—PRODUCT BROCHURE
SVIT isolated truckSuitable for UniGear switchgear12...40.5 kV, ...4000 A, ...50 kA
— Table of contents
005
006 – 007
008 – 014
015 – 016
017 – 018
018
1 Summary
2 Technical data
3 Overall dimensions
4 Electric circuit diagrams
5 Installation, commissioning and operation
6 Maintenance
—For your safety!
• Make sure that the installation room (spaces, divisions and ambient) is suitable for the electrical apparatus
• Check that all the installation, putting into service and maintenance operations are carried out by qualified personnel with suitable knowledge of the apparatus
• Make sure that the standard and legal prescriptions are complied with during installation, putting into service and maintenance, so that installations according to the rules of good working practice and safety in the work place are constructed
• Strictly follow the information given in this instruction manual
• Check that the rated performance of the apparatus is not exceeded during service
• Check that the personnel operating the apparatus have this instruction manual to hand as well as the necessary information for correct intervention
• Pay special attention to the danger notes indicated in the manual by the following symbol
All the installation, putting into service, running and maintenance operations must be carried out by skilled personnel with in-depth knowledge of the apparatus.
4 SVIT ISOLATED TRUCK PRODUCT BROCHURE
—1 Summary
1.1 GeneralSVIT isolated truck is suitable for the indoor air- insulated withdrawable version switchgear, for the main circuit without load transfer, as well as the isolation for electrical equipment with chared lines, for example, main bus bar, circuit breaker, etc.
These trucks allow the top contacts to be connected directly to the bottom ones, connection is made extremely safe and reliable by using the "pole" type to insulate the connection busbars from the external environment.
In the incoming/outgoing units, the isolated truck connects the main busbar system to the power cables, whereas in the bus-tie units, it connects the two sides of the bus bar system.
1.2 Standards and specification1.2.1 StandardsThe SVIT isolated trucks conform to the specifications of the following standards.• GB/T 11022, common technical requirements
of high-voltage switchgear and control equipment
• IEC 60694 and VDE 0670 part 1000, common specifications for high-voltage switchgear and control gear standards
• GB/T 1985, high-voltage AC isolated switch and earthing switch
• IEC 62271-102 and DIN VDE 0671 part 102, common alternating current disconnectors and earthing switches
1.2.2 Installation and operatingThe relevant standards and specifications shall be considered and complied, in particular:• IEC 61936 and DIN VDE 0101, power installations
exceeding 1 kV a.c.• Safety and accident prevention regulations
published by professional groups or organizations• Related safety guidelines of auxiliary materials
and operational tools• Safety regulations of ABB Xiamen switchgear
Co., Ltd.
1.3 Operating conditions1.3.1 Normal service condition• Ambient temperature
- Max temperature +40°- Average maximum over 24 hours +35° - Min temperature -15°
• Humidity- The average relative humidity measured for
a period longer than 24 must not exceed the 95%
- The average value of the pressure of the water vapor, measured for a period longer than 24 hours, must not exceed 2.2 kPa
- The average value of the relative humidity, measured for a period longer than 1 month, must not exceed the 90%
- The average value of the pressure of the water vapor, measured for a period longer than 1 month, must not exceed 1.8 kPa
• Altitude: ≤1000 m
• Atmospheric environmentAmbient air should not be obviously polluted by the dust, smoke, corrosive or flammable gas, vapor, spray.
1.3.2 Special service conditions• Installation above 1000 m altitude
Possible within the limits allowed by reduction of the dielectric resistance of air
• Increase the air temperatureIn order to avoid the risk of corrosion or other damage in areas with high humidity and/or rapid large fluctuations in temperature, take appropriate measures (for example, using suitable electric heaters) to prevent any condensation phenomena. For special installation requirements or other operating conditions, please contact ABB.
S U M M A R Y 5
2.1 Technical data of SVIT isolated truck
2.2 Technical date for different type of SVIT isolated truck
Overall
dimension
s
Electric
circuit
diagrams
1) If require, it can reach to 190 kV.
