ORP/pH Digital Controller
Rola-Chem Generation II
Digital ControllersReady-to-Mount Systems
1
7/27/2019 Professional Lines ORP/PH Rolachem presentation
http://slidepdf.com/reader/full/professional-lines-orpph-rolachem-presentation 2/31
What is ORP?
• ORP stands for Oxidation Reduction Potential.
• ORP is a measurement to oxidize
contaminants. It is the only practical method
we have to electronically monitor sanitizer
effectiveness.
• ORP and pH sensors allow us to electronically
monitor and control sanitizer residual and pH
automatically.
2
7/27/2019 Professional Lines ORP/PH Rolachem presentation
http://slidepdf.com/reader/full/professional-lines-orpph-rolachem-presentation 3/31
What Affects ORP?
• Pool chemistry:
– Cyanuric acid levels
– pH variations
– Temperature changes
– Total dissolved solids
– Chlorine neutralizer
– Bather loads
– Use of alternative sanitizer
3
7/27/2019 Professional Lines ORP/PH Rolachem presentation
http://slidepdf.com/reader/full/professional-lines-orpph-rolachem-presentation 4/31
Why Use Automation?
• Help ensure bather safety
• Protect pool equipment from damage
•
Minimize costs associated with chemicals,equipment and liability
• Flatten curve of dispensing chemical (manual
feed vs. automated feed)• Reduce need for human contact with chemical
4
7/27/2019 Professional Lines ORP/PH Rolachem presentation
http://slidepdf.com/reader/full/professional-lines-orpph-rolachem-presentation 5/31
Benefits of ORP/pH Controllers
• Continually monitors PH and sanitizer activity
• Constantly adjusts feeding of chemicals
proportional to demand
• Eliminates human error
• Maintains chemical levels 24 hours a day
•
Complies with health departmentchemistry standards
5
7/27/2019 Professional Lines ORP/PH Rolachem presentation
http://slidepdf.com/reader/full/professional-lines-orpph-rolachem-presentation 6/31
Optimize Chemical Usage
• Dispenses chemical only as required, thus
creating significant cost savings
•
Equalizes water chemistry, eliminating PH andsanitizer highs and lows
6
7/27/2019 Professional Lines ORP/PH Rolachem presentation
http://slidepdf.com/reader/full/professional-lines-orpph-rolachem-presentation 7/31
Digital Controllers
7
7/27/2019 Professional Lines ORP/PH Rolachem presentation
http://slidepdf.com/reader/full/professional-lines-orpph-rolachem-presentation 8/31
Digital Controllers
8
7/27/2019 Professional Lines ORP/PH Rolachem presentation
http://slidepdf.com/reader/full/professional-lines-orpph-rolachem-presentation 9/31
Digital Controllers
9
7/27/2019 Professional Lines ORP/PH Rolachem presentation
http://slidepdf.com/reader/full/professional-lines-orpph-rolachem-presentation 10/31
Digital Controllers
10
7/27/2019 Professional Lines ORP/PH Rolachem presentation
http://slidepdf.com/reader/full/professional-lines-orpph-rolachem-presentation 11/31
Ready-to-Mount Systems
11
7/27/2019 Professional Lines ORP/PH Rolachem presentation
http://slidepdf.com/reader/full/professional-lines-orpph-rolachem-presentation 12/31
Ready-to-Mount Systems
12
7/27/2019 Professional Lines ORP/PH Rolachem presentation
http://slidepdf.com/reader/full/professional-lines-orpph-rolachem-presentation 13/31
Ready-to-Mount Systems
13
7/27/2019 Professional Lines ORP/PH Rolachem presentation
http://slidepdf.com/reader/full/professional-lines-orpph-rolachem-presentation 14/31
Ready-to-Mount Systems
14
7/27/2019 Professional Lines ORP/PH Rolachem presentation
http://slidepdf.com/reader/full/professional-lines-orpph-rolachem-presentation 15/31
Liquid System Diagram
15
7/27/2019 Professional Lines ORP/PH Rolachem presentation
http://slidepdf.com/reader/full/professional-lines-orpph-rolachem-presentation 16/31
Erosion System Diagram
16
7/27/2019 Professional Lines ORP/PH Rolachem presentation
http://slidepdf.com/reader/full/professional-lines-orpph-rolachem-presentation 17/31
