January 2005 1 Product manual LEANtouch (monochrome), SMARTtouch (monochrome, colour) Type: 6136/30M-500, 6136/100M-500, 6136/100C-500, 6136/100CB 6936/30M, 6936/100M, 6936/100C, 6936/100CB Intelligent Installation Systems ABB i-Bus ® EIB ABB Powernet EIB

Transcript of Product manual ABB i-Bus EIB ABB i-bus EIB ABB … · ABB i-bus ® EIB ABB Powernet EIB ... 9...

Page 1: Product manual ABB i-Bus EIB ABB i-bus EIB ABB … · ABB i-bus ® EIB ABB Powernet EIB ... 9 Functions of the panel software 2 - 11 ... Touch-sensitive display 320 x 240 pixels

January 2005 1

ABB i-bus® EIBABB Powernet EIB

Product manual

LEANtouch (monochrome),SMARTtouch (monochrome, colour)Type: 6136/30M-500, 6136/100M-500,

6136/100C-500, 6136/100CB6936/30M, 6936/100M,6936/100C, 6936/100CB

Intelligent Installation Systems

ABB i-Bus® EIBABB Powernet EIB

Page 2: Product manual ABB i-Bus EIB ABB i-bus EIB ABB … · ABB i-bus ® EIB ABB Powernet EIB ... 9 Functions of the panel software 2 - 11 ... Touch-sensitive display 320 x 240 pixels

2 January 2005

ABB i-bus® EIBABB Powernet EIB

Contents

LEANtouch (monochrome) 6x36/30M(-500) 2 - 4SMARTtouch (monochrome) 6x36/100M(-500) 2 - 5SMARTtouch (colour) 6x36/100C(-500) 2 - 6SMARTtouch B&O 6x36/100CB 2 - 7Application programs 2 - 8Circuit diagram 2 - 8Installation of the supplementary software 2 - 9Functions of the panel software 2 - 11Functional description: Basic settings 2 - 14Functional description: Touch surfaces (Homepage) 2 - 18Functional description: Touch surfaces (Control page) 2 - 26Functional description: Time programs 2 - 41Functional description: IR control 2 - 46Functional description: Room thermostat 2 - 52Functional description: Lightscenes 2 - 61Functional description: Alarm function 2 - 64Functional description: Presence simulation 2 - 66Functional description: Logical functions 2 - 67

Page 3: Product manual ABB i-Bus EIB ABB i-bus EIB ABB … · ABB i-bus ® EIB ABB Powernet EIB ... 9 Functions of the panel software 2 - 11 ... Touch-sensitive display 320 x 240 pixels

January 2005 3

ABB i-bus® EIBABB Powernet EIB

Page 4: Product manual ABB i-Bus EIB ABB i-bus EIB ABB … · ABB i-bus ® EIB ABB Powernet EIB ... 9 Functions of the panel software 2 - 11 ... Touch-sensitive display 320 x 240 pixels

4 January 2005

ABB i-bus® EIBABB Powernet EIB

LEANtouch (monochrome)Type: 6136/30M-500

6936/30M

– Number of touch surfaces 6(possible control pages) on Homepage

– Number of possible functions per 5control page

– Total of operator functions 30– Scope of time programs 5 channels, 5 switching times each– Scope of scenes 32 scenes with max. 10 objects

(loads)– Number of alarm signals 5– Presence simulation max. 10 devices– IR remote control channels 10– Integrated room thermostat– Child protection– Number of logic functions 10

(AND, OR, NAND, NOR, multiplexer,multiplier, GATE, temperature comparator)

Technical Data

Power supply – Nominal voltage 230 V AC +10%– Bus voltage (TP only) 24 V DC– Power consumption 10 W

Operating and display elements – Touch-sensitive display 320 x 240 pixels16 grey shades (monochrome)

Connections – Power supply Screw plug-in terminals up to 2.5 mm²– EIB bus connection (TP only) Screw plug-in terminals up to 1.5 mm²– Multimedia/SD card 1 module slot at the front

Type of protection – IP 20, EN 60 529Protection class – IIAmbient temperature range – Operation 0 °C to + 45 °C

– Storage and transport - 20°C to + 60 °CDimensions – Panel with cover frame 184.6 x 218 mm (H x W)

– Flush-mounted box 163.5 x 199 x 60 (H x W x D)Weight – 0.742 kgCertification – EIB-certifiedCE norm – in accordance with the EMC guideline

and the low voltage guideline

Functional overview

The LEANtouch panel is a high-qualityEIB touch-sensitive display. The paneloffers approx. 30 operator functionswith a monochrome display. It is usedas a control, monitoring andindication unit for the complete EIBinstallation which can be operatedacross different rooms.

The touch-sensitive display is set in ablack, high-gloss frame and hasbacklighting available. The integratedloudspeaker can e.g. feed backoperations acoustically or signalalarm and fault messages.

The panel has a pen for operationand a slot for a multimedia/SD card.

The operation and control is carriedout in a clear menu structure via thetouch surfaces which are labelled inclear text. The functional assignmentof the touch surfaces can be createdindividually and is dependent on theparameterisation.

All the functions of the panel are listedin the table below “Functionaloverview” (see below).

Page 5: Product manual ABB i-Bus EIB ABB i-bus EIB ABB … · ABB i-bus ® EIB ABB Powernet EIB ... 9 Functions of the panel software 2 - 11 ... Touch-sensitive display 320 x 240 pixels

January 2005 5

ABB i-bus® EIBABB Powernet EIB

SMARTtouch (monochrome)Type: 6136/100M-500

6936/100M

The SMARTtouch panel is a high-quality EIB touch-sensitive display.The panel offers approx. 100 operatorfunctions with a monochrome display.It is used as a control, monitoring andindication unit for the complete EIBinstallation which can be operatedacross different rooms.

The touch-sensitive display (either incolour or black/white) is set in a black,high-gloss frame and hasbacklighting available. The integratedloudspeaker can e.g. feed backoperations acoustically or signalalarm and fault messages.

The panel has a pen for operationand a slot for a multimedia/SD card.

The operation and control is carriedout in a clear menu structure via thetouch surfaces which are labelled inclear text. The functional assignmentof the touch surfaces can be createdindividually and is dependent on theparameterisation.

All the functions of the panel are listedin the table below “Functionaloverview” (see below).

– Number of touch surfaces 10(possible control pages) on Homepage

– Number of possible functions per 10control page

– Total of operator functions 100– Scope of time programs 20 channels, 10 switching times each– Scope of scenes 32 scenes with max. 20 objects

(loads)– Number of alarm signals 10– Monitoring function Monitoring of up to 30 signalling

inputs (e.g. window contacts,movement detectors)

– Presence simulation max. 10 devices– IR remote control channels 10– Integrated room thermostat– Info function– Timer function– Child protection– Number of logic functions 20

(AND, OR, NAND, NOR, multiplexer,multiplier, GATE, temperature comparator)

Technical Data

Power supply – Nominal voltage 230 V AC +10%– Bus voltage (TP only) 24 V DC– Power consumption 10 W

Operating and display elements – Touch-sensitive display 320 x 240 pixels16 grey shades (monochrome)

Connections – Power supply Screw plug-in terminals up to 2.5 mm²– EIB bus connection (TP only) Screw plug-in terminals up to 1.5 mm²– Multimedia/SD card 1 module slot at the front

Type of protection – IP 20, EN 60 529Protection class – IIAmbient temperature range – Operation 0 °C to + 45 °C

– Storage and transport - 20°C to + 60 °CDimensions – Panel with cover frame 184.6 x 218 mm (H x W)

– Flush-mounted box 163.5 x 199 x 60 (H x W x D)Weight – 0.742 kgCertification – EIB-certifiedCE norm – in accordance with the EMC guideline

and the low voltage guideline

Functional overview:

Page 6: Product manual ABB i-Bus EIB ABB i-bus EIB ABB … · ABB i-bus ® EIB ABB Powernet EIB ... 9 Functions of the panel software 2 - 11 ... Touch-sensitive display 320 x 240 pixels

6 January 2005

ABB i-bus® EIBABB Powernet EIB

SMARTtouch (colour)Type: 6136/100C-500

6936/100C

The SMARTtouch panel is a high-quality EIB touch-sensitive display.The panel offers approx. 100 operatorfunctions with a colour display. It isused as a control, monitoring andindication unit for the complete EIBinstallation which can be operatedacross different rooms.

The touch-sensitive display (either incolour or black/white) is set in a black,high-gloss frame and hasbacklighting available. The integratedloudspeaker can e.g. feed backoperations acoustically or signalalarm and fault messages.

The panel has a pen for operationand a slot for a multimedia/SD card.

The operation and control is carriedout in a clear menu structure via thetouch surfaces which are labelled inclear text. The functional assignmentof the touch surfaces can be createdindividually and is dependent on theparameterisation.

All the functions of the panel are listedin the table below “Functionaloverview” (see below).

Technical Data

Power supply – Nominal voltage 230 V AC +10%– Bus voltage (TP only) 24 V DC– Power consumption 10 W

Operating and display elements – Touch-sensitive display 320 x 240 pixels16 grey shades (monochrome)

Connections – Power supply Screw plug-in terminals up to 2.5 mm²– EIB bus connection (TP only) Screw plug-in terminals up to 1.5 mm²– Multimedia/SD card 1 module slot at the front

Type of protection – IP 20, EN 60 529Protection class – IIAmbient temperature range – Operation 0 °C to + 45 °C

– Storage and transport - 20°C to + 60 °CDimensions – Panel with cover frame 184.6 x 218 mm (H x W)

– Flush-mounted box 163.5 x 199 x 60 (H x W x D)Weight – 0.742 kgCertification – EIB-certifiedCE norm – in accordance with the EMC guideline

and the low voltage guideline

– Number of touch surfaces 10(possible control pages) on Homepage

– Number of possible functions per 10control page

– Total of operator functions 100– Scope of time programs 20 channels, 10 switching times each– Scope of scenes 32 scenes with max. 20 objects

(loads)– Number of alarm signals 10– Monitoring function Monitoring of up to 30 signalling

inputs (e.g. window contacts,movement detectors)

– Presence simulation max. 10 devices– IR remote control channels 10– Integrated room thermostat– Info function– Timer function– Child protection– Number of logic functions 20

(AND, OR, NAND, NOR, multiplexer,multiplier, GATE, temperature comparator)

Functional overview:

Page 7: Product manual ABB i-Bus EIB ABB i-bus EIB ABB … · ABB i-bus ® EIB ABB Powernet EIB ... 9 Functions of the panel software 2 - 11 ... Touch-sensitive display 320 x 240 pixels

January 2005 7

ABB i-bus® EIBABB Powernet EIB

SMARTtouch B&OType: 6136/100CB

6936/100CB

The SMARTtouch panel is a high-quality EIB touch-sensitive display.The panel offers approx. 100 operatorfunctions with a colour display. It isused as a control, monitoring andindication unit for the complete EIBinstallation which can be operatedacross different rooms.

The touch-sensitive display (either incolour or black/white) is set in a black,high-gloss frame and hasbacklighting available. The integratedloudspeaker can e.g. feed backoperations acoustically or signalalarm and fault messages.

The panel has a pen for operationand a slot for a multimedia/SD card.

The operation and control is carriedout in a clear menu structure via thetouch surfaces which are labelled inclear text. The functional assignmentof the touch surfaces can be createdindividually and is dependent on theparameterisation.

The SMARTtouch B&O panel isidentical to the “standard”SMARTtouch panel. In addition, it canbe controlled remotely via a Bang &Olufsen remote control Beo4 e.g. toretrieve a lightscene in the panel. TheSMARTtouch B&O panel can furtheralso be operated via the Busch-Jaeger IR remote control.

All the functions of the panel are listedin the table below “Functionaloverview” (see below).Technical Data

Power supply – Nominal voltage 230 V AC +10%– Bus voltage (TP only) 24 V DC– Power consumption 10 W

Operating and display elements – Touch-sensitive display 320 x 240 pixels256 colours

Connections – Power supply Screw plug-in terminals up to 2.5 mm²– EIB bus connection (TP only) Screw plug-in terminals up to 1.5 mm²– Multimedia/SD card 1 module slot at the front

Type of protection – IP 20, EN 60 529Protection class – IIAmbient temperature range – Operation 0 °C to + 45 °C

– Storage and transport - 20°C to + 60 °CDimensions – Panel with cover frame 184.6 x 218 mm (H x W)

– Flush-mounted box 163.5 x 199 x 60 (H x W x D)Weight – 0.742 kgCertification – EIB-certifiedCE norm – in accordance with the EMC guideline

and the low voltage guideline

– Number of touch surfaces 10(possible control pages) on Homepage

– Number of possible functions per 10control page

– Total of operator functions 100– Scope of time programs 20 channels, 10 switching times each– Scope of scenes 32 scenes with max. 20 objects

(loads)– Number of alarm signals 10– Monitoring function Monitoring of up to 30 signalling

inputs (e.g. window contacts,movement detectors)

– Presence simulation max. 10 devices– IR remote control channels 10– Integrated room thermostat– Info function– Timer function– Child protection– Number of logic functions 20

(AND, OR, NAND, NOR, multiplexer,multiplier, GATE, temperature comparator)

Functional overview:

Page 8: Product manual ABB i-Bus EIB ABB i-bus EIB ABB … · ABB i-bus ® EIB ABB Powernet EIB ... 9 Functions of the panel software 2 - 11 ... Touch-sensitive display 320 x 240 pixels

8 January 2005

ABB i-bus® EIBABB Powernet EIB

Circuit diagram

41

2

35

1 Touch-sensitive display 320 x 240 3 MMC/SD card readerpixels, colour 4 230 V power supply

2 Operating pen 5 24 V EIB bus voltage (TP only)

Application programs Number of Max. number of Max. number ofcommunication objects group addresses associations

for LEANtouch/SMARTtouch panel Twisted Pair:Panel TP/1 approx. 500 approx. 4000 approx. 4000for LEANtouch/SMARTtouch panel Powernet:Panel PL/1 approx. 500 approx. 4000 approx. 4000

Note Do not lead any live cables behind thedevice through the flush-mounted box.Separation of the TP bus and mainscable!

LEANtouch (monochrome),SMARTtouch (monochrome, colour)Type: 6x36/30M(-500), 6x36/100x(-500), 6x36/100CB

Note If the SMARTtouch panel 6x36/100CBshould be used, there is no separateentry for it in the ETS or Power-Projectdatabase.

In this case, the SMARTtouch panel6x36/100C must be used. Thedifference between them is that theSMARTtouch panel 6x36/100CB canreact to signals of the Bang&OlufsonIR remote control Beo4. (See also IRcontrol)

Page 9: Product manual ABB i-Bus EIB ABB i-bus EIB ABB … · ABB i-bus ® EIB ABB Powernet EIB ... 9 Functions of the panel software 2 - 11 ... Touch-sensitive display 320 x 240 pixels

January 2005 9

ABB i-bus® EIBABB Powernet EIB

LEANtouch (monochrome),SMARTtouch (monochrome, colour)Type: 6x36/30M(-500), 6x36/100x(-500), 6x36/100CB

Installation of the supplementarysoftware (RCP tool)

To be able to parameterise the LEAN-touch or SMARTtouch panel in ETS 2,in ETS 3 or in Power-Project (from ver-sion 4.0 onwards), the supplementarysoftware RCP-Tool must be installed.You can find this software on the EIBproduct database CD-ROM (art. no.0405) or on the Internet at www.Busch-Jaeger.de.

The software can be plugged intoETS 2, ETS 3 and/or Power-Project.That means that as soon as youretrieve the parameters of a panel inETS or Power-Project, the panelsoftware is opened automatically inwhich you carry out all further settings.

Before you start the installation ofthe panel software, please ensurethat ETS or Power-Project hasalready been installed on yourcomputer.

The following section describes theindividual installation steps.

An installation wizard helps you to in-stall the panel software. This is startedby double clicking on the file“Setup.exe” and can run in either“German” or “English”.

The panel sofware requires at leastWindows 98. You require full administra-tor rights of the operating system in or-der to install the panel software.

Once you have confirmed the welcomescreen with “Next”, you can enter yourname and the name of your company inthe “User info” dialog. If several userswork on the computer on which youwish to install the software, you can li-mit access to the software. This meansthat either all the users can start thesoftware or only you.

The installation path for the panel soft-ware is defined in the next dialog. Bydefault, this is “C:\Program Files\EIB-Programs\”. It is advisable to keep thispath as e.g. Power-Project has thesame default installation path. All EIBprograms and additional EIB softwarecan thus be easily located on the harddisk.

Page 10: Product manual ABB i-Bus EIB ABB i-bus EIB ABB … · ABB i-bus ® EIB ABB Powernet EIB ... 9 Functions of the panel software 2 - 11 ... Touch-sensitive display 320 x 240 pixels

10 January 2005

ABB i-bus® EIBABB Powernet EIB

LEANtouch (monochrome),SMARTtouch (monochrome, colour)Type: 6x36/30M(-500), 6x36/100x(-500), 6x36/100CB

In the “Select functions” dialog, you defi-ne whether the VD2 or VD3 files shouldbe copied locally onto the hard disk. Yourequire these to be able to use theLEANtouch/SMARTtouch panel in con-nection with an ETS version. (Also ob-serve the note at the end of this chap-ter).

By default, the files are copied into thefollowing directory:C:\Program Files\EIB-Programs\RCP-Tool\VDX

Once you have confirmed the “Selectfunctions” dialog with “Next”, theinstallation wizard carries out aninitialisation. This means that all therequired files are compiled togetherand stored temporarily. The dialog“Updating the system” is shown forvisual monitoring purposes.

All the required files are then copied intothe appropriate directories. The installa-tion is concluded with an automaticamendment of the Windows registrationentries.

The computer must be restarted depen-ding on the operating system used.

NoteOnce you have installed the panelsoftware, you must import the productdata (VD2 or VD3 files) in the ETSdatabase if you wish to parameterise apanel with ETS.

To do so, please retrieve the ETS im-port tool (ETS 2 or ETS 3) and importthe VD2 (ETS 2) or VD3 files (ETS 3)from the default directoryC:\Program Files\EIB-Programs\RCP-Tool\VDX.

You must import the VD2 or VD3 filesin full.

Caution:The import of individual files is notpossible.

Commissioning a panel

The commissioning of a panel ispossible either via a multimedia/SDcard (not included) or with “standard”bus programming.

Due to the high level of functionality,full programming via the bus takes along time depending on theconfiguration and medium (TwistedPair or Powernet). The use of themultimedia/SD card is thereforerecommended for quick and simplecommissioning. It is not advisable tocarry out full bus programming viaPowernet.

The menu item “Download” of the com-missioning tool therefore has two furt-her submenus via which the user canselect the required commissioning me-thod. If he selects programming via mul-timedia card, the configuration is storedon a card which is connected to the PC.

With a project that is saved in thisway, the panel itself can becommissioned by inserting the card.The slot for the multimedia/SD card islocated behind the chrome flap of thepanel.

Several projects can be stored on onemultimedia card. After inserting thecard in the panel, the user can selectthe required project which should beloaded into the panel.

