Presenters - ANHA
Transcript of Presenters - ANHA
2012LifeSafetyCodeUpdate June20,2016
AlabamaDepartment ofPublicHealth 1
REVISED CMS REGULATIONS AND THE
2012 NFPA CODES
FIRE SAFETY REQUIREMENTSFOR NURSING HOMES
Alabama Department of Public HealthTechnical Services Unit
Presenters
Victor HuntSally Kimbrough-McAuley
Tony Dunklin
2012LifeSafetyCodeUpdate June20,2016
AlabamaDepartment ofPublicHealth 2
Change from 2000 Codes to 2012 Codes
• The Centers for Medicare and Medicaid Services (CMS) published announcement on May 4, 2016
• Adoption of National Fire Protection Association (NFPA) codes and referenced standards
• Adoption of 2012 Life Safety Code includes Tentative Interim Amendments (TIA) 12-1 through 12-4.
• Adoption of 2012 NFPA 99 Health Care Facilities Code, excluding chapters 7, 8, 12, and 13. Includes TIAs 12-2 through 12-6.
www.nfpa.org, “Codes and Standards,” “List of Codes and Standards,” select code,
“Editions,” 2012
2000 Codes to 2012 Codes
2000 Codes to 2012 Codes
• Compliance required on July 5, 2016 • Chapter 18, New Healthcare Occupancies
– Plan approval by ADPH on or after July 5• Chapter 19, Existing Healthcare
Occupancies – All facilities constructed prior to July 5– Plan approval by ADPH prior to July 5
2012LifeSafetyCodeUpdate June20,2016
AlabamaDepartment ofPublicHealth 3
Building Rehabilitation
• 2000 LSC – Alterations, renovations, additions, and new equipment meet requirements for NEW (paragraph 4.6.7)
• 2012 LSC – Comply with Chapter 43, Building Rehabilitation
Building Rehabilitation
Chapter 43 Work Categories • Repair• Renovation • Modification• Reconstruction• Change of use or occupancy classification • Addition
Means of Egress
Comply with Chapter 7Applies to New and Existing Buildings, per
7.1.1
Construction ProjectsLSC 19.7.9.2 Not new Means of egress in construction areas shall
be inspected daily for availability for full instant use in case of an emergency.
2012LifeSafetyCodeUpdate June20,2016
AlabamaDepartment ofPublicHealth 4
Emergency Hardware
• Fire Exit Hardware only on fire-rated doors– Latch holding device never permitted
(dogging, or dogged down) • Panic Hardware only on doors not fire-
rated – Dogging, or dogged down, is permitted
Per LSC 7.2.1.7
Electric Hardware on Egress Doors
New, per LSC 7.2.1.5.6 Electric hardware permitted in means of egress: 1. Hardware mounted on door leaf 2. Obvious operation in direction of egress (panic)3. Operable with one hand in direction of egress4. Hardware operation interrupts power to electric
lock 5. Loss of power to hardware unlocks door 6. Hardware listed per ANSI/UL 294Key, key pad, or card reader not allowed on
egress side of door.
Stairway Identification
LSC 7.2.2.5.4 • Requirements for special stair signage
apply to -– Existing enclosed stairs serving 5 or more
stories – New enclosed stairs serving 3 or more stories
“Story” includes basement level.
2012LifeSafetyCodeUpdate June20,2016
AlabamaDepartment ofPublicHealth 5
Stairway Identification
See LSC 7.2.2.5.4. •13 Requirements •Additional contents•Lettering minimum heights•Illumination by emergency
lighting•Tactile designation (Braille) for floor level number
Means of Egress LightingLSC7.8.1.2and7.8.1.2.2• Illuminationmustbecontinuous duringperiodswhenneeded.
• Canbecontrolledbyautomaticmotionsensor-typeswitches.
