall plant control system

    LIST OF AUTONOMOUS SYSTEMS:

    Autonomous system Remote control Remote monitoring

    Condenser tube cleaning

    system

    No Yes

    HV breakers for GT and

    ST generators

    synchronisation

    Yes Yes

    Waste water system No Yes

    Cooling water dosing

    system

    No Yes

    Generator step up and

    unit transformer

    Yes Yes

    Compressed air supply

    system

    No Yes

    Static starting device Yes Yes

    synchronisation Yes Yes

    Electrical protection

    system

    Yes Yes

    Automatic voltage

    regulator

    Yes Yes

    Fire protection system No Yes

    Stand by diesel generator Yes Yes

  • 5/28/2018 Protection of Generators

    13/50

    TURBINE

    The turbine converts the thermal energy in the combustion gas into

    mechanical energy which is transmitted through the compressor to the generator

    which produces electrical energy to the grid.

    INTRODUCTION TO GAS TURBINE:

    The gas turbine and generator delivers electric power to a grid in single cycle

    operation. Alternatively, it can deliver electrical power to a grid and its exhaust

    gasses to a heat recovery steam generator (HRSG) in combined cycle operation.

    The major components of the gas turbo set are the air intake system;

    compressor; combustor; turbine; exhaust gas system generator and exciter. This

    section will briefly describe the function of these components.

    GAS TURBINE IN POWER PLANT:

    The major components of the gas turbine are described below:

    The casing, which holds encloses the turbine and its stationary blade carrier,is a made of globular cast iron.

    The rotor is made of discs welded together to form a single shaft with thecompressor rotor.

    Turbine bladingconsists of stationary and rotating blades. The former aremounted in a blade carrier attached to the casing, while the rotating blades

  • 5/28/2018 Protection of Generators

    14/50

    are attached to the rotor. The conversion of heat energy into mechanical

    energy takes place within the turbines blading.

    The ring shaped stationary vane carrier holds the stationary vanes in theirrespective grooves. The carrier which hangs inside the turbine casing is

    made of material which can expand with changes in temperature.

    FUELSUSED INGAS TURBINE:

    Natural Gas from GAIL Naphtha (HPCL)

  • 5/28/2018 Protection of Generators

    15/50

    FEATURESOFGASTURBINES

    The gas turbines have the following opearational features. They are

    1. The gas turbines produce a large amount of useful work from the relativelysmall input

    2. The maintainance cost is less and the mechanical life is long when compared toapiston driven engine.

    3. The start up time to a full load for a gas turbine is in minutes VS for a steamturbine

    4. Gas turbines can operate utilizing various types of fuels. But generally naturalgas is been used in it.

    5. Atmospheric air is typically the working fluid for the gas turbine and doesnotrequire any coolant for basic power generation.

    AIR INTAKE SYSTEM

    The air intake system draws in ambient air, which passes through filtering

    and sound damping systems. It is then forwarded to the combustor where it is used

    in combustion and cooling functions.

    3-stage filter are used where required by ambient conditions. An anti-icing

    device is installed in cold weather climates to prevent the formation of ice at the

    compressor inlet.

    The major components of an air intake system with standard 2-stage filter

    are described below.

    LOUVERS:

    Ambient air is drawn in through louvers which prevent rain water and large

    foreign objects from entering the air intake duct.

    FILTER:

    The air then passes through a 2-stage filter which removes dirt and

    contaminants contained in the air.

  • 5/28/2018 Protection of Generators

    16/50

    SILENCER:

    The air, flowing at relatively high speed, then passes through a sound

    damper or silencer, which lessens the noise level.

    SAFETY FLAP VALVES:

    Located downstream from the filter housing, the safety flap valves open

    automatically if the filters become clogged and negative pressure within the

    housing becomes too high. This action prevents damage to the filter housing, air

    intake elbow and manifold.

    MANHOLE:

    A manholeis provided for cleaning and inspection purposes.

    COMPRESSOR:

    Air from the air intake system is forwarded to the compressor where it is

    compressed by the combined effect of rotating blades and stationary vanes. Atthe

    compressor outlet the compressed air is directed through a diffuser to the

    combustion chamber and into the hot gas path for cooling purposes. Another part

    of the compressed air is branched off for sealing purposes at those locations where

    the rotor passes through the casing.The intermediate shaft is attached to the

    compressors rotor coupling, at the cool end of the gas turboset. The intermediate

    shaft performs the following functions:

    Transfers mechanical power of gas turbines rotor to the generator rotor. Transfers the slow rotational motion of barring device through a latch wheel

    to the compressor and generator rotors to prevent the turbine shaft from

    bending during cool down period.