Page 11: Product manual ABB i-Bus EIB ABB i-bus EIB ABB … · ABB i-bus ® EIB ABB Powernet EIB ... 9 Functions of the panel software 2 - 11 ... Touch-sensitive display 320 x 240 pixels

January 2005 11

ABB i-bus® EIBABB Powernet EIB

LEANtouch (monochrome),SMARTtouch (monochrome, colour)Type: 6x36/30M(-500), 6x36/100x(-500), 6x36/100CB

Functions of the panel software

The functions and applications are ar-ranged with all the communication ob-jects in the centre. If necessary, the in-dividual functions/applications must firstbe activated so that the communicationobjects become visible. The functionsare defined via a pull-down menu.

The parameters of the individual func-tions are displayed on the right-handside. The parameters of the function thatis marked in the centre are always dis-played.

To obtain a better overview, individualfunctions can be temporarily hidden viathe function view.

The buttons at the bottom always jumpdirectly to the selected function. This isparticularly advisable if the function treein the centre has been fully extended.

If you have inserted a LEANtouch orSMARTtouch panel in Power-Projector in ETS, open the panel software byretrieving the “Edit device” dialog(Power-Project) or the parameters(ETS) of the panel. The panelsoftware starts automatically with thefollowing interface.

The method of operation of the panelsoftware is identical to that of Power-Project or ETS. The “standard” group

addresses and the internal groupaddresses are arranged on the left-hand side. Internal group addressesare not sent on the bus and aretherefore used to relieve the load onthe bus. A touch surface can forexample be linked with a lightscenevia an internal group address. Thegroup addresses and the internalgroup addresses are linked with thecommunication objects in the centreusing drag & drop.

Page 12: Product manual ABB i-Bus EIB ABB i-bus EIB ABB … · ABB i-bus ® EIB ABB Powernet EIB ... 9 Functions of the panel software 2 - 11 ... Touch-sensitive display 320 x 240 pixels

12 January 2005

ABB i-bus® EIBABB Powernet EIB

LEANtouch (monochrome),SMARTtouch (monochrome, colour)Type: 6x36/30M(-500), 6x36/100x(-500), 6x36/100CB

Copying a panel

Only one panel can be parameterisedat one time. To provide several panelswith the same functionality(generation of a duplicate of apreviously configured panel), pleaseproceed as follows:

Retrieve the function “Save as...” fromthe File menu. The project is storedwith the file ending *.rcp. Now closethe panel software. Please insert anew panel in ETS or Power-Project.This can be in the same or anotherproject. Then open the panel softwarefor the inserted panel. Select thefunction “Open” in the File menu andselect the previously saved file.

Please note that you can load thedata of a LEANtouch panel into aSMARTtouch panel but not vice versa.

During the import, the following windowis displayed in which you can selectwhether the import should be carriedout with or without group addresses.

During an import with group addresses,you must ensure that all the groupaddresses or actions are already loca-ted in the project with identical EIS ty-pes to the template. Otherwise, you canonly import the data without groupaddresses. You must then however linkthem again.

Auto backup file

When you retrieve the menu item“Settings” under the File menu, youcan set the period, after which thepanel software will carry out anautomatic backup. This is a temporaryfile which is stored on your hard disk.

If e.g. your computer crashes, you canretrieve the last automatic backupwith the menu item “Reset” under theFile menu.

Copying functions

To shorten the configuration time, it ispossible to copy the settings of afunction (touch surface, time function,lightscene). To do so, click on thefunction with the right mouse buttonwhich should be copied.

Note:Only touch surfaces with identical appli-cations or functions can be duplicated.

Functions of the panel software

Page 13: Product manual ABB i-Bus EIB ABB i-bus EIB ABB … · ABB i-bus ® EIB ABB Powernet EIB ... 9 Functions of the panel software 2 - 11 ... Touch-sensitive display 320 x 240 pixels

January 2005 13

ABB i-bus® EIBABB Powernet EIB

LEANtouch (monochrome),SMARTtouch (monochrome, colour)Type: 6x36/30M(-500), 6x36/100x(-500), 6x36/100CB

Important noteIf you have inserted a LEANtouch/SMARTtouch panel in ETS 2, you mayno longer retrieve the followingfunction:– Shrink database

The reason for this lies in thedatabase structure of ETS 2. It is notlarge enough to take all the panelinformation. The panel information isstored temporarily in several files onthe hard disk. If you carry out thefunction mentioned above, the filesare no longer taken into account andthe result is data loss or damage tothe database.

For ETS 2 users:After importing an ETS 2 project with aLEANtouch/SMARTtouch panel, adatabase consistency check must becarried out in any case. Otherwise,the panel is not displayed correctly/fully within the framework of thecommissioning process.

Functions of the panel software

Page 14: Product manual ABB i-Bus EIB ABB i-bus EIB ABB … · ABB i-bus ® EIB ABB Powernet EIB ... 9 Functions of the panel software 2 - 11 ... Touch-sensitive display 320 x 240 pixels

14 January 2005

ABB i-bus® EIBABB Powernet EIB

LEANtouch (monochrome),SMARTtouch (monochrome, colour)Type: 6x36/30M(-500), 6x36/100x(-500), 6x36/100CB

Functional description: Basicsettings

Background illumination

The backlighting of the panel isswitched on automatically as soon asthe display is operated. After theadjustable period “Backgroundillumination on for”, the lighting isswitched off again provided that thepanel has not been pressed again.

The panel has three communicationobjects in the basic settings. All threeobjects are used to control thebacklighting and are 1 bit in size.

The backlighting can be switched viathe object “Background illumination”.A ON telegram received via the EIBswitches the backlighting on while anOFF telegram switches it off again.

The object can however also belinked with an internal address.

Example:The panel backlighting should alwaysswitch on at 18:00 in the evening andswitch off again at 10:00 in themorning. To do so, a channel of thetime program function isparameterised with switching and theswitch object of the channel is linkedwith the same internal address as thebackground illumination object. Thebus load is reduced on the EIB sidedue to the internal link and groupaddresses or actions are saved.

The object “Status backgroundillumination” sends an ON telegramas soon as the backlighting has beenswitched on. If the backlightingswitches off again after the set resetperiod, the object sends an OFFtelegram.

The backlighting can be disabled viathe object “Enable status”. If an ONtelegram is received, the backlightingcan be switched. If an OFF telegramis received, the backlighting remainsdisabled.

General

By default, the panel has thelanguages German and English. Thedisplay language can be set to a thirdlanguage via the setting “Country-specific”. This third language must betransferred to the panel via a firmwareupdate. The additional languagesavailable can be downloaded from theBusch-Jaeger homepage(www.Busch-Jaeger.de).

The panel distinguishes between ashort and long push button action e.g.when dimming or moving shutters. Itis possible to set the period which thepanel detects as a long push buttonaction. By default, the period is set at500 ms.

The panel has an internaltemperature sensor. The measuredvalue is displayed on the homepage.The display can also be deactivatedvia the setting “Display temperatureindoors”.

The outside temperature is notdisplayed by default. The display canbe activated via the display “Displaytemperature outdoors”. The outsidetemperature is the temperature valuewhich the panel receives via the2-byte communication object“Temperature outside”. It can berecorded e.g. by a “standard” EIBtemperature sensor and sent via its2-byte communication object “Actualvalue”.

Page 15: Product manual ABB i-Bus EIB ABB i-bus EIB ABB … · ABB i-bus ® EIB ABB Powernet EIB ... 9 Functions of the panel software 2 - 11 ... Touch-sensitive display 320 x 240 pixels

January 2005 15

ABB i-bus® EIBABB Powernet EIB

LEANtouch (monochrome),SMARTtouch (monochrome, colour)Type: 6x36/30M(-500), 6x36/100x(-500), 6x36/100CB

If the indoor and outdoor temperatureshould be displayed simultaneously,the corresponding point on thedisplay changes every 5 s.

The panel can display the date andtime. The display can be carried out inthe German format (TT.MM.JJJJ; 24h)or in the English format (MM.TT.JJJJ;12h).

The panel can send and receive thedate and time on the EIB via the two3-byte communication objects “Date”and “Time”. The panel can thus act asa master clock for other EIB devicesor as an extension unit. In its functionas an extension unit, the date andtime can e.g. be sent by an EIB DCF-77 receiver on the bus. By default, thedate and time are neither sent norreceived.

If the date and the time should bedisplayed on the panel, thecorresponding display switchesbetween date and time every 5 s.

The panel has an info page, an alarmclock and a timer. All three functionscan be activated in the basic settings.

Address page

The contact person, company,telephone, fax and email of theelectrical company which carried outthe installation can be stored on theaddress page. In the event ofchanges, the customer (end user)does not need to search in hisdocumentation to find the right contactperson. He will find all the relevantdata directly in the panel.

System settings

The system settings are not enabledas standard. This means that a fourdigit code (by default 0000) must beentered on the display so thatchanges can be carried out. Onlyauthorised personnel may thereforeview and modify the system settings.It is possible however to enable thesystem settings in principle e.g. inenclosed rooms with users who arepermitted to carry out settings. Thesystem settings can also be fullydisabled.

Caution:If you disable the system settingscompletely, the menu item“Commissioning” on the panel can nolonger be selected. In this case, youmust carry out a long operation at thebottom left of the display and therebyswitch on the mains voltage. Themenu item “System” becomes visibleand the panel can e.g. becommissioned with the multimedia/SD card.

If the system settings are saved withthe help of a code, the code is definedvia the parameter “Code for systemsettings”.

The following settings can be carriedout in the system settings on thedisplay:

– Change date– Change time– Display lighting– Volume– Contrast / brightness– Signal tones

– Alarm messages– Timer / alarm clock– Incorrect input– Push button click

– Touchscreen adjustment– Commissioning

– EIB programming– Reading multimedia/SD card

(see also diagram for modifyingsystem settings)

Page 16: Product manual ABB i-Bus EIB ABB i-bus EIB ABB … · ABB i-bus ® EIB ABB Powernet EIB ... 9 Functions of the panel software 2 - 11 ... Touch-sensitive display 320 x 240 pixels

16 January 2005

ABB i-bus® EIBABB Powernet EIB

The time which has been stored inthe parameter “Backgroundillumination on for” is modified via“Background illumination”.

The volume and the contrast orbrightness must be adapted to theenvironment and requirements of theend user.

The complete touch surface issynchronised again with thetouchscreen adjustment. To do so,the operating pen must be clickedprecisely on specific points which areindicated on the display.

The commissioning can be carriedout both via the EIB and via themultimedia/SD card module slot. ForPowernet variants, it is notadvisable to carry out theprogramming via the bus as this isvery time-consuming and faultscaused by cyclical transmitters (e.g.room thermostats or movementdetectors) can lead to theprogramming being interrupted.

LEANtouch (monochrome),SMARTtouch (monochrome, colour)Type: 6x36/30M(-500), 6x36/100x(-500), 6x36/100CB

Changing system settings directly onthe LEANtouch/SMARTtouch paneldisplay

Page 17: Product manual ABB i-Bus EIB ABB i-bus EIB ABB … · ABB i-bus ® EIB ABB Powernet EIB ... 9 Functions of the panel software 2 - 11 ... Touch-sensitive display 320 x 240 pixels

January 2005 17

ABB i-bus® EIBABB Powernet EIB

Communication objectsGeneral (Outside temperature, dateand time)

Communication objectsfor display illumination

General parametersThe default setting for the valuesis printed in bold type.

Display parametersThe default setting for the valuesis printed in bold type.

No. Type Object name Function0 2byte Temperature outside Receive1 3byte Date Send/Receive2 3byte Time Send/Receive

No. Type Object name Function0 1 bit Background illumination Receive1 1 bit Status background illumination Send2 1 bit Enable status Receive

General:– System language German

EnglishCountry-specific

– Long push 300 ms / 500 ms / 750 ms / 1 s– Display temperature indoors No / Yes– Display temperature outdoors No / Yes– Show Date

TimeDate & Time

– Date format TT.MM.JJJJMM.TT.JJJJ

– Time format show 24 hshow 12 h

– Time and Date receive from the bussend to the busdo not send/receive

– Info page No / Yes– Alarm clock No / Yes– Timer No / YesAddress field:– Headline of the address field “Address Installer”– Company “Mustermann”– Contact person “Mr. Muster”– Telephone “+44 ...”– Fax “+44 ...”– E-mail “mustermann@…co.uk”System settings:– Enable system settings for end Yes

customers With codeNo*1

– Code for system settings 0000(0000…9999)

Display parameters:– Background illumination on for always on

2 min5 min10 min30 min1 h

LEANtouch (monochrome),SMARTtouch (monochrome, colour)Type: 6x36/30M(-500), 6x36/100x(-500), 6x36/100CB

*1 Caution: Observe the note on page 15

Page 18: Product manual ABB i-Bus EIB ABB i-bus EIB ABB … · ABB i-bus ® EIB ABB Powernet EIB ... 9 Functions of the panel software 2 - 11 ... Touch-sensitive display 320 x 240 pixels

18 January 2005

ABB i-bus® EIBABB Powernet EIB

Functional description: Touchsurfaces (Homepage)

LEANtouch (monochrome),SMARTtouch (monochrome, colour)Type: 6x36/30M(-500), 6x36/100x(-500), 6x36/100CB

Homepage

The homepage of the panel is the firstpage which is shown by default. If asubmenu (control function) has beenretrieved via the touch surfaces, thepanel automatically reverts to the lastcontrol page after a long period ofinactivity.

The homepage can be provided witha heading which is defined via thesetting “Headline Homepage”.

No direct functions can be executedon the homepage itself. It is used asa navigation page in which you canchange e.g. to the required rooms inorder to carry out switching functions.

Touch surfaces

Up to 10 (6 for LEANtouch) touchsurfaces can be displayed on thehomepage. Each touch surface can atleast adopt the function “Controlfunction”. The setting “Inactive” shouldonly be selected if the touch surfaceis not used and should not display ormonitor anything.

Touch surfaces (Control function)

If a touch surface on the homepage isassigned the application “Controlfunction”, a submenu can be retrievedin which up to 10 (6 for LEANtouch)further functions can be stored.

The text which appears on the touchsurface is defined via the parameter“Name of touch surface (Homepage)”.

Touch surfaces (Monitoring function)

The first touch surface of the SMART-touch panel can be assigned with a mo-nitoring function instead of a controlfunction. In the dialog field “Monitoringfunction” which is retrieved via the firsttouch surface, the panel can be armedor deactivated and an overview of allthe alarm and fault messages can beretrieved.

Note:The monitoring function is not used toset up a VDS-certified alarm systembut merely offers the opportunity ofmonitoring e.g. windows, doors orinterior rooms via EIB-type movementdetectors. It is not a replacement foran alarm system.

Inputs (Entry 1 up to 16,Monitoring function)

The monitoring function can monitorup to 16 inputs. Each input has itsown 1-bit communication objectavailable “Input ...”. The parameter“Number of inputs” determines howmany inputs are actually visible.

It can be set for each input via theparameter “Type of input” whether it isa window, a movement detector whichmay or may not be in the entrancearea, a “standard” door or one ofthree doors in the entrance area. Thesetting should however only be seenas a configuration tool. All the inputsare treated the same internally in thepanel, regardless of the “Type ofinput” assigned.

Text can be freely assigned to eachindividual input via the parameter“Description of the input”. If an input isnow triggered on the panel, not onlythe input number is shown but also aclear text description such as“Bathroom window open”.

The input objects are linked via groupaddresses with the sensor objects(binary inputs, magnetic contacts,switch/key bolt contact, …) of thewindow, movement detector or doorsthat are to be monitored. The linkedsensors must send their inputsignals, both “0” and “1”, cyclically onthe bus so that the panel knows the sta-tus of the installation at any time.

Page 19: Product manual ABB i-Bus EIB ABB i-bus EIB ABB … · ABB i-bus ® EIB ABB Powernet EIB ... 9 Functions of the panel software 2 - 11 ... Touch-sensitive display 320 x 240 pixels

January 2005 19

ABB i-bus® EIBABB Powernet EIB

LEANtouch (monochrome),SMARTtouch (monochrome, colour)Type: 6x36/30M(-500), 6x36/100x(-500), 6x36/100CB

If e.g. a movement detector is preven-ted from detecting movements throughsabotage, the panel notes the sabota-ged movement detector as it has notsent out any telegrams within the “Moni-toring time of inputs”. The panel thusautomatically sets the linked input tofault mode.

The “Monitoring time of inputs” can beadjusted and represents acompromise between a high bus loadand system reliability. The monitoringtime should be set too short,particularly in Powerline installations.

Note:Set the cyclic period of the sensors(binary inputs or movement detectors)to sensible values.Example:– Monitoring time of the inputs:

10 min– Cyclic period of the sensors:

4.5 minIt is therefore guaranteed that atelegram is received at least twicewithin the monitoring time.

If the mains voltage fails, the inputsinitially remain inactive on mainsvoltage recovery. The time until theinputs become active is set via theparameter “Monitoring of inputs aftermains voltage recovery”.

If an ON telegram is set while thesystem is “armed”, the input istriggered. That means that the “Textfor on” is entered in the panel in thelist of monitoring functions. If an inputfails, the “Text for failure” is entered inthe list of faults. Both the “Text for on”and the “Text for off” can be freely setfor each input.

The monitoring function has twocommunication objects “Releasinginputs” and “Failure inputs” which cansend out the input states. The twoobjects can adopt 1-byte or 14-bytevalues. This is dependent on thesetting “Type of output”.

In the case of a 1-byte output variable,when an input is triggered in thearmed state, the number of the inputwhich has been triggered is sent tothe 1-byte object “Releasing inputs”. Ifan input fails, the number of the inputwhich has failed is sent to the 1-byteobject “Failure inputs”.

If the “Type of output” is set to 14 bytes,the “Message text at releasing” of therespective input is sent to the 14-byteobject “Releasing inputs” when an inputis triggered. In the event of a fault, the14-byte object “Failure inputs” sends the“Message text at failure” of the input.Both text elements can be freely assig-ned to each input and contain up to 13characters.

The transmitted 14-byte text can opena pop-up window on the display withthe help of the alarm functionality,which immediately displays a visualand/or acoustic fault or a trigger. Theuser does not therefore need to firstchange to the list of alarm and faultmessages but sees directly that thereis a problem with the installation.

If at least one input has a fault, theinstallation can be armed directly. Theinput or inputs must first beacknowledged in order to arm thesystem. The faulty inputs are removedfrom the monitoring as a result. Theacknowledgement can either becarried out directly on the panel or viathe 1-bit communication object“Failure reset inputs”.

Example:The installation should be armedexternally at an entrance door with thehelp of a key-operated switch. Themovement detector in the cellar ishowever currently faulty i.e. it nolonger sends a cyclical telegram andis thus faulty. So that the user can stillarm his system, he must firstacknowledge the faulty input. This cane.g. be carried out via a 1-fold switchsensor.