• 5conditions arelisted(3conditionsin2000LifeSafetyCode)
Delayed-Egress Locks
LSC 19.2.2.2.4 • 2000 LSC – “not more than one . . . in any
egress path” Deleted in 2012 LSC. Comply with Section 7.2.1.6.1 • Emergency lighting on egress side of the
door (new requirement) • Accurately reflect delay time on the sign
(not new)
2012LifeSafetyCodeUpdate June20,2016
AlabamaDepartment ofPublicHealth 6
Door Locking for SecurityLSC 19.2.2.2.5.1 • Patients require specialized security
or pose a security threat. • LSC Handbook: “addresses the locking of
sleeping room doors” • Doors released manually by staff
– Remote control (kill switch), or – Keying locks to keys carried by staff
• No change from 2000 Life Safety Code
Staff and Locked Doors
LSC 19.7.3.2Requires “adequate staff qualified to
release locks and direct occupants from the immediate danger area”
Door Locking for Safety
LSC 19.2.2.2.5.2 • Patients require specialized protective
measures for their safety. • New provision, not in 2000 Life Safety
Code • Corresponds to ADPH “Exit Door Locking
Arrangements” article
2012LifeSafetyCodeUpdate June20,2016
AlabamaDepartment ofPublicHealth 7
Door Locking for SafetyLSC 19.2.2.2.5.2 1. Staff can readily unlock doors at all times. 2. Emergency release switch (kill switch).
ADPH requires sign at each switch, and restricted resetting of switch.
3. Complete sprinkler system required4. Fail-safe electrical locks. ADPH allows
10-second unlocking delay for power failure to fire alarm.
Door Locking for Safety
LSC 19.2.2.2.5.2 5. Locks release automatically upon:
1. Smoke detection system activation, or2. Sprinkler system water flow, or3. Disablement of fire alarm system (ADPH)
6. Release switch at each locked door (ADPH)
7. Written justification (ADPH)
Sliding Doors
LSC 19.2.2.2.10.2 • New section containing 5 requirements• Emergency break-away swing feature not
required when the door serves fewer than 10 occupants. (New)
2012LifeSafetyCodeUpdate June20,2016
AlabamaDepartment ofPublicHealth 8
Projections Into CorridorsLSC 19.2.3.4(2) Corridors 6 feet or more wide• New LSC provision for 6 inch projections
from wall above handrail height• ADA Accessibility Guidelines (ADAAG)
allows 4 inch projections into circulation path.
• ADAAG allows 4-1/2 inch handrail projections.
• CMS – Technical assistance regarding how to avoid noncompliance with ADA requirement.
Projections Into Corridors
2012 LSC 19.2.3.4(2) •Allowed in corridors at least 6 feet wide
2010 ADA •Paragraph 307.2•Handrails 4-1/2 inches
Wheeled Equipment in Corridors
LSC 19.2.3.4(4) •Clear width at wheeled items isat least 60 inches •Fire Safety Plan and Training Program for Emergency relocation•Limited to:
•Equipment and carts in use•Medical emergency equipment not in use (new)•Patient lift and transport equipment (new)
2012LifeSafetyCodeUpdate June20,2016
AlabamaDepartment ofPublicHealth 9
Permissible Wheeled Equipment
Food Service Carts (In Use)Housekeeping Carts (In Use)Medication Carts (In Use)Isolation CartsCrash CartsWheeled Emergency Medical Equipment (not stored)Portable Lift EquipmentTransport Equipment
Fixed Furniture in CorridorsLSC 19.2.3.4(5) Summary of requirements: •Securely attached to floor or wall•On one side of the corridor•Each grouping limited to 50 square feet•Groupings at least 10 feet apart•No obstruction of access to building and fire equip.
•Corridors have smoke detection, or furniture in view from nurse station•Sprinkler system in compartment
Hazardous Areas
LSC 19.3.2.1.5• Soiled linen rooms with a volume
exceeding 64 gallons• “Trash collection rooms” changed to
“Rooms with collected trash.” Hazardous if volume exceeds 64 gallons.
