PARAMETER LIST
Protection and Power Management, PPM-3● Alarm list● Parameter list
Document no.: 4189340672ASW version: 3.04. or later
-
8/17/2019 PPM-3 Parameter List 4189340672 UK
2/144
1. General information1.1. Warnings, legal information and safety..................................................................................................5
1.1.1. Warnings and notes ......................................................................................................................51.1.2. Legal information and disclaimer ..................................................................................................5
1.1.3. Safety issues ................................................................................................................................51.1.4. Electrostatic discharge awareness ...............................................................................................51.1.5. Factory settings ............................................................................................................................5
1.2. About the Parameter List........................................................................................................................61.2.1. General purpose............................................................................................................................61.2.2. Intended users...............................................................................................................................61.2.3. Contents and overall structure ......................................................................................................6
2. Alarm lis t2.1. Reverse power pro tection......................................................................................................................9
2.1.1. Reverse pow er protection..............................................................................................................92.2. Overcurrent protec tion..........................................................................................................................10
2.2.1. Overcurre nt protection.................................................................................................................102.3. Generator voltage protection................................................................................................................15
2.3.1. Generator voltage protection.......................................................................................................152.4. Generator frequen cy protection............................................................................................................17
2.4.1. Generator frequency protection...................................................................................................172.5. Busbar voltage pro tection.....................................................................................................................20
2.5.1. Busbar vo ltage protection............................................................................................................202.6. Busbar frequency protection................................................................................................................23
2.6.1. Busbar fre quency protection........................................................................................................232.7. Overload protectio n..............................................................................................................................26
2.7.1. Overload protection.....................................................................................................................262.8. Current unbalance protection...............................................................................................................29
2.8.1. Current u nbalance protection......................................................................................................292.9. Voltage asymmetry protection..............................................................................................................30
2.9.1. Voltage a symmetry protection.....................................................................................................302.10. Reactive power im port (loss of excitation)..........................................................................................30
2.10.1. Reactive power import (loss of excitation).................................................................................302.11. Reactive power e xport (overexcitation)..............................................................................................31
2.11.1. Reactive power export (overexcitation).....................................................................................312.12. Busbar Unbalanc e voltage protection................................................................................................31
2.12.1. Busbar U nbalance voltage protection........................................................................................312.13. Non Essential Lo ad trip......................................................................................................................32
2.13.1. Non Ess ential Load trip..............................................................................................................322.14. Max. parallel time protection..............................................................................................................36
2.14.1. Max. par allel time protection......................................................................................................362.15. Breaker external t rip alarm.................................................................................................................37
2.15.1. Breaker external trip alarm........................................................................................................372.16. Synchronisation a nd breaker alarms..................................................................................................38
2.16.1. Synchro nisation and breaker alarms.........................................................................................38
2.17. Regulation alarms ..............................................................................................................................422.17.1. Regulati on alarms......................................................................................................................422.18. Binary input setup ...............................................................................................................................44
2.18.1. Binary in put setup......................................................................................................................442.19. Analogue input se tup (option M15.6).................................................................................................59
2.19.1. Analogu e input setup (option M15.6).........................................................................................592.20. Multi-functional a nalogue input setup.................................................................................................63
2.20.1. Multi-inp ut no. 102.....................................................................................................................632.20.2. Multi-input n o. 105.....................................................................................................................692.20.3. Multi-inp ut no. 108.....................................................................................................................75
2.21. Overspeed , running, start/stop failure................................................................................................822.21.1. Over speed, running, start/stop failure........................................................................................82
2.22. Analogue input se tup (option M15.8).................................................................................................85
PPM-3 parameter list 4189340672 UK
DEIF A/S Page 2 of 144
-
8/17/2019 PPM-3 Parameter List 4189340672 UK
3/144
2.22.1. Analogue input setup (option M15.8).........................................................................................852.23. Aux. supply setup...............................................................................................................................90
2.23.1. Aux. supply setup......................................................................................................................902.24. General setup.....................................................................................................................................92
2.24.1. General setup............................................................................................................................922.25. Communication..................................................................................................................................932.25.1. Communication..........................................................................................................................93
2.26. Engine interface communication alarms............................................................................................942.26.1. Engine interface communication alarms....................................................................................94
2.27. Application error.................................................................................................................................972.27.1. Application error.........................................................................................................................97
2.28. External I/O com munication error.......................................................................................................982.28.1. External I/O communication error..............................................................................................98
2.29. External I/O alarm setup.....................................................................................................................982.29.1. External I/O alarm setup............................................................................................................982.29.2. Analogue in puts.........................................................................................................................992.29.3. Digital input s............................................................................................................................100
3. Parameter lis t3.1. Synchronisation.... ..............................................................................................................................1023.1.1. Synchroni sation.........................................................................................................................102
3.2. Regulation............. .............................................................................................................................1043.2.1. Regulatio n..................................................................................................................................104
3.3. Digital output setup .............................................................................................................................1103.3.1. Digital out put setup....................................................................................................................110
3.4. Pulse width modul ation......................................................................................................................1133.4.1. Pulse wid th modulation..............................................................................................................113
3.5. Load reduction...... ..............................................................................................................................1143.5.1. Load redu ction...........................................................................................................................114
3.6. Analogue output li mits........................................................................................................................1153.6.1. Analogue output limits...............................................................................................................115
3.7. Transducer outputs ............................................................................................................................1163.7.1. Transducer o utputs....................................................................................................................116
3.8. Regulator outp ut selection..................................................................................................................1203.8.1. Regulator out put selection.........................................................................................................120
3.9. System............ ...................................................................................................................................1213.9.1. System......... ..............................................................................................................................1213.9.2. General s etup............................................................................................................................122
3.10. EDG setup.......... ..............................................................................................................................1273.10.1. EDG set up...............................................................................................................................127
3.11. External commun ication...................................................................................................................1283.11.1. External communication..........................................................................................................128
3.12. Internal communi cation....................................................................................................................1283.12.1. Internal communication............................................................................................................128
3.13. Engine interface c ommunication......................................................................................................1293.13.1. Engine i nterface communication..............................................................................................129
3.14. External I/O com munication setup...................................................................................................1303.14.1. External I/O communication setup...........................................................................................130
3.15. Power managem ent setup...............................................................................................................1313.15.1. Power m anagement setup.......................................................................................................131
3.16. Jump men us.....................................................................................................................................1363.16.1. Jump menus............................................................................................................................1363.16.2. 9000 Softwa re version.............................................................................................................1363.16.3. 9020 Servic e port.....................................................................................................................1363.16.4. 9070 M4 SW version...............................................................................................................1363.16.5. 9100 De vice type.....................................................................................................................1373.16.6. 911X Passw ord........................................................................................................................1373.16.7. 9120 Se rvice menu..................................................................................................................1373.16.8. 9130 AC co nfiguration.............................................................................................................138
PPM-3 parameter list 4189340672 UK
DEIF A/S Page 3 of 144
-
8/17/2019 PPM-3 Parameter List 4189340672 UK
4/144
3.16.9. 9150 Backlight dimmer............................................................................................................1383.16.10. 9160 Application setup..........................................................................................................1383.16.11. 9190 Application broadcast...................................................................................................138
3.17. GSM settings....................................................................................................................................139
3.17.1. GSM settings...........................................................................................................................1393.18. Passwords........................................................................................................................................1393.18.1. Passwords...............................................................................................................................139
3.19. VDO 102...........................................................................................................................................1403.19.1. VDO 102..................................................................................................................................140
3.20. VDO 105...........................................................................................................................................1423.20.1. VDO 105..................................................................................................................................142
3.21. VDO 108...........................................................................................................................................1423.21.1. VDO 108..................................................................................................................................142
3.22. Multi-inputs selections......................................................................................................................1433.22.1. Multi-inputs selections.............................................................................................................143
3.23. External digital outputs.....................................................................................................................1433.23.1. External digital outputs............................................................................................................143
3.24. External Module Status....................................................................................................................144
3.24.1. External Module Status............................................................................................................144
PPM-3 parameter list 4189340672 UK
DEIF A/S Page 4 of 144
-
8/17/2019 PPM-3 Parameter List 4189340672 UK
5/144
1. General information1.1 Warnings, legal information and safety
1.1.1 Warnings and notesThroughout this document, a number of warnings and notes with helpful user information will be presented.To ensure that these are noticed, they will be highlighted as follows in order to separate them from the gener-al text.
Warnings
Warnings i ndicate a potentially dangerous situation, which cou ld result i n death, personal in- jury or damaged equipment, i f certain guideli nes are not fo ll owed.
Notes
Notes provide general information, which will be helpful for the reader to bear in mind.
1.1.2 Legal information and disclaimer DEIF takes no responsibility for installation or operation of the generator set. If there is any doubt about howto install or operate the engine/generator controlled by the Multi-line 2 unit, the company responsible for theinstallation or the operation of the set must be contacted.
The Multi-line 2 unit is not to be op ened by unauthorised personnel. If opened anyway, the war-ranty will be lost.
Disclaimer DEIF A/S reserves the right to change any of the contents of this document without prior notice.
1.1.3 Safety issuesInstalling and operating the Multi-line 2 unit may imply work with dangerous currents and voltages. Therefore,the installation should only be carried out by authorised personnel who understand the risks involved in work-ing with live electrical equipment.
Be aware of the hazardous live currents and voltages. Do not touch any AC measurement in-puts as this could lead to injury or death.
1.1.4 Electro static d ischarge awareness
Sufficient care must be taken to protect the terminal against static discharges during the installation. Once theunit is installed and connected, these precautions are no longer necessary.
1.1.5 Factory settingsThe Multi-line 2 unit is delivered from factory with certain factory settings. These are based on average valuesand are not necessarily the correct settings for matching the engine/generator set in question. Precautionsmust be taken to check the settings before running the engine/generator set.