Page 20: Product manual ABB i-Bus EIB ABB i-bus EIB ABB … · ABB i-bus ® EIB ABB Powernet EIB ... 9 Functions of the panel software 2 - 11 ... Touch-sensitive display 320 x 240 pixels

20 January 2005

ABB i-bus® EIBABB Powernet EIB

LEANtouch (monochrome),SMARTtouch (monochrome, colour)Type: 6x36/30M(-500), 6x36/100x(-500), 6x36/100CB

Note:Using this function, it is possible toarm the installation even if an input isfaulty. The input is temporarilyremoved from the monitoredinstallation through theacknowledgement.

If the parameter “Delete failuremessage at external display” is set to“yes”, a so-called zero string is sent tothe object “Failure inputs” in the eventof a fault acknowledgement. Thismeans that a telegram is sent whoseuseful information consists of bitswith the value “0”. Display text on anexternal display is thus reset.

Arming (Monitoring function)

The installation can be armedinternally or externally. Internallymeans entering a four-digit PIN codedirectly on the panel. This is definedvia the setting “Code for arming/disarming”. The code can howeveralso be modified by the user. To doso, the old code must be enteredonce and the new code must beentered twice.

Note:Please note the setting “Overwritecode at download”. If “yes” isselected, the code which has beenmodified by the user is overwrittenwith the original code after eachreconfiguration of the panel.

The system can be armed externallyvia a maximum of three 1-bitcommunication objects “Arming ...”.Each object can be controlled via aseparate group address. This isnecessary if the system should bearmed from several entry doors. It isdefined via “Number of entry doors”whether one, two or three armingobjects are displayed.

The “Type of arming/disarming” isonly for information, in a similar wayto the inputs. The setting has noinfluence on the behaviour of thepanel.

When the system is armed, all the inputobjects must send the value “0” cycli-cally i.e. all the windows must be closedand the movement detectors cannotreport any movement. If the inputshould not send any “0” values cyclical-ly due to a fault, the panel can be ack-nowledged directly via the panel or via

the object “Failure reset inputs” of theinput i.e. removed from the monitoring. Itis then possible to arm the system.

&

>1Arming internal

Armed

Arming external 1Arming external 2Arming external 3

Lock Arming

The system can be armed via the first“Arming” object, the second object orthe third. The inputs are linked with anOR function. In addition, an “Activatearming” object is enabled via acorresponding parameter. If the objectis visible, arming is enabled with anON telegram. An OFF telegramdisables the possibility of arming thesystem.

Once the panel has been armed, adelay period elapses until the panelis actually triggered by an inputsignal. The period is set via “Timedelay at arming”. If e.g. the panel islocated in the entrance area of ahouse, the user must still be giventhe opportunity to leave the housebefore the system is armed. If thisdelay did not exist, in many cases analarm would always be triggeredimmediately after arming the system.

Armed status (Monitoring function)

It is indicated via two 1-bitcommunication objects that thesystem is in the armed state. Theobject “Armed status” sends an ONtelegram as soon as the system isarmed (once the “Time delay atarming” has elapsed). If the system isdisarmed, the object sends an OFFtelegram. It would therefore bepossible e.g. for an LED of a switchsensor which is mounted at anentrance door to be switched.

The second object “Armed statusflashing” must first be enabled via thecorresponding parameter. A telegramsequence is then sent via this objectonce the system is armed so that e.g.an external lamp flashes three times.The user who has armed his housevia a key bolt contact is thereforeinformed before he reaches hishouse that the system is now set.Depending on the status of theactuator, six telegrams are sent withthe following useful information:

1 - 0 - 1 - 0 - 1 - 0 or0 - 1 - 0 - 1 - 0 - 1

Page 21: Product manual ABB i-Bus EIB ABB i-bus EIB ABB … · ABB i-bus ® EIB ABB Powernet EIB ... 9 Functions of the panel software 2 - 11 ... Touch-sensitive display 320 x 240 pixels

January 2005 21

ABB i-bus® EIBABB Powernet EIB

LEANtouch (monochrome),SMARTtouch (monochrome, colour)Type: 6x36/30M(-500), 6x36/100x(-500), 6x36/100CB

Alarm (Monitoring function)

If an ON telegram is received at aninput in the armed state, the paneltriggers an alarm. There are fourdifferent alarm messages (objects).

Internal alarm:The internal alarm is triggeredimmediately and without a delay. AnON telegram is sent to the 1-bitcommunication object “Internalalarm”. This could trigger anadditional horn in the house or belinked with the alarm function of thepanel itself. In the latter case, amessage and if necessary a signaltone is displayed/triggered at thepanel itself.

AlarmThe alarm is a continuous alarm andis sent via the 1-bit communicationobject “Alarm” with a time delay. The“Time delay as long as alarmrelease” can be set. A warning lampfor example could be addressed viathis object.Example:A system has been armed directly onthe panel in the hallway. The usercomes home and automaticallytriggers an internal alarm. He nowhas the “Time delay as long as alarmrelease” to prevent an acoustic signale.g. an outdoor siren.

Alarm impulseThe 1-bit object “Alarm impulse” isused to address a horn in front of thehouse. In the event of an alarm, thismay only be triggered for maximum 3min (legal regulation). This meansthat an ON telegram is sent to theobject once the “Time delay as longas alarm release” has elapsed. Theperiod “Time of the external audiosignal” now starts. If this haselapsed, an OFF telegram is sent.The “Time of the external audiosignal” can be set to 1 min, 2 min or3 min.

Silent alarmThe silent alarm is retrieved byentering the PIN code for the silentalarm.Example:An intruder has entered the house inthe night and forces the owner tocancel the alarm. Normally, the ownerwould enter the PIN code todeactivate the system and the systemwould be disarmed. If he however en-

ters the PIN code for the silent alarm,the objects “Alarm”, “Internal alarm” and“Alarm impulse” are reset but the 1-bitcommunication object “Silent alarm”sends an ON telegram. A telephone di-alling device or similar could beaddressed via this object.

The PIN code for the silent alarm isdefined in the panel software in asimilar way to the PIN code forarming/disarming the system. Theuser can modify the PIN code,whereby he presses the touchsurface that is assigned themonitoring function and retrieves thefunction “Code for silent alarm” in thesubsequent window (only visible inthe disarmed state).

Input failure if armed(Monitoring function)

If an input failure occurs while thesystem is armed, this does not triggeran alarm. To inform the user aboutthis input failure, there is the 1-bitcommunication object “Inputs failureif armed”. In the event of faults, an ONtelegram is sent via this object.

Installation status (Monitoringfunction)

The new status is sent via the object“Installation status” as soon as thestatus of the panel changes. Theobject is 1 byte or 14 bytes dependingon the setting “Type of output”. Thesystem knows three different states:– Unset– Ready to set– Set

Page 22: Product manual ABB i-Bus EIB ABB i-bus EIB ABB … · ABB i-bus ® EIB ABB Powernet EIB ... 9 Functions of the panel software 2 - 11 ... Touch-sensitive display 320 x 240 pixels

22 January 2005

ABB i-bus® EIBABB Powernet EIB

Living room

Floor

Kitchen

Bathroom

MC5 MC6

MC4

MC3

MC2 MC1

Entrance door 1with switch/key bolt contact

MD1

MD2

Outdoor light

Example: Detached house

BM1 and BM2:Movement detectors

MK1 to MK6:Magnetic contacts

LEANtouch (monochrome),SMARTtouch (monochrome, colour)Type: 6x36/30M(-500), 6x36/100x(-500), 6x36/100CB

The diagram above shows anapplication example for themonitoring function of theSMARTtouch panel.

The states of the magnetic contactsMC1 to MC6 and the switch/key boltcontact of the entrance door are recor-ded with binary inputs or universal inter-faces and sent on the EIB. The detec-tors MD1 and MD2 are EIB movementdetectors and send their signals imme-diately on the bus.

The magnetic contacts and themovement detectors are linked viagroup addresses/actions with theinputs of the panel. The switch/keybolt contact with a group address isassigned to an arming object.

When the user leaves the house, hearms the system by locking up. If theexternal light is also controlled viaEIB, it can signal via the object“Armed status flashing” that thesystem is now armed. If the userdoes not receive a flashing status, heknows that there is a problem with theinstallation. A window is still openperhaps.

The following table indicates which va-lues are sent for the different bit sizes:

State 1 byte 14 byteSet 0 UnsetReady to set 1 Ready to

setSet 2 Set

Page 23: Product manual ABB i-Bus EIB ABB i-bus EIB ABB … · ABB i-bus ® EIB ABB Powernet EIB ... 9 Functions of the panel software 2 - 11 ... Touch-sensitive display 320 x 240 pixels

January 2005 23

ABB i-bus® EIBABB Powernet EIB

LEANtouch (monochrome),SMARTtouch (monochrome, colour)Type: 6x36/30M(-500), 6x36/100x(-500), 6x36/100CB

Functional description: Touchsurfaces (Homepage)

Function ApplicationHeadline Homepage SettingsButton 1 Control function(Homepage) Monitoring function

InactiveButton 2 Control function(Homepage) InactiveButton 3 Control function(Homepage) InactiveButton 4 Control function(Homepage) InactiveButton 5 Control function(Homepage) InactiveButton 6 Control function(Homepage) InactiveButton 7 Control function(Homepage) InactiveButton 8 Control function(Homepage) InactiveButton 9 Control function(Homepage) InactiveButton 10 Control function(Homepage) Inactive

Page 24: Product manual ABB i-Bus EIB ABB i-bus EIB ABB … · ABB i-bus ® EIB ABB Powernet EIB ... 9 Functions of the panel software 2 - 11 ... Touch-sensitive display 320 x 240 pixels

24 January 2005

ABB i-bus® EIBABB Powernet EIB

Communication objectsfor monitoring function

LEANtouch (monochrome),SMARTtouch (monochrome, colour)Type: 6x36/30M(-500), 6x36/100x(-500), 6x36/100CB

No. Type Object name Function0 1 bit Arming 1 Receive1 1 bit Arming 2 Receive2 1 bit Arming 3 Receive3 1 bit Activate arming Receive4 1 bit Alarm Send5 1 bit Internal alarm Send6 1 bit Silent alarm Send7 1 bit Alarm impulse Send8 1 bit Armed status Send9 1 bit Armed status flashing Send

10 1 byte Releasing inputs Send11 1 byte Failure inputs Send12 1 bit Failure reset inputs Receive13 1 bit Inputs failure if armed Send14 1 byte Installation status Send15 1bit Entry 1 (Input 1) Receive16 1bit Entry 2 (Input 2) Receive17 1bit Entry 3 (Input 3) Receive18 1bit Entry 4 (Input 4) Receive19 1bit Entry 5 (Input 5) Receive20 1bit Entry 6 (Input 6) Receive21 1bit Entry 7 (Input 7) Receive22 1bit Entry 8 (Input 8) Receive23 1bit Entry 9 (Input 9) Receive24 1bit Entry 10 (Input 10) Receive25 1bit Entry 11 (Input 11) Receive26 1bit Entry 12 (Input 12) Receive27 1bit Entry 13 (Input 13) Receive28 1bit Entry 14 (Input 14) Receive29 1bit Entry 15 (Input 15) Receive30 1bit Entry 16 (Input 16) Receive

No. Type Object name Function…10 14 byte Releasing inputs Send11 14 byte Failure inputs Send…14 14 byte Installation status Send…

Page 25: Product manual ABB i-Bus EIB ABB i-bus EIB ABB … · ABB i-bus ® EIB ABB Powernet EIB ... 9 Functions of the panel software 2 - 11 ... Touch-sensitive display 320 x 240 pixels

January 2005 25

ABB i-bus® EIBABB Powernet EIB

LEANtouch (monochrome),SMARTtouch (monochrome, colour)Type: 6x36/30M(-500), 6x36/100x(-500), 6x36/100CB

– Headline Homepage <Text>

– Name of touch surface <Text>(Homepage)

– Name of touch surface <Text>General:– Code for arming/disarming 0000

(0000…9999)– Code for silent alarm 0000

(0000…9999)– Overwrite code at download No / Yes– Number of entry doors None (internal monitoring)

123

– Type of arming/disarming Internal lock/PIN code/push buttonBlock lockExternal lock/PIN code/transponderBolt switch contact

– Monitoring time of inputs 1 min / 3 min / 5 min / 10 min / 20 min /30 min

– Number of inputs 8(1…16)

– Monitoring of inputs after 20 s / 30 s / 1 min / 5 min / 10 minmains voltage recovery

– Time delay at arming None / 10 s / 15 s / 20 s / 25 s / 30 s /35 s / 40 s / 1 min

– Time delay as long as None / 10 s / 15 s / 20 s / 25 s / 30 s /alarm release 35 s / 40 s / 1 min

– Time of the external audio signal 1 min / 2 min / 3 min– Activate arming via object No / Yes– Armed status flashing No / Yes– Delete failure message at No / Yes

external display– Type of output 1 Byte / 14 Byte

Separate for each input:– Type of input … Window

Watch dog sensorWatch dog sensor in the entry areaDoor (not in the entry area)Entry door 1Entry door 2Entry door 3

– Description of the input <Text>– Text for on <Text>– Text for failure <Text>– Message text at releasing <Text>

(max. 13 characters)– Message text at failure <Text>

(max. 13 characters)

Parameters: Headline HomepageThe default setting for the valuesis printed in bold type.

Control function parameterThe default setting for the valuesis printed in bold type.

Monitoring function parametersThe default setting for the valuesis printed in bold type.

Input parametersThe default setting for the valuesis printed in bold type.

Page 26: Product manual ABB i-Bus EIB ABB i-bus EIB ABB … · ABB i-bus ® EIB ABB Powernet EIB ... 9 Functions of the panel software 2 - 11 ... Touch-sensitive display 320 x 240 pixels

26 January 2005

ABB i-bus® EIBABB Powernet EIB

LEANtouch (monochrome),SMARTtouch (monochrome, colour)Type: 6x36/30M(-500), 6x36/100x(-500), 6x36/100CB

Functional description: Touchsurfaces (Control page)

Each touch surface can adopt variousfunctions. Depending on the setfunction, the panel software displaysdifferent communication objects andparameters.

The “Name of touch surface” isalways on the left-hand side of thetouch surface. This can be freelyassigned to each touch surface withthe corresponding parameter.

The status display is on the right-handside of the touch surface. This caneither be a symbol or text.

If this button is “Active”, a windowopens when the touch surface isoperated. The “Name of touchsurface” appears in the window as aheading. The buttons (designatedhere with “ON” and “OFF”) can bedescribed with text or adopt symbols.

As soon as a touch surface isoperated, the panel sends acorresponding telegram to the linkedcommunication object. In somewindows, a slide rule appears inaddition to the buttons. If the button onthe slide rule is set to a new position,the linked object also sends the newvalue automatically.

If the status display or the buttondescription should adopt a symbol, itcan be selected from a pull-downmenu. The panel software alwaysindicates all the context-related sym-bols. (See also the parameter listings ofthe individual functions)

Switch

If the function of the touch surface isdefined as “Switch”, the panel sendsON or OFF telegrams via theassociated 1-bit object “Switch”.

In the default setting, the touchsurface sends OFF telegrams whenthe right-hand side is pressed andsends ON telegrams when the left-hand side is pressed. The method ofoperation of the touch surface can beinverted via the parameter“Behaviour”.

Push button

In the “Push button” function, there isa 1-bit communication object “Switch”available for defined switching. ON,OFF or TOGGLE telegrams can besent on the EIB via this object.

Each pulse edge can therefore be setindividually. This means: if the touchsurface is pressed, this is evaluatedby the panel as a rising pulse edgewhile the release of the touch surfaceis evaluated as a falling pulse edge.

The touch surface can thus beadapted to a wide variety ofapplications. If e.g. inching modeshould be implemented, the setting“Send on at rising edge, off at fallingedge” should be selected.

Dimmer

With the “Dimmer” function, an ON orOFF command is sent to the 1-bitcommunication object “Switch” after ashort operation of the correspondingtouch surface. If the surface isoperated for a longer period, thepanel sends commands for dimmingbrighter or darker to the 4-bit object“Dim”. If the touch surface is releasedafter a long operation, the panelimmediately sends the command“Stop dimming”.

The behaviour of the buttons can beset. This means it is possible to dimbrighter or darker via the left or rightbutton (switch on, off or toggle).

Page 27: Product manual ABB i-Bus EIB ABB i-bus EIB ABB … · ABB i-bus ® EIB ABB Powernet EIB ... 9 Functions of the panel software 2 - 11 ... Touch-sensitive display 320 x 240 pixels

January 2005 27

ABB i-bus® EIBABB Powernet EIB

LEANtouch (monochrome),SMARTtouch (monochrome, colour)Type: 6x36/30M(-500), 6x36/100x(-500), 6x36/100CB

The status display of the button canalso display the direct value(0%…100% or 0…255) as analternative to the text or symboldisplay. To do so, the 1-byte object ofthe touch surface must first be linkedwith that of the dimming actuator.

Shutter

In the “Shutter” function, the touchsurface has two 1-bit communicationobjects “Move” and “Step”. After a longoperation, the panel sends telegramsto the linked shutter actuators to raiseor lower the shutters. After a shortoperation, it sends telegrams to stopshutter movement or for louvreadjustment.

With the setting “Behaviour”, it isdefined whether the shutter movesupwards or downwards when theright or the left touch surface ispressed.

Lightscenes external input (1 bit)

In the function “Lightscenes externalinput (1 bit)”, the touch surface has a1-bit communication object. Twolightscenes can be sent via thisobject. On each operation of the pulseedge, the active lightscene changes(from 0 to 1, from 1 to 0).

Lightscenes external input (1 byte)

With the function “Lightscenesexternal input (1 byte)”, one of 32lightscenes can be sent via a 1-bytecommunication object. The setting“Lightscene number” defines whichlightscene is sent.

The user has the option of storinglightscenes himself. To do so, theparameter “Store scene by long push”must be set to “possible”. After a longoperation of the touch surface (> 3 s),a bit is additionally set to “1” in the 1-byte lightscene telegram. A lightscenemodule (generally the LEANtouch/SMARTtouch panel) therefore knowsthat the requested lightscene shouldbe stored and not retrieved. (See also“Functional description: Lightscenes”)

Value (1 byte, 2 byte)

The “Value” function causes the touchsurface to send value telegrams via theassociated “Value” object. Dependingon whether the function “Value (1 byte)”

or “Value (2 byte)” has been selected,the communication object is 1 byte or 2bytes in size.

The 1-byte value function can displayor send the following physicalvariables:– Brightness– Wetness (show only)– Volume– Value– Temperature offset– Current (show only)

The 2-byte value function has thefollowing variables by default:– Temperature– Illumination– Wind force

The respective physical variables aredefined via the parameter “Displaytype”. There is also the possibility ofsetting the “Display type” to “freescalable” for both values (1 byte and 2byte). Other values than the presetvalues can thus also be displayed.

With the freely scalable setting, it ispossible to parameterise the numberof decimal places, the minimum andmaximum object value and theminimum and maximum displayvalue.

If the touch surface is pressed (“showand send”), the panel indicates aslide rule in the open window. Theindividual values can be set via thisslide. A display in the upper section ofthe window indicates the exact value.The value is adjusted upwards ordownwards by the smallest possibleunit via the fields “On” or “Off”.