    Transfers the actual rotational speed of the rotor to the control systemthrough a gear wheel by non-contact rotational speed measurement.

    Transfer the phase angle to the control system by non-contact Proximitermeasurement.

  • 5/28/2018 Protection of Generators

    17/50

    The major components of compressor are described below:

    VARIABLE INLET GUIDE VANES:

    VIGV modulate the air flow from the air intake structure through the

    compressor.

    BLOW-OFF VALVES:

    These expel excess air to atmosphere during gas turbine start-ups and shut-

    downs. This prevents air turbulence with in the compressor and consequent

    stressing of the blades.

    DIFFUSER:

    It is a ring shaped device located at the compressors outlet. After thecompressed air flows through the diffuser, it is deflected by guide vanes into the

    turbine housing where it cools the turbinesstationary vane carrier before passing

    on the combustor.

  • 5/28/2018 Protection of Generators

    18/50

    BLADES:

    Rotating and fixed blades compress the air which flows into the compressor

    from the air intake system.

    BEARINGS:

    One journal and one thrust bearing is located in the air intake section hold

    and guide the compressors rotor in the radial and axial direction respectively. Oil

    from the lube oil system lubricates and cools the bearings.

    COMBUSTOR:

    The combustor is annular (ring) type is device placed around the shaft

    between the compressor and the turbine, it is here that the combustion process

    takes place. Combustion is a chemical reaction between oxygen in the pressurized

    air and combustible components(carbon and hydrogen) in the fuel. when the

  • 5/28/2018 Protection of Generators

    19/50

    mixture is ignited in the combustor, the hot, pressurized combustion gas is

    forwarded to the turbine where it is expanded through the blading.

    Because of the heat developed during combustion, the combustor must be

    cooled with air from the compressor. This happens in a counter-flow manner, thatis, the combustion gas flow and the cooling air flow move in opposite directions.

    The main components of the annular combustor are described below:

    A ring shaped housing, which encloses and holds all components of the

    combustor, is suspended with in the turbine housing.

    A heat shield segment and its support protect the primary zone from direct

    flame radiation. Its back side is cooled by air from the compressor.

    A front segment and its support protect the primary zone in which combustion

    takes place. It includes a cover plate and a support for the burners. The cover plate

    has holes through which the combustion air from the compressor reaches the

    compressor.

    STEAMTURBINESYSTEMS

    The steam turbine extract the energy of pressurized superheated steam as

    mechanical movement. An ideal steam turbine is considered to be anisentropic

    process,or constant entropy process, in which the entropy of the steam entering the

    turbine is equal to the entropy of the steam leaving the turbine. No steam turbine is

    truly isentropic, however, with typical isentropic efficiencies ranging from 20%-

    90% based on the application of the turbine. The interior of a turbine comprises

    several sets of blades, or buckets as they are more commonly referred to. One set

    of stationary blades is connected to the casing and one set of rotating blades is

    connected to the shaft. The sets intermesh with certain minimum clearances, with

    the size and configuration of sets varying to efficiently exploit the expansion of

    steam at each stage.

    http://en.wikipedia.org/wiki/Isentropic_processhttp://en.wikipedia.org/wiki/Isentropic_processhttp://en.wikipedia.org/wiki/Isentropic_processhttp://en.wikipedia.org/wiki/Isentropic_process
  • 5/28/2018 Protection of Generators

    20/50

    In a steam turbine nozzles apply pressurized supersonic steam to a set of

    curved blades mounted on a rotor. Each blade whips the steam back in the opposite

    direction, simultaneously allowing the steam to expand a little. A stationary blade

    then redirects the steam towards the next set of blades toward the exhaust end with

    the gap between acting like a nozzle. The process repeats in successive stages untilthe steam is exhausted at nearly atmospheric pressure. The moving blades are

    mounted radially on the rotor, while the stationary blades are mounted to the case

    of the turbine. Turbines always consist of a number of stages, with each stage

    being carefully optimized for the pressure and volume of steam that it contacts.

