PRESSURE INDEPENDENT BALANCING & CONTROL VALVE …

4
Sl Parts Materials 1 Body Ductile Iron 2 Core Stainless Steel 3 Stem Stainless Steel 4 Membrane EPDM 5 Spring Stainless Steel 6 Sealing EPDM 7 Actuator Shell : Flame Retardant Pc Internals : Reinforced POM PRESSURE INDEPENDENT BALANCING & CONTROL VALVE FLANGED END LEHRY Pressure Independent Control Valve (PICV) is used in HVAC systems equipment of air conditioning equipment (such as air conditioner, make-up air units, air processor) temperature control, by configuring the intelligent modular to control system, it can facilitate the flow and temperature to control the loop. To achieve the rational use of energy, energy saving, intelligent management. Application of Pressure Independent Control Valve (PICV), terminal equipment is not affected by system pressure fluctuations, making the system more stable, more energy, particularly suitable for system load changes in variable flow systems. Features: Pressure independent control valve (PICV) Set of dynamic balance and electric regulation and integration, can replace the static balance valve and pressure balance valve combination Use the rotary electric actuator, small torque, quick response, sensitive Pressure independent control valve (PICV) consist of two functional control elements First, the external instructions to respond, in addition to the system changes can be induced to make their own adjustment Balancing cavity of Pressure independent control valve (PICV) adopts built- in connecting pipe. It has more compact structure and can avoid damages during installation compared with external connecting pipe The customer can be customized according to requirements of maximum flow The valve body(DN40-DN250) is made of high grade ductile iron GJS450- 10, the surface takes imported paint spraying technology, the appearance looks nice The valve has a shutdown function, leakage≤1.5L/Hour; The driver with the standard configuration manual function and power switch; Standard of flange connection in accordance with EN10226/EN1092Applications: Pressure independent Balancing valve consists of flowing adjustment and dynamic balancing. The structure of flowing adjustment can achieve to set and regulate.it equipped with actuator which can realize to electronic regulate and shutoff functions. The structure of dynamic balancing can realize to flow constant. Its core part including diaphragm and spring. Diaphragm can induct differential pressure among of entrance and chamber of balancing valve core, and then keep constant differential pressure Technical Specification: Material of Construction: Dimensions : DN40-DN250 Working Temperature : -10~120Working Pressure : PN16 Fluid Medium : Water / Ethylene Glycol / Propylene Glycol Connection : Flanged Connection Connection Standard : EN1092-1/2 GB/T 17241.6-2008 Control Deviation : ≤5% Working Δ P : 30-420KPa Working voltage : 24VAC Control Signal : 0-10VDC / 4-20mA IP Grade : IP54 / 65 Control Characteristic : equal percentage

Transcript of PRESSURE INDEPENDENT BALANCING & CONTROL VALVE …

Page 1: PRESSURE INDEPENDENT BALANCING & CONTROL VALVE …

Sl Parts Materials

1 Body Ductile Iron

2 Core Stainless Steel

3 Stem Stainless Steel

4 Membrane EPDM

5 Spring Stainless Steel

6 Sealing EPDM

7 Actuator Shell : Flame Retardant Pc

Internals : Reinforced POM

PRESSURE INDEPENDENT BALANCING & CONTROL VALVE FLANGED END

LEHRY Pressure Independent Control Valve (PICV) is used in HVAC systems equipment of air conditioning equipment (such as air conditioner, make-up air units, air processor) temperature control, by configuring the intelligent modular to control system, it can facilitate the flow and temperature to control the loop. To achieve the rational use of energy, energy saving, intelligent management. Application of Pressure Independent Control Valve (PICV), terminal equipment is not affected by system pressure fluctuations, making the system more stable, more energy, particularly suitable for system load changes in variable flow systems.

Features:

Pressure independent control valve (PICV) Set of dynamic balance and electric regulation and integration, can replace the static balance valve and

pressure balance valve combination;

Use the rotary electric actuator, small torque, quick response, sensitive;

Pressure independent control valve (PICV) consist of two functional control elements First, the external instructions to respond, in addition to the

system changes can be induced to make their own adjustment;

Balancing cavity of Pressure independent control valve (PICV) adopts built-in connecting pipe. It has more compact structure and can avoid damages

during installation compared with external connecting pipe;

The customer can be customized according to requirements of maximum

flow;

The valve body(DN40-DN250) is made of high grade ductile iron GJS450-10, the surface takes imported paint spraying technology, the appearance

looks nice;

The valve has a shutdown function, leakage≤1.5L/Hour; The driver with the standard configuration manual function and power switch;

Standard of flange connection in accordance with EN10226/EN1092;

Applications:

Pressure independent Balancing valve consists of flowing adjustment and dynamic balancing.

The structure of flowing adjustment can achieve to set and regulate.it equipped with actuator which can realize to electronic regulate and shutoff functions.

