Product Training: The Basics - Jefferson Electric
Transcript of Product Training: The Basics - Jefferson Electric
Introduction Overview of JEI Transformers
Transformer Basics Low voltage offerings Medium voltage offerings Resources for sales
Jefferson Product Training
Transformer Basics • What is covered:
• Transformer design and construction • Terms and definitions • Single and three-phase configurations • Sizing, specifying
Jefferson Product Training
Transformer Basics
Standard transformers consist of:
Coil (Conductor, windings)
Core (Laminations)
Insulation
Enclosure
C om p o n en ts
C O R E
PR IM A R Y
W IN D IN G
S EC O N D A R Y
W IN D IN G
IN SU LA T IO N
Transformer Basics
Basic Terms to Know Dry Type Transformer A transformer that is cooled by means other than a liquid, usually airflow
kVA Kilovolt ampere or thousand volt ampere. This is how transformers are rated.
Line Voltage Also known as the primary voltage. This is the voltage from the source.
Load Voltage Also know as the secondary voltage. Voltage required to operate the load.
Transformer Basics
Basic Terms to Know Single Phase
Two lines of AC power (Hot & Neutral)
Three Phase Three lines of AC power where each line is 120 degrees out of phase with the other two (A, B & C)
For more terms see the website glossary .
Transformer Basics
Meeting DOE-2016 Standards Jefferson Electric offers a full line of three phase Ventilated Dry Type Transformers designed to meet the highest industry standards for quality, durability, and reliability in the commercial, industrial, and OEM markets. Standards • Meets DOE 2016 standard Part 431, Subpart K for
energy efficiency • Built in accordance with NEMA, ANSI and CSA standards • UL and cUL Listed
Available Enclosures: NEMA 1 NEMA 3R NEMA 4 NEMA 4X NEMA 12 TENV
Transformer Basics
Configuration: Single Phase Many single phase transformers have dual primary and secondary voltages
For example 240 x 480 – 120/240
Primary is 240 or 480 Typically marked H1, H2, H3, H4
Secondary is 120 or 240 or 120 and 240 Typically marked X1, X2, X3, X4
Transformer Basics
Configuration: Three Phase Primary
Most three phase transformers have a single primary voltage in a “Delta” (3-wire) configuration. Typically marked H1, H2, H3
Example voltage configurations
480 – 208Y/120 (delta – wye) 600 – 240 (delta – delta)
Transformer Basics
Configuration: Three Phase Secondary Three phase secondary voltage may be a “Delta,”
3-wire or “Y” (Wye), 4-wire or Star configuration 3-wire = X1, X2, X3 4-wire = X0 (neutral), X1, X2, X3 The secondary can have a three phase voltage
and a single phase voltage
Example voltage configurations 480 – 208Y/120 (delta – wye) 600 – 240 (delta – delta)
Transformer Basics
Configuration: Three Phase Primary
■ Delta ■ Wye
480 V
480 V
480 V
208 V 208 V
120 V
120 V
Neutral
Transformer Basics
Configuration: Three Phase Actual Winding Example – Delta-Wye
H3
X2
X3
H2
H1 Primary
X1 Secondary
X0 Neutral
Transformer Basics
Configuration: Three Phase Secondary
■ Delta with center tap 240 V
120 V
240 V
208 V “high leg”
120 V
240 V
Transformer Basics
Transformer Sizing Transformer size is determined by the kVA rating of the load
(secondary=equipment).
Determine the load voltage
Determine the load current (amps)
Determine whether the load is single phase or three phase
Determine the line voltage
Transformer Basics
Transformer Sizing Transformer size is determined by the kVA of the load
Formulas Single Phase: VOLTS x AMPS = kVA 1000
Three Phase: VOLTS x AMPS x 1.73 = kVA 1000
See Catalog page 4 or website for reference.
