PRODUCT MANUAL type 457 - zpanp.eu · multi-hole orifices pursuant to ČSN EN ISO 5167-2:2003,...

34
TP – 304337 1 / 34 Heat and cold meter, evaluation unit of gas flow INMAT 57 type 457 APPLICATION - Measurement of flow and heat transferred by water steam - Measurement of flow and heat in condensate - Measurement of flow and heat transferred by water - Measurement of cold - of flow of fluids - of flow of gases - As independent meter for building closed measuring units and for building extensive distributed systems - Compact design and Ingress Protection IP 65 enables the use of the evaluation unit in the most demanding conditions - It is not designed for operation in explosive environment In certified design as a rated meter according to Act No. 505/1990 Coll., on metrology For measurement of flow and heat transferred by water steam with direct, indirect and replacement method, measurement of heat in condensate, measurement of flow and heat transferred by water, for measurement of cold and also for measurement of flow of gases in the function of the evaluation unit of the flown quantity of gas o It complies with MPM 18-95 (Directive for permissible methods of measurement of heat in water steam and in condensate in business contact) o For billing purposes, it is necessary to use the measuring path for the measurement of flow that corresponds to the applicable standards or technical conditions of the used flow meter o During the evaluation of flow, it uses the calculations for the following primary items: centric orifices pursuant to ČSN EN ISO 5167-2:2003, discharge nozzles pursuant to ČSN EN ISO 5167-3:2003, Venturi tubes pursuant to ČSN EN ISO 5167-4:2003, multi-hole orifices pursuant to ČSN EN ISO 5167- 2:2003, orifices with conical input pursuant to ISO TR 15377: 2007, quarter-circle orifices pursuant to ISO TR 15377: 2007, segment orifices pursuant to ČSN 25 7711, Annubary Rosemount 485 and general throttling unit, volume flow meters, mass flow meters, water meters and gas meters o It evaluates flow from 5 % of the range of flow with the use of a throttling unit or speed probe and the pressure difference sensor o It evaluates flow from 0.5 % of the range of flow with the use of the flow meter evaluating the volume or mass flow (whirl, inductive, ultrasonic, Coriolis, thermal flow meter) o With the use of the water meter and the gas meter, the minimum measurable flow is determined by the technical conditions of the used flow meter o Overloading the flow meter is determined by technical conditions of the used flow meter, but overloading of current inputs is max. 25 % o In case of meters of cross-section (orifice, discharge nozzle...), the nominal difference pressure dp can be overloaded by 20 % o Variables, which are specified as sums (e.g. flown quantity), are stored to memory and backed-up against power failure for the period of at least 10 years (storing takes place in the interval of 1 sec.) o On the basis of an agreement, the software of the rated meter can be extended with a non-billing part of the application, which is not subjected to verification; extension of the application may not influence the function of the rated meter. The devices are rated products pursuant to the Act No. 22/1997 Coll., as amended, and a Declaration of Conformity EC-457000 is issued for them. FIGURE 1 - DIMENSIONAL DRAWING MEASUREMENT OF FLOW AND HEAT TRANSFERRED BY WATER STEAM Evaluation unit of the meter of heat in the systems of steam measurement INMAT 57 is designed, pursuant to Act No. 505/1990 Coll., as amended, for measurement of heat in the systems of measurement of water steam pursuant to MPM 18-95. Pursuant to Annex to the Decree No. 345/2002 Coll., as amended, as evaluation unit, which is a part of the heat meter. Furthermore, it can be used as meter of flown quantity of the condensate in the systems for steam measurement pursuant to MPM 18-95. The meter INMAT 57 enables: - Measurement of heat transferred by water steam with direct method (without measurement of the condensate) in combination with the substitute method - Measurement of heat transferred by water steam with indirect method, i.e. with a calculation from the quantity of overheated water steam detected by the measurement of quantity of the condensate and temperature and pressure of overheated steam, in combination with the substitute method - Measurement of heat in condensate Flow of water steam is measured with throttling units or speed probes with one pressure difference sensor with output current unified signal or volume flow meter (e.g. whirl) with linear output signal of frequency or unified current. Flow of the condensate (for indirect method) is measured with volume flow meter (e.g. whirl) with linear output signal of frequency or with water meter with impulse output signal. Temperature of water steam in the piping is measured with a resistance temperature sensor with measuring resistor in four- PRODUCT MANUAL Installation seal

Transcript of PRODUCT MANUAL type 457 - zpanp.eu · multi-hole orifices pursuant to ČSN EN ISO 5167-2:2003,...

Page 1: PRODUCT MANUAL type 457 - zpanp.eu · multi-hole orifices pursuant to ČSN EN ISO 5167-2:2003, orifices with conical input pursuant to ISO TR 15377: 2007, quarter-circle orifices

TP – 304337

1 / 34

Heat and cold meter, evaluation unit of gas flow INMAT 57

type 457

A P P L I C A T I O N - Measurement of flow and heat transferred by water steam - Measurement of flow and heat in condensate - Measurement of flow and heat transferred by water - Measurement of cold - of flow of fluids - of flow of gases - As independent meter for building closed measuring units

and for building extensive distributed systems - Compact design and Ingress Protection IP 65 enables the

use of the evaluation unit in the most demanding conditions

- It is not designed for operation in explosive environment In certified design as a rated meter according to Act No. 505/1990 Coll., on metrology

For measurement of flow and heat transferred by water steam with direct, indirect and replacement method, measurement of heat in condensate, measurement of flow and heat transferred by water, for measurement of cold and also for measurement of flow of gases in the function of the evaluation unit of the flown quantity of gas o It complies with MPM 18-95 (Directive for

permissible methods of measurement of heat in water steam and in condensate in business contact)

o For billing purposes, it is necessary to use the measuring path for the measurement of flow that corresponds to the applicable standards or technical conditions of the used flow meter

o During the evaluation of flow, it uses the calculations for the following primary items: centric orifices pursuant to ČSN EN ISO 5167-2:2003, discharge nozzles pursuant to ČSN EN ISO 5167-3:2003, Venturi tubes pursuant to ČSN EN ISO 5167-4:2003, multi-hole orifices pursuant to ČSN EN ISO 5167-2:2003, orifices with conical input pursuant to ISO TR 15377: 2007, quarter-circle orifices pursuant to ISO TR 15377: 2007, segment orifices pursuant to ČSN 25 7711, Annubary Rosemount 485 and general throttling unit, volume flow meters, mass flow meters, water meters and gas meters

o It evaluates flow from 5 % of the range of flow with the use of a throttling unit or speed probe and the pressure difference sensor

o It evaluates flow from 0.5 % of the range of flow with the use of the flow meter evaluating the volume or mass flow (whirl, inductive, ultrasonic, Coriolis, thermal flow meter)

o With the use of the water meter and the gas meter, the minimum measurable flow is determined by the technical conditions of the used flow meter

o Overloading the flow meter is determined by technical conditions of the used flow meter, but overloading of current inputs is max. 25 %

o In case of meters of cross-section (orifice, discharge nozzle...), the nominal difference pressure dp can be overloaded by 20 %

o Variables, which are specified as sums (e.g. flown quantity), are stored to memory and backed-up against power failure for the period of at least 10 years (storing takes place in the interval of 1 sec.)

o On the basis of an agreement, the software of the rated meter can be extended with a non-billing part of the application, which is not subjected to verification; extension of the application may not influence the function of the rated meter.

The devices are rated products pursuant to the Act No. 22/1997 Coll., as amended, and a Declaration of Conformity EC-457000 is issued for them.

FIGURE 1 - DIMENSIONAL DRAWING

MEASUREMENT OF FLOW AND HEAT TRANSFERRED BY WATER STEAM Evaluation unit of the meter of heat in the systems of steam measurement INMAT 57 is designed, pursuant to Act No. 505/1990 Coll., as amended, for measurement of heat in the systems of measurement of water steam pursuant to MPM 18-95. Pursuant to Annex to the Decree No. 345/2002 Coll., as amended, as evaluation unit, which is a part of the heat meter. Furthermore, it can be used as meter of flown quantity of the condensate in the systems for steam measurement pursuant to MPM 18-95. The meter INMAT 57 enables: - Measurement of heat transferred by water steam with

direct method (without measurement of the condensate) in combination with the substitute method

- Measurement of heat transferred by water steam with indirect method, i.e. with a calculation from the quantity of overheated water steam detected by the measurement of quantity of the condensate and temperature and pressure of overheated steam, in combination with the substitute method

- Measurement of heat in condensate Flow of water steam is measured with throttling units or speed probes with one pressure difference sensor with output current unified signal or volume flow meter (e.g. whirl) with linear output signal of frequency or unified current. Flow of the condensate (for indirect method) is measured with volume flow meter (e.g. whirl) with linear output signal of frequency or with water meter with impulse output signal. Temperature of water steam in the piping is measured with a resistance temperature sensor with measuring resistor in four-

PRODUCT MANUAL

Installation seal

Page 2: PRODUCT MANUAL type 457 - zpanp.eu · multi-hole orifices pursuant to ČSN EN ISO 5167-2:2003, orifices with conical input pursuant to ISO TR 15377: 2007, quarter-circle orifices

TP – 304337 PRODUCT MANUAL TYPE 457 - Meter INMAT 57

2 / 34

wire connection or with a thermometer with converter to the unified current signal. Operating temperature of water steam in the transferring piping may be 600 °C as a maximum. Temperature of the condensate (for indirect method) is measured with resistance temperature sensor with measuring resistor in four-wire connection or thermometer with converter to the unified current signal. Operating temperature of the condensate may be 200°C as a maximum. Pressure of water steam is measured with the absolute pressure sensor or with the overpressure sensor with unified current signal. The use of the absolute pressure sensor is recommended for the operating pressures smaller than 1 MPa. The meter INMAT 57 performs automatic correction of changes of density and enthalpy pursuant to IAPWS IF97 within the range of temperature from the limit of saturation to 600 °C and within the range of abs. pressure from 60 kPa to 18 MPa. The status of wet steam is signalled with the system of self-diagnostics. In case of a drop of the steam temperature under the limit of saturation, the measurement of flow and heat is switched over to the substitute method. The evaluation of flow and heat with both methods does not influence one another. Heat, heat output, flown quantity and flow steam within the zone of overheated steam are displayed on independent meters. The evaluation within the limited area of wet steam under the limit of saturation takes place on independent meters within the zone, the upper limit of which is the temperature of steam saturation (TS), the bottom limit is limited to 10°C under the temperature of saturation (TS - 10°C). Quantities of flow and thermal output in the area of wet steam are marked with the index mp. Heat and flown quantity under the limit of saturation are assessed separately in two zones. 1st zone within the temperature interval TS to TS - 2°C is marked with index mp, 2nd zone within the temperature interval TS - 2°C to TS - 10°C is marked with index mv. Data of the thermal output and heat in wet steam are multiplied with a coefficient Kh (0.5 to 1). In case of the direct method, data of flow and flown quantity in wet steam are multiplied with a coefficient Km (0.5 to 1). User adjustable coefficients Kh and Km are established contractually between the supplier and the customer of heat (implicitly Kh = Km = 1) and their change can be protected with a password. The measurement methods are established in compliance with MPM 18-95 (Directive for permissible methods of measurement of heat in water steam and in condensate in business contact). The limit of saturation is established pursuant to “International formulation of thermodynamic properties of water and water steam for industrial purposes IAPWS-IF97. Measurement in the area of overheated steam and measurement of the condensate has a nature of a rated operating meter. Measurement in the area of wet steam (so-called substitute method) has a nature of a non-rated operating meter. For billing purposes, it is necessary to use a measuring path for the measurement of flow that corresponds to the applicable standards or technical conditions of the used flow meter. The sensor pressure, thermometers and meters of the flown quantity of carrying medium, which are, together with the evaluation unit, elements of heat meters, shall be compatible with the evaluation unit INMAT 57, have type approval in the Czech Republic and have valid certification. MEASUREMENT OF HEAT TRANSFERRED BY WATER, MEASUREMENT OF COLD The meter INMAT 57 evaluates flow of water and quantity of heat transferred by water or it evaluates quantity of cold. The flow is measured with throttling units or speed probes with one pressure difference sensor with output current unified signal, volume flow meter (e.g. inductive, ultrasonic or whirl), mass flow meter with linear output signal of frequency or unified current and water meter with impulse signal. Temperature of the medium in transferring and return piping is measured with pair resistance temperature sensors with measuring resistor in four-wire connection. INMAT 57 can be used for a discretionary operating temperature difference from 0 to 200 °C and for water temperature from 0 to 200 °C. For measurement of cold, the temperature range is from -50 to 200°C. After an agreement, at a special request also in another smaller range.