The structure of dynamic balancing can realize to flow constant. Its core part including diaphragm and spring. Diaphragm can induct differential pressure among of entrance and chamber of balancing valve core, and then keep constant differential pressure

Technical Specification: Material of Construction:

Dimensions : DN40-DN250

Working Temperature : -10~120℃ Working Pressure : PN16 Fluid Medium : Water / Ethylene Glycol / Propylene Glycol Connection : Flanged Connection Connection Standard : EN1092-1/2 GB/T 17241.6-2008 Control Deviation : ≤5% Working Δ P : 30-420KPa Working voltage : 24VAC Control Signal : 0-10VDC / 4-20mA IP Grade : IP54 / 65 Control Characteristic : equal percentage

Page 2: PRESSURE INDEPENDENT BALANCING & CONTROL VALVE …

Size Working Rated Actuator Force(N)

Actuating Time (S)

Temp DegC

Inch Mm ∆ P

(Kpa) Flow (m³/h)

1 ½” 40 30-420 8 25 120

10˚C~120˚C

2” 50 30-420 14 25 120

2 ½” 65 30-420 24.5 25 120

3” 80 30-420 35 65 120

4” 100 30-420 50 65 120

5” 125 30-420 70 100 140

6” 150 30-420 100 100 140

8” 200 30-420 184 150 140

10” 250 30-420 240 150 140

Size Opening(%)-Flow(m³/h)

Inch Mm 10 20 30 40 50 60 70 80 90 100

1 ½” 40 1 1.5 2.1 2.8 3.7 4.6 5.5 6.4 7.3 8

2” 50 2 2.2 3.3 4.5 6.2 8 9.6 11 13 14

2 ½” 65 2 3 4.2 6 8.5 11 14 17 21 25

3” 80 3 5 7 9.5 12 16 20 25 30 35

4” 100 5 8 11 16 21 27 33 38 44 50

5” 125 8 11 15 19 26 34 42 53 62 70

6” 150 12 16 20 26 35 45 56 68 82 100

8” 200 25 34 46 62 78 98 118 139 160 184

10” 250 37 48 60 78 95 115 138 170 205 240

Technical Parameter:

Actuator Selection & Parameter Table Flow Characteristics: Equal Percentage Control Characteristics Different Pressure-Flow Characteristics

Size Actuator Selection

Moment Power (W)

24VAC Time (S) 24 VAC

Input signal

Output signal

Protection level

40mm LIV-ELA-RB25-10

25Nm 5.5 120 0-10V 2-10V

0-20mA

4-20mA

0-10V

IP54

50mm

65mm

80mm LIV-ELA-RB65-10

65Nm 11 120 100mm

125mm LIV-ELA-RB100-10

100Nm 12 140 IP65

150mm

200mm LIV-ELA-RB150-10

150Nm 15 140 250mm

Page 3: PRESSURE INDEPENDENT BALANCING & CONTROL VALVE …

Dimensions (All Dimensions are in mm) Attention: Please read the instruction manual, check the product model and parameters before installation, and set the working voltage and input signal according to the requirement;

Ensure vertical installation, reserved space to facilitate maintenance;

The installation should pay attention to ensure that the direction of flow with the arrow pointing on the body consistent;

The proposed design system bypass connectivity, filling should bypass the impurities in the pipeline clean, otherwise it may cause valve blockage;

System shutdown and system filling, should be set to normally open state (refer to module operation instructions);

The installation should be guaranteed before and after the valve reserved for a length of straight pipe section, usually in the reserved pipe diameter of 10 times the length of the straight pipe, export reserved pipe diameter 5 times the length of straight pipe section;

Installation:

Downward Installation Prohibited

Notice: When we do the pipe pressure testing and flushing, the valve body should be in a state of full open. This operation can not only protect the internal parts of valve body, but also prevent pipe from blocking. pipeline

Size G n x d L H1 H2

Inch MM

40 1½" 110 4xΦ18 200 240 92

50 2" 125 4xΦ18 230 255 110

65 2½" 145 4xΦ18 290 265 136

80 3" 160 8xΦ18 310 280 142.5

100 4" 180 8xΦ18 350 300 148.5

125 5" 210 8xΦ18 400 335 188

150 6" 240 8xΦ22 480 370 205

200 8” 295 12xΦ22 600 420 265

250 10” 355 12xΦ26 730 480 325

Maintenance:

When doing service work on the actuator: Close the pump and turn off the power supply. Close the shut-off valve, exhaust water in the pipe to

reduce the pressure inside pipes. Make water pipe(hot water) cool down naturally.

Dismantle electric wires from wiring terminals.

Remark: Before debugging valve again, install actuator correctly.

Downward installation is forbidden, when the medium is chilled/hot water and the flow direction of medium in valve should be consistent with the medium of Pipe Line

Page 4: PRESSURE INDEPENDENT BALANCING & CONTROL VALVE …

INTELLIGENT ACTUATOR

LEHRY intelligent actuator is a kind of electronic and mechanical product; it can be matched with 40MM & above size valve body by different connectors. As the intelligent actuator is connected with valve by connecting nut, so it can be installed after the valve has been installed. It can be installed on field, and its wiring is flexible and convenient. The flat-designed actuator makes it possible to be installed more closely to wall, and takes little space. The product is reliable and durable. It operates with reversible motor and can provide increasing control signal. It has low working noise and can work reliable in high temperature condition, which often appears in concealed fan coil devices. Characteristics

Driven by bi-directional synchronous motor with low AC voltage. Easy & Flexible Installation Position Feedback auxiliary switch for option Die-Casting Aluminum Alloy Chassis. Pass reliability and Safety Testing Self-adjusting function, automatic record stroke data Working states changed easily 0(2)~10V DC or (0)4~20mA DC input signal control, proportional

control 0~10V DC feedback signal Fireproof ABS engineering plastic casing.

Features:

AC two-way synchronous motor Built-in switch has power-off function when in place, achieving

longer service life Built-in switch allows limited adjustment Manual lever provides flexible switch operation Proportional control actuator can provide DC0-10V feedback Signal The control signals of proportional, floating-point and on/off are optional

Manual Operation

If user needs to switch calibration/operation mode, make sure the JP1 has been set correctly, then press SW 1 calibration/reset button. Don’t need to cut off power Note : It is Strongly recommended that JP1 Switch Should be set on operation mode in normal use.