Safety instructions Process pressure transmitter IPT-1* PTB 06 ATEX 2017 X, 1. supplement II 1G, II 1/2G, II 2GEx ia IIC T6 Process pressure transmitter IPT-1*

Transcript of Process pressure transmitter IPT 1 -...

Page 1: Process pressure transmitter IPT 1 - WIKAapps.wika.com/declarations/01_SI_IPT-10-11_Atex_IS_38985-EN.pdf · Fieldbus l IPT1* - Vers .3 0-37300 - 4 … 20 mA, 31543 - 4 … 20 mA/HART,

Safety instructions

Process pressure transmitter IPT-1*

PTB 06 ATEX 2017 X, 1. supplementII 1G, II 1/2G, II 2G Ex ia IIC T6

Process pressure transmitter IPT-1*

Page 2: Process pressure transmitter IPT 1 - WIKAapps.wika.com/declarations/01_SI_IPT-10-11_Atex_IS_38985-EN.pdf · Fieldbus l IPT1* - Vers .3 0-37300 - 4 … 20 mA, 31543 - 4 … 20 mA/HART,

Contents

1 Area of applicability . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6

2 General information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6

2.1 Category 1G instruments . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6

2.2 Category 1/2G instruments . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6

2.3 Category 2G instruments . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6

3 Technical data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7

3.1 Electrical data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7

4 Application conditions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9

5 Protection against static electricity . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11

6 Use of an overvoltage arrester . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11

7 Grounding . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11

8 Impact and friction sparks . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11

9 Material resistance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12

10 Mounting with external indicating unit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12

11 Installation/mounting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12

Please note:

These safety instructions are part of the documentation:

l IPT1* - Vers. 2.0

- 37299 - 4 … 20 mA, 31540 - 4 … 20 mA/HART, 31541 - Profibus PA, 31542 - FoundationFieldbus

l IPT1* - Vers. 3.0

- 37300 - 4 … 20 mA, 31543 - 4 … 20 mA/HART, 31544 - Profibus PA, 331545 - FoundationFieldbus

l 39357 - EC type approval certificate PTB 06 ATEX 2017 X

2 WIKA Safety Instructions Process pressure transmitter IPT-1*

38985-EN-121031

Page 3: Process pressure transmitter IPT 1 - WIKAapps.wika.com/declarations/01_SI_IPT-10-11_Atex_IS_38985-EN.pdf · Fieldbus l IPT1* - Vers .3 0-37300 - 4 … 20 mA, 31543 - 4 … 20 mA/HART,

DESicherheitshinweise für den Einsatz in explosionsgefährdeten Bereichen, verfügbar in denSprachen deutsch, englisch, französisch und spanisch.

ENSafety instructions for the use in hazardous areas are available in German, English, Frenchand Spanish language.

FRConsignes de sécurité pour l'utilisation en atmosphère explosible, disponibles dans leslangues allemande, anglaise, française et espagnole.

ESInstrucciones de seguridad para el empleo en áreas con riesgo de explosión, disponible enlos siguientes idiomas alemán, ingles, francés y español.

CZPokud nastanou potíže při čtení bezpečnostních upozornění v otištěných jazycích,poskytneme. Vám na základě žádosti k dispozici kopii v jazyce Vaší země.

DAHvis De har svært ved at forstå sikkerhedsforskrifterne på de trykte sprog, kan. De få en kopipå Deres sprog, hvis De ønsker det.

ELΕάν δυσκολεύεστε να διαβάσετε τις υποδείξεις ασφαλείας στις γλώσσες που ήδη έχουντυπωθεί, τότε σε περίπτωση ζήτησης μπορούμε να θέσουμε στη διάθεσή σας ένααντίγραφο αυτών στη γλώσσα της χώρας σας.

ETKui teil on raskusi trükitud keeltes ohutusnõuete lugemisega, siis saadame me teiejärelepärimise peale nende koopia teie riigi keeles.

FILaitteen mukana on erikielisiä turvallisuusohjeita. Voit tilata meiltä äidinkieliset turvallisuu-sohjeet, jos et selviä mukana olevilla kielillä.

HUHa a biztonági előírásokat a kinyomtatott nyelveken nem tudja megfelelően elolvasni, akkorlépjen velünk kapcsolatba: azonnal a rendelkezésére bocsátunk egy példányt az Önországában használt nyelven.