    Because high pressure steam exhausted through a nozzle into the air travels so fast,

    the turbine, in order for it to be efficient, must rotate very fast. This requires that

    the rotor and its blades be well balanced to protect it against vibrations, and creates

    difficulties with the seals around the rotor. The centrifugal force experienced bythe blade is so strong that it must be carefully designed and made out of the

    strongest available materials to prevent it from failing catastrophically.

    MAJOR COMPONENTS OF STEAM TURBINE:

    Casings Blading Blade carriers with stationary blades Welded disc rotor with rotating blades Dummy piston Rotor coupling Gland seals Bearings Stop and control valves Drain lines

  • 5/28/2018 Protection of Generators

    21/50

    CROSS SECTION OF STEAM TURBINE:

    CLASSIFICATION OF STEAM TURBINE PRESSURE:

    HP high pressure >105bar

    IP intermediate pressure ~105bar

    LP low pressure ~26bar

  • 5/28/2018 Protection of Generators

    22/50

    HP turbine casings are of double designed type, based on steam pressure and

    temperature at which the turbine will operate and the application for which the

    turbine was designed.

    LP blading, which is a mixture of impulse and reaction blading, operates in aslightly different environment. Steam passing through this section on its way to the

    condenser, expands from superheated steam to the point of saturation.

    NEED FOR PROTECTION OF GENERATORS

    Generators, unit transformers and auxiliary transformers are subject to a number of

    possible hazards for which protection should be provided. The main objective of

    generator protection is to detect faults and abnormal conditions as fast as possible

    and in case of fault to avoid extending the damage to a minimum.

    Protection scheme for Generator and unit transformers depend on many factors,

    such as size and importance of the machine, type of prime mover, grounding,

    protection philosophy etc, thereto, two main subjects must be taken into

    consideration at the design stage:

    Proper overall concept with co-ordinated main and backup protectionfunctional strategy. Selection should be based more on generators

    importance than on its rating

    Depending on power plant layout and its functional concept the Hardware should

    allow a tailored solution with a minimum of components.

  • 5/28/2018 Protection of Generators

    23/50

    PROTECTION SCHEMES OF GENERATORS

    The following are the main protection schemes adopted for our generator.

    1. Generator Differential Protection

    2. Loss of Field or Loss of Excitation Protection

    3. Negative Sequence or Current Unbalance Protection

    4. Over Fluxing or Over Excitation Protection

    5. Over Current Protection

    6. Stator Earth Fault Protection

    7. Rotor Earth Fault Protection

    8. Restricted Earth Fault Protection

    9. Backup Impedance Protection

    10. Low Forward Power Protection

    11. Reverse Power Protection

    12. Pole Slip Protection

    13. Pole Discrepancy Protection

    14. Local Breaker Back Protection

    15. Bus Bar Protection

    16. Over Frequency Protection

    17. Under Frequency Protection

    18. Over Voltage Protection

  • 5/28/2018 Protection of Generators

    24/50

    1.GENERATOR DIFFERENTIAL PROTECTION:

    Setting : 0.5 Amp Time : Instantaneous

    It is one of the important protections to protect generator winding against internal

    faults such as phase-to-phase and three phase-to-ground faults. This type of fault is

    very serious because very large current can flow and produce large amounts of

    damage to the winding if it is allowed to persist. One set current transformers of

    the generator on neutral and phase side, is exclusively used for this protection. The

    differential protection can not detect turn-to-turn fault and phase to ground within

    one winding for high impedance neutral grounding generator such as ours. Upon

    the detection of a phase-to-phase fault in the winding, the unit is tripped with out

    time delay.

    Relays acted : a. Flag operation at Protection panel.

    b. Acting of Master relay

    c. Indication at Annunciation Panel.

    Consequences : a. Tripping of 220KV breaker

    b. Tripping of Field breaker

    c. Stop command to Turbine thro Mark-IV

    Status : a. Unit is at coasting down.

    Once the differential protection operated, the unit can not be taken into service

    unless the generator winding is thoroughly examined by the maintenance staff of

    any internal faults

  • 5/28/2018 Protection of Generators

    25/50

    2.LOSS OF FIELD OR EXCITATION PROTECTION :

    Setting : K1-2, K2-1, K3-2 Trip after 2 Sec.

    When the synchronous machine with excitation, is connected to the grid, it

    generates reactive power along with active power to the grid and the rotor speed is

    same as that of grid frequency. Loss of field or loss of excitation results in loss of

    synchronism between rotor flux & stator flux. The synchronous machine operates

    as an induction machine at higher speed and draws reactive power from the grid.

