CASE STUDY
PARTIAL DISCHARGE TEST
FOR MOTOR & GENERATOR
![Page 2: PowerPD Case Studies for Motor & Generator](https://reader036.fdocuments.in/reader036/viewer/2022081502/552d3ff34a7959035a8b467d/html5/thumbnails/2.jpg)
Case Study 6Rotating machine (condensing), US
![Page 3: PowerPD Case Studies for Motor & Generator](https://reader036.fdocuments.in/reader036/viewer/2022081502/552d3ff34a7959035a8b467d/html5/thumbnails/3.jpg)
The data was collected three months before the condensing rotating machine failed
![Page 4: PowerPD Case Studies for Motor & Generator](https://reader036.fdocuments.in/reader036/viewer/2022081502/552d3ff34a7959035a8b467d/html5/thumbnails/4.jpg)
Fault 1 (on “Back end”)
![Page 5: PowerPD Case Studies for Motor & Generator](https://reader036.fdocuments.in/reader036/viewer/2022081502/552d3ff34a7959035a8b467d/html5/thumbnails/5.jpg)
Fault 2 (on “back end”)
![Page 6: PowerPD Case Studies for Motor & Generator](https://reader036.fdocuments.in/reader036/viewer/2022081502/552d3ff34a7959035a8b467d/html5/thumbnails/6.jpg)
Fault 3 (on “front end”)
![Page 7: PowerPD Case Studies for Motor & Generator](https://reader036.fdocuments.in/reader036/viewer/2022081502/552d3ff34a7959035a8b467d/html5/thumbnails/7.jpg)
45 MVA Generator in Thailand
![Page 8: PowerPD Case Studies for Motor & Generator](https://reader036.fdocuments.in/reader036/viewer/2022081502/552d3ff34a7959035a8b467d/html5/thumbnails/8.jpg)
![Page 9: PowerPD Case Studies for Motor & Generator](https://reader036.fdocuments.in/reader036/viewer/2022081502/552d3ff34a7959035a8b467d/html5/thumbnails/9.jpg)
Internal Inspection Findings
![Page 10: PowerPD Case Studies for Motor & Generator](https://reader036.fdocuments.in/reader036/viewer/2022081502/552d3ff34a7959035a8b467d/html5/thumbnails/10.jpg)
??? MVA G t??? MVA Generator in Thailand
![Page 11: PowerPD Case Studies for Motor & Generator](https://reader036.fdocuments.in/reader036/viewer/2022081502/552d3ff34a7959035a8b467d/html5/thumbnails/11.jpg)
![Page 12: PowerPD Case Studies for Motor & Generator](https://reader036.fdocuments.in/reader036/viewer/2022081502/552d3ff34a7959035a8b467d/html5/thumbnails/12.jpg)
15 MVA Generator in Thailand
![Page 13: PowerPD Case Studies for Motor & Generator](https://reader036.fdocuments.in/reader036/viewer/2022081502/552d3ff34a7959035a8b467d/html5/thumbnails/13.jpg)
45 MVA Generator in Thailand
![Page 14: PowerPD Case Studies for Motor & Generator](https://reader036.fdocuments.in/reader036/viewer/2022081502/552d3ff34a7959035a8b467d/html5/thumbnails/14.jpg)
126.6 MVA Generator in ThailandThailand
![Page 15: PowerPD Case Studies for Motor & Generator](https://reader036.fdocuments.in/reader036/viewer/2022081502/552d3ff34a7959035a8b467d/html5/thumbnails/15.jpg)
148 MW Generator in US
![Page 16: PowerPD Case Studies for Motor & Generator](https://reader036.fdocuments.in/reader036/viewer/2022081502/552d3ff34a7959035a8b467d/html5/thumbnails/16.jpg)
Case Study 7PD source from inside of insulation
![Page 17: PowerPD Case Studies for Motor & Generator](https://reader036.fdocuments.in/reader036/viewer/2022081502/552d3ff34a7959035a8b467d/html5/thumbnails/17.jpg)
Internal Inspection Findings
![Page 18: PowerPD Case Studies for Motor & Generator](https://reader036.fdocuments.in/reader036/viewer/2022081502/552d3ff34a7959035a8b467d/html5/thumbnails/18.jpg)
Case Study 8Signal (PD and 6 pulse) was collected from HFCT installed on the tank ground of
Transformer. This signal(PD and 6 pulse) transmitted from the generator side.
