Transcript of Product Note Kabeldon CD 145 2013
Product noteKabeldon dry plug-in cable termination for GIS and TRFCD 145
CD 145 contains of two main parts as follows.
CD 145: Plug-in termination kit including
1. Plug-in connector
Aluminium or copper mechanical connector. Including two
contact springs made from silver-plated copper.
2. Locking half
Made of aluminium.
3. Stress relief cone
The stress relief cone is made from EPDM rubber and
designed for geometric field control. It is premolded
which enables routine testing.
4. Pre-loaded spring assembly
Made from aluminium.
5. Box body
Made from aluminium alloy.
6. Earth clamp
The earth clamp is made from tin-plated brass and
clamped with stainless steel bolts. The earth clamp has
a nominal cross section of 1050 mm².
7. Cable clamp
Made from aluminium alloy. The clamp secures the
cable in a fixed position. Bitumized paper is used for
a snug fit under the cable clamp.
Dry plug-in cable termination 145 kV suitable as a fi xed connection point in a gas-insulated switchgear or an oil-fi lled transformer box. Designed to meet the requirements of internationally accepted standards.
Main technical data
Electrical data, IEC standard 60840 Voltage kV
Highest voltage for equipment, Um
145
Rated voltage, U 132–138
Value of U0 for determination of test voltage 76
Heating cycle voltage test, 2U0
152
Partial discharges test <5pC, 1.5U0
114
Lighting impulse voltage test, BIL + 650
Power frequency voltage test, 2.5U0
190
CDI 145: Insulator kit including
8. Top fitting
Top fitting is made from silver-plated aluminium.
9. Insulator
Insulator is made from epxoy with an integrated screen
interruption.
10. Pressure ring
Made of stainless steel with a packing made of paper
laminate.
8
10
1
9
5
6
7
2
4
3
Do
cu
men
t ID
: 7
AB
A1
02
35
7
For additional information, please visit:
www.abb.com/cableaccessories
© Copyright 2013 ABB. All rights reserved.
Specifi cations subject to change without notice.
Common specifications
Classifications HV GIS/TRF
Rated frequency, Hz 50/60
Max inclination, degrees No limitations
Dimensions according to IEC 62271-209 (GIS)
Routine test
Epoxy insulator according to EN 50089
Dimensional and electric test is perfomed on each stress relief cone
Visual inspection is performed on all parts of the termination
Accessories for TRF Designation
Corona shield CST 170
Contact bolt for TRF CBT 84-170
Optional equipment Designation
Insulator protective cover IPC
Installation tool RKM 145
Peeling and stripping tool SH 80, SH 130
Spare peeling blade FK-SH 80, FK-SH 130
Spare stripping blade IK-SH 80, IK-SH 130
Slot knife SLK-SH 80, SLK-SH 130
Base plate for slot knife and stripping blade BSL-SH 130
Earthing kit JSA, SCK
Type testing in a high voltage laboratory.
Cable range
Prepared insulation Ø (mm) 44–96
Conductor Cu/Al (mm²) 300–2000
Oversheath Ø (mm) 150 CUW
Oversheath Ø (mm) 130 PAL, MET
Storage
When stored in original, unopened packaging at
temperatures in the range of -30°C to 30°C:
− The stress relief cone has a shelf life of ten years
from date of manufacture.
− Tapes and grease have a shelf life of five years.
− Metal hardwares have no shelf life limit.
Ø 14 (12x)
Ø 320
Ø 283
Ø 345
Insulator mounting ring for CD 145.
470 mm470 mm
1149 mm1149 mm
CDI 145, insulator kit.
CD 145, termination kit.
Dimensions in mm
CBT
Contact bolt for installation
in transformer.
CST 170
Corona shield for
installation in transformer.
Packaging Gross weight Dimensions
kg mm
CD 145 33 800 x 400 x 450
CDI 145 25 700 x 340 x 340
Insulator mounting ring 6 340 x 340 x 60
Dimensions and weights may vary as products occasionally
have different packaging.