12 kV /17.5 kV withdrawable version suitable for UniGear ZS1 switchgear
IT 1212-31 H=205 P=150
IT 1212-31 H=205 P=210
IT 1212-40 H=310 P=210 4)
IT 1212-50 H=310 P=210
IT 1216-50 H=310 P=210
IT 1220-50 H=310 P=210
IT 1220-50 H=310 P=275
IT 1225-50 H=310 P=275
IT 1231-50 H=310 P=275
IT 1240 1)-50 H=310 P=275
12 kV /17.5 kV withdrawable version suitable for UniGear 550 switchgear
SVIT/L 12.12.32 H=240 P=150
SVIT/L 12.20.32 H=240 P=150
24 kV withdrawable version suitable for UniGear ZS1 switchgear
SVIT/P 24.12.25 H=310 P210
SVIT/P 24.12.25 H=310 P275
SVIT/P 24.25 1).25 H=310 P275
SVIT/P 24.12.32 H=310 P210
SVIT/P 24.12.32 H=310 P275
SVIT/P 24.20 2).32 H=310 P275
SVIT/P 24.32 1).32 H=310 P275
40.5 kV withdrawable version suitable for UniGear ZS3.2 switchgear 3)
IT 4012-31 H=328 P=280
IT 4016-31 H=328 P=280
IT 4025-31 H=328 P=280
IT 4031 1)-31 H=328 P=280
Rated
voltage
kV
12-17.5
12-17.5
12-17.5
12-17.5
12-17.5
12-17.5
12-17.5
12-17.5
12-17.5
12-17.5
12-17.5
12-17.5
24
24
24
24
24
24
24
40.5
40.5
40.5
40.5
Rated
current
A
...1250
...1250
...1250
...1250
...1600
...2000
...2000
...2500
...3150
...4000
...1250
...2000
...1250
...1250
...2500
...1250
...1250
...2000
...3150
...1250
...1600
...2500
...3150
Rated Peak
withstand
current kA
...80
...80
...100
...125
...125
...125
...125
...125
...125
...125
...80
...80
...63
...63
...63
...80
...80
...80
...80
...100
...100
...100
...100
Rated short-
time withstand
current kA
...31.5
...31.5
...40
...50
...50
...50
...50
...50
...50
...50
...31.5
...31.5
...25
...25
...25
...31.5
...31.5
...31.5
...31.5
...31.5
...31.5
...31.5
...31.5
Rated duration
of short-circuit
s
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
1YH8122134
1YH8122135
1YH8122136
1YH8125117
1YH8125118
1YH8122137
1YH8122138
1YH8122139
1YH8122140
1YH8122141
1YH8102114
1YH8123101
1YH8123112
1YH8123112
1YH8123101
1) With force ventilation.2) Meet 2500 A with force ventilation.3) BIL 190 kV, need special remarks when ordering.4) There are two types of contact tulip, need special remarks when ordering.
—2 Technical data
6 SVIT ISOLATED TRUCK PRODUCT BROCHURE
Rated voltage
Rated power frequency withstand voltage
Rated frequency
Rated power frequency withstand voltage-across the insulating distance
Rated lightning impulse withstand voltage
Rated lightning impulse withstand voltage-across the insulating distance
Rack in/out cycle
24
65
50/60
79
125
145
1000
40.5
95
50/60
118
185 1)
215
1000
17.5
38
50/60
45
95
110
1000
12
42
50/60
48
75
85
1000
kV
kV
Hz
kV
kV
kV
second
Types
IT...
2.4 Technical data of the locking magnet (-RL2/-Y0) on truck
Characteristic
s
Locking
magnet
(-RL2/-Y0)
Rated Voltage
V
DC*
24-30-48-60-110
125-127-132-220-240
AC 50/60 Hz**
24-30-48-60-110
125-127-132-220-230...240
Range of
voltage
80...110% Un
80...110% Un
Inrush
power
250 W
250 VA
Continuous
power 1)
5 W
5 VA
Inrush
duration ms
150
150
Inrush
duration
Long time
Long time
1) Approximation.