PPM-3 parameter list 4189340672 UK General information
DEIF A/S Page 5 of 144
-
8/17/2019 PPM-3 Parameter List 4189340672 UK
6/144
1.2 Abou t the Parameter List
1.2.1 General purpose
This document is a complete parameter list including all parameters, which means that some of the optionparameters included may not be accessible in the system in question.
The document includes a complete standard alarm list and a complete standard parameter list for setup.Therefore, this document is to be used for reference, when information about specific alarms and parametersis needed.
Please make sure to read this document b efore starting to work with th e Multi-line 2 unit andthe gen-set to be controlled. Failure to do this could result in human inju ry or damage to theequipment.
1.2.2 Intended users
This Parameter List is mainly intended for the person responsible for the unit parameter setup. In most cases,this would be a panel builder designer. Naturally, other users might also find useful information here.
1.2.3 Contents and overall structureThis document is divided into chapters, and in order to make the structure simple and easy to use, eachchapter will begin from the top of a new page.
PPM-3 parameter list 4189340672 UK General information
DEIF A/S Page 6 of 144
-
8/17/2019 PPM-3 Parameter List 4189340672 UK
7/144
2. Alarm l ist
In the followi ng, these abbreviations are used:G: Generator GB: Generator br eaker TB: Tie breaker (for emergency generator)SG: Shaft generator SGB: Shaft g enerator br eaker SC: Shore connectionSCB: Shore connection breaker BT: Bus tieBTB: Bus tie breaker BA: Busbar A (BTB unit)N/A: Not available
This chapter includes a complete alarm list, including all possible options. Therefore, this chapter is to beused for reference when specific information about the individual parameters is needed for the unit setup.
The table consists of the following possible adjustments:
Setpoint: The alarm setpoint is adjusted in the setpoint menu. The setting is a percentageof the nominal values.
Delay: The timer setting is the time that must expire from the alarm level is reached untilthe alarm occurs.
Relay output A: A relay can be activated by output A.
Relay output B: A relay can be activated by output B.
Enable: The alarm can be activated or deactivated. ON means always activated,RUN means that the alarm has run status.This means it is activated when the running signal is present.
Fail class: When the alarm occurs, the unit will react depending on the selected fail class.
PPM-3 parameter list 4189340672 UK Alarm list
DEIF A/S Page 7 of 144
-
8/17/2019 PPM-3 Parameter List 4189340672 UK
8/144
Fail classes are:
Fail class DG
(Diesel gener-ator)
EDG
(Emergencydiesel genera-
tor)
SC
(Shore con-nection)
SG
(Shaft genera-tor)
BTB
(Bus tie break-er)
1 Block Block Block Block Block
2 Warning Warning Warning Warning Warning
3 Trip GB Trip GB Trip SCB Trip SGB Trip BTB
4 Trip + Stop Trip + Stop N/A N/A N/A
5 Shut down Shut down N/A N/A N/A
6 Safety stop N/A N/A N/A N/A
7 N/A Trip TB N/A N/A N/A
Small differences due to the character of the parameters may exist between the individual ta-bles.
It is also possible to configure the pa-rameters by using the PC utility soft-ware. It will be possible to make thesame configurations as describedabove.
By using the PC utility software, someextra functionalities are available. For all the protections, it is possible tomake an automatic acknowledgementof the alarm.
PPM-3 parameter list 4189340672 UK Alarm list
DEIF A/S Page 8 of 144
-
8/17/2019 PPM-3 Parameter List 4189340672 UK
9/144
2.1 Reverse power pr otecti on
2.1.1 Reverse power protecti on
No. Setting Min.Max.
Factorysetting
Notes Ref. Description
1000 G/SG/SC reverse power 1
1001 G/SG/SC –P>1
Set-point
-110.0%0.0%
- 8.0% Designer’sReferenceHandbook
The alarm and fail class areactivated when the reversepower has been continuouslyabove the programmed valueduring the programmed de-lay.
1002 G/SG/SC -P>1
Delay 0.1 s300.0 s
5.0 s
1003 G/SG/
SC -P>1
Relay
output A
Not used
Option-de-pendent
Not
used
1004 G/SG/SC -P>1
RelayoutputB
Not usedOption-de-pendent
Notused
1005 G/SG/SC -P>1
Enable OFFON
ON
1006 G/SG/SC -P>1
Failclass
F1…F7 Trip GB(F3)
1010 G/SG/SC reverse power 2
1011 G/SG/SC -P>2
Set-point
-110.0%0.0%
- 15.0% Designer’sReferenceHandbook
The alarm and fail class areactivated when the reversepower has been continuouslyabove the programmed valueduring the programmed de-lay.
1012 G/SG/SC -P>2
Delay 0.1 s300.0 s
2.0 s
1013 G/SG/SC -P>2
Relayoutput
A
Not usedOption-de-pendent
Notused
1014 G/SG/SC -P>2
RelayoutputB
Not usedOption-de-pendent
Notused
1015 G/SG/SC -P>2
Enable OFFON
ON
1016 G/SG/SC -P>2
Failclass
F1…F7 Trip GB(F3)
PPM-3 parameter list 4189340672 UK Alarm list
DEIF A/S Page 9 of 144
-
8/17/2019 PPM-3 Parameter List 4189340672 UK
10/144
2.2 Overcurrent protection
2.2.1 Overcurrent protection
No. Setting Min.Max.
Facto-rysetting
Notes Ref. Description
1030 G/SG/SC/BA overcurrent 1
1031 G/SG/SC/BAI> 1
Set-point
50%200%
100% Design-er’s Refer-enceHandbook
The alarm and fail class are activa-ted when the current has beencontinuously above the program-med value during the programmeddelay.
1032 G/SG/SC/BAI> 1
Delay 0.1 s999.9 s
20.0 s
1033 G/SG/SC/BAI> 1
Relayoutput A
NotusedOption-de-pend-ent
Notused
1034 G/SG/SC/BAI> 1
RelayoutputB
NotusedOption-de-pend-ent
Notused
1035 G/SG/SC/BAI> 1
Enable OFFON
ON
1036 G/SG/SC/BAI> 1
Failclass
F1…F7 Warn-ing(F2)
1040 G/SG/SC/BA overcurrent 2
1041 G/SG/SC/BAI> 2
Set-point
50%200%
110% Design-er’s Refer-enceHandbook
The alarm and fail class are activa-ted when the current has beencontinuously above the program-med value during the programmeddelay.
1042 G/SG/
SC/BAI> 2
Delay 0.1 s
999.9 s
60.0 s
1043 G/SG/SC/BAI> 2
Relayoutput
A
NotusedOption-de-pend-ent
Notused
PPM-3 parameter list 4189340672 UK Alarm list
DEIF A/S Page 10 of 144
-
8/17/2019 PPM-3 Parameter List 4189340672 UK
11/144
No. Setting Min.Max.
Facto-rysetting
Notes Ref. Description
1044 G/SG/SC/BAI> 2
RelayoutputB
NotusedOption-de-pend-ent
Notused
1045 G/SG/SC/BAI> 2
Enable OFFON
ON
1046 G/SG/SC/BA
I> 2
Failclass
F1…F7 TripGB
(F3)1050 G/SG/SC/BA overcurrent 3
1051 G/SG/SC/BAI> 3
Set-point
50%200%
130% Design-er’s Refer-enceHandbook
The alarm and fail class are activa-ted when the current has beencontinuously above the program-med value during the programmeddelay.
1052 G/SG/SC/BAI> 3
Delay 0.1 s999.9 s
30.0 s
1053 G/SG/SC/BAI> 3
Relayoutput
A
NotusedOption-
de-pend-ent
Notused
1054 G/SG/SC/BAI> 3
RelayoutputB
NotusedOption-de-pend-ent
Notused
1055 G/SG/SC/BAI> 3
Enable OFFON
ON
1056 G/SG/SC/BAI> 3
Failclass
F1…F7 TripGB(F3)
1060 G/SG/SC/BA overcurrent 4
1061 G/SG/SC/BAI> 4
Set-point
50%200%
150% Design-er’s Refer-enceHandbook
The alarm and fail class are activa-ted when the current has beencontinuously above the program-med value during the programmeddelay.
PPM-3 parameter list 4189340672 UK Alarm list
DEIF A/S Page 11 of 144
-
8/17/2019 PPM-3 Parameter List 4189340672 UK
12/144
No. Setting Min.Max.
Facto-rysetting
Notes Ref. Description
1062 G/SG/SC/BAI> 4
Delay 0.1 s999.9 s
10.0 s
1063 G/SG/SC/BAI> 4
Relayoutput
A
NotusedOption-de-pend-ent
Notused
1064 G/SG/SC/BA
I> 4
Relayoutput
B
Notused
Option-de-pend-ent
Notused
1065 G/SG/SC/BAI> 4
Enable OFFON
ON
1066 G/SG/SC/BAI> 4
Failclass
F1…F7 TripGB(F3)
1100 Voltage-dependent overcurrent curve setting
1101 Voltagedep. I> set-pointI1
50%200% 110% @50%nom volt-age
Design-er’s Refer-enceHandbook
Settings relate to nominal genera-tor current.The condition has to be true i.e.I1
set-pointI6
50%200%
200% @100%nom volt-age
1110 Voltage-dependent overcur rent alarm
PPM-3 parameter list 4189340672 UK Alarm list
DEIF A/S Page 12 of 144
-
8/17/2019 PPM-3 Parameter List 4189340672 UK
13/144
No. Setting Min.Max.
Facto-rysetting
Notes Ref. Description
1111 Voltagedep. I>
Timer 0.1 s300.0 s
1.0 s Design-er’s Refer-enceHandbook
The alarm and fail class is activa-ted when the overcurrent has beencontinuously above the program-med value during the programmeddelay. Values are set in parame-ters 1101-1106.