![Page 19: PowerPD Case Studies for Motor & Generator](https://reader036.fdocuments.in/reader036/viewer/2022081502/552d3ff34a7959035a8b467d/html5/thumbnails/19.jpg)
6 pulse coming from Generator side
![Page 20: PowerPD Case Studies for Motor & Generator](https://reader036.fdocuments.in/reader036/viewer/2022081502/552d3ff34a7959035a8b467d/html5/thumbnails/20.jpg)
Inspection Findings
![Page 21: PowerPD Case Studies for Motor & Generator](https://reader036.fdocuments.in/reader036/viewer/2022081502/552d3ff34a7959035a8b467d/html5/thumbnails/21.jpg)
Case Study 9Warning level of PD was collected from HFCT installed on the tankWarning level of PD was collected from HFCT installed on the tank ground of Transformer. This PD transmitted from the generator and shot down the generator for maintenanceshot down the generator for maintenance
![Page 22: PowerPD Case Studies for Motor & Generator](https://reader036.fdocuments.in/reader036/viewer/2022081502/552d3ff34a7959035a8b467d/html5/thumbnails/22.jpg)
PD burst collected from HFCT
![Page 23: PowerPD Case Studies for Motor & Generator](https://reader036.fdocuments.in/reader036/viewer/2022081502/552d3ff34a7959035a8b467d/html5/thumbnails/23.jpg)
Inspection Findings
After serviceAfter service
![Page 24: PowerPD Case Studies for Motor & Generator](https://reader036.fdocuments.in/reader036/viewer/2022081502/552d3ff34a7959035a8b467d/html5/thumbnails/24.jpg)
Case Study 10230 KV 300 MVA @ Thailand@
![Page 25: PowerPD Case Studies for Motor & Generator](https://reader036.fdocuments.in/reader036/viewer/2022081502/552d3ff34a7959035a8b467d/html5/thumbnails/25.jpg)
PD burst collected from sensor3(yellow)
![Page 26: PowerPD Case Studies for Motor & Generator](https://reader036.fdocuments.in/reader036/viewer/2022081502/552d3ff34a7959035a8b467d/html5/thumbnails/26.jpg)
Internal Inspection Finding
![Page 27: PowerPD Case Studies for Motor & Generator](https://reader036.fdocuments.in/reader036/viewer/2022081502/552d3ff34a7959035a8b467d/html5/thumbnails/27.jpg)
Case Study 11500 KV 500MVA @ Philippines500 KV 500MVA @ Philippines
![Page 28: PowerPD Case Studies for Motor & Generator](https://reader036.fdocuments.in/reader036/viewer/2022081502/552d3ff34a7959035a8b467d/html5/thumbnails/28.jpg)
PD collected from AE and HFCT
![Page 29: PowerPD Case Studies for Motor & Generator](https://reader036.fdocuments.in/reader036/viewer/2022081502/552d3ff34a7959035a8b467d/html5/thumbnails/29.jpg)
Internal Inspection Finding: Burnt cable from 500kv winding to K pic2 3Burnt cable from 500kv winding to K_pic2.3
![Page 30: PowerPD Case Studies for Motor & Generator](https://reader036.fdocuments.in/reader036/viewer/2022081502/552d3ff34a7959035a8b467d/html5/thumbnails/30.jpg)
Case Study 12 Transformer Test Results:
• TTR Test OK• Doble Test OKDoble Test OK• Doble SFR Test inconclusive• ABB DFR Test:
– Indicates a problem between H&X Winding - Tertiary• Final DGA Test –
Acetylene 3 ppmMethane 1259 ppmEthane 163 ppmEthylene 7 ppmHydrogen 27123 ppm
• ABB Internal Inspection – B phase core shifted due to through f lt / i di t l ifaults/winding telescoping
![Page 31: PowerPD Case Studies for Motor & Generator](https://reader036.fdocuments.in/reader036/viewer/2022081502/552d3ff34a7959035a8b467d/html5/thumbnails/31.jpg)
Transformer test with TP500A @ US
![Page 32: PowerPD Case Studies for Motor & Generator](https://reader036.fdocuments.in/reader036/viewer/2022081502/552d3ff34a7959035a8b467d/html5/thumbnails/32.jpg)
Internal Inspection Findings
E id f h ti b BØ C C li D tEvidence of heating above BØ Core Cooling Ducts
![Page 33: PowerPD Case Studies for Motor & Generator](https://reader036.fdocuments.in/reader036/viewer/2022081502/552d3ff34a7959035a8b467d/html5/thumbnails/33.jpg)
Internal Inspection Findings
Shifted Core over BØ:
Shifted approx ¾” vertically & ½” Horizontally
![Page 34: PowerPD Case Studies for Motor & Generator](https://reader036.fdocuments.in/reader036/viewer/2022081502/552d3ff34a7959035a8b467d/html5/thumbnails/34.jpg)
Case Study 13PD source between winding (Data collected with TP500A)
![Page 35: PowerPD Case Studies for Motor & Generator](https://reader036.fdocuments.in/reader036/viewer/2022081502/552d3ff34a7959035a8b467d/html5/thumbnails/35.jpg)
Internal Inspection Findings
![Page 36: PowerPD Case Studies for Motor & Generator](https://reader036.fdocuments.in/reader036/viewer/2022081502/552d3ff34a7959035a8b467d/html5/thumbnails/36.jpg)
Case Study 14 Transformer Test Results:
• Final DGA TestFinal DGA Test Methane 532 ppmEthane 363 ppmEthane 363 ppmEthylene 13 ppmHydrogen 1,140 ppm (From last year 08 Hydrogen was at 964)y g , pp ( y y g )
![Page 37: PowerPD Case Studies for Motor & Generator](https://reader036.fdocuments.in/reader036/viewer/2022081502/552d3ff34a7959035a8b467d/html5/thumbnails/37.jpg)
PD source from inside of insulation (Data collected with TP500A)
![Page 38: PowerPD Case Studies for Motor & Generator](https://reader036.fdocuments.in/reader036/viewer/2022081502/552d3ff34a7959035a8b467d/html5/thumbnails/38.jpg)
Internal Inspection Findings
![Page 39: PowerPD Case Studies for Motor & Generator](https://reader036.fdocuments.in/reader036/viewer/2022081502/552d3ff34a7959035a8b467d/html5/thumbnails/39.jpg)
Case Study 15 220 KV GIS Test Results: Data collected with iGMS P8220 KV GIS Test Results: Data collected with iGMS_P8
Data from UHF1
Data from UHF2
Data from HFCT
![Page 40: PowerPD Case Studies for Motor & Generator](https://reader036.fdocuments.in/reader036/viewer/2022081502/552d3ff34a7959035a8b467d/html5/thumbnails/40.jpg)
Case Study 16 220 KV GIS Test Results: Data collected with iGMS_P8_
Data from UHF 1 Data from UHF 2 Data from UHF 3 Data from UHF 4