Page 1: Power Transducer User’s Guide · 2018-12-26 · Reference Charts and Information A. Transducer output calculations ... Resistance is represented by the letter symbol “R.” One

Power TransducerUser’s Guide

Volume 1

Page 2: Power Transducer User’s Guide · 2018-12-26 · Reference Charts and Information A. Transducer output calculations ... Resistance is represented by the letter symbol “R.” One

© 1991 Moore Industries-International, Inc.

™Power Transducer User's Guide

Volume 1

Applying Power Transducers

Notes

Page 3: Power Transducer User’s Guide · 2018-12-26 · Reference Charts and Information A. Transducer output calculations ... Resistance is represented by the letter symbol “R.” One

© 1991 Moore Industries-International, Inc.

Volume 1

I. Why Monitor Power? ................................................................. 1

II. Beginning Definitions ................................................................ 3

III. Basic Concepts of AC Power ................................................... 5

IV. Common AC Power Systems .................................................. 11

V. Monitoring Common AC Power Systems ................................ 15

VI. Taking Watt and VAR Measurements ..................................... 19

VII. Glossary .................................................................................. 25

VIII. Reference Charts and InformationA. Transducer output calculations ............................................ 33B. Full-load motor currents ........................................................ 35C. Nameplate voltage ratings of standard induction motors .... 36D. Nominal system voltages ..................................................... 37

IX. Power Transducers available from Moore Industries ............. 39

Page

Page 40

Notes

Specifications subject to change

Page 4: Power Transducer User’s Guide · 2018-12-26 · Reference Charts and Information A. Transducer output calculations ... Resistance is represented by the letter symbol “R.” One

© 1991 Moore Industries-International, Inc.

I. Why Monitor Power?With ac power consumption and measurement drawing ever-moreattention throughout the process industries, an understanding ofbasic ac parameters becomes increasingly important.

This simple reference guide uses illustrations and simple defini-tions to explain the basics of ac power and its uses in the processindustries. This comparison shows the relationship between theterms used in measuring electrical current and standard processflow concepts:

Electrical Term Flow Term

Current FlowVoltage Pressure

Resistance Pressure Drop

Keeping this simple analogy in mind should help you understandand apply the basic principles needed to use power transducers.

For help in controlling your ac power usage, or ordering powertransducers, please call your local representative. In addition, ourhelpful Sales Engineers are available during business hours. Pleaseconsult the back of this booklet for the phone number of the officenearest you.

C. Nameplate Voltage Ratings of StandardInduction Motors

Nominal System Voltage Nameplate Voltage

Single-Phase Motors:120 ........................................................... 115240 ........................................................... 230

Three-Phase Motors:208 ........................................................... 200240 ........................................................... 230480 ........................................................... 460600 ........................................................... 5752400 ....................................................... 23004160 ....................................................... 40004800 ....................................................... 46006900 ....................................................... 660013800 ................................................... 13200

Data taken from IEEE Std. 141-1976

Reference Charts and Information

Page 36 Page 1

Page 5: Power Transducer User’s Guide · 2018-12-26 · Reference Charts and Information A. Transducer output calculations ... Resistance is represented by the letter symbol “R.” One

© 1991 Moore Industries-International, Inc.

II. Beginning DefinitionsPrior to reading further in this booklet, please familiarize yourselfwith these basic terms of electricity and ac power measurement.

Ampere —The basic unit used to measure current, often abbrevi-ated as “amp” or “A.” It equals a unit of electrical current or the rateof flow of electrons. One volt across one ohm of resistance resultsin current flow of one ampere.Current —The movement or flow of electrons through a conductor,represented by the letter symbol “I.”Voltage —The force causing current to flow through a conductor,represented by the letter symbol “E.” The unit of measure is thevolt, or “V.” One volt equals the force required to produce a currentflow of one ampere through a resistance of one ohm.Element —The portion of a transducer which senses one input eachof voltage and current.Impedance —As current flows through a conductor it encountersforce which blocks its path. The force consists of passive compo-nents (resistance) and reactive components (inductive andcapacitive reactance.) Impedance is measured in ohms and thesymbol is “Z.”Resistance —Component of impedance due to passive elements ofthe load. Resistance is represented by the letter symbol “R.” Oneunit of resistance is known as an ohm.Reactance —Component of impedance due to active elements ofthe load. Symbol is “X.”Ohm—A single ohm equals the amount of impedance that will limitthe current in a conductor to one ampere when one volt is applied tothe conductor, represented by the Greek letter “Ω.”Frequency —The number of times that the variations of an alternat-ing current represented by the sine waveform are repeated duringone second of time, expressed in hertz or “Hz.” One hertz equalsone cycle per second.

Custom Transducer CalibrationsIf we use the same transducers and transformers as in example 1,and say that the customer has a meter that is already scaled for 0-60,000 watts, we have to work in reverse to determine the appropri-ate calibration point for the transducer. We would take the 60,000watts and divide this by the transformer ratios:

In order to get 60,000 watts full scale with the customer’s transform-ers, we would have to calibrate the transducer to 375 watts perelement.

Page 34 Page 3

Reference Charts and Information

60,000

480

120

100

52 ELEMENTS

375 WATTS/ELEMENTX

=X

Page 6: Power Transducer User’s Guide · 2018-12-26 · Reference Charts and Information A. Transducer output calculations ... Resistance is represented by the letter symbol “R.” One

© 1991 Moore Industries-International, Inc.