Page 28: Product manual ABB i-Bus EIB ABB i-bus EIB ABB … · ABB i-bus ® EIB ABB Powernet EIB ... 9 Functions of the panel software 2 - 11 ... Touch-sensitive display 320 x 240 pixels

28 January 2005

ABB i-bus® EIBABB Powernet EIB

LEANtouch (monochrome),SMARTtouch (monochrome, colour)Type: 6x36/30M(-500), 6x36/100x(-500), 6x36/100CB

Room thermostat

If the function of the touch surface isdefined as “Room thermostat”, thetouch surface is used to control a roomthermostat in order to change operatingmode in the thermostat.

As the room thermostat touch surfaceis an active button, a window withthree further buttons “Comfort”,“Night” and “Frost” opens when it isoperated. Each of these three buttonshas a 1-bit communication object.The objects “Comfort/Standby”,“Night” and “Frost/heat protection” areeach linked via a group address withthe similarly named objects of a roomthermostat.

The linked room thermostat can bethe internal thermostat of the panel oran external device (e.g. Busch-triton®

RT).

Floating point value

With the “Floating value” function, atouch surface can display and/or senda value of -99,999 to +99,999. Thereis a 4-byte communication object“Floating point value” available for thisfunction.

If the “Floating value” touch surface ispressed, the panel displays a sliderule and three buttons in the openwindow. Values can be set intuitivelyvia the slide rule by adjusting thecontrol button. Depending on thesetting, the value can be increased ordecreased via the buttons. As soon asthe slide rule is released or a buttonhas been pressed, a new telegram

with the new floating point value is trig-gered.

The displayed or transmitted values canadopt up to three decimal places, de-pending on the setting. The default set-ting is a percentage value (0…100%).

The object value and the display valuecan be set separately in theparameters. The object value is thevalue which is sent via the 4-byte object“Floating point value”. The maximum orminimum object as well as the smallestor largest display value can be set indi-vidually (from-99,999 to +99,999). It is thereforepossible to display a larger value andto simultaneously limit thetransmitted value to a smaller range.

Counter

If a touch surface is assigned thefunction “Counter”, it is used toindicate counter contents. These canbe counts with and without leadingsigns. It depends on the setting“Display type” as to whether thedisplay has a leading sign.

Three different bit sizes can bedisplayed. It is defined directly via thefunctional selection whether a 1-byte,2-byte or a 4-byte count should bedisplayed. Depending on theselection, a 1-byte, 2-byte or a 4-bytecommunication object “Counter value”is available for receiving new countvalues.

Text

The “Text” function enables a 14-bytelong text element to be displayed onthe touch surface or sent. Thefunction has a 14-byte communicationobject “Text” for receiving and sendingtext.

It is defined via the “Text” setting in theparameters whether the text shouldonly be displayed or displayed andsent. If text should also be sent, thetext is defined in the field “Messagetext”. The text may be 13 characterslong.

Page 29: Product manual ABB i-Bus EIB ABB i-bus EIB ABB … · ABB i-bus ® EIB ABB Powernet EIB ... 9 Functions of the panel software 2 - 11 ... Touch-sensitive display 320 x 240 pixels

January 2005 29

ABB i-bus® EIBABB Powernet EIB

LEANtouch (monochrome),SMARTtouch (monochrome, colour)Type: 6x36/30M(-500), 6x36/100x(-500), 6x36/100CB

Functional description: Touchsurfaces (Control page)

Function ApplicationButton 1 Inactive(Control page) Switch

Push buttonDimmerShutterLightscenes external input (1 Bit)Lightscenes external input (1 Byte)Value (1 Byte)Value (2 Byte)Room thermostatFloating value (4 Byte)Counter (2 Byte)Counter (4 Byte)Counter (1 Byte)Text

Button 2 Inactive(Control page) Switch

Push buttonDimmerShutterLightscenes external input (1 Bit)Lightscenes external input (1 Byte)Value (1 Byte)Value (2 Byte)Room thermostatFloating value (4 Byte)Counter (2 Byte)Counter (4 Byte)Counter (1 Byte)Text

…Button 10 Inactive(Control page) Switch

Push buttonDimmerShutterLightscenes external input (1 Bit)Lightscenes external input (1 Byte)Value (1 Byte)Value (2 Byte)Room thermostatFloating value (4 Byte)Counter (2 Byte)Counter (4 Byte)Counter (1 Byte)Text

Page 30: Product manual ABB i-Bus EIB ABB i-bus EIB ABB … · ABB i-bus ® EIB ABB Powernet EIB ... 9 Functions of the panel software 2 - 11 ... Touch-sensitive display 320 x 240 pixels

30 January 2005

ABB i-bus® EIBABB Powernet EIB

LEANtouch (monochrome),SMARTtouch (monochrome, colour)Type: 6x36/30M(-500), 6x36/100x(-500), 6x36/100CB

Communication objectsfor “Switch” touch surfaces (Controlpage)

Communication objectsfor “Push button” touch surfaces(Control page)

Communication objectsfor “Dimmer” touch surfaces (Controlpage)

Communication objectsfor “Shutter” touch surfaces (Controlpage)

Communication objectsfor “1-bit lightscenes” touch surfaces(Control page)

Communication objectsfor “1-byte lightscenes” touch surfaces(Control page)

Communication objectsfor “1-byte value” touch surfaces(Control page)

Communication objectsfor “2 byte value” touch surfaces(Control page)

Communication objectsfor “Room thermostat” touch surfaces(Control page)

Communication objectsfor “Floating value” touch surfaces(Control page)

Communication objectsfor “2-byte counter” touch surfaces(Control page)

Communication objectsfor “4-byte counter” touch surfaces(Control page)

Communication objectsfor “1-byte counter” touch surfaces(Control page)

Communication objectsfor “Text” touch surfaces (Controlpage)

No. Type Object name Function0 1 bit Switch Send/Receive

No. Type Object name Function0 1 bit Switch Send/Receive

No. Type Object name Function0 1 bit Switch Send/Receive1 4 bit Dim Send2 1 byte Value Receive

No. Type Object name Function0 1 bit Move Send/Receive1 1 bit Step Send

No. Type Object name Function0 1 bit Lightscene number Send/Receive

No. Type Object name Function0 1 byte Lightscene number Send/Receive

No. Type Object name Function0 1 byte Value Send/Receive

No. Type Object name Function0 2 byte Value Send/Receive

No. Type Object name Function0 1 bit Standby/Comfort Send/Receive1 1 bit Night Send/Receive2 1 bit Frost/heat protection Send/Receive

No. Type Object name Function0 4 byte Floating point value Send/Receive

No. Type Object name Function0 2 byte Counter value Receive

No. Type Object name Function0 4 byte Counter value Receive

No. Type Object name Function0 1 byte Counter value Receive

No. Type Object name Function0 14 byte Text Send/Receive

Page 31: Product manual ABB i-Bus EIB ABB i-bus EIB ABB … · ABB i-bus ® EIB ABB Powernet EIB ... 9 Functions of the panel software 2 - 11 ... Touch-sensitive display 320 x 240 pixels

January 2005 31

ABB i-bus® EIBABB Powernet EIB

LEANtouch (monochrome),SMARTtouch (monochrome, colour)Type: 6x36/30M(-500), 6x36/100x(-500), 6x36/100CB

– Name of the button <Text>– Button Inactive

ActiveOnly if “Active” is selected:– Behaviour Left=Off, Right=On

Left=On, Right=Off– Status display Text

SymbolOnly if “Text” is selected:– Text for on On– Text for off OffOnly if “Symbol” is selected: (see below)

– Button description TextSymbol

Only if “Text” is selected:– Text for on On– Text for off OffOnly if “Symbol” is selected: (see below)

– Name of touch surface <Text>(Control page)

– Button InactiveActive

Only if “Active” is selected:– Behaviour Send off at rising flank

Send off at falling flankSend off at both flanksSend on at falling flankSend off at rising flank,on at falling flankSend on at rising flankSend on at rising flank,off at falling flankSend on at both flanksToggle at rising flank

– Display switching status TextSymbol

Only if “Text” is selected:– Text for 1 On– Text for 0 OffOnly if “Symbol” is selected: (see below)

– Button description TextOnly if “Text” is selected:– Button text Push button

Symbols for status display ON/OFF:

Symbols for button description ON/OFF:

Parameters: “Switch” touch surfaceThe default setting for the valuesis printed in bold type.

Parameters: “Push button” touchsurfaceThe default setting for the valuesis printed in bold type.

Symbols for “Switch” or “Pushbutton” touch surface

Page 32: Product manual ABB i-Bus EIB ABB i-bus EIB ABB … · ABB i-bus ® EIB ABB Powernet EIB ... 9 Functions of the panel software 2 - 11 ... Touch-sensitive display 320 x 240 pixels

32 January 2005

ABB i-bus® EIBABB Powernet EIB

Parameters: “Dimmer” touchsurfaceThe default setting for the valuesis printed in bold type.

– Name of touch surface <Text>– Button Inactive

ActiveOnly if “Active” is selected:– Behaviour Left brighter on, right darker off

Left darker off, right brighter onLeft brighter toggle, right darker toggleLeft darker toggle, right brighter toggle

– Button description TextSymbol

Only if “Text” is selected:– Text for ON resp. brighter On– Text for OFF resp. darker OffOnly if “Symbol” is selected: (see below)

– Display switching status TextSymbolDirect value display (0%…100%)Direct value display (0…255)

Only if “Text” is selected:– Text for ON resp. brighter On– Text for OFF resp. darker OffOnly if “Symbol” is selected: (see below)

Symbols for button description ON/OFF or brighter/darker:

Symbols for status display ON/OFF or brighter/darker:

LEANtouch (monochrome),SMARTtouch (monochrome, colour)Type: 6x36/30M(-500), 6x36/100x(-500), 6x36/100CB

Page 33: Product manual ABB i-Bus EIB ABB i-bus EIB ABB … · ABB i-bus ® EIB ABB Powernet EIB ... 9 Functions of the panel software 2 - 11 ... Touch-sensitive display 320 x 240 pixels

January 2005 33

ABB i-bus® EIBABB Powernet EIB

LEANtouch (monochrome),SMARTtouch (monochrome, colour)Type: 6x36/30M(-500), 6x36/100x(-500), 6x36/100CB

Parameters: “Shutter” touch surfaceThe default setting for the valuesis printed in bold type.

– Name of touch surface <Text>(Control page)

– Behaviour Left=up/right=downLeft=down/right=up

– Button description TextSymbol

Only if “Text” is selected:– Text for 1 resp. down Down– Text for 0 resp. up UpOnly if “Symbol” is selected: (see below)

– Display switching status TextSymbol

Only if “Text” is selected:– Text for 1 resp. down Down– Text for 0 resp. up UpOnly if “Symbol” is selected: (see below)

Symbols for button description 1-0 or UP/DOWN:

Symbols for status display 1-0 or UP/DOWN:

Page 34: Product manual ABB i-Bus EIB ABB i-bus EIB ABB … · ABB i-bus ® EIB ABB Powernet EIB ... 9 Functions of the panel software 2 - 11 ... Touch-sensitive display 320 x 240 pixels

34 January 2005

ABB i-bus® EIBABB Powernet EIB

Parameters: “1-bit lightscenes”touch surfaceThe default setting for the valuesis printed in bold type.

– Name of touch surface <Text>(Control page)

– Lightscene number 0 / 1– Store scene by long not possible

push– Button description Text

SymbolOnly if “Text” is selected:– Text for lightscene call StartOnly if “Symbol” is selected: (see below)

– Display switching status TextSymbol

Only if “Text” is selected:– Text if scene is active ActiveOnly if “Symbol” is selected: (see below)

Symbols for button description “Lightscene retrieval”:

Symbols for status display if scene is active:

LEANtouch (monochrome),SMARTtouch (monochrome, colour)Type: 6x36/30M(-500), 6x36/100x(-500), 6x36/100CB

Page 35: Product manual ABB i-Bus EIB ABB i-bus EIB ABB … · ABB i-bus ® EIB ABB Powernet EIB ... 9 Functions of the panel software 2 - 11 ... Touch-sensitive display 320 x 240 pixels

January 2005 35

ABB i-bus® EIBABB Powernet EIB

LEANtouch (monochrome),SMARTtouch (monochrome, colour)Type: 6x36/30M(-500), 6x36/100x(-500), 6x36/100CB

Parameters: “1-byte lightscenes”touch surfaceThe default setting for the valuesis printed in bold type.

– Name of touch surface <Text>(Control page)

– Lightscene number 1 / 2 / 3 / … / 31 / 32– Store scene by long not possible

push possible– Button description Text

SymbolOnly if “Text” is selected:– Text for lightscene call StartOnly if “Symbol” is selected: (see below)

– Display switching status TextSymbol

Only if “Text” is selected:– Text if scene is active ActiveOnly if “Symbol” is selected: (see below)

Symbols for button description “Lightscene retrieval”:

Symbols for status display if scene is active:

Page 36: Product manual ABB i-Bus EIB ABB i-bus EIB ABB … · ABB i-bus ® EIB ABB Powernet EIB ... 9 Functions of the panel software 2 - 11 ... Touch-sensitive display 320 x 240 pixels

36 January 2005

ABB i-bus® EIBABB Powernet EIB

LEANtouch (monochrome),SMARTtouch (monochrome, colour)Type: 6x36/30M(-500), 6x36/100x(-500), 6x36/100CB

Parameters: “1-byte value” touchsurfaceThe default setting for the valuesis printed in bold type.

– Name of touch surface <Text>(Control page)

– Display type BrightnessWetnessVolumeValueTemperature offset (-5K…+5K)Currentfree scalable

Only for brightness, volume and value:– Value show only

show and send– Range of values 0% to 100%

0 to 255Only for “show and send”:– Button description Text

SymbolOnly if “Text” is selected:– Text for value increasing On– Text for value lowering OffOnly if “Symbol” is selected: (see below)

Only for wetness:– Value show only– Range of values 0% to 100%

0 to 255Only for temperature offset:– Value show and send

– Range of values -5K to +5K– Button description Text

SymbolOnly if “Text” is selected:– Text for value increasing On– Text for value lowering OffOnly if “Symbol” is selected: (see below)

Only for current:– Value show only– Range of values 0 to 51.5 mA

0 to 25.5 AOnly for “free scalable”:– Unit %– Decimal places 0 / 1 / 2– Minimum object value 0– Maximum object value 255– Lowest display value 0– Highest display value 255– Value show only

show and sendOnly for “show and send”:– Button description Text

SymbolOnly if “Text” is selected:– Text for value increasing On– Text for value lowering OffOnly if “Symbol” is selected: (see below)

Symbols for button description:

Page 37: Product manual ABB i-Bus EIB ABB i-bus EIB ABB … · ABB i-bus ® EIB ABB Powernet EIB ... 9 Functions of the panel software 2 - 11 ... Touch-sensitive display 320 x 240 pixels

January 2005 37

ABB i-bus® EIBABB Powernet EIB

LEANtouch (monochrome),SMARTtouch (monochrome, colour)Type: 6x36/30M(-500), 6x36/100x(-500), 6x36/100CB

Parameters: “2-byte value” touchsurfaceThe default setting for the valuesis printed in bold type.

– Name of touch surface <Text>(Control page)

– Display type TemperatureIlluminationWind forcefree scalable

Only for temperature:– Range of values -0.0°C … 40.0°C

-99.9°C … 600.0°C-5K … +5K

Only for -0.0°C…40.0°C:– Increment 0.25°C / 0.5°C / 1°C / 2°COnly for -99.9°C…600.0°C:– Increment 3°C / 5°C / 10°C / 20°COnly for -5K…+5K:– Increment 0.1K / 0.2K / 0.5K / 1K

– Value show onlyshow and send

– Button description TextSymbol

Only if “Text” is selected:– Text for value increasing On– Text for value lowering OffOnly if “Symbol” is selected: (see below)Only for illumination:– Range of values 0…100,000 luxOnly for wind force:– Range of values 0…200 m/sOnly for “free scalable”:– Unit %– Decimal places 0 / 1 / 2 / 3– Minimum object value 0– Maximum object value 100– Lowest display value 0– Highest display value 100– Button description Text

SymbolOnly if “Text” is selected:– Text for value increasing On– Text for value lowering OffOnly if “Symbol” is selected: (see below)

Symbols for button description:

Page 38: Product manual ABB i-Bus EIB ABB i-bus EIB ABB … · ABB i-bus ® EIB ABB Powernet EIB ... 9 Functions of the panel software 2 - 11 ... Touch-sensitive display 320 x 240 pixels

38 January 2005

ABB i-bus® EIBABB Powernet EIB

LEANtouch (monochrome),SMARTtouch (monochrome, colour)Type: 6x36/30M(-500), 6x36/100x(-500), 6x36/100CB

Parameters: “Room thermostat”touch surfaceThe default setting for the valuesis printed in bold type.

– Name of touch surface <Text>(Control page)

– Button InactiveActive

– Button description TextSymbol

Only if “Text” is selected:– Text for comfort Comfort– Text for standby Standby– Text for night reduction NightOnly if “Symbol” is selected: (see below)

Symbols for button description:

Page 39: Product manual ABB i-Bus EIB ABB i-bus EIB ABB … · ABB i-bus ® EIB ABB Powernet EIB ... 9 Functions of the panel software 2 - 11 ... Touch-sensitive display 320 x 240 pixels

January 2005 39

ABB i-bus® EIBABB Powernet EIB

LEANtouch (monochrome),SMARTtouch (monochrome, colour)Type: 6x36/30M(-500), 6x36/100x(-500), 6x36/100CB

Parameters: “Floating value” touchsurfaceThe default setting for the valuesis printed in bold type.

– Name of touch surface <Text>(Control page)

– Unit %– Decimal places 0 / 1 / 2 / 3– Minimum object value 0– Maximum object value 100– Lowest display value 0– Highest display value 100– Value show only

show aOnly for “show and send”:– Button description Text

SymbolOnly if “Text” is selected:– Text for value increasing On– Text for value lowering OffOnly if “Symbol” is selected: (see below)

Symbols for button description:

Page 40: Product manual ABB i-Bus EIB ABB i-bus EIB ABB … · ABB i-bus ® EIB ABB Powernet EIB ... 9 Functions of the panel software 2 - 11 ... Touch-sensitive display 320 x 240 pixels

40 January 2005

ABB i-bus® EIBABB Powernet EIB

LEANtouch (monochrome),SMARTtouch (monochrome, colour)Type: 6x36/30M(-500), 6x36/100x(-500), 6x36/100CB

Parameters: “2-byte counter” touchsurfaceThe default setting for the valuesis printed in bold type.

Parameters: “4-byte counter” touchsurfaceThe default setting for the valuesis printed in bold type.

Parameters: “1-byte counter” touchsurfaceThe default setting for the valuesis printed in bold type.

Parameters: “Text” touch surfaceThe default setting for the valuesis printed in bold type.