ITSe le Normative di sicurezza sono stampate in una lingua di difficile comprensione, poteterichiederne una copia nella lingua del vostro paese.

LTJei Jums sunku suprasti saugos nuorodų tekstą pateiktomis kalbomis, kreipkitės į mus ir mesJums duosime kopiją Jūsų šalies kalba.

LVJa Jums ir problēmas drošības noteikumus lasīt nodrukātajās valodās, tad mēs Jumssniegsim pēc pieprasījuma kopiju Jūsu valsts valodā.

MTF’kaz li jkollok xi diffikulta` biex tifhem listruzzjonijiet ta’ sigurta`kif ipprovduti, infurmana u ahnanibghatulek kopja billingwa tieghek.

NLAls u moeilijkheden mocht hebben met het lezen van de veiligheidsinstructies in deafgedrukte talen, sturen wij u op aanvraag graag een kopie toe in uw eigen taal.

PLW przypadku trudności odczytania przepisów bezpieczeństwa pracy w wydrukowanychjęzykach, chętnie udostępnimy Państwu kopię w języku obowiązującym w danym kraju.

PTCaso tenha dificuldade de ler as instruções de segurança no idioma, no elas foramimpressas, poderá solicitar junto a nós uma cópia em seu idioma.

SKPokiaľ nastanú problémy pri čítaní bezpečnostných pokynov vo vydaných jazykoch,poskytneme Vám na základe žiadosti k dispozícii kópiu v jazyku Vašej krajiny.

SLKadar se pojavijo težave pri branju varnostnih navodil v izdanih jezikih, vam bomo na osnovizahtevka dali na razpolago kopijo v jeziku vaše države.

SVOm du har problem att läsa säkerhetsanvisningarnapå de här tryckta språken, ställer vi gärnapå begäran en kopia på ditt språk till förfogande.

WIKA Safety Instructions Process pressure transmitter IPT-1* 3

38985-EN-121031

Page 4: Process pressure transmitter IPT 1 - WIKAapps.wika.com/declarations/01_SI_IPT-10-11_Atex_IS_38985-EN.pdf · Fieldbus l IPT1* - Vers .3 0-37300 - 4 … 20 mA, 31543 - 4 … 20 mA/HART,

4 WIKA Safety Instructions Process pressure transmitter IPT-1*

38985-EN-121031

Page 5: Process pressure transmitter IPT 1 - WIKAapps.wika.com/declarations/01_SI_IPT-10-11_Atex_IS_38985-EN.pdf · Fieldbus l IPT1* - Vers .3 0-37300 - 4 … 20 mA, 31543 - 4 … 20 mA/HART,

WIKA Safety Instructions Process pressure transmitter IPT-1* 5

38985-EN-121031

Page 6: Process pressure transmitter IPT 1 - WIKAapps.wika.com/declarations/01_SI_IPT-10-11_Atex_IS_38985-EN.pdf · Fieldbus l IPT1* - Vers .3 0-37300 - 4 … 20 mA, 31543 - 4 … 20 mA/HART,

1 Area of applicability

These safety instructions apply to the process pressure transmitters IPT-10/11-A-***-**-******C/X-**,

IPT-10/11-R-***-**-******C-**, IPT-10/11-4-***-**-******C/X-**, IPT-10/11-5-***-**-******C/X-** accord-ing to EG type approval certificate PTB 06 ATEX 2017 X with the 1. supplement (certificate numberon the type label and for all instruments with the number of the safety instruction (38985) on the typelabel).

2 General information

The process pressure transmitters IPT-10/11-A/R/4/5-***-**-******C/X-** are also used for pressuremeasurement in hazardous areas.

The measured products can also be combustible liquids, gases, mist or vapour.

The IPT-10/11-A/R/4/5-***-**-******C/X-** consist of an electronics housing with integrated electronicsmodule, a process fitting element and a sensor, the pressure measuring cell with optionallyconnected isolated diaphragm. As an option the indicating and adjustment module can also beintegrated.

The IPT-10/11-A/R/4/5-***-**-******C/X-** are suitable for use in hazardous atmospheres of allcombustible materials of explosion group IIA, IIB and IIC for applications requiring instruments ofcategory 1G, category 1/2G or category 2G.

