PROFESSIONAL SERIES · LED 4 (Comp) & LED 5 (ConFM) are ON CTh warms to 3 above the set point,...
Transcript of PROFESSIONAL SERIES · LED 4 (Comp) & LED 5 (ConFM) are ON CTh warms to 3 above the set point,...
PROFESSIONAL SERIES
PROFESSIONAL - SSE
PROFESSIONAL - SSE
PROFESSIONAL - SSE
Stainless steel interior and exterior (with galvanized back and bottom) Innovative variable speed compressor with “adaptive control” technology Energy efficient thermostatic expansion valve, self contained refrigeration system Two years parts and labor warranty
Comp Circuit Diagnosis: If Comp does not start, check for 115VAC at K1 connector pin #10 gray (GY) wire to any white (W) neutral wire. If 115VAC is not present, CB is bad and must be replaced. If 115VAC is present, check for 115VAC at Comp relay coil
gray (GY) wire to any white (W) neutral wire. If 115VAC is present, and Comp is not on, check for 115VAC at Comp relay orange (O) wire to Comp relay red (R) wire. If 115VAC
is present, Comp relay is bad and must be replaced. If 115VAC is not present, check for 115VAC at Comp relay red (R) wire to any white (W) neutral wire. If 115VAC is not present, electronic unit is bad and must be replaced. If 115VAC is present, and Comp
is not on, remove the electronic unit to access Comp terminals. Next, check for 80VAC from each Comp terminal to ground. If 80VAC is not present, electronic unit is bad and
must be replaced. If 80VAC is present, check Comp continuity.
VSC COMPRESSOR MODULE
The compressor adjusts its speed in steps to any in-creasing or decreasing cooling demand, within the minimum and maximum speed limits. If the thermo-stat switches the compressor "ON": After a 60-minute running time, the speed will increase stepwise every 15 minutes, depending on the latest speed used, until the maximum is reached. If the thermostat switches the compressor "OFF": After each "ON", the compressor either restarts with lower speed steps than the recently used, until the minimum is reached, or increases its speed stepwise, after a new 60-minute running time.
COMPRESSOR OPERATION
CAUTION! Do not attempt to repair the compressor electronic unit
-SSE CONTROL BOARD
RIBBON CABLE
DISPLAY BOARD
SSE CONTROL CIRCUIT
Professional
CLICK LABEL FOR PRINTABLE VERSION
SSE SERIES CONTROLLER ADJUSTMENT GUARDED ACCESS MENU
•Press the “UP” and “DOWN” keys together for three seconds.
Press both buttons at the
same time
SSE SERIES CONTROLLER ADJUSTMENT GUARDED ACCESS MENU
•1st Adjustment: •Temperature Setpoint Average cabinet temperature
•2nd Adjustment: •Defrost Frequency
Refrigerator: Automatic defrost “df X” has no effect Freezer: Ex. “df” 4 = 4 defrost per day
•3rd Adjustment: •Units of display:
F = Fahrenheit C = Celsius
TEMPGUARD™ (SSE) DISPLAY CODES
Alarm display~ Alternates between code and box temp.
• E2- Low cabinet temperature ~ 4 Beeps 8° F Below set point for more than 1 hour
• E3- Freezer defrost over 1 hour ~ 5 Beeps
• E4- High pressure 3 x in 1 hour ~ 6 Beeps (5 x cuts off) • E6 - E7 High voltage (8 Beeps) and Low voltage (9 Beeps)
• E8 - E9 Defrost or Cabinet temperature sensor failure (Continuous buzzer)
• E10 Communication error (Dual Temp only)
• dEF Unit in defrost or recovery
•CF~ Clean filter ~ 1 Beep. •door~ Displays when open~ 2 Beeps if open>3 Min
• E1- High Cabinet temperature ~ 3 Beeps 25° F above set point for more than 4 hours
PROFESSIONAL – SSE REFRIGERATOR
SWITCH ON LED 3 is OFF (EvapFM ON), 2.5 min.
Compressor delay timer starts, Cabinet temp. appears on display after the CB revision # (r##)
COOL DOWN LED 4 (Comp) & 5 (ConFM) are ON
EvapFM continues, the 2.5 min. Comp. minimum run timer starts
COOL DOWN ACHIEVED LED 3 is OFF (EvapFM ON)
CB monitors the CTh when it cools to 3◦ below set point the Comp. and ConFM de-energize
EvapFM Continues and the 2.5 min. Comp. minimum off timer starts
COOL DOWN RESTART LED 4 (Comp) & LED 5 (ConFM) are ON
CTh warms to 3◦ above the set point, EvapFM continues, Comp. and ConFM energize 2.5 min.