Pressure of the medium for the calculation of flow is considered constant 1.6 MPa abs. Pressure can be measured and displayed for other purposes. In that case, pressure is measured with the absolute or relative pressure sensor with unified current signal. Measurement of pressure is only possible in connection with the frequency or impulse signal of flow. Bi-directional flow In connection with the bi-directional flow meter, INMAT 57 can evaluate both directions of flow of the medium. In case of use of the bi-directional flow meter, the signal of direction of flow of the evaluation switches over between the first circuit and the second circuit. If the signal of flow is of the current type, the direction of flow is switched over with the logical signal brought to impulse / frequency input (as contact or open collector). Signal connected for direction 1, disconnected for direction 2. If the signal of flow is of impulse/frequency nature, the direction of flow is switched over with unified current signal brought to input I3. Signal over 12mA = direction 1, signal up to 12 mA for direction 2. MEASUREMENT OF FLOW OF FLUIDS Flow of water and technical fluids is measured with throttling units or speed probes with one sensor of pressure difference with output current unified signal, volume flow meter (e.g. inductive, ultrasonic or whirl), mass flow meter with linear output signal of frequency or unified current and water meter with impulse signal. Temperature of the medium in the piping is measured with resistance temperature sensor with measuring resistor in four-wire connection or resistance thermometer with converter to unified current signal. The meter INMAT 57 can be used for water temperature from 0 to 200 °C and temperature of technical fluids from -50 to 200°C (maximum -100 to 600 °C). Pressure of the medium in the piping for the calculation of flow can be considered constant or measured with the absolute pressure sensor or the overpressure sensor with unified current signal. If constant pressure of the medium is considered, the measured pressure can only be displayed for other purposes. Bi-directional flow In connection with the bi-directional flow meter, INMAT 57 can evaluate both directions of flow of the medium. In case of using the bi-directional flow meter, of signal of direction of flow of evaluation switches over between the first circuit and the second circuit. If the signal of flow is of the current type, direction of flow is switched over with the logical signal brought to impulse/frequency input (as contact or open collector). Signal connected for direction 1, disconnected for direction 2. If the signal of flow is of impulse/frequency nature, the direction of flow is switched over with the unified current signal brought to input I3. Signal over 12mA = direction 1, signal up to 12 mA for direction 2. MEASUREMENT OF FLOW OF GASES - Evaluation unit of the meter of flown quantity of gas The meter INMAT 57 operates as an evaluation unit of flow and flown quantity of gases. Flow and volume of gas are recalculated to reference conditions of pressure and temperature, or, as the case may be, to mass. The unit consists of INMAT 57, measuring pressure converter (absolute pressure or overpressure) and measuring temperature converter. The evaluation unit is used in connection with the meter of flown volume of gas or, as the case may be, flow of gas. For billing measurement, it is necessary to use measuring converters with valid type approval and official certification identified in the Decision about gauge type approval. Measuring converters located on gas conduit with the use for heating, explosive and flammable gases shall have an approval for that particular environment. To ensure intrinsic safety of input and output signals of the evaluation unit, it is possible to use barriers approved for that particular environment. Flow is measured: - with throttling units or speed probes with one sensor of

pressure difference with output current unified signal

Page 3: PRODUCT MANUAL type 457 - zpanp.eu · multi-hole orifices pursuant to ČSN EN ISO 5167-2:2003, orifices with conical input pursuant to ISO TR 15377: 2007, quarter-circle orifices

TP – 304337 PRODUCT MANUAL TYPE 457 - Meter INMAT 57

3 / 34

- volume flow meter (e.g. whirl) with linear output signal of frequency, impulse or unified current

- mass flow meter with linear output signal of frequency, impulse or unified current

- gas meter with output signal of impulse, frequency or with unified current

Temperature of gas is measured with resistance temperature sensor with measuring resistor in four-wire connection or thermometer with converter to unified current signal. Pressure of gas is measured with the absolute pressure sensor or the overpressure sensor with unified current signal. For heating gases, the sensor of relative pressure can be used only in case if the lower limit of the operating range of gas pressure is higher than or equal to 2.1 MPa abs. The temperature range is: - for heating gases from - 20 °C to 50 °C - for technical gases from - 50 °C to 100 °C - (other limits after an agreement with the manufacturer

maximum - 100 °C to 600 °C) Pressure range of the re-calculator is 5 to 100 % of the measuring range of the used pressure converter. The calculation of the correction or re-calculation coefficient of density considers the coefficient of compressibility. Compressibility can be constant or variable. The calculation of compressibility factors is realized for heating gases pursuant to AGA NX 19mod. or SGERG 88. For technical gases, the re-calculation of compressibility factors is realized by means of virial development or state equation (Van Der Waals, Redlich Kwong, Soave Redlich Kwong, Peng Robinson, Peng Robinson Gasem) according to an agreement with the user. INMAT 57 can re-calculate volume and volume flow for a discretionary relative conditions, e.g. to normal conditions (pn = 101.325 kPa, Tn = 288.15 K or pn = 98.0665 kPa, Tn = 293.15 K). Furthermore, it can evaluate mass and volume non-recalculated flow. INMAT 57 is not designed for operation in the explosive environment. Measuring converters in non-explosive design with fixed closure or in spark safe design can be used in the explosive environment, qualification of the environment pursuant to the used sensors. Any changes of the parameters and constants related to the calculation programme and applicable meters are protected with an official mark. Permitted changes of the parameters (depending on design of dv, %CO2, %N2, %H2, Hs, Vc, Pc, Tc and ) are efficiently protected with passwords and recording to memory that cannot be deleted. Description of the function of passwords and use of the metrological password is described in the article OPERATION AND MAINTENANCE, USER AND METROLOGICAL PASSWORD.

D E S C R I P T I O N INMAT 57 is located in the compact plastic box covered with the tilting lid with the display unit and two controlling push-buttons. After tilting the lid away, a sealable cartridge of the changer is accessible, which determines all metrological parameters of the device. The cartridge is provided with a connector terminal board that can be divided. The structural design enables a simple installation and uninstallation of partial components of this unit. The box of the evaluation unit is adapted for the installation on the wall and it enables a simple replacement of partial components of the unit. Controlling of the device is possible without opening the lid. The wires to the terminal board are brought with sealed outlets. The installation seal prevents from access to the terminal board. Seals on the cover of the cartridge of the meter prevent from access to the electronics (calibration seal or, as the case may be, an official mark for a certified design), which disable influencing the measurement with an unprofessional or intentional intervention. It is also possible to certify the actual cartridge of the meter without the display unit. Therefore, it is not necessary to disconnect cabling and remove the device from the wall. The official mark (self-sealing sticker located on the measuring cartridge) is visible through the through-hole in the face label of the device.

P R I N C I P L E The activity of the device is controlled with a one-chip micro-processor. Analogue input signals are transferred to the digital form with A/D converter and, with a possible impulse/ frequency input, they are processed in the processor. On the basis of such data, INMAT 57 calculates instantaneous mass flow, flown quantity etc. The calculated quantities can be displayed on the two-line 16-position alpha-numerical display from liquid crystals with back light. The selection of the required data for displaying on the display is made with the push-button MODE. Quantities displayed on the display are updated cyclically (with user-adjustable period). At the same time, it is evaluated if the quantities are within the pre-programmed limits. The second line of the display is used for displaying error messages as response to exceeding limits of some quantities and other internal tests. The assessed quantities can be transmitted by means of the interface RS485 or RS232C or M-Bus to the master computer. The network interface RS485 and M-Bus enable the meter to operate in the local network. On the interface RS485, it is possible to connect to 30 equipments (e.g. meter INMAT 57, INMAT 51, INMAT 66, ...) with one computer. On the network, it is possible to transfer all values stored in the unit. Communication network possibilities of the interface enable access to individual quantities of the devices, without violating the activity of measurement. By means of the communication interface, it is possible to set-up real time, date, user constants, menu user, conduct of error messages etc. The assessed quantities can be transferred to the following equipment in the form of a unified current signal 4 to 20 mA or impulse output signal. The selection of the output quantities and the range is adjustable by the user by means of communication interface and programme SWK45702. The provision of the analogue current output or impulse output is specified in the number of design refer to TABLE 1 - DESIGN OF METERS INMAT 57 - TYPE 457.

T E C H N I C A L D A T A Requirements for design: The device is designed according to ČSN EN 61010-1 as an electrical equipment of protection class III, for application in networks with the category of overvoltage in installation I and pollution grade 1 and 2. Electric insulation resistance:

circuit of power supply, inputs, outputs and shielding against screws of the lid min. 20 M Electric strength of insulation:

circuit of power supply, inputs, outputs and shielding against screws of the lid 500 V AC (750 V DC) Ingress Protection pursuant to ČSN EN 60529: IP 65 Electric power input: max 4 W (meter INMAT 57 max. 0.25 W + power supply of converters) Display: LCD with back light

2 × 16 characters, height of character 5.55 mm, width of character 2.95 mm Weight: approx. 0.5 kg Type of operation: continuous Used materials: box: plastic PC Electric connection: Terminals screw type for cross-section of wires max.

2.5 mm2 Bushings 5 x Pg7 pursuant to DIN 40430 grey colour

for cable diameter 2.5 to 6.5 mm 3 x Pg9 pursuant to DIN 40430 grey colour

for cable diameter 4 to 8 mm Service life of the battery: typically 5 years Discharging of the internal battery is signalled by self-diagnostics on the bottom line of the display (during the operation of the device) and also by the communication program in the menu Display/Diagnostics. In case of a certified design, the battery is replaced during the following certification.

O P E R A T I N G C O N D I T I O N S Operating environment: The device is designed for the environment defined by the group of parameters and their severity grades IE 36/3M1, but with the minimum ambient temperature only -10 °C, pursuant to ČSN EN 60721-3-3 and the operating conditions pursuant to TP. The device complies with the class of environment C pursuant to ČSN EN 1434-1. The device complies with mechanical

Page 4: PRODUCT MANUAL type 457 - zpanp.eu · multi-hole orifices pursuant to ČSN EN ISO 5167-2:2003, orifices with conical input pursuant to ISO TR 15377: 2007, quarter-circle orifices

TP – 304337 PRODUCT MANUAL TYPE 457 - Meter INMAT 57

4 / 34

class M1 and class of environment E2 pursuant to ČSN EN 12405-1+A2. Ambient temperature: - 10 to + 55 °C Relative humidity of surrounding environment: 5 to 100 % with condensation Atmospheric pressure: 70 to 106 kPa Vibrations pursuant to ČSN EN 60068-2-6 ed.2: - Frequency range [Hz] 10 to 55 Hz - Drift amplitude [mm] 0.35 (0.014 in) - Acceleration amplitude [m.s-2] 49 (5g) Operating position:

vertical; the outlets shall not be situated downwards Power supply: Direct current device shall be supplied from the source SELV/PELV, the output of which corresponds to ČSN EN 61010-1 Article 6.3. Type of power supply network: DC 24 V Tolerance of supply voltage: ± 25 % Real time clock have stand-in power supply from 3V Li battery CR2032 located in the holder – refer to FIGURE 2 - LOCATION OF THE MANUFACTURING LABEL ON THE BOX OF THE DEVICE, LOCATION OF BATTERY. Settlement period after switching power supply on: 30 minutes Electromagnetic compatibility (EMC): 1) Radiation complies with the requirements of standards

ČSN EN 61000-6-3 ed.2, ČSN EN 61000-6-4 ed.2, ČSN EN 55022/B and ČSN EN 1434-4, Article 6.18

2) Resistance complies with the requirements of ČSN EN 61000-6-2 ed.3 a) Electrostatic discharges pursuant to ČSN EN 61000-4-

2 ed.2: level 4, (intensity ± 15 kV air, ± 8 kV discharge), test conditions pursuant to ČSN EN 1434-4, Article 6.13, functional criterion 1

b) Electromagnetic field pursuant to ČSN EN 61000-4-3 ed.3: level 4, (intensity 30 V/m) test conditions pursuant to ČSN EN 1434-4, Article 6.12, functional criterion 1

c) Fast transient phenomena, pursuant to ČSN EN 61000-4-4 ed.2: level 3, (test voltage 1 kV) test conditions pursuant to ČSN EN 1434-4, Article 6.11.1 functional criterion 1

d) Surge, pursuant to ČSN EN 61000-4-5 ed.2: (test voltage 0.5 kV), test conditions pursuant to ČSN EN 1434-4, Article 6.11.2 ENV 50 140 functional criterion 1

e) External electromagnetic field spread by wiring, pursuant to ČSN EN 61000-4-6 ed.3: level 3, (intensity 10 V eff) functional criterion 1

f) Electromagnetic field of network frequency, pursuant to ČSN EN 61000-4-8 ed.2: test conditions pursuant to ČSN EN 1434-4, Article 6.15 (intensity 60 A/m), functional criterion 1,

g) Static magnetic field: test conditions pursuant to ČSN EN 1434-4, Article 6.14 100 kA/m, functional criterion 1

h) Drops and failures of power supply, pursuant to ČSN EN 61000-4-11 ed.2: level 2 level 0 % UT, drop of voltage by 100 %, period of existence 5 periods AC (100 ms DC), functional criterion 1

M E T R O L O G I C A L D A T A INPUT SIGNALS a) current inputs - I1, I2 and I3

1 to 3 × current loop 0 to 20mA or 4 to 20mA b) resistance inputs - R1, R2

0 to 2 × resistance for measurement of resistance in four-wire connection e.g. for thermometer Pt 100, (at a special request Pt 200, Pt 500 or Pt 1000) pursuant to ČSN EN 60751 in four-wire connection, loop resistance max. 20 .

c) impulse and frequency input - IMP/FR

1 × impulse and frequency input with/without treatment of glimmers (dampening) Ranges:

without treatment of glimmers 0 Hz to 10 kHz with treatment of glimmers 0 to maximum 500Hz

upper limit depends on the setup of dampening pursuant to the used flow meter Designed for REED contact or OK (open collector), power supply DC 5 V. Maximum frequency can be overloaded by 20 %.

Note: It can also work as a logical input. Depending on use, INMAT 57 is delivered in some of the following combinations of inputs: - 2x resistance + 1x current +1x impulse/frequency - 1x resistance + 2x current +1x impulse/frequency - 0x resistance + 3x current +1x impulse/frequency Specific scheme of connection can be seen after tilting the lid away on the self-sealing sticker located on cover of the display. The range of temperature measurement pursuant to the used sensor and measured medium can be max.

0 to 200 °C for water 0 to 600 °C for water steam - 100 to 200 °C for gases - 100 to 600 °C for other use *)

*) Other ranges are possible after an agreement with the manufacturer. INPUT SIGNALS Measurement of heat and flow transferred by water steam a) from sensor dp current :

0 to 20mA or 4 to 20mA b) from flow meter current :

0 to 20mA or 4 to 20mA frequency: 0 to 10 kHz impulse: max. 500 Hz

c) from sensor of relative pressure or absolute pressure current: 0 to 20 mA or 4 to 20 mA

d) from temperature sensors resistance: Pt 100, according to ČSN EN 60751 Pt 200, Pt 500 or Pt 1000 *) current: 0 to 20 mA or 4 to 20 mA

e) control of flow direction: positive and negative direction of flow of the condensate *) (>12 ÷ ≤21) mA /(>3.6 ÷ ≤12) mA / for current input, connected/disconnected for impulse input

*) It is possible after an agreement with the manufacturer.

