PowerSouth Lowman AC/DC Essential Voltage System.

34
PowerSouth Lowman AC/DC Essential Voltage System

Transcript of PowerSouth Lowman AC/DC Essential Voltage System.

Page 1: PowerSouth Lowman AC/DC Essential Voltage System.

PowerSouth Lowman AC/DC Essential Voltage System

Page 2: PowerSouth Lowman AC/DC Essential Voltage System.

Essential Voltage System• Original Design Weaknesses• Event Report• New Design

Page 3: PowerSouth Lowman AC/DC Essential Voltage System.

Original Design Overview

Page 4: PowerSouth Lowman AC/DC Essential Voltage System.

Original Design Weaknesses• Manual operation• Break-before-make switching• Lack of redundancy• Lack of Data/Alarms

Page 5: PowerSouth Lowman AC/DC Essential Voltage System.

480V Emergency Section• Manual breaker operation with Kirk-key interface

Page 6: PowerSouth Lowman AC/DC Essential Voltage System.

Diesel Generator• No adequate PM testing on Diesel Generator

Page 7: PowerSouth Lowman AC/DC Essential Voltage System.

Chargers/Batteries• Single point of failure with one charger

Page 8: PowerSouth Lowman AC/DC Essential Voltage System.

Inverters• Single point of failure with one inverter feeding

primary and secondary control power in some areas

Page 9: PowerSouth Lowman AC/DC Essential Voltage System.

Event Report

Page 10: PowerSouth Lowman AC/DC Essential Voltage System.

Event Recap• Normal operation• Unit 2 charger is impaired with no direct alarming

Page 11: PowerSouth Lowman AC/DC Essential Voltage System.

Event Recap (cont.)• Batteries become depleted• Switchgear relaying begins to alarm

Page 12: PowerSouth Lowman AC/DC Essential Voltage System.

Event Recap (cont.)• Standby Charger was swapped to Unit 2• DC breaker from Standby Charger tripped

numerous times

Page 13: PowerSouth Lowman AC/DC Essential Voltage System.

Event Recap (cont.)• AC Switchgear not able to transfer to station

service• No DC power • Turbine Trips and spins down without adequate

lube or seal oil supply.

Page 14: PowerSouth Lowman AC/DC Essential Voltage System.

Rotor/Bearing Damage

Page 15: PowerSouth Lowman AC/DC Essential Voltage System.

Hydrogen Seal Casing Damage

Page 16: PowerSouth Lowman AC/DC Essential Voltage System.

Need for Improvement• Safety• Reliability• Adequate feedback• Automated operation where possible

• Redundancy

Page 17: PowerSouth Lowman AC/DC Essential Voltage System.

Upgraded System Overview

Page 18: PowerSouth Lowman AC/DC Essential Voltage System.

480V Automatic Transfer

Normal Feed

Emergency Feed

Page 19: PowerSouth Lowman AC/DC Essential Voltage System.

480V Automatic Transfer Switch

Page 20: PowerSouth Lowman AC/DC Essential Voltage System.

480V Paralleling Switchgear

480V Paralleling SWGR

Page 21: PowerSouth Lowman AC/DC Essential Voltage System.

Diesel Generator/Paralleling

SwitchgearProtective Relay

Sync Indication

Unit 2 Feed

Unit 3 Feed

Diesel Gen Feed

Page 22: PowerSouth Lowman AC/DC Essential Voltage System.

350kW Diesel Generator

Page 23: PowerSouth Lowman AC/DC Essential Voltage System.

Redundant Charging with Standby

Utility Fed Charger

Emer. Fed Charger

Unit 2 Batteries

Standby

Page 24: PowerSouth Lowman AC/DC Essential Voltage System.

Battery Chargers

Unit 3 Chargers

Unit 2 ChargersStandby

Charger

Page 25: PowerSouth Lowman AC/DC Essential Voltage System.

Batteries

Unit 3 Batteries

Standby Batteries

Unit 2 Batteries

Page 26: PowerSouth Lowman AC/DC Essential Voltage System.

DC Switchboard/Distribution

Page 27: PowerSouth Lowman AC/DC Essential Voltage System.

DC Switchboard

Unit 2 Battery Breaker

2A Charger Feed2B Charger Feed

Page 28: PowerSouth Lowman AC/DC Essential Voltage System.

Dual Inverters

Inverter 2A

Inverter 2B

Page 29: PowerSouth Lowman AC/DC Essential Voltage System.

Dual Inverters

Inverter 2A

Inverter 2B

Inverter3A

Inverter3B

Page 30: PowerSouth Lowman AC/DC Essential Voltage System.

120V Essential Power Transformers

120V Essential Power Transformer 2A

120V Essential Power Transformer 2B

Page 31: PowerSouth Lowman AC/DC Essential Voltage System.

Control Screen

Page 32: PowerSouth Lowman AC/DC Essential Voltage System.

DC Voltage Visual

Page 33: PowerSouth Lowman AC/DC Essential Voltage System.

Critical Event Response

Open

Page 34: PowerSouth Lowman AC/DC Essential Voltage System.

Questions/Comments?