PROFESSIONAL SERIES · LED 4 (Comp) & LED 5 (ConFM) are ON CTh warms to 3 above the set point,...

15
PROFESSIONAL SERIES

Transcript of PROFESSIONAL SERIES · LED 4 (Comp) & LED 5 (ConFM) are ON CTh warms to 3 above the set point,...

Page 1: PROFESSIONAL SERIES · LED 4 (Comp) & LED 5 (ConFM) are ON CTh warms to 3 above the set point, EvapFM continues, Comp. and ConFM energize 2.5 min. Comp. minimum run timer starts DEFROST

PROFESSIONAL SERIES

Page 2: PROFESSIONAL SERIES · LED 4 (Comp) & LED 5 (ConFM) are ON CTh warms to 3 above the set point, EvapFM continues, Comp. and ConFM energize 2.5 min. Comp. minimum run timer starts DEFROST

PROFESSIONAL - SSE

Page 3: PROFESSIONAL SERIES · LED 4 (Comp) & LED 5 (ConFM) are ON CTh warms to 3 above the set point, EvapFM continues, Comp. and ConFM energize 2.5 min. Comp. minimum run timer starts DEFROST

PROFESSIONAL - SSE

Page 4: PROFESSIONAL SERIES · LED 4 (Comp) & LED 5 (ConFM) are ON CTh warms to 3 above the set point, EvapFM continues, Comp. and ConFM energize 2.5 min. Comp. minimum run timer starts DEFROST

PROFESSIONAL - SSE

Stainless steel interior and exterior (with galvanized back and bottom) Innovative variable speed compressor with “adaptive control” technology Energy efficient thermostatic expansion valve, self contained refrigeration system Two years parts and labor warranty

Page 5: PROFESSIONAL SERIES · LED 4 (Comp) & LED 5 (ConFM) are ON CTh warms to 3 above the set point, EvapFM continues, Comp. and ConFM energize 2.5 min. Comp. minimum run timer starts DEFROST

Comp Circuit Diagnosis: If Comp does not start, check for 115VAC at K1 connector pin #10 gray (GY) wire to any white (W) neutral wire. If 115VAC is not present, CB is bad and must be replaced. If 115VAC is present, check for 115VAC at Comp relay coil

gray (GY) wire to any white (W) neutral wire. If 115VAC is present, and Comp is not on, check for 115VAC at Comp relay orange (O) wire to Comp relay red (R) wire. If 115VAC

is present, Comp relay is bad and must be replaced. If 115VAC is not present, check for 115VAC at Comp relay red (R) wire to any white (W) neutral wire. If 115VAC is not present, electronic unit is bad and must be replaced. If 115VAC is present, and Comp

is not on, remove the electronic unit to access Comp terminals. Next, check for 80VAC from each Comp terminal to ground. If 80VAC is not present, electronic unit is bad and

must be replaced. If 80VAC is present, check Comp continuity.

VSC COMPRESSOR MODULE

The compressor adjusts its speed in steps to any in-creasing or decreasing cooling demand, within the minimum and maximum speed limits. If the thermo-stat switches the compressor "ON": After a 60-minute running time, the speed will increase stepwise every 15 minutes, depending on the latest speed used, until the maximum is reached. If the thermostat switches the compressor "OFF": After each "ON", the compressor either restarts with lower speed steps than the recently used, until the minimum is reached, or increases its speed stepwise, after a new 60-minute running time.

COMPRESSOR OPERATION

CAUTION! Do not attempt to repair the compressor electronic unit

Page 6: PROFESSIONAL SERIES · LED 4 (Comp) & LED 5 (ConFM) are ON CTh warms to 3 above the set point, EvapFM continues, Comp. and ConFM energize 2.5 min. Comp. minimum run timer starts DEFROST

-SSE CONTROL BOARD

RIBBON CABLE

DISPLAY BOARD

SSE CONTROL CIRCUIT

Page 7: PROFESSIONAL SERIES · LED 4 (Comp) & LED 5 (ConFM) are ON CTh warms to 3 above the set point, EvapFM continues, Comp. and ConFM energize 2.5 min. Comp. minimum run timer starts DEFROST

Professional

CLICK LABEL FOR PRINTABLE VERSION

Page 8: PROFESSIONAL SERIES · LED 4 (Comp) & LED 5 (ConFM) are ON CTh warms to 3 above the set point, EvapFM continues, Comp. and ConFM energize 2.5 min. Comp. minimum run timer starts DEFROST

SSE SERIES CONTROLLER ADJUSTMENT GUARDED ACCESS MENU

•Press the “UP” and “DOWN” keys together for three seconds.