1112 Voltagedep. I>
Relay A
NotusedOption-de-pend-ent
Notused
1113 Voltagedep. I>
RelayB
NotusedOption-
de-pend-ent
Notused
1114 Voltagedep. I>
Acti-vate
OFFON
OFF
1115 Voltagedep. I>
Failclass
F1…F7 Warn-ing(F2)
1130 G/SG/SC/BA fast overcur rent 1
1131 G/SG/SC/BA
I>> 1
Set-point
80%350%
200% Design-er’s Refer-
enceHandbook
The alarm and fail class are activa-ted when the current has been
continuously above the program-med value during the programmeddelay.
1132 G/SG/SC/BAI>> 1
Delay 0.0 s3.0 s
0.0 s
1133 G/SG/SC/BAI>> 1
Relayoutput
A
NotusedOption-de-pend-ent
Notused
1134 G/SG/SC/BAI>> 1
RelayoutputB
NotusedOption-de-pend-ent
Notused
1135 G/SG/SC/BAI>> 1
Enable OFFON
OFF
PPM-3 parameter list 4189340672 UK Alarm list
DEIF A/S Page 13 of 144
-
8/17/2019 PPM-3 Parameter List 4189340672 UK
14/144
No. Setting Min.Max.
Facto-rysetting
Notes Ref. Description
1136 G/SG/SC/BAI>> 1
Failclass
F1…F7 TripGB(F3)
1140 G/SG/SC/BA fast overcur rent 2
1141 G/SG/SC/BAI>> 2
Set-point
80%350%
300% Design-er’s Refer-enceHandbook
The alarm and fail class are activa-ted when the current has beencontinuously above the program-med value during the programmeddelay.
1142 G/SG/SC/BAI>> 2
Delay 0.0 s3.0 s
0.0 s
1143 G/SG/SC/BAI>> 2
Relayoutput
A
NotusedOption-de-pend-ent
Notused
1144 G/SG/SC/BAI>> 2
RelayoutputB
NotusedOption-de-pend-ent
Notused
1145 G/SG/SC/BAI>> 2
Enable OFFON OFF
1146 G/SG/SC/BAI>> 2
Failclass
F1…F7 TripGB(F3)
PPM-3 parameter list 4189340672 UK Alarm list
DEIF A/S Page 14 of 144
-
8/17/2019 PPM-3 Parameter List 4189340672 UK
15/144
2.3 Generator voltage protection
2.3.1 Generator voltage protection
No. Setting Min.Max.
Factorysetting
Notes Ref. Description
1150 G/SG/SC overvoltage 1
1151 G/SG/SCU> 1
Set-point
80%120%
105% Designer’sReferenceHandbook
The alarm and fail class are ac-tivated when the voltage hasbeen continuously above theprogrammed value during theprogrammed delay.
1152 G/SG/SCU> 1
Timer 0.1 s100.0 s
5.0 s
1153 G/SG/
SCU> 1
Relay
A
Not used
Option-depend-ent
Not
used
1154 G/SG/SCU> 1
RelayB
Not usedOption-depend-ent
Notused
1155 G/SG/SCU> 1
Enable OFFON
ON
1156 G/SG/SCU> 1
Failclass
F1…F7 Warning(F2)
1160 G/SG/SC overvoltage 2
1161 G/SG/SCU> 2
Set-point
80%120%
115% Designer’sReferenceHandbook
The alarm and fail class are ac-tivated when the voltage hasbeen continuously above theprogrammed value during theprogrammed delay.
1162 G/SG/SCU> 2
Timer 0.1 s100.0 s
1.0 s
1163 G/SG/SCU> 2
Relay A
Not usedOption-depend-
ent
Notused
1164 G/SG/SCU> 2
RelayB
Not usedOption-depend-ent
Notused
1165 G/SG/SCU> 2
Enable OFFON
ON
PPM-3 parameter list 4189340672 UK Alarm list
DEIF A/S Page 15 of 144
-
8/17/2019 PPM-3 Parameter List 4189340672 UK
16/144
No. Setting Min.Max.
Factorysetting
Notes Ref. Description
1166 G/SG/SCU> 2
Failclass
F1…F7 Block(F1)
1170 G/SG/SC undervoltage 1
1171 G/SG/SCU< 1
Set-point
50%100%
95% Designer’sReferenceHandbook
The alarm and fail class are ac-tivated when the voltage hasbeen continuously under theprogrammed value during theprogrammed delay.
1172 G/SG/SCU< 1
Timer 0.1 s100.0 s
5.0 s
1173 G/SG/SCU< 1
Relay A
Not usedOption-depend-ent
Notused
1174 G/SG/SCU< 1
RelayB
Not usedOption-depend-ent
Notused
1175 G/SG/SCU< 1
Enable OFFON
ON
1176 G/SG/SC
U< 1
Failclass
F1…F7 Warning(F2)
1180 G/SG/SC undervoltage 2
1181 G/SG/SCU< 2
Set-point
50%100%
80% Designer’sReferenceHandbook
The alarm and fail class are ac-tivated when the voltage hasbeen continuously under theprogrammed value during theprogrammed delay.
1182 G/SG/SCU< 2
Timer 0.1 s100.0 s
3.0 s
1183 G/SG/SCU< 2
Relay A
Not usedOption-depend-
ent
Notused
1184 G/SG/SCU< 2
RelayB
Not usedOption-depend-ent
Notused
1185 G/SG/SCU< 2
Enable OFFON
ON
PPM-3 parameter list 4189340672 UK Alarm list
DEIF A/S Page 16 of 144
-
8/17/2019 PPM-3 Parameter List 4189340672 UK
17/144
No. Setting Min.Max.
Factorysetting
Notes Ref. Description
1186 G/SG/SCU< 2
Failclass
F1…F7 Block(F1)
1190 G/SG/SC undervoltage 3
1191 G/SG/SCU< 3
Set-point
50%100%
70% Designer’sReferenceHandbook
The alarm and fail class are ac-tivated when the voltage hasbeen continuously under theprogrammed value during theprogrammed delay.
1192 G/SG/SCU< 3
Timer 0.1 s100.0 s
1.0 s
1193 G/SG/
SCU< 3
Relay
A
Not used
Option-depend-ent
Not
used
1194 G/SG/SCU< 3
RelayB
Not usedOption-depend-ent
Notused
1195 G/SG/SCU< 3
Enable OFFON
OFF
1196 G/SG/SCU< 3
Failclass
F1…F7 Block(F1)
2.4 Generator frequency protection
2.4.1 Generator frequency protection
Frequency settings relate to t he nominal frequency setting.
PPM-3 parameter list 4189340672 UK Alarm list
DEIF A/S Page 17 of 144
-
8/17/2019 PPM-3 Parameter List 4189340672 UK
18/144
No. Setting Min.Max.
Factorysetting
Notes Ref. Description
1210 G/SG/SC overfrequency 1
1211 G/SG/SCf> 1
Set-point
80%120%
105% Designer’sReferenceHandbook
The alarm and fail class are ac-tivated when the frequency hasbeen continuously above theprogrammed value during theprogrammed delay.
1212 G/SG/SCf> 1
Timer 0.2 s100.0 s
5.0 s
1213 G/SG/SCf> 1
Relay A
Not usedOption-dep.
Notused
1214 G/SG/SCf> 1
RelayB
Not usedOption-dep.
Notused
1215 G/SG/SCf> 1
Enable OFFON
ON
1216 G/SG/SCf> 1
Failclass
F1…F7 Warning(F2)
1220 G/SG/SC overfrequency 2
1221 G/SG/SCf> 2
Set-point
80%120%
107% Designer’sReferenceHandbook
The alarm and fail class are ac-tivated when the frequency hasbeen continuously above theprogrammed value during theprogrammed delay.
1222 G/SG/SCf> 2
Timer 0.2 s100.0 s
3.0 s
1223 G/SG/SCf> 2
Relay A
Not usedOption-dep.
Notused
1224 G/SG/SCf> 2
RelayB
Not usedOption-dep.
Notused
1225 G/SG/SC
f> 2
Enable OFFON
ON
1226 G/SG/SCf> 2
Failclass
F1…F7 Block(F1)
1230 G/SG/SC overfrequency 3
PPM-3 parameter list 4189340672 UK Alarm list
DEIF A/S Page 18 of 144
-
8/17/2019 PPM-3 Parameter List 4189340672 UK
19/144
No. Setting Min.Max.
Factorysetting
Notes Ref. Description
1231 G/SG/SCf> 3
Set-point
80%120%
110% Designer’sReferenceHandbook
The alarm and fail class are ac-tivated when the frequency hasbeen continuously above theprogrammed value during theprogrammed delay.
1232 G/SG/SCf> 3
Timer 0.2 s100.0 s
1.0 s
1233 G/SG/SCf> 3
Relay A
Not usedOption-dep.
Notused
1234 G/SG/SCf> 3
RelayB
Not usedOption-dep.
Notused
1235 G/SG/SCf> 3
Enable OFFON
OFF
1236 G/SG/SCf> 3
Failclass
F1…F7 Block(F1)
1240 G/SG/SC underfrequency 1
1241 G/SG/SCf< 1
Set-point
80%100%
95% Designer’sReferenceHandbook
The alarm and fail class are ac-tivated when the frequency hasbeen continuously under theprogrammed value during the
programmed delay.1242 G/SG/
SCf< 1
Timer 0.2 s100.0 s
5.0 s
1243 G/SG/SCf< 1
Relay A
Not usedOption-dep.
Notused
1244 G/SG/SCf< 1
RelayB
Not usedOption-dep.
Notused
1245 G/SG/SCf< 1
Enable OFFON
ON
1246 G/SG/SCf< 1
Failclass
F1…F7 Warning(F2)
1250 G/SG/SC underfrequency 2
1251 G/SG/SCf< 2
Set-point
80%100%
93% Designer’sReferenceHandbook
The alarm and fail class are ac-tivated when the frequency hasbeen continuously under theprogrammed value during theprogrammed delay.
PPM-3 parameter list 4189340672 UK Alarm list
DEIF A/S Page 19 of 144
-
8/17/2019 PPM-3 Parameter List 4189340672 UK
20/144
No. Setting Min.Max.