If the IPT-10/11-A/R/4/5-***-**-******C/X-** are installed and operated in hazardous areas, the generalEx installation regulations EN 60079-14 as well as these safety instructions must be observed.

The operating instructions as well as the applicable, valid Ex mounting regulations and standards forelectrical equipment must be observed.

The installation of explosion-endangered systems must always be carried out by qualified personnel.

2.1 Category 1G instruments

The IPT-10/11-A/R/4/5-***-**-******C/X-** are installed in hazardous areas requiring instruments ofcategory 1G.

2.2 Category 1/2G instruments

The process connection element is installed in the separating wall, which separates areas in whichinstruments of category 2G or 1G are required. The electronics housing is installed in hazardousareas requiring instruments of category 2. The sensor is installed in hazardous areas requiringinstruments of category 1G.

2.3 Category 2G instruments

The IPT-10/11-A/R/4/5-***-**-******C/X-** are installed in hazardous areas requiring instruments ofcategory 2G.

6 WIKA Safety Instructions Process pressure transmitter IPT-1*

38985-EN-121031

Page 7: Process pressure transmitter IPT 1 - WIKAapps.wika.com/declarations/01_SI_IPT-10-11_Atex_IS_38985-EN.pdf · Fieldbus l IPT1* - Vers .3 0-37300 - 4 … 20 mA, 31543 - 4 … 20 mA/HART,

3 Technical data

3.1 Electrical data

Process pressure transmitter IPT-10/11-A/R-***-**-******C/X-**

Power supply and signal circuit: (terminals1[+], 2[-] in electronics compartment; withdouble chamber housing version in connec-tion compartment)

In ignition protection type intrinsic safety Ex ia IIC

Only for connection to a certified, intrinsically safecircuit.Maximum values:Ui = 30 V

Ii = 131 mA

Pi = 983 mW

The effective internal capacitance Ci is negligiblysmall.The effective internal inductance Li is negligiblysmall.In the version with fix mounted connection cable Ci

wire/wire = 58 pF/m, Ci wire/screen = 270 pF/m and Li =

55 µH/m has to be taken into account.

Process pressure transmitter IPT-10/11-4/5-***-**-******C/X-**

Power supply and signal circuit: (terminals1[+], 2[-] in electronics compartment; withdouble chamber housing version in connec-tion compartment)

In ignition protection type intrinsic safety Ex ia IIC/IIB

for instruments of category 1G or 1/2G and Ex ia IIC/

IIB resp. Ex ib IIC/IIB for instruments of category 2G.

Only for connection to a certified, intrinsically safecircuit.Maximum values:Ui = 17.5 V

Ii = 500 mA

Pi = 5.5 W

The effective internal capacitance Ci is negligiblysmall.The effective internal inductance is Li ≤ 10 µH.

The instrument is suitable for connection to aFieldbus system according to the FISCO model(IEC 60079-27), e.g. Profibus PA or FoundationFieldbus.or:Ui = 24 V

Ii = 250 mA

Pi = 1.2 W

WIKA Safety Instructions Process pressure transmitter IPT-1* 7

38985-EN-121031

Page 8: Process pressure transmitter IPT 1 - WIKAapps.wika.com/declarations/01_SI_IPT-10-11_Atex_IS_38985-EN.pdf · Fieldbus l IPT1* - Vers .3 0-37300 - 4 … 20 mA, 31543 - 4 … 20 mA/HART,

The effective internal capacitance Ci is negligiblysmall.The effective internal inductance is Li ≤ 10 µH.

In the version with fix mounted connection cable Ci

wire/wire = 58 pF/m, Ci wire/screen = 270 pF/m andadditionally Li = 55 µH/m has to be taken intoaccount.