– Name of touch surface <Text>(Control page)

– Display type without leading signwith leading sign

– Name of touch surface <Text>(Control page)

– Display type without leading signwith leading sign

– Name of touch surface <Text>(Control page)

– Display type without leading signwith leading sign

– Name of touch surface <Text>(Control page)

– Text show onlyshow and send

Only for “show and send”:– Message text Text

(max. 13 characters)

Page 41: Product manual ABB i-Bus EIB ABB i-bus EIB ABB … · ABB i-bus ® EIB ABB Powernet EIB ... 9 Functions of the panel software 2 - 11 ... Touch-sensitive display 320 x 240 pixels

January 2005 41

ABB i-bus® EIBABB Powernet EIB

LEANtouch (monochrome),SMARTtouch (monochrome, colour)Type: 6x36/30M(-500), 6x36/100x(-500), 6x36/100CB

Functional description: Timeprograms

Settings

Depending on the parameterisation,the SMARTtouch panel offers up to 20(5 for LEANtouch) switch channels.The number of channels that shouldbe enabled is defined in the generalsettings.

In addition, there is the possibility of“Enable time programs for endcustomers” via the correspondingparameter. The modification optioncan be given a code or fully disabled.

Changes made by the end customerare stored in the memory of the paneland are not lost on mains voltagefailure. If however changes are madeto the rest of the panel configurationand then programmed into the panel,the panel software overwrites bydefault the time settings of the endcustomer. This behaviour can bemodified via the setting “Overwritetime switch settings at download”.

A so-called astro function can also beactivated for the individual switchingtimes. This means that a setswitching time adapts itself tosunrises and sunsets. With the option“Town selection”, it is possible toselect a town in Germany which isclosest to the installation site of thepanel. If the exact coordinates areknown, the longitude and latitude canalso be entered.

Holiday

The LEANtouch/SMARTtouch panelhas the option of setting eachindividual channel to a so-calledholiday function. The setting “active onholidays” can be selected for eachswitching time on the switch channel.

Under the menu item “Extra” on thepanel, you can find the “Holiday” touchsurface which you use to activate theholiday function. Two further buttons“Start of holiday” and “End of holiday”are activated which you can use toenter the required date. If the date forthe “Start of holiday” is reached, all thecorresponding holiday time programsare activated automatically.

Individual time programs can thus beretrieved in the holiday period (holidayprofile). When the date for the “End ofholiday” is reached, the holiday timeprograms are automaticallydeactivated.

The holiday function is activated viathe 1-bit communication object“Holiday”. An ON telegram switchesthe function on while an OFF telegramswitches it off again. The linking of theobject “Holiday” with an internaladdress of the panel can of coursealso be carried out.

Note:Please note that only those switchchannels which you have explicitlyselected via the parameter “Switchingfunction” switch on and off in theholiday function. This is carried outseparately for each switching time onthe channel.

Switch channels

Each switch channel has at least one1-bit or 1-byte communication object.It is therefore possible for switch,shutter and/or dimming actuators tobe addressed. The bit size isdetermined via the setting “Function”.

Alternatively, it can also bedetermined via the “Function”parameter whether a room thermostatshould be addressed via a switchchannel. In this case, the switchchannel has two 1-bit objects“Standby/Comfort” and “Night”. It isthereby possible to directly toggle the“Comfort” and “Night” communicationobjects of the room thermostat. Thesecan either be internal objects of thepanel which are linked via an internalgroup address or an external roomthermostat. In the latter case, theobjects must be linked with acorresponding group address.

An additional 1-bit enable object canbe activated on each switch channel.This is carried out via the parameter“Activation object”. If an enable objectis activated, this must receive an ONtelegram so that the time switchchannel is able to switch.

The switch channels of theSMARTtouch panel have 10 (5 forLEANtouch) switching times each.The switching times can either be seton the panel (see diagram) or in theparameters of the panel software.

It can be defined on which day of theweek and at which switching time thechannel should be switched.

Page 42: Product manual ABB i-Bus EIB ABB i-bus EIB ABB … · ABB i-bus ® EIB ABB Powernet EIB ... 9 Functions of the panel software 2 - 11 ... Touch-sensitive display 320 x 240 pixels

42 January 2005

ABB i-bus® EIBABB Powernet EIB

LEANtouch (monochrome),SMARTtouch (monochrome, colour)Type: 6x36/30M(-500), 6x36/100x(-500), 6x36/100CB

If a 1-bit function is set, it is possibleto switch either OFF/UP or ON/DOWN.If a 1-byte function is set, a valuebetween 0 and 255 or a percentagevalue of 0% to 100% can be sent. Theroom thermostat function makes itpossible to change to the comfort,standby or night operating mode ofthe room thermostat.

In addition, the astro functionality canbe activated for each channel.Blocking times can also be set suchas “not before 05:00” or “not after22:00”. The automatic adjustment ofthe astro programs are restricted dueto the position of the sun whichchanges daily. For example, a shutterwould never be lowered later than22:00, even if a further connectionwould be necessary according to theASTRO calender.

Diagram for setting the switchingtimes directly on the panel, if thisoption is enabled

In addition, there is the possibility ofintegrating each channel in theholiday functionality (see also“Holiday”)

Page 43: Product manual ABB i-Bus EIB ABB i-bus EIB ABB … · ABB i-bus ® EIB ABB Powernet EIB ... 9 Functions of the panel software 2 - 11 ... Touch-sensitive display 320 x 240 pixels

January 2005 43

ABB i-bus® EIBABB Powernet EIB

LEANtouch (monochrome),SMARTtouch (monochrome, colour)Type: 6x36/30M(-500), 6x36/100x(-500), 6x36/100CB

Functional description: Timeprograms

Function ApplicationGeneral SettingsSwitch channel 1 SwitchSwitch channel 2 SwitchSwitch channel 3 SwitchSwitch channel 4 SwitchSwitch channel 5 SwitchSwitch channel 6 SwitchSwitch channel 7 SwitchSwitch channel 8 SwitchSwitch channel 9 SwitchSwitch channel 10 SwitchSwitch channel 11 SwitchSwitch channel 12 SwitchSwitch channel 13 SwitchSwitch channel 14 SwitchSwitch channel 15 SwitchSwitch channel 16 SwitchSwitch channel 17 SwitchSwitch channel 18 SwitchSwitch channel 19 SwitchSwitch channel 20 Switch

Communication objectsfor time programs (General)

Communication objectsfor “Switch” switch channel

Communication objectsfor “Value” switch channel

Communication objectsfor RT switch channel

No. Type Object name Function0 1 bit Holiday Receive

No. Type Object name Function0 1 bit Switch Send2 1 bit Enable Send/Receive

No. Type Object name Function0 1 byte Value Send2 1 bit Enable Send/Receive

No. Type Object name Function0 1 bit Standby/Comfort Send1 1 bit Night Send2 1 bit Enable Send/Receive

Page 44: Product manual ABB i-Bus EIB ABB i-bus EIB ABB … · ABB i-bus ® EIB ABB Powernet EIB ... 9 Functions of the panel software 2 - 11 ... Touch-sensitive display 320 x 240 pixels

44 January 2005

ABB i-bus® EIBABB Powernet EIB

LEANtouch (monochrome),SMARTtouch (monochrome, colour)Type: 6x36/30M(-500), 6x36/100x(-500), 6x36/100CB

Parameters: General settingsThe default setting for the valuesis printed in bold type.

General parameters for switchchannels (separate for each switchchannel)The default setting for the valuesis printed in bold type.

General– Number of switch channels 1 / 2 / 3 / 4 / … / 19 / 20

1…20 (LEANtouch (1…5))– Overwrite time switch settings No / Yes

at download– Enable time programs for end Yes

customers With codeNo

– Coordinates for astro displacement via town selectionvia input of coordinates

Only for town selection:– Town Berlin

BielefeldBremenEssenFlensburgFrankfurtHamburgHannoverKasselKölnMönchengladbachMünchenNürnbergSaarbrückenStuttgartDresden

Only for coordinates:– Latitude 51.216– Longitude 7.633

General– Name of time channel <Text>– Function 1 Bit

1 Byte (0…255)1 Byte (0…100%)RT (Standby/Comfort Night)

– Activation object No / YesOnly for “Yes”:– Activation object after mains Disabled

voltage recovery Enabled

Page 45: Product manual ABB i-Bus EIB ABB i-bus EIB ABB … · ABB i-bus ® EIB ABB Powernet EIB ... 9 Functions of the panel software 2 - 11 ... Touch-sensitive display 320 x 240 pixels

January 2005 45

ABB i-bus® EIBABB Powernet EIB

LEANtouch (monochrome),SMARTtouch (monochrome, colour)Type: 6x36/30M(-500), 6x36/100x(-500), 6x36/100CB

– Time 00:00– Weekday Monday

TuesdayWednesdayThursdayFridaySaturdaySundayMonday to FridayMonday to SaturdayMonday to SundaySaturday and Sunday

Only for 1-bit function:– Status Off/Up

On/DownOnly for 1-byte function (0…255)– Status 0Only for 1-byte function (0…100%):– Status 0% / 10% / 20% / … / 90% / 100%Only for RT function:– Status Standby

ComfortNight

– Astro InactiveActive

– Locking Inactivenot before … o‘clocknot after … o‘clock

– Blocking time 00:00– Switching function always inactive

always activeactive on holidaysinactive on holidays

Parameters for switching times(separate for each switching time)The default setting for the valuesis printed in bold type.

Page 46: Product manual ABB i-Bus EIB ABB i-bus EIB ABB … · ABB i-bus ® EIB ABB Powernet EIB ... 9 Functions of the panel software 2 - 11 ... Touch-sensitive display 320 x 240 pixels

46 January 2005

ABB i-bus® EIBABB Powernet EIB

LEANtouch (monochrome),SMARTtouch (monochrome, colour)Type: 6x36/30M(-500), 6x36/100x(-500), 6x36/100CB

Functional description: IR control General

The LEANtouch/SMARTtouch panelcan be addressed via IR remotecontrol. All the panel types operatetogether with the Busch-Ferncontrol®

IR hand-held transmitter. TheSMARTtouch B&O panel canalternatively also be controlled by theBang&Olufson remote control Beo4.

The receiving range of a panel can beset. The IR colours “white”, “blue” or“white & blue”. It is possible to switchbetween colours with the help of aslide switch directly on the Busch-Ferncontrol® hand-held transmitter. Ifthe IR range is set to “white & blue”,the panel software indicates theindividual push button pairs twice -once for the “white” IR range and afurther time for the “blue” IR range.

The parameter “Bang&Olufson” onlyoperates together with theSMARTtouch panel 6x36/100CB. If theIR range is set to “Bang&Olufson”, thepanel can either be operated via theBusch-Ferncontrol® IR hand-heldtransmitter or the Bang&Olufson Beo4IR remote control.

Push button assignment

The individual push button pairs ofthe Busch-Ferncontrol® IR hand-heldtransmitter or the Bang & Olufsonremote control Beo4 can be assignedthe following functions:– Switch,– Dimmer,– Shutter,– Push button,– Value– and Lightscene external input.

The memo buttons of the IR hand-held transmitter or the push buttonsgreen, orange, red, blue and stop ofthe Bang & Olufson remote controlBeo4 can be used for sendinglightscene numbers.

Switch

With the “Switch” function, a 1-bitcommunication object “Switch” isenabled for the push button pair.Switching telegrams are sent via thisobject to the linked actuators. Theparameter “Behaviour” defineswhether the right or the left pushbutton switches “ON”. The setting“TOGGLE” means that toggling is

always carried out when the right orleft push button is pressed i.e. thecommunication object adopts a newvalue after each operation.

Example:If the object currently has the value“1”, the object adopts the value “0”after an operation and sends it. If theobject has the value “0”, the objectvalue changes to “1” after anoperation. The value “1” is of coursealso sent out after a change.

Dimmer

If the function of a push button pair isdefined as a dimmer, the push buttonpair has two communication objects -a 1-bit object “Switch” for sendingswitching telegrams and a 4-bitobject “Dim” for sending dimmingtelegrams.

A switching telegram (ON or OFFtelegram) is always sent after a shortoperation. If a push button is operatedfor a long period (>0.5 s), a dimmingtelegram is triggered.

The parameter “Behaviour” defineswhether dimming brighter or darker iscarried out when the right or left pushbutton is pressed.

Shutter

The shutter functionality of a pushbutton pair causes a push button pairto send stop/step telegrams after ashort operation and up/downtelegrams after a long operation(>0.5 s) to linked shutter actuators.

The shutter function has two 1-bitcommunication objects - “Step” (stop/step) and “Move” (up/down).

The “Behaviour” parameter defineswhether the shutter is raised orlowered when the right or left pushbutton is pressed.

Push button

Via the “Push button” function, it ispossible to send telegrams when apush button of the pair is pressed,released or pressed and released. A1-bit communication object “Switchleft” or “Switch right” is available foreach push button of the pair.

Page 47: Product manual ABB i-Bus EIB ABB i-bus EIB ABB … · ABB i-bus ® EIB ABB Powernet EIB ... 9 Functions of the panel software 2 - 11 ... Touch-sensitive display 320 x 240 pixels

January 2005 47

ABB i-bus® EIBABB Powernet EIB

The behaviour is defined via thecorresponding parameter. When thepush button is operated (on release),an ON, OFF or TOGGLE telegram canbe sent. “TOGGLE” means thattoggling is always carried out whenthe right or left push button isswitched i.e. the communicationobject adopts a new value after eachoperation.

Example:If the object currently has the value“1”, the object adopts the value “0”after an operation and sends it. If theobject has the value “0”, the objectvalue changes to “1” after anoperation. The value “1” is of coursealso sent out after a change.

Value

A value telegram can also betriggered with a push buttonoperation. To do so, the function mustbe set to “Value”. In this case, thepush button pair indicates a 1-bytecommunication object “Value” viawhich the value can be sent.

The parameters “Value push buttonleft” and “Value push button right”define which values should be sentwhen the right or left push button ispressed. Various values between “0”and “255” can be set for the right andleft push button.

Lightscene external input

The function “Lightscene externalinput” enables one of 32 lightscenesto be sent on each push button of thepair. The lightscenes are sent tolinked lightscene modules via a1-byte communication object“Lightscene number”. This can eitherbe the internal lightscenes which arestored in the panel or an externallightscene module.

The settings “Lightscene number left”and “Lightscene number right” definewhich lightscene number is sent.

By default, it is not possible to storelightscenes via the IR hand-heldtransmitter. This can be enabled viathe parameter “Save lightscenes”. Inthis case, the panel sends thelightscene number plus the saveinformation if a push button ispressed for longer than 3 s. Thismeans that an additional bit is set in

LEANtouch (monochrome),SMARTtouch (monochrome, colour)Type: 6x36/30M(-500), 6x36/100x(-500), 6x36/100CB

the lightscene telegram so that thelinked lightscene modules know thatthey must now query the currentstatus values of the actuators.

Lightscene number

If the “Lightscene number” function isused, only one push button e.g. M1 orM2 (no push button pair) is availablefor sending a lightscene. The functionenables the retrieval of one of 32lightscenes. The lightscenes are sentto linked lightscene modules via a1-byte communication object“Lightscene number”. These caneither be the internal lightsceneswhich are stored in the panel or anexternal lightscene module.

The setting “Lightscene number”defines which lightscene number issent.

By default, it is not possible to storelightscenes via the IR hand-heldtransmitter. This can be enabled viathe parameter “Save lightscenes”. Inthis case, the panel sends thelightscene number plus the saveinformation if a push button ispressed for longer than 3 s. Thismeans that an additional bit is set inthe lightscene telegram so that thelinked lightscene modules know thatthey must now query the currentstatus values of the actuators.

Page 48: Product manual ABB i-Bus EIB ABB i-bus EIB ABB … · ABB i-bus ® EIB ABB Powernet EIB ... 9 Functions of the panel software 2 - 11 ... Touch-sensitive display 320 x 240 pixels

48 January 2005

ABB i-bus® EIBABB Powernet EIB

LEANtouch (monochrome),SMARTtouch (monochrome, colour)Type: 6x36/30M(-500), 6x36/100x(-500), 6x36/100CB

Remote control via Bang & Olufsenhand-held transmitter Beo4

The IR hand-held transmitter offersthe following options for controllingthe panel.

Button description Beo4:

Light: Changing of illumination

Record: Saving of lightscene

0 – 9: Light 1 up to 10

A: Lightscene 1

C: Lightscene 2

D: Lightscene 3

F: Lightscene 4

B: On or dimming brighter

E: Off or dimming darker

Stop: All Off

Switching and dimming:

Press the “LIGHT” button on theremote control. The text “LIGHT”appears in the display of the remotecontrol. This mode is active for 25seconds. If the display switches toaudio/video playback again, the“LIGHT” button must be pressedagain.

Once the LIGHT mode is active, thepush buttons for triggering therequired function follow. See the table.

The format LIGHT + 1 + B means thatthe three push buttons must bepressed in sequence (notsimultaneously).

Function Push buttons

Light 1 on

Light 1 dimming brighter

LIGHT + 1 + B

LIGHT + 1 + B, B long push

Light 1 off

Light 1 dimming darker

LIGHT + 1 + E

LIGHT + 1 + E, E long push

Light 2 up to 9 analogue to

Light 1

Light 10 onLight 10 dimming brighter

LIGHT + 0 + B LIGHT + 0 + B, B long push

Light 10 offLight 10 dimming darker

LIGHT + 0 + E LIGHT + 0 + E, E long push

Retrieving and saving lightscenes

Press the “LIGHT” button on theremote control. The text “LIGHT”appears in the display of the remotecontrol. This mode is active for 25seconds. If the display switches toaudio/video playback again, the“LIGHT” button must be pressedagain.

Once the LIGHT mode is active, thepush buttons for triggering therequired function follow. See the table.

The format LIGHT + A means that thetwo push buttons must be pressed insequence (not simultaneously).

Function Push buttons

Call Lightscene 1 LIGHT + A

Call Lightscene 2 LIGHT + C

Call Lightscene 3 LIGHT + D

Call Lightscene 4 LIGHT + F

Save Lightscene 1 LIGHT + RECORD + A

Save Lightscene 2 LIGHT + RECORD + C

Save Lightscene 3 LIGHT + RECORD + D

Save Lightscene 4 LIGHT + RECORD + F

ALL OFF

All the loads are switched off with onepush button action when the “STOP”button is pressed.

Page 49: Product manual ABB i-Bus EIB ABB i-bus EIB ABB … · ABB i-bus ® EIB ABB Powernet EIB ... 9 Functions of the panel software 2 - 11 ... Touch-sensitive display 320 x 240 pixels

January 2005 49

ABB i-bus® EIBABB Powernet EIB

Functional description: IR control forBusch-Ferncontrol® IR hand-heldtransmiter

blue=blue infrared range

white=white infrared range

Functional description: IR remotecontrol for Bang&Olufson remotecontrol Beo4

LEANtouch (monochrome),SMARTtouch (monochrome, colour)Type: 6x36/30M(-500), 6x36/100x(-500), 6x36/100CB

Function ApplicationPush button pair 1 (blue/white) Inactive

SwitchDimmerShutterPush buttonValueLightscene external input

Push button pair 2 (blue/white) InactiveSwitchDimmerShutterPush buttonValueLightscene external input

…Push button pair 5 (blue/white) Inactive

SwitchDimmerShutterPush buttonValueLightscene external input

Memo push button M1 (blue/white) InactiveLightscene number

Memo push button M2 (blue/white) InactiveLightscene number

Memo push button Rot (blue/white) InactiveLightscene number

Function ApplicationPush button 1 up/down Inactive

SwitchDimmerShutterPush buttonValueLightscene external input

Push button 2 up/down InactiveSwitchDimmerShutterPush buttonValueLightscene external input

…Push button 9 up/down Inactive

SwitchDimmerShutterPush buttonValueLightscene external input

Functional description: IR controlGeneral settings.