Factorysetting
Notes Ref. Description
1252 G/SG/SCf< 2
Timer 0.2 s100.0 s
3.0 s
1253 G/SG/SCf< 2
Relay A
Not usedOption-dep.
Notused
1254 G/SG/SCf< 2
RelayB
Not usedOption-dep.
Notused
1255 G/SG/SCf< 2
Enable OFFON
ON
1256 G/SG/SCf< 2
Failclass
F1…F7 Block(F1)
1260 G/SG/SC underfrequency 3
1261 G/SG/SCf< 3
Set-point
80%100%
90% Designer’sReferenceHandbook
The alarm and fail class are ac-tivated when the frequency hasbeen continuously under theprogrammed value during theprogrammed delay.
1262 G/SG/SCf< 3
Timer 0.2 s100.0 s
1.0 s
1263 G/SG/SCf< 3
Relay A
Not usedOption-dep.
Notused
1264 G/SG/SCf< 3
RelayB
Not usedOption-dep.
Notused
1265 G/SG/SCf< 3
Enable OFFON
OFF
1266 G/SG/SCf< 3
Failclass
F1…F7 Block(F1)
2.5 Busbar volt age protection
2.5.1 Busbar voltage protection
Voltage settings relate to the nominal vo ltage setting.
PPM-3 parameter list 4189340672 UK Alarm list
DEIF A/S Page 20 of 144
-
8/17/2019 PPM-3 Parameter List 4189340672 UK
21/144
No. Setting Min.Max.
Factorysetting
Notes Ref. Description
1270 Busbar overvoltage 1
1271 BBU> 1
Set-point
90%150%
110% Designer’sReferenceHandbook
The alarm and fail class are acti-vated when the voltage has beencontinuously above the program-med value during the program-med delay.
1272 BBU> 1
Timer 0.00 s99.99 s
5.00 s
1273 BBU> 1
Relay A Not usedOption-dep.
Notused
1274 BBU> 1
Relay B Not usedOption-dep.
Notused
1275 BBU> 1 Enable OFFON ON
1276 BBU> 1
Failclass
F1…F7 Warning(F2)
1280 Busbar overvoltage 2
1281 BBU> 2
Set-point
90%150%
120% Designer’sReferenceHandbook
The alarm and fail class are acti-vated when the voltage has beencontinuously above the program-med value during the program-med delay.
1282 BBU> 2
Timer 0.00 s99.99 s
3.00 s
1283 BBU> 2
Relay A Not usedOption-
dep.
Notused
1284 BBU> 2
Relay B Not usedOption-dep.
Notused
1285 BBU> 2
Enable OFFON
ON
1286 BBU> 2
Failclass
F1…F7 Trip GB(F3)
1290 Busbar overvoltage 3
1291 BBU> 3
Set-point
90%150%
130% Designer’sReference
Handbook
The alarm and fail class are acti-vated when the voltage has been
continuously above the program-med value during the program-med delay.
1292 BBU> 3
Timer 0.00 s99.99 s
1.00 s
1293 BBU> 3
Relay A Not usedOption-dep.
Notused
1294 BBU> 3
Relay B Not usedOption-dep.
Notused
PPM-3 parameter list 4189340672 UK Alarm list
DEIF A/S Page 21 of 144
-
8/17/2019 PPM-3 Parameter List 4189340672 UK
22/144
No. Setting Min.Max.
Factorysetting
Notes Ref. Description
1295 BBU> 3
Enable OFFON
OFF
1296 BBU> 3
Failclass
F1…F7 Trip GB(F3)
1300 Busbar undervoltage 1
1301 BBU< 1
Set-point
50%100%
95% Designer’sReferenceHandbook
The alarm and fail class are acti-vated when the voltage has beencontinuously under the program-med value during the program-med delay.
1302 BBU< 1
Timer 0.00 s99.99 s
5.00 s
1303 BBU< 1
Relay A Not usedOption-
dep.
Notused
1304 BBU< 1
Relay B Not usedOption-dep.
Notused
1305 BBU< 1
Enable OFFON
ON
1306 BBU< 1
Failclass
F1…F7 Warning(F2)
1310 Busbar undervoltage 2
1311 BBU< 2
Set-point
50%100%
80% Designer’sReference
Handbook
The alarm and fail class are acti-vated when the voltage has been
continuously under the program-med value during the program-med delay.
1312 BBU< 2
Timer 0.00 s99.99 s
3.00 s
1313 BBU< 2
Relay A Not usedOption-dep.
Notused
1314 BBU< 2
Relay B Not usedOption-dep.
Notused
1315 BBU< 2
Enable OFFON
ON
1316 BB
U< 2
Fail
class
F1…F7 Trip GB
(F3)1320 Busbar undervoltage 3
1321 BBU< 3
Set-point
50%100%
70% Designer’sReferenceHandbook
The alarm and fail class are acti-vated when the voltage has beencontinuously under the program-med value during the program-med delay.
1322 BBU< 3
Timer 0.00 s99.99 s
2.00 s
1323 BBU< 3
Relay A Not usedOption-dep.
Notused
PPM-3 parameter list 4189340672 UK Alarm list
DEIF A/S Page 22 of 144
-
8/17/2019 PPM-3 Parameter List 4189340672 UK
23/144
No. Setting Min.Max.
Factorysetting
Notes Ref. Description
1324 BBU< 3
Relay B Not usedOption-dep.
Notused
1325 BBU< 3
Enable OFFON
OFF
1326 BBU< 3
Failclass
F1…F7 Trip GB(F3)
1330 Busbar undervoltage 4
1331 BBU< 4
Set-point
50%100%
60% Designer’sReferenceHandbook
The alarm and fail class are acti-vated when the voltage has beencontinuously under the program-med value during the program-med delay.
1332 BB
U< 4
Timer 0.00 s
99.99 s
1.00 s
1333 BBU< 4
Relay A Not usedOption-dep.
Notused
1334 BBU< 4
Relay B Not usedOption-dep.
Notused
1335 BBU< 4
Enable OFFON
OFF
1336 BBU< 4
Failclass
F1…F7 Trip GB(F3)
2.6 Busbar frequency pro tection
2.6.1 Busbar frequency protection
Frequency settings relate to t he nominal frequency setting.
PPM-3 parameter list 4189340672 UK Alarm list
DEIF A/S Page 23 of 144
-
8/17/2019 PPM-3 Parameter List 4189340672 UK
24/144
No. Setting Min.Max.
Factorysetting
Notes Ref. Description
1350 Busbar overfrequency 1
1351 BB f>1
Set-point
100%130%
105% Designer’sReferenceHandbook
The alarm and fail class are acti-vated when the frequency hasbeen continuously above the pro-grammed value during the pro-grammed delay.
1352 BB f>1
Timer 0.00 s99.99 s
5.00 s
1353 BB f>1
Relay A Not usedOption-dep.
Notused
1354 BB f>1
Relay B Not usedOption-dep.
Notused
1355 BB f>1 Enable OFFON ON
1356 BB f>1
Failclass
F1…F7 Warning(F2)
1360 Busbar overfrequency 2
1361 BB f>2
Set-point
100%130%
110% Designer’sReferenceHandbook
The alarm and fail class are acti-vated when the frequency hasbeen continuously above the pro-grammed value during the pro-grammed delay.
1362 BB f>2
Timer 0.00 s99.99 s
8.00 s
1363 BB f>2
Relay A Not usedOption-
dep.
Notused
1364 BB f>2
Relay B Not usedOption-dep.
Notused
1365 BB f>2
Enable OFFON
ON
1366 BB f>2
Failclass
F1…F7 Trip GB(F3)
1370 Busbar overfrequency 3
1371 BB f>3
Set-point
100%130%
120% Designer’sReference
Handbook
The alarm and fail class are acti-vated when the frequency has
been continuously above the pro-grammed value during the pro-grammed delay.
1372 BB f>3
Timer 0.00 s99.99 s
6.00 s
1373 BB f>3
Relay A Not usedOption-dep.
Notused
1374 BB f>3
Relay B Not usedOption-dep.
Notused
PPM-3 parameter list 4189340672 UK Alarm list
DEIF A/S Page 24 of 144
-
8/17/2019 PPM-3 Parameter List 4189340672 UK
25/144
No. Setting Min.Max.
Factorysetting
Notes Ref. Description
1375 BB f>3
Enable OFFON
OFF
1376 BB f>3
Failclass
F1…F7 Trip GB(F3)
1380 Busbar underfrequency 1
1381 BB f<1
Set-point
80%100%
96% Designer’sReferenceHandbook
The alarm and fail class are acti-vated when the frequency hasbeen continuously under the pro-grammed value during the pro-grammed delay.
1382 BB f<1
Timer 0.00 s99.99 s
5.00 s
1383 BB f<1
Relay A Not usedOption-
dep.
Notused
1384 BB f<1
Relay B Not usedOption-dep.
Notused
1385 BB f<1
Enable OFFON
ON
1386 BB f<1
Failclass
F1…F7 Warning(F2)
1390 Busbar underfrequency 2
1391 BB f<2
Set-point
80%100%
93% Designer’sReference
Handbook
The alarm and fail class are acti-vated when the frequency has
been continuously under the pro-grammed value during the pro-grammed delay.
1392 BB f<2
Timer 0.00 s99.99 s
10.00 s
1393 BB f<2
Relay A Not usedOption-dep.
Notused
1394 BB f<2
Relay B Not usedOption-dep.
Notused
1395 BB f<2
Enable OFFON
ON
1396 BB f<
2
Fail
class
F1…F7 Trip GB
(F3)1400 Busbar underfrequency 3
1401 BB f<3
Set-point
80%100%
92% Designer’sReferenceHandbook
The alarm and fail class are acti-vated when the frequency hasbeen continuously under the pro-grammed value during the pro-grammed delay.
1402 BB f<3
Timer 0.00 s99.99 s
8.00 s
1403 BB f<3
Relay A Not usedOption-dep.