Transformer Basics
3-Phase Transformer Sizing Full load currents In amperes (line to line)
kVA 208V 240V 480V 600V
3 8.3 7.2 3.6 2.9 6 16.6 14.4 7.2 5.8 9 25 21.6 10.8 5.8
15 41.6 36.0 18.0 14.4 30 83 72 36 29 45 125 108 54 43 75 208 180 54 43
112.5 312 270 135 108 150 416 360 180 144 225 625 542 271 217 300 830 720 360 290 500 1,390 1,200 600 480 750 2,080 1,800 900 720
Low Voltage Transformers
Overview Specifications Ventilated transformers Encapsulated transformers Options
Jefferson Product Training
Low Voltage Transformers
Single-Phase Three-Phase Encapsulated Ventilated Special Voltages Drive Isolation Non-Linear (K-Factor)
Buck-Boost Industrial Control Lighting Transformers Pool & Spa Autotransformers, Prewired Seismic Totally Enclosed (TENV) ABS
Standard Offerings
Low Voltage Transformers
Standard Transformers Available Ratings
• 50 VA to 2,500 kVA • Up to 600V • UL, cUL, CSA
Modified Standards Specials Contact Applications for a quote
Ventilated Transformers
• For general loads, including lighting, industrial and commercial applications
• Ventilated enclosures provide circulation of external air
• Enclosures are designed for air flow while protecting contents
• Large connection compartment make wiring and installation easy
Ventilated Transformers
Single Phase • 15 through 1,650 kVA • 60 Hertz • Aluminum Windings • 150°C temperature rise • NEMA 3R • Meets DOE-2016 and C802
standards for energy efficiency • Floor-mount design • Wall-mount Brackets available up
to 75 kVA
Ventilated Transformers
Three Phase • 15 through 2,500 kVA • 60 Hertz • Aluminum Windings • 150°C temperature rise • NEMA 3R • Meets DOE-2016 and C802
standards for energy efficiency • Floor-mount design • Wall-mount brackets available
up to 75 kVA
Ventilated Transformers
Options • Low Temperature Rise ( 80 & 115°C Rise) • Copper Windings • Electrostatic Shield • CE Mark • 50 Hertz • Special Voltages • Auto Transformers
• NEMA 1 enclosures • Floor-mount design • Special Paint
Ventilated Transformers
Efficiency: DOE-2016 vs TP1 • DOE more efficient than TP-1 • 75 kVA is 98.6% vs. 98% • TP1 required in 2007 • DOE required in 2016
• Meets DOE2016 standard
Part 431, Subpart K for energy efficiency
• All models now to this standard
• Enclosures with built-in weather shields (NEMA 3R)
Ventilated Transformers
Canadian High Efficiency • TP1 = CSA 802.2 • New NRCAN 2019 efficiencies
meet CSA 802.2.14 = DOE 2106 • Required to sell in Canada as of
April 2019 • “CSA Verified” required
Ventilated Transformers
K-Factor Rated • This is a rating devised by Underwriters
Laboratories to provide a uniform standard for transformers designed to handle non-linear loads, including solid state devices such as ballast computers and communication equipment
• K4, K13, K20 • 15 to 1,000 kVA • Electrostatic shields • 200% neutral • See Catalog page 3-2 to calculate
K-FACTOR TYPE OF LOAD
K-1 Resistance heating Incandescent lighting Motors Transformers • Control • Distribution
K-4 Welders Induction heaters HID lighting Fluorescent lighting Solid state controls
K-13 Telecommunications equipment Branch circuits in classrooms and healthcare facilities
K-20 Mainframe computers Variable speed drives Branch circuits with exclusive loads of data processing equipment
Ventilated Transformers