T E C H N I C A L D A T A 7
2.3 Technical data of the truck motor (-MT) 1)
Rated voltage
V, DC
48
110
220
Range of voltage
80...110% Un
80...110% Un
80...110% Un
Rated current
1.5
0.6
0.3
Rated Power 2)
40
40
40
Motor time Work
position-isolated position
S
35~60
35~60
35~60
Work system
S2
S2
S2
1) It is only available for 12 kV/17.5 kV/24 kV isolated truck for UniGear ZS1. 2) Approximation.
Suitable for UniGear ZS1
1) Rail.2) Front edge of bar.3) Insulated tubing is used only for 630 A 25 kA rating.4) Heat shrink tubing.5) If ф49 needed, please remark when ordering.
IT For VD4
1YH 8122134
Ur 12 kV
17.5 kV
Ir 1250 A
Isc 31.5 kA
IT For VD4
1YH 8122135
Ur 12 kV
17.5 kV
Ir 1250 A
Isc 40 kA
P
150
210
A
502
650
C
466
616
D
490
640
E
503
653
G
42.5
41.5
I
492
636
фW
35
49
фM
79
88
—3 Overall dimensions
8 SVIT ISOLATED TRUCK PRODUCT BROCHURE
Travel 8-11 mm
Travel 8-11 mm
*) Rail1) Remove and store prior
to commissioning
IT For VD4
1YH 8122136
Ur 12 kV
17.5 kV
Ir 1250 A
1600 A
2000 A
2500 A
3150 A
4000 A*
Isc 50 kA
Ir
1250 A
1600 A
2000 A
2500 A
3150 A
4000 A
P
210
210
275
210
275
275
275
275
A
650
650
850
650
850
850
850
850
C
618
618
812
618
812
812
812
812
D
640
640
836
640
836
836
836
836
E
653
653
853
653
853
853
853
853
G
636
636
844
636
844
844
844
844
M
128
128
128
128
128
152
152
152
W
79
79
79
79
79
109
109
109
U
694
694
694
694
694
694
735
735
1) Only suitable for ≥3150 A. * With force ventilation.
O V E R A L L D I M E N S I O N S 9
Travel 8-11 mm
10 SVIT ISOLATED TRUCK PRODUCT BROCHURE
Suitable for UniGear 550
SVIT/L For Vmax
1YH 8125117
Ur 12 kV
17.5 kV
Ir ...1250 A
Isc ...31.5 kA
SVIT/L For Vmax
1YH 8125118
Ur 12 kV
17.5 kV
Ir ...2000 A
Isc ...31.5 kA
P
210
275
A
610
805
B
641
836
C
650
850
D
653
853
G
636
842
H
44
144
* With force ventilation.
1600-2000 A 2500 A
O V E R A L L D I M E N S I O N S 11
Suitable for UniGear ZS1
SVIT/P For VD4
1YH 8122137
Ur 24 kV
Ir ...1250 A
Isc ...25 kA
SVIT/P For VD4
1YH 8122138
Ur 24 kV
Ir 1600 A
2000 A
2500 A*
Isc ...25 kA
1250 A
P
210
275
A
650.5
850.5
C
570
750
D
608
808
E
636
836
F
653
853
G
44
144
*) Rail.**) Front edge of bar.1) Suitable for UniGear ZS1.1b) BT1&BT2 (S8/S9) inside the truck.2) Remove and store prior to commissioning.
*) Rail.**) Front edge of bar.1) Suitable for UniGear ZS1.1b) BT1&BT2 (S8/S9) inside the truck.2) Remove and store prior to commissioning.3) 2500 A With force ventilation.
12 SVIT ISOLATED TRUCK PRODUCT BROCHURE
Suitable for UniGear ZS1
SVIT/P For VD4
1YH 8122139
Ur 24 kV
Ir 1250 A
Isc 31.5 kA
Suitable for UniGear ZS1
SVIT/P For VD4
1YH 8122140
Ur 24 kV
Ir 2000 A
Isc 31.5 kA
*) Rail.1) Suitable for UniGear ZS1.1b) BT1&BT2 (S8/S9) inside the truck.2) Remove and store prior to commissioning.3) 3150A With force ventilation.
