BA058D/06/en/10.0350098512
Valid as of software version:V 1.06.XX (amplifier)V 1.03.XX (communication)
PROline promass 80Coriolis Mass Flow Mesuring System
Description of Device Functions
MASS FLOW VOLUME FLOW DENSITY TEMPERATURE
UNIT VOLUMEUNIT MASS FLOW UNIT MASS
COMMISSIONING
LANGUAGE
ASSIGN LINE 1
SUMASSIGN
TOTALIZER
ASSIGN CURRENT
OPERATIONMODE
ASSIGN STATUSOUTPUT
ASSIGN STATUSINPUT
TAGNAME
ASSIGNLF-CUTOFF
INSTALLATIONDIRECTION
K-FACTOR
ACTUAL SYSTEMCONDITION
FAILSAFE MODE
SERIALNUMBER
SW-REV.AMP.
ACCESS CODE
ASSIGN LINE 2
OVERFLOW
CURRENT SPAN
ASSIGNFREQUENCY
ON-VALUE
AKTIVE LEVEL
TAGDESCRIPTION
ON-VALUE
MEASURINGMODE
ZEROPOINT
PREVIOUS SYST.CONDITION
SIMULATIONMEASURAND
SW-REV.-NO.SENSOR
SENSORTYPE
I/O-MODULTYPE
SW-REV.I/O-MODUL
UNITVOLUME FLOW
DEFINE PRIVATECODE
100% VALUELINE 1
100% VALUELINE 2
UNIT SUM
VALUE 0_4 mA VALUE 20 mA
END VALUEFREQUENCY
OFF-VALUE
MIN. PULSE WIDTH
BUS ADDRESSE
OFF-VALUE
POSITVE ZERORETURN
NOMINALDIAMETER
ASSIGN SYSTEMERROR
VALUESIMULATION
STATUS ACCESS
VALUE F LOW
TIME CONSTANT
SIMULATIONSTATUS
HART PROTOCOL
EPD
SYSTEMDAMPING
SENSORTYPE
ERRORCATEGORY
MEASURINGVALUES
SYSTEM UNITS
QUICK SETUP
OPERATION
USER INTERFACE
TOTALIZER
CURRENTOUTPUT
PULSE/FREQ.-OUTPUT
STATUSOUTPUT
STATUSINPUT
COMMUNICATION
PROCESSPARAMETER
SYSTEMPARAMETER
SENSOR DATA
SUPERVISION
SIMULATION SYST.
SENSOR VERSION
AMP. VERSION
MASS FLOW VOLUME FLOW DENSITY TEMPERATURE
UNIT VOLUMEUNIT MASS FLOW UNIT MASS
COMMISSIONING
LANGUAGE
ASSIGN LINE 1
SUMASSIGN
TOTALIZER
ASSIGN CURRENT
OPERATIONMODE
ASSIGN STATUSOUTPUT
ASSIGN STATUSINPUT
TAGNAME
ASSIGNLF-CUTOFF
INSTALLATIONDIRECTION
K-FACTOR
ACTUAL SYSTEMCONDITION
FAILSAFE MODE
SERIALNUMBER
SW-REV.AMP.
ACCESS CODE
ASSIGN LINE 2
OVERFLOW
CURRENT SPAN
ASSIGNFREQUENCY
ON-VALUE
AKTIVE LEVEL
TAGDESCRIPTION
ON-VALUE
MEASURINGMODE
ZEROPOINT
PREVIOUS SYST.CONDITION
SIMULATIONMEASURAND
SW-REV.-NO.SENSOR
SENSORTYPE
I/O-MODULTYPE
SW-REV.I/O-MODUL
UNITVOLUME FLOW
DEFINE PRIVATECODE
100% VALUELINE 1
100% VALUELINE 2
UNIT SUM
VALUE 0_4 mA VALUE 20 mA
END VALUEFREQUENCY
OFF-VALUE
MIN. PULSE WIDTH
BUS ADDRESSE
OFF-VALUE
POSITVE ZERORETURN
NOMINALDIAMETER
ASSIGN SYSTEMERROR
VALUESIMULATION
STATUS ACCESS
VALUE F LOW
TIME CONSTANT
SIMULATIONSTATUS
HART PROTOCOL
EPD
SYSTEMDAMPING
SENSORTYPE
ERRORCATEGORY
MEASURINGVALUES
SYSTEM UNITS
QUICK SETUP
OPERATION
USER INTERFACE
TOTALIZER
CURRENTOUTPUT
PULSE/FREQ.-OUTPUT
STATUSOUTPUT
STATUSINPUT
COMMUNICATION
PROCESSPARAMETER
SYSTEMPARAMETER
SENSOR DATA
SUPERVISION
SIMULATION SYST.
SENSOR VERSION
AMP. VERSION
COMMISSIONING
LANGUAGE
ASSIGN LINE 1
SUMASSIGN
TOTALIZER
ASSIGN CURRENT
OPERATIONMODE
ASSIGN STATUSOUTPUT
ASSIGN STATUSINPUT
TAGNAME
ASSIGNLF-CUTOFF
INSTALLATIONDIRECTION
K-FACTOR
ACTUAL SYSTEMCONDITION
FAILSAFE MODE
SERIALNUMBER
SW-REV.AMP.
ACCESS CODE
ASSIGN LINE 2
O
CURRENT SPAN
ASSIGNFREQUENCY
ON-VALUE
AKTIVE LEVEL
TAGDESCRIPTION
ON-VALUE
MEASURINGMODE
ZEROPOINT
PREVIOUS SYST.CONDITION
SIMULATIONMEASURAND
SSENSORTYPE
I/O-MODULTYPE I
DEF
1
VA
EF
O
MIN.
BUS
O
PO
D
ASS
S
QUICK SETUP
OPERATION
USER INTERFACE
TOTALIZER
CURRENTOUTPUT
PULSE/FREQ.-OUTPUT
STATUSOUTPUT
STATUSINPUT
COMMUNICATION
PROCESSPARAMETER
SYSTEMPARAMETER
SENSOR DATA
SUPERVISION
SIMULATION SYST.
SENSOR VERSION
AMP. VERSION
Device Functions PROline Promass 80
2 Endress+Hauser
Device Functions PROline Promass 80 Table of Contents
Endress+Hauser 3
Table of Contents
1 Function matrix PROline Promass 80 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 51.1 The function matrix: layout and use . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 51.2 Graphical illustration of the function matrix . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
2 Group MEASURING VALUES . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
3 Group SYSTEM UNITS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
4 Group QUICK SETUP . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
5 Group OPERATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
6 Group USER INTERFACE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
7 Group TOTALIZER 1/2 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
8 Group HANDLING TOTALIZER . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
9 Group CURRENT OUTPUT 1/2 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
10 Group PULSE/FREQUENCY OUTPUT . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
11 Group STATUS OUTPUT . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3811.1 Information on the response of the status output . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4011.2 Switching action of the status output . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41
12 Group STATUS INPUT . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 42
13 Group COMMUNICATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 44
14 Group PROCESS PARAMETER . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 45
15 Group SYSTEM PARAMETER . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 49
16 Group SENSOR DATA . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 52
17 Group SUPERVISION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 54
18 Group SIMULATION SYSTEM . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 56
19 Group SENSOR VERSION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 57
20 Group AMPLIFIER VERSION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 57
21 Factory settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5821.1 SI units (not for USA and Canada) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5821.2 US units (only for USA and Canada) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 59
22 Index of key words . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 61
Table of Contents Device Functions PROline Promass 80
4 Endress+Hauser
Registered trademarks
HART�
Registered trademark of HART Communication Foundation, Austin, USA
S-DAT™, T-DAT™, F-CHIP™Registered trademarks of Endress+Hauser Flowtec AG, Reinach, CH
Device Functions PROline Promass 80 1 Function matrix PROline Promass 80
Endress+Hauser 5
1 Function matrix PROline Promass 80
1.1 The function matrix: layout and use
The function matrix is a two-level construct: the groups form one level, functions the other.The groups are the highest-level grouping of the control options for the measuring device.Each group comprises a number of functions.You select a group in order to access the individual functions for controlling or parameterizing the measuring device.
You will find an overview of the groups in the table of contents on Page 3 and in the graphical representation of the function matrix on Page 6.You will also find an overview of the functions on Page 6, complete with the page references of the detailed function descriptions.The descriptions of the individual functions start on Page 7.
Example of how to parameterize a function (in this case changing the language for the user interface):➀ Entry into the function matrix (F-key).➁ Select the OPERATION group.➂ Select the LANGUAGE function, change the setting from ENGLISH to DEUTSCH
with OS and save F (all texts displayed on the user interface appear in German).➃ Exit the function matrix (ESC > 3 seconds).
F-x
0xxx
xxx-
19-x
x-xx
-xx-
000
>3s
- + E
Esc
E
E
E
E
E E E E E
–+
➁
➃
➂
➀+
Esc
–+Esc
–
+Esc
–
E
1 Function matrix PROline Promass 80 Device Functions PROline Promass 80
6 Endress+Hauser
1.2 Graphical illustration of the function matrixU
NIT
LE
NG
TH
(p
. 12)
AC
TU
AL
FR
EQ
.(p
. 33)
DE
NS
ITY
SE
T V
ALU
E(p
. 47)
DE
NS
ITY
CO
EF.
C 1
(p. 5
3)
UN
IT T
EM
PE
RAT
UR
E(p
. 11)
TE
ST
DIS
PLA
Y(p
. 19)
VALU
E S
IM.
CU
RR
. (p
. 28)
FAIL
SA
FE
VA
LUE
(p
. 33)
VA
LUE
SIM
ULA
TIO
N
PU
LSE
(p.
37)
ZE
RO
PO
INT
AD
JUS
T
(p. 4
7)
DE
NS
ITY
CO
EF.
C 0
(p. 5
3)
OP
ER
ATIO
N H
OU
RS
(p. 5
5)
UN
IT R
EF.
DE
NS
ITY
(p
. 11)
BA
CK
LIG
HT
(p. 1
9)
SIM
ULA
TIO
N C
UR
R.
(p. 2
7)
FAIL
SA
FE
MO
DE
(p. 3
3)
SIM
ULA
TIO
N P
ULS
E(p
. 37)
FIX
. RE
F. D
EN
SIT
Y(p
. 47)
CA
L. C
OE
F. K
D 2
(p. 5
2)
MA
X. T
EM
P. C
AR
R.
(p. 5
3)
SY
ST
EM
RE
SE
T(p
. 55)
UN
IT D
EN
SIT
Y(p
. 11)
CO
NT
RA
ST
LC
D(p
. 19)
AC
TU
AL
CU
RR
EN
T(p
. 27)
TIM
E C
ON
STA
NT
(p. 3
2)
FAIL
SA
FE
MO
DE
(p. 3
6)
VA
L. S
IM. S
WIT
. PN
T(p
. 39)
EP
D R
ES
PO
NS
ET
IME
(p
. 46)
CA
L. C
OE
F. K
D 1
(p. 5
2)
MIN
. TE
MP.
CA
RR
.(p
. 53)
ALA
RM
DE
LAY
(p. 5
5)
TE
MP
ER
ATU
RE
(p. 7
)
UN
IT C
OR
R. V
OLU
ME
(p
. 10)
DIS
PLA
Y D
AM
PIN
G(p
. 19)
RE
SE
T T
OTA
L.(p
. 21)
FAIL
SA
FE
MO
DE
(p. 2
7)
OU
TP
UT
SIG
NA
L (p
. 32)
OU
TP
UT
SIG
NA
L(p
. 36)
SIM
. SW
ITC
H P
OIN
T
(p. 3
9)
DE
VIC
E I
D
(p. 4
4)
EP
D V
ALU
E H
IGH
(p. 4
6)
TE
MP.
CO
EF.
KT
(p. 5
2)
MA
X. T
EM
P. M
EA
S.
(p. 5
3)
ER
RO
R C
ATE
GO
RY
(p. 5
5)
RE
FE
RE
NC
E D
EN
SIT
Y
(p. 7
)
UN
IT C
OR
R. V
OL.
F
LOW
(p.
10)
AC
CE
SS
CO
DE
C
OU
NT
ER
(p.
16)
FO
RM
AT
(p. 1
8)
TOTA
LIZ
ER
MO
DE
(p. 2
1)
TIM
E C
ON
STA
NT
(p. 2
7)
VA
LUE
F H
IGH
(p
. 30)
PU
LSE
WID
TH
(p. 3
5)
AC
TU
AL
STA
TU
S(p
. 39)
VA
L. S
IM. S
TAT.
IN(p
. 43)
MA
NU
FAC
TU
RE
R ID
(p. 4
4)
EP
D V
ALU
E L
OW
(p. 4
6)
PR
ES
SU
RE
(p. 4
8)
FLO
W D
AM
PIN
G
(p. 5
1)
TE
MP.
CO
EF.
KM
2(p
. 52)
MIN
. TE
MP.
ME
AS
.(p
. 53)
AS
SIG
N P
RO
C. E
RR
. (p
. 54)
DE
NS
ITY
(p. 7
)
UN
IT V
OLU
ME
(p. 9
)
STA
TU
S A
CC
ES
S(p
. 16)
100%
VA
LUE
(p. 1
8)
UN
IT T
OTA
LIZ
ER
(p. 2
1)
VA
LUE
20
mA
(p. 2
4)
VALU
E F
LO
W
(p. 3
0)
PU
LSE
VA
LUE
(p. 3
5)
TIM
E C
ON
STA
NT
(p. 3
9)
SIM
. STA
TU
S IN
(p. 4
2)
HA
RT
PR
OTO
CO
L (p
. 44)
EM
PT
Y P
IPE
DE
T.(p
. 46)
PR
ES
SU
RE
MO
DE
(p. 4
8)
DE
NS
ITY
DA
MP
ING
(p. 5
1)
TE
MP.
CO
EF.
KM
(p. 5
2)
DE
NS
ITY
CO
EF.
C 5
(p. 5
3)
ER
RO
R C
ATE
GO
RY
(p
. 54)
SW
-RE
V. I/
O(p
. 57)
CO
RR
.VO
L.-F
LOW
(p
. 7)
UN
IT V
OLU
ME
FLO
W(p
. 9)
DE
F. P
RIV
ATE
CO
DE
(p. 1
6)
100%
VA
LUE
(p. 1
8)
OV
ER
FLO
W(p
. 20)
VA
LUE
0_4
mA
(p. 2
4)
EN
D V
ALU
E F
RE
Q.
(p. 2
9)
AS
SIG
N P
ULS
E(p
. 34)
OF
F-V
ALU
E
(p. 3
8)
MIN
. P
ULS
E W
IDT
H(p
. 42)
BU
S A
DD
RE
SS
(p. 4
4)
OF
F-V
AL.
LF
-CU
T O
FF
(p. 4
5)
RE
STO
RE
OR
IGIN
AL
(p. 4
8)
PO
S. Z
ER
O R
ET
UR
N
(p. 5
0)
NO
MIN
AL
DIA
ME
TE
R
(p. 5
2)
DE
NS
ITY
CO
EF.
C 4
(p. 5
3)
AS
SIG
N S
YS
. ER
RO
R
(p. 5
4)
VALU
E S
IM. M
EA
S.