2012LifeSafetyCodeUpdate June20,2016
AlabamaDepartment ofPublicHealth 10
Residential Cooking Equipment
LSC 19.3.2.5.2• Food warming or limited cooking • No fire extinguishing system required
(new expanded wording) • Room not required to be protected as a
hazardous area (modified wording)
“Culture Change” Kitchen
LSC 19.3.2.5.3 to prepare meals for up to 30 residents (per Appendix)
• “Cooking facility” open to corridor• No separation required from other spaces
within the smoke compartment• 13 Conditions listed • Requires plan review through Technical
Services
“Culture Change” KitchenLSC 19.3.2.5.4 to prepare meals for up to 30
residents• “Cooking facility” not open to corridor• Separation required from corridor• Not a sleeping room• 11 Conditions apply• Requires plan review through Technical
Services
2012LifeSafetyCodeUpdate June20,2016
AlabamaDepartment ofPublicHealth 11
“Traditional” Kitchens
LSC 19.3.2.5.5• Cooking equipment protected by kitchen
fire extinguishing system• Not considered hazardous area • Not open to the corridor
Alcohol-Based Hand Rub Dispensers
LSC 19.3.2.6 “ABHR” K-211• Comply with this paragraph in lieu of NFPA 30 • Quantity within a smoke compartment clarified,
generally up to 10 gallons totaled is acceptable– One dispenser within a bedroom not included in this
limitation
• More than 5 gallons stored in a compartment to comply with NFPA 30
• Aerosol dispensers added
Alcohol-Based Hand Rub Dispensers Locations
LSC 19.3.2.6(8)• In corridors at least 6 feet
wide. • At least 48 inches apart• Mounted over carpet only
in sprinklered smoke compartments
• Mounting near an ignition source, including:
– Light switch– Electrical receptacle
2012LifeSafetyCodeUpdate June20,2016
AlabamaDepartment ofPublicHealth 12
Alcohol-Based Hand Rub Dispensers
“Inappropriate Access” statements by CMS in code adoption announcement, Page 63.
• Certain patients or residents may misuse ABHR solutions, which are toxic and flammable.
• Secure dispensers from inappropriate access– Not in corridors in or near dementia or psychiatric units– Only where units can be easily and frequently
monitored
Powered Corridor Doors
LSC 19.3.6.3.7 New provision to allow powered doors in
corridor wall. Doors may swing or slide. • Must have latching device to keep the door in a
closed position• Must comply with 7.2.1.9, “Powered Door Leaf
Operation”
Protective Door Plates
LSC 19.3.6.3.122012 wording removed the height restriction
on protective plates on corridor doors.
Plates may be factory-applied or field-applied.Fire rating of the plate is not required.
2012LifeSafetyCodeUpdate June20,2016
AlabamaDepartment ofPublicHealth 13
Corridor Wall Openings
LSC A19.3.6.5.1 New Annex note • Unprotected mail slots and pass-through
openings in walls, vision panels and doors• Not intended to be at hazardous areas
Bedroom Outside Window
LSC 19.3.8 • NFPA deleted code requirement for outside
window or door at each sleeping room. However –• CMS added the requirement to the revised
federal regulations for hospitals and long term care facilities. Required sill heights.
• ADPH licensure requirement
Indoor Gas FireplacesLSC 19.5.2.3 Expanded requirements• Direct-vent type, per NFPA 54• May be within smoke compartment with sleeping
rooms if sprinklered with quick-response or residential sprinklers
• Not within a sleeping room• Locked or restricted gas controls• Wire mesh screen and sealed glass front • Electrically supervised carbon monoxide
detection in the room
2012LifeSafetyCodeUpdate June20,2016
AlabamaDepartment ofPublicHealth 14
Indoor Solid Fuel Fireplaces
LSC 19.5.2.3 • Minimum 1-hour fire separation from patient
sleeping space• Fireplace enclosure such as tempered glass • Electrically supervised carbon monoxide
detection in the room• AHJ may require lock on enclosure, and other
safety precautions.• Raised hearth required in Chapter 18 New.
Smoking Areas
LSC 19.7.4No changes.
Portable Space HeatersLSC 19.7.8No changes.