II. Beginning DefinitionsPrior to reading further in this booklet, please familiarize yourselfwith these basic terms of electricity and ac power measurement.

Ampere —The basic unit used to measure current, often abbrevi-ated as “amp” or “A.” It equals a unit of electrical current or the rateof flow of electrons. One volt across one ohm of resistance resultsin current flow of one ampere.Current —The movement or flow of electrons through a conductor,represented by the letter symbol “I.”Voltage —The force causing current to flow through a conductor,represented by the letter symbol “E.” The unit of measure is thevolt, or “V.” One volt equals the force required to produce a currentflow of one ampere through a resistance of one ohm.Element —The portion of a transducer which senses one input eachof voltage and current.Impedance —As current flows through a conductor it encountersforce which blocks its path. The force consists of passive compo-nents (resistance) and reactive components (inductive andcapacitive reactance.) Impedance is measured in ohms and thesymbol is “Z.”Resistance —Component of impedance due to passive elements ofthe load. Resistance is represented by the letter symbol “R.” Oneunit of resistance is known as an ohm.Reactance —Component of impedance due to active elements ofthe load. Symbol is “X.”Ohm—A single ohm equals the amount of impedance that will limitthe current in a conductor to one ampere when one volt is applied tothe conductor, represented by the Greek letter “Ω.”Frequency —The number of times that the variations of an alternat-ing current represented by the sine waveform are repeated duringone second of time, expressed in hertz or “Hz.” One hertz equalsone cycle per second.

Custom Transducer CalibrationsIf we use the same transducers and transformers as in example 1,and say that the customer has a meter that is already scaled for 0-60,000 watts, we have to work in reverse to determine the appropri-ate calibration point for the transducer. We would take the 60,000watts and divide this by the transformer ratios:

In order to get 60,000 watts full scale with the customer’s transform-ers, we would have to calibrate the transducer to 375 watts perelement.

Page 34 Page 3

Reference Charts and Information

60,000

480

120

100

52 ELEMENTS

375 WATTS/ELEMENTX

=X

Page 7: Power Transducer User’s Guide · 2018-12-26 · Reference Charts and Information A. Transducer output calculations ... Resistance is represented by the letter symbol “R.” One

© 1991 Moore Industries-International, Inc.

III. Basic Concepts of Ac PowerThis material should give non-electrical engineers a feel for some ofthe basic characteristics of electrical systems. Ideally, this informa-tion will help you implement and work with an energy monitoring andmanagement system.

Power—Direct Current CircuitIn a direct current circuit voltage and current are constant. Thereare only resistive loads. The relationship between voltage, currentand resistance is E = IR. Power is defined P = EI = I2R. A watt isone volt times one amp. 1W = (1V) (1A).

Power—Alternating Current CircuitAlternating current is created by rotating a coil of conductive wirethrough a magnetic field (Drawing 1). Drawing 2 represents theresults of the rotating action through the magnetic field. In an accircuit, voltage and current vary in amplitude in a sinusoidal fashion.

Drawing 1. Typical ac motor

Glossary

Volt-ampere-reactive-hour —The measure of the number of VAR’sused in one hour. VAR-hr and whr are frequently used to calculateaverage power factor during a billing period.Voltage (V) —The force which causes current to flow through aconductor. One volt equals the force required to produce a currentflow of one ampere through a resistance of one ohm.

Watt (W)—A measure of real power. The unit of electric powerrequired to do work at the rate of one joule per second. It is thepower expended when one ampere of direct current flows through aresistance of one ohm.Watt demand —The usual demand billing factor where peak aver-age demand is measured in watts or real power.Watt-hour (whr) —A unit of electrical work indicating the expendi-ture of one watt of electrical power for one hour.Wattmeter —An instrument for measuring the real power in anelectric circuit. Its scale is usually graduated in watts, kilowatts, ormegawatts.

Page 32 Page 5

Slipring

Brush

Rotating Conductor

Directionof rotation

UniformMagneticField

Load

Page 8: Power Transducer User’s Guide · 2018-12-26 · Reference Charts and Information A. Transducer output calculations ... Resistance is represented by the letter symbol “R.” One

© 1991 Moore Industries-International, Inc.

Drawing 2. One rotation of an ac motor

Resistive LoadWhen this coil is wired to a purely resistive load, the voltage and theresulting current occur simultaneously. In other words, they arerotating “in phase” (Drawing 3).

Drawing 3. Resistive Load

Sliding demand interval —A method of calculating average de-mand by averaging the demand over several successive short timeintervals, advancing one short time interval each time. Updatingaverage demand at short time intervals gives the utility a muchbetter measure of true demand and makes it difficult for the cus-tomer to obscure high short-term loads.Subsidiary billing factors —Secondary billing factors in a rateschedule, including such things as fuel-adjustment costs, multiplemetering points, interruptible service provisions, and transformerownership benefits.

Time-dependent clauses —Rate schedule provisions which varyrates depending on the time of day or time of year when energy isconsumed. Frequently these clauses cover both demand andenergy charges. There is money to be saved by operating highloads and consuming high amounts of energy during off-peakperiods when rates are lower.True power —Same as real power.

Unbalanced loads —A situation existing in an alternating currentsystem using more than two current-carrying conductors whereuneven loading of the phases results in unequal current in thecurrent-carrying conductors.