    This will result in the flow of slip frequency currents in the rotor body as well as

    severe torque oscillations in the rotor shaft. As the rotor is not designed to sustain

    such currents or to withstand the high alternating torques which results in rotor

    overheating, coupling slippage and even rotor failure.

    A loss of excitation normally indicates a problem with the excitation system. Some

    times it may be due to inadvertent tripping of filed breaker, open or short circuit of

    field winding or loss of source to the exciter. If the generator is not disconnected

    immediately when it loses excitation wide spread instability may very quickly

  • 5/28/2018 Protection of Generators

    26/50

    develop and major system shutdown may occur.

    When loss of excitation alarm annunciates at annunciation panel, the machine may

    probably be running with less excitation at leading MVAR power. Increase the

    excitation on the machine until it reaches on lagging MVAR power. The machinetrips on the same protection along with alarm resynchronize the machine and try to

    stabilize at required MVAR power. If not possible, trip the machine immediately

    and inform to the maintenance staff for thorough checking of the Automatic

    Voltage Regulator (AVR) and its associated parts.

    Relays acted : a. Flag operation at Protection panel.

    b. Acting of Master relay

    c. Indication at Annunciation Panel.

    Consequences : a. Tripping of 220KV breaker

    b. Tripping of Field breaker

    c. Stop command to Turbine thro Mark-IV

    Status : a. Unit is at coasting down.

  • 5/28/2018 Protection of Generators

    27/50

  • 5/28/2018 Protection of Generators

    28/50

    3.NEGATIVE SEQUENCE OR CURRENT UNBALANCE PROTECTION:

    Setting : Alarm75% of 12s Time - 5 Sec.

    Trip75% of 12s Time - 300 Sec.

    When the machine delivering the equal currents in three phases, no unbalance or

    negative phase sequence current is produced as the vector sum of these currents is

    zero, when the generator is supplying an unbalanced load to a system, a negative

    phase sequence current is imposed on the generator. The system unbalance may be

    due to opening of lines, breaker failures or system faults. The negative sequence

    current in the stator winding creates a magnetic flux wave in the air gap which

    rotates in opposite direction to that of rotor synchronous speed. This flux induces

    currents in the rotor body, wedges, retaining rings at twice the line frequency.

    Heating occurs in these areas and the resulting temperatures depend upon the level

  • 5/28/2018 Protection of Generators

    29/50

    and duration of the unbalanced currents. Under these conditions it is possible to

    reach temperatures at which the rotor material no longer contain the centrifugal

    forces imposed on them resulting in serious damage to the turbine-generator set.

    Any machine as per design data will permit some level of negative sequence

    currents for continuous period.

    An alarm will annunciate at annunciation panel if negative sequence currents

    exceeds a normal level. Reduce the MVAR power on the machine if necessary

    load also and keep the machine for some time till the alarm vanishes at

    annunciation panel. If the machine trips on the Negative sequence protection never

    take the machine into service until the temperatures on the rotor parts settle down

    to its lower value. Resynchronize the machine to the grid after considerable time

    under grid & feeder parameters are within limits. If the unit trips again on the same

    protection, stop the machine after consideration time so as to cool down the rotor

    parts and inform to the maintenance staff for thorough examination of the system.

    Relays acted : a. Flag operation at Protection panel.

    b. Acting of Master relay

    c. Indication at Annunciation Panel.

    Consequences : a. Tripping of 220KV breaker

    b. Tripping of Field breaker

    Status : a. Unit is at FSNL.

  • 5/28/2018 Protection of Generators

    30/50

    4. OVER FLUXING OR EXCITATION OR VOLTS PER HERTZ

    PROTECTION:

    Setting : Alarm1.17 Time - 10 Sec.

    Trip1.17 Time - 30 Sec.

    Per unit voltage divided by per unit frequency commonly called Volts/Hertz is a

    measurable quantity that is proportional to flux in the generator or step-up

    transformer cores. Moderate over fluxing (105-110%) increases core loss resulting

    in increase of core temperatures due to hysterics & eddy currents loss. Long term

    operation at elevated temperatures can shorten the life of the stator insulation.

    Severe over fluxing can breakdown inter-laminar insulation followed by rapid

    local core melting. Over fluxing normally can be caused by over speed of the

    turbine or over excitation during Off-line condition, and load rejection or AVR

    mal-functioning during On-line condition.