O V E R A L L D I M E N S I O N S 13
Suitable for UniGear ZS1
SVIT/P For VD4
1YH 8122141
Ur 24 kV
Ir 3150 A
Isc 31.5 kA
A
12 kV24 kV
Earthing device on truck (suitable for 12 kV/17.5 kV/ 24 kV)
14 SVIT ISOLATED TRUCK PRODUCT BROCHURE
Suitable for UniGear ZS3.2
IT For VD4
1YH 8102114
Ur 40.5 kV
Ir 1250 A
1600 A
2500 A
3150 A
Isc ...31.5 kA
TK =Transport bracket 147TP =Transport profile 148K =Entrance for control cables50.2 =Front partition plate170 =Fan
NOTE:Transport bracket TK (147) and transport profile TP (148) only fitted for handing.Remove and store prior to commissioning.The travel of truck is 450 mm.
a) 1250 A and 1600 A contact arm.b) 2000 A to 3150 A contact arm, 3150 A With force
ventilation.
Electric circuit diagrams (suitable for UniGear ZS1/ZS3.2) No.: 1YH8123101
E L E C T R I C C I R C U I T D I A G R A M S 15
—4 Electric circuit diagrams
Stat
e o
f o
per
atio
n sh
own
Th
e d
iag
ram
ind
icat
es t
he
follo
win
g c
on
dit
ion
s: T
he
iso
late
d
tru
ck in
th
e ra
cked
-in
po
siti
on
.
Des
crip
tio
n o
f fi
gur
esF
ig.8
= L
ock
ing
mag
net
. Th
e m
ech
anis
m lo
cked
wh
en
de-
ener
giz
ed t
o p
reve
nt t
he
rack
-in
/ou
t o
per
atio
n o
f is
ola
ted
tru
ckF
ig.5
1= C
ont
acts
fo
r el
ectr
ical
sig
nalin
g o
f is
ola
ted
tru
ck in
th
e ra
cked
-in
an
d is
ola
ted
po
siti
on
, lo
cate
d o
n t
he
iso
late
d t
ruck
.F
ig.4
0=
Ele
ctri
c d
rive
cir
cuit
fo
r tr
uck
Fig
.60
= C
ont
rol c
ircu
it u
sed
in f
orc
e ve
ntila
tio
n c
on
dit
ion
.
Cap
tio
n□
=
Nu
mb
er o
f d
iag
ram
of
fig
ure
-QS
= Is
ola
ted
Tru
ck-X
O=
Co
nn
ecto
r o
f th
e is
ola
ted
tru
ck c
ircu
its
-X
= T
erm
inal
bo
x in
th
e sw
itch
gea
r (o
uts
ide
the
iso
late
d
tru
ck)
-S8
= C
ont
acts
fo
r el
ectr
ical
sig
nal
ing
of
iso
late
d t
ruck
in
iso
late
d p
osi
tio
n (
see
no
te E
)-S
9=
Co
ntac
ts f
or
elec
tric
al s
ign
alin
g o
f is
ola
ted
tru
ck in
ra
cked
-in
po
siti
on
(se
e n
ote
E)
-Y0
= L
ock
ing
mag
net
. Wh
en d
e-en
erg
ized
it m
ech
anic
ally
p
reve
nts
iso
late
d t
ruck
co
nn
ecti
on
an
d is
ola
tio
n.
-V0
= S
erie
s re
ctif
ier
-MT
= T
ruck
dri
vin
g m
oto
r-F
AN
No
tes
A)
Th
e is
ola
ted
tru
ck is
on
ly w
ith
th
e ac
cess
ori
es
sp
ecif
ied
in t
he
ord
er c
on
firm
atio
n.-Y
0 a
nd
-M
T
are
fitt
ing
s se
lect
ion
. In
any
cas
e, c
on
sid
erin
g
the
po
ssib
ility
of
dif
fere
nt c
on
fig
ura
tio
n o
f th
e is
ola
ted
tru
ck, o
r th
e is
ola
ted
tru
ck it
self
mig
ht
be
up
dat
ed, t
he
actu
al c
ont
rol c
ircu
it m
ight
be
up
dat
ed.