– IR range whitebluewhite & blueBang & Olufson (only 6x36/100CB)

Page 50: Product manual ABB i-Bus EIB ABB i-bus EIB ABB … · ABB i-bus ® EIB ABB Powernet EIB ... 9 Functions of the panel software 2 - 11 ... Touch-sensitive display 320 x 240 pixels

50 January 2005

ABB i-bus® EIBABB Powernet EIB

LEANtouch (monochrome),SMARTtouch (monochrome, colour)Type: 6x36/30M(-500), 6x36/100x(-500), 6x36/100CB

Push button 0 up/down InactiveSwitchDimmerShutterPush buttonValueLightscene external input

Push button A green InactiveLightscene number

Push button B orange InactiveLightscene number

Push button C red InactiveLightscene number

Push button D blue InactiveLightscene number

Push button stop InactiveLightscene number

Functional description: IR control forBang&Olufson remote control

Communication objectsfor “Switch”

Communication objectsfor “Dimmer”

Communication objectsfor “Shutter”

Communication objectsfor “Push button”

Communication objectsfor “Value”

Communication objectsfor “Lightscene external input” and“Lightscene number”

No. Type Object name Function0 1 bit Switch Send/Receive

No. Type Object name Function0 1 bit Switch Send/Receive1 1 bit Dim Send

No. Type Object name Function0 1 bit Move Send1 1 bit Step Send

No. Type Object name Function0 1 bit Switch left Send1 1 bit Switch right Send

No. Type Object name Function0 1 byte Value Send

No. Type Object name Function0 1 byte Lightscene number Send

Page 51: Product manual ABB i-Bus EIB ABB i-bus EIB ABB … · ABB i-bus ® EIB ABB Powernet EIB ... 9 Functions of the panel software 2 - 11 ... Touch-sensitive display 320 x 240 pixels

January 2005 51

ABB i-bus® EIBABB Powernet EIB

LEANtouch (monochrome),SMARTtouch (monochrome, colour)Type: 6x36/30M(-500), 6x36/100x(-500), 6x36/100CB

Parameters: IR control “Switch”The default setting for the valuesis printed in bold type.

Parameters: IR control “Dimmer”The default setting for the valuesis printed in bold type.

Parameters: IR control “Shutter”The default setting for the valuesis printed in bold type.

Parameters: IR control “Pushbutton”The default setting for the valuesis printed in bold type.

Parameters: IR control “Value”The default setting for the valuesis printed in bold type.

Parameters: IR control “Lightsceneexternal input”The default setting for the valuesis printed in bold type.

Parameters: IR control “Lightscenenumber”The default setting for the valuesis printed in bold type.

– Behaviour Left=on, right=offLeft=off, right=onLeft=toggle, right=toggle

– Behaviour Left brighter on, right darker offLeft darker off, right brighter onLeft brighter toggle, right darker toggleLeft darker toggle, right brighter toggle

– Behaviour Left=up/right=downLeft=down/right=up

– Push button left Send off at rising flankSend off at falling flankSend off at both flanksSend on at falling flankSend off at rising flank,on at falling flankSend on at rising flankSend on at rising flank,off at falling flankSend on at both flanksToggle at rising flank

– Push button right Send off at rising flankSend off at falling flankSend off at both flanksSend on at falling flankSend off at rising flank,on at falling flankSend on at rising flankSend on at rising flank,off at falling flankSend on at both flanksToggle at rising flank

– Value push button left 0– Value push button right 255

– Lightscene number left 1(1…32)

– Lightscene number right 2(1…32)

– Save lightscenes not possiblepossible

– Lightscene number memo 11push button (1…32)

– Save lightscenes not possiblepossible

Page 52: Product manual ABB i-Bus EIB ABB i-bus EIB ABB … · ABB i-bus ® EIB ABB Powernet EIB ... 9 Functions of the panel software 2 - 11 ... Touch-sensitive display 320 x 240 pixels

52 January 2005

ABB i-bus® EIBABB Powernet EIB

Night Comfort Frost/heat prot. object object object

Operating mode Frost prot. 1

Comfort 1 0Night 1 0

Standby 0

A push on theTemperature displayopens the room thermostatoperation modes .

A push on the partysymbol (4. button),changes the operation mode tocomfort for temporary.

LEANtouch (monochrome),SMARTtouch (monochrome, colour)Type: 6x36/30M(-500), 6x36/100x(-500), 6x36/100CB

Functional description: Roomthermostat

The LEANtouch/SMARTtouch panelhas an integrated room thermostat.This has a comparable functionality tothe usual EIB room thermostats.

Operating modes

The room thermostat function hasfour operating modes:– Frost protection mode:

The room temperature control is outof service; the room is only heated ifthe room temperature has fallen solow that there is a risk of the heatinginstallation freezing.

– Comfort mode:The setpoint for the roomtemperature is set to a value whichenables “normal use” of the room ata pleasant temperature.

– Standby mode:The room temperature is lowered(e.g. during temporary absence) sothat heating costs are saved but thecomfort temperature can bereached again quickly.

– Night mode:If the room is not used for anextensive period during the night;

the room temperature is lowered toa pleasant night temperature andcan be increased again relativelyquickly in the morning.

It is possible to toggle betweent theseoperating modes through switchingtelegrams to the communicationobjects “Frost protection”, “Night” and“Comfort” or via the panel display(see also the diagram of theoperating modes). The frost/heatprotection has the highest priority i.e.it is not possible to switch to anotheroperating mode in this case. To doso, the frost/heat protection modemust first be deactivated e.g. byclosing an open window. Comfortmode has the next highest priorityfollowed by night mode. If none of thethree operating modes is active, theroom thermostat is in standby mode.

Party time (Comfort extension)

If the panel is switched to night modevia the bus (or internally), the partytime can be activated via the paneldisplay (change to comfort mode, seediagram top left). Once the party timehas elapsed, the thermostat switchesback to night mode.

During the party time, the symbols fornight and party are shown together inthe display. By pressing the partybutton again, the party time can bereset manually to night reduction.

This function can also be used for thetemporary deactivation of the heat andfrost protection. As in night mode, it ispossible to switch to comfort modefor the parameterised period. Thefunction is switched on and off in thesame way. The symbols for frostprotection and party are showntogether in the display during thiscomfort extension.

Priorities of the operating modes

Page 53: Product manual ABB i-Bus EIB ABB i-bus EIB ABB … · ABB i-bus ® EIB ABB Powernet EIB ... 9 Functions of the panel software 2 - 11 ... Touch-sensitive display 320 x 240 pixels

January 2005 53

ABB i-bus® EIBABB Powernet EIB

SetpointHeating

SetpointCooling

Frost/Heatprotection

Controller calls no power( Control value = 0 )

Comfortmode

Standbymode

NightmodeTemp.

Controlleris act. value > setpoint cooling

cools

Controllerif act. value < setpoint heating

heats

Setpoints in the different operation modes, if heating and cooling is active

Basis-Sollwert

Dead zone between

Setpoint heat protection

Setpoint frost protection

Increasing nightcoolingIncreasing

standby

Lowering nightheating

standbyLowering

heating

heating and cooling

If the party time is inactive, the first but-ton with comfort/standby toggling alsodirectly operates the comfort object. It istherefore possible to set the operatingmode directly to comfort mode while innight mode. When the frost or heat pro-tection mode is active, toggling via thefirst button is stored in the comfort ob-ject.

The recording of the actualtemperature is normally carried out bya built-in temperature sensor. It isalso possible to switch to an externalmeasurement with the parameter“Actual value survey”. Temperaturevalues which are received via theobject “Actual temperature” can thusbe used for control purposes. If nonew values are received for 30 min,the thermostat suspends its functionand no more control value telegramsare sent.

Setpoint values

The following setpoint values can beset for heating mode: “Base setpointin °C (16..31) (Comfort temperatureheating)”, “Lowering standbyoperation heating ... (1..15)”,“Lowering night operation heating inK (1..15)” and “Setpoint frostprotection in °C (4..10)”.

For cooling mode, the comforttemperature can be set via the “Deadzone between heating and cooling inK (1…8)”. The setpoint adjustmentsfor standby and night mode refer tothis value: “Increasing standbyoperation cooling” and “Increasingnight operation cooling”.

If e.g. a room should be cooled at25°C in comfort mode with a basesetpoint of 22°C, a dead zone of 3°Cmust be set. If it should now becooled at 27°C in standby mode, thevalue must be increased by 2°K.Cooling in night mode from 29°Crequires an increase in this value of4°K.

To protect against uncontrolledoverheating of rooms, it is possible toassign a setpoint for heat protectionafter which cooling takes place. If heatprotection is not required, cooling canbe switched off.

LEANtouch (monochrome),SMARTtouch (monochrome, colour)Type: 6x36/30M(-500), 6x36/100x(-500), 6x36/100CB

Setpoints in the different operatingmodes

Page 54: Product manual ABB i-Bus EIB ABB i-bus EIB ABB … · ABB i-bus ® EIB ABB Powernet EIB ... 9 Functions of the panel software 2 - 11 ... Touch-sensitive display 320 x 240 pixels

54 January 2005

ABB i-bus® EIBABB Powernet EIB

Control valueOutput

Control valueRegulatorinternal

00

100%

100%

80%

20%

20% 80%

The base setpoint can be modified asoften as necessary via the bus. To doso, a 2-byte temperature value mustbe sent to the object “Base setpoint”.

The setpoint temperature can bechanged manually via the rockerbuttons on the panel display. Theparameters “Area for manual setpointsetting”, “Maximum increasing ofsetpoint at heating” and “Maximumlowering of control value at cooling”determine the scope for modifying thesetpoint. If a new telegram is sent tothe communication object “Basesetpoint” after a manual setpointadjustment, the manual setpointadjustment can also be reversed.

Heating/cooling

To be able to address the variouscontroller types for heating or coolingmode, the room thermostat can beparameterised as a continuous orswitching controller. In the case of aswitching controller, it is possible tochoose between a PWM controller (“PIcontroller”) and a “Two-positioncontroller”.

In the case of a continuous controlresponse and a switching PWMcontroller, the preset controlparameters regarding the installationtype of the heating or air conditioningsystem can be used. If other controlparameters are needed, they can beset individually via the freeparameterisation option. This optionshould only be used if the user hassufficient experience in controltechnology.

The continuous controller sends its con-trol value to a 1-byte object. Electromo-tive or electrothermal drives which areconnected to heating actuators withPWM control can thus be controlled.

To prevent unnecessary bus loads, itis possible to set by how much thecontrol value must change in order tobe sent on the bus. The setting iscarried out as a percentage. Thesending of the control value is presetby a cyclic period, provided it has notbeen modified. This cycle time shouldnot be set too low (e.g. every 10 min).

In the case of a switching PWMcontroller, the output value of thecontroller (0...255) is converted intoan ON/OFF ratio. If e.g. a control valueof 70% should be issued, the ON timeis 7 min and the OFF time is 3 min ata preset cycle time of 10 min. Thedynamic range can also be limited inthe same way as a continuouscontroller. The parameters “PWMcycle is 0% up to control value” and“PWM cycle is 100% up to controlvalue” are used for this purpose. Ife.g. a maximum control value of 80%is set, the controller automaticallysends the value 255 when a controlvalue of 204 is exceeded. (See alsothe diagram below)

To optimise the control characteristicsof the heating or cooling system, the“Cycle time of the control value” canbe set. To set the correct cycle time,the type of heating or cooling as wellas the valve drive used should betaken into account. The following re-commendations can be used:

LEANtouch (monochrome),SMARTtouch (monochrome, colour)Type: 6x36/30M(-500), 6x36/100x(-500), 6x36/100CB

Page 55: Product manual ABB i-Bus EIB ABB i-bus EIB ABB … · ABB i-bus ® EIB ABB Powernet EIB ... 9 Functions of the panel software 2 - 11 ... Touch-sensitive display 320 x 240 pixels

January 2005 55

ABB i-bus® EIBABB Powernet EIB

a)Electrothermal valve drive:To fully open an electrothermal valvedrive takes approx. 2-3 minutes. Ashorter cycle time than 15 minutesis therefore not advisable.

b)Floor heating:The time constant of a floor heatingsystem is very high. A cycle time of20 minutes is therefore sufficient.

c)Warm water heating:Electrothermal drives are frequentlyused here. A cycle time of 15minutes produces very goodresults.

d)Electric fan heating:Cycle times between 10 and 15minutes are recommended,depending on the electric heatingand spatial conditions.

If a two-position controller is used forheating or cooling control, it ispossible to select the hysteresis bywhich the setpoint fluctuates. If e.g.the setpoint in heating mode is 20°Cand the hysteresis is 0.5 K, thecontroller switches on at 19.75°C andswitches off again at 20.25°C. Thehysteresis that is set then dependson how quickly the heating can heatup the room or how quickly thecooling cools down the room as wellas how sensitive the customer is totemperatures. The hysteresis shouldnot be set too low as otherwise thevalve drive continually opens andcloses. The hysteresis shouldhowever not be set too high as thetemperature fluctuations in the roomare then relatively high.

To increase the accuracy of thecontrol, the parameter “Lowering ofhysteresis” is used. If this parameteris active the hysteresis is reducede.g. every minute by 0.1 K, if requireduntil 0 K. The temperature fluctuationsare effectively reduced during thecontrol by the lowered hysteresis. If areduction should be used, it isadvisable to select a reduction that isless than one fifth of the hysteresis.e.g. Hysteresis 0.5 K =>

Reduction < 0.1 K/min

In certain cases (floor heating), it maybe necessary to install a fast-actingadditional system to enable you toheat the room up quickly. If the“Additional heating” is active, thepanel has a second heating systemavailable with a switching control(1 bit) or a quasi continuous controlwhich regulates the heating with the 1-byte values 0% and 100%.

With the parameters “Level distancefrom the base level to the additionallevel in K” and “Hysteresis (one-sided)”, it is determined when theadditional level is switched on andwhen it is switched off. If e.g. thesetpoint for the second heating levelis set at 18°C with a hysteresis at0.5 K (one-sided), the thermostatswitches on at 18°C and switches offat 18.5°C.

As some valve drives close at a 1-bytevalue of 255 or a 1-bit value of 1 andopen at the corresponding invertedvalues, the “Effective mode” can beinverted.

The toggling between heating andcooling is carried out automatically bythe room thermostat. If this is notrequired, the “Toggle between heatingand cooling” can be carried out by anexternal, central control via the 1-bitobject “Toggle heating cooling”. In thissetting, the heating or coolingsymbols are permanently visibleduring the corresponding operatingmode. If an ON telegram is receivedat the operating mode object, theheating mode is switched on. If anOFF telegram is received, the coolingmode is switched on.

Automatic shading

To prevent the room warming up dueto sunlight, automatic shading can becarried out by lowering one or severalblinds. The object “Shading” is usedfor this purpose.

The parameter “Shading setpoint”determines at which temperature theblinds should be lowered.

If the temperature falls below the setshading temperature, no commandsfor lowering the blinds are sent. Theblinds could be raised at a specifictime e.g. with a central command.

Group master mode

In rooms such as large open-plan of-fices, it can be difficult to achieve effec-tive control throughout the room withonly one panel operating as a roomthermostat. In such cases, it is advisab-le to divide the room into several zonesin which one room thermostat is usedper zone. So that these room thermos-tats always use the same setpoint, the-

LEANtouch (monochrome),SMARTtouch (monochrome, colour)Type: 6x36/30M(-500), 6x36/100x(-500), 6x36/100CB

Page 56: Product manual ABB i-Bus EIB ABB i-bus EIB ABB … · ABB i-bus ® EIB ABB Powernet EIB ... 9 Functions of the panel software 2 - 11 ... Touch-sensitive display 320 x 240 pixels

56 January 2005

ABB i-bus® EIBABB Powernet EIB

LEANtouch (monochrome),SMARTtouch (monochrome, colour)Type: 6x36/30M(-500), 6x36/100x(-500), 6x36/100CB

re is the possibility of activating the pa-rameter “Group master operation mode”for one device. In this case, this devicehas the 2-byte communication object“Base setpoint for slaves” which islinked with the 2-byte communicationobjects “Base setpoint - Telegr. tempe-rature” of the other devices. The manualsetpoint adjustment should then bedisabled for these objects. The opera-ting modes heating/cooling or frost/night/comfort must be set exactly thesame on the master and slave devicesby configuring or assigning the samegroup addresses to the operating modeobjects.

Offset

If the measured temperature iscorrupted by the self-heating of thepanel, an offset value can be set forthe room temperature measurement(setting “Offset value in K x 0.1 K”).

The installation site of the panel andthe appropriate selection ofparameter settings is decisive in theaccurate recording of temperatures.

Page 57: Product manual ABB i-Bus EIB ABB i-bus EIB ABB … · ABB i-bus ® EIB ABB Powernet EIB ... 9 Functions of the panel software 2 - 11 ... Touch-sensitive display 320 x 240 pixels

January 2005 57

ABB i-bus® EIBABB Powernet EIB

Functional description: Roomthermostat

LEANtouch (monochrome),SMARTtouch (monochrome, colour)Type: 6x36/30M(-500), 6x36/100x(-500), 6x36/100CB

Function ApplicationRT Inactive

Heating/Heating and cooling

Communication objects No. Type Object name Function0 1 bit Frost protection Receive1 1 bit Night Send/Receive2 1 bit Comfort Send/Receive3 2 byte Base setpoint Receive4 2 byte Actual temperature Send5 2 byte Act. setpoint Send6 1 bit Shading Send7 1 bit Heating switched Send8 1 bit Additional heating switched Send9 1 bit Cooling switched Send

10 1 bit Toggle heating cooling Send/Receive

No. Type Object name Function…

5 2 byte Base setpoint for slaves Send…

7 1 byte Heating continuously Send8 1 byte Additional heating continuously Send9 1 byte Cooling continuously Send

Page 58: Product manual ABB i-Bus EIB ABB i-bus EIB ABB … · ABB i-bus ® EIB ABB Powernet EIB ... 9 Functions of the panel software 2 - 11 ... Touch-sensitive display 320 x 240 pixels

58 January 2005

ABB i-bus® EIBABB Powernet EIB

LEANtouch (monochrome),SMARTtouch (monochrome, colour)Type: 6x36/30M(-500), 6x36/100x(-500), 6x36/100CB

Parameters: Room thermostatThe default setting for the valuesis printed in bold type.