Process pressure transmitterIPT-10/11-A/R/4/5-***-**-******C/X-**

Indicating and adjustment circuit: (terminals5, 6, 7, 8 in the electronics compartment orplug connection with double chamber hous-ing version)

In ignition protection type intrinsic safety Ex ia IIC

For connection to the intrinsically safe circuit of thecorresponding external indicating unit "Display andProgramming Module for IPT10/11"(PTB 06 ATEX 2020 X)

The regulations for the interconnection of intrinsicallysafe circuits between IPT-10/11-A/R/4/5-***-**-

******C/X-** and the external indicating unit VEGADIS

61 are complied with if the total inductance and totalcapacitance of the connection cable between IPT-10/

11-A/R/4/5-***-**-******C/X-** and the external indi-cating unit VEGADIS 61 Lwire = 100 µH and Cwire =

2.8 µF are not exceeded. The indicating and adjust-ment module integrated in IPT-10/11-A/R/4/5-***-**-

******C/X-** is taken into account.When using the delivered connection cable betweenIPT-10/11-A/R/4/5-***-**-******C/X-** and the externalindicating unit, the following listed cable inductancesLi and cable capacitances Ci must be taken intoaccount with a cable length > 50 m.

Li = 0.62 µH/mCi wire/wire = 132 pF/mCi wire/screen = 208 pF/mCi screen/screen = 192 pF/m

Circuit of the indicating and adjustmentmodule: (spring contacts in the electronicscompartment; with double chamber housingversion also in the connection compartment)

In ignition protection type intrinsic safety Ex ia IIC

Only for connection to the internal indicating andadjustment module AB-Modul.WIKA.

With the double chamber housing version, theindicating and adjustment module may be mountedeither in the electronics compartment or in theconnection compartment.

Circuit between sensor unit and externalelectronics

In ignition protection type intrinsic safety Ex ia IIC

With IPT-10/11-A/R/4/5-***-**-******C/X-** in the ver-sion with fix mounted cable on the sensor unit andexternal electronics, the supplied cable between theexternal housing and the sensor unit must not exceeda length of 50 m.

The intrinsically safe circuits are electrically separated from parts which can be grounded.

8 WIKA Safety Instructions Process pressure transmitter IPT-1*

38985-EN-121031

Page 9: Process pressure transmitter IPT 1 - WIKAapps.wika.com/declarations/01_SI_IPT-10-11_Atex_IS_38985-EN.pdf · Fieldbus l IPT1* - Vers .3 0-37300 - 4 … 20 mA, 31543 - 4 … 20 mA/HART,

The metallic parts of the IPT-10/11-A/R/4/5-***-**-******C/X-** are electrically connected with theearth terminals.

For applications requiring instruments of category 2G, the intrinsically safe power supply and signalcircuit can correspond to protection class ia or ib. For connection to a circuit with protection class ib,the ignition protection type identification is Ex ib IIC T6.

For applications requiring instruments of category 1G or 1/2G, the intrinsically safe power supply andsignal circuit must correspond to protection class ia.

For applications requiring instruments of category 1G or 1/2G the IPT-10/11-A/R/4/5-***-**-******C/X-

** is preferably connected to appropriate equipment with galvanically isolated, intrinsically safecircuits.

4 Application conditions

Process pressure transmitter IPT-10/11-A/R-***-**-******C/X-**

The max. permissible ambient temperatures depending on the temperature classes are specified inthe following tables.

Category 1G instruments

Temperature class Ambient temperature on the sensor and elec-

tronics

T6 -20 … +39 °C

T5 -20 … +51 °C

T4, T3, T2, T1 -20 … +60 °C

For applications requiring category 1 instruments the pressure of the hazardous atmosphere mustbe between 0.8 … 1.1 bar. With the stated permissible ambient temperatures on the sensor the80 % consideration of section 6.4.2/EN 1127-1 is taken into account.

Category 1/2G instruments

Temperature class Ambient temperature on the

electronics

Ambient temperature on the

sensor

T6 -40 … +55 °C -20 … +57 °C

T5 -40 … +70 °C -20 … +60 °C

T4, T3, T2, T1 -40 … +90 °C -20 … +60 °C

For applications requiring instruments of category 1/2 the pressure of the explosive atmospheremust be between 0.8 … 1.1 bar. The 80 % consideration of sect. 6.4.2/EN 1127-1 is taken intoaccount with the permissible ambient temperatures. If the IPT-10/11-A/R-***-**-******C/X-** areoperated at temperatures higher than those specified in the above table, please make sure bymeans of appropriate measures, under consideration of the 7 K self heating of the sensor, thatthere is no danger of ignition from such hot surfaces. The max. permissible temperature on theelectronics/housing should not exceed the values stated in the above table. The applicationconditions in areas without hazardous mixtures are specified in the manufacturer information.