    If alarm annunciation panel, Increase/Reduce the speed of the turbine to ratedgenerator speed (3000RPM) and reduce the generator voltage to rated during Off-

    line condition. Reduce the MVAR power on the generator during On-line

    condition. If the machine trips on over fluxing protection during On-line, Keep the

    machine at FSNL till the grid parameters stabilize and resins. Again the machine

    trips on the same stop the machine for examination of the AVR & Governor

  • 5/28/2018 Protection of Generators

    31/50

    systems by maintenance staff.

    Relays acted : a. Flag operation at Protection panel.

    b. Acting of Master relay

    c. Indication at Annunciation Panel.

    Consequences : a. Tripping of 220KV breaker

    b. Tripping of Field breaker

    c. Stop command to Turbine thro Mark-IV

    Status : a. Unit is at coasting down.

  • 5/28/2018 Protection of Generators

    32/50

    5.OVER CURRENT WITH VOLTAGE RESTRAINT PROTECTION:

    Setting : Alarm85% Time - 10 Sec.

    Trip100% Time - 0.5 Sec.

    Normally generators are designed to operate continuously at rated MVA,

    frequency and power factor over a range of 95 to 105% rated voltage. Operating

    the generator at rated MVA with 95% voltage, 105% stator current is permissible.

    Operating of the generator beyond rated KVA may result in harmful stator over

    current. A consequence of over current in winding is stator core over heating and

    leads to failure of insulation.

    If alarm annunciates at annunciation panel, Reduce the stator current to the below

    the rated by reducing the MVAR power on the machine. When the trips on thesame protection, Resins the machine after keeping the machine at FSNL for some

    time, and keep the stator current below the rated.

    Relays acted : a. Flag operation at Protection panel.

    b. Acting of Master relay

    c. Indication at Annunciation Panel.

    Consequences : a. Tripping of 220KV breaker

    b. Tripping of Field breaker

    Status : a. Unit is at FSNL.

  • 5/28/2018 Protection of Generators

    33/50

    6. STATOR EARTH FAULT PROTECTION:

    Setting : 70% Time - 5 Sec.

    Normally the generator stator neutral operates at a potential close to ground. If a

    faulty phase winding connected to ground, the normal low neutral voltage could

    rise as high as line-to-neutral voltage depending on the fault location. Although a

    single ground fault will not necessarily cause immediate damage, the presence of

    one increases the probability of a second. A second fault even if detected by

    differential relay, may cause serious damage. The usual method of detection fault

    is by measuring the voltage across the secondary of neutral grounding transformer

    (NGT). Here are two over lapping zones to detect stator ground faults in a high

    impedance grounded generator system, the two zones are put together cover 100%

    stator winding for earth faults. A fundamental frequency neutral over voltage relaycovers about 0-95% of the stator zonal winding for all faults except those near the

    neutral. Another third harmonic neutral under voltage relay covers remaining 96-

    100% of the stator zone 2 winding on neutral side.

    Relays acted : a. Flag operation at Protection panel.

    b. Acting of Master relay

    c. Indication at Annunciation Panel.

    Consequences : a. Tripping of 220KV breaker

    b. Tripping of Field breaker

    c. Stop command to Turbine thro Mark-IV

    Status : a. Unit is at coasting down.

  • 5/28/2018 Protection of Generators

    34/50

    7.ROTOR EARTH FAULT PROTECTION :

    Settings : Less than 80K ohm

    Any rotor field winding of the generator is electrically isolated from the ground.

    Therefore the existence of one ground fault in the field winding will usually not

    damage the rotor. However the presence of two or more ground faults in the

    winding will cause magnetic and thermal imbalance plus localized heating and

    damage to the rotor metallic parts. The rotor earth fault may be caused due to

    insulation failure of winding or inter-turn fault followed by localized heat.

    Relays acted : a. Flag operation at Protection panel.

    b. Acting of Master relay

    Consequences : a. Tripping of 220KV breaker

    b. Tripping of Field breaker

    c. Stop command to Turbine thro Mark-IV

  • 5/28/2018 Protection of Generators

    35/50

    Status : a. Unit is at coasting down.

    8.RESTRICTED EARTH FAULT PROTECTION:

    Settings : 0.1 Amp. Time : Instantaneous

    It is Status : a. Unit is at coasting down.

    similar to generator differential protection in working. It protects the high voltage

    winding of 11/220KV power transformer against internal faults. One set current

    transformers of the power transformer on neutral and phase side, is exclusively

    used for this protection. The protection can not detect turn-to-turn fault within one

    winding. Upon the detection of a phase-to-phase or phase-to-ground fault in the

    winding, the unit to be tripped without time delay.