Measurement of flow and heat transferred by water, measurement of cold a) from sensor dp current :

0 to 20mA or 4 to 20mA b) from flow meter current :

0 to 20mA or 4 to 20mA frequency: 0 to 10 kHz impulse: max. 500 Hz

c) from water meter impulse: max. 500 Hz d) from temperature sensors resistance:

Pt 100, according to ČSN EN 60751 Pt 200, Pt 500 or Pt 1000 *) current: 0 to 20 mA or 4 to 20 mA

e) pressure current: 0 to 20 mA or 4 to 20 mA *)

f) direction of flow current: 0 to 20 mA or 4 to 20 mA logical: connected/disconnected *) It is possible after an agreement with the manufacturer.

Flow of fluids a) from sensor dp current :

0 to 20mA or 4 to 20mA b) from flow meter current :

0 to 20mA or 4 to 20mA frequency: 0 to 10 kHz impulse: max. 500 Hz

Page 5: PRODUCT MANUAL type 457 - zpanp.eu · multi-hole orifices pursuant to ČSN EN ISO 5167-2:2003, orifices with conical input pursuant to ISO TR 15377: 2007, quarter-circle orifices

TP – 304337 PRODUCT MANUAL TYPE 457 - Meter INMAT 57

5 / 34

c) from water meter impulse: max. 500 Hz d) from temperature sensors resistance:

Pt 100, according to ČSN EN 60751 Pt 200, Pt 500 or Pt 1000 *) current: 0 to 20 mA or 4 to 20 mA

e) control of direction of flow: positive and negative direction of flow of the condensate *) (>12 ÷ ≤21) mA /(>3.6 ÷ ≤12) mA / for current input, connected/disconnected for impulse input *) It is possible after an agreement with the manufacturer.

Measurement of flow of gases - meter INMAT 57 of status re-calculator of gases a) from sensor dp current :

0 to 20mA or 4 to 20mA b) from flow meter current :

0 to 20mA or 4 to 20mA frequency: 0 to 10 kHz impulse: max. 500 Hz

c) from gas meter impulse: max. 500 Hz d) from sensor of relative pressure or absolute pressure

current: 0 to 20 mA or 4 to 20 mA

e) from temperature sensors resistance: Pt 100, according to ČSN EN 60751 Pt 200, Pt 500 or Pt 1000 *) current: 0 to 20 mA or 4 to 20 mA

*) It is possible after an agreement with the manufacturer. OUTPUTS The assessed quantities are displayed on LCD display - two lines with sixteen characters with back light. INMAT 57 can also be equipped with analogue current output or impulse output - refer to the table of designs. Display Meaning of special symbols: = symbol for quarter-hour maximum, it concerns the

biggest quantity or heat per continuous quarter-hour ▲ = symbol for maximum value, it concerns the maximum minute diameter of that particular quantity The assessed quantities - flow and heat transferred by water steam: in the menu Operation (and User) User-defined string, e.g. name of circuit 2x16 characters P1 - heat output (steam) [GJ/h] or [MW] E1 - heat quantity (steam) [GJ] or [MWh] Qm1 - instantaneous flow (steam) [t/h] M1 - quantity of water steam (steam) [t] Pmp1 - heat output outside parameters [GJ/h] or [MW] Emp1 - heat quantity outside parameters [GJ] or [MWh] Emv1 - heat quantity outside parameters [GJ] or [MWh] Qmmp1- flow of water steam outside parameters [t/h] Mmp1 - quantity of water steam outside parameters [t] Mmv1 - quantity of water steam outside parameters [t] Pc1 - instantaneous heat output (steam + wet steam) [GJ/h] or [MW] Ec1 - heat quantity (steam + wet steam) [GJ] or [MWh] Qmc1 - instantaneous flow of water steam (steam + wet steam) [t/h] Mc1 - quantity of water steam (steam +wet steam) [t] t1 - steam temperature [°C] dt1 - overheating = steam temperature-temperature of saturation *) [°C] pa1 - absolute static pressure [MPa] pg1 - relative static pressure [MPa]

Ec1 - quarter-hour heat maximum [GJ], [MWh] Mc1 - quarter-hour maximum quantity of steam [t]

▲Pc1 - maximum thermal output [GJ/h], [MW] ▲Qmc1- maximum of flow [t/h] ▲t1 - maximum temperature [°C] ▲p1 - maximum pressure (abs. /rel. according to sensor type) [MPa] time - time outside parameters(wet steam) [dd hh mm] - operating time [dd hh mm] - real time (according to setup CET or SCET) [dd:hh:mm] - date [day month year] For measurement by means of throttling units: dp1 - difference pressure [kPa] tq1 - temperature before throttling unit [°C] paq1 - abs. pressure before throttling unit [MPa] *) The steam temperature is considered temperature before the throttling unit For indirect method also: Pk1 - heat output - condensate [GJ/h] or [MW] Ek1 - heat quantity - condensate [GJ] or [MWh] Qmk1 - flow of condensate [t/h] Mk1 - quantity of condensate [t] Vk1 - flown volume of condensate [m3] tk1 - temperature of condensate [°C] PD1 - heat output steam-condensate [GJ/h] or [MW] ED1 - heat quantity steam-condensate [GJ] or [MWh] PDmp1 - heat output wet steam-condensate [GJ/h] or [MW] EDmp1 - heat quantity wet steam - condensate [GJ] or [MWh] EDmv1 - heat quantity wet steam - condensate [GJ] or [MWh] ▲tk1 - maximum temperature [°C] In menu Service hp1 - steam enthalpy [kJ/kg] TS1 - temperature of saturation [°C] v1 - specific volume of steam (only for direct method) [m3/kg] according to design ix - value of current on input x [mA] rx - value of resistance on input x [] imp1 - number of impulses per 1s [imp/s] or f1 - frequency value [Hz] User-adjustable sums for fast inspection of compliance with the mechanical counter on the water meter or the gas meter, adjustable by means of SWK45702. imp – sum of impulses, which came to impulse input [1] Qp – Status on the flow meter (number of impulses *imp. number) [m3] For indirect method also: vk1 - specific volume of condensate [m3/t] hk1 - enthalpy of condensate [kJ/kg] Resetting quarter-hour maxima is realized by means of control push-buttons in the menu Setup or by software by means of communication interface and SWK45702. Note: for indirect method, if flow meter with impulse output is used, instantaneous values P1, Qm1, Pmp1, Qmmp1, Pc1, Qmc1, Pk1, Qmk1, PD1 and PDmp1 are only informative. Assessed quantities - flow and heat transferred by water, measurement of cold: in the menu Operation (and User) User-defined string, e.g. name of circuit 2x16 characters P1 - instantaneous heat output [GJ/h] or [MW]

Page 6: PRODUCT MANUAL type 457 - zpanp.eu · multi-hole orifices pursuant to ČSN EN ISO 5167-2:2003, orifices with conical input pursuant to ISO TR 15377: 2007, quarter-circle orifices

TP – 304337 PRODUCT MANUAL TYPE 457 - Meter INMAT 57

6 / 34

E1 - heat quantity [GJ] or [MWh] Qm1 - instantaneous mass flow [t/h] M1 - flown quantity [t] Q1 - instantaneous volume flow [m3/h] V1 - flown volume [m3] t1p - water temperature in the transferring piping [°C] t1v - water temperature in return piping [°C] t1 - water temperature difference in transferring and return piping [°C]

E1 - quarter-hour heat maximum [GJ], [MWh] M1 - quarter-hour maximum quantity of steam [t]

▲P1 - maximum thermal output [GJ/h], [MW] ▲Qm1 - maximum of flow [t/h] ▲tp1 - maximum of temperature in the transferring piping [°C] ▲tv1 - maximum temperature in return piping [°C] ▲dt1 - maximum temperature difference [°C] time - operating time [dd hh mm] - real time (according to setup CET or SCET) [dd:hh:mm] - date [day month year] for bi-directional measurement of flow P2 - instantaneous heat output [GJ/h] or [MW] E2 - heat quantity [GJ] or [MWh] Qm2 - instantaneous mass flow [t/h] M2 - flown quantity [t] Q2 - instantaneous volume flow [m3/h] V2 - flown volume [m3] direction of flow 1 = there, 2 = back if pressure is measured pa1 - abs. pressure of medium [MPa] pg1 - overpressure of medium [MPa] for measurement by means of throttling units: dp1 - difference pressure [kPa] tq1 - temperature before throttling unit [°C] paq1 - abs. pressure before throttling unit [MPa] In menu Service hp1 - enthalpy in the transferring piping [kJ/kg] hv1 - enthalpy in return piping [kJ/kg] v1 - specific volume in the transferring piping [m3/t] according to design ix - value of current on input x [mA] rx - value of resistance on input x [] imp1 - number of impulses per 1s [imp/s] or fr1 - frequency value [Hz] User-adjustable sums for fast inspection of compliance with the mechanical counter on the water meter or the gas meter, adjustable by means of SWK45702. imp - sum of impulses, which came to the impulse input [1] Qp – Status on the flow meter (number of impulses *imp. number) [m3] Resetting quarter-hour maxima is realized by means of control push-buttons in the menu Setup or by software by means of communication interface and SWK45702. Note: If flow meter is used with impulse output, instantaneous values P1, Qm1 and Q1 are only informative. Assessed quantities - flow of fluids: in the menu Operation (and User) User-defined string, e.g. name of circuit 2x16 characters Qm1 - instantaneous mass flow [t/h] M1 - flown quantity [t] Q1 - instantaneous volume flow [m3/h] V1 - flown volume [m3] t1 - temperature of liquid [°C] pa1 - abs. pressure of liquid [MPa] pg1 - rel. pressure of liquid [MPa]

M1 - quarter-hour maximum quantity [t] V1 - quarter-hour maximum of volume [m3]

▲Qm1 - maximum weight of flow [t/h] ▲Q1 - maximum volume of flow [m3/h]

▲t1 - maximum of temperature in the transferring piping [°C] ▲p1 - maximum pressure [MPa]) time - operating time [dd hh mm] - real time (according to setup CET or SCET) [dd:hh:mm] - date [day month year] if pressure is measured pa1 - abs. pressure of medium [MPa] pg1 - overpressure of medium [MPa] for measurement by means of throttling units: dp1 - difference pressure [kPa] tq1 - temperature before throttling unit [°C] paq1 - abs. pressure before throttling unit [MPa] In menu Service v1 - specific volume in the transferring piping [m3/t] according to design ix - value of current on input x [mA] rx - value of resistance on input x [] imp1 - number of impulses per 1s [imp/s] or fr1 - frequency value [Hz] User-adjustable sums for fast inspection of compliance with the mechanical counter on the water meter or the gas meter, adjustable by means of SWK45702. imp - sum of impulses, which came to the impulse input [1] Qp – Status on the flow meter (number of impulses *imp.number) [m3] Resetting quarter-hour maxima is realized by means of control push-buttons in the menu Setup or by software by means of communication interface and SWK45702. Note: If flow meter is used with impulse output, instantaneous values Qm1 and Q1 are only informative. Assessed quantities - measurement of flow of gases: in the menu Operation (and User) User-defined string, e.g. name of circuit 2x16 characters Qn1 - standardized flow of gases [m3/h] Vn1 - standardized volume [m3] Q1 - operating flow of gases [m3/h] V1 - operating volume [m3] Qm1 - instantaneous mass flow [t/h] M1 - flown quantity of gas [t] Qnmp1 - standardized flow of gases outside parameters [m3/h] Vn1mp - standardized volume outside parameters [m3] Qmp1 - operating flow of gases outside parameters [m3/h] Vmp1 - operating volume outside parameters [m3] Qmmp1- instantaneous mass flow outside parameters [t/h] Mmp1 - flown quantity of gas outside parameters [t] K1 - compressibility grade Z1 - re-calculating number t1 - temperature of gas [°C] pa1 - absolute pressure of gas [MPa] pg1 - relative pressure of gas [MPa]

Vn1 - quarter-hour maximum of re-calculated volume [m3]

M1 - quarter-hour maximum quantity [kg] ▲Qn1 - maximum of flow [m3/h] ▲Qm1 - maximum of flow [kg/h] ▲t1 - maximum of temperature in the transferring piping [°C] ▲p1 - maximum pressure (abs. /rel. according to sensor type) [MPa] time - time outside parameters [dd hh mm] - operating time [dd hh:mm] - real time (according to setup CET or SCET) [dd:hh:mm] - date [day month year] for measurement by means of throttling units: dp1 - difference pressure [kPa]

Page 7: PRODUCT MANUAL type 457 - zpanp.eu · multi-hole orifices pursuant to ČSN EN ISO 5167-2:2003, orifices with conical input pursuant to ISO TR 15377: 2007, quarter-circle orifices

TP – 304337 PRODUCT MANUAL TYPE 457 - Meter INMAT 57

7 / 34

tq1 - temperature before throttling unit [°C] paq1 - abs. pressure before throttling unit [MPa] In menu Service according to design ix - value of current on input x [mA] rx - value of resistance on input x [] imp1 - number of impulses per 1s [imp/s] or fr1 - frequency value [Hz] User-adjustable sums for fast inspection of compliance with the mechanical counter on the water meter or the gas meter, adjustable by means of SWK45702. imp - sum of impulses, which came to the impulse input [1] Qp – Status on the flow meter (number of impulses *imp.number) [m3] Resetting quarter-hour maxima is realized by means of control push-buttons in the menu Setup or by software by means of communication interface and SWK45702.

Note: If flow meter is used with impulse output, instantaneous values of flow (Qn1, Q1, Qm1, Qnmp1, Qmp1 and Qmmp1) are only informative. Current output (optionally) Depending on design, INMAT 57 can be equipped with the current output module with passive galvanic separation with the unified current signal 4 to 20 mA. The selection of the output quantity and the range are user-adjustable by means of communication interface and the programme SWK45702. When the range is exceeded, the value of the output signal remains on the maximum value (typically 21 mA).