Volt-ampere (VA) —The unit of apparent power. It equals volts xamperes, regardless of the power factor.Volt-ampere demand —Where peak average demand is measuredin volt-amperes rather than watts. In this case the customer isautomatically penalized for operating at any power factor less thanunity.Volt-ampere-reactive (VAR) —The unit of reactive power, asopposed to real power, in watts. One VAR is equal to one reactivevolt-ampere.Volt-ampere-reactive demand —Measuring VAR demand is amethod of penalizing for poor power factor. Multiplying by somerate ($/VAR) penalizes for operating at any power less than unity.

Frequently there is a quantity of “free” VAR which is determinedas some percentage of the peak average watt demand. All excessVAR over this quantity is then billed at this $/VAR rate. Effectively,this penalizes for operating below some specified power factor lessthan unity.

Page 6

Basic Concepts of Ac Power Glossary

Page 31

E

I

E

0

One Rotation–

+

360°

Page 9: Power Transducer User’s Guide · 2018-12-26 · Reference Charts and Information A. Transducer output calculations ... Resistance is represented by the letter symbol “R.” One

© 1991 Moore Industries-International, Inc.

Basic Concepts of Ac Power

The power is defined as P = EI cosØ, where Ø is the phase anglebetween the voltage and current. Here (Drawing 4) the angle iszero. CosØ = 1, so P = EI and alternates between some positivevalue and zero.

Drawing 4 shows instantaneous values of the voltage, current,and power. The quantities used in the equations and in the applica-tions are the RMS (root mean squared) values.

Drawing 4. Current, voltage and power values of a resistive load

Inductive LoadWhen the applied load is a pure inductance, the current will lag thevoltage by 90°. Phase angleØ = 90°. The resulting power: P = EIcos(–90°) = 0. The product of E and I varies between equalamounts of positive and negative values resulting in an RMS valueof zero power (Drawing 5).

Drawing 5. Inductive Load

Glossary

respective watt-hour meter potential coil by 60°. This is generallyaccomplished by cross-phasing, thus eliminating the need for aphase-shifting transformer. The VAR-hr information can be calcu-lated as follows: VAR-hr= (2Q hr - whr)/ sqrt3

Ratchet clause —A rate schedule clause which states that billingdemand may be based on current month peak average demand oron historical peak average demand, depending on relative magni-tude.

Usually the historical period is the past eleven months, althoughit can be for the life of the contract. Billing demand is either thecurrent month’s peak average demand or some percentage (75% istypical) of the highest historical peak average demand, dependingon which is largest.Reactance —The opposition to the flow of alternating current.Capacitive reactance is the opposition offered by capacitors andinductive reactance is the opposition offered by an inductive load.Both reactances are measured in ohms.Reactive power —Also called a watt-less power and measured involt-amperes-reactive. Reactive power increases with decreasingpower factor and is the component of apparent power which doesno real work in a system.Real power —The component of apparent power that representstrue work in an alternating current circuit. It is expressed in wattsand is equal to the apparent power times the power factor.Resistance —The property of a substance which impedes currentflow and results in the dissipation of power in the form of heat. Theunit of resistance is the ohm. One ohm is the resistance throughwhich a difference of potential of one volt will produce a current ofone ampere.Revenue meter —A meter used by a utility to generate billinginformation. Many types of meters fall in this category dependingon the rate structure.Root mean square (RMS) —The effective value of alternatingcurrent or voltage. The RMS value of voltage and current can beused for the accurate computation of power in watts. The RMSvalue is the same value as if continuous direct current were appliedto a pure resistance.

Single-phase —An alternating current circuit in which only onephase of current is available in a two-conductor or three-conductorsystem where the load lines are 0° or 180° out of phase.

Page 30 Page 7

E

360°

I

P

ØPhaseAngle

E

Ø = 0

P

I

360°

Page 10: Power Transducer User’s Guide · 2018-12-26 · Reference Charts and Information A. Transducer output calculations ... Resistance is represented by the letter symbol “R.” One

© 1991 Moore Industries-International, Inc.

Capacitive LoadWhen the applied load is a pure capacitance, the current will leadthe voltage by 90°. Phase angle = 90°. P = EI cos90 = 0. Again,RMS power is zero (Drawing 6).

Drawing 6. Capacitive load

Real LoadsIn actual practice loads are never purely resistive, inductive, orcapacitive. For an example, let’s consider a circuit whose loadsresult in a small amount of inductive reactance. In this example(Drawing 7) the current lags the voltage by 60°.

Drawing 7. Inductive and reactive loads

Basic Concepts of Ac Power Glossary

Peak average demand —The highest average load over a utility-specified time interval during a billing period. If there is no ratchetclause in the rate schedule then the peak average demand is alsothe billing demand.Polyphase —Having or utilizing several phases. A polyphasealternating current power circuit has several phases of alternatingcurrent with a fixed phase angle between phases.Potential transformer (PT) —An instrument transformer of which theprimary winding is connected in parallel with the circuit whosevoltage is to be measured or controlled. PT’s normally are used tostep down high voltage potentials to levels acceptable to measuringinstruments.Potential transformer ratio —The ratio of primary voltage dividedby secondary voltage.Power demand controllers —Control devices designed to minimizeand level average demand by maintaining it below some pre-selected level. This is normally accomplished by shedding andrestoring discretionary loads. There are many basic principles ofoperation of power demand controllers.Power factor —The ratio of real power (in watts) of an alternatingcurrent circuit to the apparent power in volt-amperes. Also thecosine of the phase angle between the voltage applied to a loadand the current passing through it.Power factor correction —Steps taken to raise the power factor bybringing the current more nearly in phase with the applied voltage.Most frequently this consists of increasing the lagging power factorof inductive circuits by adding capacitance.Power factor penalty —The charge utilities impose for operating atpower factors below some rate-schedule-specified level. This levelranges from a lagging power factor of 0.80 to unity. Utilities calcu-late power factor penalties in countless ways.Pulse initiator —An assemblage added to a revenue meter whichgenerates pulses proportional to meter disk rotation. Each pulserepresents a discrete quantity of energy consumed. Most frequentlythe pulses are generated photoelectrically and output throughmercury-wetted relays.