Press both buttons at the

same time

Page 9: PROFESSIONAL SERIES · LED 4 (Comp) & LED 5 (ConFM) are ON CTh warms to 3 above the set point, EvapFM continues, Comp. and ConFM energize 2.5 min. Comp. minimum run timer starts DEFROST

SSE SERIES CONTROLLER ADJUSTMENT GUARDED ACCESS MENU

•1st Adjustment: •Temperature Setpoint Average cabinet temperature

•2nd Adjustment: •Defrost Frequency

Refrigerator: Automatic defrost “df X” has no effect Freezer: Ex. “df” 4 = 4 defrost per day

•3rd Adjustment: •Units of display:

F = Fahrenheit C = Celsius

Page 10: PROFESSIONAL SERIES · LED 4 (Comp) & LED 5 (ConFM) are ON CTh warms to 3 above the set point, EvapFM continues, Comp. and ConFM energize 2.5 min. Comp. minimum run timer starts DEFROST

TEMPGUARD™ (SSE) DISPLAY CODES

Alarm display~ Alternates between code and box temp.

• E2- Low cabinet temperature ~ 4 Beeps 8° F Below set point for more than 1 hour

• E3- Freezer defrost over 1 hour ~ 5 Beeps

• E4- High pressure 3 x in 1 hour ~ 6 Beeps (5 x cuts off) • E6 - E7 High voltage (8 Beeps) and Low voltage (9 Beeps)

• E8 - E9 Defrost or Cabinet temperature sensor failure (Continuous buzzer)

• E10 Communication error (Dual Temp only)

• dEF Unit in defrost or recovery

•CF~ Clean filter ~ 1 Beep. •door~ Displays when open~ 2 Beeps if open>3 Min

• E1- High Cabinet temperature ~ 3 Beeps 25° F above set point for more than 4 hours

Page 11: PROFESSIONAL SERIES · LED 4 (Comp) & LED 5 (ConFM) are ON CTh warms to 3 above the set point, EvapFM continues, Comp. and ConFM energize 2.5 min. Comp. minimum run timer starts DEFROST

PROFESSIONAL – SSE REFRIGERATOR

Page 12: PROFESSIONAL SERIES · LED 4 (Comp) & LED 5 (ConFM) are ON CTh warms to 3 above the set point, EvapFM continues, Comp. and ConFM energize 2.5 min. Comp. minimum run timer starts DEFROST

SWITCH ON LED 3 is OFF (EvapFM ON), 2.5 min.

Compressor delay timer starts, Cabinet temp. appears on display after the CB revision # (r##)

COOL DOWN LED 4 (Comp) & 5 (ConFM) are ON

EvapFM continues, the 2.5 min. Comp. minimum run timer starts

COOL DOWN ACHIEVED LED 3 is OFF (EvapFM ON)

CB monitors the CTh when it cools to 3◦ below set point the Comp. and ConFM de-energize

EvapFM Continues and the 2.5 min. Comp. minimum off timer starts

COOL DOWN RESTART LED 4 (Comp) & LED 5 (ConFM) are ON

CTh warms to 3◦ above the set point, EvapFM continues, Comp. and ConFM energize 2.5 min.

Comp. minimum run timer starts

DEFROST

INIATION LED 5 (ConFM) is ON LED 3 is OFF

(EvapFM ON), when the DTh cools to 13◦ the 20 min. minimum off cycle defrost starts. Cabinete temperature displayed on DB, EvapFM continues ConFM continues or

energizes

DEFROST TERMINATION LED 4 (Comp) & LED 5 (CondFM) ON

When the DTh warms to 40◦ EvapFM and ConFM continue, the 2.5 minute Comp delay

timer terminates and the Comp. energizes

PROFESSIONAL – SSE REFRIGERATOR

Page 13: PROFESSIONAL SERIES · LED 4 (Comp) & LED 5 (ConFM) are ON CTh warms to 3 above the set point, EvapFM continues, Comp. and ConFM energize 2.5 min. Comp. minimum run timer starts DEFROST