Drive Isolation Transformers For industrial and commercial applications with SCR-controlled adjustable speed motor drives and AC adjustable frequency or DC drives 3 to 990 kVA Primary Voltages
• 230, 460 or 575V Secondary Voltages
• 230Y/133V or 460Y/266V Specials
• 6, 12, 18 pulse • Reactors, Chokes, Ripple Filters • Contact Applications for Specials
Ventilated Transformers
Totally Enclosed Non-Ventilated (TENV) Applications: • Textile plants • Chemical plants • Foundries • Cement plants • Food packaging • Paper manufacturing • Wash down areas • Automotive
15 to 500 kVA NEMA 3R enclosure NEMA 4/4X (stainless) or other NEMA
enclosures optional Windings — Copper or Aluminum Temperature Rise — 150, 115, 80°C 60 Hz standard, 50 Hz optional Electrostatic Shields optional UL/cUL CE Mark, ABS and Seismic
Qualified optional
Encapsulated Transformers
For use where locations have environmental challenges – gases, dust, liquids
Windings are encapsulated with electrical grade resin
Units may be banked for 3-Phase operations
Encapsulated Transformers
Three Phase • 3 thru 75 kVA • Lifting hooks on Wall Mount
Enclosures • 30 kVA and larger are Floor Mount • NEMA 3R • Optional stainless steel
enclosures
Single Phase • 50 VA thru 25 kVA • Wall-mount design • NEMA 3R standard
Encapsulated Transformers
Pool and Spa Lighting Transformers 100 through 1000 watts
Single-Phase Encapsulated
Primary - 120 Volts
Secondary - 12/13/14 Volts
Resettable circuit breaker
60 Hertz operation
NEMA 3R rated
Encapsulated Transformers
Pre-Wired Autotransformers Autotransformers • Lower cost
• Smaller footprint
Pre-wired • Easier to install
Panel boosters • Adjust voltage at panel
• 200 Amp to 800 Amp
Buck-Boost Transformers
Encapsulated transformers designed for correcting voltage drop, landscape lighting, low voltage lighting, international voltage adaptation and motor applications
Note: NOT to compensate for fluctuating line voltages
Buck-Boost Transformers
Low voltage applications 50VA to 10 kVA Single phase Isolation transformer
• 120 x 240V— 12/24V • 120 x 240V— 16/32V • 240 x 480V— 24/48V
Windings —Aluminum/Copper Enclosures — NEMA 3R 60 Hz standard Wall mounted with slotted
mounting holes
Buck-Boost Applications Single- or three-phase encapsulated
autotransformer • Open Delta uses two single phase
transformers • Wye uses three single phase
transformers Economical for stepping voltages up or
down Solve over/under voltage problems
efficiently
Industrial Control Transformers
For commercial and industrial control applications including
• Control panels
• Conveyor systems
• Machine tool equipment
• Pump systems
• Commercial AC applications
Core and coil design
Industrial Control Transformers
50 VA to 5,000 VA
UL and cUL listed
50/60 Hertz operation
Primary and Secondary Fuse Clips
Finger safe covers for terminals and fuse clips
Units 350VA and smaller come with “finger-safe” terminals. No need to buy terminal covers
Covers available for fuse clips
Boxes UPS shippable up to 2000VA
Most come with secondary fuse clips (-300 models)
Optional Primary fuse blocks
Common units stocked at warehouses
Custom designs available
Class I Division 2
Class I, Div 2 transformers are encapsulated units rated for use in Group A, B, C, D hazardous locations.
Environments where normally confined volatile and flammable liquids and gases are used but may be present due to accidental rupture or breakdown of their systems.