Q—A phantom quantity used by power companies to calculate volt-ampere-reactive (VAR) when there are both leading and laggingpower factors. A Q-hour meter will determine VAR-hr’s when thepower factors vary from 30° leading to 90° lagging.Q-hour meter —Similar to a watt-hour meter except that the voltageapplied to each potential coil lags the voltage supplied to the

Page 8 Page 29

P

ØPhaseAngle

360°

I E

E

I

360°180°

P

Average Power

Page 11: Power Transducer User’s Guide · 2018-12-26 · Reference Charts and Information A. Transducer output calculations ... Resistance is represented by the letter symbol “R.” One

© 1991 Moore Industries-International, Inc.

Drawing 7 shows that there is more positive power than negativepower, so the RMS value will be positive. P = EI cos60° = EI(0.5).

Real PowerSo far when we have referred to power we have meant useful or realpower, or power which does work. Real power = EI cosØ = I2R =I2ZcosØ. It is expressed in units of watts (watts = volts x amps xcosØ).

Apparent powerApparent power is the product of the voltage and current withoutregard to the applied load or the phase angle. Its measured valueis called “volt-amps” or VA. When a real world load is applied to thecircuit a combination of real power and reactive power results.

Reactive PowerReactive power is the result of the net reactance in the circuit.Rather than doing useful work, reactive power is stored in themagnetic and electric fields of the inductance and capacitance,then returned to the circuit. The unit for reactive power is VAR forvolt-amps-reactive. Reactive power = EIsinØ = I2ZsinØ.

Power TriangleA convenient method to display the relationship between apparent,reactive, and real power and the phase angle is with the powertriangle. The lengths of the sides of the triangle correspond to therelative values of the respective parameters.

You can easily see that if the phase angle is zero, then the VARs are

Basic Concepts of Ac Power

Initiator pulses —Electrical impulses generated by pulse-initiatormechanisms installed in utility revenue meters. Each pulse indi-cates the consumption of a specific number of watts. These pulsescan be used to measure energy consumption and demand.Installed load—Equivalent to connected load.

Joule —Unit of measure. One joule of work is accomplished when avoltage of one volt causes one coulomb of electrons to pass througha circuit.

Kilowatt-hour (kwhr) —A unit of electrical measurement indicatingthe expenditure of 1,000 watts for one hour. Higher quantities areexpressed in megawatt hours, or the expenditure of one millionwatts for one hour.

Lagging current —The current flowing in a circuit which is mostlyinductive. If a circuit contains only inductance the current lags theapplied voltage by 90°. Lagging current means lagging powerfactor of less than unity.Leading current —The current flowing in a circuit which is mostlycapacitive. If a circuit contains only capacitance the current leadsthe applied voltage by 90°. Leading current means leading powerfactor of less than unity.Load —Any device or circuit which consumes power in an electricalsystem.Load restoring —The energization of loads that were previouslyremoved from the line to limit the load and control demand level.Load shedding —The removal of loads from the line to limit loadand control demand level.

Neutral —The conductor chosen as the return path for the currentfrom the load to the source in power measurement procedures. Theneutral is frequently, but not necessarily, grounded.

Ohm—The unit of electrical resistance. One ohm is the value ofresistance through which a potential difference of one volt willmaintain a current flow of one ampere.Ohms’ Law —The voltage across an element of a direct currentcircuit is equal to the current in amperes through the elementmultiplied by the resistance of the element in ohms.

Glossary

Page 28 Page 9

Apparent Power(VA)

Reactive Power(VARs)

Real Power (watts)

Phase Angle (ø)

Page 12: Power Transducer User’s Guide · 2018-12-26 · Reference Charts and Information A. Transducer output calculations ... Resistance is represented by the letter symbol “R.” One

© 1991 Moore Industries-International, Inc.

zero and apparent power = real power.IV. Common Ac Power SystemsAc power systems offer a number of configurations for using power.In most instances, you will encounter the four arrangements de-scribed in this section.

Single-Phase Two-WireThe most recognizable ac power system is the single-phase two-wire system. This configuration provides power within your home foroperating domestic appliances like toasters and refrigerators.

The voltage on this type of circuit is measured and written as aline to line value. This illustration shows a 120 volt system. Measur-ing power on this system requires one voltage and one currentmeasurement, or a one element transducer.

Single-Phase Three-WireThis type of system provides electricity to homes in the UnitedStates and you will rarely encounter it in an industrial situation. Thetwo wires and neutral leg comprise a single phase system. Thissystem can be monitored with either a 1-1/2 or two element trans-ducer so that the voltage and current on each phase may bemeasured.