General:– Control heating Active– Control additional heating Inactive

Active– Control cooling Inactive

Active– Operation mode after reset Comfort

StandbyNightFrost protection

– Cyclic sending of actual value and 14:50setpoint in mm.ss (03:00…60:00)

– Change of actual temp. for Inactive / 0.2 K / 0.4 K / 0.6 K / 0.8 K /automatic sending 1.0 K / 1.5 K / 2.0 K

– Automatic shading (see also Inactivesetpoints) Active

– Party time (extension of comfort Inactive / 30 min / 1 h / 1.5 h / 2 h /mode) 2.5 h / 3 h / 4 h

– Display heating/cooling is active If operation mode is activeAt heating resp. cooling

– Group master operation mode InactiveActive

– Disable frost/heat protection manually Locked(extension of comfort mode) Free

– Actual value survey InternalExternal

– Toggle between heating and automaticcooling via object

– Offset value in K x 0.1 K 0

Setpoints general:– Area for manual setpoint setting Disabled / +- 1K / +- 3K / +- 5K– Maximum increasing of setpoint 3

at heating in K (0…5)Only for cooling:– Maximum lowering of setpoint 3

at cooling in K (0…5)– Send actual setpoint at change Inactive

Active– Manual setpoint setting Reset at receiving of base

setpointHold at receiving of basesetpoint

Only for shading:– Shading setpoint Comfort temperature + 2K

Comfort temperature + 4KComfort temperature + 6KComfort temperature + 8K

– Temperature display at Act. setpointsetpoint adjustment Base setpoint

Page 59: Product manual ABB i-Bus EIB ABB i-bus EIB ABB … · ABB i-bus ® EIB ABB Powernet EIB ... 9 Functions of the panel software 2 - 11 ... Touch-sensitive display 320 x 240 pixels

January 2005 59

ABB i-bus® EIBABB Powernet EIB

LEANtouch (monochrome),SMARTtouch (monochrome, colour)Type: 6x36/30M(-500), 6x36/100x(-500), 6x36/100CB

Setpoints heating:– Base setpoint in °C (16…31) 21

Comfort temperature heating– Lowering standby operation heating 2

in K (1…15)– Lowering night operation heating 4

in K (1…15)– Setpoint frost protection 7

in °C (4…10)– Level distance from the base level 3

to the additional level in K

Controlling/Control value heating:– Output of control value continuously

switched– Control type Two-position controller

PI controllerOnly for two-position controller:– Hysteresis 0.3K / 0.5K / 0.7K / 1K / 1.5K / 2K– Lowering of hysteresis Inactive

0.2 K/min0.1 K/min0.06 K/min0.04 K/min0.03 K/min0.02 K/min

– Cycle time of the control value in mm:ss 14:50(03:00…60:00)Only for continuous controller:– Change for automatic sending of Inactive / 2% / 5% / 10%

control valueOnly for PI controller:– Control parameters via installation type

free setting of parametersOnly for installation type:– Type of heating system Warm water heating (1.5K/100min)

Electric heating (1.5K/50min)Floor heating (4K/200min)

Only for free parameterisation:– Proportional area 1.0K / 1.5K / 2.0K / 2.5K / 3K / 4K /

6K / 8K / 10K– Reset time in min. I part inactive / 10 min / 20 min /

30 min / … / 100 min / … / 240 minOnly for switched controller:– PWM cycle 3min / 5min / 10min / 15min / 20min /

30min / 40min / 50min / 60min– PWM cycle is 0% up to control value 0% / 10% / 20% / 30%– PWM cycle is 100% up to control value 70% / 80% / 90% / 100%– Effective mode Normal

Inverted

Only for additional heating:– Hysteresis (one-sided) 0.3K / 0.5K / 0.7K / 1.0K / 1.5K / 2.0K– Cycle time for automatic sending of the 14:50

control value e in mm:ss (03:00…60:00)– Control value type switched

quasi contin. (1 Byte: 0% or 100%)– Effective mode Normal

Inverted

Parameters: Room thermostatThe default setting for the valuesis printed in bold type.

Page 60: Product manual ABB i-Bus EIB ABB i-bus EIB ABB … · ABB i-bus ® EIB ABB Powernet EIB ... 9 Functions of the panel software 2 - 11 ... Touch-sensitive display 320 x 240 pixels

60 January 2005

ABB i-bus® EIBABB Powernet EIB

LEANtouch (monochrome),SMARTtouch (monochrome, colour)Type: 6x36/30M(-500), 6x36/100x(-500), 6x36/100CB

Only for cooling:Setpoints cooling:– Dead zone between heating and 4

cooling in K (1…8)– Increasing standby operation cooling 2– Increasing night operation cooling 4– Setpoint heat protection Cooling switched off

30°C35°C40°C44°C

Controlling/Control value cooling:– Output of control value continuously

switched– Control type Two-position controller

PI controllerOnly for two-position controller:– Hysteresis 0.3K / 0.5K / 0.7K / 1.0K / 1.5K / 2.0K– Lowering of hysteresis Inactive

0.2 K/min0.1 K/min0.06 K/min0.04 K/min0.03 K/min0.02 K/min

– Cycle time of the control value in 04:46mm:ss (03:00…60:00)

– Effective mode NormalInverted

Only for PI controller:– Control parameters via installation type

free setting of parameters– Type of cooling system Cooling ceiling (5K/240min)

SplitUnit/Fan cooling (4K/90min)– PWM cycle 3min / 5min / 10min / 15min / 20min /

30min / 40min / 50min / 60min– PWM cycle is 0% up to control value 0% / 10% / 20% / 30%– PWM cycle is 100% up to control value 70% / 80% / 90% / 100%– Effective mode Normal

InvertedOnly for free parameterisation:– Proportional area 1.0K / 1.5K / 2.0K / 2.5K / 3K / 4K /

6K / 8K / 10K– Restet time in min. I part inactive / 10 min / 20 min / …

100 min / … / 200 min / 240 minOnly for continuous controller:– Cycle time of the control value in mm:ss 04:46

(03:00…60:00)– Effective mode Normal

Inverted– Change for automatic sending of Inactive / 2% / 5% / 10%

control value

Parameters: Room thermostatThe default setting for the valuesis printed in bold type.

Page 61: Product manual ABB i-Bus EIB ABB i-bus EIB ABB … · ABB i-bus ® EIB ABB Powernet EIB ... 9 Functions of the panel software 2 - 11 ... Touch-sensitive display 320 x 240 pixels

January 2005 61

ABB i-bus® EIBABB Powernet EIB

LEANtouch (monochrome),SMARTtouch (monochrome, colour)Type: 6x36/30M(-500), 6x36/100x(-500), 6x36/100CB

Functional description: LightscenesGeneral settings

General

The LEANtouch/SMARTtouch panelcan be used to send and savelightscenes. Up to 20 EIB actuatorscan be addressed via the memocommunication objects. The numberof memo objects available to thepanel is dependent on the type usedand on the setting “Number of objectsper lightscene”. This can be amaximum of 20 (6 for LEANtouch)objects.

The 1-byte communication object“Lightscene number” is used forretrieving lightscenes. The panelreceives one of 32 lightscene numbersat this object. These lightscenenumbers can be retrieved internally inthe panel e.g. via a touch surface withthe appropriate settings or externally viaan EIB switch sensor.

If the panel receives a lightscenetelegram at its memo objects, it willsend switching or value telegrams insequence to linked actuators. The“Telegram rate between two lightscenetelegrams” can be set. In the Powernetversion, this should not be set too lowas otherwise the bus load isexcessively increased. The preset valueof “1 s” should be sufficient and shouldbe changed if necessary. In theTwisted Pair variant, the telegram rateis not critical and can be lowered ifnecessary.

Lightscene

The size of the memo communicationobjects can be adapted to switch,dimming or shutter actuators. Thismeans that if a switch or shutteractuator should be addressed via amemo object, the object is 1 bit. If adimming actuator should beaddressed, the object is 1 byte. Thebit size is defined individually for eachmemo object via the parameter“Actuator type”.

The LEANtouch/SMARTtouch panelsoftware displays various optionsdepending on the selection.

With the selection “Switch or shutteractuator”, it is possible to set “Off/Up”or “On/Down”. Alternatively, anactuator can also be “Inactive” withina scene.

If “Dim actuator” is set as the actuatortype, percentage values of 0% to100% can be set in increments of10%.

Saving lightscenes

If the end customer would like to carryout changes to the predefinedlightscenes, he can do this without anygreat effort. He must first set all thelamps and/or shutters to the requiredposition i.e. he dims or moves theindividual components via separate EIBswitch sensors or via the touch surfacesof the panel. He then triggers alightscene storage telegram with a longoperation (> 3 s) of a lightscene touchsurface or an additional lightsceneswitch sensor. This telegram isreceived at the object “Lightscenenumber”. The individual memo objectsnow send read requests to the linkedEIB actuators. If the read flag is set forthese objects, the actuators send backtheir current values in responsetelegrams. These values are stored inthe panel and are not lost in the eventof a bus voltage failure.

If changes are carried out on theLEANtouch/SMARTtouch panel andthen programmed in the panel,lightscenes that have been stored byend customers are likewise not lost bydefault. This behaviour can also bemodified via the parameter “Overwritelightscene settings at download”. All thelightscenes can thus be reset to thepreset options which were carried outwith the panel software.

Page 62: Product manual ABB i-Bus EIB ABB i-bus EIB ABB … · ABB i-bus ® EIB ABB Powernet EIB ... 9 Functions of the panel software 2 - 11 ... Touch-sensitive display 320 x 240 pixels

62 January 2005

ABB i-bus® EIBABB Powernet EIB

LEANtouch (monochrome),SMARTtouch (monochrome, colour)Type: 6x36/30M(-500), 6x36/100x(-500), 6x36/100CB

Functional description: LightscenesGeneral settings

Functional description: LightscenesApplication

Function ApplicationLightscene actuator Lightscene

General:– Number of objects per lightscene 8

(1…20)– Telegram rate between two 130ms / 260ms / 520ms / 1s / 2s /

lightscene telegrams 4s / 10s / 35s– Overwrite lightscene settings No / Yes

at download

Communication objects for 1-bitactuator types

Communication objects for 1-byteactuator types

No. Type Object name Function0 1 byte Lightscene number Receive1 1 bit Memo object 1 Send/Receive2 1 bit Memo object 2 Send/Receive3 1 bit Memo object 3 Send/Receive4 1 bit Memo object 4 Send/Receive5 1 bit Memo object 5 Send/Receive6 1 bit Memo object 6 Send/Receive7 1 bit Memo object 7 Send/Receive8 1 bit Memo object 8 Send/Receive9 1 bit Memo object 9 Send/Receive

10 1 bit Memo object 10 Send/Receive11 1 bit Memo object 11 Send/Receive12 1 bit Memo object 12 Send/Receive13 1 bit Memo object 13 Send/Receive14 1 bit Memo object 14 Send/Receive15 1 bit Memo object 15 Send/Receive16 1 bit Memo object 16 Send/Receive17 1 bit Memo object 17 Send/Receive18 1 bit Memo object 18 Send/Receive19 1 bit Memo object 19 Send/Receive20 1 bit Memo object 20 Send/Receive

No. Type Object name Function0 1 byte Lightscene number Receive1 1 byte Memo object 1 Send/Receive2 1 byte Memo object 2 Send/Receive3 1 byte Memo object 3 Send/Receive4 1 byte Memo object 4 Send/Receive5 1 byte Memo object 5 Send/Receive6 1 byte Memo object 6 Send/Receive7 1 byte Memo object 7 Send/Receive8 1 byte Memo object 8 Send/Receive9 1 byte Memo object 9 Send/Receive

10 1 byte Memo object 10 Send/Receive11 1 byte Memo object 11 Send/Receive12 1 byte Memo object 12 Send/Receive13 1 byte Memo object 13 Send/Receive14 1 byte Memo object 14 Send/Receive15 1 byte Memo object 15 Send/Receive16 1 byte Memo object 16 Send/Receive17 1 byte Memo object 17 Send/Receive18 1 byte Memo object 18 Send/Receive19 1 byte Memo object 19 Send/Receive20 1 byte Memo object 20 Send/Receive

Page 63: Product manual ABB i-Bus EIB ABB i-bus EIB ABB … · ABB i-bus ® EIB ABB Powernet EIB ... 9 Functions of the panel software 2 - 11 ... Touch-sensitive display 320 x 240 pixels

January 2005 63

ABB i-bus® EIBABB Powernet EIB

LEANtouch (monochrome),SMARTtouch (monochrome, colour)Type: 6x36/30M(-500), 6x36/100x(-500), 6x36/100CB

Separate for each actuator type (1…20):– Actuator type Switch or shutter actuator

Dim actuatorOnly for switch or shutter actuator:Separate for each scene (1…32):– Scene … Off / Up

On / DownInactive

Only for dim actuator:Separate for each scene (1…32):– Scene 0% / 10% / 20% / 30% / 40% / 50% /

60% / 70% / 80% / 90% / 100%

Parameters: LightscenesThe default setting for the valuesis printed in bold type.

Page 64: Product manual ABB i-Bus EIB ABB i-bus EIB ABB … · ABB i-bus ® EIB ABB Powernet EIB ... 9 Functions of the panel software 2 - 11 ... Touch-sensitive display 320 x 240 pixels

64 January 2005

ABB i-bus® EIBABB Powernet EIB

LEANtouch (monochrome),SMARTtouch (monochrome, colour)Type: 6x36/30M(-500), 6x36/100x(-500), 6x36/100CB

Functional description: Alarmfunction

The panel offers the possibility ofdisplaying up to 10 different alarmmessages. The parameter “Numberof alarm messages” defines therequired number.

Each alarm message has its owncommunication object “Alarm 1” to“Alarm 10”. The communicationobjects can either be 1 bit or 14 byte.The setting “Type of the alarm object”sets the size of the object. Each alarmobject can thus be set individually.

The alarm function can be used incombination with the inputs of themonitoring function (see page 18) oron its own. In combination with themonitoring function, the inputs andthe alarm objects must be linked viainternal group addresses.

If a telegram e.g. an ON telegram isreceived at an alarm object, a windowis opened in the screen of the panel,in which the alarm text is displayed.The alarm text can be freely entered inthe panel software. The panelsimultaneously triggers a signal tone.The duration of the signal tone can beset and it can also be deactivated.

All alarm messages which occur orhave occurred can be displayed via afurther window in the panel. Thewindow is opened by pressing the“Extras” button followed by “Alarmmessages/Fault messages”. Allalarm and fault messages aredisplayed with the date, time andacknowledgement.

The acknowledgement of an alarmmessage is carried out via the “OK”button in the alarm text window. If thesetting “Send zero at acknowledge”has been activated with “yes” for a1-bit alarm object, the group addressthat is linked with the alarm object issent on the bus with the value “0”.

In the case of a 14-byte alarm object,an individual acknowledgement text(max. 13 characters) can be sent withthe acknowledgement.

Via the acknowledgement object“Acknowledge global”, a groupaddress is sent as soon as anacknowledgement has been carriedout at one of the alarm objects.

Page 65: Product manual ABB i-Bus EIB ABB i-bus EIB ABB … · ABB i-bus ® EIB ABB Powernet EIB ... 9 Functions of the panel software 2 - 11 ... Touch-sensitive display 320 x 240 pixels

January 2005 65

ABB i-bus® EIBABB Powernet EIB

LEANtouch (monochrome),SMARTtouch (monochrome, colour)Type: 6x36/30M(-500), 6x36/100x(-500), 6x36/100CB

Functional description: Alarmfunction

Function ApplicationAlarm messages Inactive

Settings

Communication objects for 1-bitalarm messages

Communication objects for 14-bytealarm messages

No. Type Object name Function0 1 bit Acknowledge global Send1 1 bit Alarm 1 Send/Receive2 1 bit Alarm 2 Send/Receive3 1 bit Alarm 3 Send/Receive4 1 bit Alarm 4 Send/Receive5 1 bit Alarm 5 Send/Receive6 1 bit Alarm 6 Send/Receive7 1 bit Alarm 7 Send/Receive8 1 bit Alarm 8 Send/Receive9 1 bit Alarm 9 Send/Receive

10 1 bit Alarm 10 Send/Receive

No. Type Object name Function…

1 14 byte Alarm 1 Send/Receive2 14 byte Alarm 2 Send/Receive3 14 byte Alarm 3 Send/Receive4 14 byte Alarm 4 Send/Receive5 14 byte Alarm 5 Send/Receive6 14 byte Alarm 6 Send/Receive7 14 byte Alarm 7 Send/Receive8 14 byte Alarm 8 Send/Receive9 14 byte Alarm 9 Send/Receive

10 14 byte Alarm 10 Send/Receive

General:– Number of alarm messages 5

(1…10)

Separate for each alarm message:Alarm message…:– Type of the alarm object …: 1 Bit / 14 Byte

Only for 1 bit:– Text for alarm message <Text>– Text at acknowledge <Text>– Send zero at acknowledge No / YesOnly for 14 byte:– Send text at acknowledge No / Yes

Only if “Yes” is selected:– Text at acknowledge <Text>

– Time of the audio signal No signal30 s1 min2 in5 min10 min30 min1 h

Parameters: Alarm functionThe default setting for the valuesis printed in bold type.

Page 66: Product manual ABB i-Bus EIB ABB i-bus EIB ABB … · ABB i-bus ® EIB ABB Powernet EIB ... 9 Functions of the panel software 2 - 11 ... Touch-sensitive display 320 x 240 pixels

66 January 2005

ABB i-bus® EIBABB Powernet EIB

LEANtouch (monochrome),SMARTtouch (monochrome, colour)Type: 6x36/30M(-500), 6x36/100x(-500), 6x36/100CB

Functional description: Presencesimulation

Functional description: Presencesimulation

Function ApplicationSimulation Inactive

Active

Communication objects No. Type Object name Function0 1 bit Activation Receive1 1 bit Simulation 1 Send/Receive2 1 bit Simulation 2 Send/Receive3 1 bit Simulation 3 Send/Receive4 1 bit Simulation 4 Send/Receive5 1 bit Simulation 5 Send/Receive6 1 bit Simulation 6 Send/Receive7 1 bit Simulation 7 Send/Receive8 1 bit Simulation 8 Send/Receive9 1 bit Simulation 9 Send/Receive

10 1 bit Simulation 10 Send/Receive

– Waiting time up to the activation 30s / 40s / 50s / 1min / 1.1min /1.2min / 1.5 min / 2 min

Parameters: Presence simulationThe default setting of the valuesis printed in bold type.

The panel has an integratedpresence simulation function. Thismeans that the panel can send outtelegrams fully independently andconveys the impression that thehouse is occupied.

If the presence simulation function isactivated, the panel software displays10 x 1-bit communication objects“Simulation 1” to “Simulation 10” forcontrolling switch and/or shutteractuators and a 1-bit communicationobject “Activation” for the activation ordeactivation of the presencesimulation.

The presence simulation is activatedwith an ON telegram at the “Activation”object. An OFF telegram deactivates itagain.