Parameters: output signal: 4 to 20 mA power supply output: 24V DC (10 to 36V DC) galvanic separation: 500V Impulse output (optionally) Depending on the design, INMAT 57 can be equipped with the impulse output module, which realizes galvanic separated output of the type of open collector. The function of the module, the selection of output quantities and the range are user-adjustable by means of communication interface and the programme SWK45702. Parameters:

output with galvanic separation with open collector function: impulse output or signalling of errors and alarms length of pulse: adjustable 100 ms to 900 ms frequency of pulses: max. 3000 imp per hour (overload capacity 20%)

external source: max. 70 V DC, max. 20 mA (type 5 mA)

galvanic separation: 500V logical levels: 1 - transistor connected, 0 - transistor disconnected

COMMUNICATION INTERFACE Depending on the design, INMAT 57 is equipped with one of the following communication interfaces. A more detailed description of the interface and communication protocol is identified in the independent Annex - Communication protocol INMAT 57, which can be downloaded from www.zpanp.cz. Implicit setup of the parameters from the manufacturer: address 0, transmission speed 9600 Bd, without parity. Serial line RS485 - input/output Bi-directional communication line is used for communication of one or more units with the computer (max. 30 equipments without repeater). By means of RS485, it is possible to read the measured and assessed data. It is also possible to set-up some parameters (date, time, user constants, parameters of the communication interface RS485, ...). The connection is realized with the structure of the type of bus. Twisted wire (twist) is used as the connecting medium most often with the maximum recommended length 1200 m. Transmission speed is optional, maximum 1152000 Bd.

The terminating resistor is connected (at the end station) with the switchover DIP over the right part of the terminal board – by switching over to the position ON (refer to FIGURE 2 - LOCATION OF THE MANUFACTURING LABEL ON THE BOX OF THE DEVICE, LOCATION OF BATTERY). The line has galvanic separation.

Serial line RS 232 - input/output - not for certified design Bi-directional communication line designed for data transfer between one device and the computer to a short distance (unit: m). By means of RS 232, it is possible to read the measured and assessed data. It is also possible to set-up some parameters (date, time, user constants, parameters of communication interface). Transmission speed is optional, maximum 1152000 Bd. The line has galvanic separation.

Serial line M-Bus - input/output Bi-directional communication line is used for communication of one or more units with the computer. Transmission speed is optional, maximum 9600 Bd. The line has galvanic separation. SELF-DIAGNOSTICS - ERROR MESSAGES The meter INMAT 57 has a built-in self-diagnostics in its firmware, which controls the limits of the measured quantity, assessed quantities and internal battery. Data of the diagnostics can be displayed on the bottom line of the display and in the menu Diagnostics; they are also available on the communication interface. The test results are only displayed in case of a detected error. It means that in case of a successful test, no message is displayed. The message can be reset after the confirmation thereof with the push-button ACK in the menu Diagnostics or with the communication programme SWK45702. A more detailed description of setup of the error messages is identified in the Article OPERATION AND MAINTENANCE. Data of self-diagnostics - Measurement of flow and heat transferred by steam

The following is signalled on the display: o Wet steam o Interrupted thermometer t1 o Error of pressure sensor p1 o Error of flow sensor o Errors of probes-blocked calculation of flow o Exceeded temperature t1 o Input 1 is outside limits o Input 2 is outside limits o Input 3 is outside limits

- Measurement of flow and heat transferred by water, measurement of cold The following is signalled on the display: o Interrupted thermometer tp1 - transferring piping o Interrupted thermometer tv1 - return piping o Error of pressure sensor p1 o Error of flow sensor o Errors of probes-blocked calculation of flow o Exceeded temperature tp1 - transferring piping o Exceeded temperature tv1 - return piping o Input 1 is outside limits o Input 2 is outside limits o Input 3 is outside limits

- Measurement of flow of fluids

The following is signalled on the display: o Interrupted thermometer t1 o Error of pressure sensor p1 o Error of flow sensor o Errors of probes-blocked calculation of flow o Exceeded temperature t1 o Input 1 is outside limits o Input 2 is outside limits o Input 3 is outside limits

- Measurement of flow of gases

The following is signalled on the display: o Substitute parameters o Interrupted thermometer t1 o Error of pressure sensor p1

Page 8: PRODUCT MANUAL type 457 - zpanp.eu · multi-hole orifices pursuant to ČSN EN ISO 5167-2:2003, orifices with conical input pursuant to ISO TR 15377: 2007, quarter-circle orifices

TP – 304337 PRODUCT MANUAL TYPE 457 - Meter INMAT 57

8 / 34

o Error of flow sensor o Errors of probes-blocked calculation of flow o Exceeded temperature t1 o Input 1 is outside limits o Input 2 is outside limits o Input 3 is outside limits

LIMITS OF PERMITTED BASIC ERROR - current loop 0 to 20mA or 4 to 20mA: error 0.1 %

from the measured value; 0.02 % from the range *) - resistance in four-wire connection: error 0.1 %

from the measured value; 0.02 % from the range *) - frequency / impulse input: error 0.1 %

from the measured value; 0.02 % from the range *) - operating and real time: 3.5 PPM (2 min/year) - current/impulse output : error 0.2 %

from the measured value; 0.04 % from the range *) *) during the assessment, the bigger value of the highest permitted error established by the applicable specifications is used Limits of permitted basic error - flow and heat transferred by steam

The device operates in accuracy class 4 and 5. Maximum permitted error of calculation of the thermal output, heat, flow and flown quantity:

0.1 % from the measured value within the range 5 to 100 % for volume and mass flow meters within the range 2 to 100 %

- Flow and heat transferred by water, cold Maximum permitted error of calculation of the thermal output, heat, flow and flown quantity:

0.1 % from the measured value within the range 5 to 100 % of flow, for volume and mass flow meters within the range 2 to 100 % and for temperature difference within the range 3°C to 200 °C

- Flow of fluids

Maximum permitted error of calculation of flow and flown quantity:

0.1 % from the measured value within the range 5 to 100 % of flow, for volume and mass flow meters within the range 2 to 100 %

- Meter INMAT 57 of status re-calculator of gases

Maximum permitted error of calculation of the instantaneous re-calculated flow of gases:

0.1 % from the measured value within the range 5 to 100 of flow of gases, for volume and mass flow meters within the range 2 to 100 %

Maximum permitted error of the used temperature meter: o resistance of the temperature sensor:

class A and B pursuant to ČSN EN 60751 o converters of temperature with converter R/I:

0.25 % from measuring range of the output signal

Maximum permitted error of the used pressure meter (overpressure, absolute pressure):

o - measuring converter of overpressure: 0.20 % from measuring range of the output signal

o - measuring converter of absolute pressure: 0.25 % from measuring range of the output signal

Maximum permitted error of the used pressure difference meter: 0.2 % from measuring range of the output signal

HYSTERESIS: max. 0.01 % REPRODUCTION ERROR: max. 0.01 % INSENSITIVITY ZONE: max. 0.01 % LONG-TERM DRIFT FOR 4800 HOURS: max. 0.05 % ADDITIONAL ERRORS For a change of ambient temperature: max. ± 0.1 % / 10 °C Evaluation of output signals

Evaluation of output signals: All quantities displayed on the displaying unit digitally correspond to the relevant units without the re-calculation constant. Also a scientific notation can be used (e.g. 7654321 is displayed as 8E6).

D E S I G N A T I O N Data on the product can be divided into several groups. 1) Data on the manufacturing label on the cover of the device: - Trademark - Text: Made in Czech Republic - Product number - Manufacturing number - Type of power supply network - Maximum power input - Ingress Protection - Other data according to design - CE mark - Accuracy class 1 - Environment class A, C 2) Data on verification labels on the cover of the device: The data are specified in the Type Approval Certificate. 3) Data displayed on the display of the device in the menu CONFIG, labels of the device or on the front panel: - Product number - Manufacturing number with year and month of

manufacture - Calculated (referential) values of the throttling unit or the

flow meter - Used principle of measurement of flow - Calculated flow of the throttling unit or the range of the

flow meter Mv - Calculated temperature of the throttling unit or reference

temperature of the flow meter tv - Calculated pressure of the throttling unit or reference

pressure of the flow meter pv (for steam and gases) - Signal of flow - Type of thermometer (e.g. Pt100 4-wire) - Range of the pressure sensor (e.g. 0-1.6 MPa rel.) - Signal of the pressure sensor - Other data are specified in the Type Approval Certificate D E L I V E R Y Unless agreed otherwise with the customer, each delivery includes - Delivery note - Products pursuant to the purchase order - Optional accessories

o Communication program SWK 457 02 o Power supply source INAP 904

- Accompanying technical documentation in Czech: o Product quality and completeness certificate, which

also serves as the warranty certificate o Calibration sheet (for non-certified design) o Product manual

If it is established in the purchase contract or agreed otherwise, the following documentation can be also delivered with the product: - ES Declaration of Conformity - Confirmation of certification of the rated meter (for

certified design) - Certificate of proof of metrological compliance

P A C K I N G The products and accessories are delivered in a packing ensuring resistance to the impact of thermal effects and mechanical effects pursuant to controlled packing regulations.

T R A N S P O R T The products may be transported on conditions corresponding to the set of combinations of classes IE 21 pursuant to ČSN EN 60721-3-2 (i.e. by airplanes and trucks, in premises that are ventilated and protected against atmospheric conditions; in case of the air transport, only heated overpressure cargo areas of airplanes are considered).

S T O R A G E The products may be stored on conditions corresponding to the set of combinations of classes IE 12 pursuant to ČSN EN

Page 9: PRODUCT MANUAL type 457 - zpanp.eu · multi-hole orifices pursuant to ČSN EN ISO 5167-2:2003, orifices with conical input pursuant to ISO TR 15377: 2007, quarter-circle orifices

TP – 304337 PRODUCT MANUAL TYPE 457 - Meter INMAT 57

9 / 34

60721-3-1 (i.e. in places continuous temperature control from 0 to 55 °C and humidity of surrounding air 45% and max. content of 29g H2O/m3 of dry air, without a special threat of an attack with biological agents, with vibrations of small significance and not situated close to sources of dust and sand). The shelf life is max. 12 months. After this period, control piece tests shall be performed on the product according to TP.

R E L I A B I L I T Y Indicators of reliability in operation conditions and conditions of the environment specified herein - Mean time of operation between failures 96 000 hours

(inf. value) - Expected service life 10 years

O R D E R I N G The purchase order shall specify - Name - Product ordering number - Filled-in questionnaire (essential annex to the purchase

order)

- Calculation of a throttling unit (essential annex to the purchase order)

For measurement of flow by means of a throttling unit): - Number of pieces

P U R C H A S E O R D E R E X A M P L E Meter INMAT 57 457 110 100/P1/PO 5 pcs Filled-in questionnaires enclosed

O R D E R I N G A C C E S S O R I E S The purchase order shall specify: - Name - Product ordering number - Number of pieces

P U R C H A S E O R D E R E X A M P L E Program communication for INMAT 57 SWK 457 02 1 pc

Page 10: PRODUCT MANUAL type 457 - zpanp.eu · multi-hole orifices pursuant to ČSN EN ISO 5167-2:2003, orifices with conical input pursuant to ISO TR 15377: 2007, quarter-circle orifices

TP – 304337 PRODUCT MANUAL TYPE 457 - Meter INMAT 57

10 / 34

TABLE 1 - DESIGN OF METERS INMAT 57 - TYPE 457

SPECIFICATIONS ORDERING NUMBER

457 x x 0 x 00

Communication

RS485 1 M-Bus 2 RS232 (it cannot be selected for certified design) 3

Output module

Impulse output 1 Current output 4 to 20 mA 2

Application

Measurement of flow and heat transferred by steam - direct method (code P2 cannot be selected)

1

Measurement of flow and heat transferred by steam - indirect method (code P2 cannot be selected)

2

Measurement of flow and heat transferred by water, cold 3 Measurement of flow of fluids (it cannot be certified) 4 Measurement of flow of gases (code P2 cannot be selected) 5 Measurement of flow and heat in condensate 6 Special application *) 9

*) Special applications are delivered after an agreement with the manufacturer. TABLE 2 – ADDITIONAL REQUIREMENTS FOR DESIGN OF METERS INMAT 57 - TYPE 457

SPECIFICATIONS CODE CERTIFICATION AND CALIBRATION

Certification according to the Act 505/1990 Coll., as amended

Measurement of flow and heat transferred by steam - direct method

/P1

Measurement of flow and heat transferred by steam - indirect method Measurement of flow and heat transferred by water, cold – outside the areas of application defined in the Decree of the Government No. 464/2005 Coll., (application outside residential and commercial areas and light industry) Measurement of flow and heat in condensate Measurement of flow and heat transferred by water, cold – outside the areas of application defined in the Decree of the Government No. 464/2005 Coll., with bi-directional flow meter (application outside residential and commercial areas and light industry)

/P2

Measurement of flow of gases /P3

Without certification (only calibration)

Measurement of flow and heat transferred by steam - direct method

/Q1

Measurement of flow and heat transferred by steam - indirect method Measurement of flow and heat transferred by water, cold – outside the areas of application defined in the Decree of the Government No. 464/2005 Coll., (application outside residential and commercial areas and light industry) Measurement of flow and heat in condensate Measurement of flow of fluids Measurement of flow and heat transferred by water, cold – outside the areas of application defined in the Decree of the Government No. 464/2005 Coll., with bi-directional flow meter (application outside residential and commercial areas and light industry) /Q2

Measurement of flow of fluids with bi-directional flow meter Measurement of flow of gases /Q3

REQUIREMENT FOR OTHER DOCUMENTATION APPLICATION FOR

Confirmation about certification of the rated meter /P1, /P2 and

/P3 /PO

Specify the codes behind the ordering product number. TABLE 3 - ACCESSORIES – to be ordered separately

SPECIFICATIONS ORDERING NUMBER Program communication for INMAT 57 SWK45702 Power supply source INAP 904, output DC 24V/350mA, Ingress Protection IP65

The source can supply 2 devices INMAT 57 including the required two-wire converters