Contract load capacity —A load capacity contracted with a utilityand related to connected load. The minimum monthly demandcharge is sometimes established by applying the demand rate tosome specified percentage of the contracted capacity.Coulomb —The unit of electric charge equal to the quantity ofelectricity transferred by a current of one ampere in one second.Current Transformer (CT) —An instrument transformer, intended formeasuring or control purposes, designed to have its primarywinding connected in series with a conductor carrying the current tobe measured or controlled. Also see clamp-on CT, where theconductor itself acts as the primary. CT’s step down high currentsto lower values which can be used as input signals to measuringinstruments. They must be used with caution.Current transformer ratio –The ratio of primary amperes divided bysecondary amperes.

Demand —A measure of the customer load connected to theelectrical power system at any given time. Units are usually watts orvolt-amperes.Demand-hours —The equivalent number of hours in a month duringwhich the peak average demand is fully utilized. In other words, ifenergy consumption for the current month is X kwhr and the peakaverage demand is Y kw, then the demand-hours is equal to X/Yhours.

The higher the number of demand-hours the better the demandleveling situation and the more efficiently demand is being used.Many rate schedules have demand-hour based energy rate breakswhere the higher the demand-hour figure the lower the energyconsumption rate in $/kwhr.Demand interval —Demand charges are based on peak averagedemand over a utility-specified time interval, not on the instantane-ous demand (or connected load) at any given moment. This periodof time is called the demand interval. Demand intervals typicallyrange from 15, 20, to 30 minutes, although they can drop as low afive minutes.Demand-utilization efficiency —Related to demand-hours andreally a measure of how successful demand leveling procedureshave been. Calculated by dividing demand hours by 720, thenumber of hours in a 30 day billing period. Although demand-utilization efficiency heavily depends on the type of facility, ingeneral an efficiency of 50% is considered average, 40% and lowerpoor, and 60% and higher good.

Glossary

Page 26 Page 11

N

120 VAC

120 VAC

240 VAC

L1

L2

120 VAC

L1

L2

Page 13: Power Transducer User’s Guide · 2018-12-26 · Reference Charts and Information A. Transducer output calculations ... Resistance is represented by the letter symbol “R.” One

© 1991 Moore Industries-International, Inc.

Three-Phase Three-WireMost industrial motors and other equipment within the processindustries operate with this type of system, commonly called a deltasystem.

The voltage values are expressed as line to line values becauseno neutral is present. Monitoring this type of system requires a two-element transducer.

Three-Phase Four-WireYou will find this type of system, consisting of three wires and aneutral, providing the entrance power to an industrial building.Common names for it include “wye” or “Y connected.”

Because the system has a neutral leg the voltages may bemeasured line to line or line to neutral. The proper description ofthis circuit uses both values (i.e. 208Y/120). Although commonlyonly the first value is used (208) for the purpose of power measure-ment we must use the line to neutral value (120ac)

Common Ac Power Systems

Page 12 Page 25

VII. Glossary

Ampere —A unit of electrical current or rate of flow of electrons.One volt across one ohm of resistance causes a current flow of oneampere. A flow of one coulomb per second equals one ampere.Apparent Power —The product of voltage and current in a circuit inwhich the two reach their peaks at different times, or, in other words,there is a phase angle between voltage and current. Units are VA.

Balanced load —An alternating current power system consisting ofmore than two current-carrying conductors in which these current-carrying conductors all carry the same current.Billing demand —The demand level which a utility uses to calculatethe demand charges on the current month’s bill. If the rate sched-ule includes a ratchet clause or minimum demand charge, billingdemand may or may not be the actual average demand for thecurrent month.Burden —The electrical load an instrument or meter places on acurrent or potential transformer. All current and potential transform-ers have a rated burden which should not be exceeded or thetransformer accuracy will deteriorate.

Capacitor —A device consisting essentially of two conductingsurfaces separated by an insulating material or dielectric such asair, paper, mica, plastic, film, or oil. A capacitor stores electricalenergy, blocks the flow of direct current, and permits the flow ofalternating current to a degree dependent upon the capacitanceand frequency.Capacitive Reactance —Component of impedance due to capaci-tance. Symbol is “XC.”Clamp-on CT —A current transformer which clamps around acurrent-carrying conductor so that the conductor does not have tobe opened for insertion of the transformer primary. Particularlysuited for making energy surveys where current must be sensed atmany points for relatively short periods.Connected load —The total load which a customer can impose onthe electrical system if everything is connected at one time. Con-nected load can be measured in horsepower, watts, or volt-am-peres. Some rate schedules establish a minimum demand chargeby imposing a fee per unit of connected load.

208 VAC

L1

N

L2

L3

120 VAC

120 VAC120 VAC

L1

L2

L3

480VAC

480 VAC480 VAC

Page 14: Power Transducer User’s Guide · 2018-12-26 · Reference Charts and Information A. Transducer output calculations ... Resistance is represented by the letter symbol “R.” One

© 1991 Moore Industries-International, Inc.

In this example, 208 volts is the line to line value and the line toneutral value is 120 volts (line voltage divided by the square root ofthree). For the greatest accuracy, a three element transducershould be used for monitoring this type of system. If the systemvoltage is completely balanced (the voltages and loads on the threephases are equal), a 2-1/2 element transducer may be used.

Should you forget all these illustrations, use this helpful rule ofthumb for determining how many elements a transducer shouldhave for monitoring a particular system: subtract one from the totalnumber of wires in the system.