(p. 5
6)
SW
-RE
V. S
-DAT
(p. 5
7)
I/O M
OD
UL
TY
PE
(p. 5
7)
VO
LUM
E F
LOW
(p. 7
)
UN
IT M
AS
S(p
. 8)
AC
CE
SS
CO
DE
(p. 1
5)
AS
SIG
N L
INE
2(p
. 17)
SU
M(p
. 20)
FAIL
SA
FE
MO
DE
(p
. 22)
CU
RR
EN
T S
PAN
(p. 2
3)
AS
SIG
N F
RE
QU
EN
CY
(p. 2
9)
VA
LUE
SIM
. FR
EQ
. (p
. 34)
ON
-VA
LUE
(p
. 38)
AC
TIV
E L
EV
EL
(p. 4
2)
TAG
DE
SC
RIP
TIO
N(p
. 44)
ON
-VA
L. L
F-C
UT
OF
F(p
. 45)
DE
NS
ITY
AD
JUS
T(p
. 48)
ME
AS
UR
ING
MO
DE
(p
. 49)
ZE
RO
PO
INT
(p. 5
2)
DE
NS
ITY
CO
EF.
C 3
(p. 5
3)
PR
EV.
SY
S. C
ON
D
(p. 5
4)
SIM
. M
EA
SU
RA
ND
(p
. 56)
SE
NS
OR
TY
PE
(p. 5
7)
LAN
GU
AG
E G
RO
UP
(p. 5
7)
MA
SS
FLO
W(p
. 7)
UN
IT M
AS
S F
LOW
(p. 8
)
UN
IT P
RE
SS
UR
E
(p. 1
2)
QS
CO
MM
ISS
ION
(p
. 13)
LAN
GU
AG
E(p
. 15)
AS
SIG
N L
INE
1(p
. 17)
AS
SIG
N T
OTA
LIZ
ER
(p. 2
0)
RE
SE
T A
LL T
OTA
LIZ
-E
RS
(p.
22)
AS
SIG
N C
UR
RE
NT
(p
. 23)
OP
ER
ATIO
N M
OD
E
(p. 2
9)
SIM
ULA
TIO
N F
RE
Q.
(p. 3
4)
AS
SIG
N S
TAT
US
(p. 3
8)
AS
SIG
N S
TAT
US
IN(p
. 42)
TAG
NA
ME
(p. 4
4)
AS
SIG
N L
F-C
UT
OF
F
(p. 4
5)
ME
AS
UR
E F
LUID
(p
. 47)
INS
TL.
DIR
. SE
NS
OR
(p
. 49)
K-F
AC
TOR
(p. 5
2)
DE
NS
ITY
CO
EF.
C 2
(p. 5
3)
AC
TU
AL
SY
S. C
ON
D.
(p. 5
4)
SIM
. FA
ILS
AF
E M
OD
E
(p. 5
6)
SE
RIA
L N
UM
BE
R
(p. 5
7)
SW
-RE
V. A
MP.
(p
. 57)
▼ ▼ ▼ ▼ ▼ ▼ ▼ ▼ ▼ ▼ ▼ ▼ ▼ ▼ ▼ ▼ ▼ ▼ ▼
ME
AS
UR
ING
VA
LU
ES
(p
. 7)
SY
ST
EM
UN
ITS
(p. 8
)
QU
ICK
SE
TU
P(p
. 13)
OP
ER
AT
ION
(p. 1
5)
US
ER
INT
ER
FAC
E(p
. 17)
TOTA
LIZ
ER
1/2
(p. 2
0)
HA
ND
LIN
G T
OTA
LIZ
ER
(p. 2
2)
CU
RR
EN
T O
UT
PU
T 1
/2(p
. 23)
PU
LS
E/F
RE
Q. O
UT.
(p
. 29)
STA
TU
S O
UT
PU
T
(p. 3
8)
STA
TU
S IN
PU
T(p
. 42)
CO
MM
UN
ICA
TIO
N
(p. 4
4)
PR
OC
ES
S P
AR
AM
. (p
. 45)
SY
ST
EM
PA
RA
ME
TE
R
(p. 4
9)
SE
NS
OR
DA
TA(p
. 52)
SU
PE
RV
ISIO
N(p
. 54)
SIM
UL
AT.
SY
ST
EM
(p. 5
6)
SE
NS
OR
VE
RS
ION
(p. 5
7)
AM
P. H
W V
ER
SIO
N(p
. 57)
Device Functions PROline Promass 80 2 Group MEASURING VALUES
Endress+Hauser 7
2 Group MEASURING VALUES
Function description MEASURING VALUES
! Note!• The engineering unit of the measured variable shown here can be set in the “SYSTEM UNITS” group
(see Page 8).• If the fluid in the pipe flows backwards, a negative sign prefixes the flow reading on the display.
MASS FLOW In this function, the currently measured mass flow appears on the display.
Display shows:5-digit floating-point number, including unit and sign(e.g. 462.87 kg/h; –731.63 lb/min; etc.)
VOLUME FLOW In this function, the currently measured volumetric flow appears on the display. The volumetric flow is derived from the measured mass flowrate and the den-sity of the fluid measured.
Display shows:5-digit floating-point number, including unit and sign(e.g. 5.5445 dm3/min; 1.4359 m3/h; –731.63 gal/d; etc.)
CORRECTED VOLUME FLOW
The calculated corrected volume flow appears on the display. The calculated corrected volume flow is derived from the measured mass flow and the refer-ence density of the fluid (density at reference temperature, measured or fixed entry).
User Interface:5-digit floating-point number, including unit and sign (e.g. 1.3549 Nm3/h; 7.9846 scm/day; etc.)
DENSITY In this function, the currently measured density or the specific gravity appears on the display.
Display shows:5-digit fixed-point number, including unit(e.g. 1.2345 kg/dm3; 993.5 kg/dm3; 1.0015 SG_20 °C; etc.)
REFERENCE DENSITY The density of the fluid, at reference temperature, appears on the display. The reference density can be measured or also specified via the function FIXED REFERENCE DENSITY.
User Interface:5-digit floating-point number, including unit, corresponding to 0.1000...6.0000 kg/dm3
(e.g. 1.2345 kg/dm3; 993.5 kg/m3; 1.0015 SG_20 °C; etc.)
TEMPERATURE In this function, the currently measured temperature appears on the display.
Display shows:5-digit floating-point number, including unit and sign(e.g. –23.4 °C; 160.0 °F; 295.4 K; etc.)
3 Group SYSTEM UNITS Device Functions PROline Promass 80
8 Endress+Hauser
3 Group SYSTEM UNITS
Function description SYSTEM UNITS
You can select the unit for the measured variable in this function group.
UNIT MASS FLOW Use this function to select the unit for displaying the mass flow (mass/time).
The unit you select here is also valid for:• Current output• Frequency output• Switching points (limit value for mass flow, flow direction)• Low flow cut off
Options:Metric:gram → g/s; g/min; g/h; g/daykilogram → kg/s; kg/min; kg/h; kg/dayMetric ton → t/s; t/min; t/h; t/day
US:ounce → oz/s; oz/min; oz/h; oz/daypound → lb/s; lb/min; lb/h; lb/dayton → ton/s; ton/min; ton/h; ton/day
Factory setting:Country dependent (kg/h or US lb/day)
UNIT MASS Use this function to select the unit for displaying the mass.
The unit you select here is also valid for:• Pulse value (e.g. kg/p)
Options:Metric → g; kg; t
US → oz; lb; ton
Factory setting:Country dependent (kg or US lb)
! Note!The unit for the totalizer is independent of your choice here, it is selected separately in the TOTALIZER group (see Page 20).
Device Functions PROline Promass 80 3 Group SYSTEM UNITS
Endress+Hauser 9
UNIT VOLUME FLOW Use this function to select the unit for the volume flow.
The unit you select here is also valid for:• Current output• Frequency output• Switching points (limit value for volume flow, flow direction)• Low flow cut off
Options:Metric:Cubic centimeter → cm3/s; cm3/min; cm3/h; cm3/dayCubic decimeter → dm3/s; dm3/min; dm3/h; dm3/dayCubic meter → m3/s; m3/min; m3/h; m3/dayMilliliter → ml/s; ml/min; ml/h; ml/dayLiter → l/s; l/min; l/h; l/dayHectoliter → hl/s; hl/min; hl/h; hl/dayMegaliter → Ml/s; Ml/min; Ml/h; Ml/day
US:Cubic centimeter → cc/s; cc/min; cc/h; cc/dayAcre foot → af/s; af/min; af/h; af/dayCubic foot → ft3/s; ft3/min; ft3/h; ft3/dayFluid ounce → oz f/s; oz f/min; oz f/h; oz f/dayGallon → gal/s; gal/min; gal/h; gal/dayMillion gallon → Mgal/s; Mgal/min; Mgal/h; Mgal/dayBarrel (normal fluids: 31.5 gal/bbl) → bbl/s; bbl/min; bbl/h; bbl/dayBarrel (beer: 31.0 gal/bbl) → bbl/s; bbl/min; bbl/h; bbl/dayBarrel (petrochemicals: 42.0 gal/bbl) → bbl/s; bbl/min; bbl/h; bbl/dayBarrel (filling tanks: 55.0 gal/bbl) → bbl/s; bbl/min; bbl/h; bbl/day
Imperial:Gallon → gal/s; gal/min; gal/h; gal/dayMega gallon → Mgal/s; Mgal/min; Mgal/h; Mgal/dayBarrel (beer: 36.0 gal/bbl) → bbl/s; bbl/min; bbl/h; bbl/dayBarrel (petrochemicals: 42.0 gal/bbl) → bbl/s; bbl/min; bbl/h; bbl/day
Factory setting:Country dependent (m3/h or US Mgal/day)
UNIT VOLUME Use this function to select the unit for the volume.
The unit you select here is also valid for:• Pulse value (e.g. m3/p)
Options:Metric → cm3; dm3; m3; ml; l; hl; Ml
US → cc; af; ft3; oz f; gal; Mgal; bbl (normal fluids); bbl (beer); bbl (petrochemicals); bbl (filling tanks)
Imperial → gal; Mgal; bbl (beer); bbl (petrochemicals)
Factory setting:Country dependent (m3 or US Mgal)
! Note!The unit for the totalizer is independent of your choice here, it is selected separately in the TOTALIZER 1/2 group (see Page 20).
Function description SYSTEM UNITS
3 Group SYSTEM UNITS Device Functions PROline Promass 80
10 Endress+Hauser
UNIT CORRECTED VOL-UME FLOW
Use this function to select the unit for displaying the corrected volume flow (corrected volume/time).
The unit you select here is also valid for:• Current outputs• Frequency outputs• Relay switch points (limit value for corrected volume flow, flow direction)• Low flow cut off
Options:Metric:Nl/sNl/minNl/hNl/dayNm3/sNm3/minNm3/hNm3/day
US:Sm3/s; Sm3/min; Sm3/h; Sm3/dayScf/s; Scf/min; Scf/h; Scf/day
Factory setting:Nm3/h
UNIT CORRECTED VOL-UME
Use this function to select the unit for displaying the corrected volume.
The unit you select here is also valid for:• Pulse value (e.g. Nm3/p)
Options:Metric:Nm3
Nl
US:Sm3
Scf
Factory setting:Nm3
! Note!The unit of the totalizers is independent of your choice here. The unit for each totalizer is selected separately for the totalizer in question.
Function description SYSTEM UNITS
Device Functions PROline Promass 80 3 Group SYSTEM UNITS
Endress+Hauser 11
UNIT DENSITY Use this function to select the unit for displaying the fluid density.
The unit you select here is also valid for:• Current output• Frequency output• Switching points• Density adjustment value• Density responce value for EPD
Options:Metric → g/cm3; g/cc; kg/dm3; kg/l; kg/m3; SD 4 °C, SD 15 °C, SD 20 °C; SG 4 °C, SG 15 °C, SG 20 °C
US → lb/ft3; lb/gal; lb/bbl (normal fluids); lb/bbl (beer); lb/bbl (petrochemi-cals); lb/bbl (filling tanks)
Imperial → lb/gal; lb/bbl (beer); lb/bbl (petrochemicals)
Factory setting:kg/l
SD = Specific Density, SG = Specific GravityThe specific density is the ratio of fluid density to water (at water temperature = 4, 15, 20 °C)
UNIT REFERENCE DEN-SITY
Use this function to select the unit for displaying the reference density.
The unit you select here is also valid for:• Current outputs• Frequency outputs• Relay switch points (limit value for density)• Fixed reference density (for calculation of corrected volume flow)
Options:Metric:kg/Nm3
kg/Nl
US:g/Scckg/Sm3
lb/Scf
Factory setting:kg/Nl
UNIT TEMPERATURE Use this function to select the unit for displaying the temperature.
The unit you select here is also valid for:• Current output• Frequency output• Switching points
Options:°C (CELSIUS)
K (KELVIN)°F (FAHRENHEIT)°R (RANKINE)
Factory setting:°C (CELSIUS)
Function description SYSTEM UNITS
3 Group SYSTEM UNITS Device Functions PROline Promass 80
12 Endress+Hauser
UNIT LENGTH Use this function to select the unit for the unit of length for nominal diameter.
The unit you select here is also valid for:• nominal diameter of the sensor (see the NOMINAL DIAMETER function on
Page 52).
Options:MILLIMETERINCH
Factory setting:Country dependent (MILLIMETER or INCH)
UNIT PRESSURE Use this function to select the unit for pressure.
The unit you select here is also valid for:• Specified pressure (see function DRUCK auf Page 48)
Option:BAR GPSI GBAR APSI A
Factory setting:BAR G
Function description SYSTEM UNITS
Device Functions PROline Promass 80 4 Group QUICK SETUP
Endress+Hauser 13
4 Group QUICK SETUP
! Note!• The display returns to the QUICK SETUP COMMISSION cell if you press the ESC key
combination during programming of a parameter.
• ➀ Only units not yet configured in the current Quick Setup are offered for selectionin each cycle. The unit for mass and volume is derived from the corresponding flow unit.
• ➁ The “YES” option remains visible until all the units have been parameterised.“NO” is the only option displayed when no further units are available.
• ➂ Only the outputs not yet configured in the current Quick Setup are offered for selection in each cycle.
• ➃ The “YES” option remains visible until all the outputs have been parameterised.“NO” is the only option displayed when no further outputs are available.
• ➄ The “automatic parameterization of the display” option contains the following basicsettings/factory settings:YES: Main line = Mass flow; Additional line = Totalizer 1.NO: The existing (selected) settings remain.
➀ – ➄: see next page
Function description QUICK SETUP
QUICK SETUP COMMISSION
Use this function to start the Setup menu for commissioning.
Options:NOYES
Factory setting:NO
4 Group QUICK SETUP Device Functions PROline Promass 80
14 Endress+Hauser
++ +E EEsc
E- +
➄
Yes
Yes
Yes
No
No
No
Mass flow
Current output 1
Volume flow Density
Frequency/Pulse output
Selection System Units
Selection output type
Configuration another unit ?
Configuration another output ?
Automatically configuration display ?
Temperature Quit
Quit
UnitMass flow
AssignCurrent
Current span
Value0/4 mA
Value20 mA
Time constant
Time constantFailsafe mode
Failsafe mode
Failsafe mode
AssignFrequency
End valuefrequency
ValueF Low
ValueF High
Output signal
AssignPulse
Pulse value
Pulse width
Output signal
UnitflowVolume
UnitDensity
Operation mode
UnitTemperature
MeasuringMode
UnitTotalizer
UnitTotalizer
Frequency Pulse
Automaticallyparameterization
of the display
Language
Pre-setting
Quick Setup
HOME-POSITION
Quick SetupCommission
AssignCurrent
Current span
Value0/4 mA
Value20 mA
Time constant
Failsafe mode
Current output 2
➀
➁
➂
➃
Corr. Vol. flow
UnitCorr. Vol. flow
UnitRef. Density
FixRef. Density
F06-80xxxxx-19-xx-xx-en-000
Device Functions PROline Promass 80 5 Group OPERATION
Endress+Hauser 15
5 Group OPERATION
Function description OPERATION
LANGUAGE Use this function to select the language for all texts, parameters and mes-sages shown on the local display.
! Note!The displayed options depend on the available language group shown in the LANGUAGE GROUP (8226) function.
Options: Language group WEST EU / USA:ENGLISHDEUTSCHFRANCAISESPANOLITALIANONEDERLANDSPORTUGUESE
Language group EAST EU / SCAND:ENGLISHNORSKSVENSKASUOMIPOLISHRUSSIANCZECH
Language group ASIA:ENGLISHBAHASA INDONESIAJAPANESE (syllabary)
Factory setting:Country-dependent (see Page 58 ff.)
! Note!• If you press the OS keys at startup, the language defaults to “ENGLISH”.
ACCESS CODE All data of the measuring system are protected against inadvertent change. Programming is disabled and the settings cannot be changed until a code is entered in this function.If you press the OS key in any function the measuring system automatically goes to this function and the prompt to enter the code appears on the display (programming disabled).
You can enable programming by entering the personal code (Factory setting = 80, see the DEFINE PRIVATE CODE function)
User input:max. 4-digit number: 0...9999
! Note!• The programming levels are disabled if you do not press a key within 60
seconds following return to the HOME position.• You can also disable programming in this function by entering any number
(other than the defined private code).• The Endress+Hauser service organization can be of assistance if you lose
your personal code.
5 Group OPERATION Device Functions PROline Promass 80
16 Endress+Hauser
DEFINE PRIVATE CODE Use this function to define a personal code number for enabling programming.
User input:max. 4-digit number: 0...9999
Factory setting:80
! Note!• If you define the personal code number = 0, the programming is always
enabled.• Programming has to be enabled before this code can be changed.
When programming is disabled the function can’t be changed, this precaution prevents others from changing your personal code without your knowledge and consent.
STATUS ACCESS Use this function to check the access status for the function matrix.
Display shows:ACCESS CUSTOMER (Parameterization enabled)LOCKED (Parameterization disabled)
ACCESS CODE COUNTER
Displays how often the customer code, service code or the digit “0” (code-free) has been entered to gain access to the function matrix.
Display:max. 7-digit number: 0...9999999
Factory setting:0
Function description OPERATION
Device Functions PROline Promass 80 6 Group USER INTERFACE
Endress+Hauser 17
6 Group USER INTERFACE
Function description USER INTERFACE
ASSIGN LINE 1 Use this function to define the display value assigned to the main line (the upper line of the local display) for display during normal measuring operation.
Options:OFFMASS FLOWMASS FLOW IN %VOLUME FLOWVOLUME FLOW IN %DENSITYTEMPERATURETOTALIZER 1TOTALIZER 2CORRECTED VOLUME FLOWCORRECTED VOLUME FLOW IN %REFERENCE DENSITY
Factory setting:MASS FLOW
ASSIGN LINE 2 Use this function to define the display value assigned to the additional line (the bottom line of the local display) for display during normal measuring operation.
Options:OFFMASS FLOWMASS FLOW IN %VOLUME FLOWVOLUME FLOW IN %DENSITYTEMPERATURETOTALIZER 1TAG NAMEOPERATION/SYSTEM CONDITIONDISPLAY FLOW DIRECTIONMASS FLOW BARGRAPH IN %VOLUME FLOW BARGRAPH IN %TOTALIZER 2CORRECTED VOLUME FLOWCORRECTED VOLUME FLOW IN %CORRECTED VOLUME FLOW BARGRAPH IN %REFERENCE DENSITY
Factory setting:TOTALIZER
6 Group USER INTERFACE Device Functions PROline Promass 80
18 Endress+Hauser
100% VALUE(Line 1) ! Note!
This function is not available unless one of the following was selected in the ASSIGN LINE 1 function:• MASS FLOW IN %• VOLUME FLOW IN %• CORRECTED VOLUME FLOW IN %
Use this function to define the flow value to be shown on the display as the 100% value of the variable assigned to line 1.
User input:5-digit floating-point number
Factory setting:• 10 kg/s (if MASS FLOW IN % or MASS FLOW BARGRAPH IN % is selected)
• 10 l/s (if VOLUME FLOW IN % or VOLUME FLOW BARGRAPH IN % is selected)
100% VALUE(Line 2) ! Note!
This function is not available unless one of the following was selected in the ASSIGN LINE 2 function:• MASS FLOW IN %• VOLUME FLOW IN %• MASS FLOW BARGRAPH IN %• VOLUME FLOW BARGRAPH IN %• CORRECTED VOLUME FLOW BARGRAPH IN %
Use this function to define the flow value to be shown on the display as the 100% value of the variable assigned to line 2.
User input:5-digit floating-point number
Factory setting:• 10 kg/s (if MASS FLOW IN % or MASS FLOW BARGRAPH IN % is selected)
• 10 l/s (if VOLUME FLOW IN % or VOLUME FLOW BARGRAPH IN % is selected)
FORMAT Use this function to define the maximum number of places after the decimal point displayed for the reading in the main line.
Options:XXXXX. - XXXX.X - XXX.XX - XX.XXX -X.XXXX
Factory setting: X.XXXX
! Note!• Note that this setting only affects the reading as it appears on the display, it
has no influence on the accuracy of the system's calculations.• The places after the decimal point as computed by the measuring device
cannot always be displayed, depending on this setting and the engineering unit. In these instances an arrow appears on the display between the meas-ured value and the engineering unit (e.g. 1.2 → kg/h), indicating that the measuring system is computing with more decimal places than can be shown on the display.
Function description USER INTERFACE
Device Functions PROline Promass 80 6 Group USER INTERFACE
Endress+Hauser 19
DISPLAY DAMPING Use this function to enter a time constant defining how the display reacts to severely fluctuating flow variables, either very quickly (enter a low time con-stant) or with damping (enter a high time constant).
User input:0...100 s
Factory setting:1 s
! Note!Setting the time constant to zero seconds switches off damping.
CONTRAST LCD Use this function to optimize display contrast to suit local operating conditions.
User input:10...100%
Factory setting:50%
BACKLIGHT Use this function to optimize the backlight to suit local operating conditions.
User input:0...100%
! Note!Entering the value “0” means that the backlight is “switched off”. The display then no longer emits any light, i.e. the display texts can no longer be read in the dark.
Factory setting:50%
TEST DISPLAY Use this function to test the operability of the local display and its pixels.
Options:OFFON
Factory setting:OFF
Test sequence:1. Start the test by selecting ON.
2. All pixels of the main line and additional line are darkened for minimum 0.75 second.
3. Main line and additional line show an “8” in each field for minimum 0.75 second.
4. Main line and additional line show a “0” in each field for minimum 0.75 second.
5. Main line and additional line show nothing (blank display) for minimum 0.75 second.
6. When the test completes the local display returns to its initial state and the setting changes to OFF.
Function description USER INTERFACE
7 Group TOTALIZER 1/2 Device Functions PROline Promass 80
20 Endress+Hauser
7 Group TOTALIZER 1/2
Function description TOTALIZER 1/2
ASSIGN TOTALIZER Use this function to assign a measured variable to the totalizer.
Options:MASS FLOWVOLUME FLOWCORRECTED VOLUME FLOW
Factory setting:MASS FLOW
! Note!The totalizer is reset to “0” as soon as the selection is changed.
SUM Use this function to view the total for the totalizer measured variable aggregated since measuring commenced. The value can be positive or negative.
Display shows:max. 7-digit floating-point number, including sign and unit (e.g. 15467.04 kg)
! Note!The totalizer response to faults is defined in the FAILSAFE MODE function (see Page 22).
OVERFLOW Use this function to view the overflow for the totalizer aggregated since measuring commenced.
Total flow quantity is represented by a floating decimal point number consisting of max. 7 digits. You can use this function to view higher
numerical values (>9,999,999) as overflows. The effective quantity is thus the total of OVERFLOW plus the value returned by the SUM function.
Example:Reading for 2 overflows: 2 E7 kg (= 20,000,000 kg)The value returned by the SUM function = 196,845.7 kgEffective total quantity = 20,196,845.7 kg
Display shows: Integer with exponent, including sign and unit, e.g. 2 E7 kg
Device Functions PROline Promass 80 7 Group TOTALIZER 1/2
Endress+Hauser 21
UNIT TOTALIZER Use this function to define the unit for the totalizer measured variable, as selected beforehand.
Options (for the MASS FLOW assignment):Metric → g; kg; tUS → oz; lb; ton
Factory setting:Depends on nominal diameter and country,[value] / [g ...kg or US oz...US ton]corresponding to the totalizer unit factory setting (see Page 58 ff.)
Options (for the VOLUME FLOW assignment):Metric → cm3; dm3; m3; ml; l; hl; Ml
US → cc; af; ft3; oz f; gal; Mgal; bbl (normal fluids); bbl (beer); bbl (petro-chemicals); bbl (filling tanks)
Imperial → gal; Mgal; bbl (beer); bbl (petrochemicals)
Options (for the CORRECTED VOLUME FLOW assignment):Metric → Nl; Nm3
US → Sm3; Scf
Factory setting:Depends on nominal diameter and country,[value] / [dm3 ...m3 or US gal...US Mgal]corresponding to the totalizer unit factory setting (see Page 58 ff.)
TOTALIZER MODE Use this function to define how the flow components are to be totalized.
Options:BALANCEPositive and negative flow components. The positive and negative flow com-ponents are balanced. In other words, net flow in the flow direction is regis-tered.
FORWARD Only positive flow components are totalized.
REVERSE Only negative flow components are totalized.
Factory setting:Totalizer 1 = BALANCETotalizer 2 = FORWARD
RESET TOTALIZER Use this function to reset the sum and the overflow of the totalizer to zero (= RESET).
Options:NOYES
Factory setting:NO
! Note!If the device has a status input and is appropriately configured, a reset for the totalizer can also be triggered by a pulse.
Function description TOTALIZER 1/2
8 Group HANDLING TOTALIZER Device Functions PROline Promass 80
22 Endress+Hauser
8 Group HANDLING TOTALIZER
Function description HANDLING TOTALIZER
RESET ALL TOTALIZ-ERS
Use this function to reset the totals (including all overflows) of the totalizers (1...2) to “zero” (= RESET).
Options:NOYES
Factory setting:NO
! Note!If the device has a status input and if it is appropriately configured, a reset for the totalizer (1...2) can also be triggered by a pulse (see the ASSIGN STATUS INPUT function ).
FAILSAFE MODE Use this function to define the response of all totalizers (1...2) to a fault.
Options:STOPThe totalizer is paused until the fault is rectified. The totalizer stops at the last value prior to the occurrence of the error.
ACTUAL VALUEThe totalizer continues to count is based on the current flow measured value. The fault is ignored.
HOLD VALUEThe totalizer continues to count the flow is based on the last valid flow value (before the fault occurred).
Factory setting:STOP
Device Functions PROline Promass 80 9 Group CURRENT OUTPUT 1/2
Endress+Hauser 23
9 Group CURRENT OUTPUT 1/2
Function description CURRENT OUTPUT 1/2
ASSIGN CURRENT Use this function to assign a measured variable to the current output.
Options:OFF MASS FLOWVOLUME FLOWCORRECTED VOLUME FLOWDENSITYREFERENCE DENSITYTEMPERATURE
Factory setting:MASS FLOW
! Note!If you select OFF, the only function shown in this group is these (ASSIGN CURRENT) function.
CURRENT SPAN Use this function to define the current span. The selection specifies the opera-tional range and the lower and upper signal on alarm. For the current output 1 the option HART can be defined additionally.
Options:0–20 mA4–20 mA4–20 mA HART (only current output1)4–20 mA NAMUR4–20 mA HART NAMUR (only current output1)4–20 mA US4–20 mA HART US (only current output1)0–20 mA (25 mA)4–20 mA (25 mA)4–20 mA (25 mA) HART (only current output1)
Factory setting:4–20 mA HART NAMUR (für current output 1)4–20 mA NAMUR (für current output 2)
! Note!• The option HART is only supported by the current output designated as cur-
rent output 1 in the device software, (terminals 26 and 27).• When switching the hardware from an active (factory setting) to a passive
output signal select a current span of 4–20 mA (please refer to the Operat-ing Instructions PROline promass 80, BA 057D/06/en)
9 Group CURRENT OUTPUT 1/2 Device Functions PROline Promass 80
24 Endress+Hauser
CURRENT SPAN(contd)
Current span, operational range and signal on alarm level
A = Current span1 = Operational range (measuring information)2 = Lower signal on alarm level3 = Upper signal on alarm level
! Note!• If the measured value exceeds the measuring range (as defined in the func-
tions VALUE 0_4 mA and VALUE 20 mA a notice message is generated (#351...352, current span).
• In case of a fault the behaviour of the current output is according to the selected option in the function FAILSAFE MODE. Change the error category in the function ASSIGN SYSTEM ERROR to generate a fault message instead of a notice message.
VALUE 0_4 mA! Note!This function is not available unless the DENSITY, REFERENCE DENSITY or TEMPERATURE option was selected in the ASSIGN CURRENT function.
Use this function to assign a value to the 0/4 mA current, (see “Setting the span by means of the 0_4 mA and 20 mA value” on Page 25).
Option:5-digit floating-point number (with sign for the TEMPERATURE measured variable)
Factory setting:0.5 [kg/l] or –50 [°C]
VALUE 20 mA Use this function to assign a value to the 20 mA current, (see “Setting the span by means of the 0_4 mA and 20 mA value” on Page 25).
Option:5-digit floating-point number (with sign for the MASS FLOW, VOLUME FLOW, CORRECTED VOLUME FLOW and TEMPERATURE measured variables)
Factory setting:Depends on nominal diameter [kg/h] or 2 [kg/l] or 200 [°C]
Function description CURRENT OUTPUT 1/2
12 3
I[mA]
A 1 2 3
0-20 mA
4-20 mA
4-20 mA NAMUR
4-20 mA US
0-20 mA (25 mA)
4-20 mA (25 mA)
0 - 20.5 mA 0 22
4 - 20.5 mA 2 22
3.8 - 20.5 mA 3.5 22.6
3.9 - 20.8 mA 3.75 22.6
0 - 24 mA 0 25
4 - 24 mA 2 25
4-20 mA HART 4 - 20.5 mA 2 22
4-20 mA HART NAMUR 3.8 - 20.5 mA 3.5 22.6
4-20 mA HART US 3.9 - 20.8 mA 3.75 22.6
4-20 mA (25 mA) HART 4 - 24 mA 2 25 F06-
x3xx
xxxx
-05-
xx-x
x-xx
-017
Device Functions PROline Promass 80 9 Group CURRENT OUTPUT 1/2
Endress+Hauser 25
Setting the span by means of the 0_4 mA and 20 mA value
The span for the measured variable selected in the ASSIGN CURRENT function is specified via the VALUE 0_4 mA and VALUE 20 mA functions.
The span is defined differently, depending on the measured variable selected:
MASS FLOW, VOLUME FLOW and CORRECTED VOLUME FLOW• The VALUE 0_4 mA function is not available; the value for the zero flow (0
kg/h or 0m3/h) is assigned to the 0/4 mA current.• The flow value for the 20 mA current is defined in the VALUE 20 mA function,
(input range –99999 to +99999). The appropriate unit is taken from the UNIT MASS FLOW, UNIT VOLUME FLOW or UNIT CORR. VOL. FLOW function.
Example (for standard measuring mode):
➀ = Initial value (0...20 mA)
➁ = Lower signal on alarm level:: depends on the setting in the function CURRENT SPAN
➂ = Initial value (4...20 mA): depends on the setting in the function CURRENT SPAN
➃ = Full scale value (0/4...20 mA): depends on the setting in the function CURRENT SPAN
➄ = Maximum current value: depends on the setting in the function CURRENT SPAN
➅ = Failsafe mode (upper signal on alarm level): depends on the setting in the functions CURRENT SPAN and FAILSAFE MODE,
A = Measuring range (the minimum measuring range has to exceed the value that corre-lates with a flow velocity of 0.3 m/s)
(Continued on next page)
Function description CURRENT OUTPUT 1/2
0
3
45
6
I [mA]
2
A
1
Q
F06
-80x
xxxx
-05-
xx-x
x-xx
-00
8
9 Group CURRENT OUTPUT 1/2 Device Functions PROline Promass 80
26 Endress+Hauser
Setting the span by means of the 0_4 mA and 20 mA value(contd)
DENSITY and REFERENCE DENSITY• The density value for the 0/4 mA current is defined in the
VALUE 0_4 mA function, (input range 0.0000 to +99999). The appropriate unit is taken from the UNIT DENSITY function.
• The density value for the 20 mA current is defined in the VALUE 20 mA function, (input range 0.0000 to +99999). The appropriate unit is taken from the UNIT DENSITY and UNIT REF. DENSITY function.
Example (for standard measuring mode):
➀ = Initial value (0...20 mA)
➁ = Lower signal on alarm level:: depends on the setting in the function CURRENT SPAN
➂ = Initial value (4...20 mA): depends on the setting in the function CURRENT SPAN
➃ = Full scale value (0/4...20 mA): depends on the setting in the function CURRENT SPAN
➄ = Maximum current value: depends on the setting in the function CURRENT SPAN
➅ = Failsafe mode (upper signal on alarm level): depends on the setting in the functions CURRENT SPAN and FAILSAFE MODE
A = Measuring range (the minimum measuring range has to exceed the value that corre-lates with a flow velocity of 0.3 m/s)
TEMPERATURE• The temperature value for the 0/4 mA current is defined in the
VALUE 0_4 mA function, (input range –99999 to +99999). The appropriate unit is taken from the UNIT TEMPERATURE function.
• The temperature value for the 20 mA current is defined in the VALUE 20 mA function, (input range –99999 to +99999). The appropriate unit is taken from the UNIT TEMPERATURE function.
! Note!Values with different signs cannot be entered for the 0_4 mA and 20 mA val-ues if SYMMETRY is the option selected in the MEASURING MODE function, (see Page 49), The message “INPUT RANGE EXCEEDED” appears on the dis-play.
Example (for standard measuring mode)
➀ = Initial value (0...20 mA)
➁ = Lower signal on alarm level:: depends on the setting in the function CURRENT SPAN
➂ = Initial value (4...20 mA): depends on the setting in the function CURRENT SPAN
➃ = Full scale value (0/4...20 mA): depends on the setting in the function CURRENT SPAN
➄ = Maximum current value: depends on the setting in the function CURRENT SPAN
➅ = Failsafe mode (upper signal on alarm level): depends on the setting in the functions CURRENT SPAN and FAILSAFE MODE
A = Measuring range (the minimum measuring range has to exceed the value that corre-lates with a flow velocity of 0.3 m/s)
Function description CURRENT OUTPUT 1/2
0
3
45
6
I [mA]
2
A
1
Q
F06
-80x
xxxx
-05-
xx-x
x-xx
-009
0
3
45
6
I [mA]
2
A
1
Q
F06
-80x
xxxx
-05-
xx-x
x-xx
-010
Device Functions PROline Promass 80 9 Group CURRENT OUTPUT 1/2
Endress+Hauser 27
TIME CONSTANT Use this function to enter a time constant defining how the current output signal reacts to severely fluctuating measured variables, either very quickly (enter a low time constant) or with damping (enter a high time constant).
User input:Fixed-point number 0.01...100.00 s
Factory setting:1.00 s
FAILSAFE MODE For safety reasons it is advisable to ensure that the current output assumes a predefined state in the event of a fault. The setting you select here affects only the current output. It has no effect on other outputs and the display (e.g. total-izers).
Options: MIN. CURRENTThe current output adopts the value of the lower signal on alarm level (as defined in the function CURRENT SPAN.
MAX. CURRENTThe current output adopts the value of the upper signal on alarm level (as defined in the function CURRENT SPAN.
HOLD VALUE (not recommended)Measuring value output is based on the last measuring value saved before the error occurred .
ACTUAL VALUE Measured value output is based on the current flow measurement.The fault is ignored .
Factory setting:MIN. CURRENT
ACTUAL CURRENT Use this function to view the computed value of the output current.
Display shows:0.00...25.00 mA
SIMULATION CURRENT Use this function to activate simulation of the current output.
Options:OFFON
Factory setting:OFF
! Note!• The “SIMULATION CURRENT OUTPUT” message indicates that simulation
is active. • The measuring device continues to measure while simulation is in progress,
i.e. the actual measured values are output correctly via the other outputs.
" Caution!The setting is not saved if the power supply fails.
Function description CURRENT OUTPUT 1/2
9 Group CURRENT OUTPUT 1/2 Device Functions PROline Promass 80
28 Endress+Hauser
VALUE SIMULATION CURRENT ! Note!
This function is not available unless the SIMULATION CURRENT function is active (= ON).Use this function to define a selectable value (e.g. 12 mA) to be output at the current output. This value is used to test downstream devices and the flow-meter itself.
User input:floating-point number: 0.00...25.00 mA
Factory setting:0.00 mA
" Caution!The setting is not saved if the power supply fails.
Function description CURRENT OUTPUT 1/2
Device Functions PROline Promass 80 10 Group PULSE/FREQUENCY OUTPUT
Endress+Hauser 29
10 Group PULSE/FREQUENCY OUTPUT
Function description PULSE/FREQUENCY OUTPUT
OPERATION MODE Use this function to configure the output as a pulse or frequency output.The functions available in this function group vary, depending on which option you select here.
Options:PULSE FREQUENCY
Factory setting:PULSE
ASSIGN FREQUENCY! Note!This function is not available unless the FREQUENCY setting was selected in the OPERATION MODE function.
Use this function to assign a measured variable to the frequency output.
Options:OFFMASS FLOWVOLUME FLOWCORRECTED VOLUME FLOWDENSITYREFERENCE DENSITYTEMPERATURE
Factory setting:MASS FLOW
! Note!If you select OFF, the only functions shown in this function group are ASSIGN FREQUENCY and OPERATION MODE.
END VALUE FREQUENCY ! Note!
This function is not available unless the FREQUENCY setting was selected in the OPERATION MODE function.
Use this function to define a full scale frequency for the frequency output.You define the associated measured value of the measuring range in the VALUE F HIGH function described on Page 30.
User input:4-digit fixed-point number: 2...1000 Hz
Factory setting:1000 Hz
Example:• VALUE F HIGH = 1000 kg/h, full scale frequency = 1000 Hz: i.e. a frequency
of 1000 Hz is output at a flow of 1000 kg/h.• VALUE F HIGH = 3600 kg/h, full scale frequency = 1000 Hz: i.e. a frequency
of 1000 Hz is output at a flow of 3600 kg/h.
! Note!In the FREQUENCY operating mode the output signal is symmetrical (on/off ratio = 1:1). At low frequencies the pulse duration is limited to a maximum of 2 seconds, i.e. the on/off ratio is no longer symmetrical.
10 Group PULSE/FREQUENCY OUTPUT Device Functions PROline Promass 80
30 Endress+Hauser
VALUE F LOW! Note!This function is not available unless the DENSITY, REFERENCE DENSITY or TEMPERATURE option was selected in the ASSIGN FREQUENCY function.
Use this function to assign a value to the start value frequency (0 Hz), (see “Setting the span by means of the f-min. and f-max. value” on Page 30).
Option:5-digit floating-point number (with sign for the TEMPERATURE measured variable)
Factory setting:0.5 [kg/l] or –50 [°C]
VALUE F HIGH Use this function to assign a value to the END VALUE FREQUENCY, (see “Setting the span by means of the f-min. and f-max. value” on Page 30).
Option:5-digit floating-point number (with sign for the MASS FLOW, VOLUME FLOW, CORRECTED VOLUME FLOW and TEMPERATURE measured variables)
Factory setting:Depends on nominal diameter [kg/h] or 2 [kg/l] or 200 [°C]
Setting the span by means of the f-min. and f-max. value
The span for the measured variable selected in the ASSIGN FREQUENCY function is specified via the VALUE F LOW and VALUE F HIGH functions.
The span is defined differently, depending on the measured variable selected:
MASS FLOW, VOLUME FLOW and CORRECTED VOLUME FLOW• The VALUE F LOW function is not available; the value for the zero flow
(0 kg/h or 0m3/h) is assigned to the start value frequency.• The flow value for the end value frequency is defined in the VALUE F HIGH
function, (input range –99999 to +99999). The appropriate unit is taken from the UNIT MASS FLOW, UNIT VOLUME FLOW or UNIT CORRECTED VOL-UME FLOW function.
Example (for standard measuring mode):
➀ = Flow value at which a frequency of 0 Hz should be output (preset, cannot be edited).
➁ = Flow value at which the, in the function END VALUE FREQUENCY defined, frequency should be output (entry in VALUE F HIGH function).
(Continued on next page)
Function description PULSE/FREQUENCY OUTPUT
�
�
125
100
Measuring range Measured variable (amount)
Value f minValue f max
Frequency [%]
0 F06
-80x
xxxx
x-05
-xx-
xx-e
n-01
1
Device Functions PROline Promass 80 10 Group PULSE/FREQUENCY OUTPUT
Endress+Hauser 31
Setting the span by means of the f-min. and f-max. value(contd)
DENSITY and REFERENCE DENSITY• The density value for the start value frequency is defined in the
VALUE F LOW function, (input range 0.0000 to +99999). The appropriate unit is taken from the UNIT DENSITY and UNIT REF. DENSITY function.
• The density value for the end value frequency is defined in the VALUE F HIGH function, (input range 0.0000 to +99999). The appropriate unit is taken from the UNIT DENSITY and UNIT REF. DENSITY function.
Example (for standard measuring mode):
➀ = Density value and reference density at which a frequency of 0 Hz should be output (entry in VALUE F LOW function).
➁ = Density value and reference density at which the, in the function END VALUE FREQUENCY defined, frequency should be output (entry in VALUE F HIGH function).
TEMPERATURE• The temperature value for the 0/4 mA current is defined in the
VALUE F LOW function, (input range –99999 to +99999). The appropriate unit is taken from the UNIT TEMPERATURE function.
• The temperature value for the 20 mA current is defined in the VALUE F HIGH function, (input range –99999 to +99999). The appropriate unit is taken from the UNIT TEMPERATURE function.
! Note!Values with different signs cannot be entered for the VALUE F LOW and VALUE F HIGH if SYMMETRY is the option selected in the MEASURING MODE function (see Page 49). The message “INPUT RANGE EXCEEDED” appears on the display.
Example (for standard measuring mode):
➀ = Temperature value at which a frequency of 0 Hz should be output (entry in VALUE F LOW function).
➁ = Temperature value at which the, in the function END VALUE FREQUENCY defined, frequency should be output (entry in VALUE F HIGH function).
Function description PULSE/FREQUENCY OUTPUT
125
100
Measuring range Measured variable (amount)
Value f minValue f max
Frequency [%]
0
➀
➀
➁➁
F06
-80x
xxxx
x-05
-xx-
xx-e
n-01
2
➁
➀
➀
➁
125
100
Measuring range Measured variable (amount)
Value f minValue f max
Frequency [%]
0 F06
-80x
xxxx
x-05
-xx-
xx-e
n-01
3
10 Group PULSE/FREQUENCY OUTPUT Device Functions PROline Promass 80
32 Endress+Hauser
OUTPUT SIGNAL! Note!This function is not available unless the FREQUENCY setting was selected in the OPERATION MODE function.
Use this function to select the polarity of the frequency signal.
Options:PASSIVE - POSITIVEPASSIVE - NEGATIVE
Factory setting:PASSIVE - POSITIVE
PASSIVE:
! Note!For continuous currents up to 25 mA (Imax = 250 mA / 20 ms)
TIME CONSTANT! Note!This function is not available unless the FREQUENCY setting was selected in the OPERATION MODE function.
Use this function to enter a time constant defining how the frequency output signal reacts to severely fluctuating measured variables, either very quickly (enter a low time constant) or with damping (enter a high time constant).
User input:floating-point number: 0.00...100.00 s
Factory setting:0.00 s
Function description PULSE/FREQUENCY OUTPUT
1 5 8 37+
-
=
OpenCollector
U = 30 V DCExternal power supply
max
F-x
xxxx
xx-0
4-xx
-xx-
en-
000
PASSIVE-NEGATIVE
conducting conducting
nonconducting
nonconducting
t t
transistor transistor
PASSIVE-POSITIVE
F-x
xxxx
xx-0
5-xx
-xx-
en-0
02
Device Functions PROline Promass 80 10 Group PULSE/FREQUENCY OUTPUT
Endress+Hauser 33
FAILSAFE MODE! Note!This function is not available unless the FREQUENCY setting was selected in the OPERATION MODE function.
For reasons of safety it is advisable to ensure that the frequency output assumes a predefined state in the event of a fault. Use this function to define this state. The setting you select here affects only the frequency output. It has no effect on other outputs and the display (e.g. totalizer).
Options:FALLBACK VALUEOutput is 0 Hz.
FAILSAFE LEVELOutput is the frequency specified in the FAILSAFE VALUE function.
HOLD VALUEMeasured value output is based on the last measured value saved before the fault occurred.
ACTUAL VALUEMeasured value output is based on the current flow measurement. The fault is ignored.
Factory setting:FALLBACK VALUE
FAILSAFE VALUE! Note!This function is not available unless FREQUENCY was selected in the OPERATION MODE function and FAILSAFE LEVEL was selected in the FAILSAFE MODE function.
Use this function to define frequency that the measuring device outputs in the event of an fault.
User input:max. 4-digit number: 0...1250 Hz
Factory setting:1250 Hz
ACTUAL FREQUENCY! Note!This function is not available unless the FREQUENCY setting was selected in the OPERATION MODE function.
Use this function to view the computed value of the output frequency.
Display shows:0...1250 Hz
Function description PULSE/FREQUENCY OUTPUT
10 Group PULSE/FREQUENCY OUTPUT Device Functions PROline Promass 80
34 Endress+Hauser
SIMULATION FREQUENCY ! Note!
This function is not available unless the FREQUENCY setting was selected in the OPERATION MODE function.
Use this function to activate simulation of the frequency output.
Options:OFFON
Factory setting:OFF
! Note!• The “SIMULATION FREQUENCY OUTPUT” message indicates that
simulation is active.• The measuring device continues to measure while simulation is in progress,
i.e. the currently measured values are output correctly via the other outputs.
" Caution!The setting is not saved if the power supply fails.
VALUE SIMULATION FREQUENCY ! Note!
This function is not available unless FREQUENCY was selected in the OPERATION MODE function and the VALUE SIMULATION FREQUENCY function is active (= ON).
Use this function to define a selectable frequency value (e.g. 500 Hz) to be output at the frequency output. This value is used to test downstream devices and the flowmeter itself.
User input:0...1250 Hz
Factory setting:0 Hz
" Caution!The setting is not saved if the power supply fails.
ASSIGN PULSE! Note!This function is not available unless the PULSE setting was selected in the OPERATION MODE function.
Use this function to assign a measured variable to the pulse output.
Options:OFFMASS FLOWVOLUME FLOWCORRECTED VOLUME FLOW
Factory setting:MASS FLOW
! Note!If you select OFF, the only functions shown in this function group are ASSIGN PULSE and OPERATION MODE.
Function description PULSE/FREQUENCY OUTPUT
Device Functions PROline Promass 80 10 Group PULSE/FREQUENCY OUTPUT
Endress+Hauser 35
PULSE VALUE! Note!This function is not available unless the PULSE setting was selected in the OPERATION MODE function.
Use this function to define the flow at which a pulse is triggered. These pulses can be totaled by an external totalizer, and the total flow quantity since measuring started can be registered in this way.
User input:5-digit floating-point number
Factory setting:Depends on nominal diameter and country,[value] [dm3 ...m3 or US gal...US Mgal] / pulsescorresponding to the factory setting for the pulses value (see Page 58 ff.)
! Note!The appropriate unit is taken from the corresponding UNIT function in the group SYSTEM UNITS (see Page 8).
PULSE WIDTH! Note!This function is not available unless the PULSE setting was selected in the OPERATION MODE function.
Use this function to enter the maximum pulse width of the output pulses.
User input:0.5...2000 ms
Factory setting:100 ms
Pulse output is always with the pulse width (B) entered in this function.The intervals (P) between the individual pulses are automatically configured. However, they must at least correspond to the pulse width (B = P).
B = Pulse width entered (the illustration applies to positive pulses)P= Intervals between the individual pulses
! Note!When entering the pulse width, select a value that can still be processed by an external totalizer (e.g. mechanical totalizer, PLC, etc.).
" Caution!If the pulse number or frequency resulting from the pulse value entered, (see function PULSE VALUE on Page 35), and from the current flowis too large to maintain the pulse width selected (interval P is smaller than the pulse width B entered), a system error message (pulse memory) is generated after buffering/balancing time.
Function description PULSE/FREQUENCY OUTPUT
B=P
B
PP
B
B< P
F06-xxxxxxxx-05-xx-xx-xx-012
10 Group PULSE/FREQUENCY OUTPUT Device Functions PROline Promass 80
36 Endress+Hauser
OUTPUT SIGNAL! Note!This function is not available unless the PULSE setting was selected in the OPERATION MODE function.
Use this function to configure the output in such a way that it for example matches an external totalizer. According to the application, the direction of the pulses can be selected here.
Options:PASSIVE - POSITIVEPASSIVE - NEGATIVE
Factory setting:PASSIVE - POSITIVE
PASSIVE:
! Note!For continuous currents up to 25 mA (Imax = 250 mA / 20 ms)
FAILSAFE MODE! Note!This function is not available unless the PULSE setting was selected in the OPERATION MODE function.
For reasons of safety it is advisable to ensure that the pulse output assumes a predefined state in the event of a fault. Use this function to define this state. The setting you select here affects only the pulse output. It has no effect on other outputs and the display (e.g. totalizer).
Options:FALLBACK VALUEOutput is 0 pulse.
HOLD VALUEMeasured value output is based on the last measured value saved before the fault occurred.
ACTUAL VALUEMeasured value output is based on the current flow measurement. The fault is ignored.
Factory setting:FALLBACK VALUE
Function description PULSE/FREQUENCY OUTPUT
1 5 8 37+
-
=
OpenCollector
U = 30 V DCExternal power supply
max
F-x
xxxx
xx-0
4-xx
-xx-
en-
000
B B
PASSIVE-POSITIVEpulses
conducting conducting
nonconducting
nonconducting
t t
transistor transistor
PASSIVE-NEGATIVEpulses
B = Pulse width
F-x
xxxx
xx-0
5-xx
-xx-
en-0
01
Device Functions PROline Promass 80 10 Group PULSE/FREQUENCY OUTPUT
Endress+Hauser 37
SIMULATION PULSE ! Note!This function is not available unless the PULSE option was selected in the OPERATING MODE function.
Use this function to activate simulation of the pulse output.
Options: OFFCOUNTDOWNThe pulses specified in the VALUE SIMULATION PULSE function are output.
CONTINUOUSLYPulses are continuously output with the pulse width specified in the PULSE WIDTH function. Simulation is started once the CONTINUOUSLY option is confirmed with the F key.
! Note!Simulation is started by confirming the CONTINUOUSLY option with the F key.The simulation can be switched off again via the SIMULATION PULSE function.
Factory setting:OFF
! Note!• The notice message #631 “SIM. PULSE” indicates that simulation is active.• The on/off ratio is 1:1 for both types of simulation.• The measuring device continues to measure while simulation is in progress,
i.e. the current measured values are output correctly via the other outputs.
" Caution!The setting is not saved if the power supply fails.
VALUE SIMULATION PULSE ! Note!
This function is not available unless the COUNTDOWN option was selected in the SIMULATION PULSE function.
Use this function to specify the number of pulses (e.g. 50) which are output during the simulation. This value is used to test downstream devices and the measuring device itself. The pulses are output with the pulse width specified in the PULSE WIDTH function. The on/off ratio is 1:1.
Simulation is started once the specified value is confirmed with the F key. The display remains at 0 if the specified pulses have been output.
User input:0...10 000
Factory setting:0
! Note!Simulation is started by confirming the simulation value with the F key.The simulation can be switched off again via the SIMULATION PULSE function.
" Caution!The setting is not saved if the power supply fails.
Function description PULSE/FREQUENCY OUTPUT
11 Group STATUS OUTPUT Device Functions PROline Promass 80
38 Endress+Hauser
11 Group STATUS OUTPUT
Function description STATUS OUTPUT
This group is not available unless the measuring device is fitted with a status output.
ASSIGN STATUS Use this function to assign a switching function to the status output.
Options:OFFON (operation)FAULT MESSAGENOTICE MESSAGEFAULT MESSAGE or NOTICE MESSAGEEMPTY PIPE DETECTION (only if function is active)FLOW DIRECTIONLIMIT MASS FLOWLIMIT VOLUME FLOWLIMIT CORRECTED VOLUME FLOWLIMIT DENSITYLIMIT REFERENCE DENSITYLIMIT TEMPERATURE
Factory setting:FAULT MESSAGE
! Note!• The behaviour of the status output is of the quiescent-current type, in other
words the output is closed (transistor conductive) when normal, error-free measuring is in progress.
• Please read and comply with the information on the switching characteris-tics of the status output (see Page 40, 41).
• If you select OFF, the only function shown in this function group is this func-tion, in other words ASSIGN STATUS.
ON-VALUE! Note!This function is not available unless LIMIT MASS FLOW, LIMIT VOLUME FLOW, LIMIT CORRECTED VOLUME FLOW, LIMIT TEMPERATURE, LIMIT DENSITY, LIMIT REFERENCE DENSITY or FLOW DIRECTION was selected in the ASSIGN STATUS function.
Use this function to assign a value to the switch-on point (status output conductive). The value can be greater or less than the switch-off point.Positive and negative values are permissible.
User input:5-digit floating-point number
Factory setting:0 [kg/h] or 0 [m3/h] or 2 [kg/l] or 200 [°C]
OFF-VALUE! Note!This function is not available unless LIMIT MASS FLOW, LIMIT VOLUME FLOW, LIMIT CORRECTED VOLUME FLOW, LIMIT TEMPERATURE, LIMIT DENSITY, LIMIT REFERENCE DENSITY was selected in the ASSIGN STATUS function.
Use this function to assign a value to the switch-off point (status output not conductive). The value can be greater or less than the switch-on point.Positive and negative values are permissible.
User input:5-digit floating-point number
Factory setting:0 [kg/h] or 0 [m3/h] or 2 [kg/l] or 200 [°C]
Device Functions PROline Promass 80 11 Group STATUS OUTPUT
Endress+Hauser 39
TIME CONSTANT! Note!This function is not available unless one of the following was selected in the ASSIGN STATUS function:FLOW DIRECTIONLIMIT MASS FLOWLIMIT VOLUME FLOWLIMIT CORRECTED VOLUME FLOWLIMIT DENSITYLIMIT REFERENCE DENSITYLIMIT TEMPERATURE
Use this function to enter a time constant defining how the status output reacts to severely fluctuating measured variables, either very quickly (enter a low time constant) or with damping (enter a high time constant). The purpose of damping, therefore, is to prevent the status output changing state continuously in response to fluctuations in flow.
User input:5-digit floating-point number: 0.00...100.00 s
Factory setting:0.00 s
ACTUAL STATUS Use this function to check the current status of the status output.
Display shows:NOT CONDUCTIVECONDUCTIVE
SIMULATIONSWITCH POINT
Use this function to activate simulation of the status output.
Options:OFFON
Factory setting:OFF
! Note!• The “SIMULATION STATUS OUTPUT” message indicates that simulation is
active.• The measuring device continues to measure while simulation is in progress,
i.e. the current measured values are output correctly via the other outputs.
" Caution!The setting is not saved if the power supply fails.
VALUE SIMULATION SWITCH POINT ! Note!
This function is not available unless the ON setting was selected in the SIMU-LATION SWITCH POINT function.
Use this function to define the switching response of the status output during the simulation. This value is used to test downstream devices and the flow-meter itself.
User input:NOT CONDUCTIVECONDUCTIVE
Factory setting:NOT CONDUCTIVE
" Caution!The setting is not saved if the power supply fails.
Function description STATUS OUTPUT
11 Group STATUS OUTPUT Device Functions PROline Promass 80
40 Endress+Hauser
11.1 Information on the response of the status output
GeneralIf you have configured the status output for “LIMIT” or “FLOW DIRECTION”, you can define the requisite switching points in the ON-VALUE and OFF-VALUE functions. When the measured variable in question reaches one of these predefined values, the status output signal switches as shown in the illustrations below.
Status output configured for direction of flowThe value you entered in the ON-VALUE function defines the switching points for the positive and negative directions of flow. If, for example, the switching point you define is = 1 kg/h, the status output is not conductive at –1 kg/h and is conductive at +1 kg/h. Set the switching point to 0 if your process calls for direct switchover (no switching hysteresis). If low flow cut off is used, it is advisable to set hysteresis to a value greater than or equal to the low flow cut off rate.
Switch-off / switch-on point
a = Status output conductiveb = Status output not conductive
Status output configured for limit valueThe status output signal switches as soon as the measured variable falls below or exceeds a defined switching point. Application: Monitoring flow or process-related boundary conditions.
Measured variable
➀ = ON ≤ OFF-VALUE (maximum safety)➁ = ON > OFF-VALUE (minimum safety)➂ = Status output off (not conductive)
F-x
xxxx
xx-0
5-xx
-xx-
xx-0
04
t
➀
➂ ➂
➁
F-x
xxxx
xx-0
5-xx
-xx-
xx-0
05
Device Functions PROline Promass 80 11 Group STATUS OUTPUT
Endress+Hauser 41
11.2 Switching action of the status output
Function State Open Collector (Transistor)
ON (operation) System in measuring mode
conductive
System not in measuring mode (power supply failure) not
conductive
Fault message System OK
conductive
(System or process error)Fault ➝ Error response of outputs, inputs and totalizer
not conductive
Notice message System OK
conductive
(System or process error)Fault ➝ Continuation of measuring
not conductive
Fault messageorNotice message
System OK
conductive
(System or process error)Fault ➝ Response to error or Info ➝ Continuation of measuring
not conductive
Empty pipe detection (EPD)
Fluid density above response level, e.g. full measuring tube
conductive
Fluid density below response level, e.g. empty measuring tube
not conductive
Flow direction forward
conductive
reversenot
conductive
Limit value• mass flow• volume flow• corrected vol-
ume flow• density• corrected density• temperature
Limit value not overshot or undershot
conductive
Limit value overshot or undershot not
conductive
12 Group STATUS INPUT Device Functions PROline Promass 80
42 Endress+Hauser
12 Group STATUS INPUT
Function description STATUS INPUT
This group is not available unless the measuring device is fitted with a status input I/O module.
ASSIGN STATUS INPUT Use this function to assign a switching function to the status input.
Options:OFFRESET TOTALIZER 1POSITIVE ZERO RETURNZEROPOINT ADJUSTMENTRESET TOTALIZER 2RESET ALL TOTALIZERS
Factory setting:OFF
! Note!Positive zero return is active as long as the active level is available at the status input (continuous signal). All other assignments react to a change in level (pulse) at the status input.
ACTIVE LEVEL Use this function to define whether the assigned function (see ASSIGN STATUS INPUT function) is released when the signal level is present (HIGH) or not present (LOW).
Options:HIGHLOW
Factory setting:HIGH
MINIMUM PULSE WIDTH
Use this function to define a minimum width which the input pulse must achieve in order to trigger the defined switching function.
User input:20...100 ms
Factory setting:50 ms
SIMULATION STATUS INPUT
Use this function to activate simulation of the status input, in other words to trigger the function assigned to the status input (see the ASSIGN STATUS INPUT function on Page 38).
Options: OFFON
Factory setting:OFF
! Note!• The “SIMULATION STATUS INPUT” message indicates that simulation is
active.• The measuring device continues to measure while simulation is in progress,
i.e. the current measured values are output correctly via the outputs.
" Caution!The setting is not saved if the power supply fails.
Device Functions PROline Promass 80 12 Group STATUS INPUT
Endress+Hauser 43
VALUE SIMULATION STATUS INPUT ! Note!
This function is not available unless the ON setting was selected in the SIMULATION STATUS INPUT function.
Use this function to select the level to be assumed at the status input during the simulation.
Options:HIGHLOW
Factory setting:LOW
" Caution!The setting is not saved if the power supply fails.
Function description STATUS INPUT
13 Group COMMUNICATION Device Functions PROline Promass 80
44 Endress+Hauser
13 Group COMMUNICATION
Function description COMMUNICATION
TAG NAME Use this function to enter a tag name for the measuring device. You can edit and read this tag name at the local display or via the HART protocol.
User input:max. 8-character text, permissible: A-Z, 0-9, +,–, punctuation marks
Factory setting:“_ _ _ _ _ _ _ _” (without text)
TAG DESCRIPTION Use this function to enter a tag description for the measuring device. You can edit and read this tag description at the local display or via the HART protocol.
User input:max. 16-character text, permissible: A-Z, 0-9, +,–, punctuation marks
Factory setting:“_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _” (without text)
BUS ADDRESS Use this function to define the address for the exchange of data with the HART protocol.
User input:0...15
Factory setting:0
! Note!Addresses 1...15: a constant 4 mA current is applied.
HART PROTOCOL Use this function to display if the HART protocol is active.
Anzeige:OFF = HART protocol not aktiveON = HART protocol aktive
! Note!The HART protocol can be activated with the selection 4-20 mA HART resp. 4-20 mA (25 mA) HART in the CURRENT SPAN function (see Page 23).
MANUFACTURER ID Use this function to view the manufacturer ID in decimal numerical format.
Display shows:Endress+Hauser17 = (≅ 11 hex) for Endress+Hauser
DEVICE ID Use this function to view the device ID in hexadecimal numerical format.
Display shows:50 = (≅ 80 dez) for Promass 80
Device Functions PROline Promass 80 14 Group PROCESS PARAMETER
Endress+Hauser 45
14 Group PROCESS PARAMETER
Function description PROCESS PARAMETER
ASSIGN LOW FLOW CUT OFF
Use this function to assign the switching point for the low flow cut off.
Options:OFFMASS FLOWVOLUME FLOWCORRECTED VOLUME FLOW
Factory setting:MASS FLOW
ON VALUE LOW FLOW CUT OFF
Use this function to assign the on value for the low flow cut off. Low flow cut off is active if the setting is a value not equal to 0. The sign of the flow value is highlighted on the display to indicate that low flow cut off is active.
User input:5-digit floating-point number
Factory setting:depends on nominal diameter
! Note!The appropriate unit is taken from the corresponding UNIT function in the group SYSTEM UNITS (see Page 8).
OFF VALUE LOW FLOW CUT OFF
Use this function to enter the switch-off point for low flow cut off.Enter the switch-off point as a positive hysteresis value from the switch-on point.
User input:Integer 0...100%
Factory setting:50%
Example:
Q = Flow [volume/time]t = TimeH = Hysteresisa = ON VALUE LOW FLOW CUT OFF = 200 g/hb = OFF VALUE LOW FLOW CUT OFF = 10%c = Low flow cut off active1 = Low flow cut off is switched on at 200 g/h2 = Low flow cut off is switched off at 220 g/h
1
c c
Q
t
1
2b
a
2
H
F0
6-80
xxxx
xx-0
5-xx
-xx-
xx-0
07
14 Group PROCESS PARAMETER Device Functions PROline Promass 80
46 Endress+Hauser
EMPTY PIPE DETECTION (EPD)
Use this function to activate the empty pipe detection (EPD). With empty measuring tubes the density of the fluid falls below a specified value (see EPD VALUE LOW function).
Options: OFFON
Factory setting:OFF
" Caution!• Select a correspondingly low EPD VALUE LOW so that the difference to the
effective density of the fluid is sufficiently large enough.This ensures that totally empty measuring tubes and not partially filled ones are detected.
• For gas measurement we strongly recommend to switch off empty pipe detection.
EPD VALUE LOW! Note!This function is not available unless the ON selection was selected in the EMPTY PIPE DETECTION (EPD) function.
Use this function to set an lower threshold for the measured density value, in order to detect possible problems in the process indicated by too low density.
User input:5-digit floating-point number
Factory setting:0.2000 g/cc
EPD VALUE HIGH! Note!This function is not available unless the ON selection was selected in the EMPTY PIPE DETECTION (EPD) function.
Use this function to set an upper threshold for the measured density value.
User input:5-digit floating-point number
Factory setting:6.0000 g/cc
EPD RESPONSE TIME Use this function to enter the time span for which the criteria for an empty pipe have to be satisfied without interruption before a notice message or fault mes-sage is generated.
User input:fixed-point number: 1.0...60.0 s
Factory setting:1.0 s
Function description PROCESS PARAMETER
Device Functions PROline Promass 80 14 Group PROCESS PARAMETER
Endress+Hauser 47
FIXED REFERENCE DENSITY
In this function, a fixed value for the reference density can be entered, with which the corrected volume flow or corrected volume is calculated.
User input:5-digit floating-point number
Factory setting:1 kg/Nl
ZERO POINT ADJUST This function enables a zero point adjustment to be automatically carried out. The new zero point determined by the measuring system is adopted by the ZERO POINT function (see Page 52).
Options:CANCELSTART
Factory setting:CANCEL
" Caution!Before carrying out the calibration, please refer to BA 057D/06/en “Promass 80 Operating Instructions” where a detailed description of the zero point adjust-ment is given.
! Note!• Programming is locked during zero point adjustment and the display shows:
“ZERO ADJUST RUNNING”.• If the zero point adjustment is not possible, e.g. with a flow velocity
> 0.1 m/s, or has been cancelled, then the alarm message “ZERO ADJUST NOT POSSIBLE” is shown on the display.
• If the Promass 80 measuring electronics are fitted with a status input, then the zero point can also be activated by using this input.
• After Zero point adjustment is completed, the new zero point can be called up with theF key. If the F key is pressed again, you return to the ZERO POINT ADJUST function.
DENSITY SET VALUE In this function, enter the density set value of the particular fluid for which you want to carry out a field density adjustment.
User input:5 digit floating-point number, incl. units (corresponding to 0.1...5.9999 kg/l)
! Note!• The preset density entered here should not vary from the actual fluid density
by a more than ±10%.• The appropriate unit is taken from the corresponding UNIT function in the
group SYSTEM UNITS (see Page 8).
MEASURE FLUID In this function the actual density of the fluid is measured for the density adjustment.
Options:CANCELSTART
Function description PROCESS PARAMETER
14 Group PROCESS PARAMETER Device Functions PROline Promass 80
48 Endress+Hauser
DENSITY ADJUST With this function a density adjustment can be carried out on site. The density set value will thus be recalculated and stored. This ensures that the values dependent on density calculations (e.g. volume flow) are as accurate as possi-ble.
" Caution!Before carrying out a density adjustment, please refer to BA 057D/06/en “Promass 80 Operating Instructions” where a detailed description of the density adjustment is given.
! Note!The density adjustment can be executed if:• The sensor does not accurately measure the density which the operator
expects based on laboratory trials.• The characteristics of the fluid are outside the measuring points set at the
factory or reference conditions under which the flowmeter has been calibrated.
• The plant is used solely for measuring a fluid whose density is to be determined very accurately under constant conditions.
User input:CANCELDENSITY ADJUST
Factory setting:CANCEL
RESTORE ORIGINAL With this function the original density coefficient determined at the factory are restored.
Options:NOYES
Factory setting:NO
PRESSURE MODE Use this function to configure an automatic pressure correction. In this way, the effect of a pressure deviation between the calibration and process pressures on the measured error for mass flow is compensated for, (see also Operating Instructions PROline promass 80, BA 057D/06/en, Accuracy Chapter).
Options:OFFFIX (A fixed process pressure for pressure correction is specified)
Factory setting:OFF
PRESSURE! Note!This function is not available unless FIX was selected in the PRESSURE MODE function.
Use this function to enter the value for the process pressure which should be used during pressure correction.
User input:7-digit floating-point number
Factory setting:0 bar g
! Note!The appropriate unit is taken from the function group SYSTEM UNITS (see Page 8).
Function description PROCESS PARAMETER
Device Functions PROline Promass 80 15 Group SYSTEM PARAMETER
Endress+Hauser 49
15 Group SYSTEM PARAMETER
Function description SYSTEM PARAMETER
INSTALLATION DIRECTION SENSOR
Use this function to reverse the sign of the measured variable, if necessary.
Options:NORMAL (flow as indicated by the arrow)INVERSE (flow opposite to direction indicated by the arrow)
Factory setting:NORMAL
! Note!Ascertain the actual direction of fluid flow with reference to the direction indicated by the arrow on the sensor (nameplate).
MEASURING MODE Use this function to define the measuring mode for all outputs.
Options:STANDARDSYMMETRY
Factory setting:STANDARD
The responses of the individual outputs in each of the measuring modes are described in detail below:
Current and frequency outputSTANDARDThe output signals of the current and frequency output are proportional to the measured variable. The flow components outside the scaled measuring range (between VALUE 0_4 mA or VALUE F LOW ➀ and the VALUE 20 mA or VALUE F HIGH ➁) are not taken into account for signal output, but a message “CURRENT RANGE AT FULL SCALE VALUE” or “FREQUENCY RANGE AT FULL SCALE VALUE” is issued.
Example for current output:
SYMMETRYThe output signals of the current and frequency output are independent of the direction of flow (absolute amount of the measured variable). The “VALUE 20 mA” or “VALUE F HIGH” ➂ (e.g. backflow) corresponds to the mirrored VALUE 20 mA or VALUE F HIGH ➁ (e.g. flow).
Example for current output:
Q
20
4
0➀ ➁
mA
F-x
xxxx
xx-0
5-xx
-xx-
xx-0
03
Q
20
0➀ ➁➂
mA
4 F-x
xxxx
xx-0
5-xx
-xx-
xx-0
07
15 Group SYSTEM PARAMETER Device Functions PROline Promass 80
50 Endress+Hauser
MEASURING MODE(Continuation)
Pulse outputSTANDARDOnly positive flow components are totaled. Negative components are not taken into account.
SYMMETRYPositive and negative flow components are taken into account.
! Note!The direction of flow can be output via the configurable status output.
Status output
! Note!Only if in the ASSIGN STATUS function the LIMIT option is selected.
STANDARDThe status output signal switches at the defined switching points.
SYMMETRYThe status output signal switches at the defined switching points, irrespective of the sign. In other words, if you define a switching point with a positive sign the status output signal switches as soon as the value is reached in the nega-tive direction (negative sign) (see illustration).
Example for the SYMMETRY measuring mode:
Switch-on point: Q = 4Switch-off point: Q = 10➀ = Status output switched on (conductive)➁ = Status output switched off (non-conductive)
POSITIVE ZERO RETURN
Use this function to interrupt evaluation of measured variables. This is neces-sary when a piping system is being cleaned, for example. This setting acts on all functions and outputs of the measuring device.
Options:OFFON (signal output is set to zero flow value, temperature and density are output normally)
Factory setting:OFF
Function description SYSTEM PARAMETER
0
- 4
- 10
4
10
Q
t
➀ ➀ ➀➁ ➁
F-x
xxxx
xx-0
5-xx
-xx-
xx-0
05
Device Functions PROline Promass 80 15 Group SYSTEM PARAMETER
Endress+Hauser 51
DENSITY DAMPING The density filter allows the sensitivity of the density measuring signal to be lowered with respect to variations in the density of the fluid, e.g. with inhomo-geneous liquids.
User input:max. 5-digit number, including unit: 0.00...100.00 s
Factory setting:0.00 s
! Note!The damping acts on all functions and outputs of the measuring device.
FLOW DAMPING Using the interference blanking (= time constant for exponential filter) the sensitivity of the flow measurement signal can be reduced with respect to transient flows and interference peaks; e.g. with fluid containing solids or gas bubbles, etc.
User input:0...100 s
Factory setting:0 s
! Note!The damping acts on all functions and outputs of the measuring device.
Function description SYSTEM PARAMETER
16 Group SENSOR DATA Device Functions PROline Promass 80
52 Endress+Hauser
16 Group SENSOR DATA
Function description SENSOR DATA
All sensor data, including calibration factor, zero point, nominal diameter, etc. are set at the factory. All the sensor's parameter settings are saved on the S-DAT™ memory chip.
" Caution!Under normal circumstances you should not change these parameter settings, because changes affect numerous functions of the entire measuring facility in general, and the accuracy of the measuring system in particular. Consequently, most of the functions described below can be accessed only by entering a special service code, which is not the same as your private code number.
Contact the E+H service organization if you have any questions about these functions.
K-FACTOR This function shows the current calibration factor for the sensor.
Factory setting:depends on nominal diameter and calibration
! Note!If the service code is used to call this function, this value can be edited.
ZERO POINT This function shows the current zero-point correction value for the sensor. The zero-point correction factor is calculated and set at the factory.
User input:max. 5-digit number: –99999...+99999
Factory setting:depends on calibration
NOMINAL DIAMETER This function shows the nominal diameter for the sensor. The nominal diameter depends on the size of the sensor and is set at the factory.
Factory setting:depends on the size of the sensor
! Note!If the service code is used to call this function, this value can be edited.
TEMPERATURE COEFFICIENT KM
This function shows the temperatur coefficient KM.
TEMPERATURE COEFFICIENT KM 2
This function shows the temperatur coefficient KM 2.
TEMPERATURE COEFFICIENT KT
This function shows the temperatur coefficient KT.
CALIBRATION COEFFICIENT KD 1
This function shows the calibration coefficient KD 1.
CALIBRATION COEFFICIENT KD 2
This function shows the calibration coefficient KD 2.
Device Functions PROline Promass 80 16 Group SENSOR DATA
Endress+Hauser 53
DENSITY COEFFICIENT C 0
This function shows the actual density coefficient C 0.
" Caution!A density adjustment can alter the calibration value of this coefficient.
DENSITY COEFFICIENT C 1
This function shows the actual density coefficient C 1.
" Caution!A density adjustment can alter the calibration value of this coefficient.
DENSITY COEFFICIENT C 2
This function shows the actual density coefficient C 2.
" Caution!A density adjustment can alter the calibration value of this coefficient.
DENSITY COEFFICIENT C 3
This function shows the actual density coefficient C 3.
" Caution!A density adjustment can alter the calibration value of this coefficient.
DENSITY COEFFICIENT C 4
This function shows the actual density coefficient C 4.
" Caution!A density adjustment can alter the calibration value of this coefficient.
DENSITY COEFFICIENT C 5
This function shows the actual density coefficient C 5.
" Caution!A density adjustment can alter the calibration value of this coefficient.
MINIMAL TEMPERATURE MEASURED
Display of the lowest fluid temperature measured.
MAXIMAL TEMPERATURE MEASURED
Display of the highest fluid temperature measured.
MINIMAL TEMPERATURE CARRIER TUBE
Display of the lowest carrier tube temperature measured.
MAXIMAL TEMPERATURE CARRIER TUBE
Display of the highest carrier tube temperature measured.
Function description SENSOR DATA
17 Group SUPERVISION Device Functions PROline Promass 80
54 Endress+Hauser
17 Group SUPERVISION
Function description SUPERVISION
ACTUAL SYSTEM CONDITION
Use this function to check the current system status.
Display shows:“SYSTEM OK” or the fault / notice message with the highest priority.
PREVIOUS SYSTEM CONDITION
Use this function to view the fifteen most recent fault and notice messages since measuring last started.
Display shows:The 15 most recent fault or notice messages.
ASSIGN SYSTEM ERROR
Use this function to view all system messages and the associated error categories (fault message or notice message). If you select a single system fault you can change its error category.
Display shows:List of system errors
! Note!• Press the F key twice to call the ERROR CATEGORY function.• Use the OS key combination or select CANCEL in the system error list to
exit the function.
ERROR CATEGORY Use this function to define whether a system fault triggers a notice message or a fault message. If you select “FAULT MESSAGES”, all outputs respond to a fault in accordance with their defined error response patterns.
Options:NOTICE MESSAGES (display only)FAULT MESSAGES (outputs and display)
! Note!• Press the F key twice to call the ASSIGN SYSTEM ERROR function.• Use the OS key combination to exit the function.
ASSIGN PROCESS ERROR
Use this function to view all process errors and the associated error categories (fault message or notice message). If you select a single process error you can change its error category.
Display shows:List of process errors
! Note!• Press the F key twice to call the ERROR CATEGORY function.• Use the OS key combination or select CANCEL in the process error list to
exit the function.
Device Functions PROline Promass 80 17 Group SUPERVISION
Endress+Hauser 55
ERROR CATEGORY Use this function to define whether a process error triggers a notice message or a fault message. If you select “FAULT MESSAGES”, all outputs respond to a fault in accordance with their defined error response patterns.
Options: NOTICE MESSAGES (display only)FAULT MESSAGES (outputs and display)
! Note!• Press the F key twice to call the ASSIGN PROCESS ERROR function.• Use the OS key combination to exit the function.
ALARM DELAY Use this function to define a time span for which the criteria for an error have to be satisfied without interruption before an error or notice message is generated.
Depending on the setting and the type of fault, this suppression acts on:• Displa• Current output• Frequency output• Status output
User input:0...100 s (in steps of one second)
Factory setting:0 s
" Caution!If this function is activated fault and notice messages are delayed by the time corresponding to the setting before being forwarded to the higher-order controller (process controller, etc.). It is therefore imperative to check in advance in order to make sure whether a delay of this nature could affect the safety requirements of the process. If fault and notice messages cannot be suppressed, a value of 0 seconds must be entered here.
SYSTEM RESET Use this function to perform a reset of the measuring system.
Options:NORESTART SYSTEM (restart without interrupting line supply)
Factory setting:NO
OPERATION HOURS The hours of operation of the device appear on the display.
Display:Depends on the number of hours of operation elapsed:Hours of operation < 10 hours → display format = 0:00:00 (hr:min:sec)Hours of operation 10...10,000 hours → display format = 0000:00 (hr:min)Hours of operation > 10,000 hours → display format = 000000 (hr)
Function description SUPERVISION
18 Group SIMULATION SYSTEM Device Functions PROline Promass 80
56 Endress+Hauser
18 Group SIMULATION SYSTEM
Function description SIMULATION SYSTEM
SIMULATION FAILSAFE MODE
Use this function to set all inputs, outputs and totalizer to their defined fault response modes, in order to check whether they respond correctly. During this time, the words “SIMULATION FAILSAFE MODE” appear on the display.
Options:OFFON
Factory setting:OFF
SIMULATION MEASURAND
Use this function to set all inputs, outputs and totalizer to their defined flow-response modes, in order to check whether they respond correctly. During this time, the words “SIMULATION MEASURAND” appear on the display.
Options:OFFMASS FLOWVOLUME FLOWCORRECTED VOLUME FLOWDENSITYREFERENCE DENSITYTEMPERATURE
Factory setting:OFF
" Caution!• The measuring device cannot be used for measuring while this simulation is
in progress.• The setting is not saved if the power supply fails.
VALUE SIMULATION MEASURAND ! Note!
This function is not available unless the SIMULATION MEASURAND function is active.
Use this function to define a selectable value (e.g. 12 kg/s). This value is used to test downstream devices and the flowmeter itself.
User input:5-digit floating-point number
Factory setting:0 kg/h (MASS FLOW)0 m3/h (VOLUME FLOW)0 Nm3/h (CORRECTED VOLUME FLOW)0 kg/l (DENSITY)0 kg/NI (REFERENCE DENSITY)0 °C (TEMPERATURE)
" Caution!The setting is not saved if the power supply fails.
Device Functions PROline Promass 80 19 Group SENSOR VERSION
Endress+Hauser 57
19 Group SENSOR VERSION
20 Group AMPLIFIER VERSION
Function description SENSOR VERSION
SERIAL NUMBER Use this function to view the serial number of the sensor.
SENSOR TYPE Use this function to view the sensor type (e.g. Promass F).
SOFTWARE REVISION NUMBER S-DAT
Use this function to view the software revision number of the S-DAT.
Function description AMPLIFIER VERSION
SOFTWARE REVISION NUMBER AMPLIFIER
Use this function to view the software revision number of the amplifier.
LANGUAGE GROUP Use this function to view the language group.
The following language groups can be ordered: WEST EU / USA, EAST EU / SCAND., ASIA.
Display:available language group
! Note!• The language options of the available language group are displayed in the
LANGUAGE function.• You can change the language group via the configuration software
FieldTool. Please do not hesitate to contact your E+H sales office if you have any questions.
I/O MODUL TYPE Use this function to view the I/O type (input/output type).
SOFTWAREREVISION NUMBER I/O
Use this function to view the software revision number of the I/O module.
21 Factory settings Device Functions PROline Promass 80
58 Endress+Hauser
21 Factory settings
21.1 SI units (not for USA and Canada)
Low flow cut off, full scale value, pulse value
Language
Nominal diameter
Low flow cut off Full scale value Pulse value
[mm] (approx. v = 0.04 m/s) (approx. v = 2 m/s) (approx. 2 pulse/s at 2 m/s)
1 0.08 kg/h 4 kg/h 0.001 kg/p
2 0.40 kg/h 20 kg/h 0.010 kg/p
4 1.80 kg/h 90 kg/h 0.010 kg/p
8 8.00 kg/h 400 kg/h 0.100 kg/p
15 26.00 kg/h 1300 kg/h 0.100 kg/p
15 FB 72.00 kg/h 3600 kg/h 1.000 kg/p
25 72.00 kg/h 3600 kg/h 1.000 kg/p
25 FB 180.00 kg/h 9000 kg/h 1.000 kg/p
40 180.00 kg/h 9000 kg/h 1.000 kg/p
40 FB 300.00 kg/h 15000 kg/h 10.000 kg/p
50 300.00 kg/h 15000 kg/h 10.000 kg/p
80 720.00 kg/h 36000 kg/h 10.000 kg/p
100 1200.00 kg/h 60000 kg/h 10.000 kg/p
150 2600.00 kg/h 130000 kg/h 100.000 kg/p
* DN 15, 25, 40 “FB” = Full bore versions Promass I
Country Language
Australia English
Austria Deutsch
Belgium English
Czech Republic Czech
Denmark English
England English
Finland Suomi
France Francais
Germany Deutsch
Hong Kong English
Hungary English
India English
Indonesia Bahasa Indonesia
Instruments International English
Italy Italiano
Japan Japanese
Malaysia English
Netherlands Nederlands
Norway Norsk
Poland Polish
Portugal Portuguese
Russia Russian
Singapore English
South Africa English
Spain Espanol
Sweden Svenska
Switzerland Deutsch
Thailand English
Device Functions PROline Promass 80 21 Factory settings
Endress+Hauser 59
Density, length, temperature, reference density
21.2 US units (only for USA and Canada)
Low flow cut off, full scale value, pulse value
Language, density, length, temperature, reference density
Unit
Density kg/lLength mmTemperature °C
Reference density kg/Nl
Nominal diameter
Low flow cut off Full scale value Pulse value
[mm] (approx. v = 0.04 m/s) (approx. v = 2 m/s) (approx. 2 pulse/s at 2 m/s)
1 0.003 lb/min 0.15 lb/min 0.002 lb/p
2 0.015 lb/min 0.75 lb/min 0.020 lb/p
4 0.066 lb/min 3.30 lb/min 0.020 lb/p
8 0.300 lb/min 15.00 lb/min 0.200 lb/p
15 1.000 lb/min 50.00 lb/min 0.200 lb/p
15 FB 2.600 lb/min 130.00 lb/min 2.000 lb/p
25 2.600 lb/min 130.00 lb/min 2.000 lb/p
25 FB 6.600 lb/min 330.00 lb/min 2.000 lb/p
40 6.600 lb/min 330.00 lb/min 2.000 lb/p
40 FB 11.000 lb/min 550.00 lb/min 20.000 lb/p
50 11.000 lb/min 550.00 lb/min 20.000 lb/p
80 26.000 lb/min 1300.00 lb/min 20.000 lb/p
100 44.000 lb/min 2200.00 lb/min 20.000 lb/p
150 95.000 lb/min 4800.00 lb/min 200.000 lb/p
* DN 15, 25, 40 “FB” = Full bore versions Promass I
UnitLanguage English
Density g/ccLength INCHTemperature °F
Reference density g/Scc
21 Factory settings Device Functions PROline Promass 80
60 Endress+Hauser
Device Functions PROline Promass 80 22 Index of key words
Endress+Hauser 61
22 Index of key words
AAccess code . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15Active Level . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 42Actual
Current . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27Frequency . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33Status output . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39System condition . . . . . . . . . . . . . . . . . . . . . . . . 54
AdjustDensity . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 48Zero point . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 47
Alarm delay . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 55Assign
Current output . . . . . . . . . . . . . . . . . . . . . . . . . . . 23Display line 1 . . . . . . . . . . . . . . . . . . . . . . . . . . . 17Display line 2 . . . . . . . . . . . . . . . . . . . . . . . . . . . 17Frequency . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29Low flow cut off . . . . . . . . . . . . . . . . . . . . . . . . . . 45Process error . . . . . . . . . . . . . . . . . . . . . . . . . . . 54Pulse . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34Status input . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 42Status output . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38System error . . . . . . . . . . . . . . . . . . . . . . . . . . . . 54Totalizer . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
BBus address . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 44
CCalibration coefficient
KD 1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 52KD 2 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 52
Carrier tube temperatureMaximal . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 53Minimal . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 53
CodeAccess code counter . . . . . . . . . . . . . . . . . . . . . 16
CoefficientCalibration
KD 1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 52KD 2 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 52
DensityC 0 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 53C 1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 53C 2 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 53C 3 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 53C 4 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 53C 5 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 53
TemperatureKM . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 52KM 2 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 52KT . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 52
Contrast LDC . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19Current
OutputCurrent span . . . . . . . . . . . . . . . . . . . . . . . . 24
Span . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23, 24Current Output
Actual . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27Assign . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23Failsafe mode . . . . . . . . . . . . . . . . . . . . . . . . . . . 27Simulation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27Span . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23Time constant . . . . . . . . . . . . . . . . . . . . . . . . . . . 27Value Simulation . . . . . . . . . . . . . . . . . . . . . . . . . 28Value 0_4 mA . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24Value 20 mA . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
DDamping
Density . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 51Flow . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 51
Define private code . . . . . . . . . . . . . . . . . . . . . . . . . . 16Density . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
CoefficientC 0 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 53C 1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 53C 2 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 53C 3 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 53C 4 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 53C 5 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 53
Set value . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 47Density adjust . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 48Density damping . . . . . . . . . . . . . . . . . . . . . . . . . . . . 51Device ID . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 44Display
Damping . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19Format . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18Test . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
EEmpty pipe detection
EPD . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 46High value . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 46Low value . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 46Response time . . . . . . . . . . . . . . . . . . . . . . . . . . . 46
End value frequency . . . . . . . . . . . . . . . . . . . . . . . . . 29Error category
Process error . . . . . . . . . . . . . . . . . . . . . . . . . . . . 55System error . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 54
FFactory setting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 58Failsafe mode
Current output . . . . . . . . . . . . . . . . . . . . . . . . . . . 27Frequency . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33Pulse . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36Simulation system . . . . . . . . . . . . . . . . . . . . . . . . 56Totalizer . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
Failsafe valueFrequency . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33
Flow damping . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 51Frequency
22 Index of key words Device Functions PROline Promass 80
62 Endress+Hauser
Actual . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33Assign . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29End value . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29Failsafe mode . . . . . . . . . . . . . . . . . . . . . . . . . . . 33Failsafe value . . . . . . . . . . . . . . . . . . . . . . . . . . . 33Output signal . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32Simulation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34Time constant . . . . . . . . . . . . . . . . . . . . . . . . . . . 32Value F high . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30Value F low . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30Value Simulation . . . . . . . . . . . . . . . . . . . . . . . . . 34
Funktion matrixGraphical illustration . . . . . . . . . . . . . . . . . . . . . . . 6Layout and use . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
GGroup
Amplifier Version . . . . . . . . . . . . . . . . . . . . . . . . . 57Communication . . . . . . . . . . . . . . . . . . . . . . . . . . 44Current output . . . . . . . . . . . . . . . . . . . . . . . . . . . 23Measuring values . . . . . . . . . . . . . . . . . . . . . . . . . 7Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15Process parameter . . . . . . . . . . . . . . . . . . . . . . . 45Pulse/Frequency output . . . . . . . . . . . . . . . . . . . 29Quick Setup . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13Sensor data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 52Sensor Version . . . . . . . . . . . . . . . . . . . . . . . . . . 57Simulation system . . . . . . . . . . . . . . . . . . . . . . . . 56Status input . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 42Status/Relais output . . . . . . . . . . . . . . . . . . . . . . 38Supervision . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 54System parameter . . . . . . . . . . . . . . . . . . . . . . . . 49System units . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8Totalizer . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20User interface . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
HHART protocol . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 44
II/O Modul type . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 57Installation direction sensor . . . . . . . . . . . . . . . . . . . 49
KK-Factor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 52
LLanguage . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15LCD Contrast . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19Low flow cut off
Assign . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 45Off-value . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 45On-value . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 45
MManufacturer ID . . . . . . . . . . . . . . . . . . . . . . . . . . . . 44Mass flow . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7Maximal
Carrier tube temperature . . . . . . . . . . . . . . . . . . 53Temperature measured . . . . . . . . . . . . . . . . . . . 53
Measured fluid . . . . . . . . . . . . . . . . . . . . . . . . . . . . 47Measuring mode . . . . . . . . . . . . . . . . . . . . . . . . . . . 49Minimal
Carrier tube temperature . . . . . . . . . . . . . . . . . . 53Temperature measured . . . . . . . . . . . . . . . . . . . 53
Minimum pulse width . . . . . . . . . . . . . . . . . . . . . . . 42
NNominal Diameter . . . . . . . . . . . . . . . . . . . . . . . . . . 52
OOff-value
Low flow cut off . . . . . . . . . . . . . . . . . . . . . . . . . 45Status output . . . . . . . . . . . . . . . . . . . . . . . . . . . 38
On-valueLow flow cut off . . . . . . . . . . . . . . . . . . . . . . . . . 45Status output . . . . . . . . . . . . . . . . . . . . . . . . . . . 38
OperationMode Pulse-/Freq.-output . . . . . . . . . . . . . . . . . 29
Output signalFrequency . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32Pulse . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36
OverflowTotalizer . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
PPositive zero return . . . . . . . . . . . . . . . . . . . . . . . . . 50Pressure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 48Pressure mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . 48Previous system condition . . . . . . . . . . . . . . . . . . . 54Process Error
Assign . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 54Error category . . . . . . . . . . . . . . . . . . . . . . . . . . 55
PulseAssign . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34Failsafe value . . . . . . . . . . . . . . . . . . . . . . . . . . . 36Output signal . . . . . . . . . . . . . . . . . . . . . . . . . . . 36Value . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35Width . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35
QQuick Setup
Commission . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13Commission (Diagram) . . . . . . . . . . . . . . . . . . . 14
RReset
System . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 55Totalizer . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
Restore original . . . . . . . . . . . . . . . . . . . . . . . . . . . . 48
SSensor type . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 57Serial number sensor . . . . . . . . . . . . . . . . . . . . . . . 57Simulation
Current . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27Failsafe mode . . . . . . . . . . . . . . . . . . . . . . . . . . . 56Frequency . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34Measurand . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 56Status input . . . . . . . . . . . . . . . . . . . . . . . . . . . . 42
Device Functions PROline Promass 80 22 Index of key words
Endress+Hauser 63
Switch point . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39Software revision number
Amplifier . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 57I/O . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 57S-DAT . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 57
StatusAccess . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
Status inputActive level . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 42Assign . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 42Minimum pulse width . . . . . . . . . . . . . . . . . . . . . 42Simulation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 42Value Simulation . . . . . . . . . . . . . . . . . . . . . . . . . 43
Status outputActual . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39Assign . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38Direction of flow . . . . . . . . . . . . . . . . . . . . . . . . . 40General . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40Limit value . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40Off-Value . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38On-Value . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38Switching action . . . . . . . . . . . . . . . . . . . . . . . . . 41Time constant . . . . . . . . . . . . . . . . . . . . . . . . . . . 39
SumTotalizer . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
Switch pointSimulation Status output . . . . . . . . . . . . . . . . . . . 39Value Simulation Status output . . . . . . . . . . . . . . 39
SystemCondition
Actual . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 54Previous . . . . . . . . . . . . . . . . . . . . . . . . . . . 54
Reset . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 55System Error
Assign . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 54Error category . . . . . . . . . . . . . . . . . . . . . . . . . . . 54
TTag
Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 44Name . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 44
Temperature . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7Temperature coefficient
KM . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 52KM 2 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 52KT . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 52
Temperature measuredMaximal . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 53Minimal . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 53
Test Display . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
Time constantCurrent output . . . . . . . . . . . . . . . . . . . . . . . . . . . 27Frequency . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32Status output . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39
TotalizerAssign . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20Failsafe mode . . . . . . . . . . . . . . . . . . . . . . . . . . . 22Overflow . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20Reset . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21Sum . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20Unit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
UUnit
Density . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11Length . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12Mass . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8Mass flow . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8Pressure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12Temperature . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11Totalizer . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21Volume . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9Volume flow . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
VValue
Pulse . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35Value F high . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30Value F low . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30Value Simulation
Current . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28Frequency . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34Measurand . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 56Status input . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43Switch point . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39
Value 0_4 mA . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24Value 20 mA . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24Version
Amplifier . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 57Sensor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 57
Volume flow . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
ZZero point . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 52Zero point adjust . . . . . . . . . . . . . . . . . . . . . . . . . . . . 47
Numerics100% Value
Line 1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18Line 2 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
Europe
Austria – Wien❑ Endress+Hauser Ges.m.b.H.Tel. (01) 88 05 60, Fax (01) 88 05 63 35
Belarus – MinskBelorgsintezTel. (017) 2 50 84 73, Fax (017) 2 50 85 83
Belgium / Luxembourg – Bruxelles❑ Endress+Hauser S.A. / N.V.Tel. (02) 2 48 06 00, Fax (02) 2 48 05 53
Bulgaria – SofiaIntertech-Automation Ltd.Tel. (02) 9 62 71 52, Fax (02) 9 62 14 71
Croatia – Zagreb❑ Endress+Hauser GmbH+Co.Tel. (01) 6 63 77 85, Fax (01) 6 63 78 23
Cyprus – NicosiaI+G Electrical Services Co. Ltd.Tel. (02) 48 47 88, Fax (02) 48 46 90
Czech Republic – Praha❑ Endress+Hauser Czech s.r.o.Tel. (02) 66 78 42 00, Fax (026) 66 78 41 79
Denmark – Søborg❑ Endress+Hauser A/STel. (70) 13 11 32, Fax (70) 13 21 33
Estonia – TartuElvi-Aqua OÜTel. (7) 30 27 32, Fax (7) 30 27 31
Finland – Helsinki❑ Metso Endress+Hauser OyTel. (204) 8 31 60, Fax (204) 8 31 61
France – Huningue❑ Endress+Hauser S.A.Tel. (389) 69 67 68, Fax (389) 69 48 02
Germany – Weil am Rhein❑ Endress+Hauser Messtechnik GmbH+Co. KGTel. (07621) 9 75 01, Fax (07621) 97 55 55
Great Britain – Manchester❑ Endress+Hauser Ltd.Tel. (0161) 2 86 50 00, Fax (0161) 9 98 18 41
Greece – AthensI & G Building Services Automation S.A.Tel. (01) 9 24 15 00, Fax (01) 9 22 17 14
Hungary – Budapest❑ Endress+Hauser MagyarországTel. (01) 4 12 04 21, Fax (01) 4 12 04 24
Iceland – ReykjavikSindra-Stál hfTel. 5 75 00 00, Fax 5 75 00 10
Ireland – Clane / County Kildare❑ Flomeaco Endress+Hauser Ltd.Tel. (045) 86 86 15, Fax (045) 86 81 82
Italy – Cernusco s/N, Milano❑ Endress+Hauser S.p.A.Tel. (02) 92 19 21, Fax (02) 92 19 23 62
Latvia – RigaElekoms Ltd.Tel. (07) 33 64 44, Fax (07) 33 64 48
Lithuania – KaunasUAB Agava Ltd.Tel. (03) 7 20 24 10, Fax (03) 7 20 74 14
Macedonia – BeogradMeris d.o.o.Tel. (11) 44 42 96 6, Fax (11) 30 85 77 8
Moldavia – ChisinauS.C. Techno Test SRLTel. (02) 22 61 60, Fax (02) 22 83 13
Netherlands – Naarden❑ Endress+Hauser B.V.Tel. (035) 6 95 86 11, Fax (035) 6 95 88 25
Norway – Lierskogen❑ Endress+Hauser A/STel. 32 85 98 50, Fax 32 85 98 51
Poland – Wroclaw❑ Endress+Hauser Polska Sp. z o.o.Tel. (071) 7 80 37 00, Fax (071) 7 80 37 60
Portugal – Cacem❑ Endress+Hauser Lda.Tel. (21) 4 26 72 90, Fax (21) 4 26 72 99
Romania – BucharestRomconseng S.R.L.Tel. (021) 41 12 50 1, Fax (021) 41 01 63 4
Russia – Moscow❑ Endress+Hauser GmbH+CoTel. (095) 78 32 85 0, Fax (095) 78 32 85 5
Slovak Republic – BratislavaTranscom Technik s.r.o.Tel. (2) 44 88 86 90, Fax (2) 44 88 71 12
Slovenia – Ljubljana❑ Endress+Hauser (Slovenija) D.O.O.Tel. (01) 5 19 22 17, Fax (01) 5 19 22 98
Spain – Sant Just Desvern❑ Endress+Hauser S.A.Tel. (93) 4 80 33 66, Fax (93) 4 73 38 39
Sweden – Sollentuna❑ Endress+Hauser ABTel. (08) 55 51 16 00, Fax (08) 55 51 16 55
Switzerland – Reinach/BL 1❑ Endress+Hauser Metso AGTel. (061) 7 15 75 75, Fax (061) 7 11 16 50
Turkey – Levent/IstanbulIntek Endüstriyel Ölcü ve Kontrol SistemleriTel. (0212) 2 75 13 55, Fax (0212) 2 66 27 75
Ukraine – KievPhotonika GmbHTel. (44) 2 68 81 02, Fax (44) 2 69 07 05
Yugoslavia Republic – BeogradMeris d.o.o.Tel. (11) 4 44 29 66, Fax (11) 3 08 57 78
Africa
Algeria – AnnabaSymes Systemes et MesuresTel. (38) 88 30 03, Fax (38) 88 30 02
Egypt – Heliopolis/CairoAnasia Egypt For Trading (S.A.E.)Tel. (02) 2 68 41 59, Fax (02) 2 68 41 69
Morocco – CasablancaOussama S.A.Tel. (02) 22 24 13 38, Fax (02) 2 40 26 57
Rep. South Africa – Sandton❑ Endress+Hauser (Pty.) Ltd.Tel. (011) 2 62 80 00, Fax (011) 2 62 80 62
Tunisia – TunisCMR Controle, Maintenance et RegulationTel. (07) 17 93 07 7, Fax (07) 17 88 59 5
America
Argentina – Buenos Aires❑ Endress+Hauser Argentina S.A.Tel. (11) 45 22 79 70, Fax (11) 45 22 79 09
Brazil – Sao Paulo❑ Samson Endress+Hauser Ltda.Tel. (011) 50 33 43 33, Fax (011) 50 31 30 67
Canada – Burlington, Ontario❑ Endress+Hauser Canada Ltd.Tel. (905) 68 19 29 2, Fax (905) 68 19 44 4
Chile – Santiago de Chile❑ Endress+Hauser (Chile) Ltd.Tel. (02) 3 21 30 09, Fax (02) 3 21 30 25
Colombia – Bogota D.C.Colsein Ltda.Tel. (01) 2 36 76 59, Fax (01) 6 10 78 68
Costa Rica – San JoseEuro-Tec S.A.Tel. 2 20 28 08, Fax 2 96 15 42
Ecuador – QuitoInsetec Cia. Ltda.Tel. (02) 2 26 91 48, Fax (02) 2 46 18 33
El Salvador – San SalvadorAutomatizacion y Control Industrial de El Salvador, S.A. de C.V.Tel. 2 60 24 24, Fax 2 60 56 77
Guatemala – Ciudad de GuatemalaAutomatizacion y Control Industrial, S.A.Tel. (03) 34 59 85, Fax (03) 32 74 31
Honduras – San Pedro Sula, CortesAutomatizacion y Control Industrial de Honduras, S.A. de C.V.Tel. 5 57 91 36, Fax 5 57 91 39
Mexico – México, D.F❑ Endress+Hauser (México), S.A. de C.V.Tel. (5) 5 55 68 24 07, Fax (5) 5 55 68 74 59
Nicaragua – ManaguaAutomatización y Control Industrial de Nicaragua, S.A.Tel. 2 22 61 90, Fax 2 28 70 24
Peru – MirafloresCorsusa InternationalTel. (1) 44 41 20 0, Fax (1) 44 43 66 4
USA – Greenwood, Indiana❑ Endress+Hauser Inc.Tel. (317) 5 35 71 38, Fax (317) 5 35 84 98
USA – Norcross, Atlanta❑ Endress+Hauser Systems & Gauging Inc.Tel. (770) 4 47 92 02, Fax (770) 4 47 57 67
Venezuela – CaracasControval C.A.Tel. (212) 9 44 09 66, Fax (212) 9 44 45 54
Asia
Azerbaijan – BakuModcon Systems - BakuTel. (12) 92 98 59, Fax (12) 99 13 72
Brunei – Negara Brunei DarussalamAmerican International Industries (B) Sdn. Bhd.Tel. (3) 22 37 37, Fax (3) 22 54 58
Cambodia – Khan Daun Penh, Phom PenhComin Khmere Co. Ltd.Tel. (23) 42 60 56, Fax (23) 42 66 22
China – Shanghai❑ Endress+Hauser (Shanghai) Instrumentation Co. Ltd.Tel. (021) 54 90 23 00, Fax (021) 54 90 23 03
China – Beijing❑ Endress+Hauser (Beijing) Instrumentation Co. Ltd.Tel. (010) 65 88 24 68, Fax (010) 65 88 17 25
Hong Kong – Tsimshatsui / Kowloon❑ Endress+Hauser (H.K.) Ltd.Tel. 8 52 25 28 31 20, Fax 8 52 28 65 41 71
India – Mumbai❑ Endress+Hauser (India) Pvt. Ltd.Tel. (022) 56 93 83 33, Fax (022) 56 93 88 330
Indonesia – JakartaPT Grama BazitaTel. (21) 7 95 50 83, Fax (21) 7 97 50 89
Iran – TehranPatsa IndustryTel. (021) 8 72 68 69, Fax (021) 8 71 96 66
Israel – NetanyaInstrumetrics Industrial Control Ltd.Tel. (09) 8 35 70 90, Fax (09) 8 35 06 19
Japan – Tokyo❑ Sakura Endress Co. Ltd.Tel. (0422) 54 06 11, Fax (0422) 55 02 75
Jordan – AmmanA.P. Parpas Engineering S.A.Tel. (06) 5 53 92 83, Fax (06) 5 53 92 05
Kazakhstan – AlmatyBEI ElectroTel. (72) 30 00 28, Fax (72) 50 71 30
Korea, South – Seoul❑ Endress+Hauser (Korea) Co. Ltd.Tel. (02) 26 58 72 00, Fax (02) 26 59 28 38
Kuwait – SafatUnited Technical Services Est. For General TradingTel. 2 41 12 63, Fax 2 41 15 93
Lebanon – Jbeil Main EntryNetwork EngineeringTel. (3) 94 40 80, Fax (9) 54 80 38
Malaysia – Shah Alam, Selangor Darul Ehsan❑ Endress+Hauser (M) Sdn. Bhd.Tel. (03) 78 46 48 48, Fax (03) 78 46 88 00
Pakistan – KarachiSpeedy AutomationTel. (021) 7 72 29 53, Fax (021) 7 73 68 84
Philippines – Pasig City, Metro Manila❑ Endress+Hauser (Phillipines) Inc.Tel. (2) 6 38 18 71, Fax (2) 6 38 80 42
Saudi Arabia – JeddahAnasia Trading Est.Tel. (02) 6 53 36 61, Fax (02) 6 53 35 04
Singapore – Singapore❑ Endress+Hauser (S.E.A.) Pte. Ltd.Tel. (65) 66 82 22, Fax (65) 66 68 48
Sultanate of Oman – RuwiMustafa & Sultan Sience & Industry Co. L.L.C.Tel. 63 60 00, Fax 60 70 66
Taiwan – TaipeiKingjarl CorporationTel. (02) 27 18 39 38, Fax (02) 27 13 41 90
Thailand – Bangkok 10210❑ Endress+Hauser (Thailand) Ltd.Tel. (2) 9 96 78 11-20, Fax (2) 9 96 78 10
United Arab Emirates – DubaiDescon Trading L.L.C.Tel. (04) 2 65 36 51, Fax (04) 2 65 32 64
Uzbekistan – TashkentIm Mexatronika-TesTel. (71) 1 91 77 07, Fax (71) 1 91 76 94
Vietnam – Ho Chi Minh CityTan Viet Bao Co. Ltd.Tel. (08) 8 33 52 25, Fax (08) 8 33 52 27
Australia + New Zealand
Australia – North Ryde NSW 2113❑ Endress+Hauser Australia Pty. Ltd.Tel. (02) 88 77 70 00, Fax (02) 88 77 70 99
New Zealand – AucklandEMC Industrial Group Ltd.Tel. (09) 4 15 51 10, Fax (09) 4 15 51 15
All other countries❑ Endress+Hauser GmbH+Co. KGInstruments InternationalWeil am Rhein, GermanyTel. (07621) 9 75 02, Fax (07621) 97 53 45
❑ Members of the Endress+Hauser group
http://www.endress.com
05.03
BA058D/06/en/10.0350098512FM+SGML 6.0