E)
Th
e co
ntac
ts f
or
elec
tric
al s
ign
alin
g o
f is
ola
ted
tr
uck
in t
he
rack
ed-i
n a
nd
iso
late
d p
osi
tio
n
sho
w in
fig
s.51
are
loca
ted
on
th
e is
ola
ted
tru
ck
(mo
vin
g p
art)
.F
) F
igs.
40
on
ly s
uit
able
fo
r 12
kV
an
d 2
4 k
V
iso
late
d t
ruck
wit
h d
rivi
ng
mo
tor.
Electric circuit diagrams (suitable for UniGear ZS1/ZS3.2) No.: 1YH8123112
16 SVIT ISOLATED TRUCK PRODUCT BROCHURE
Stat
e o
f o
per
atio
n sh
own
Th
e d
iag
ram
ind
icat
es t
he
follo
win
g c
on
dit
ion
s: T
he
iso
late
d
tru
ck in
th
e ra
cked
-in
po
siti
on
.
Des
crip
tio
n o
f fi
gur
esF
ig.8
=
Lo
ckin
g m
agn
et. T
he
mec
han
ism
lock
ed
wh
en d
e-en
erg
ized
to
pre
vent
th
e ra
ck-i
n/o
ut
op
erat
ion
of
iso
late
d t
ruck
Fig
.51
= C
ont
acts
fo
r el
ectr
ical
sig
nalin
g o
f is
ola
ted
tr
uck
in t
he
rack
ed-i
n a
nd
iso
late
d
po
siti
on
, lo
cate
d o
n t
he
iso
late
d t
ruck
.F
ig.4
0=
Ele
ctri
c d
rive
cir
cuit
fo
r tr
uck
Cap
tio
n□
=
Nu
mb
er o
f d
iag
ram
of
fig
ure
-QS
= Is
ola
ted
Tru
ck-X
B
=
Co
nn
ecto
r o
f th
e is
ola
ted
tru
ck c
ircu
its
-XB
1
= T
erm
inal
bo
x in
th
e sw
itch
gea
r (o
uts
ide
the
iso
late
d t
ruck
)-X
B4
*9=
Ap
plic
atio
n c
on
nec
tors
-BT
2
= C
ont
acts
fo
r el
ectr
ical
sig
nal
ing
of
iso
late
d t
ruck
in
iso
late
d p
osi
tio
n (
see
no
te E
)-B
T1
=
Co
ntac
ts f
or
elec
tric
al s
ign
alin
g o
f is
ola
ted
tru
ck
in r
acke
d-i
n p
osi
tio
n (
see
no
te E
)-R
L2
= L
ock
ing
mag
net
. Wh
en d
e-en
erg
ized
it
mec
han
ical
ly p
reve
nts
iso
late
d t
ruck
co
nn
ecti
on
an
d is
ola
tio
n.
-BD
= P
osi
tio
n c
ont
act
of
swit
chg
ear
do
or
-MT
= T
ruck
dri
vin
g m
oto
r
No
tes
B)
Th
e is
ola
ted
tru
ck is
on
ly w
ith
th
e ac
cess
ori
es s
pec
ifie
d in
th
e o
rder
co
nfi
rmat
ion
.-R
L2 a
nd
-M
T a
re f
itti
ng
s se
lect
ion
. In
any
cas
e, c
on
sid
erin
g t
he
po
ssib
ility
of
dif
fere
nt
con
fig
ura
tio
n o
f th
e is
ola
ted
tru
ck, o
r th
e is
ola
ted
tru
ck
itse
lf m
ight
be
up
dat
ed, t
he
actu
al c
ont
rol c
ircu
it m
ight
b
e u
pd
ated
.G
) T
he
cont
acts
fo
r el
ectr
ical
sig
nal
ing
of
iso
late
d t
ruck
in
the
rack
ed-i
n a
nd
iso
late
d p
osi
tio
n s
ho
w in
fig
s.51
are
lo
cate
d o
n t
he
iso
late
d t
ruck
(m
ovi
ng
par
t).
