Prevent Ice Plugs with the FM Approved Dry Air Pac for Freezer Room Fire Protection

50
he Leading Manufacturer of Air Compressors he Leading Manufacturer of Air Compressors Designed for All Types of Dry Pipe Sprinkler Systems Designed for All Types of Dry Pipe Sprinkler Systems Quality & Service Since 1936

description

The Dry Air Pac from General Air Products is an FM Approved air compressor, desiccant dryer package designed to eliminate ice plugs in freezer room fire protection sprinkler systems. The Dry Air Pac can also be used to slow the effects of corrosion in dry pipe sprinkler systems and is used frequently in critical applications where a moisture free environment is a must.

Transcript of Prevent Ice Plugs with the FM Approved Dry Air Pac for Freezer Room Fire Protection

Page 1: Prevent Ice Plugs with the FM Approved Dry Air Pac for Freezer Room Fire Protection

The Leading Manufacturer of Air Compressors The Leading Manufacturer of Air Compressors Designed for All Types of Dry Pipe Sprinkler SystemsDesigned for All Types of Dry Pipe Sprinkler Systems

Quality& ServiceSince 1936

Page 2: Prevent Ice Plugs with the FM Approved Dry Air Pac for Freezer Room Fire Protection

The Leading Manufacturer of Air Compressors The Leading Manufacturer of Air Compressors Designed for All Types of Dry Pipe Sprinkler SystemsDesigned for All Types of Dry Pipe Sprinkler Systems

Proud Member of

Page 3: Prevent Ice Plugs with the FM Approved Dry Air Pac for Freezer Room Fire Protection

Dry Air Pac For Critical Applications

•Basics of Compressed Air

•Ice Plugs

•Primary Components

•A Closer Look At The Integrated Control Panel

•Inside the Control Panel

•Troubleshooting

Page 4: Prevent Ice Plugs with the FM Approved Dry Air Pac for Freezer Room Fire Protection

Dry Air Pac For Critical Applications

Basics of Compressed Air

Page 5: Prevent Ice Plugs with the FM Approved Dry Air Pac for Freezer Room Fire Protection

Basics of Compressed Air

Air Compressors

Compressed Air: Atmospheric air compressed by a mechanical device to increase its pressure.

• Compressed air is an energy source – often considered the 4th utility.

Moisture

Dewpoint: Temperature at which moisture will occur.

• Example: 75ºF, 75 RH, 25 CFM = 4.5 gallons of water per day

Air Dryers

• Refrigerated, 30ºF – 39ºF dewpoint

• Chemical, down to -100ºF dewpoint

Page 6: Prevent Ice Plugs with the FM Approved Dry Air Pac for Freezer Room Fire Protection

Basics of Compressed Air

Compression Ratio

It takes 7.8 Ft3 of atmospheric air (14.69 PSIA) to make one actual cubic foot of air at 100 psig. (psia / atmosphere)

Page 7: Prevent Ice Plugs with the FM Approved Dry Air Pac for Freezer Room Fire Protection

Basics of Compressed Air

Compression Ratio

Page 8: Prevent Ice Plugs with the FM Approved Dry Air Pac for Freezer Room Fire Protection

Dry Air Pac For Critical Applications

Ice Plugs

Page 9: Prevent Ice Plugs with the FM Approved Dry Air Pac for Freezer Room Fire Protection

The Problem - Ice Plugs

• Ice Plug formation causes partial and eventually complete blockage of the dry-pipe system.

•Factory Mutual, after several years of study, found that 50% to 70% of the dry pipe systems inspected were plagued with Ice Plug problems.

Page 10: Prevent Ice Plugs with the FM Approved Dry Air Pac for Freezer Room Fire Protection

The Cause - Ice Plugs

• Evaporating Priming Water

• Water left in the lines after annual trip test.

• The Major Culprit, moisture laden compressed air meeting freezing temperatures in the Dry Pipe System.

