Powerware9910-P10 and 9910-P15
High Performance
High Reliability & Availability
Flexible & Configurable
Advanced Communications
Fourth-Generation Online™ topology ensures continuous, clean powerAdvanced Battery Management Plus (ABM Plus™) significantly increases battery lifeExtended Battery Modules (EBMs) prolong backup timesLoad Segments enable scheduled shutdownsTwo-in-One form factor provides versatility2U rack-mount height conserves valuable rack spaceHot-swappable batteries simplify service
Product SnapshotPower Rating: 1000 VA/700 Watt
1500 VA/1050 WattVoltage: 110-127 VacFrequency: 50/60 HzConfiguration: 2U, 19” tower or rackRuntime (in min,): Half/Full load (15/5)Input line cord: 5-15P Number of outlets: 6Options: EBM, SNMP, rack kit
and MultiServer
P10 and P15 Features
P10 and P15 ApplicationsThe P10 and P15 were specifically designed, engineered and approved for IBM applications
iSeries and AS/400pSeries and RS/6000xSeries and other eServersStorage and networking devices
9910 UPSs are ideal power protection foriSeries family of servers
9406 7025 7043 7044
P15 with i5 520 Tower
Series 9 Power ProtectionThe P10 and P15 provide double-conversion online power protection from all 9 of the most common power problems that threaten your equipment and data
Power failures High voltage spikes
Power sags Frequency variations
Power surges Switching transients
Brownouts Harmonic distortion
Line noise
Utility Load
Internal Automatic Bypass
Battery
AC to DC Rectifier
DC to AC Inverter
Bi-Directional Power Converter
Filtering
Wide input voltage rangeReduces battery usageReserves batteries for power failures--when you need maximum runtimeExtends UPS service lifeReduces battery replacement costs
EnergyShareUnder extremely poor utility conditions, P10 and P15 models take power from both the utility and batteryReduces battery usageExtends runtime and service life of the battery
P10 and P15 Fourth-Generation Online TopologyTM
Energy Share
EnergyShare range: 120-160V(combined battery and utility)
Battery Power: <120V
Battery Power: >288V
Online voltage regulation: 160-288V
(no battery power needed)
Input Voltage RangeDuring extreme brownouts, the P10 and P15 provide an extra level of protection; the UPS “shares” battery and incoming voltage to continue to provide ±3% of nominal voltage
B CABM® Technology• Doubles battery
service life by charging only when needed
• Optimizes recharge time
• Does not trickle chargeand starve the electrolyte
• Intelligent microprocessor controlled -Only true & automatic battery check (periodic, controlled discharge) for most accurate advanced failure protection
• Sleep Feature - no unnecessary battery “drain”
Compact DesignThe P10 and P15 packs superior power protection in a sleek, compact design.
19”
17”
3.5”
Informative User Interface
On Button(Start-On-Battery)
Overtemperature
Overload
Load Level/Battery LevelBypass Mode
Alarm Silence/Test Button Off Button
Battery Mode
Normal Mode (UPS On)
Site Wiring Fault
Self-Test
Replace Battery (ABM)
Note: rotate 90° for cabinet configuration
Load SegmentsPower down sequencing of Load Segments
Extends runtime for critical devicesPower up sequencing of Load Segments
Orderly power up of connected devicesScheduled on/off times
Turn off equipment for security and power conservation
Individual control of two Load Segments
No need to shut down your critical load when replacing batteries
Hot-Swappable Batteries
UPS and two EBMs
Add EBMs to extend backup time
Extended Battery Modules
Attach EBMs with simple daisy-chain connection EBM Connection
EBM #1 EBM #2
P10 Battery RuntimesBattery Runtime (in minutes)*
Standard (Std)Watts Internal Batteries +1 EBM +2 EBMs
140 37 271 546
280 19 142 278
490 9 72 156
595 6 59 124
700 5 48 104
Rack height 2 4 6
* Up to 2 EBMs can be connected to the P10. EBM runtimes include P10 internal batteries. Runtime chart provides typical information. Battery runtimes are approximate and may vary with equipment, configuration, battery age, temperature, etc.
