Product Note Kabeldon CD 145 2013

2
Product note Kabeldon dry plug-in cable termination for GIS and TRF CD 145 CD 145 contains of two main parts as follows. CD 145: Plug-in termination kit including 1. Plug-in connector Aluminium or copper mechanical connector. Including two contact springs made from silver-plated copper. 2. Locking half Made of aluminium. 3. Stress relief cone The stress relief cone is made from EPDM rubber and designed for geometric field control. It is premolded which enables routine testing. 4. Pre-loaded spring assembly Made from aluminium. 5. Box body Made from aluminium alloy. 6. Earth clamp The earth clamp is made from tin-plated brass and clamped with stainless steel bolts. The earth clamp has a nominal cross section of 1050 mm². 7. Cable clamp Made from aluminium alloy. The clamp secures the cable in a fixed position. Bitumized paper is used for a snug fit under the cable clamp. Dry plug-in cable termination 145 kV suitable as a xed connection point in a gas-insulated switchgear or an oil-lled transformer box. Designed to meet the requirements of internationally accepted standards. Main technical data Electrical data, IEC standard 60840 Voltage kV Highest voltage for equipment, U m 145 Rated voltage, U 132–138 Value of U 0 for determination of test voltage 76 Heating cycle voltage test, 2U 0 152 Partial discharges test <5pC, 1.5U 0 114 Lighting impulse voltage test, BIL + 650 Power frequency voltage test, 2.5U 0 190 CDI 145: Insulator kit including 8. Top fitting Top fitting is made from silver-plated aluminium. 9. Insulator Insulator is made from epxoy with an integrated screen interruption. 10. Pressure ring Made of stainless steel with a packing made of paper laminate. 8 10 1 9 5 6 7 2 4 3

description

GIS cable termination document

Transcript of Product Note Kabeldon CD 145 2013

Page 1: Product Note Kabeldon CD 145 2013

Product noteKabeldon dry plug-in cable termination for GIS and TRFCD 145

CD 145 contains of two main parts as follows.

CD 145: Plug-in termination kit including

1. Plug-in connector

Aluminium or copper mechanical connector. Including two

contact springs made from silver-plated copper.

2. Locking half

Made of aluminium.

3. Stress relief cone

The stress relief cone is made from EPDM rubber and

designed for geometric field control. It is premolded

which enables routine testing.

4. Pre-loaded spring assembly

Made from aluminium.

5. Box body

Made from aluminium alloy.

6. Earth clamp

The earth clamp is made from tin-plated brass and

clamped with stainless steel bolts. The earth clamp has

a nominal cross section of 1050 mm².

7. Cable clamp

Made from aluminium alloy. The clamp secures the

cable in a fixed position. Bitumized paper is used for

a snug fit under the cable clamp.

Dry plug-in cable termination 145 kV suitable as a fi xed connection point in a gas-insulated switchgear or an oil-fi lled transformer box. Designed to meet the requirements of internationally accepted standards.

Main technical data

Electrical data, IEC standard 60840 Voltage kV

Highest voltage for equipment, Um

145

Rated voltage, U 132–138

Value of U0 for determination of test voltage 76

Heating cycle voltage test, 2U0

152

Partial discharges test <5pC, 1.5U0

114

Lighting impulse voltage test, BIL + 650

Power frequency voltage test, 2.5U0

190

CDI 145: Insulator kit including

8. Top fitting

Top fitting is made from silver-plated aluminium.

9. Insulator

Insulator is made from epxoy with an integrated screen

interruption.

10. Pressure ring

Made of stainless steel with a packing made of paper

laminate.

8

10

1

9

5

6

7

2

4

3

Page 2: Product Note Kabeldon CD 145 2013

Do

cu

men

t ID

: 7

AB

A1

02

35

7

For additional information, please visit:

www.abb.com/cableaccessories

© Copyright 2013 ABB. All rights reserved.

Specifi cations subject to change without notice.

Common specifications

Classifications HV GIS/TRF

Rated frequency, Hz 50/60

Max inclination, degrees No limitations

Dimensions according to IEC 62271-209 (GIS)

Routine test

Epoxy insulator according to EN 50089

Dimensional and electric test is perfomed on each stress relief cone

Visual inspection is performed on all parts of the termination

Accessories for TRF Designation

Corona shield CST 170

Contact bolt for TRF CBT 84-170

Optional equipment Designation

Insulator protective cover IPC

Installation tool RKM 145

Peeling and stripping tool SH 80, SH 130

Spare peeling blade FK-SH 80, FK-SH 130

Spare stripping blade IK-SH 80, IK-SH 130

Slot knife SLK-SH 80, SLK-SH 130

Base plate for slot knife and stripping blade BSL-SH 130

Earthing kit JSA, SCK

Type testing in a high voltage laboratory.

Cable range

Prepared insulation Ø (mm) 44–96

Conductor Cu/Al (mm²) 300–2000

Oversheath Ø (mm) 150 CUW

Oversheath Ø (mm) 130 PAL, MET

Storage

When stored in original, unopened packaging at

temperatures in the range of -30°C to 30°C:

− The stress relief cone has a shelf life of ten years

from date of manufacture.

− Tapes and grease have a shelf life of five years.

− Metal hardwares have no shelf life limit.

Ø 14 (12x)

Ø 320

Ø 283

Ø 345

Insulator mounting ring for CD 145.

470 mm470 mm

1149 mm1149 mm

CDI 145, insulator kit.

CD 145, termination kit.

Dimensions in mm

CBT

Contact bolt for installation

in transformer.

CST 170

Corona shield for

installation in transformer.

Packaging Gross weight Dimensions

kg mm

CD 145 33 800 x 400 x 450

CDI 145 25 700 x 340 x 340

Insulator mounting ring 6 340 x 340 x 60

Dimensions and weights may vary as products occasionally

have different packaging.