Ready-to-Mount System Components
• ORP/pH Controller / pH Controller – Flow Cell
– Flow Switch
– ORP Probe – pH Probe
– Flow Cell Valves
– Rola-Chem Chemical Feeders
– All tubing, inlet/injection fittings – All mounted on polypropylene board
17
7/27/2019 Professional Lines ORP/PH Rolachem presentation
http://slidepdf.com/reader/full/professional-lines-orpph-rolachem-presentation 18/31
Quick Start Reference
• Quick Start Reference
– On/Off:
• Press the mode button to turn on
• Note: blue ‘FLOW’ light must illuminate
• Press and hold the mode button to turn off
• “OFF” will be displayed in the window
18
7/27/2019 Professional Lines ORP/PH Rolachem presentation
http://slidepdf.com/reader/full/professional-lines-orpph-rolachem-presentation 19/31
Operation
• To Operate:
– Press and release the mode button until the
“AUTO” LED is lit. Unit will now operate in the
factory preset settings.• Set levels: ORP = 650 mv, pH = 7.4
• Feed times: 0.6 second feed with a 5-minute delay
• Limits: ORP; 900 hi, 100 low, pH = 8.0 hi, 7.0 low
19
7/27/2019 Professional Lines ORP/PH Rolachem presentation
http://slidepdf.com/reader/full/professional-lines-orpph-rolachem-presentation 20/31
Changing Settings
• To change settings: – Note: Press and release the mode button until the desired
ORP or pH LED is lit. Once the settings are changed, theywill remain at those settings until they are changed again.
– Set level: Press the Set Level button until the desired setpoint is reached. Release the button.
– Feed time: Press the Feed Time button until the desiredfeed time is reached. Release the button. The numbers
represent the seconds of feed time (all with 5-minutedelays). Range is 0.6 to 900 seconds (15 minutes). Constantfeed is ‘con.’ Factory setting is 0.6 seconds.
continued
20
7/27/2019 Professional Lines ORP/PH Rolachem presentation
http://slidepdf.com/reader/full/professional-lines-orpph-rolachem-presentation 21/31
Changing Settings, cont.
• Hi alert: Press the Hi Alert button until the desired level is
reached. Release the button.
• Low alert: Press the Low Alert button until the desired level is
reached. Release the button.
21
7/27/2019 Professional Lines ORP/PH Rolachem presentation
http://slidepdf.com/reader/full/professional-lines-orpph-rolachem-presentation 22/31
Manual Feed Settings
• Press and release the mode button to light theLED associated with the desired feeder to bemanually fed — ORP or pH.
• Press the “feed once” button. The desiredfeeder will go through one “set feed” timecycle. There is no manual feed option whenthe unit is in constant feed.
– (Manual feed will not work if cycle time is set at0.6 or ‘cont’)
22
7/27/2019 Professional Lines ORP/PH Rolachem presentation
http://slidepdf.com/reader/full/professional-lines-orpph-rolachem-presentation 23/31
Other Manual Information
• See the appropriate manual sections for:
– Setting the time-out feature
– Calibrating the pH sensor / probe
– Changing dip switches (pH/ORP interlock, feeder
time-out, acid/base and lockout)
23
7/27/2019 Professional Lines ORP/PH Rolachem presentation
http://slidepdf.com/reader/full/professional-lines-orpph-rolachem-presentation 24/31
Specifications
ORP and pH Ranges ORP pH
Display: 0 – 995 mv 6.8 – 8.4
Control: 400 mv – 900 mv
(5 mv increments)
7.0 – 8.0
Factory default: 650 mv 7.4
24
Input power: •120 volts AC, 50/60 HZ, three-wire grounded power cord
•Combined load not to exceed 15 amps
•
GFCI source requiredOutput power: •120 volts AC, 50/60 HZ, ORP and pH -5 amps each (fused)
•Two 3-wire grounded power receptacles
•Terminal strip for hardwire applications (included)
7/27/2019 Professional Lines ORP/PH Rolachem presentation
http://slidepdf.com/reader/full/professional-lines-orpph-rolachem-presentation 25/31
Specifications, cont.