904 000 001

C E R T I F I C A T I O N P U R S U A N T T O T H E A C T 5 0 5 / 1 9 9 0 C o l l . It is possible to verify the whole device or only the cartridge of the meter without the displaying unit. When verifying the actual cartridge only, it is not necessary to disconnect cabling and remove the device from the wall. In this case, another box is used with the display unit and push-buttons from type INMAT 57 during the verification. INMAT 57 has assigned official marks of gauge type approval: TCM 311/11-4815, TCM 143/11-4833 and TCM 311/11-4844. Only a worker of AMS or ČMI may violate the official mark. If the official mark was invalidated or removed, validity of certification of the meter expires. A "Confirmation of certification of the rated meter" can be issued later on for the certified INMAT 57 upon request of the customer. The purchase order shall specify: a) Product ordering number *)

b) Manufacturing number *) *) Data are specified on the device label. Certified INMAT 57 is provided with marks of the manufacturer and official marks of certification and type approval. Non-certified INMAT 57 is provided with marks of the manufacturer. For the location of marks of the manufacturer and official marks - refer to FIGURE 2 - LOCATION OF THE MANUFACTURING LABEL ON THE BOX OF THE DEVICE, LOCATION OF BATTERY, FIGURE 3 - LOCATION OF OFFICIAL MARKS AND MANUFACTURING LABEL ON THE CARTRIDGE and Decision about type approval. The manufacturer performs the initial and follow-up certification according to the Act No. 505/1990 Coll., on metrology, as amended. The follow-up certification is ordered

Page 11: PRODUCT MANUAL type 457 - zpanp.eu · multi-hole orifices pursuant to ČSN EN ISO 5167-2:2003, orifices with conical input pursuant to ISO TR 15377: 2007, quarter-circle orifices

TP – 304337 PRODUCT MANUAL TYPE 457 - Meter INMAT 57

11 / 34

separately at the department AMS ZPA Nová Paka, a.s ([email protected]). FIGURE 2 - LOCATION OF THE MANUFACTURING LABEL ON THE BOX OF THE DEVICE, LOCATION OF THE BATTERY

FIGURE 3 - LOCATION OF OFFICIAL MARKS AND MANUFACTURING LABEL ON THE CARTRIDGE

I N S T A L L A T I O N A N D C O N N E C T I O N

Warning! Installation and uninstallation of the meter, connecting and disconnecting of wires including disconnecting and connecting of the display connector MUST be performed with switched off supply voltage. INSTALLATION OF THE METER Installation, commissioning, monitoring activity and maintenance are realized pursuant to ČSN EN 1434-6. The device is connected on the wall or frame with four screws according to FIGURE 2 – DIMENSIONAL DRAWING. ELECTRICAL CONNECTION Electrical connection may only be realized by qualified workers pursuant to Section 5 the Decree 50/1978 Coll. Scheme of connection of the terminal board is provided in FIGURE 14 - SCHEME OF CONNECTION AND CONNECTING TERMINAL BOARD. The terminal board is accessible after tilting the lid away. The device is connected with shielded cable with insulated Cu wires with total insulation resistance min. 10 M, dimensioned according to ČSN 33 2000-4-43 ed.2 with maximum cross-section 2.5 mm2. Shielding is connected only on one side of the cable, namely on the terminal board of the mathematical element. The use of cables exceeding 10 m is possible. Cable outlets are delivered in sealed conditions, before the application of the outlet, it is necessary to dismantle the plug. Unused cable outlets shall remain sealed with plugs. The principle of uninstallation for access to the terminal board and holder of the battery:

1) Remove the installation seal of the cover. 2) Release the lid by loosening two screws in the

bottom part of the lid. 3) Tilt the lid away.

Procedure for removing and inserting of the cartridge of the meter:

1) When the lid is tilted away, disconnect the connector terminal board without disconnecting the cabling.

2) Disconnect the display connector (between lid of the box and the cartridge).

3) Unscrew and remove 4 screws holding a cartridge of the meter in the box. It concerns screws, which are closer to the centre of the cartridge. Warning: Side screws are secured with seals and may not be unloosed!

4) Remove the cartridge from the box. 5) Close and secure the box of the device.

Installation shall be realized in the reversed order. The temperature sensor is used with four-wire connection and it is connected independently with a four-wire with shielded cable. Shielding is connected only on one side of the cable, namely on the terminal board of the mathematical element. Temperature sensor with converter is connected pursuant to article Installation of the sensors with output current loop. Resistance of individual loops including the inner resistance of wiring of the sensor may be max. 20 . Installation of the sensors with current loop output: INMAT 57 enables to connect the sensors in two ways:

1) directly connected two-wire converter with output 4 to 20 mA, which is supplied from a common source with a mathematical element (power supply source shall be dimensioned also for power supply of the required number of the converters)

2) active current signal 0 to 20 mA or 4 to 20 mA The sensors are connected with a shielded cable pursuant to own TP. Shielding is connected only on one side of the cable, namely on the terminal board of the mathematical element. Impulse signal from the flow meter/gas meter is connected to the device with the cable with unshielded or, as the case may be, shielded twisted pair.

Official mark

Manufacturing label and type approval mark

Official mark

Official mark

Manufacturing label

Manufacturing label

Page 12: PRODUCT MANUAL type 457 - zpanp.eu · multi-hole orifices pursuant to ČSN EN ISO 5167-2:2003, orifices with conical input pursuant to ISO TR 15377: 2007, quarter-circle orifices

TP – 304337 PRODUCT MANUAL TYPE 457 - Meter INMAT 57

12 / 34

Communication interface is connected with shielded cable. Shielding is connected only on the side of the master equipment (PC). Current/Impulse output is connected with shielded cable. Shielding is connected only on the side of the evaluation equipment.

Warning! During the installation, this installation manual shall be complied with. INSTALLATION OF RATED METERS Installation and commissioning of rated meters, pursuant to the Act No. 505/90 Coll., on metrology, can only be realized by a person that is a bearer of a valid AUTHORIZATION for installation and maintenance of rated meters issued by ZPA Nová Paka a.s.

C O M M I S S I O N I N G After the connection, the device is prepared for operation. If the communication line RS485 is used, one device is configured as the end device by the change of the setup of switchovers of the terminating resistor. The device is delivered in the configuration of the transient member of the network (switchovers in position 0, terminating resistors not connected). These switchovers are accessible after tilting the lid of the terminal board away. If required, it is possible to set-up the date and time by means of communication interface. Note: Setup of time simultaneously for the whole group of the devices with the same password is possible by means of broadcast (group) address. A detailed description of the set-up is a part of the communication programme HELP. Before the start of the operation, it is necessary to comply with the period of heating of 30 min. INMAT 57 in the open design shall be provided, after commissioning, by an appointed worker of the installation and service organization, with marks of the installation and service organization. The installation seal (mark) secures the sealing screws on the right side of the device (refer to FIGURE 1 – DIMENSIONAL DRAWING).

O P E R A T I O N A N D M A I N T E N A N C E INMAT 57 is equipped with a two-line display for displaying the measured and calculated values, warning messages and data about the configuration. The measured values are displayed in the top line of the alphanumerical display including the units and the relevant text in the bottom line of the display. The texts are displayed including diacritics. To display the warning messages, the bottom line of the display is used. If more conditions were met for displaying an error message during the operation, warning messages are ordered into a list of warning messages, which can be scrolled in the menu Diagnostics. The display can display either only the sign of the error (flashing bell) or the most actual warning messages in the form of a running text. Actions of the diagnostics can be set-up in the menu Setup/Diagnostics or by means of SWK45702. Operation of the device is realized by means of two control push-buttons of the keyboard according to FIGURE 1 – DIMENSIONAL DRAWING. As a default, INMAT 57 is delivered in multi-language design. The user can select the language: Czech, Slovak, Polish, German, English and Russian. The language is set-up by the user directly on the device in the menu Setup/Language or by means of SWK45702. INMAT 57 is equipped with the user menu - User. In this menu, the user can set-up displayed quantities and their sequence. It is possible to choose from all data from the menu Operation. A big advantage of the menu User is that during the common operation of the device, it is possible to see only several key data and it is not necessary to scroll in an extensive menu Operation. The set-up is possible directly from the meter in the menu Setup/PořVmenuUŽIVAT or by means of SWK45702.

SETUP BY MEANS OF CONTROL KEYS The set-up of the parameters is realized from menu SETUP. You can switch to the menu SETUP with the push-button ACK from the MAIN MENU, from position >Menu SETUP with the push-button ACK. Another pressing of ACK returns you back, the push-button MODE moves to individual positions of menu SETUP. The set-up can be protected with a password. This status is signalled on the display with the symbol of a key. In this case, the device requests entering a valid password at first. Without entering it, it is not possible to change or see the adjusted parameters. With the push-button ACK, you can return to the Main menu, with the push-button MODE the device requests entering a valid password, which is signalled with flashing cursor under the first position of the password. With the push-button MODE, you can cyclically change the value (0 to 9). The push-button ACK moves to other position of the entered password, where you can change the value again with the push-button MODE. After correct entering of the fourth position of the password with the push-button ACK, INMAT switches over to the set-up mode. If the password is entered incorrectly, the text "Password is incorrect! Wait ..." is displayed and after approx. 5 sec the device is returned to the Main menu. ENTRY AND SETUP OF THE PASSWORD SETUP/New password - By pressing the push-button ACK, the device switches over to the mode of entering the user password. Another pressing of the push-button ACK returns you back to the menu SETUP, the push-button MODE switches over to entering the first position of the password. With the push-button MODE, it is possible to cyclically change the value (0 to 9). The push-button ACK moves to the next place of the entered password, where you can change the value with the push-button MODE again. After entering the fourth place of the password, the cursor is moved again with the push-button ACK to the second line, where the password is confirmed in a similar way. If the new password is entered incorrectly during the confirmation, the password shall be set-up again. RESETTING QUARTER-HOUR MAXIMUM - SETUP/ > Resetting maxima By pressing the push-button ACK, the device switches over to the mode of RESETTING MAXIMA. Another pressing of the push-button ACK returns you back to the menu SETUP, the push-button MODE switches over to resetting display, which displays time of the last resetting and help "MODE = reset". Pressing the push-button MODE resets the quarter-hour maximum and displays a new time of resetting. A double pressing of ACK returns you back to the menu SETUP. Resetting maxima can be realized from the communication interface by means of the programme SWK45702. DATE / TIME - SETUP/ > Date/time By pressing the push-button ACK, the device switches over to the mode of time setup. Another pressing of the push-button ACK returns you back to the menu SETUP, the push-button MODE switches over to setup of minutes. The item being set-up is signalled with a flashing cursor. A change of the value is realized cyclically with the push-button MODE, another item is selected cyclically with the push-button ACK. After the setup of all items, the push-button ACK switches over to display with the text "Save? ACK=yes". Pressing ACK will save the set-up value and return you to the menu SETUP, the MODE returns to the menu SETUP without saving. The setup of date and time can be realized more comfortably from the communication interface by means of the programme SWK45702. TIME CORRECTION - SETUP/ > Time correction By pressing the push-button ACK, the device switches over to the mode of setup time correction. Another pressing of the push-button ACK returns you back to the menu SETUP, the push-button MODE switches over to the selection for automatic switching over of summer and winter times. The symbol ● means automatic switching over of summer and winter times, the symbol ○ means permanent setup of time without switching over. The change is made with the push-button MODE, the push-button ACK switches over to the menu SETUP. The setup can be realized from the communication interface by means of the programme SWK45702.

Page 13: PRODUCT MANUAL type 457 - zpanp.eu · multi-hole orifices pursuant to ČSN EN ISO 5167-2:2003, orifices with conical input pursuant to ISO TR 15377: 2007, quarter-circle orifices

TP – 304337 PRODUCT MANUAL TYPE 457 - Meter INMAT 57

13 / 34

The parameter Aging Offset (-3 to +3, implicitly 0) can speed up or slow down the clock within the range 0.3 ppm. A positive value slows down, a negative values speeds up. COMMUNICATION - SETUP/ > Communication By pressing the push-button ACK, the device switches over to the mode of setup of the parameters communication. Another pressing of the push-button ACK returns you back to the menu SETUP, the push-button MODE switches over to selection of parity. With the push-button MODE, you will set-up one of the options (without parity/odd/even). The push-button ACK switches over to the set-up of transmission speed. Its value is set-up with the push-button MODE. With another pressing of the push-button ACK, you switch over to the setup of address of the device. A double pressing of ACK returns you back to the menu SETUP. LANGUAGE - SETUP/ > Language By pressing the push-button ACK, the device switches over to the mode of setup of the language of the device. Another pressing of the push-button ACK returns you back to the menu SETUP, the push-button MODE switches over to the current language. With the push-button MODE, another language is set-up cyclically. The fact what language is selected, is signalled with the symbol ● while at the others there is the symbol ○. You will exit the menu with double pressing of the push-button ACK.