H)
Fig
s.4
0 o
nly
su
itab
le f
or
VD
4 is
ola
ted
tru
ck w
ith
dri
vin
g
mo
tor.
5.1 General requirementsIsolated truck doesn't have the capability of on and off load current, therefore not allowed to rack in/out isolated truck with load.
5.2 Installation preparation• Clean the insulating parts with clean dry cloths• Check that the top and bottom terminals are
clean and free of any deformation caused by shocks received during transport or storage
5.3 Installation and Commissioning of switchgearApplicable switchgear types of isolated truck refer to section 2.2 content.
For rack in/out of the switchgear, fully insert the lever in the appropriate seat and work it clockwise for racking-in, and anticlockwise for racking-out, until the limit switch positions are reached.
Isolated truck racking-in/-out must be carried out gradually to avoid shocks which may deform the mechanical interlocks and the limit switches. If operations are prevented or difficult, do not force them, check that the operating sequence is correct and locking magnet on the truck (-RL2/-Y0) (if provided) is powered.
NoteTo complete the racking-in/out operation, about 20 rotations of the lever are required for isolated- trucks up to 12 kV and 40.5kV, and about 30 rotations for 24 kV isolated-trucks.
Isolated-trucks of the same type have the same dimension, as well as same earthing methods and installation position.
5.3.1 Motorized isolated truckMotorized isolated trucks rack into the pane, must take following inspection and test.• Cut down the power for the drive motor supply,
check whether the isolated truck is pushed in place, truck beam positioning interlocking piece whether into the slots on either side the corresponding switch cabinet, handle whether can move around flexible
• Turn the lever to the required position. Check whether there is truck wave into the binding,
truck and earthing knife, interlocking is reset• Check whether the motor power supply positive
and negative polarity is correct:a) Using manual handle isolated truck into the
middle position;b) Remove the manual handle;c) Connect the power;d) Through the switchgear electrical control
to operate and check its moving direction is correct.
If its moving direction is not correct, please quickly to cut off the dive motor power (usually by a limit switch to make its stop motion). To avoid personal injury, please shut the door.
Motorized truck operations• Activate the controls for electrical racking-in
and racking-out (the withdrawable isolated truck traverses in the directions indicated by the controls)
• Check the position indicators
NoteIf the motor failure or burned, can be switch to manual mode to rock the isolated truck into service position or test isolated position, should be cut down the power of electric locking truck drive motor. The conversion process from motorized to manual:• Disconnect the power• Insert the handle into the hole• Truck in service position: clockwise, rotation 45°
Truck in test position: counterclockwise, rotation 45° Truck in middle position: slight wobble around the handle
• For normal manual operation
Note: For the motorized truck, if by manual mode rock in/out the isolated truck, the signal correctly, in order to ensure its position auxiliary contacts must be rocked into the limit position.
• Isolated truck rock into the test position, should ensure that the screw head to figure a position counter-clockwise again after wave around 45°
I N S T A L L A T I O N , C O M M I S S I O N I N G A N D O P E R A T I O N 17
—5 Installation, commissioning and operation
• Isolated truck rock into the service positions should ensure the handle cannot be rocked again
The operation about the truck rocked out of the panel from the test position:Should ensure the handle position as shown in fig. a, and the handle of the truck (17) can flexible moving.
Fig. a
Motor control protection device MDC2 can be configured to avoid various types of failures or burning, other choice of motor protection devices must be matched with the device and using same characteristics and replacement of spare parts, otherwise it may damage the electrical machine.
5.4 Connection of the auxiliary circuitsNote: the minimum cross-section of the wires used for the auxiliary circuits must not be less than the one used for the internal cabling. Furthermore, they must be insulated for 2 kV of test.
Isolated truck auxiliary circuit connection factory has passed the aviation plug lead.
5.1 General requirementsIsolated truck doesn't have the capability of on and off load current, therefore not allowed to rack in/out isolated truck with load.