(Contrary to popular belief, using air from the freezer room for the dry pipe systemWill not solve the ice plug problem)

Page 11: Prevent Ice Plugs with the FM Approved Dry Air Pac for Freezer Room Fire Protection

Dry Air Pac For Critical Applications

The Solution …

• Freezer Rooms

• Cold Storage

• Parking Garages

• Potential MIC Effected Areas

• Anywhere Dry Air is Essential

Page 12: Prevent Ice Plugs with the FM Approved Dry Air Pac for Freezer Room Fire Protection

Dry Air Pac For Critical Applications

Primary Components

Page 13: Prevent Ice Plugs with the FM Approved Dry Air Pac for Freezer Room Fire Protection

FM Approval eliminates requirement to connect air intake to freezer room.

Page 14: Prevent Ice Plugs with the FM Approved Dry Air Pac for Freezer Room Fire Protection

Industrial Duty Compressor Pump

Page 15: Prevent Ice Plugs with the FM Approved Dry Air Pac for Freezer Room Fire Protection

Removable Intake Filter with Weatherhood

Page 16: Prevent Ice Plugs with the FM Approved Dry Air Pac for Freezer Room Fire Protection

Compact Air Cooled Aftercooler

Page 17: Prevent Ice Plugs with the FM Approved Dry Air Pac for Freezer Room Fire Protection

Pressure Switch

Page 18: Prevent Ice Plugs with the FM Approved Dry Air Pac for Freezer Room Fire Protection

Check Valve

Page 19: Prevent Ice Plugs with the FM Approved Dry Air Pac for Freezer Room Fire Protection

ASME / NB Tank (30 Gallons)

Page 20: Prevent Ice Plugs with the FM Approved Dry Air Pac for Freezer Room Fire Protection

Integrated Electronic Drain

Page 21: Prevent Ice Plugs with the FM Approved Dry Air Pac for Freezer Room Fire Protection

Vibration Isolation Pads

Page 22: Prevent Ice Plugs with the FM Approved Dry Air Pac for Freezer Room Fire Protection

Prefilter with Differential Pressure Gauge

Page 23: Prevent Ice Plugs with the FM Approved Dry Air Pac for Freezer Room Fire Protection

SAEJ10 Towers

Page 24: Prevent Ice Plugs with the FM Approved Dry Air Pac for Freezer Room Fire Protection

Purge Pressure Gauge

Page 25: Prevent Ice Plugs with the FM Approved Dry Air Pac for Freezer Room Fire Protection

Oversized Mufflers for quiet discharges and low backpressure

Page 26: Prevent Ice Plugs with the FM Approved Dry Air Pac for Freezer Room Fire Protection

UL Listed / FM Approved Air Maintenance Device

Page 27: Prevent Ice Plugs with the FM Approved Dry Air Pac for Freezer Room Fire Protection

Combination Afterfilter & Regulator

Page 28: Prevent Ice Plugs with the FM Approved Dry Air Pac for Freezer Room Fire Protection

Dry Air Outlet

Page 29: Prevent Ice Plugs with the FM Approved Dry Air Pac for Freezer Room Fire Protection

Dewpoint Test Port

Page 30: Prevent Ice Plugs with the FM Approved Dry Air Pac for Freezer Room Fire Protection

Dry Air Pac Test Kit

gives visual indication if moisture is present (Available as option).

Page 31: Prevent Ice Plugs with the FM Approved Dry Air Pac for Freezer Room Fire Protection

Fully Integrated Control Panel ensures package performs to specification.

Page 32: Prevent Ice Plugs with the FM Approved Dry Air Pac for Freezer Room Fire Protection

A Closer Look at the Fully Integrated Control

Panel

Page 33: Prevent Ice Plugs with the FM Approved Dry Air Pac for Freezer Room Fire Protection

Fully Integrated Control Panel – Performance Lights

Page 34: Prevent Ice Plugs with the FM Approved Dry Air Pac for Freezer Room Fire Protection

Fully Integrated Control Panel –

•Reset Button

•Control Panel Power

•Incorporated Automatic Drain Controls

Page 35: Prevent Ice Plugs with the FM Approved Dry Air Pac for Freezer Room Fire Protection