19.7.5.1 Drapes vs. Cubicle Curtains
• Cubicle curtains still have to be flame resistant.
2012LifeSafetyCodeUpdate June20,2016
AlabamaDepartment ofPublicHealth 15
19.7.5.1 Drapes vs. Cubicle Curtains
• Draperies and curtains are not required to be flame resistant in patient rooms within a sprinklered smoke compartment.
• Draperies and curtains in other rooms or areas if the panels are not more than 48 sq ft, not exceeding 20% of wall area, and in sprinklered locations.
19.7.5.4 Mattresses and Upholstered
Furniture• No change for Alabama Nursing Homes.
• Since all existing nursing homes in Alabama have complete automatic sprinkler systems, the requirement for smoke detectors in the patient room does not apply.
19.7.5.6Decorations
• Flame-retardant or treated with approved coating
• Meet the NFPA 701, Standard Methods of Fire Tests for Flame Propagation of Textiles and Films, using the 20 kW ignition source
• Heat release not exceeding 100kW, NFPA 289, Standard Methods of Fire Tests for Individual Fuel Packages
2012LifeSafetyCodeUpdate June20,2016
AlabamaDepartment ofPublicHealth 16
19.7.5.6(4) Decorations Attached to
Walls, Ceilings & Doors Inside any room or space of a smoke compartment:
• Without a sprinklered system in the smoke compartment, decorations shall not exceed 20% of the wall, ceiling, and door in the area.
• With a sprinklered system in the smoke compartment, decorations shall not exceed 30% of the wall, ceiling, and door area.
• For patient sleeping rooms in a smoke compartment with sprinkler coverage, 50% is the max of the wall, ceiling, and door area.
19.7.5.7 Trash & Linen Containers
No new requirements. Soiled linen or trash collection receptacles shall not exceed 32 gallons in capacity.
Exception: No limit in hazardous areas.
19.7.5.7 Trash & Linen Containers
• Average density of container capacity in a room or space shall not exceed 0.5 gallon per square foot.Exception: No limit in hazardous areas.
2012LifeSafetyCodeUpdate June20,2016
AlabamaDepartment ofPublicHealth 17
19.7.5.7 Linen Containers
• General guideline: Bedrooms may have one 30 gallon linen container per resident.
19.7.5.7Trash & Linen
Containers
“Mobile soiled linen or trash collection receptacles with capacities greater than 32 gallons shall be located in a room protected as a hazardous area when not attended.”
19.7.5.7 (Handbook)Trash & Linen
Containers
2012LifeSafetyCodeUpdate June20,2016
AlabamaDepartment ofPublicHealth 18
Recycling ContainersLSC 19.5.7.2 – New provision for clean
paper
• Up to 96 gallon size
• If more than 96 gallons, shall be located in a room with self-closing door. Walls and ceiling resist the passage of smoke.
• The container used shall be labeled and listed as meeting FM approved Standard 6921, or equivalent.
Essential 2012 NFPA Codes
catalog.nfpa.org
$98
$73
catalog.nfpa.org
Essential 2012 NFPA CodesNFPA 99
2012LifeSafetyCodeUpdate June20,2016
AlabamaDepartment ofPublicHealth 19
$60
catalog.nfpa.org
Essential 2012 NFPA CodesNFPA 25
• Types of SuitesSleeping SuitePatient Care Non-Sleeping SuiteNon-Patient Care Suite
• 19.2.5.7.2.1 Sleeping Suite ArrangementStaff SupervisionSleeping Rooms within the Suite
2012 NFPA 101 Suites
2012LifeSafetyCodeUpdate June20,2016
AlabamaDepartment ofPublicHealth 20
• 19.2.5.7.2.2 Sleeping Suite Means of Egress
Exit Access DoorsExit into Other Suites
• 19.2.5.7.2.3 Sleeping Suite Maximum Size
Not to Exceed 5,000 square feet
Suites, continued
Sprinkler Requirements • 19.3.5.2 High-rise Buildings
Sprinkler System Throughout
Egress Lighting
• 7.8.1.3 New StairsIllumination Levels
• 7.9.2.2 New Power Systems for Emergency Lighting
Type 10, Class 1.5, Level 1
2012LifeSafetyCodeUpdate June20,2016
AlabamaDepartment ofPublicHealth 21
• 4.1 Building Systems CategoriesThe Code lists four categories: Category 1Category 2Category 3Category 4Risk AssessmentApplication
NFPA 99 Fundamentals
• 9.1 ApplicabilityNew constructionRenovated or Altered
Requirement for smoke venting in anesthetizing locations has been deleted from NFPA 99.