Note: Russian is installed in the device only at a special request after an agreement with the manufacturer. DISPLAY - SETUP/ > Display By pressing the push-button ACK, the device switches over to the mode of setup of the parameters of back light and contrast of the display and setup of speed of data refreshing on the display and speed of movement of the texts. Another pressing of the push-button ACK returns you back to the menu SETUP, the push-button MODE switches over to the set-up. The back light can be switched off, permanently switched on or dimmed after the preset number of minutes. With the push-button MODE, the parameter of back light is changed cyclically. The push-button ACK switches over to the setup of contrast of the display, the value of which can be increased with the push-button MODE (next to the value of the contrast, the symbol ▲ is lit), another pressing of ACK switches over to the possibility to decrease the contrast (symbol ▼ is lit). The parameter of the contrast moves within the range 10. The following pressing of ACK enables to set-up time, when data on the display will be refreshed = Refresh. We can increase the time with the push-button MODE (next to the value of the contrast, the symbol ▲ is lit), another pressing of ACK switches over to the possibility to decrease the contrast (the symbol ▼ is lit). We can decrease the time with the push-button MODE. The parameter Refresh can be changed within the range 1s to 9.9s. Implicitly the value 2.1s is established. Use of a longer time is suitable at low ambient temperatures, when the LCD display has a slower response or e.g. if the operator cannot manage to write the status of the indicator during the implicitly set-up time. The following pressing of ACK will enable to set-up the speed of moving the text of the error message and the speed of flashing of the texts. We can increase the time with the push-button MODE (next to the value, the symbol ▲ is lit), another pressing of ACK switches over to the possibility to decrease the speed (the symbol ▼ is lit). The parameter can be changed within the range from 0.05s to 1.50s. Implicitly the value 0.4s is established. A double pressing of ACK returns you back to the menu SETUP. MENU USER - SETUP/ > PořVmenuUžIVAT By pressing the push-button ACK, the device switches over to the mode of selection of items from the menu OPERATION, which will be displayed in the menu USER. Another pressing of the push-button ACK returns you back to the menu SETUP, the push-button MODE switches over to the first item of the menu OPERATION. Displaying the item in the menu USER is indicated with the symbol [● and the fact that the item is not displayed, is indicated with the symbol [○. The selection of the item is realized with the push-button MODE. Switching off and switching on of the display is realized with the push-button ACK. When switching on, the item is ranked on the last place

of the list. It is advantageous to switch off the display of all items at first and them switch them on gradually in the required sequence. You can return to the menu SETUP with the push-button ACK from the place, where the following text is displayed on the display: SETUP/ > PořVmenuUžIVAT and < ACK on the second line. Another possibility is to use the key shortcut, i.e. long pressing of the push-button ACK from any place in the menu. Setup of the items and their sequence in the menu USER can be realized comfortably from the communication interface by means of the programme SWK45702. SETUP OF DIAGNOSTIC MESSAGES - SETUP/ > DiagnostMessages By pressing the push-button ACK, the device switches over to the mode of setup of diagnostic messages. Another pressing of the push-button ACK returns you back to the menu SETUP, the push-button MODE switches over to setup the first diagnostic message. Setup of individual parameters of action of the error message is realized cyclically with the push-button ACK, the selection of another message in the sequence is realized with the push-button MODE. The sequence of the set-up message is identified at the end of the first line of the display; the text of the error message is on the second line. Return to the menu SETUP is possible with the push-button ACK from the place, where the following text is displayed on the display: DiagnosticMessages and < ACK on the second line. Another possibility is to use the key shortcut, i.e. long pressing of the push-button ACK from any place of the menu. Setup of action of the error messages can be realized comfortably from the communication interface by means of the programme SWK45702. Error messages in INMAT are divided into two groups: - system (defective battery, Hw errors...) - their message is

permanently functional, setup cannot be changed - from the application (errors of probes, exceeded flow,

etc.) - their action can be defined Error messages are displayed including the description of the error and the date and time of occurrence of the error. System messages are set-up firmly (!, Hold, Msg), action of the error message from the application can be set-up by the user directly on the device in the menu SETUP or by means of SWK45702. Meaning of setup: "!" ● - in case of an error, back light of the display flashes as a warning ○ - flashing of back light in case of an error is switched off "Hold" ● - If an error occurs, the error message remains even after the end of the error till the confirmation with ACK ○ - Error messages are displayed only for the period of existence of the error "Msg" ● - Error messages roll on the bottom line of the display ○ - On the display, a bell is flashing, errors are listed in the menu Diagnostics Possible combinations ! ○Hold ○Msg ○ - error message switched off ! ○Hold ○Msg ● - on the display for the period of existence of the error, the error message is rolling ! ○Hold ●Msg ○ - on the display, only the bell is

flashing and error remains saved till the confirmation with ACK

! ○Hold ●Msg ● - it rolls on the display and the error remains stored till the confirmation with ACK

! ●Hold ○Msg ○ - in case of an error, a bell is flashing on the display as warning ! ●Hold ○Msg ● - in case of an error, display flashes as a

warning and error message rolls on the display

! ●Hold ●Msg ○ - in case of an error, display flashes as a warning, error remains stored till the confirmation with ACK, a bell is flashing !●Hold ●Msg ● - in case of an error, a display is flashing

as warning, the error remains stored till the confirmation with ACK, error message rolls

Page 14: PRODUCT MANUAL type 457 - zpanp.eu · multi-hole orifices pursuant to ČSN EN ISO 5167-2:2003, orifices with conical input pursuant to ISO TR 15377: 2007, quarter-circle orifices

TP – 304337 PRODUCT MANUAL TYPE 457 - Meter INMAT 57

14 / 34

Note: In the said sequence, action of the error message is changed during the set-up. BATTERY - SETUP/ > Battery By pressing the push-button ACK, the device switches over to the mode of measurement of the battery voltage. Another pressing of the push-button ACK returns you back to the menu SETUP, the push-button MODE switches over to the mode of measurement. On the display, the valid value of voltage of the battery and its status (OK for good and KO for discharged battery) is displayed within three seconds. On the first line of the display, the temperature TBAT is displayed (inside the box of the device) and the period of temperature of compensation of the real time clock, which can be adjusted to 64, 128, 256 or 512s. Implicitly the value 512s is set-up. A shorter period means more frequent compensation at the expense of shortening service life of the battery. A double pressing of ACK returns you back to the menu SETUP.

Warning! Voltage of the battery is checked after the start-up of the device and once per day at 24:00. Possible poor condition of the battery is indicated by the diagnostic system. The battery is also changed during the follow-up certification. PUSH-BUTTONS Push-button MODE This push-button enables a gradual selection of display of the values of individual quantities from the selected menu. After pressing the push-button, the following data is displayed automatically. The push-button is provided with the function auto-repeat. i.e. when it is pressed, the displayed quantities are selected automatically. The measurement and other functions are not impacted by the activation of the push-button MODE. In the menu SETUP, the push-button MODE is used for the change of the set-up item. Push-button ACK The push-button ACK has several functions according to the mode, in which the device operates. The main function is back scrolling in the items of the menu. The second function is switching over between individual menus. Another function is switching over of individual set-up items in the menu SETUP (e.g. at the set-up of the password). Key shortcuts: - Long pressing of the push-button ACK will return you from

anywhere to the MAIN MENU to the place for switching over to the menu USER.

- By pressing the push-button ACK, following long pressing of the push-button MODE and holding both, you switch over to the menu DIAGNOSTICS. Then you need to release the push-button ACK and then MODE.

DESCRIPTION OF THE STRUCTURE OF DISPLAYED DATA The displayed data is divided into several groups - MAIN MENU, OPERATION, USER, BALANCE, DIAGNOSTICS, SETUP, CONFIG AND SERVICE. Switching over between individual groups of data is realized as follows:

1) By means of the push-button MODE, we can select the text for switching over in the first line of the display

(e.g. OPERATION -> service). The current mode is displayed in capital letters, while small letters indicate the mode, to which you can switch over.

2) By pressing the push-button ACK (refer to help on the second line of the display), we select a new mode. The text is changed to the opposite one (SERVICE -> operation)

3) With the push-button MODE, we can now select the displayed data from the selected menu.

MAIN MENU The main menu is used for switching over between individual modes: USER, OPERATION, BALANCE, DIAGNOSTICS, SETUP, CONFIG AND SERVICE – refer to FIGURE 5 - STRUCTURE OF MAIN MENU. OPERATION In the menu OPERATION, virtually all assessed quantities are displayed, including time data and user-adjustable string, where the user can set-up e.g. the name of the measured circuit etc. - refer to FIGURE 6 - STRUCTURE OF MENU OPERATION. USER In the menu USER, the selected items are displayed from the menu OPERATION - refer to FIGURE 7 - STRUCTURE OF MENU USER. The user can set-up not only what items will be displayed but also their sequence. The selection and set-up is possible from the menu SETUP or from the computer by means of the service programme SWK45702. BALANCE In this menu, flown quantity and energy for the last hours, days, month and years are displayed. Structure of the data is in FIGURE 8 - STRUCTURE OF MENU BALANCE. You will exit the menu with a long pressing of the push-button ACK. DIAGNOSTICS This menu displays error messages, i.e. their number and for messages also the time of occurrence of the error and text of the error message, refer to FIGURE 9 - STRUCTURE OF MENU DIAGNOSTICS. Individual errors can be confirmed in this menu and deleted by pressing the push-button ACK. The symbol of the bell in the place between the date and time, which means a sign of an error, disappears. If the error still continues, the symbol of the bell and the current time appear again. SETUP In this menu, you can set-up a new password, date and time, automatic switching over of summer and winter times, parameters of the communication interface, select language of the device, set-up dimming of the back light of the display, contrast of the display and speed of refreshing of the data on the display, set-up items in the menu USER, action of the diagnostic messages, display the status of the battery and reset the maxima. Changes of the setup can be protected with a password. The active user password is signalled in the menu SETUP with a symbol of the key. STRUCTURE OF MENU SETUP without the password is in FIGURE 10, with the password in FIGURE 11. CONFIG The configuration data include the data about the type number and manufacturing number of the device, version of calculations, version of the firmware. This menu also displays the type of application, calculated parameters, ranges of input and output signals, their meaning etc. Structure of the data is in FIGURE 12. Note: In the mode CONFIG, on the second line of the display, only a sign of the possible error detected by the diagnostics is displayed. The running description of the error is not displayed. Possible warning message appears after switching over to another mode (USER, OPERATION, SERVICE). If the operator leaves the device in the mode CONFIG, the device switches over after eight minutes to the mode USER to the 1st . item, which ensures displaying of warning messages. SERVICE In the menu SERVICE, parameters of communication interface are displayed (address, speed, parity); then it displays additional data, which are used for more detail information about the measured object (enthalpy and specific volume of the medium, temperature of saturation, ...) and values of input signals. For the STRUCTURE OF MENU SERVICE - refer to FIGURE 13 - STRUCTURE OF MENU SERVICE.

Page 15: PRODUCT MANUAL type 457 - zpanp.eu · multi-hole orifices pursuant to ČSN EN ISO 5167-2:2003, orifices with conical input pursuant to ISO TR 15377: 2007, quarter-circle orifices

TP – 304337 PRODUCT MANUAL TYPE 457 - Meter INMAT 57

15 / 34

FIGURE 4 – STRUCTURE OF MAIN MENU

MAIN MENU> Menu CONFIG

MODE

MODE

MODE

MODE

MODE

MODE

ACK

MODE

USER > Main Menu

ACK OPERATION > Main Menu

BALANCE< Main Menu

ACK

DIAGNOSTICS X< Main Menu

ACK

ACK SETUP> New password

CONFIG< Main Menu

ACK

SERVICE< Main Menu

ACK

ACK

ACK

ACK

MAIN MENU> Menu SETUP

MAIN MENU> Menu SERVICE

MAIN MENU> Menu DIAGNOSTICS

MAIN MENU< Menu OPERATION

MAIN MENU< Menu USER

MAIN MENU< Menu BALANCE

Page 16: PRODUCT MANUAL type 457 - zpanp.eu · multi-hole orifices pursuant to ČSN EN ISO 5167-2:2003, orifices with conical input pursuant to ISO TR 15377: 2007, quarter-circle orifices

TP – 304337 PRODUCT MANUAL TYPE 457 - Meter INMAT 57

16 / 34

FIGURE 5 - STRUCTURE OF MENU OPERATION

FIGURE 6 - STRUCTURE OF MENU USER

ACK

OPERATION > Main Menu

ACK

MODE

MODE

MODE

MODE

MODE

1234d 12h 12m Operation time

User defined string

Oper. display 1 Item description

Oper. display x Item description

MODE

Wednesday 12:12:1212 September 2009

ACK

ACK

ACK

ACK

MAIN MENU< Menu OPERATION

MODE

MODE

User display 1Item description

User display xItem description

USER > Main Menu

ACK

MODE

ACK

ACK

MAIN MENU< Menu USER

Page 17: PRODUCT MANUAL type 457 - zpanp.eu · multi-hole orifices pursuant to ČSN EN ISO 5167-2:2003, orifices with conical input pursuant to ISO TR 15377: 2007, quarter-circle orifices

TP – 304337 PRODUCT MANUAL TYPE 457 - Meter INMAT 57

17 / 34

FIGURE 7 - STRUCTURE OF MENU BALANCE

Selecting value with push-button MODE

Selecting item with push-button ACK

0.00000000000000

2009 mmdd.hh:mm

0.00000000000000

2010 mmdd.hh:mm

MODE

MODE

MODE

0.00000000000000

2000 mmdd.hh:mm

ACK

ACK

ACK

ACK

ACK

ACK

0.00000000000000 rrrrmmdd.hh: 00

MODE

MODE

ACK

0.00000000000000 rrrmmdd.hh: 15

MODE

ACK

0.00000000000000 rrrmmdd.hh: 45

MODE

ACK

0.00000000000000

2010mmdd.hh:mm

MODE

0.00000000000000 _ rrrrmmdd.hh:mm

BALANCE < Main Menu

ACK

MODE

MODE

0.00000000000000_ rrrmmdd.hh:mm

MODE

After switch-over, identification of variable is displayed briefly, e.g.: 0.0000 E1 [GJ] _ rrrmmdd.hh:mm

ACK

0.00000000000000

2010mmdd.hh:mmACK

MODE

MODE

0.00000000000000

2010mmdd.hh:mm

MODE

0.00000000000000

2010mmdd.hh:mm

ACK

ACK

ACK

ACK

ACK

ACK

MAIN MENU < Menu BALANCE

Page 18: PRODUCT MANUAL type 457 - zpanp.eu · multi-hole orifices pursuant to ČSN EN ISO 5167-2:2003, orifices with conical input pursuant to ISO TR 15377: 2007, quarter-circle orifices

TP – 304337 PRODUCT MANUAL TYPE 457 - Meter INMAT 57

18 / 34

FIGURE 8 - STRUCTURE OF MENU DIAGNOSTICS

MODE

MODE

rrrmmdd hh:mmerror message 1

rrrmmdd hh:mmerror message x

DIAGNOSTICS X< Main Menu

ACK

MODE

Date and time of error occurrence

MAIN MENU< Menu User

ACK

Number of errormessages

MAIN MENU > Menu DIAGNOSTICS

Error sign ACK = confirmation

Text of error message

Page 19: PRODUCT MANUAL type 457 - zpanp.eu · multi-hole orifices pursuant to ČSN EN ISO 5167-2:2003, orifices with conical input pursuant to ISO TR 15377: 2007, quarter-circle orifices