Fully Integrated Control Panel – Hour Meter

Page 36: Prevent Ice Plugs with the FM Approved Dry Air Pac for Freezer Room Fire Protection

Fully Integrated Control Panel – Receiver Pressure Gauge

Page 37: Prevent Ice Plugs with the FM Approved Dry Air Pac for Freezer Room Fire Protection

Fully Integrated Control Panel – Left Tower Pressure Gauge

Page 38: Prevent Ice Plugs with the FM Approved Dry Air Pac for Freezer Room Fire Protection

Fully Integrated Control Panel – Right Tower Pressure Gauge

Page 39: Prevent Ice Plugs with the FM Approved Dry Air Pac for Freezer Room Fire Protection

Fully Integrated Control Panel – Outlet Pressure Gauge

Page 40: Prevent Ice Plugs with the FM Approved Dry Air Pac for Freezer Room Fire Protection

Inside the Control Panel

Page 41: Prevent Ice Plugs with the FM Approved Dry Air Pac for Freezer Room Fire Protection

Inside the Control Panel – Magnetic Line Starter (NEMA Rated)

Page 42: Prevent Ice Plugs with the FM Approved Dry Air Pac for Freezer Room Fire Protection

Inside the Control Panel – Control Circuit Transformer (with primary and secondary fusing)

Page 43: Prevent Ice Plugs with the FM Approved Dry Air Pac for Freezer Room Fire Protection

Inside the Control Panel – Cam Timer

Page 44: Prevent Ice Plugs with the FM Approved Dry Air Pac for Freezer Room Fire Protection

Inside the Control Panel – Solenoid Valves

Page 45: Prevent Ice Plugs with the FM Approved Dry Air Pac for Freezer Room Fire Protection

Dry Air Pac For Critical Applications

Troubleshooting

Page 46: Prevent Ice Plugs with the FM Approved Dry Air Pac for Freezer Room Fire Protection

Troubleshooting the Dry Air Pac

Problem

Poor Dewpoint Performance

Probable Cause

Low pressure on desiccant dryer

Excessive water or oil in dryer

Low purge flow

Desiccant contamination

High inlet temp. to dryer

Solution

Reset Pressure Switch .

Check coalescing filter & automatic drain operation

Check purge pressure setting

Check the date of the last desiccant change. Recommended change every 1 to 2 years

Clean aftercooler

Page 47: Prevent Ice Plugs with the FM Approved Dry Air Pac for Freezer Room Fire Protection

Troubleshooting the Dry Air Pac

Problem

Excessive Pressure Drop

Probable Cause

Switching valve failure . .

Desiccant breakdown

Clogged filters

Solution

Check tower-operating sequence to verify and identify which valves are operating.

Change desiccant

Change filter elements

Page 48: Prevent Ice Plugs with the FM Approved Dry Air Pac for Freezer Room Fire Protection

Troubleshooting the Dry Air Pac

Problem

Switchover Failure

Probable Cause

Electric power loss . .

Solenoid valve failure

Solution

Turn dryer off; check connections to cam timer and inlet to unit.

Check valve operative sequence. Replace valve.

Page 49: Prevent Ice Plugs with the FM Approved Dry Air Pac for Freezer Room Fire Protection

Troubleshooting the Dry Air Pac

Problem

Repressurization Failure or Purge Failure

Probable Cause

Purge flow control valve orifice clogged.

Failed check valve.

Purge exhaust solenoid valve failure.

Purge exhaust muffler clogged.

Solution

Clean or replace. .

Replace.

Turn dryer off, check connections to cam timer, inspect valve and solenoid, replace if necessary. .

Clean or replace.

Page 50: Prevent Ice Plugs with the FM Approved Dry Air Pac for Freezer Room Fire Protection

The Leading Manufacturer of Air Compressors The Leading Manufacturer of Air Compressors Designed for All Types of Dry Pipe Sprinkler SystemsDesigned for All Types of Dry Pipe Sprinkler Systems

Call Toll Free

1-800-345-8207Or visit our web site

www.GeneralAirProducts.com