(# of wires) - 1 = # of Elements

Page 24 Page 13

Common Ac Power Systems

1 Element

1-1/2 Element

2 Element

2 1/2 Element

3 Element

1 Phase

3 Phase, 3-wire

3 Phase, 3-wire

3 Phase, 4-wire

3 Phase, 4-wire

Connection

Code Application Voltage Load

CONFIGURATION RESTRICTIONS

None

Balanced

None

Balanced

None

None

Balanced

None

None

None

1E

1.5E

2E

2.5E

3E

Page 15: Power Transducer User’s Guide · 2018-12-26 · Reference Charts and Information A. Transducer output calculations ... Resistance is represented by the letter symbol “R.” One

© 1991 Moore Industries-International, Inc.

V. Monitoring Common Ac Power SystemsMonitoring and recording the voltage and current used by any of thesystems described above requires the use of volt and currenttransducers. The output signals from these transducers can beused to provide input to meters and activate alarms or other devicesshould current or voltage fall outside of a safety range.

Measuring VoltageAc voltage measurements occur across a source or a load. “Load”devices (such as heaters and motors) consume power. “Source”devices, such as transformers and generators, create ac voltage.Figure 1 shows a typical circuit for measuring voltage using a MooreIndustries PAV Voltage Transducer. As the illustration shows, theoutput from the transducer should be carried on a twisted, shieldedwire pair.

Figure 1.

The above illustration shows measurement using the directconnect method. This requires using a measuring device which fitsdirectly in to the circuit. An alternative method, especially popular inhigh voltage situations, requires using a step down device, knownas a voltage or potential transformer (PT).

A step down device is a transformer that inductively senses thevoltage, steps it down, and provides a proportional output. Thestepped down voltage reduces the risk of injury to personnel.

The format used to express the ratio between the primary andsecondary voltage places the primary voltage as the first numberand the secondary (stepped down) voltage as the second number.For example, 480:120 represents the ratio of a PT that steps down

Another way to measure a three-phase four-wire system is with a 2-1/2 element transducer, but some accuracy will be sacrificed if thesystem is not completely balanced. A 2-1/2 element transduceruses all three current and only two voltage inputs. About the onlyfacility which might have balanced loads is a utility transmission site.(Unbalanced loads result from the variations in load drawn byequipment on the various phases of the circuit.)

Figure 8 shows a Moore Industries PWT 2-1/2 element transducerconnected to a balanced three-phase four-wire circuit. An examplemodel number for this unit is:

PWT/120AC,5A/4-20MA/2.5E/-120AC[SM]

Figure 8.

Taking Watt and VAR Measurements

Page 22 Page 15

1 2 3 4 5 6

PAV0-150 ac Input, 4-20mA Output

Digital Meter

115.00

Input115VAC

250 Ohm Resistor

FIGURE 1

VOLTS

Output

120 ACAuxiliaryPower

1 2 3 4 5 6

7 98 10 11 121b

– +

OUTPUT

Output+–

LINE

LOAD

N Va

A B C

Ia Ic Ia Ic

Vc N

12A

EXTPWRIb

6 A EXTPWR

ExternalPower ifApplicable

N

PWTWATTTRANSDUCER

Page 16: Power Transducer User’s Guide · 2018-12-26 · Reference Charts and Information A. Transducer output calculations ... Resistance is represented by the letter symbol “R.” One

© 1991 Moore Industries-International, Inc.

480 volts to 120 volts.Drawing 8 represents a PT, using black dots to show the phase/

polarity reference for the PT. A PT must be installed with the correctpolarity reference or else all readings will be inaccurate.

Drawing 8.

Figure 2 shows a typical voltage measurement using a PT and aMoore Industries PAV Voltage Transducer. A likely application forthis is monitoring voltage level on a motor or light when a thresholdlevel of voltage must be maintained.

Figure 2.

Current MeasurementAs in voltage measurement, current may be measured by thedirect connect method or using a current transformer (CT) as astep down device. Figure 3, on the next page, shows the directconnect method with a current transducer.

Taking Watt and VAR Measurements

Three-Phase Four-WireThese circuits are best served by a three-element transducer, whichprovides optimum accuracy for both balanced and unbalancedconditions. The transducer reads all three voltages with respect toneutral and all three currents. The transducer sums the readingfrom all three elements to create an output representing total watts.

Figure 7 shows a Moore Industries PWT Watt Transducer con-nected to a three-phase four-wire circuit, using PTs and CTs. Anexample model number for this application is:

PWT/120AC,5A/4-20MA/3E/-120AC[SM]Watts equal:W = 3 • V • A • CosØ

Figure 7.

Monitoring Common Ac Power Systems

Page 21Page 16

LEGEND:H = Primary (energy from source) X = Secondary (load)

•= High side of PT O = Connection point

480.00

Input480 VAC

480 = 120 VAC

Digital Meter

1000 Ohm Resistor

VOLTS

Output

1 2 3 4

PAV0-150ac Input, 0-1mA Output

1 2 3 4 5 6

7 98 10 11 121b

– +

OUTPUT

Output+–

LINE

LOAD

N Va

A B C

Ia Ic Ia Ic

Vb Vc

12A

EXTPWRIb

6 A EXTPWR

ExternalPower ifApplicable

N

PWTWATTTRANSDUCER

Primary Secondary

H2 X2

H1 X1

Page 17: Power Transducer User’s Guide · 2018-12-26 · Reference Charts and Information A. Transducer output calculations ... Resistance is represented by the letter symbol “R.” One

© 1991 Moore Industries-International, Inc.