If the presence simulation is notactive (OFF telegram has beenreceived at the activation object), itportrays “normal” telegram traffic. Thepanel learns the habits of theoccupants of the house. The panelhas a memory which recordstelegrams for seven days. On theeighth day, the memory location of thefirst of the seven days is overwritten.

If the panel only had three days tocarry out a recording, only these threedays are repeated when the functionis activated.

The panel ignores cyclicaltransmitters during the recording.This means it only records an actualchange.

Once an ON telegram has beenreceived at the “Activation” object, thepanel first waits until the “Waiting timeup to the activation” has elapsed. Onlythen does the simulation start. Thedelay can be set between 30 s and2 min.

The activated presence simulationsends the information that has beenrecorded over several days on a 1:1basis.

It is a good idea to integrate functionsin the presence simulation which arenot linked with a holiday function of atime channel. This could be e.g. thelounge light, the kitchen light andabove all the hallway light.

Page 67: Product manual ABB i-Bus EIB ABB i-bus EIB ABB … · ABB i-bus ® EIB ABB Powernet EIB ... 9 Functions of the panel software 2 - 11 ... Touch-sensitive display 320 x 240 pixels

January 2005 67

ABB i-bus® EIBABB Powernet EIB

&E1

E2 A

E1 E2 A0 0 00 1 01 0 01 1 1

And

>1E1

E2 A

E1 E2 A0 0 00 1 11 0 11 1 1

Or

&E1

E2 A

E1 E2 A0 0 10 1 11 0 11 1 0

NAND

>1E1

E2 A

E1 E2 A0 0 10 1 01 0 01 1 0

NOR

LEANtouch (monochrome),SMARTtouch (monochrome, colour)Type: 6x36/30M(-500), 6x36/100x(-500), 6x36/100CB

Functional description: Logicalfunctions (1…8)

E1: Input 1E2: Input 2

A: Output

Up to 8 different logic functions canbe integrated in the panel. Each logicfunction can adopt one of thefollowing functions:– AND– OR– NAND– NOR– Multiplexer– Multiplier– Gate– Temperature comparator 1I1O– Temperature comparator 2I1O

AND, OR, NAND and NOR

If the function is defined with AND,OR, NAND or NOR, up to four inputcommunication objects can beenabled per logic function. The size ofthe inputs can either be 1 bit or 1 byte.When a new telegram is received atthe input, it is switched according tothe selected function. In addition, theinputs can be inverted together.

Example of “AND” 1-byte inputs:If the inputs are 1 byte, all the inputvalues must be greater than “0” inorder to achieve a positive result.

Example of inverted “AND” 1-byteinputs:If the inputs are 1 byte and inverted,all the input values must be equal to“0” in order to achieve a positiveresult.

Each function has an output object towhich the result determined from theinputs is sent. The output object canbe 1 bit or 1 byte, depending on theparameterisation. The default valuewhich should be sent in the event of apositive result can be set. In addition,a delay for sending the output signalcan also be selected.

It is also possible to set an output filter.This means that either only “On”, only“Off” or “On and Off” can be sent for a1-bit output object. With a 1-byte outputobject, it can be set whether “only thegiven value”, “only Off” or “only the gi-ven value and Off” should be sent.

Page 68: Product manual ABB i-Bus EIB ABB i-bus EIB ABB … · ABB i-bus ® EIB ABB Powernet EIB ... 9 Functions of the panel software 2 - 11 ... Touch-sensitive display 320 x 240 pixels

68 January 2005

ABB i-bus® EIBABB Powernet EIB

LEANtouch (monochrome),SMARTtouch (monochrome, colour)Type: 6x36/30M(-500), 6x36/100x(-500), 6x36/100CB

So that the inputs are not undefinedafter a voltage failure and subsequentvoltage recovery, there is theparameter “Behaviour of inputs afterreset”. The inputs can either be readi.e. send read requests to the linkedobjects which leads to an increasedbus load or the inputs can adoptdefault values which can be definedin the parameters.

Multiplexer

&

&

>1

S

E1

S

E2

A

Via the “Multiplexer” logic function, theinput data to the output can becontrolled directly. The function hasfour communication objects“Controller”, “Input 1”, “Input 2” and“Output”. The diagram aboveindicates the function of a 1-bitmultiplexer (S=Controller, E1=Input 1,E2=Input 2, A= Output).

The bit size of the inputs and outputscan be set to 1 byte or 2 byte via theparameter “Object type input/output”.The above functionality is therebyretained. That means that only input 1is visible at the output if the controlinput has the value “1”. Input 2 isswitched to the output as soon as thecontrol input has the value “0”.

Note:The output is only sent when there isan actual change of the inputs. If e.g.the control input changes without theinput value changing, the outputsignal remains as it is. A new outputvalue is sent only if an input signalchanges.

Multiplier

The “Multiplier” function enables up tofour output telegrams to be sent with aninput telegram. The input communicationobject is 1 bit. The output communicati-on objects can either be 1 bit or 1 byte.

The size is set via a corresponding pa-rameter.

It can be defined via the setting“Starting conditions” whether aduplication of an input telegramshould be triggered after an ON orOFF telegram. Moreover, there is thepossibility of sending outputtelegrams with a time delay. Bydefault, a delay of 1 s is defined.

The useful information (values) whichshould be sent with the outputtelegrams can be set individually foreach output via a correspondingparameter. For 1-bit outputs, this is“On” or “Off” while for 1-byte outputs,values between “0” and “255” can beassigned.

Gate

With the “Gate” logic function, it ispossible to filter specific signals andto disable the signal flow temporarily.The function has threecommunication objects “Controlinput”, “Input” and “Output”.

The control input is 1 bit and the inputand output objects are likewise 1 bitby default. The object types at theinput and output can also be set to“not assigned”. That means that thebit size can be freely assigned. Thefirst internal or external groupaddress which is assigned and isalready linked with anothercommunication object defines thesize.

The control is always carried out frominput to output provided that this ispermitted by the control input. Theactivation via the control input can becarried out via an ON or an OFFtelegram. If the setting “Control input”is set to “ON telegram” for example,only telegrams from the input to theoutput are routed if a “1” haspreviously been received at thecontrol input.

For 1-bit input and output objects, it canbe set whether the input signals shouldbe saved or not “During the blocking”. Ifthe setting “Store input signal” is se-lected, the output sends its value if atelegram has been received at the inputduring the blocking.

Page 69: Product manual ABB i-Bus EIB ABB i-bus EIB ABB … · ABB i-bus ® EIB ABB Powernet EIB ... 9 Functions of the panel software 2 - 11 ... Touch-sensitive display 320 x 240 pixels

January 2005 69

ABB i-bus® EIBABB Powernet EIB

LEANtouch (monochrome),SMARTtouch (monochrome, colour)Type: 6x36/30M(-500), 6x36/100x(-500), 6x36/100CB

If the input and output objects are1 bit, it is possible to invert the output.An inversion element can therefore beimplemented by a gate.

It is also possible to block signals viathe “Filter function” setting. Thefollowing settings are possible: “Filternothing”, “Filter ON” or “Filter OFF”.This function is e.g. only necessary ifthe ON telegram from a sensor is ofinterest and this sensor does nothave a filter function in its applicationprogram.

Temperature comparator

The two temperature comparatorfunctions correspond to the functionsof the DIN rail mounted logic module.

Temperature comparator 1I1O

With the function “Temperaturecomparator 1I1O”, a temperature iscompared with an internally definedtemperature value. The functionmakes an input available with a2-byte communication object.Temperature telegrams which aretriggered by an EIB temperaturesensor are received at this object andcompared.

The value which the temperature atinput 1 should be compared with, isdefined in the parameter“Comparative value in °C”. Thiscomparative value (input 2) can adoptvalues between –30 °C and +70 °C.

Application example:Monitoring of a warehouse. Foodshould be stored in the warehouse ata temperature below 12 °C. An EIBtemperature sensor is installed forthis purpose. If the storagetemperature exceeds 12 °C, a coolingunit is switched on in order to keepthe food fresh.

So that telegrams are not triggeredcontinually, if the temperature values forcomparison are almost identical, it isadvisable to set a hysteresis. By default,this is set at 1.5 K. This means that if thetemperature of the comparative value hasa value of 12 °C and the temperature atthe input exceeds a value of 12 °C, a te-legram is not immediately triggered at theoutput. It is only triggered when it exceeds12.75 °C. The output is reset when a tem-perature falls below 11.25 °C.

The output communication object is1 bit by default. ON or OFF telegramsare sent to this object. It is defined inthe parameters when a telegram issent. Depending on the setting“Telegram will be sent at”, telegramsare triggered if an input is greaterthan another input or if the resultchanges. A change in the resultmeans that the value of the input hasexceeded or fallen below thecomparative value.

In addition, it can be set whether anON telegram or an OFF telegram issent when the value exceeds or fallsbelow the comparative value.

1-byte values can also be sent to theoutput object. To do so, the parameter“Object type of the output” must be setto “1 byte”. In a similar way to theswitch output, different conditions canalso be set to determine when atelegram should be sent. The valuewhich is sent is defined with thesettings “It will be sent if input >comparative value” or “…if input <comparative value”. Values between 0and 255 can be sent.

The output value is sent cyclically ifthe setting “Send output cycle” isactivated. The cycle time is set bydefault at 9:59 but can be adapted toa required cycle time.

Temperature comparator 2I1O

Two temperatures can be comparedwith this function. There are twoseparate inputs available with 2-bytecommunication objects. Temperaturetelegrams which are triggered by EIBtemperature sensors are received atthese objects and compared witheach other.

Application example:Summer/wintertime conversion in aventilation control system. An EIBtemperature sensor is installed in thesupply air and discharge air ducts. Ifthe incoming temperature is identicalto or warmer than the outgoing tempera-ture, it is possible to switch to summermode.

The output communication object is1 bit by default. ON or OFF telegramsare sent to this object. It is defined in theparameters when a telegram is sent.Depending on the setting “Telegram will

Page 70: Product manual ABB i-Bus EIB ABB i-bus EIB ABB … · ABB i-bus ® EIB ABB Powernet EIB ... 9 Functions of the panel software 2 - 11 ... Touch-sensitive display 320 x 240 pixels

70 January 2005

ABB i-bus® EIBABB Powernet EIB

be sent at”, telegrams are triggered if aninput is greater than another input or ifthe result changes. A change in the re-sult means that the value of input 1 hasexceeded or fallen below the value ofinput 2.

In addition, it can be set whether anON telegram or an OFF telegram issent when the value of one inputexceeds or falls below the value of theother input.

1-byte values can also be sent to theoutput object. To do so, the parameter“Object type of the output” must be setto “1 byte”. In a similar way to theswitch output, different conditions canalso be set to determine when atelegram should be sent. The valuewhich is sent is defined with thesettings “It will be sent if input 1 >input 2” or “…if input 1 < input 2”.Values between 0 and 255 can besent.

The output value is sent cyclically if thesetting “Send output cycle” is activated.The cycle time is set by default at 9:59but can be adapted to a required cycletime.

LEANtouch (monochrome),SMARTtouch (monochrome, colour)Type: 6x36/30M(-500), 6x36/100x(-500), 6x36/100CB

Page 71: Product manual ABB i-Bus EIB ABB i-bus EIB ABB … · ABB i-bus ® EIB ABB Powernet EIB ... 9 Functions of the panel software 2 - 11 ... Touch-sensitive display 320 x 240 pixels

January 2005 71

ABB i-bus® EIBABB Powernet EIB

Functional description: Logicalfunctions (1…8)

LEANtouch (monochrome),SMARTtouch (monochrome, colour)Type: 6x36/30M(-500), 6x36/100x(-500), 6x36/100CB

Function ApplicationLogical function 1 Inactive

ANDORNANDNORMultiplexerMultiplierGateTemperature comparator 1I1OTemperature comparator 2I1O

Logical function 2 InactiveANDORNANDNORMultiplexerMultiplierGateTemperature comparator 1I1OTemperature comparator 2I1O

…Logical function 7 Inactive

ANDORNANDNORMultiplexerMultiplierGateTemperature comparator 1I1OTemperature comparator 2I1O

Logical function 8 InactiveANDORNANDNORMultiplexerMultiplierGateTemperature comparator 1I1OTemperature comparator 2I1O

Page 72: Product manual ABB i-Bus EIB ABB i-bus EIB ABB … · ABB i-bus ® EIB ABB Powernet EIB ... 9 Functions of the panel software 2 - 11 ... Touch-sensitive display 320 x 240 pixels

72 January 2005

ABB i-bus® EIBABB Powernet EIB

LEANtouch (monochrome),SMARTtouch (monochrome, colour)Type: 6x36/30M(-500), 6x36/100x(-500), 6x36/100CB

Communication objects for 1-bitinputs (AND, OR, NAND and NOR)

Communication objects for 1-byteinputs (AND, OR, NAND and NOR)

Communication objects for 1-bitmultiplexer

Communication objects for 1-bytemultiplexer

Communication objects for 2-bytemultiplexer

Communication objects for 1-bitmultiplier

Communication objects for 1-bytemultiplier

Communication objects for gatefunction

Communication objects fortemperature comparator 1I1O with1-bit output

No. Type Object name Function0 1 bit Output Send/Receive1 1 bit Input 1 Receive2 1 bit Input 2 Receive3 1 bit Input 3 Receive4 1 bit Input 4 Receive

No. Type Object name Function0 1 bit Output Send/Receive1 1 byte Input 1 Receive2 1 byte Input 2 Receive3 1 byte Input 3 Receive4 1 byte Input 4 Receive

No. Type Object name Function0 1 bit Controller Receive1 1 bit Input 1 Receive2 1 bit Input 2 Receive3 1 bit Output Send

No. Type Object name Function0 1 bit Controller Receive1 1 byte Input 1 Receive2 1 byte Input 2 Receive3 1 byte Output Send

No. Type Object name Function0 1 bit Controller Receive1 2 byte Input 1 Receive2 2 byte Input 2 Receive3 2 byte Output Send

No. Type Object name Function0 1 bit Input Receive1 1 bit Output 1 Send2 1 bit Output 2 Send3 1 bit Output 3 Send4 1 bit Output 4 Send

No. Type Object name Function0 1 bit Input Receive1 1 byte Output 1 Send2 1 byte Output 2 Send3 1 byte Output 3 Send4 1 byte Output 4 Send

No. Type Object name Function0 1 bit Control input Receive1 1 bit Input Send/Receive2 1 bit Output Send/Receive

No. Type Object name Function0 2 byte Input Receive1 1 bit Output Send

Page 73: Product manual ABB i-Bus EIB ABB i-bus EIB ABB … · ABB i-bus ® EIB ABB Powernet EIB ... 9 Functions of the panel software 2 - 11 ... Touch-sensitive display 320 x 240 pixels

January 2005 73

ABB i-bus® EIBABB Powernet EIB

LEANtouch (monochrome),SMARTtouch (monochrome, colour)Type: 6x36/30M(-500), 6x36/100x(-500), 6x36/100CB

Communication objects fortemperature comparator 1I1O with1-byte output

Communication objects fortemperature comparator 2I1O with1-bit output

Communication objects fortemperature comparator 2I1O with1-byte output

No. Type Object name Function0 2 byte Input Receive1 1 byte Output Send

No. Type Object name Function0 2 byte Input 1 Receive1 2 byte Input 2 Receive2 1 bit Output Send

No. Type Object name Function0 2 byte Input 1 Receive1 2 byte Input 2 Receive2 1 byte Output Send

Page 74: Product manual ABB i-Bus EIB ABB i-bus EIB ABB … · ABB i-bus ® EIB ABB Powernet EIB ... 9 Functions of the panel software 2 - 11 ... Touch-sensitive display 320 x 240 pixels

74 January 2005

ABB i-bus® EIBABB Powernet EIB

LEANtouch (monochrome),SMARTtouch (monochrome, colour)Type: 6x36/30M(-500), 6x36/100x(-500), 6x36/100CB

– Used inputs 1 / 2 / 3 / 4– Type of input 1 Bit / 1 Byte– Invert inputs No / Yes– Behaviour of inputs after reset Reading

Given valueOnly for 1 bit:– Given value Off / OnOnly for 1 byte:– Given value 0

– Type of output 1 Bit / 1 Byte– Behaviour of the output Send always

At change– After overwriting of output Take value

Do not take value– Delay of the output No / Yes

telegramOnly if “Yes” is selected:– Time delay 04:59

Only for 1 bit:– Output filter Send only on

Send only offSend on and off

Only for 1 byte:– Output filter Send only given value

Send only offSend given value and off

– Given value 1(1…255)

– Object type input/output 1 Bit1 Byte2 Byte

General:– Starting conditions OFF telegram

ON telegram– Telegram delay (s) 01:00Separate for each output:– Object type Output … 1 Bit / 1 Byte

Only for 1 bit:– Display output … Off / OnOnly for 1 byte:– Display output … 0

– Control input Activate at OFFActivate at ON

– Object type of input and output 1 Bitnot assigned

Only for 1 bit:– During the blocking Do not store input signal

Store input signal– Filter function Filter nothing

Filter ONFilter OFF

– Invert output No / Yes

Parameters: AND, OR, NAND andNOR logic functionsThe default setting for the valuesis printed in bold type.

Parameters: MultiplexerThe default setting for the valuesis printed in bold type.

Parameters: MultiplierThe default setting for the valuesis printed in bold type.

Parameters: Gate functionThe default setting for the valuesis printed in bold type.

Page 75: Product manual ABB i-Bus EIB ABB i-bus EIB ABB … · ABB i-bus ® EIB ABB Powernet EIB ... 9 Functions of the panel software 2 - 11 ... Touch-sensitive display 320 x 240 pixels

January 2005 75

ABB i-bus® EIBABB Powernet EIB

LEANtouch (monochrome),SMARTtouch (monochrome, colour)Type: 6x36/30M(-500), 6x36/100x(-500), 6x36/100CB

General:– Comparative value (in °C) 18– Hysteresis 1.5– Object type of the output 1 Bit / 1 Byte– Telegram will be sent at Input is greater than comparative value

Input is less than comparative valueOutput changing

Only for 1 bit:– It will be sent if OFF telegram

Input > Comparative value ON telegram– It will be sent if OFF telegram

Input > Comparative value ON telegramOnly for 1 byte:– It will be sent if 0

Input > Comparative value– It will be sent if 255

Input > Comparative value– Send output cycle No / Yes

Only if “Yes” is selected:– Cycle time (mm:ss) 09:59

General:– Object type of the output 1 Bit / 1 Byte– Telegram will be sent at Input 1 is greater than input 2

Input 1 is less than input 2Output changing

Only for 1 bit:– It will be sent if OFF telegram

Input 1 > Input 2 ON telegram– It will be sent if OFF telegram

Input 1 < Input 2 ON telegramOnly for 1 byte:– It will be sent if 0

Input 1 > Input 2– It will be sent if 255

Input 1 < Input 2– Send output cycle No / Yes

Only if “Yes” is selected:– Cycle time (mm:ss) 09:59

Parameters: Temperaturecomparator 1I1O (1 input 1 output)The default setting for the valuesis printed in bold type.

Parameters: Temperaturecomparator 2I1O (2 inputs 1 output)The default setting for the valuesis printed in bold type.