TP – 304337 PRODUCT MANUAL TYPE 457 - Meter INMAT 57

19 / 34

FIGURE 9 - STRUCTURE OF MENU SETUP - without password

SETUP> New password

SETUP > Language

MODE

MODE

MODE

MODE

MODE

MODE

MODE

New password: 0000Confirm: ****

SETUP > RS485/RS232

SETUP

> Menu User

ACK

ACK

ACK

ACK

Item x [ Item description x

ACK

MODE selects another item

for displayACK selectsor cancels

selection

SETUP

> Display

ACK

SETUP > Battery

ACK

SETUP > Date/time

ACK

SETUP > Time correction

ACK

SETUP

> Reset maxima

ACKSETUP

> DiagnostMessages

MODE

MODE

! Hold Msg[xyerror massage

MODE selectsanother item

ACK cyclicallychanges type

of messages

SETUP < Main Menu

MODE

ACK

MODE

Time setup can be saved immediately(push-button MODE)

Cz Sk Pl En De Ru

Wednesday 18:55:00 9 September 2009

Summer/winter:[

tBAT 28.75°C 512sVBAT 3.03V OK

PořVMenuUživatel< ACK

MODE MODE

MODE

MODE = reset 20091130-14:49

1 115200 -Adr Speed Parity

Change is savedwithin 1s after exit of

Menu Setup

Light: -min 0Refr: 2.1 0.40 s

ACK MAIN MENU > Menu SETUP

Page 20: PRODUCT MANUAL type 457 - zpanp.eu · multi-hole orifices pursuant to ČSN EN ISO 5167-2:2003, orifices with conical input pursuant to ISO TR 15377: 2007, quarter-circle orifices

TP – 304337 PRODUCT MANUAL TYPE 457 - Meter INMAT 57

20 / 34

FIGURE 10 - STRUCTURE OF MENU SETUP - with password

SETUP > New password

SETUP > Language

MODE

MODE

MODE

MODE

MODE

MODE

MODE

New password: 0000Confirm: ****

SETUP > RS485/RS232

SETUP > Menu User

ACK

ACK

ACK

ACK

Item x [ Item description x

ACK

MODE selectsanother item for display ACK selects

or cancels

selection

SETUP > Display

ACK

SETUP > Battery

ACK

SETUP > Date/time

ACK

SETUP > Time correction

ACK

SETUP > Resetting maxima

ACKSETUP > DiagnostMessages

MODE

MODE

! Hold Msg[xyerror message

MODE selectsanother item

ACK cyclicallychanges type

of messages

SETUP < Main Menu

MODE

ACK

MODE

ACK

Time setup can

be saved immediately

(push-button MODE)

Cz Sk Pl En De Ru

Wednesday 18:55:00 9 September 2009

Summer/winter: [

tBAT 28.75°C 512sVBAT 3.03V OK

PořVMenuUživatel< ACK

MODE MODE

MAIN MENU > Menu SETUP

SETUP < ACK

MODE

Sign of passwordapplication

MODE

Passwordentry

MODE = reset 20091130-14:49

1 115200 -Adr Speed Parity

Change is saved

within 1s after exit of Menu Setup

Light: -min 0Refr: 2.1 0.40 s

Page 21: PRODUCT MANUAL type 457 - zpanp.eu · multi-hole orifices pursuant to ČSN EN ISO 5167-2:2003, orifices with conical input pursuant to ISO TR 15377: 2007, quarter-circle orifices

TP – 304337 PRODUCT MANUAL TYPE 457 - Meter INMAT 57

21 / 34

FIGURE 11 - STRUCTURE OF MENU CONFIG FIGURE 12 - STRUCTURE OF MENU SERVICE

USER AND METROLOGICAL PASSWORDS The meter INMAT 57 is equipped with USER and METROLOGICAL passwords. These passwords block changes of some parameters (time and date, user constants ....). When entering any of the protected values, INMAT 57 requests entering a valid password. If the password is correct, it permits entry of the data to the device. The user password can be changed or blocked. For this change, it is necessary to know the current user password. The user password can be deactivated permanently by entering the value of the password "0000" (4 zeros). By entering another value, the function of the password is reset. The length of the password is 4 characters ['0' to '9'], and it can be changed in the menu Setup / User password or from the computer and programme swk45702. The password can be changed by entering the currently valid password at first; after its confirmation, enter the new password 2 × (with the confirmation). The second entry of the password is intended for inspection and if it does not match the first one, the new password is not set-up. INMAT 57 is delivered with the user password set-up to 0000, i.e. the password is switched off. The meter INMAT 57 in design for measurement of gas enables a change of its composition (according to design dv, %CO2, %N2, %H2, Hs, Vc, Pc, Tc, ). The change is realized by software by means of a computer connected to the communication interface. The change is possible in cases when compressibility is pursuant to AGA NX 19mod., SGERG 88 or virial development. The change of the parameters of gas is protected with the user and metrological passwords, without which such change is not possible. When entering any value to INMAT (composition of natural gas, time and date, address, user constants, parameters of archiving ...), INMAT 57 requests entry of the

valid password by means of a request on the computer. If the password is correct, it permits entry of the data to the device for the period of three minutes. After this period, the access is blocked and further entering of data to INMAT 57 requires a repeated entry of the valid password. When changing the parameters of gas, data are entered to the archive of changes. The following is stored to the archive of changes: date and time of change, new parameters and who made the change (user, metrologist or change without the password when the password is deactivated). The archive of changes can be read by means of interface RS485. By means of the user password, it is possible to realize 100 changes; when this number is exceeded, other changes can only be realized with the application of the metrological password. This password can release the archive of changes for the new set-up (again 100 changes). A detailed description of work with the password is included in Help of the service programme delivered by the manufacturer of the device. A forgotten password can only be unblocked at the manufacturer at the expense of a violation of the seals and loss of validity of the certification! MAINTENANCE Replacement of the internal battery (CR2032) is realized during the follow-up certification, or, as the case may be, at the latest after 5 years. If the internal battery is discharged sooner, it shall be replaced. Discharging of the internal battery is signalled by the diagnostics of the device. Status of the battery can be identified also in the menu SETUP/ BATTERY. During the replacement of the battery, the stored data remain without damage. If power supply is switched off during the replacement of the battery, it is necessary to set-up date and time in the device. OPERATION AND MAINTENANCE OF RATED METERS For rated meters, it is necessary to comply with the prescribed period for follow-up certification in the intervals identified by the

Name of application

MODE

MODE

MODE

MODE

MODE

Specification of circuit

Calculation version XXXXXXXXXXXXXXXX

FWrrrmmdd hh:mmDTrrrmmdd hh:mm

CONFIG < Main Menu

ACK

MODE SN:1234567890 TYPE 457 123456

ACK

ACK

ACK

ACK

ACK

MODE MAIN MENU > Menu CONFIG

MODE

MODE

MODE

MODE

Additional quantities

r1 175.22 ohm Thermometer resistance

r2 115.68 ohm Thermometer resistance

i3 17.522 mA Manometer signal

SERVICE< Main Menu

ACK

MODE

MODE

imp1 0 imp Imp.from flow meter

Input signalsby design

A: 1 r: 9600 Bd Rx Tx [0000]

MODE

ACK

ACK

ACK

ACK

ACK

ACK

MAIN MENU> Menu SERVICE

Page 22: PRODUCT MANUAL type 457 - zpanp.eu · multi-hole orifices pursuant to ČSN EN ISO 5167-2:2003, orifices with conical input pursuant to ISO TR 15377: 2007, quarter-circle orifices

TP – 304337 PRODUCT MANUAL TYPE 457 - Meter INMAT 57

22 / 34

Decree of the Ministry of Industry and Trade No. 345/2002 Coll., as amended. Replacement and connection of the verified devices shall be realized by an appointed worker of the installation and service organization, who shall seal the sensors again. Only a worker of AMS or ČMI may violate the official mark. If the official mark was invalidated or removed, validity of certification of the meter expires.

S P A R E P A R T S The design of the device does not require any delivery of spare parts. WARRANTY Pursuant to Section 429 of the Commercial Code and the provisions of Section 620 (2) of the Civil Code, the manufacturer warrants for technical and operation parameters of the product specified in the manual. The warranty period is 24 months from the receiving of the product by the customer, unless established otherwise in the contract. The rejection of defects shall be enforced in writing at the manufacturer within the warranty period. The rejecting side shall identify the product name, ordering and manufacturing numbers, date of issue and number of the delivery note, clear description of the occurring defect and the subject of the claim. If the rejecting side is invited to send the device for repair, it shall do so in the original package of the manufacturer and/or in another package ensuring safe transport. The warranty shall not apply to defects caused by unauthorized intervention into the device, its forced

mechanical damage or failure to comply with operation conditions of the product and the product manual.

R E P A I R S The devices shall be repaired by the manufacturer. They shall be sent for repair in the original or equal package marked pursuant to ČSN EN ISO 780: HANDLE WITH CARE – FRAGILE.

D I S A B L I N G A N D L I Q U I D A T I O N They shall be realized in compliance with the Waste Act No. 106/2005 Coll. The product and its package do not include any parts that could impact the environment. Products that are withdrawn from operation, including their packages (with the exception of products marked as electrical equipment for the purposes of return withdrawal and separate salvage of electrical waste and battery), may be disposed of to sorted or unsorted waste pursuant to the type of waste. The manufacturer realizes free return withdrawal of marked electrical equipment (from 13.8.2005) and batteries from the consumer and points out the danger connected with their illegal disposal. The package of the device can by recycled completely. Metal parts of the products are recycled, non-recyclable plastic materials, electrical waste and the battery shall be disposed of in compliance with the aforesaid Act.

FIGURE 13 - SCHEME OF CONNECTION AND CONNECTING THE TERMINAL BOARD Measurement of heat transferred by water steam - direct method Measurement of flow of gases a) Temperature measured with resistance thermometer Pt100 in four-wire connection

Transient

End

Page 23: PRODUCT MANUAL type 457 - zpanp.eu · multi-hole orifices pursuant to ČSN EN ISO 5167-2:2003, orifices with conical input pursuant to ISO TR 15377: 2007, quarter-circle orifices

TP – 304337 PRODUCT MANUAL TYPE 457 - Meter INMAT 57

23 / 34

b) Temperature measured with thermometer with two-wire converter

t Signal from temperature sensor p Signal from pressure sensor Q Signal from flow meter or pressure difference sensor or water meter or gas meter Measurement of heat transferred by water steam - indirect method Temperature measured with resistance thermometers Pt100 in four-wire connection

t Signal from temperature sensor - steam tk Signal from temperature sensor - condensate

p Signal from pressure sensor Q Signal from flow meter or water meter

Transient

End

Transient

End

Transient

End

Page 24: PRODUCT MANUAL type 457 - zpanp.eu · multi-hole orifices pursuant to ČSN EN ISO 5167-2:2003, orifices with conical input pursuant to ISO TR 15377: 2007, quarter-circle orifices

TP – 304337 PRODUCT MANUAL TYPE 457 - Meter INMAT 57

24 / 34

Measurement of flow and heat transferred by water, measurement of cold a) Temperature measured with resistance thermometer Pt100 in four-wire connection

b) Temperature measured with thermometer with two-wire converter

tp Signal from temperature sensor - transferring piping tv Signal from temperature sensor - return piping Q Signal from flow meter or pressure difference sensor or water meter

Transient

End

Transient

End

Page 25: PRODUCT MANUAL type 457 - zpanp.eu · multi-hole orifices pursuant to ČSN EN ISO 5167-2:2003, orifices with conical input pursuant to ISO TR 15377: 2007, quarter-circle orifices

TP – 304337 PRODUCT MANUAL TYPE 457 - Meter INMAT 57

25 / 34

Measurement of flown quantity of liquids a) Temperature measured with resistance thermometer Pt100 in four-wire connection

b) Temperature measured with thermometer with two-wire converter

t Signal from temperature sensor ( p ) Signal from pressure sensor (optionally) Q Signal from flow meter or pressure difference sensor or water meter

Transient

End

Transient

End

Page 26: PRODUCT MANUAL type 457 - zpanp.eu · multi-hole orifices pursuant to ČSN EN ISO 5167-2:2003, orifices with conical input pursuant to ISO TR 15377: 2007, quarter-circle orifices

TP – 304337 PRODUCT MANUAL TYPE 457 - Meter INMAT 57

26 / 34

Measurement of flown quantity of fluids by mass flow meter

Q Signal from mass flow meter Options of combinations of analogue inputs a) 3x current input

Transient

End

Transient

End

Page 27: PRODUCT MANUAL type 457 - zpanp.eu · multi-hole orifices pursuant to ČSN EN ISO 5167-2:2003, orifices with conical input pursuant to ISO TR 15377: 2007, quarter-circle orifices

TP – 304337 PRODUCT MANUAL TYPE 457 - Meter INMAT 57

27 / 34

b) 2x current input + 1x resistance input

c) 1x current input + 2x resistance input

Transient

End

Transient

End

Page 28: PRODUCT MANUAL type 457 - zpanp.eu · multi-hole orifices pursuant to ČSN EN ISO 5167-2:2003, orifices with conical input pursuant to ISO TR 15377: 2007, quarter-circle orifices

TP – 304337 PRODUCT MANUAL TYPE 457 - Meter INMAT 57

October 2011 ZPA Nová Paka, a.s.