PROFESSIONAL – SSE Freezer

Page 14: PROFESSIONAL SERIES · LED 4 (Comp) & LED 5 (ConFM) are ON CTh warms to 3 above the set point, EvapFM continues, Comp. and ConFM energize 2.5 min. Comp. minimum run timer starts DEFROST

SWITCH ON P5 & Earlier LED 3 ON (evap. Fan off) 2.5 min. comp. delay timer starts , cabinet

temperature appears on display board

P6 and later LED 3 off (evap. Fan ON) 2.5 min. comp. delay timer starts , cabinet temperature appears on display board

NOTE: Evap. Fan motor operation LED 3 OFF fan ON, LED 3 On fan

OFF. P5 and earlier S3 dip switch 7 or 8 (OFF) = EvapFM cycles on and

off with compressor, as well as with door.

P6 and later S3 dip switch 7 or 8 (ON) =EvapFM on continuous

from start-up, only shuts off when door opens

COOL DOWN P5 and earlier LED 4(comp) & 5 (ConFM) are ON, LED 3 is OFF

(EvapFM) ON

P6 and later LED 4&5 (comp., ConFM) ON , LED 3 OFF (EvapFM) ON continuous

COOL DOWN ACHIEVED P5 and earlier LED 3 ON

(EvapFM OFF) CB monitors CTH when box gets 3◦ below set point (Comp, ConFM, &

EvapFM de-energize )

P6 and later LED3 OFF (EvapFM ON) CB monitors

CTH when box gets 3◦ below set point EvapFM continues,

Comp and CondFM de-energize

COOL DOWN RESTART P5 and earlier LED 4(Comp)

and 5 (ConFM) are ON, LED3 OFF (EvapFM ON) CTh

warms to 3◦ above setpoint 2.5 min. Comp delay timer

terminates (Comp., ConFM, and EvapFM energize)

P6 and later LED 4(Comp)

and 5 (ConFM) are ON, LED3 OFF (EvapFM ON) CTh

warms to 3◦ above setpoint 2.5 min. Comp delay timer

terminates (Comp., ConFM, and EvapFM continues and

Comp . and ConFM energize

Time or manual-initiated Defrost (The time initiated def. is factory set 6

times per day or every 4 hours)

P5 and earlier LED 1 (DH) & 3 are ON (EvapFM OFF) DT terminates or manual

defrost initiated, 20 minute minimum timer starts, 1 hour max timer starts and “def” is

displayed

P6 and later LED 1 (DH,DrH,DcTH, and CordH) and 3 are ON (EvapFM OFF) DT terminates or manual defrost initiated, 20 minute minimum timer starts, 1 hour max

timer starts and “def” is displayed

DEFROST RECOVERY (DRIP TIME) P5 and earlier LED 4(Comp) & 5 (ConFM) are ON

LED 3 is OFF (EvapFM is ON) DTh warms to 100◦ or the 1 hr. timer terminates. DH de-energizes 5-min. later

Comp & ConFM energizes EvapFM continues

P6 & later LED 3 (EvapFM OFF), 4 (Comp), & 5 (ConFM) are ON, DTH warms to 100◦ or 1 hr. timer

terminates DH de-energizes 5-min. later Comp. & ConFM energize

When the DTh cools to 70◦ or lower the EvapFM

energizes.

DEFROST COMPLEATION LED 4(Comp) & 5 (ConFM) are ON , LED 3 (EvapFM is OFF) when the CTh reads 15◦ above the set point or less

Cabinet temp. will now be displayed

PROFESSIONAL – SSE Freezer

Page 15: PROFESSIONAL SERIES · LED 4 (Comp) & LED 5 (ConFM) are ON CTh warms to 3 above the set point, EvapFM continues, Comp. and ConFM energize 2.5 min. Comp. minimum run timer starts DEFROST

We hope that this gives you a good understanding of the operation for the Professional series units. If you

have any questions concerning this or any other technical information please send e-mail to

[email protected] or call the Technical Support Department at 1-800-233-1940.