Notused
PPM-3 parameter list 4189340672 UK Alarm list
DEIF A/S Page 25 of 144
-
8/17/2019 PPM-3 Parameter List 4189340672 UK
26/144
No. Setting Min.Max.
Factorysetting
Notes Ref. Description
1404 BB f<3
Relay B Not usedOption-dep.
Notused
1405 BB f<3
Enable OFFON
OFF
1406 BB f<3
Failclass
F1…F7 Trip GB(F3)
1410 Busbar underfrequency 4
1411 BB f<4
Set-point
80%100%
90% Designer’sReferenceHandbook
The alarm and fail class are acti-vated when the frequency hasbeen continuously under the pro-grammed value during the pro-grammed delay.
1412 BB f<
4
Timer 0.00 s
99.99 s
6.00 s
1413 BB f<4
Relay A Not usedOption-dep.
Notused
1414 BB f<4
Relay B Not usedOption-dep.
Notused
1415 BB f<4
Enable OFFON
OFF
1416 BB f<4
Failclass
F1…F7 Trip GB(F3)
2.7 Overload protection
2.7.1 Overload p rotecti on
Settings relate to nominal power.
PPM-3 parameter list 4189340672 UK Alarm list
DEIF A/S Page 26 of 144
-
8/17/2019 PPM-3 Parameter List 4189340672 UK
27/144
No. Setting Min.Max.
Facto-rysetting
Notes Ref. Description
1450 G/SG/SC/BA overload 1
1451 G/SG/SC/BAP> 1
Set-point
-200%200%
95% Designer’sReferenceHandbook
The alarm and fail class are activatedwhen the power has been continu-ously above the programmed valueduring the programmed delay.If negative values are chosen thehigh alarm must be deactivated. Thedeactivating is only available from theUSW.
1452 G/SG/SC/BAP> 1
Timer 0.1 s100.0 s
30.0 s
1453 G/SG/SC/BAP> 1
Relay A
R0Option-dep.
R0(none)
1454 G/SG/SC/BAP> 1
RelayB
R0Option-dep.
R0(none)
1455 G/SG/SC/BAP> 1
Ena-ble
OFFON
ON
1456 G/SG/SC/BAP> 1
Failclass
F1…F7 Warn-ing(F2)
1460 G/SG/SC/BA overload 2
1461 G/SG/SC/BAP> 2
Set-point
-200%200%
110% Designer’sReferenceHandbook
The alarm and fail class are activatedwhen the power has been continu-ously above the programmed valueduring the programmed delay.If negative values are chosen thehigh alarm must be deactivated. Thedeactivating is only available from theUSW.
1462 G/SG/SC/BAP> 2
Timer 0.1 s100.0 s
30.0 s
1463 G/SG/SC/BAP> 2
Relay A
R0Option-dep.
R0(none)
1464 G/SG/SC/BAP> 2
RelayB
R0Option-dep.
R0(none)
1465 G/SG/
SC/BAP> 2
Ena-
ble
OFF
ON
ON
1466 G/SG/SC/BAP> 2
Failclass
F1…F7 Trip GB(F3)
1470 G/SG/SC/BA overload 3
PPM-3 parameter list 4189340672 UK Alarm list
DEIF A/S Page 27 of 144
-
8/17/2019 PPM-3 Parameter List 4189340672 UK
28/144
No. Setting Min.Max.
Facto-rysetting
Notes Ref. Description
1471 G/SG/SC/BAP> 3
Set-point
-200%200%
120% Designer’sReferenceHandbook
The alarm and fail class are activatedwhen the power has been continu-ously above the programmed valueduring the programmed delay.If negative values are chosen thehigh alarm must be deactivated. Thedeactivating is only available from theUSW.
1472 G/SG/SC/BAP> 3
Timer 0.1 s100.0 s
10.0 s
1473 G/SG/SC/BAP> 3
Relay A
R0Option-dep.
R0(none)
1474 G/SG/SC/BA
P> 3
RelayB
R0Option-
dep.
R0(none)
1475 G/SG/SC/BAP> 3
Ena-ble
OFFON
OFF
1476 G/SG/SC/BAP> 3
Failclass
F1…F7 Trip GB(F3)
1480 G/SG/SC/BA overload 4
1481 G/SG/SC/BAP> 4
Set-point
-200%200%
130% Designer’sReferenceHandbook
The alarm and fail class are activatedwhen the power has been continu-ously above the programmed value
during the programmed delay.If negative values are chosen thehigh alarm must be deactivated. Thedeactivating is only available from theUSW.
1482 G/SG/SC/BAP> 4
Timer 0.1 s100.0 s
5.0 s
1483 G/SG/SC/BAP> 4
Relay A
R0Option-dep.
R0(none)
1484 G/SG/SC/BAP> 4
RelayB
R0Option-dep.
R0(none)
1485 G/SG/SC/BA
P> 4
Ena-ble
OFFON
OFF
1486 G/SG/SC/BAP> 4
Failclass
F1…F7 Trip GB(F3)
1490 G/SG/SC/BA overload 5
1491 G/SG/SC/BAP> 5
Set-point
-200%200%
150% Designer’sReferenceHandbook
The alarm and fail class are activatedwhen the power has been continu-ously above the programmed valueduring the programmed delay.
PPM-3 parameter list 4189340672 UK Alarm list
DEIF A/S Page 28 of 144
-
8/17/2019 PPM-3 Parameter List 4189340672 UK
29/144
No. Setting Min.Max.
Facto-rysetting
Notes Ref. Description
1492 G/SG/SC/BAP> 5
If negative values are chosen thehigh alarm must be deactivated. Thedeactivating is only available from theUSW.
Timer 0.1 s100.0 s
1.0 s
1493 G/SG/SC/BAP> 5
Relay A
R0Option-dep.
R0(none)
1494 G/SG/SC/BAP> 5
RelayB
R0Option-dep.
R0(none)
1495 G/SG/SC/BA
P> 5
Ena-ble
OFFON
OFF
1496 G/SG/SC/BAP> 5
Failclass
F1…F7 Trip GB(F3)
2.8 Current unbalance protection
2.8.1 Current unbalance protection
No. Setting Min.Max.
Facto-rysetting
Notes Ref. Description
1500 G Unbalance I
1501 G Un-bal-ance I
Set-point
0.00%100.00%
30% Design-er’s Ref-erenceHandbook
Settings relate to nominal current.The alarm and fail class are activa-ted when the difference betweenthe max. reading and the min.reading of the 3 measured currentshas been continuously above theprogrammed value during the pro-grammed delay.
1502 G Un-bal-ance I
Timer 0.1 s100.0 s
10.0 s
1503 G Un-bal-ance I
Relay A
R0Option-dep.
R0(none)
1504 G Un-bal-ance I
RelayB
R0Option-dep.
R0(none)
1505 G Un-bal-ance I
Ena-ble
OFFON
ON
1506 G Un-bal-ance I
Failclass
F1…F7 Warn-ing(F2)
PPM-3 parameter list 4189340672 UK Alarm list
DEIF A/S Page 29 of 144
-
8/17/2019 PPM-3 Parameter List 4189340672 UK
30/144
2.9 Voltage asymmetry protection
2.9.1 Voltage asymmetry protection
No. Setting Min.Max.
Facto-rysetting
Notes Ref. Description
1510 G Unbalance U
1511 G Un-bal-ance U
Set-point
0.00%50.00%
10% Design-er’s Ref-erenceHandbook
Settings relate to nominal voltage.The alarm and fail class are activa-ted when the difference between themax. reading and the min. reading of the 3 measured generator voltageshas been continuously above theprogrammed value during the pro-
grammed delay.
1512 G Un-bal-ance U
Timer 0.1 s100.0 s
10.0 s
1513 G Un-bal-ance U
Relay A R0Option-dep.
R0(none)
1514 G Un-bal-ance U
RelayB
R0Option-dep.
R0(none)
1515 G Un-bal-ance U
Ena-ble
OFFON
ON
1516 G Un-bal-ance U
Failclass
F1…F7 Warn-ing(F2)
2.10 Reactive power import (loss of excitation)
2.10.1 Reactive power import (loss of excitation)
No. Setting Min.Max.
Factorysetting
Notes Ref. Description
1520 G/SG reactive power import (loss of excitation)
1521 G/SG– Q>
Set-point
0.00%150.00%
50% Designer’sReferenceHandbook
Settings relate to nominal pow-er.The alarm and fail class are ac-tivated when imported VAr hasbeen continuously above theprogrammed value during theprogrammed delay.
1522 G/SG–
Q>
Timer 0.1 s
100.0 s
10.0 s
1523 G/SG– Q>
Relay A R0Option-dep.
R0(none)
1524 G/SG– Q>
Relay B R0Option-dep.
R0(none)
1525 G/SG– Q>
Enable OFFOFF
OFF
1526 G/SG– Q>
Failclass
F1…F7 Warning(F2)
PPM-3 parameter list 4189340672 UK Alarm list
DEIF A/S Page 30 of 144
-
8/17/2019 PPM-3 Parameter List 4189340672 UK
31/144
2.11 Reactive power export (overexcitation)
2.11.1 Reactive power export (overexcitation)
No. Setting Min.Max.
Factorysetting
Notes Ref. Description
1530 G/SG reactive power expor t (overexcitati on)
1531 G/SGQ>
Set-point
0.00%100.00%
75% Designer’sReferenceHandbook
Settings relate to nominal pow-er.The alarm and fail class are acti-vated when exported VAr hasbeen continuously above theprogrammed value during theprogrammed delay.
1532 G/SGQ>
Timer 0.1 s100.0 s
10.0 s
1533 G/SGQ>
Relay A R0Option-dep.
R0(none)
1534 G/SG
Q>
Relay B R0
Option-dep.