Monitoring Common Ac Power Systems

Figure 3.

Drawing 9 shows a CT used to step down the current on a powerline. The black dots represent the phase/polarity reference of theCT (which indicates how the unit should be oriented when installed).

H1 (or the primary) of the CT should face toward the energyflowing from the line/source to the load. X1 (or the secondary)represents the high side of the secondary winding in the CT. Install-ing the CT in the correct orientation is essential to accurate meas-urements. If installed incorrectly, the CT will be “out of phase” withthe line monitored, and all readings will be inaccurate.

Generally, the second number in a current transformer ratio is 5amps. Typical ratios are 100:5 and 1000:5. The CT ratio equalsH1:X1. Drawing 9.

Taking Watt and VAR Measurements

Figure 6.

Three-Phase Three-WireMeasuring power on this type of system, the most common arrange-ment found in the process industries, requires a two-elementtransducer. As shown in Figure 6, the voltage on the third wire (B)functions as a reference for each of the transducer’s elements.

An example model number for a two-element PWT Watt Trans-ducer for this type of system is:

PWT/120AC,5A/4-20MA/2E/-120AC[SM]

Watts equal: W = 3 • V • A • CosØ

Page 20 Page 17

H1

LoadLine

X1

10.00

Heater

Input115VAC

AMPS

Digital Meter

1000 Ohm Resistor

Output

1 2 3 4

PAC/10A10 Amp Input, 0-1mA Output

1 2 3 4 5 6

7 98 10 11 12

EXTPWR

EXTPWR

– +

OUTPUT

External Powerif Applicable

Output+–

LINE

LOAD

Vb Va

A B C

Ia Ic Ia Ic

Vc Vb

PWTWATTTRANSDUCER

Page 18: Power Transducer User’s Guide · 2018-12-26 · Reference Charts and Information A. Transducer output calculations ... Resistance is represented by the letter symbol “R.” One

© 1991 Moore Industries-International, Inc.

Monitoring Common Ac Power Systems

Note: On current transformers the secondary winding must beconnected at all times to an electrical load (i.e. transducer, meter, orprotective device) or shorted. This is necessary to insure againstthe possibility of voltage build-up. Voltage build-up will occur, andpresent a personnel hazard, if the secondary winding is opencircuited during primary current flow.

Figure 4 shows a CT used with our PAC Current Transducer tomonitor a power line.

Figure 4.

VI. Taking Watt and VAR MeasurementsThis section integrates the various ac power systems and actualequipment used to make watt and VAR measurements. The tech-niques for measuring watts and VARs are similar, so we will use onlywatts in the following examples.

Single-Phase Two-WireAs noted previously, a two-wire system requires one measuringelement to determine power. You calculate the ac power in a singlephase system using this formula:

Power = Voltage • Current • Power Factor(or)W = V • A • Cosø

An example of a correct model number for the a PWT WattTransducer from Moore Industries configured for a single-phasetwo-wire system is:

PWT/120AC,5A/4-20MA/1E/-120AC[SM]

Figure 5 shows the PWT connected to a single-phase circuitusing PTs and CTs.

Figure 5.

Page 18 Page 19

100.0Motor

100 Amps

Input115 VAC

X1

H1

Legend:CT: H1:H1CT: 100:5

AMPS

Digital Meter

1000 Ohm Resistor

Output

1 2 3 4

PAC/5A5 Amp Input, 0-1mA Output

1 2 3 4 5 6 – +

OUTPUT

Output+–

LINE

LOAD

V V I I

External Powerif Applicable

9 12

EXT PWR

PWTWATTTRANSDUCER

Legend:CT: H1:X1CT: 100:5

Page 19: Power Transducer User’s Guide · 2018-12-26 · Reference Charts and Information A. Transducer output calculations ... Resistance is represented by the letter symbol “R.” One

© 1991 Moore Industries-International, Inc.

Monitoring Common Ac Power Systems

Drawing 9.Note: On current transformers the secondary winding must be

connected at all times to an electrical load (i.e. transducer, meter, orprotective device) or shorted. This is necessary to insure againstthe possibility of voltage build-up. Voltage build-up will occur, andpresent a personnel hazard, if the secondary winding is opencircuited during primary current flow.

Figure 4 shows a CT used with our PAC Current Transducer tomonitor a power line.

Figure 4.

VI. Taking Watt and VAR MeasurementsThis section integrates the various ac power systems and actualequipment used to make watt and VAR measurements. The tech-niques for measuring watts and VARs are similar, so we will use onlywatts in the following examples.

Single-Phase Two-WireAs noted previously, a two-wire system requires one measuringelement to determine power. You calculate the ac power in a singlephase system using this formula:

Power = Voltage • Current • Power Factor(or)W = V • A • Cosø

An example of a correct model number for the a PWT WattTransducer from Moore Industries configured for a single-phasetwo-wire system is:

PWT/120AC,5A/4-20MA/1E/-120AC[SM]

Figure 5 shows the PWT connected to a single-phase circuitusing PTs and CTs.

Figure 5.