    Relays acted : a. Flag operation at Protection panel.

    b. Acting of Master relay

    c. Indication at Annunciation Panel.

    Consequences : a. Tripping of 220KV breaker

  • 5/28/2018 Protection of Generators

    36/50

    b. Tripping of Field breaker

    c. Stop command to Turbine thro Mark-IV

    Status : a. Unit is at coasting down.

    Once the restricted earth fault protection operated, the unit can not be taken into

    service unless the transformer winding is thoroughly examined by the maintenance

    staff for any internals faults.

    9.BACKUP IMPEDANCE PROTECTION:

    Settings ; K1-3, K2-0.71 Time1.5 Sec.

    As in name implies, it is used to protect the generator from supplying the over

    loaded or faulty system. It is backup protection of the generator over current

    protection. In measures ratio of the voltage and current supplied by the generator

    and initiates trip signal when the measured impedance is less than the preset value.

    If the machine trips on the Backup protection, never take the machine into serviceuntil the temperatures of the generator settle down to its lower value.

    Resynchronize the machine to the grid after considerable time when grid & feeder

    parameters are within limits.

    Relays acted : a. Flag operation at Protection panel.

  • 5/28/2018 Protection of Generators

    37/50

    b. Acting of Master relay

    c. Indication at Annunciation Panel.

    Consequences : a. Tripping of 220KV breaker

    b. Tripping of Field breaker

    c. Stop command to Turbine thro Mark-IV

    Status : a. Unit is at coasting down

  • 5/28/2018 Protection of Generators

    38/50

    10.LOW FORWARD POWER PROTECTION:

    Setting : 0.5% Time : 1 Sec.

    The generator will not develop output power when turbine input is less than the no

    load losses and motoring action develops on the turbine. The generator is able to

    generate power, usually 55 to 10% of generator capacity, within pre-determined

    time after closing of 220KV breaker.

    Relays acted : a. Flag operation at Protection panel.

    b. Acting of Master relay

    c. Indication at Annunciation Panel.

    Consequences : a. Tripping of 220KV breaker

    Status : a. Unit is at FSNL with potential.

  • 5/28/2018 Protection of Generators

    39/50

    The unit trips on the low forward protection, Resins the machine and increase input

    power to the turbine as quickly as possible within low forward power time setting.

    Even after two to three attempts, the machine is tripping on the same protection;

    probably the governor of turbine is faulty. Inform to maintenance staff for

    rectification of the same

    11.REVERSE POWER PROTECTION:

    Setting : 0.5% Time - 2.0 Sec.

    It is backup protection to the low forward protection. Motoring of a generator will

    occur when turbine output is reduced such that it develops less than no-load losses

    while the generator is still on-line, the generator will operate as a synchronousmotor and driving the turbine. The generator will not be harmed by synchronous

    motoring and a steam turbine can be harmed through over heating during

    synchronous motoring if continued long enough. The motoring of the turbine

    output can be detected by reverse power protection. The avoid false tripping due to

    power swings a time delay is incorporated before tripping signal is generated.

    Relays acted : a. Flag operation at Protection panel.

    b. Acting of Master relay

    c. Indication at Annunciation Panel.

    Consequences : a. Tripping of 220KV breaker

    b. Tripping of Field breaker

    c. Stop command to Turbine thro Mark-IV

    Status : a. Unit is at coasting down.

    The unit trips on the reverse power protection. Resins the machine and increase the

    input power to the turbine as quickly as possible within low forward power time

    setting. Even after two to three attempts, the machine is tripping on the same

    protection; probably the governor of turbine is faulty. Inform to maintenance staff

    for rectification of the same.

  • 5/28/2018 Protection of Generators

    40/50

    12.POLE SLIP OR OUT-OF-STEP PROTECTION:

    Setting : 6.9 ohm.

    When a generator loses synchronism, the resulting high current peaks and off-

    frequency operation may cause winding stresses, pulsation torques and mechanical

    resonances that have the potential danger to turbine generator. Therefore, to

    minimize the possibility of damage, it is generally accepted that the machine

    should be tripped without time delay preferably during the first half-slip cycle of

    the loss of synchronism condition. The electrical center during loss-of-synchronous

    conditions can occur in the generator as a result of increased impedance of the

    generator while decrease system impedance. The protections normally applied in

    the generator zone such as back-up impedance, loss of excitation etc., will not

    protect a generator during loss of synchronism under normal generator conditions.