Displays: • ORP and pH — red digital
• Power and flow indicator — blue or green LED
• Alert lights — red LED
• Mode LEDs
• pH mode: green LED• ORP mode: yellow LED
• Auto mode: red LED
• Feed lamps: ORP yellow; pH green
(Note: lamps flash during the feed time and are on constant
during the delay time of the feed cycle)
Operating
temperature:
40° to 120° F
25
7/27/2019 Professional Lines ORP/PH Rolachem presentation
http://slidepdf.com/reader/full/professional-lines-orpph-rolachem-presentation 26/31
Selectable Features / Options
Selectable Features
ORP and pH settings High and low ORP and pH alerts
ORP and pH feed/delay times Manual feed
pH calibration Acid/base feed
Keypad lockout Adjustable time-out
ORP and pH interlock Reset
26
Features and Options
Flow switch input
120/240 vac transformer (supplied by others)
Individually fused outputs
7/27/2019 Professional Lines ORP/PH Rolachem presentation
http://slidepdf.com/reader/full/professional-lines-orpph-rolachem-presentation 27/31
Operation / Startup
• Do not add chemicals until all start-up operationshave been completed.
• Manually adjust the balance of the pool.
• Chemical levels: – pH 7.4 – 7.6
– free chlorine 1.0 – 3.0 ppm (700 mv ORP)
– Alkalinity 80 – 120 ppm
–Cyanuric acid 20 – 30 ppm
– TDS 300 – 2,000 ppm
– Calcium hardness 200 – 400 ppm
27
7/27/2019 Professional Lines ORP/PH Rolachem presentation
http://slidepdf.com/reader/full/professional-lines-orpph-rolachem-presentation 28/31
Operation / pH Settings
• Press and release the controller mode button
until the pH LED is lit.
– Select the desired set level.
– Select feed time cycle.
– Select upper and lower alert levels.
Note: It may take up to 24 hours for the sensors
to acclimate to the system.
28
7/27/2019 Professional Lines ORP/PH Rolachem presentation
http://slidepdf.com/reader/full/professional-lines-orpph-rolachem-presentation 29/31
Operation / ORP Settings
• Press and release the controller mode button
until the ORP LED is lit.
– Use a DPD test kit to measure free chlorine.
– Adjust the ORP set level to desired level.
– Select the desired set level.
– Select feed time cycle.
– Select upper and lower alert levels.
29
7/27/2019 Professional Lines ORP/PH Rolachem presentation
http://slidepdf.com/reader/full/professional-lines-orpph-rolachem-presentation 30/31
Operational Mode
• Press and release the mode button until the
“Auto” LED is lit. Note that this is the
operational mode for the controller. The
controller must be in this mode for thefeeders to maintain the desired parameters.
• Consider recalibrating the system after the
initial 24 hours as the sensors acclimate to thesystem.
30
7/27/2019 Professional Lines ORP/PH Rolachem presentation
http://slidepdf.com/reader/full/professional-lines-orpph-rolachem-presentation 31/31
Operational Mode, cont.
• Notes:
– The ORP is highly dependent on both the pH andthe cyanuric acid levels. Both of these variables
must be kept within acceptable ranges to maintainan acceptable relationship between the ORP andthe ppm of the sanitizer.
– When using the 55400 controller with Rola-Chem
pumps, the pump switch should be in the “on”position — not “timed” or “off.”
31