5.2 Installation preparation• Clean the insulating parts with clean dry cloths• Check that the top and bottom terminals are
clean and free of any deformation caused by shocks received during transport or storage
5.3 Installation and Commissioning of switchgearApplicable switchgear types of isolated truck refer to section 2.2 content.
For rack in/out of the switchgear, fully insert the lever in the appropriate seat and work it clockwise for racking-in, and anticlockwise for racking-out, until the limit switch positions are reached.
Isolated truck racking-in/-out must be carried out gradually to avoid shocks which may deform the mechanical interlocks and the limit switches. If operations are prevented or difficult, do not force them, check that the operating sequence is correct and locking magnet on the truck (-RL2/-Y0) (if provided) is powered.
NoteTo complete the racking-in/out operation, about 20 rotations of the lever are required for isolated- trucks up to 12 kV and 40.5kV, and about 30 rotations for 24 kV isolated-trucks.
Isolated-trucks of the same type have the same dimension, as well as same earthing methods and installation position.
5.3.1 Motorized isolated truckMotorized isolated trucks rack into the pane, must take following inspection and test.• Cut down the power for the drive motor supply,
check whether the isolated truck is pushed in place, truck beam positioning interlocking piece whether into the slots on either side the corresponding switch cabinet, handle whether can move around flexible
• Turn the lever to the required position. Check whether there is truck wave into the binding,
Maintenance serves to ensure trouble-free operation and achive the longest possible working life of the switchgear.
The servicing intervals and scope are determined by environmental influences, and the rack in/out times, etc.
The isolated truck have a low maintenance requirement, only visual and function inspections are required.
• Visual inspection of poles to check for any contamination, corrosion, or traces of electrical discharge
• check the racking-in/out operation of the truck is normal or not, clean and smear lubricant
truck and earthing knife, interlocking is reset• Check whether the motor power supply positive
and negative polarity is correct:a) Using manual handle isolated truck into the
middle position;b) Remove the manual handle;c) Connect the power;d) Through the switchgear electrical control
to operate and check its moving direction is correct.
If its moving direction is not correct, please quickly to cut off the dive motor power (usually by a limit switch to make its stop motion). To avoid personal injury, please shut the door.
Motorized truck operations• Activate the controls for electrical racking-in
and racking-out (the withdrawable isolated truck traverses in the directions indicated by the controls)
• Check the position indicators
NoteIf the motor failure or burned, can be switch to manual mode to rock the isolated truck into service position or test isolated position, should be cut down the power of electric locking truck drive motor. The conversion process from motorized to manual:• Disconnect the power• Insert the handle into the hole• Truck in service position: clockwise, rotation 45°
Truck in test position: counterclockwise, rotation 45° Truck in middle position: slight wobble around the handle
• For normal manual operation
Note: For the motorized truck, if by manual mode rock in/out the isolated truck, the signal correctly, in order to ensure its position auxiliary contacts must be rocked into the limit position.
• Isolated truck rock into the test position, should ensure that the screw head to figure a position counter-clockwise again after wave around 45°
18 SVIT ISOLATED TRUCK PRODUCT BROCHURE
—6 Maintenance
• Isolated truck rock into the service positions should ensure the handle cannot be rocked again
The operation about the truck rocked out of the panel from the test position:Should ensure the handle position as shown in fig. a, and the handle of the truck (17) can flexible moving.
Fig. a
Motor control protection device MDC2 can be configured to avoid various types of failures or burning, other choice of motor protection devices must be matched with the device and using same characteristics and replacement of spare parts, otherwise it may damage the electrical machine.
5.4 Connection of the auxiliary circuitsNote: the minimum cross-section of the wires used for the auxiliary circuits must not be less than the one used for the internal cabling. Furthermore, they must be insulated for 2 kV of test.
Isolated truck auxiliary circuit connection factory has passed the aviation plug lead.
Only when the isolated truck In the test position, and the angle of the screw as shown in the right picture, the handcart may remove from the switchgear.
1YH
A0
00
123_
EN
RE
V B
20
19.0
6