Applications: • Hazardous locations • Chemical plants • Refineries • Petrochemical • other industrial facilities
Specifications: • Single phase, 1-25kVA • Three phase, 3-75kVA • 600V max • Taps optional
Low Voltage Transformer Options
CE Mark Certified Product Meets European requirements
Ventilated product
Single phase
Three phase
Special voltages
Low Voltage Transformer Options
Seismic Qualified Compliant with International Building Code (2015
IBC) and California Building Code (2016 CBC) OSHPD Certified (OSP-0109-10) Healthcare and Emergency response locations
• Hospitals • Fire Stations • Police stations
Seismic Ratings • z/h = 1.00 ; Ip = 1.5 • Encapsulated SDS=2.00g
Low Voltage Transformer Options
ABS (American Bureau of Shipping) Applications: • Commercial ships • Military ships • Offshore and near
shore oil rigs • Tankers • Other marine applications • Petro-Chemical applications
1 to 1,000 kVA Single or Three phase Encapsulated or ventilated Low voltage (<600 volts) Dry-Type 60 Hz standard, optional 50 Hz 140°C Temperature rise, optionally 115, 80 Standard Taps NEMA 3R painted enclosure, optional
stainless steel Ventilated units NEMA TP-1 compliant Copper or Aluminum windings Optional electrostatic shielding Optional anti-condensation heaters
Medium Voltage Transformers
Overview Standard specifications Optional features Markets/applications
Jefferson Product Training
Medium Voltage Transformers
Power Transformers Economic and environmentally
friendly alternative to liquid filled transformers for industrial facilities and large commercial applications
For indoor and outdoor installations
Medium Voltage Transformers
Power Transformers Product Range Size: up to 10MVA KV Class: up to 34.5KV BIL Capability: 150KV
Sweet Spot • 300KVA – 5MVA • 5KV-25KV Class • 30-125KV BIL
Standard & Custom Designs UL/CSA up to 10mVA
Medium Voltage Transformers
Standard Specifications Copper or Aluminum Windings 150°C Rise / 220°C Insulation 60 Hz Single or Three Phase Taps: 2 +/- 2 ½ % VPI Processing Open Core & Coil or NEMA 1 Enclosure 12/18 month warranty
Medium Voltage Transformers
Optional Features/Specifications
115°C & 80°C Temp Rise 50 Hz, 50/60Hz NEMA 3R Enclosure Special Impedance Electrostatic Shielding Lightning Arrestors Fans Space Heaters Ground Bus
Digital Temperature Monitor Thermocouples Kirk Key Interlocks Filters NGR Ground Fault Relay Air Terminal Chambers Extended Warranty
Medium Voltage Transformers
New Product Introduction
MV Transformer/Load Break Switch Assembly 5KV & 15KV
• 600 & 1200 Continuous Amps
Fused or Non-Fused NEMA 1 & 3R Left or Right Side Orientation Transformer & Switch arrive at project
together • Without impacting the lead time
Medium Voltage Transformers
Markets/ Applications • Oil & Gas • Data Centers • Mining • Hydropower • Steel • Commercial
Sales Resources
Overview Catalog Website overview Quote Tool brief look Contacts See individual modules for more information
Jefferson Product Training
Sales Resources
Catalog Product Type Sections Quick specifier on page 4
• kVA calculator • Determining load and line voltage • Full load currents (in amperes)
Online only sections • Section 14-References • Section 15-Wiring Diagrams,
Enclosure Information and Shipping Dimensions
Sales Resources
Catalog Product Type Sections Sections in catalog are divided by transformer type First page contains broad
description of type Specifications Selling features Standards Options and accessories Approvals
Sales Resources
Catalog – other sections In Print
Power Quality
Digital only References Technical information, installation assistance Appendix Enclosure drawings Wiring Connections Shipping Dimensions
Sales Resources
Website General information About the company “Contact Us” links, forms Product information • Catalog information and
downloads • “Find a Product” spec
sheet creation • Log in for reps
Find a Product
Log in
Contact Us
Sales Resources
Website Product Type Sections Sections in our catalog are divided by transformer type First page contains broad
description of type Specifications Selling features Standards Options and accessories Approvals
Sales Resources
Product Specifier The best way to determine
a product number Contains no pricing
information Uses the same database
as our Quote Tool Open to everyone
More training in separate
module
Search by Catalog number or input specs
Output is a detailed specification sheet