Category 2G instruments

Temperature class Ambient temperature on the

electronics

Ambient temperature on the

sensor

T6 -40 … +55 °C -40 … +73 °C

WIKA Safety Instructions Process pressure transmitter IPT-1* 9

38985-EN-121031

Page 10: Process pressure transmitter IPT 1 - WIKAapps.wika.com/declarations/01_SI_IPT-10-11_Atex_IS_38985-EN.pdf · Fieldbus l IPT1* - Vers .3 0-37300 - 4 … 20 mA, 31543 - 4 … 20 mA/HART,

Temperature class Ambient temperature on the

electronics

Ambient temperature on the

sensor

T5 -40 … +70 °C -40 … +88 °C

T4 -40 … +90 °C -40 … +123 °C

T3, T2, T1 -40 … +90 °C -40 … +188 °C

If the IPT-10/11-A/R-***-**-******C/X-** are operated at temperatures higher than those specified inthe above table, please make sure by means of appropriate measures, under consideration of the7 K self heating of the sensor, that there is no danger of ignition from such hot surfaces. Themaximum temperature on the electronics/housing should not exceed the values according to theabove table. The application conditions in areas without hazardous gas mixtures are specified inthe manufacturer information.

Process pressure transmitter IPT-10/11-4/5-***-**-******C/X-**

The max. permissible ambient temperatures depending on the temperature classes are specified inthe following tables.

Category 1G instruments

Temperature class Ambient temperature on the sensor and elec-

tronics

T5 -20 … +43 °C

T4, T3, T2, T1 -20 … +60 °C

For applications requiring category 1 instruments the pressure of the hazardous atmosphere mustbe between 0.8 … 1.1 bar. With the stated permissible ambient temperatures on the sensor the80 % consideration of section 6.4.2/EN 1127-1 is taken into account.

Category 1/2G instruments

Temperature class Ambient temperature on the

electronics

Ambient temperature on the

sensor

T6 -40 … +47 °C -20 … +57 °C

T5 -40 … +62 °C -20 … +60 °C

T4, T3, T2, T1 -40 … +90 °C -20 … +60 °C

For applications requiring instruments of category 1/2 the pressure of the explosive atmospheremust be between 0.8 … 1.1 bar. The 80 % consideration of sect. 6.4.2/EN 1127-1 is taken intoaccount with the permissible ambient temperatures. If the IPT-10/11-4/5-***-**-******C/X-** areoperated at temperatures higher than those specified in the above table, please make sure bymeans of appropriate measures, under consideration of the 7 K self heating of the sensor, thatthere is no danger of ignition from such hot surfaces. The max. permissible temperature on theelectronics/housing should not exceed the values stated in the above table. The applicationconditions in areas without hazardous mixtures are specified in the manufacturer information.

Category 2G instruments

Temperature class Ambient temperature on the

electronics

Ambient temperature on the

sensor

T6 -40 … +47 °C -40 … +73 °C

T5 -40 … +62 °C -40 … +88 °C

T4 -40 … +90 °C -40 … +123 °C

10 WIKA Safety Instructions Process pressure transmitter IPT-1*

38985-EN-121031

Page 11: Process pressure transmitter IPT 1 - WIKAapps.wika.com/declarations/01_SI_IPT-10-11_Atex_IS_38985-EN.pdf · Fieldbus l IPT1* - Vers .3 0-37300 - 4 … 20 mA, 31543 - 4 … 20 mA/HART,

Temperature class Ambient temperature on the

electronics

Ambient temperature on the

sensor

T3, T2, T1 -40 … +90 °C -40 … +188 °C

If the IPT-10/11-4/5-***-**-******C/X-** are operated at temperatures higher than those specified inthe above table, please make sure by means of appropriate measures, under consideration of the7 K self heating of the sensor, that there is no danger of ignition from such hot surfaces. Themaximum temperature on the electronics/housing should not exceed the values according to theabove table. The application conditions in areas without hazardous gas mixtures are specified inthe manufacturer information.

5 Protection against static electricity

The IPT-10/11-A/R/4/5-***-**-******C/X-** in the version with chargeable plastic parts, such as e.g.metal housing with inspection window, are provided with a caution label referring to the safetymeasures that must be taken in case electrostatic charging occurs during operation.