Heating, Ventilation, and Air Conditioning
• 10.2.3.6 Multiple Outlet Connection
Two or more power receptacles connected to a flexible cord to supply power to components of a movable equipment assembly that is rack, table, pedestal or cart mounted is permitted if you meet the four steps listed.
TIA 12-5.
NFPA 99 Electrical Equipment
2012LifeSafetyCodeUpdate June20,2016
AlabamaDepartment ofPublicHealth 22
• 15.1 ApplicabilityNew & Existing
NFPA 99 Features of Fire Protection
• CMS is working on a separate rule for “Emergency Preparedness” and is excluding this chapter from their regulations.
NFPA 99 Emergency Management
Remember! If It’s Not Documented, It Didn’t Happen!
– 7.9.3 Testing of emergency lighting monthly and annually
– 7.10.9 Visual inspection of Exit signs/30 days
– 9.4.6 Elevator Testing
2012LifeSafetyCodeUpdate June20,2016
AlabamaDepartment ofPublicHealth 23
Fire Alarm
It’s official! The fire alarm system doesn’t have to wake the dead in health care facilities, see 9.6.3.6.3.
You may use the private operating mode.
Sprinkler Systems• All nursing homes shall have a complete
automatic sprinkler system. 19.3.5.1
• Maintenance and testing per NFPA 25
• Documentation on the sprinkler system that you must maintain includes design and inspections for the life of the fire protection system.
Sprinkler Systems Impairment
• Reference NFPA 25
Ø Must have an “Impairment Coordinator”
Ø Sprinkler system must be tagged to show that the sprinkler system is impaired; a tag shall be posted at each fire department connection, system connection valves, and other locations as required by the AHJ to indicate all or which part is impaired.
2012LifeSafetyCodeUpdate June20,2016
AlabamaDepartment ofPublicHealth 24
Sprinkler Systems Impairment
• Planned Impairment Program
• Emergency Impairments
Sprinkler Systems Impairment
If the sprinkler system is out of service for more than 10 hours in a 24 hour period:
ØEvacuate the building or the portion of the building, or
ØImplement an approved fire watch, orØEstablish a temporary water supply, orØSet up an approved program to eliminate
potential ignition source and limit the amount of fuel for a fire.
SprinklerSystems
• Identifythelocationoftheshutoffvalveswithapermanentsign
• Testsprinklerheadsifinserviceformorethan50years,repeatat10years
• Ifsprinklersysteminstalledpriorto1929replace
• Sprinklersystemwithfast-responseelementsafter20yearsreplacedortested
2012LifeSafetyCodeUpdate June20,2016
AlabamaDepartment ofPublicHealth 25
Statement of Deficiencies (SOD)
Due out of the state office within 10 working days
Plan of Correction (POC)
Must be returned to state office within 10 calendar days
§ Each deficiency must have a POC (Plan of Correction) with a completion date not later than the date shown in the ADPH letter
§ 35 days after the health team has left your facility
§ Waivers for additional time may be granted
2012LifeSafetyCodeUpdate June20,2016
AlabamaDepartment ofPublicHealth 26
4 ELEMENTS TO A POC
1. Specific corrective action.2. Identify any other occurrences.3. Policies/procedures you have set in place to
insure the deficiency will not occur again.4. How will you monitor the policies and
procedures you have set in place? Who will collect the information? How often will it be collected? What will trigger additional action?
