Pressure Control System: Root Locus Plotting
description
Transcript of Pressure Control System: Root Locus Plotting
![Page 1: Pressure Control System: Root Locus Plotting](https://reader036.fdocuments.in/reader036/viewer/2022081504/5681455b550346895db22ba4/html5/thumbnails/1.jpg)
Pressure Control System:Root Locus Plotting
Team Green:
X
Y
Z
![Page 2: Pressure Control System: Root Locus Plotting](https://reader036.fdocuments.in/reader036/viewer/2022081504/5681455b550346895db22ba4/html5/thumbnails/2.jpg)
Outline
Pressure System Background Previous Work: Transfer Function Root Locus Theory Modeling Results Conclusions
![Page 3: Pressure Control System: Root Locus Plotting](https://reader036.fdocuments.in/reader036/viewer/2022081504/5681455b550346895db22ba4/html5/thumbnails/3.jpg)
Background: Schematic Diagram
![Page 4: Pressure Control System: Root Locus Plotting](https://reader036.fdocuments.in/reader036/viewer/2022081504/5681455b550346895db22ba4/html5/thumbnails/4.jpg)
Background: Block Diagram
Manipulated Variable
M System C
Controlled Variable
% Motor Speed Pressure in cm-H2O
![Page 5: Pressure Control System: Root Locus Plotting](https://reader036.fdocuments.in/reader036/viewer/2022081504/5681455b550346895db22ba4/html5/thumbnails/5.jpg)
Background: SSOC
0
0.5
1
1.5
2
2.5
3
3.5
4
4.5
5
0 10 20 30 40 50 60 70 80 90 100
% Motor
Operating Range: 30 – 70%
Ou
tpu
t: 1.3 –3.8 cm
H2O
![Page 6: Pressure Control System: Root Locus Plotting](https://reader036.fdocuments.in/reader036/viewer/2022081504/5681455b550346895db22ba4/html5/thumbnails/6.jpg)
Background: FOPDT Parameters
K = 0.061 cm of H2O / %
to = 0.25 sec = 0.4 sec
![Page 7: Pressure Control System: Root Locus Plotting](https://reader036.fdocuments.in/reader036/viewer/2022081504/5681455b550346895db22ba4/html5/thumbnails/7.jpg)
Feedback Control
![Page 8: Pressure Control System: Root Locus Plotting](https://reader036.fdocuments.in/reader036/viewer/2022081504/5681455b550346895db22ba4/html5/thumbnails/8.jpg)
Root Locus Theory
Where is the damping ratio.
Decay Ratio =
![Page 9: Pressure Control System: Root Locus Plotting](https://reader036.fdocuments.in/reader036/viewer/2022081504/5681455b550346895db22ba4/html5/thumbnails/9.jpg)
Effects of
Overdamped = monotonic and stable
Underdamped = oscillatory and stable
Undamped = sustained oscillations
Unstable = growing oscillations
Run-away = monotonic and unstable
![Page 10: Pressure Control System: Root Locus Plotting](https://reader036.fdocuments.in/reader036/viewer/2022081504/5681455b550346895db22ba4/html5/thumbnails/10.jpg)
Four Possible Responses
Stable, Monotonic
Unstable, Oscillatory Unstable, Monotonic
Stable, Oscillatory
![Page 11: Pressure Control System: Root Locus Plotting](https://reader036.fdocuments.in/reader036/viewer/2022081504/5681455b550346895db22ba4/html5/thumbnails/11.jpg)
Root Locus Parameters
KCD = highest value of KC that provides monotonic and stable output (critically damped)
KQD = value of KC that produces one-
quarter oscillating decay KCU = highest value of KC that causes
oscillatory and stable output (marginally stable)
![Page 12: Pressure Control System: Root Locus Plotting](https://reader036.fdocuments.in/reader036/viewer/2022081504/5681455b550346895db22ba4/html5/thumbnails/12.jpg)
Root Locus Parameters
KCD is found where the roots go from real to complex
KQD is found where the ratio of the imaginary root to the real root is 4.5
KCU is found where the real portion of the root goes from negative to positive.
![Page 13: Pressure Control System: Root Locus Plotting](https://reader036.fdocuments.in/reader036/viewer/2022081504/5681455b550346895db22ba4/html5/thumbnails/13.jpg)
Parameter Locations
ROOT LOCUS PLOT
-10
-8
-6
-4
-2
0
2
4
6
8
10
-6 -5 -4 -3 -2 -1 0 1
REAL AXIS
IMA
GIN
AR
Y A
XIS
KCD
KCUKQD
Dr Henry’s Suggestion:Put the VALUES of the Kc’sfor the different choices you have on this graph
![Page 14: Pressure Control System: Root Locus Plotting](https://reader036.fdocuments.in/reader036/viewer/2022081504/5681455b550346895db22ba4/html5/thumbnails/14.jpg)
Locations ROOT LOCUS PLOT
-10
-8
-6
-4
-2
0
2
4
6
8
10
-6 -5 -4 -3 -2 -1 0 1
REAL AXIS
IMA
GIN
AR
Y A
XIS
DR=0
DR=1/500
DR=1/10
DR=1/4
DR=1/1
![Page 15: Pressure Control System: Root Locus Plotting](https://reader036.fdocuments.in/reader036/viewer/2022081504/5681455b550346895db22ba4/html5/thumbnails/15.jpg)
Results from Root Locus
Ultimate Kcu= 37
Quarter Decay Kc = 24.
Critically Damping Kc = 0.1
Underdamped 0.1< Kc < 37
Overdamped 0 < Kc < 0.1
*all units are % / cm H2O
![Page 16: Pressure Control System: Root Locus Plotting](https://reader036.fdocuments.in/reader036/viewer/2022081504/5681455b550346895db22ba4/html5/thumbnails/16.jpg)
Conclusions
For Kc needed
Overdamped 0 < Kc < 0.1
Critically Damped Kc = 0.1
Underdamped 0.1< Kc < 36.9
Quarter Decay Kc = 24.2
*all units are % / cm H2O
![Page 17: Pressure Control System: Root Locus Plotting](https://reader036.fdocuments.in/reader036/viewer/2022081504/5681455b550346895db22ba4/html5/thumbnails/17.jpg)
Questions?