    Relays acted : a. Flag operation at Protection panel.

    b. Acting of Master relay

    c. Indication at Annunciation Panel.

    Consequences : a. Tripping of 220KV breaker

    b. Tripping of Field breaker

    c. Stop command to Turbine thro Mark-IV

    Status : a. Unit is at coasting down.

    The unit trips on the Pole slip protection, Resynch the machine after stabilization

    of the grid parameters

    13.POLE DISCREPANCY PROTECITON:

    Setting : 0.5 Sec.

    If One or two poles of generator breaker fail to close during synchronization, all

    poles of the breaker trip on this protection. It may be due to mechanical failure of

  • 5/28/2018 Protection of Generators

    41/50

    the breaker un equal distribution of closing signal to the breaker from protection

    system.

    Relays acted : a. Flag operation at 220KV Breaker panel.

    b. Indication at Annunciation Panel.

    Consequences : a. tripping of 220KV breaker

    Status : a. Unit is at FSNL with potential.

    The generator breaker trips on the pole discrepancy protection, Resynch the

    generator. Even after two to three attempts, the machine is tripping on the same

    protection, probably the generator breaker is faulty. Inform to maintenance staff for

    rectification of the same.

  • 5/28/2018 Protection of Generators

    42/50

    14.LOCAL BREAKER BACKUP PROTECTION:

    Setting : 25% Time : 0.8 Sec.

    For most of the faults, the generator breaker involves tripping the generator from

    the system. Failure of the breaker to open probably results in loss of protection and

    other problems such as motoring action or single phasing, If one or two poles of

    the generator breaker fail to open due to mechanical failure in breaker mechanism,

    the result can be a single phasing and negative phase sequence currents inducted on

    the rotor. The LBB protection is energized when the breaker trip is initiated after a

    suitable time interval if confirmation of the confirmation of breaker tripping from

    three poles is not received. The energized tripping signal from LBB protection will

    trip all 220KV generator breakers and all 220KV feeder breakers through Bus-bar

    protection.

    Relays acted : a. Flag operation at Protection panel.

    b. Acting of Master relay for all units.

    c. Indication at Annunciation Panel.

    Consequences : a. Tripping of 220KV breaker

    b. Tripping of Field breaker of all units.

    Status : a. all Units are at FSNL.

    Once the LBB protection operated, the entire station is in dark. First restore all

    essential services to all units such as lube oil system and turning gear etc., from

    battery backup and. Checkup the faulty 220KV breaker and isolate the breaker

    from the system by opening the both side of the isolators.

    After restoring all services from station supply, Close 220KV feeder breakers first

    and take all units into service one after the other duly co-coordinating with theDE/LD.

    Since it involves complex operation, it is necessary to get help from maintenance

    staff for restoring the normally in the station. Never attempt to close the faulty

    220KV generator in panic as it causes permanent damage to the generator and

    transformer.

  • 5/28/2018 Protection of Generators

    43/50

    15.BUS BAR PROTECTION:

    Setting : 0.8 Amp.

    There are mainly three protection zones namely called generator zone, bus duct

    transformer zone, 220KV breakers zone. The protection of generator zone and bus

    duct & transformer zone are covered in previous schemes. All 220KV breakers atswitchyard will come under Bus-Bar protection. Functioning of this scheme is

    similar to the generator differential protection or generator-transformer differential

    protection. It measures all incoming currents from the generators at 220KV side

    and all outgoing currents in 220KV feeders, and initiates trip signal if it detects any

    deviation more than the preset value as the algebraic sum of all currents at 220KV

  • 5/28/2018 Protection of Generators

    44/50

    bus must be less than the preset value. It isolates all 220KV generator breakers and

    all 220KV feeder breakers connected to 220KV bus.

    Relays acted : a. Flag operation at Protection panel.

    b. Acting of Master relay for all units.

    c. Indication at Annunciation Panel.

    Consequences : a. Tripping of 220KV breaker

    b. Tripping of Field breaker of all units.

    Status : a. all Units are at FSNL.

    Once the Bus-Bar protection operated, the entire station is in dark. First restore allessential services to all units such as lube oil system and turning gear etc., from

    battery backup and 6.6/0.44KV Stage II reserve power supply. Checkup the

    entire 220KV switch yard for any wire snapping or equipment damage.