Caution: Plastic parts! Danger of static charge!

l Avoid frictionl No dry cleaningl Do not mount in areas with flowing, non-conductive products

6 Use of an overvoltage arrester

On request the IPT-10/11-A/R/4/5-***-**-******C/X-** can be provided with an overvoltage arrester.

If the IPT-10/11-A/R/4/5-***-**-******C/X-** are used as category 1/2G instruments, overvoltageprotection measures according to EN 60079-14 Chapter 12.3 are not required.

When used as category 1G instrument, a suitable overvoltage arrester must be connected inbetween as protection against overvoltages according to EN 60079-14 chapter 12.3.

7 Grounding

In order to avoid the danger of electrostatic charging of the metallic parts, the IPT-10/11-A/R/4/5-***-

**-******C/X-** must be electrostatically connected to the local potential equalisation (transferresistance ≤ 1 MΩ), e.g. via the ground terminal, when used as category 1G or 1/2G instruments.

8 Impact and friction sparks

The IPT-10/11-A/R/4/5-***-**-******C/X-** in aluminium version must be mounted in such a way thatsparks from impact and friction between aluminium and steel (except stainless steel, if the presenceof rust particles can be excluded) cannot occur.

In applications as category 1G or 1/2G instrument, the process pressure transmitters in the titaniumversions must be mounted in such a way that sparks from impact and friction between titanium andany other hard material cannot occur.

WIKA Safety Instructions Process pressure transmitter IPT-1* 11

38985-EN-121031

Page 12: Process pressure transmitter IPT 1 - WIKAapps.wika.com/declarations/01_SI_IPT-10-11_Atex_IS_38985-EN.pdf · Fieldbus l IPT1* - Vers .3 0-37300 - 4 … 20 mA, 31543 - 4 … 20 mA/HART,

9 Material resistance

For applications requiring instruments of category 1G or 1/2G the IPT-10/11-A/R/4/5-***-**-******C/X-

** must only be used in products against which the wetted materials are sufficiently resistant.

10 Mounting with external indicating unit

The intrinsically safe signal circuit between IPT-10/11-A/R/4/5-***-**-******C/X-** and the externalindicating unit should be set up without grounding. The required insulation voltage is > 500 V AC.

When using the provided connection cable, this requirement is fulfilled. If grounding of the cablescreen is required, it must be carried out according to EN 60079-14 paragr. 12.2.2.3.

11 Installation/mounting

The IPT-10/11-A/R/4/5-***-**-******C/X-** have to be mounted in such a way that the sensor unit isadequately protected from touching the vessel wall, taking vessel installations and flow conditionsinto account. This applies especially to sensor lengths over 3 m.

12 WIKA Safety Instructions Process pressure transmitter IPT-1*

38985-EN-121031

Page 13: Process pressure transmitter IPT 1 - WIKAapps.wika.com/declarations/01_SI_IPT-10-11_Atex_IS_38985-EN.pdf · Fieldbus l IPT1* - Vers .3 0-37300 - 4 … 20 mA, 31543 - 4 … 20 mA/HART,

WIKA Safety Instructions Process pressure transmitter IPT-1* 13

38985-EN-121031

Page 14: Process pressure transmitter IPT 1 - WIKAapps.wika.com/declarations/01_SI_IPT-10-11_Atex_IS_38985-EN.pdf · Fieldbus l IPT1* - Vers .3 0-37300 - 4 … 20 mA, 31543 - 4 … 20 mA/HART,

14 WIKA Safety Instructions Process pressure transmitter IPT-1*

38985-EN-121031

Page 15: Process pressure transmitter IPT 1 - WIKAapps.wika.com/declarations/01_SI_IPT-10-11_Atex_IS_38985-EN.pdf · Fieldbus l IPT1* - Vers .3 0-37300 - 4 … 20 mA, 31543 - 4 … 20 mA/HART,

WIKA Safety Instructions Process pressure transmitter IPT-1* 15

38985-EN-121031

Page 16: Process pressure transmitter IPT 1 - WIKAapps.wika.com/declarations/01_SI_IPT-10-11_Atex_IS_38985-EN.pdf · Fieldbus l IPT1* - Vers .3 0-37300 - 4 … 20 mA, 31543 - 4 … 20 mA/HART,

Printing date:

All statements concerning scope of delivery, application, practical use and operatingconditions of the sensors and processing systems correspond to the informationavailable at the time of printing.