An Example of a Citation
K-25 Smoke barriers shall be constructed to provide at least a one half hour fire resistance rating and constructed in accordance with 8.3. Smoke barriers shall be permitted to terminate at an atrium wall. Windows shall be protected by fire-rated glazing or by wired glass panels and steel frames.
Example of a citation (cont.)Based on observation of all smoke barriers on 5/11/2016, the facility failed to maintain smoke barriers with a system or material capable of restricting the transfer of smoke. Findings include:
Smoke barrier at Room 201 had holes in several locations where drywall mud had fallen out. In some locations, the holes had been sealed with an orange foam product. The facility personnel could not provide documentation for the orange foam to verify if the product could be used in a commercial building for rated walls.
2012LifeSafetyCodeUpdate June20,2016
AlabamaDepartment ofPublicHealth 27
Rejected Plan of Correction Provided
1) The unsealed penetration in the smoke barrier at Room 201 will be repaired by the Maintenance Director.
2) The unapproved orange foam substance used to seal penetrations in the smoke barrier will be removed and will be sealed per life safety code standards by the maintenance personnel.
Rejected Plan of Correction Provided
3) The administrator provided training to the maintenance personnel on how to seal the smoke barrier and educated them on the importance of maintaining the wall to resist the transfer of smoke.
4) The maintenance personnel will monitor the smoke barriers weekly to ensure barriers are sealed appropriately and per life safety code standards. Any concerns noted will be addressed and monitoring will continue. A copy of these checks will be kept in the administrator’s office.
Reasons POC Rejected • This was the exact wording for the POC from
the previous years.• The name of the product used to seal the
penetrations was not provided.• What training did the administrator have in
order to train the maintenance staff on how to maintain the wall to limit the transfer of smoke?
• This facility was cited for this same tag three years in a row.
2012LifeSafetyCodeUpdate June20,2016
AlabamaDepartment ofPublicHealth 28
Why are we looking so closely?
• CMS has asked that the State Agency work to reduce repeat deficiencies in facilities.
• How can this be accomplished?ØFacilities must provide a better Plan of
Correction. ØFacility staff must be properly trained and
must be more diligent in follow-through
SprinklerSystems
• Newprovision– dry-typesprinklerheadsthathavebeeninstalledfor10yearsshallbereplaced,orasamplingsentfortesting.Retestafternext10years.
• Sampleneededfortestingnotlessthanfoursprinklersor1%,whicheverisgreater
2012LifeSafetyCodeUpdate June20,2016
AlabamaDepartment ofPublicHealth 29
Evacuation and Relocation Plan19.7
• No change– Written copies of your plan available for
supervisors and at the security desk, phone operators location, or nurses station.
– Instruct all employees periodically.– During fire drills, alarm shall be transmitted off
site.– Drill quarterly on each shift (not less than
once in any 3-month period).– Written record of drills, including participants
(LSC 4.7.6)
Fire Safety Plan 19.7.2.2• Remove all occupants.
• Transmission of fire alarm signal.
• Isolate the fire by closing the door to the effected room.
• Relocate patients as described per facility fire safety plan.
Written Safety Plan1.Use of alarms2.Transmission of alarm to fire department3.Emergency phone call to fire department (2003)4.Response to alarms5.Isolation of fire6.Evacuation of immediate area7.Evacuation of smoke compartment8.Preparation of floors and building for evacuation9.Extinguishment of fire
2012LifeSafetyCodeUpdate June20,2016
AlabamaDepartment ofPublicHealth 30
HCFA Transmittal Notice 99-94
• Issued by federal agency, still in effect– Deals with items in the corridor must be in
use, staff is actually using the equipment not just moving the equipment around because of the LSC survey. The equipment must have a permanent storage location, off of the corridor.
Not referring to “emergency medical equipment” in new wheeled equipment section.
Top 10 Deficiencies1. K147 Electrical2. K25 Smoke Barriers3. K18 Corridor Doors4. K29 Hazardous Areas5. K69 Cooking Equipment6. K66 Smoking 7. K130 Miscellaneous8. K50 Fire Drills9. K38 Maintain Exits10. K62 Sprinkler