    After restoring all services from station supply, Close 220KV feeder breakers first

    and take all units into service one after the other duly co-ordinating with the

    DE/LD.

    Since it involves complex operation, it is necessary to get help from maintenance

    staff for restoring the normalcy in the station. Never attempt to restore the 220KV

    supply at switch yard in panic unless the entire system is thoroughly examined and

    satisfy yourself as it causes permanent damage to the equipment or injury/death to

    the person working at switch yard.

  • 5/28/2018 Protection of Generators

    45/50

    16.OVER FREQUENCY PROTECTION:

    Setting : 52 Hz Time - 2 Sec.

    For a generator connected to a system, abnormal frequency operation is a result ofa severe system disturbance. The generator can tolerate moderate over frequency

    operation provided voltage is within an acceptable limits. The machine operated at

    higher speeds at which the rotor material no longer contain the centrifugal forces

    imposed on them resulting in serious damage to the turbine-generator set. The

    abnormal over frequency on the machine may be due to improper speed control

  • 5/28/2018 Protection of Generators

    46/50

    adjustment or disoperation of the speed controller or severe grid disturbance or

    sudden load through off.

    Relays acted : a. Flag operation at Protection panel.

    b. Acting of Master relay

    c. Indication at Annunciation Panel.

    Consequences : a. Tripping of 220KV breaker

    b. Tripping of Field breaker

    c. Stop command to Turbine thro Mark-IV

    Status : a. Unit is at coasting down.

    The unit trips on the over frequency protection, Resins the machine. Even after two

    to three attempts, the machine is tripping on the same protection; probably the

    governor of turbine is faulty. Inform to maintenance staff for rectification of the

    same.

    17.UNDER FREQUENCY PROTECTION:

  • 5/28/2018 Protection of Generators

    47/50

    Setting : 48 Hz Time : 2.0 Sec.

    For a generator connected to a system, under frequency operation is a result of a

    severe system disturbance. The generator can tolerate moderate under frequency

    operation provided voltage is within an acceptable limits. The machine operated atlower higher speeds causes severe over fluxing in the generator-transformer. The

    abnormal under frequency on the machine may be due to improper speed control

    adjustment or disoperation of the speed controller.

    Relays acted : a. Flag operation at Protection panel.

    b. Indication at Annunciation Panel

    Consequences : a. NIL

    Status : a. Unit is at lower speed with potential.

    Increase governor speed until machine reaches full speed. Even after two to three

    attempts, the machine are running at lower speed, probably the governor of turbine

    is faulty. Inform to maintenance staff for rectification of the same.

    18.OVER VOLTAGE PROTECTION :

  • 5/28/2018 Protection of Generators

    48/50

    Setting : a. 110% Time - 2.0 Sec.

    b. 120% Time - 0.3 Sec.

    Generator voltage is at present value under normal operating conditions as selected

    by operator in AVR. If it parts from preset value, May be due to AVR mal-

    functioning or a system disturbance. Severe over voltage can cause over fluxing

    and winding insulation failure. The over voltage protection can be considered as a

    backup to the Volts-per-Hertz protection.

    Relays acted : a. Flag operation at Protection panel.

    b. Acting of Master relay

    c. Indication at Annunciation Panel.

    Consequences : a. Tripping of 220KV breaker

    b. Tripping of Field breaker

    Status : a. Unit is at FSNL without potential.

    Raise the generator voltage slowly with manual mode in AVR and keep generator

    voltage within the limits of normal voltage. If it is unable to control the generator

    voltage, trip the field breaker and inform to the maintenance staff for rectification

    of the AVR.

  • 5/28/2018 Protection of Generators

    49/50

  • 5/28/2018 Protection of Generators

    50/50

    CONCLUSION:

    In this mini project we had linked up the project work as

    practical oriented with full pledge involvement with Operations & Maintenance

    team. We had studied the working of generator and its protection schemes atGVKenergypower plant. And we also studied how the electrical power generated

    & exported in the combined cycle power plant.

    This project completely discussed about the protection of generators

    in combined cycle power plant. As new source of natural gases are found and with

    the increasing demand for electrical power, plants like this are of significance

    importance. To increase the efficiencies of the plant, combined cycle principle is

    adopted. In this modified plant the exhausts of gas stage are used for stream stage,

    so the operational parameters have different considerations at varies operational

    times