P15 Battery RuntimesBattery Runtime (in minutes)*
Standard (Std)Watts Internal Batteries +1 EBM +2 EBMs +3 EBMs +4 EBMs
280 46 177 331 501 682
490 25 96 180 272 370
595 21 76 142 214 292
700 16 61 115 174 237
875 11 46 87 131 179
1050 8 37 70 106 144
Rack height 2 4 6 8 10* Up to 4 EBMs can be connected to the P15. EBM runtimes include P15 internal batteries. Runtime chart provides typical information. Battery runtimes are approximate and may vary with equipment, configuration, battery age, temperature, etc.
P10 and P15 Rear PanelCommunication
Port
X-Slot
Battery Connector
Power Cord with 5-15P
5-15 Receptacles
Network Transient Protector
REPO Port
REPO/Network Transient Protector
Shut down UPS remotely with REPO port; ideal for rack applications
Network Transient Protector provides protection from “back door” disturbances that travel through phone/network lines
Powerware Extensions Software for IBM Director
Seamless UPS and software integration into IBM Director Network Management System (NMS)Real time monitoring, management and alarm notification of all UPSs in the network: e.g. battery status, battery replacement, load level and metering informationAutomatically launches LanSafe and ConnectUPS Web/SNMP Card applications from within DirectorAvailable on Powerware web FREE-OF-CHARGE
Powerware Software SuiteThe industry’s most comprehensive software bundle, The PowerwareSoftware Suite, is free and included with every P10 and P15.
Software Wizard guides you through software selection and installation. In addition to multimedia demonstrations, product data sheets, and video clips, the Software Suite contains the following power management software:• LanSafe™ Network UPS shutdown and monitoring
software• PowerVision® (30-day trial version) UPS performance
analysis and monitoring software
• Foreseer® (demonstration) facility and data center management software
Power Management Software
Software ApplicationPowerware
Extensions for Application LanSafe NetWatch IBM Director
Single pSeries (serial/TTY) non-LPAR
Single pSeries (network) non-LPAR * *
Single pSeries (LPAR) *
Multiple pSeries (non-LPAR) *
Multiple pSeries (LPAR) *
IBM Director Network Device *
* Co-requisite FC 2934 ConnectUPS Web/SNMP network card.
Note: UPS for iSeries applications utilize OS/400 UPS monitoring functions.
Software ComparisonAmbient
Email/ SSL/SSH1 TemperatureApplication Monitoring Shutdown GUI SMTP Security Humidity
LanSafe Yes Yes Yes Yes / Yes No/No No/No
NetWatch - Yes - No/No No/No No/No
ConnectUPS Web/ Yes2 Yes3 Yes Yes / Yes Yes / Yes Yes / Yes4
SNMP Card (FC 2934)1SSL = Secure Sockets Layer. SSH = Secure Shell. 2Via Web Browser, LanSafe or Network Management System (e.g. IBM Director, Tivoli). 3In conjunction with NetWatch software. 4With optional FC 2938 EMP (Environmental Monitoring Probe) device attached.
Software Solution zSeries iSeries pSeries xSeries Storage Networking
LanSafe
LanSafe and ConnectUPS MultiServer card (IBM FC 2933)
NetWatch and ConnectUPS !
Web/SNMP card (IBM FC 2934) LPARs
Powerware Extensions forIBM Director
NetWatch
ConnectUPS Relay card andAS/400 cable (IBM FC 2936)!Use ConnectUPS Web/SNMP/xHub card, IBM FC 2934 to support LPAR (POWER 4 Chip Set) servers. For pSeries configurations, each LPAR needs a network connection and will install Powerware provided NetWatch or LanSafesoftware.
ConnectivityWhat you need by application
P10 and P15 CollateralAdditional information available at www.powerware.com/ibm
Select your region. Click “Products”, click “9910 Solutions” then click “Powerware pSeries” or “Powerware iSeries”
Powerware UPS Hotline for IBM1-800-925-4426
Materials availableData sheetApplication overview chartProduct presentationDocuments (manuals)