Comp. minimum run timer starts
DEFROST
INIATION LED 5 (ConFM) is ON LED 3 is OFF
(EvapFM ON), when the DTh cools to 13◦ the 20 min. minimum off cycle defrost starts. Cabinete temperature displayed on DB, EvapFM continues ConFM continues or
energizes
DEFROST TERMINATION LED 4 (Comp) & LED 5 (CondFM) ON
When the DTh warms to 40◦ EvapFM and ConFM continue, the 2.5 minute Comp delay
timer terminates and the Comp. energizes
PROFESSIONAL – SSE REFRIGERATOR
PROFESSIONAL – SSE Freezer
SWITCH ON P5 & Earlier LED 3 ON (evap. Fan off) 2.5 min. comp. delay timer starts , cabinet
temperature appears on display board
P6 and later LED 3 off (evap. Fan ON) 2.5 min. comp. delay timer starts , cabinet temperature appears on display board
NOTE: Evap. Fan motor operation LED 3 OFF fan ON, LED 3 On fan
OFF. P5 and earlier S3 dip switch 7 or 8 (OFF) = EvapFM cycles on and
off with compressor, as well as with door.
P6 and later S3 dip switch 7 or 8 (ON) =EvapFM on continuous
from start-up, only shuts off when door opens
COOL DOWN P5 and earlier LED 4(comp) & 5 (ConFM) are ON, LED 3 is OFF
(EvapFM) ON
P6 and later LED 4&5 (comp., ConFM) ON , LED 3 OFF (EvapFM) ON continuous
COOL DOWN ACHIEVED P5 and earlier LED 3 ON
(EvapFM OFF) CB monitors CTH when box gets 3◦ below set point (Comp, ConFM, &
EvapFM de-energize )
P6 and later LED3 OFF (EvapFM ON) CB monitors
CTH when box gets 3◦ below set point EvapFM continues,
Comp and CondFM de-energize
COOL DOWN RESTART P5 and earlier LED 4(Comp)
and 5 (ConFM) are ON, LED3 OFF (EvapFM ON) CTh
warms to 3◦ above setpoint 2.5 min. Comp delay timer
terminates (Comp., ConFM, and EvapFM energize)
P6 and later LED 4(Comp)
and 5 (ConFM) are ON, LED3 OFF (EvapFM ON) CTh
warms to 3◦ above setpoint 2.5 min. Comp delay timer
terminates (Comp., ConFM, and EvapFM continues and
Comp . and ConFM energize
Time or manual-initiated Defrost (The time initiated def. is factory set 6
times per day or every 4 hours)
P5 and earlier LED 1 (DH) & 3 are ON (EvapFM OFF) DT terminates or manual
defrost initiated, 20 minute minimum timer starts, 1 hour max timer starts and “def” is
displayed
P6 and later LED 1 (DH,DrH,DcTH, and CordH) and 3 are ON (EvapFM OFF) DT terminates or manual defrost initiated, 20 minute minimum timer starts, 1 hour max
timer starts and “def” is displayed
DEFROST RECOVERY (DRIP TIME) P5 and earlier LED 4(Comp) & 5 (ConFM) are ON
LED 3 is OFF (EvapFM is ON) DTh warms to 100◦ or the 1 hr. timer terminates. DH de-energizes 5-min. later
Comp & ConFM energizes EvapFM continues
P6 & later LED 3 (EvapFM OFF), 4 (Comp), & 5 (ConFM) are ON, DTH warms to 100◦ or 1 hr. timer
terminates DH de-energizes 5-min. later Comp. & ConFM energize
When the DTh cools to 70◦ or lower the EvapFM
energizes.
DEFROST COMPLEATION LED 4(Comp) & 5 (ConFM) are ON , LED 3 (EvapFM is OFF) when the CTh reads 15◦ above the set point or less
Cabinet temp. will now be displayed
PROFESSIONAL – SSE Freezer
We hope that this gives you a good understanding of the operation for the Professional series units. If you
have any questions concerning this or any other technical information please send e-mail to
[email protected] or call the Technical Support Department at 1-800-233-1940.