R0
(none)1535 G/SG
Q>Enable OFF
ONOFF
1536 G/SGQ>
Failclass
F1…F7 Warning(F2)
2.12 Busbar Unbalance voltage protection
2.12.1 Busbar Unbalance voltage protection
No. Setting Min.Max.
Facto-rysetting
Notes Ref. Description
1620 BB Unbalance U
1621 BB Un-bal-ance U
Set-point
0.00%50.00%
10% Design-er’s Ref-erenceHandbook
Settings relate to average actualvoltage.The alarm and fail class are activa-ted when the difference between themax. reading and the min. reading of the 3 measured busbar voltages hasbeen continuously above the pro-grammed value during the program-med delay.
1622 BB Un-bal-ance U
Timer 0.1 s100.0 s
10.0 s
1623 BB Un-bal-ance U
Relay A
R0Option-dep.
R0(none)
1624 BB Un-bal-ance U
RelayB
R0Option-dep.
R0(none)
1625 BB Un-bal-ance U
Ena-ble
OFFON
ON
1626 BB Un-bal-ance U
Failclass
F1…F7 Warn-ing(F2)
PPM-3 parameter list 4189340672 UK Alarm list
DEIF A/S Page 31 of 144
-
8/17/2019 PPM-3 Parameter List 4189340672 UK
32/144
2.13 Non Essential Load tr ip
2.13.1 Non Essential L oad tri p
Setting values relate to t he nominal setting.
PPM-3 parameter list 4189340672 UK Alarm list
DEIF A/S Page 32 of 144
-
8/17/2019 PPM-3 Parameter List 4189340672 UK
33/144
No. Setting Min.Max.
Factorysetting
Notes Ref. Description
1800 NEL 1 Overcurrent
1801 NEL 1 I> Setpoint 50%200%
100% Designer’s Ref-erence Hand-book
Trip of Non Essential Loaddue to overcurrent. Thisfunction activates NEL group1.
1802 NEL 1 I> Timer 0.1 s100.0 s
5.0 s
1803 NEL 1 I> Enable OFFON
OFF
1810 NEL 2 Overcurrent
1811 NEL 2 I> Setpoint 50%200%
100% Designer’s Ref-erence Hand-book
Trip of Non Essential Loaddue to overcurrent. Thisfunction activates NEL group
2.
1812 NEL 2 I> Timer 0.1 s
100.0 s
8.0 s
1813 NEL 2 I> Enable OFFON
OFF
1820 NEL 3 Overcurrent
1821 NEL 3 I> Setpoint 50%200%
100% Designer’s Ref-erence Hand-book
Trip of Non Essential Loaddue to overcurrent. Thisfunction activates NEL group3.
1822 NEL 3 I> Timer 0.1 s100.0 s
10.0 s
1823 NEL 3 I> Enable OFFON
OFF
1830 NEL 1 Busbar underfr equency
1831 NEL 1Bus f<
Setpoint 70%100%
95% Designer’s Ref-erence Hand-book
Trip of Non Essential Loaddue to low frequency. Thisfunction activates NEL group1.
1832 NEL 1Bus f<
Timer 0.1 s100.0 s
5.0 s
1833 NEL 1Bus f<
Enable OFFON
OFF
1840 NEL 2 Busbar underfr equency
1841 NEL 2Bus f<
Setpoint 70%100%
95% Designer’s Ref-erence Hand-book
Trip of Non Essential Loaddue to low frequency. Thisfunction activates NEL group
2.
1842 NEL 2
Bus f<
Timer 0.1 s
100.0 s
8.0 s
1843 NEL 2Bus f<
Enable OFFON
OFF
1850 NEL 3 Busbar underfr equency
1851 NEL 3Bus f<
Setpoint 70%100%
95% Designer’s Ref-erence Hand-book
Trip of Non Essential Loaddue to low frequency. Thisfunction activates NEL group3.
1852 NEL 3Bus f<
Timer 0.1 s100.0 s
10.0 s
PPM-3 parameter list 4189340672 UK Alarm list
DEIF A/S Page 33 of 144
-
8/17/2019 PPM-3 Parameter List 4189340672 UK
34/144
No. Setting Min.Max.
Factorysetting
Notes Ref. Description
1853 NEL 3Bus f<
Enable OFFON
OFF
1860 NEL 1 Overload
1861 NEL 1 P> Setpoint 10%200%
100% Designer’s Ref-erence Hand-book
Trip of Non Essential Loaddue to overload. This func-tion activates NEL group 1.1862 NEL 1 P> Timer 0.1 s
999.0 s5.0 s
1863 NEL 1 P> Enable OFFON
OFF
1870 NEL 2 Overload
1871 NEL 2 P> Setpoint 10%200%
100% Designer’s Ref-erence Hand-book
Trip of Non Essential Loaddue to overload. This func-tion activates NEL group 2.1872 NEL 2 P> Timer 0.1 s
999.0 s8.0 s
1873 NEL 2 P> Enable OFFON
OFF
1880 NEL 3 Overload
1881 NEL 3 P> Setpoint 10%200%
100% Designer’s Ref-erence Hand-book
Trip of Non Essential Loaddue to overload. This func-tion activates NEL group 3.1882 NEL 3 P> Timer 0.1 s
999.0 s10.0 s
1883 NEL 3 P> Enable OFFON
OFF
1890 NEL 1 High overl oad
1891 NEL 1P>>
Setpoint 10%200%
110% Designer’s Ref-erence Hand-book
Trip of Non Essential Loaddue to high overload. Thisfunction activates NEL group1.
1892 NEL 1P>>
Timer 0.1 s999.0 s
1.0 s
1893 NEL 1P>>
Enable OFFON
OFF
1900 NEL 2 High overl oad
1901 NEL 2P>>
Setpoint 10%200%
110% Designer’s Ref-erence Hand-book
Trip of Non Essential Loaddue to high overload. Thisfunction activates NEL group2.
1902 NEL 2P>>
Timer 0.1 s999.0 s
1.0 s
1903 NEL 2P>>
Enable OFFON
OFF
1910 NEL 3 High overl oad
PPM-3 parameter list 4189340672 UK Alarm list
DEIF A/S Page 34 of 144
-
8/17/2019 PPM-3 Parameter List 4189340672 UK
35/144
No. Setting Min.Max.
Factorysetting
Notes Ref. Description
1911 NEL 3P>>
Setpoint 10%200%
110% Designer’s Ref-erence Hand-book
Trip of Non Essential Loaddue to high overload. Thisfunction activates NEL group3.
1912 NEL 3P>>
Timer 0.1 s999.0 s
1.0 s
1913 NEL 3P>>
Enable OFFON
OFF
PPM-3 parameter list 4189340672 UK Alarm list
DEIF A/S Page 35 of 144
-
8/17/2019 PPM-3 Parameter List 4189340672 UK
36/144
2.14 Max. parallel time pro tection
2.14.1 Max. parallel t ime pro tection
No. Setting Min.Max.
Factorysetting
Notes Ref. Description
1930 DG/SG Max Time
1931 DG/SGMaxTime
Delay 0.1 s120.0 s
120.0 s Designer’sReferenceHandbook
Max allowable parallel timebetween diesel generatorsand shaft generator (DGunit only).1932 DG/SG
MaxTime
Relayoutput A
Not usedOption-dep.
Notused
1933 DG/SG
MaxTime
Relay
output B
Not used
Option-dep.
Not
used
1934 DG/SGMaxTime
Enable OFFON
ON
1935 DG/SGMaxTime
Failclass
F1…F7 Trip+stop(F4)
1940 DG/SC Max Time
1941 DG/SCMaxTime
Delay 0.1 s120.0 s
120.0 s Designer’sReferenceHandbook
Max allowable parallel timebetween diesel generatorsand shore connection (DGunit only).1942 DG/SC
MaxTime
Relayoutput A
Not usedOption-dep.
Notused
1943 DG/SCMaxTime
Relayoutput B
Not usedOption-dep.
Notused
1950 EG/MBB Max Time
1951 EG/MBBMaxTime
Delay 0.1 s30.0 s
30.0 s Designer’sReferenceHandbook
Max allowable parallel timebetween emergency dieselgenerator and main switch-board (EDG unit only).
1952 EG/MBBMaxTime
Relayoutput A Not usedOption-dep.
Notused
1953 EG/MBBMaxTime
Relayoutput B
Not usedOption-dep.
Notused
PPM-3 parameter list 4189340672 UK Alarm list
DEIF A/S Page 36 of 144
-
8/17/2019 PPM-3 Parameter List 4189340672 UK
37/144
2.15 Breaker external tri p alarm
2.15.1 Breaker external trip alarm
No. Setting Min.Max.
Factorysetting
Notes Ref. Description
1980 GB Externally trip ped
1981 GB Ext. trip Enable OFFON
ON Designer’s Refer-ence Handbook
The generator breaker hasbeen tripped by an externaldevice.
PPM-3 parameter list 4189340672 UK Alarm list
DEIF A/S Page 37 of 144
-
8/17/2019 PPM-3 Parameter List 4189340672 UK
38/144
2.16 Synchronisation and breaker alarms
2.16.1 Synchronisati on and b reaker alarms
No. Setting Min.Max.
Factorysetting
Notes Ref. Description
2130 GB/BTB breaker synchronisation failure
2131 GB/BTBsync fail-ure
Delay 3.0 s300.0 s
120.0 s Designer’sReferenceHandbook
GB: Generator breaker BTB: Bus tie breaker The controller has unsuccess-fully tried to synchronise thegenerator to the busbar withinthe time delay.
2132 GB/BTBsync fail-ure
Relayoutput
A
NotusedOption-dep.
Notused
2133 GB/BTBsync fail-ure
RelayoutputB
NotusedOption-dep.
Notused
2134 GB/BTBsync fail-ure
Enable OFFON
ON
2135 GB/BTBsync fail-ure
Failclass
F1…F7 Warn-ing(F2)
2140 SGB/SCB/TB breaker synchro nisati on fail ure
2141 SGB/SCB/TBsync fail-ure
Delay 3.0 s300.0 s
120.0 s Designer’sReferenceHandbook
SGB: Shaft generator breaker SCB: Shore connection breaker TB: Tie breaker (emergencygenerator)The controller has unsuccess-fully tried to synchronise thegenerator to the busbar withinthe time delay.
2142 SGB/SCB/TBsync fail-ure
Relayoutput
A
NotusedOption-dep.
Notused
2143 SGB/SCB/TBsync fail-ure
RelayoutputB
NotusedOption-dep.
Notused
2144 SGB/SCB/TBsync fail-ure
Enable OFFON
OFF
2145 SGB/SCB/TBsync fail-ure
Failclass
F1…F7 Warn-ing(F2)
2150 Phase sequence erro r
PPM-3 parameter list 4189340672 UK Alarm list
DEIF A/S Page 38 of 144
-
8/17/2019 PPM-3 Parameter List 4189340672 UK
39/144
No. Setting Min.Max.
Factorysetting
Notes Ref. Description
2151 Phaseseq error
Relayoutput
A
NotusedOption-dep.
Notused
Designer’sReferenceHandbook
During synchronisation, thecontroller has detected that therotation direction of the genera-tor phases is opposite directionas the busbar.2152 Phase
seq error RelayoutputB
NotusedOption-dep.
Notused
2153 Phaseseq error
Failclass
F1…F7 Block(F1)
2160 GB/BTB open failur e
2161 GB/BTBopen fail
Delay 1.0 s5.0 s
2.0 s Designer’sReferenceHandbook
The breaker open failure will oc-cur, if the unit has transmitted abreaker open signal and thebreaker feedback has notchanged position from ON toOFF within 2 s.
2162 GB/BTBopen fail
Relayoutput
A
NotusedOption-dep.
Notused
2163 GB/BTBopen fail
RelayoutputB
NotusedOption-dep.
Notused
2164 GB/BTBopen fail
Enable OFFON
ON
2165 GB/BTBopen fail
Failclass
F1…F7 Warn-ing(F2)
2170 GB/BTB breaker clo se failur e
2171 GB/BTBclose fail
Delay 1.0 s5.0 s
2.0 s Designer’sReferenceHandbook
The breaker close failure willoccur, if the unit has transmitteda breaker close signal and thebreaker feedback has notchanged position from OFF toON within 2 s.
2172 GB/BTBclose fail
Relayoutput
A
NotusedOption-dep.
Notused
2173 GB/BTB
close fail
Relay
outputB
Not
usedOption-dep.
Not
used
2174 GB/BTBclose fail
Enable OFFON
ON
2175 GB/BTBclose fail
Failclass
F1…F7 Warn-ing (F2)
2180 GB/BTB breaker position failure
PPM-3 parameter list 4189340672 UK Alarm list
DEIF A/S Page 39 of 144
-
8/17/2019 PPM-3 Parameter List 4189340672 UK
40/144
No. Setting Min.Max.
Factorysetting
Notes Ref. Description
2181 GB/BTBpos fail
Delay 1.0 s5.0 s
1.0 s Designer’sReferenceHandbook
This alarm will occur, if thebreaker feedbacks for ON andOFF are both missing or activefor more than 2 s at the time.
2182 GB/BTBpos fail
Relayoutput
A
NotusedOption-dep.
Notused
2183 GB/BTBpos fail
RelayoutputB
NotusedOption-dep.
Notused
2184 GB/BTBpos fail
Enable OFFON
ON
2185 GB/BTBpos fail
Failclass
F1…F7 Warn-ing(F2)
2200 SGB/SCB/TB o pen f ailure
2201 SGB/SCB/TBopen fail
Delay 1.0 s5.0 s
2.0 s Designer’sReferenceHandbook
The breaker open failure will oc-cur, if the unit has transmitted abreaker open signal and thebreaker feedback has notchanged position from ON toOFF within 2 s.
2202 SGB/SCB/TBopen fail
Relayoutput
A
NotusedOption-dep.
Notused
2203 SGB/SCB/TBopen fail
RelayoutputB
NotusedOption-dep.
Notused
2204 SGB/SCB/TBopen fail
Enable OFFON
ON
2205 SGB/SCB/TBopen fail
Failclass
F1…F7 Warn-ing(F2)
2210 SGB/SCB/TB c lose failur e
2211 SGB/SCB/TBclose fail
Delay 1.0 s5.0 s
2.0 s Designer’sReferenceHandbook
The breaker close failure willoccur, if the unit has transmitteda breaker close signal and thebreaker feedback has notchanged position from OFF toON within 2 s.
2212 SGB/SCB/TBclose fail
Relayoutput
A
NotusedOption-dep.
Notused
PPM-3 parameter list 4189340672 UK Alarm list
DEIF A/S Page 40 of 144
-
8/17/2019 PPM-3 Parameter List 4189340672 UK
41/144
No. Setting Min.Max.
Factorysetting
Notes Ref. Description
2213 SGB/SCB/TBclose fail
RelayoutputB
NotusedOption-dep.
Notused
2214 SGB/SCB/TBclose fail
Enable OFFON
ON
2215 SGB/SCB/TBclose fail
Failclass
F1…F7 Warn-ing(F2)
2220 SGB/SCB/TB posi tion failu re
2221 SGB/SCB/TBpos fail
Delay 1.0 s5.0 s
1.0 s Designer’sReferenceHandbook
This alarm will occur, if thebreaker feedbacks for ON andOFF are both missing or activefor more than 2 s.2222 SGB/
SCB/TBpos fail
Relayoutput
A
NotusedOption-dep.
Notused
2223 SGB/SCB/TBpos fail
RelayoutputB
NotusedOption-dep.
Notused
2224 SGB/
SCB/TBpos fail
Enable OFF
ON
ON
2225 SGB/SCB/TBpos fail
Failclass
F1…F7 Warn-ing(F2)
PPM-3 parameter list 4189340672 UK Alarm list
DEIF A/S Page 41 of 144
-
8/17/2019 PPM-3 Parameter List 4189340672 UK
42/144
2.17 Regulation alarms
2.17.1 Regulation alarms
No. Setting Min.Max.
Factorysetting
Notes Ref. Description
2560 Governor regulation fail
2561 Gov.reg fail
Dead-band
1%100%
30% Designer’sReferenceHandbook
The alarm is activated, if the dif-ference between the measuredvalue and the setpoint is out-side the deadband for a longer time period than specified bythe delay setpoint.
2562 Gov.reg fail
Delay 10.0 s300.0 s
60.0 s
2563 Gov.reg fail
Relayoutput A
Not usedOption-depend-
ent
Notused
2564 Gov.reg fail
Relayoutput B
Not usedOption-depend-ent
Notused
2630 Deload erro r
2631 Deloaderror
Delay 0.0 s60.0 s
10.0 s Designer’sReferenceHandbook
The alarm is activated, if thegenerator fails to deload withinthe time delay.2632 Deload
error Relayoutput A
Not usedOption-depend-ent
Notused
2633 Deloaderror
Relayoutput B
Not usedOption-depend-ent
Notused
2634 Deloaderror
Enable OFFON
ON
2635 Deloaderror
Failclass
F1…F7 Warning(F2)
2680 AVR regulation failure
2681 AVR
reg.failure
Dead-
band
1%
100%
30% Option: VAr
control (D1)
The alarm is activated, if the dif-
ference between the measuredvalue and the setpoint is out-side the setting ‘Deadband’ for a longer time period than speci-fied in the timer setpoint.
2682 AVRreg.failure
Delay 10.0 s300.0 s
60.0 s
1153 AVRreg.failure
Relay A R0Option-dep.
R0(none)
PPM-3 parameter list 4189340672 UK Alarm list
DEIF A/S Page 42 of 144
-
8/17/2019 PPM-3 Parameter List 4189340672 UK
43/144
No. Setting Min.Max.
Factorysetting
Notes Ref. Description
1154 AVRreg.failure
Relay B R0Option-dep.
R0(none)
1155 AVRreg.failure
Failclass
F1…F7 Warning(F2)
PPM-3 parameter list 4189340672 UK Alarm list
DEIF A/S Page 43 of 144
-
8/17/2019 PPM-3 Parameter List 4189340672 UK
44/144
2.18 Binary input setup
2.18.1 Binary input setup
No. Setting Min.Max.
Factorysetting
Notes Ref. Description
3010 Digital input 24
3011 Dig. in-put 24
Delay 0.0 s100.0 s
1.0 s Designer’sReferenceHandbook
The input is configurableand can have differentfunctions in different units.3012 Dig. in-
put 24Relayoutput A
Not usedOption-dep.
Not used
3013 Dig. in-put 24
Relayoutput B
Not usedOption-
dep.
Not used
3014 Dig. in-put 24
Enable OFFON
OFF
3015 Dig. in-put 24
Failclass
F1…F7 Warning(F2)
3016 Dig. in-put 24
N/X N/ON/C
N/O
3020 Digital input 25
3021 Dig. in-put 25
Delay 0.0 s100.0 s
1.0 s Designer’sReferenceHandbook
The input is configurableand can have differentfunctions in different units.3022 Dig. in-
put 25
Relay
output A
Not used
Option-dep.
Not used
3023 Dig. in-put 25
Relayoutput B
Not usedOption-dep.
Not used
3024 Dig. in-put 25
Enable OFFON
OFF
3025 Dig. in-put 25
Failclass
F1…F7 Warning(F2)
3026 Dig. in-put 25
N/X N/ON/C
N/O
3130 Digital input 43
3131 Dig. in-put 43
Delay 0.0 s100.0 s
1.0 s Designer’sReferenceHandbook
The input is configurableand can have differentfunctions in different units.3132 Dig. in-
put 43Relayoutput A
Not usedOption-dep.
Not used
3133 Dig. in-put 43
Relayoutput B
Not usedOption-dep.