28 / 34

Meaning of used symbols Two-wire converter 4 to 20 mA (power supplied from INMAT) e.g.: pressure sensor, pressure difference sensor, flow meter Source of current 0/4 to 20 mA REED contact (5 V / 10 mA) Open collector (5 V / 10 mA) Thermometer Pt100 – four-wire connection DC 24V Power supply I1 Current input 1 I2 Current input 2 I3 Current input 3 R1 Resistance input 1 R2 Resistance input 2 IMP/FR Impulse/ frequency input IOUT/IMPOUT Current/ Impulse output S Shielding RS485 Communication interface RS485 A, B Signals of interface RS485 transient Position of switchover for transient device on interface RS485 end Position of switchover for end device on interface RS485 M-Bus Communication interface M-Bus L1, L2 Signals interface M-Bus RS232 Communication interface RS232 (not for billing measurement) Rx, Tx, Signals interface RS232 TABLE 4 – NUMBERING OF SOFTWARE VERSIONS The application version is displayed in the form: "Name X.XX/XXXX" Name: Liquid Liquid Mass Mass flow meter without correction to temperature pressure Steam Steam with direct method ISteam Steam with indirect method Cond Condensate Gas Gas Water Water - heat in water/cold WaterB Water - heat in water, bi-directional flow meter X.--/---- modifications submitted to review in ČMI (addition/extension of calculation) -.XX/---- repairs of application – not submitted to review in ČMI (errors on the display, modifications of text in application, etc.) -.--/XXXX non-metrological modifications – customer requirements (addition of temperature measurement, completion of description on the display etc. ) Example: "Gas 1.00/CMi0"

Page 29: PRODUCT MANUAL type 457 - zpanp.eu · multi-hole orifices pursuant to ČSN EN ISO 5167-2:2003, orifices with conical input pursuant to ISO TR 15377: 2007, quarter-circle orifices

TP – 304337 PRODUCT MANUAL TYPE 457 - Meter INMAT 57

Copyright ZPA Nová Paka, a.s.

29 / 34

QUESTIONNAIRE for INMAT 57

Measurement of flow and heat transferred by water steam with direct method

type 457

QUESTIONNAIRE of ZPA Nová Paka, a.s. - page 1/ 1 Date of filling-in the questionnaire: 1 Product number 4 5 7 1 0 0

2 Verify according to Section 9 of Act No. 505/1990 Coll., (YES, NO)

3 Unit of thermal output, energy and quarter-hour maximum (GJ/h, GJ) or (MW,MWh)

4 Name of circuit (2 lines x max. 16 characters)

5 Calculated flow of a throttling unit in the transferring piping (steam) Mv [t/h]

or the range of the flow meter Qv [m3/h] 0 to

6 Calculated temperature of a throttling unit in the transferring piping (steam) [°C] or reference temperature of the flow meter tv

7 Calculated absolute pressure of a throttling unit in the transferring piping (steam)

[MPa]

or reference pressure of the flow meter pv

8

Overpressure or abs. pressure sensor

range of static overpressure sensor [MPa] 0 to

current signal from overpressure sensor [mA] to 20

range of absolute static pressure sensor [MPa] 0 to

current signal from absolute pressure sensor [mA] to 20

9 Temperature sensor

resistance Pt100 in four-wire connection or

with converter to signal 4 to 20mA with the range [°C] to

10 Signal of flow

quadratic current from sensor dp *) [mA] to 20

range of pressure difference sensor dp1 [kPa]

linear current - from the flow meter [mA] to 20

linear frequency - from the flow meter [Hz] 0 to

impulse [litre/impulse]

type of output (REED, OK, …….)

*) For measurement by means of throttling units, it is necessary to fill in the table: For measurement by means of

throttling units and pressure difference sensor. For measurement by means of throttling units and pressure difference sensor:

Location of temperature sensor: in front of/behind (implicitly behind)

Location of pressure sensor: in front of/behind (implicitly in front of)

The questionnaire shall be accompanied with the calculation of a throttling unit, which includes other required data!

Note: Only the data required for a particular application shall be filled in the questionnaire. Additional information about INMAT:

Page 30: PRODUCT MANUAL type 457 - zpanp.eu · multi-hole orifices pursuant to ČSN EN ISO 5167-2:2003, orifices with conical input pursuant to ISO TR 15377: 2007, quarter-circle orifices

TP – 304337 PRODUCT MANUAL TYPE 457 - Meter INMAT 57

Copyright ZPA Nová Paka, a.s.

30 / 34

QUESTIONNAIRE for INMAT 57

Measurement of flow and heat transferred by water steam with indirect method

type 457

QUESTIONNAIRE of ZPA Nová Paka, a.s. - page 1/ 1 Date of filling-in the questionnaire: 1 Product number 4 5 7 2 0 0

2 Verify according to Section 9 of Act No. 505/1990 Coll., (YES, NO)

3 Unit of thermal output, energy and quarter-hour maximum (GJ/h, GJ) or (MW,MWh)

4 Name of circuit (2 lines x max. 16 characters)

5 The range of the flow meter (condensate) Mvk [t/h]

or Qvk [m3/h] 0 to

6 Reference (most frequent) temperature of the condensate tvk [°C]

7 Reference (most frequent) temperature in the transferring piping (steam) tv

[°C]

8 Reference (most frequent) absolute pressure in the transferring piping (steam) pv [MPa]

9 Maximum operating temperature of water steam [°C]

10 Maximum operating absolute pressure of steam [MPa]

11

Overpressure or abs. pressure sensor

range of static overpressure sensor [MPa]

current signal from overpressure sensor [mA] to 20

range of absolute static pressure sensor [MPa]

current signal from absolute pressure sensor [mA] to 20

12 Temperature sensor

resistance Pt100 in four-wire connection or

with converter to signal 4 to 20mA with the range [°C] to

13 Signal of flow

linear frequency - from the flow meter [Hz] 0 to

impulse [litre/impulse]

type of output (REED, OK, …….)

Note: Only the data required for a particular application shall be filled in the questionnaire. Additional information about INMAT:

Page 31: PRODUCT MANUAL type 457 - zpanp.eu · multi-hole orifices pursuant to ČSN EN ISO 5167-2:2003, orifices with conical input pursuant to ISO TR 15377: 2007, quarter-circle orifices

TP – 304337 PRODUCT MANUAL TYPE 457 - Meter INMAT 57

Copyright ZPA Nová Paka, a.s.

31 / 34

QUESTIONNAIRE for INMAT 57

Measurement of flow and heat transferred by water, measurement of cold

type 457

QUESTIONNAIRE of ZPA Nová Paka, a.s. - page 1/ 1 Date of filling-in the questionnaire: 1 Product number 4 5 7 3 0 0

2 Verify according to Section 9 of Act No. 505/1990 Coll., (for heavy industry) or (YES, NO)

3 Unit of thermal output, energy and quarter-hour maximum (GJ/h, GJ) or (MW,MWh)

4 Name of circuit (2 lines x max. 16 characters)

5 Measurement of heat or cold (implicitly heat)

6 Measured medium (implicitly water)

7 Calculated flow of a throttling unit in the transferring piping Mv1 [t/h]

or the range of the flow meter Qv1 [m3/h] 0 to

8 Calculated temperature of a throttling unit in the transferring i i [°C]

or reference temperature of the flow meter tv1

9 Temperature sensor

resistance Pt100 in four-wire connection or

with converter to signal 4 to 20mA with the range [°C] to

10 Signal of flow

quadratic current from sensor dp *) [mA] to 20

range of pressure difference sensor dp1 [kPa]

linear current - from the flow meter [mA] to 20

linear frequency - from the flow meter [Hz] 0 to

impulse [litre/impulse]

type of output (REED, OK, …….)

11 Measurement of bi-directional flow meter (implicitly NO) (YES, NO)

12 Location of throttling unit or flow meter: 1- in transferring piping

2 - in return piping

13 Most frequent temperature difference (t1p - t1v) [°C]

*) For measurement by means of throttling units, it is necessary to fill in the table: For measurement by means of

throttling units and pressure difference sensor. For measurement by means of throttling units and pressure difference sensor:

Location of temperature sensor: in front of/behind (implicitly behind)

Location of pressure sensor: in front of/behind (implicitly in front of)

The questionnaire shall be accompanied with the calculation of a throttling unit, which includes other required data!

Note: Only the data required for a particular application shall be filled in the questionnaire. Additional information about INMAT:

Page 32: PRODUCT MANUAL type 457 - zpanp.eu · multi-hole orifices pursuant to ČSN EN ISO 5167-2:2003, orifices with conical input pursuant to ISO TR 15377: 2007, quarter-circle orifices

TP – 304337 PRODUCT MANUAL TYPE 457 - Meter INMAT 57

Copyright ZPA Nová Paka, a.s.

32 / 34

QUESTIONNAIRE for INMAT 57

Measurement of flow of fluids

type 457

QUESTIONNAIRE of ZPA Nová Paka, a.s. - page 1/1 Date of filling-in the questionnaire: 1 Product number 4 5 7 4 0 0

2 Verify according to Section 9 of Act No. 505/1990 Coll., NOT POSSIBLE

1. Circuit 3 Name of circuit (2 lines x max. 16 characters)

4 Measured liquid

5 Calculated flow of a throttling unit in the transferring piping Mv1 [t/h]

or the range of the flow meter Qv1 [m3/h]

6 Calculated temperature of a throttling unit in the transferring i i [°C]

or reference temperature of the flow meter tv1

7 Temperature sensor

resistance Pt100 in four-wire connection or

with converter to signal 4 to 20mA with the range [°C] to

8 Signal of flow

quadratic current from sensor dp *) [mA] to 20

range of pressure difference sensor dp1 [kPa]

linear current - from the flow meter [mA] to 20

linear frequency - from the flow meter [Hz] 0 to

signal of the flow meter - impulse [litre/impulse]

type of output (REED, OK, …….)

9 Measurement with bi-directional flow meter (implicitly NO) (YES, NO) *) For measurement by means of throttling units, it is necessary to fill in the table: For measurement by means of

throttling units and pressure difference sensor. For measurement by means of throttling units and pressure difference sensor:

Location of temperature sensor: in front of/behind (implicitly behind)

Location of pressure sensor: in front of/behind (implicitly before)

The questionnaire shall be accompanied with the calculation of a throttling unit, which includes other required data!

Note: Only the data required for a particular application shall be filled in the questionnaire.

Additional information about INMAT:

Page 33: PRODUCT MANUAL type 457 - zpanp.eu · multi-hole orifices pursuant to ČSN EN ISO 5167-2:2003, orifices with conical input pursuant to ISO TR 15377: 2007, quarter-circle orifices

TP – 304337 PRODUCT MANUAL TYPE 457 - Meter INMAT 57

Copyright ZPA Nová Paka, a.s.

33 / 34

QUESTIONNAIRE for INMAT 57 Measurement of flow of gases

type 457

QUESTIONNAIRE of ZPA Nová Paka, a.s. - page 1/ 2 Date of filling-in the questionnaire:

1 Product number 4 5 7 5 0 0

2 Verify according to Section 9 of Act No. 505/1990 Coll., (YES, NO)

3 Name of circuit (2 lines x max. 16 characters)

4 Measured gas - refer to Table Measured gas - codes code

5 Calculated flow of throttling unit or range of flow meter Qv with parameters p = kPa abs., t = °C

[m3/h] 0 to

6 Calculated temperature of throttling unit or reference temperature of flow meter tv [°C]

7 Calculated absolute pressure of throttling unit or reference pressure of flow meter pv [MPa]

8 Maximum operating temperature of gas [°C]

9 Maximum operating absolute pressure of gas [MPa]

10

Overpressure or abs. pressure sensor

range of static overpressure sensor [MPa]

current signal overpressure [mA] to 20

range of absolute static pressure sensor [MPa]

current signal from absolute pressure sensor [mA] to 20

11 Temperature sensor

resistance Pt100 in four-wire connection or

with converter to signal 4 to 20mA with the range [°C] to

12 Signal of flow

quadratic current from sensor dp *) [mA] to 20

range of pressure difference sensor dp1 [kPa]

linear current from the flow meter [mA] to 20

linear frequency from the flow meter [Hz] 0 to

impulse from the flow meter or the gas meter [m3/ impulse]

type of output (REED, OK, …….)

13 Re-calculation to status

101.325 kPa, 0 °C - 1 Vn [m3]

101.325 kPa, 15 °C - 2 Vn [m3]

98.0665 kPa, 20 °C - 3 Vn [m3]

other status pn = kPa abs., tn = °C - 4 Vn [m3]

15 Density of measured gas r at p = kPa abs., t = °C [kg/m3]

Gas composition COMPOSITION OF NATURAL GAS FOR GAS MIXTURE

Relative density dv [1] Item Name Content

Content of CO2 [mol %] 1 [mol %]

Content of N2 (for AGANX19mod.) [mol %] 2 [mol %]

Content of H2 (for SGERG-88) [mol %] 3 [mol %]

Calorific value Hs (for SGERG-88) [MJ/m3] 4 [mol %] *) For measurement by means of throttling units, the table shall be filled in: For measurement by means of throttling

units and the pressure difference sensor.

Page 34: PRODUCT MANUAL type 457 - zpanp.eu · multi-hole orifices pursuant to ČSN EN ISO 5167-2:2003, orifices with conical input pursuant to ISO TR 15377: 2007, quarter-circle orifices

TP – 304337 PRODUCT MANUAL TYPE 457 - Meter INMAT 57

Copyright ZPA Nová Paka, a.s.

34 / 34

QUESTIONNAIRE of ZPA Nová Paka, a.s. - page 2/ 2 For measurement by means of throttling units and the pressure difference sensor:

Location of temperature sensor: in front of/behind (implicitly behind)

Location of pressure sensor: in front of/behind (implicitly in front of)

The questionnaire shall be accompanied with the calculation of a throttling unit, which includes other required data!

Measured gas - codes: acetylene C2H2 1

ammoniac NH3 2

argon Ar 3

ethylene C2H6 4

benzene C6H6 5

butane C4H10 6

chlorine Cl2 7

hydrogen chloride HCl 8

helium He 9

air 10

methane CH4 11

neon Ne 12

propane C3H4 13

oxygen O2 14

sulphur dioxide SO2 15

carbon disulphide CS2 16

sulphide H2S 17

nitrous oxide N2O 18

nitrogen N2 19

hydrogen H2 20

natural gas - it is necessary to fill in a table of composition of natural of gas 21

carbon dioxide CO2 22

other medium - it is necessary to fill in a table for mixture of gas 99

Note: Only the data required for a particular application shall be filled in the questionnaire.

Additional information about INMAT: