Project Dry BasementA Description of the Backwater
Prevention Program
![Page 2: Project Dry Basement A Description of the …...• Project Dry Basement was developed to install backflow preventers in private residents • There were several issues to consider:](https://reader033.fdocuments.in/reader033/viewer/2022060410/5f1070a27e708231d4491e69/html5/thumbnails/2.jpg)
City of Columbus entered into a consent order in 2003
The Mayor asked the Division to develop a program to address flooded basements
Project Dry Basement was developed in 2004
![Page 3: Project Dry Basement A Description of the …...• Project Dry Basement was developed to install backflow preventers in private residents • There were several issues to consider:](https://reader033.fdocuments.in/reader033/viewer/2022060410/5f1070a27e708231d4491e69/html5/thumbnails/3.jpg)
• Project Dry Basement was developed to install backflow preventers in private residents
• There were several issues to consider:
• Installing valves on private property• Develop a Home Owners agreement• Determine who is eligible for the program• Identify the home owners responsibility• Remove clear water sources from the
service line
![Page 4: Project Dry Basement A Description of the …...• Project Dry Basement was developed to install backflow preventers in private residents • There were several issues to consider:](https://reader033.fdocuments.in/reader033/viewer/2022060410/5f1070a27e708231d4491e69/html5/thumbnails/4.jpg)
Eligibility Requirements for a valve
• Home owner must report a flooded basement to the City
• The flooded basement must be a City responsibility
• Stoppages
• Sewer headed up due to heavy rains
![Page 5: Project Dry Basement A Description of the …...• Project Dry Basement was developed to install backflow preventers in private residents • There were several issues to consider:](https://reader033.fdocuments.in/reader033/viewer/2022060410/5f1070a27e708231d4491e69/html5/thumbnails/5.jpg)
Since the inspection of the program
• 2298 residents have been made eligible
• 823 home owners have returned the agreement and had valves installed (36%)
• The 36% has stayed fairly consistent through the program
• Home Owners do not like to have their basement tore up• They do not like the home owners agreement• Rentals do not like to have a code inspection done• They do not like the idea of not being able to use water
when the valve is closed
![Page 6: Project Dry Basement A Description of the …...• Project Dry Basement was developed to install backflow preventers in private residents • There were several issues to consider:](https://reader033.fdocuments.in/reader033/viewer/2022060410/5f1070a27e708231d4491e69/html5/thumbnails/6.jpg)
The reminder of this presentation is going to focus on the valves we have installed and the Pros and Cons of each valve
Our Disclaimer
• We are not recommending or discouraging the use or purchase of any valve. We are discussing the experience we have had with installing and the use of these valves.
• Please keep in mind that you may have a different experience with these valves. Please feel free to offer any experience you may have.
![Page 7: Project Dry Basement A Description of the …...• Project Dry Basement was developed to install backflow preventers in private residents • There were several issues to consider:](https://reader033.fdocuments.in/reader033/viewer/2022060410/5f1070a27e708231d4491e69/html5/thumbnails/7.jpg)
Valves we have considered or used
• Inexpensive PVC Check Valve -0• In-Line manual shut-off gate valve (Dual
valve) -0• JR Smith Flood Gate Valve – 242• Main Line flapper valve – 196• Clean Check Valve – 270• Spears Backwater Valve – 19
• Sump Pumps installed - 265
![Page 8: Project Dry Basement A Description of the …...• Project Dry Basement was developed to install backflow preventers in private residents • There were several issues to consider:](https://reader033.fdocuments.in/reader033/viewer/2022060410/5f1070a27e708231d4491e69/html5/thumbnails/8.jpg)
Inexpensive PVC Check valve
• 0 Installed• PVC flapper• History prior to PDB • Most causes for the valve failing was a
broken, stuck or missing flapper
![Page 9: Project Dry Basement A Description of the …...• Project Dry Basement was developed to install backflow preventers in private residents • There were several issues to consider:](https://reader033.fdocuments.in/reader033/viewer/2022060410/5f1070a27e708231d4491e69/html5/thumbnails/9.jpg)
In-Line Manual Shut Off Gate ValveThe Dual valve
• 0 installed• History prior to PDB
![Page 10: Project Dry Basement A Description of the …...• Project Dry Basement was developed to install backflow preventers in private residents • There were several issues to consider:](https://reader033.fdocuments.in/reader033/viewer/2022060410/5f1070a27e708231d4491e69/html5/thumbnails/10.jpg)
![Page 11: Project Dry Basement A Description of the …...• Project Dry Basement was developed to install backflow preventers in private residents • There were several issues to consider:](https://reader033.fdocuments.in/reader033/viewer/2022060410/5f1070a27e708231d4491e69/html5/thumbnails/11.jpg)
![Page 12: Project Dry Basement A Description of the …...• Project Dry Basement was developed to install backflow preventers in private residents • There were several issues to consider:](https://reader033.fdocuments.in/reader033/viewer/2022060410/5f1070a27e708231d4491e69/html5/thumbnails/12.jpg)
![Page 13: Project Dry Basement A Description of the …...• Project Dry Basement was developed to install backflow preventers in private residents • There were several issues to consider:](https://reader033.fdocuments.in/reader033/viewer/2022060410/5f1070a27e708231d4491e69/html5/thumbnails/13.jpg)
![Page 14: Project Dry Basement A Description of the …...• Project Dry Basement was developed to install backflow preventers in private residents • There were several issues to consider:](https://reader033.fdocuments.in/reader033/viewer/2022060410/5f1070a27e708231d4491e69/html5/thumbnails/14.jpg)
![Page 15: Project Dry Basement A Description of the …...• Project Dry Basement was developed to install backflow preventers in private residents • There were several issues to consider:](https://reader033.fdocuments.in/reader033/viewer/2022060410/5f1070a27e708231d4491e69/html5/thumbnails/15.jpg)
![Page 16: Project Dry Basement A Description of the …...• Project Dry Basement was developed to install backflow preventers in private residents • There were several issues to consider:](https://reader033.fdocuments.in/reader033/viewer/2022060410/5f1070a27e708231d4491e69/html5/thumbnails/16.jpg)
![Page 17: Project Dry Basement A Description of the …...• Project Dry Basement was developed to install backflow preventers in private residents • There were several issues to consider:](https://reader033.fdocuments.in/reader033/viewer/2022060410/5f1070a27e708231d4491e69/html5/thumbnails/17.jpg)
![Page 18: Project Dry Basement A Description of the …...• Project Dry Basement was developed to install backflow preventers in private residents • There were several issues to consider:](https://reader033.fdocuments.in/reader033/viewer/2022060410/5f1070a27e708231d4491e69/html5/thumbnails/18.jpg)
![Page 19: Project Dry Basement A Description of the …...• Project Dry Basement was developed to install backflow preventers in private residents • There were several issues to consider:](https://reader033.fdocuments.in/reader033/viewer/2022060410/5f1070a27e708231d4491e69/html5/thumbnails/19.jpg)
![Page 20: Project Dry Basement A Description of the …...• Project Dry Basement was developed to install backflow preventers in private residents • There were several issues to consider:](https://reader033.fdocuments.in/reader033/viewer/2022060410/5f1070a27e708231d4491e69/html5/thumbnails/20.jpg)
![Page 21: Project Dry Basement A Description of the …...• Project Dry Basement was developed to install backflow preventers in private residents • There were several issues to consider:](https://reader033.fdocuments.in/reader033/viewer/2022060410/5f1070a27e708231d4491e69/html5/thumbnails/21.jpg)
![Page 22: Project Dry Basement A Description of the …...• Project Dry Basement was developed to install backflow preventers in private residents • There were several issues to consider:](https://reader033.fdocuments.in/reader033/viewer/2022060410/5f1070a27e708231d4491e69/html5/thumbnails/22.jpg)
![Page 23: Project Dry Basement A Description of the …...• Project Dry Basement was developed to install backflow preventers in private residents • There were several issues to consider:](https://reader033.fdocuments.in/reader033/viewer/2022060410/5f1070a27e708231d4491e69/html5/thumbnails/23.jpg)
![Page 24: Project Dry Basement A Description of the …...• Project Dry Basement was developed to install backflow preventers in private residents • There were several issues to consider:](https://reader033.fdocuments.in/reader033/viewer/2022060410/5f1070a27e708231d4491e69/html5/thumbnails/24.jpg)
![Page 25: Project Dry Basement A Description of the …...• Project Dry Basement was developed to install backflow preventers in private residents • There were several issues to consider:](https://reader033.fdocuments.in/reader033/viewer/2022060410/5f1070a27e708231d4491e69/html5/thumbnails/25.jpg)
![Page 26: Project Dry Basement A Description of the …...• Project Dry Basement was developed to install backflow preventers in private residents • There were several issues to consider:](https://reader033.fdocuments.in/reader033/viewer/2022060410/5f1070a27e708231d4491e69/html5/thumbnails/26.jpg)
![Page 27: Project Dry Basement A Description of the …...• Project Dry Basement was developed to install backflow preventers in private residents • There were several issues to consider:](https://reader033.fdocuments.in/reader033/viewer/2022060410/5f1070a27e708231d4491e69/html5/thumbnails/27.jpg)
![Page 28: Project Dry Basement A Description of the …...• Project Dry Basement was developed to install backflow preventers in private residents • There were several issues to consider:](https://reader033.fdocuments.in/reader033/viewer/2022060410/5f1070a27e708231d4491e69/html5/thumbnails/28.jpg)
![Page 29: Project Dry Basement A Description of the …...• Project Dry Basement was developed to install backflow preventers in private residents • There were several issues to consider:](https://reader033.fdocuments.in/reader033/viewer/2022060410/5f1070a27e708231d4491e69/html5/thumbnails/29.jpg)
![Page 30: Project Dry Basement A Description of the …...• Project Dry Basement was developed to install backflow preventers in private residents • There were several issues to consider:](https://reader033.fdocuments.in/reader033/viewer/2022060410/5f1070a27e708231d4491e69/html5/thumbnails/30.jpg)
![Page 31: Project Dry Basement A Description of the …...• Project Dry Basement was developed to install backflow preventers in private residents • There were several issues to consider:](https://reader033.fdocuments.in/reader033/viewer/2022060410/5f1070a27e708231d4491e69/html5/thumbnails/31.jpg)
![Page 32: Project Dry Basement A Description of the …...• Project Dry Basement was developed to install backflow preventers in private residents • There were several issues to consider:](https://reader033.fdocuments.in/reader033/viewer/2022060410/5f1070a27e708231d4491e69/html5/thumbnails/32.jpg)
![Page 33: Project Dry Basement A Description of the …...• Project Dry Basement was developed to install backflow preventers in private residents • There were several issues to consider:](https://reader033.fdocuments.in/reader033/viewer/2022060410/5f1070a27e708231d4491e69/html5/thumbnails/33.jpg)
Procheck
![Page 34: Project Dry Basement A Description of the …...• Project Dry Basement was developed to install backflow preventers in private residents • There were several issues to consider:](https://reader033.fdocuments.in/reader033/viewer/2022060410/5f1070a27e708231d4491e69/html5/thumbnails/34.jpg)
Additional Things to Consider• Maintenance – Maintenance – Maintenance• Where the concrete floor is cut use bentonite
around the concrete joint to prevent ground water from leaking through the joint.
• Size of the foot print of the valve pit.• If a sump pump is necessary you must have a
dedicated circuit in the electrical panel.• Make sure you have a positive outlet for the sump
pump.• You only have to protract what drains are in the
basement.