Not used
PPM-3 parameter list 4189340672 UK Alarm list
DEIF A/S Page 44 of 144
-
8/17/2019 PPM-3 Parameter List 4189340672 UK
45/144
No. Setting Min.Max.
Factorysetting
Notes Ref. Description
3134 Dig. in-put 43
Enable OFFON
OFF
3135 Dig. in-put 43
Failclass
F1…F7 Warning(F2)
3136 Dig. in-put 43
N/X N/ON/C
N/O
3140 Digital input 44
3141 Dig. in-put 44
Delay 0.0 s100.0 s
1.0 s Designer’sReferenceHandbook
The input is configurableand can have differentfunctions in different units.3142 Dig. in-
put 44Relayoutput A
Not usedOption-
dep.
Not used
3143 Dig. in-put 44
Relayoutput B
Not usedOption-dep.
Not used
3144 Dig. in-put 44
Enable OFFON
OFF
3145 Dig. in-put 44
Failclass
F1…F7 Warning(F2)
3146 Dig. in-put 44
N/X N/ON/C
N/O
3150 Digital input 45
3151 Dig. in-put 45
Delay 0.0 s100.0 s
1.0 s Designer’sReferenceHandbook
The input is configurableand can have differentfunctions in different units.3152 Dig. in-
put 45Relayoutput A
Not usedOption-dep.
Not used
3153 Dig. in-put 45
Relayoutput B
Not usedOption-dep.
Not used
3154 Dig. in-put 45
Enable OFFON
OFF
3155 Dig. in-
put 45
Fail
class
F1…F7 Warning
(F2)3156 Dig. in-
put 45N/X N/O
N/CN/O
3160 Digital input 46
3161 Dig. in-put 46
Delay 0.0 s100.0 s
1.0 s Designer’sReferenceHandbook
The input is configurableand can have differentfunctions in different units.3162 Dig. in-
put 46Relayoutput A
Not usedOption-dep.
Not used
PPM-3 parameter list 4189340672 UK Alarm list
DEIF A/S Page 45 of 144
-
8/17/2019 PPM-3 Parameter List 4189340672 UK
46/144
No. Setting Min.Max.
Factorysetting
Notes Ref. Description
3163 Dig. in-put 46
Relayoutput B
Not usedOption-dep.
Not used
3164 Dig. in-put 46
Enable OFFON
OFF
3165 Dig. in-put 46
Failclass
F1…F7 Warning(F2)
3166 Dig. in-put 46
N/X N/ON/C
N/O
3170 Digital input 47
3171 Dig. in-
put 47
Delay 0.0 s
100.0 s
1.0 s Designer’s
ReferenceHandbook
The input is configurable
and can have differentfunctions in different units.3172 Dig. in-put 47
Relayoutput A
Not usedOption-dep.
Not used
3173 Dig. in-put 47
Relayoutput B
Not usedOption-dep.
Not used
3174 Dig. in-put 47
Enable OFFON
OFF
3175 Dig. in-put 47
Failclass
F1…F7 Warning(F2)
3176 Dig. in-put 47
N/X N/ON/C
N/O
3180 Digital input 48
3181 Dig. in-put 48
Delay 0.0 s100.0 s
1.0 s Designer’sReferenceHandbook
The input is configurableand can have differentfunctions in different units.3182 Dig. in-
put 48Relayoutput A
Not usedOption-dep.
Not used
3183 Dig. in-put 48
Relayoutput B
Not usedOption-dep.
Not used
3184 Dig. in-put 48
Enable OFFON
OFF
3185 Dig. in-put 48
Failclass
F1…F7 Warning(F2)
3186 Dig. in-put 48
N/X N/ON/C
N/O
3190 Digital input 49
PPM-3 parameter list 4189340672 UK Alarm list
DEIF A/S Page 46 of 144
-
8/17/2019 PPM-3 Parameter List 4189340672 UK
47/144
No. Setting Min.Max.
Factorysetting
Notes Ref. Description
3191 Dig. in-put 49
Delay 0.0 s100.0 s
1.0 s Designer’sReferenceHandbook
The input is configurableand can have differentfunctions in different units.3192 Dig. in-
put 49Relayoutput A
Not usedOption-dep.
Not used
3193 Dig. in-put 49
Relayoutput B
Not usedOption-dep.
Not used
3194 Dig. in-put 49
Enable OFFON
OFF
3195 Dig. in-put 49
Failclass
F1…F7 Warning(F2)
3196 Dig. in-put 49
N/X N/ON/C
N/O
3200 Digital input 50
3201 Dig. in-put 50
Delay 0.0 s100.0 s
1.0 s Designer’sReferenceHandbook
The input is configurableand can have differentfunctions in different units.3202 Dig. in-
put 50Relayoutput A
Not usedOption-dep.
Not used
3203 Dig. in-put 50
Relayoutput B
Not usedOption-dep.
Not used
3204 Dig. in-put 50
Enable OFFON
OFF
3205 Dig. in-put 50
Failclass
F1…F7 Warning(F2)
3206 Dig. in-put 50
N/X N/ON/C
N/O
3210 Digital input 51
3211 Dig. in-put 51
Delay 0.0 s100.0 s
1.0 s Designer’sReferenceHandbook
The input is configurableand can have differentfunctions in different units.3212 Dig. in-
put 51
Relay
output A
Not used
Option-dep.
Not used
3213 Dig. in-put 51
Relayoutput B
Not usedOption-dep.
Not used
3214 Dig. in-put 51
Enable OFFON
OFF
3215 Dig. in-put 51
Failclass
F1…F7 Warning(F2)
PPM-3 parameter list 4189340672 UK Alarm list
DEIF A/S Page 47 of 144
-
8/17/2019 PPM-3 Parameter List 4189340672 UK
48/144
No. Setting Min.Max.
Factorysetting
Notes Ref. Description
3216 Dig. in-put 51
N/X N/ON/C
N/O
3220 Digital input 52
3221 Dig. in-put 52
Delay 0.0 s100.0 s
1.0 s Designer’sReferenceHandbook
The input is configurableand can have differentfunctions in different units.3222 Dig. in-
put 52Relayoutput A
Not usedOption-dep.
Not used
3223 Dig. in-put 52
Relayoutput B
Not usedOption-dep.
Not used
3224 Dig. in-put 52 Enable OFFON OFF
3225 Dig. in-put 52
Failclass
F1…F7 Warning(F2)
3226 Dig. in-put 52
N/X N/ON/C
N/O
3230 Digital input 53
3231 Dig. in-put 53
Delay 0.0 s100.0 s
1.0 s Designer’sReferenceHandbook
The input is configurableand can have differentfunctions in different units.3232 Dig. in-
put 53Relayoutput A
Not usedOption-
dep.
Not used
3233 Dig. in-put 53
Relayoutput B
Not usedOption-dep.
Not used
3234 Dig. in-put 53
Enable OFFON
OFF
3235 Dig. in-put 53
Failclass
F1…F7 Warning(F2)
3236 Dig. in-put 53
N/X N/ON/C
N/O
3240 Digital input 54
3241 Dig. in-put 54
Delay 0.0 s100.0 s
1.0 s Designer’sReferenceHandbook
The input is configurableand can have differentfunctions in different units.3242 Dig. in-
put 54Relayoutput A
Not usedOption-dep.
Not used
3243 Dig. in-put 54
Relayoutput B
Not usedOption-dep.
Not used
PPM-3 parameter list 4189340672 UK Alarm list
DEIF A/S Page 48 of 144
-
8/17/2019 PPM-3 Parameter List 4189340672 UK
49/144
No. Setting Min.Max.
Factorysetting
Notes Ref. Description
3244 Dig. in-put 54
Enable OFFON
OFF
3245 Dig. in-put 54
Failclass
F1…F7 Warning(F2)
3246 Dig. in-put 54
N/X N/ON/C
N/O
3250 Digital input 55
3251 Dig. in-put 55
Delay 0.0 s100.0 s
1.0 s Designer’sReferenceHandbook
The input is configurableand can have differentfunctions in different units.3252 Dig. in-
put 55Relayoutput A
Not usedOption-
dep.
Not used
3253 Dig. in-put 55
Relayoutput B
Not usedOption-dep.
Not used
3254 Dig. in-put 55
Enable OFFON
OFF
3255 Dig. in-put 55
Failclass
F1…F7 Warning(F2)
3256 Dig. in-put 55
N/X N/ON/C
N/O
3330 Digital input 91
3331 Dig. in-put 91
Delay 0.0 s100.0 s
1.0 s Option:7 binary inputsin slot #6(M13.6)
The input is configurableand can have differentfunctions in different units.3332 Dig. in-
put 91Relayoutput A
R0Option-dep.
R0(none)
3333 Dig. in-put 91
Relayoutput B
R0Option-dep.
R0(none)
3334 Dig. in-put 91
Enable OFFON
OFF
3335 Dig. in-
put 91
Fail
class
F1…F7 Warning
(F2)3336 Dig. in-
put 91N/O - N/C
N/ON/C
N/O
3340 Digital input 92
3341 Dig. in-put 92
Delay 0.0 s100.0 s
1.0 s Option:7 binary inputsin slot #6(M13.6)
The input is configurableand can have differentfunctions in different units.3342 Dig. in-
put 92Relayoutput A
R0Option-dep.
R0(none)
PPM-3 parameter list 4189340672 UK Alarm list
DEIF A/S Page 49 of 144
-
8/17/2019 PPM-3 Parameter List 4189340672 UK
50/144
No. Setting Min.Max.
Factorysetting
Notes Ref. Description
3343 Dig. in-put 92
Relayoutput B
R0Option-dep.
R0(none)
3344 Dig. in-put 92
Enable OFFON
OFF
3345 Dig. in-put 92
Failclass
F1…F7 Warning(F2)
3346 Dig. in-put 92
N/O - N/C
N/ON/C
N/O
3350 Digital input 93
3351 Dig. in-
put 93
Delay 0.0 s
100.0 s
1.0 s Option:
7 binary inputsin slot #6(M13.6)