Page 18 Page 19

100.0Motor

100 Amps

Input115 VAC

X1

H1

Legend:CT: H1:H1CT: 100:5

AMPS

Digital Meter

1000 Ohm Resistor

Output

1 2 3 4

PAC/5A5 Amp Input, 0-1mA Output

1 2 3 4 5 6 – +

OUTPUT

Output+–

LINE

LOAD

V V I I

External Powerif Applicable

9 12

EXT PWR

PWTWATTTRANSDUCER

Legend:CT: H1:X1CT: 100:5

Page 20: Power Transducer User’s Guide · 2018-12-26 · Reference Charts and Information A. Transducer output calculations ... Resistance is represented by the letter symbol “R.” One

© 1991 Moore Industries-International, Inc.

Monitoring Common Ac Power Systems

Figure 3.

Drawing 9 shows a CT used to step down the current on a powerline. The black dots represent the phase/polarity reference of theCT (which indicates how the unit should be oriented when installed).

H1 (or the primary) of the CT should face toward the energyflowing from the line/source to the load. X1 (or the secondary)represents the high side of the secondary winding in the CT. Install-ing the CT in the correct orientation is essential to accurate meas-urements. If installed incorrectly, the CT will be “out of phase” withthe line monitored, and all readings will be inaccurate.

Generally, the second number in a current transformer ratio is 5amps. Typical ratios are 100:5 and 1000:5. The CT ratio equalsH1:X1.

Taking Watt and VAR Measurements

Figure 6.

Three-Phase Three-WireMeasuring power on this type of system, the most common arrange-ment found in the process industries, requires a two-elementtransducer. As shown in Figure 6, the voltage on the third wire (B)functions as a reference for each of the transducer’s elements.

An example model number for a two-element PWT Watt Trans-ducer for this type of system is:

PWT/120AC,5A/4-20MA/2E/-120AC[SM]

Watts equal: W = 3 • V • A • CosØ

Page 20 Page 17

H1

LoadLine

X1

10.00

Heater

Input115VAC

AMPS

Digital Meter

1000 Ohm Resistor

Output

1 2 3 4

PAC/10A10 Amp Input, 0-1mA Output

1 2 3 4 5 6

7 98 10 11 12

EXTPWR

EXTPWR

– +

OUTPUT

External Powerif Applicable

Output+–

LINE

LOAD

Vb Va

A B C

Ia Ic Ia Ic

Vc Vb

PWTWATTTRANSDUCER

Page 21: Power Transducer User’s Guide · 2018-12-26 · Reference Charts and Information A. Transducer output calculations ... Resistance is represented by the letter symbol “R.” One

© 1991 Moore Industries-International, Inc.

480 volts to 120 volts.Drawing 8 represents a PT, using black dots to show the phase/

polarity reference for the PT. A PT must be installed with the correctpolarity reference or else all readings will be inaccurate.

Drawing 8.

Figure 2 shows a typical voltage measurement using a PT and aMoore Industries PAV Voltage Transducer. A likely application forthis is monitoring voltage level on a motor or light when a thresholdlevel of voltage must be maintained.

Figure 2.

Current MeasurementAs in voltage measurement, current may be measured by thedirect connect method or using a current transformer (CT) as astep down device. Figure 3, on the next page, shows the directconnect method with a current transducer.

Taking Watt and VAR Measurements

Three-Phase Four-WireThese circuits are best served by a three-element transducer, whichprovides optimum accuracy for both balanced and unbalancedconditions. The transducer reads all three voltages with respect toneutral and all three currents. The transducer sums the readingfrom all three elements to create an output representing total watts.

Figure 7 shows a Moore Industries PWT Watt Transducer con-nected to a three-phase four-wire circuit, using PTs and CTs. Anexample model number for this application is:

PWT/120AC,5A/4-20MA/3E/-120AC[SM]Watts equal:W = 3 • V • A • CosØ

Figure 7.

Monitoring Common Ac Power Systems

Page 21Page 16

LEGEND:H = Primary (energy from source) X = Secondary (load)

•= High side of PT O = Connection point

480.00

Input480 VAC

480 = 120 VAC

Digital Meter

1000 Ohm Resistor

VOLTS

Output

1 2 3 4

PAV0-150ac Input, 0-1mA Output

1 2 3 4 5 6

7 98 10 11 121b

– +

OUTPUT

Output+–

LINE

LOAD

N Va

A B C

Ia Ic Ia Ic

Vb Vc

12A

EXTPWRIb

6 A EXTPWR

ExternalPower ifApplicable

N

PWTWATTTRANSDUCER

Primary Secondary

H2 X2

H1 X1

Page 22: Power Transducer User’s Guide · 2018-12-26 · Reference Charts and Information A. Transducer output calculations ... Resistance is represented by the letter symbol “R.” One

© 1991 Moore Industries-International, Inc.

V. Monitoring Common Ac Power SystemsMonitoring and recording the voltage and current used by any of thesystems described above requires the use of volt and currenttransducers. The output signals from these transducers can beused to provide input to meters and activate alarms or other devicesshould current or voltage fall outside of a safety range.

Measuring VoltageAc voltage measurements occur across a source or a load. “Load”devices (such as heaters and motors) consume power. “Source”devices, such as transformers and generators, create ac voltage.Figure 1 shows a typical circuit for measuring voltage using a MooreIndustries PAV Voltage Transducer. As the illustration shows, theoutput from the transducer should be carried on a twisted, shieldedwire pair.

Figure 1.

The above illustration shows measurement using the directconnect method. This requires using a measuring device which fitsdirectly in to the circuit. An alternative method, especially popular inhigh voltage situations, requires using a step down device, knownas a voltage or potential transformer (PT).

A step down device is a transformer that inductively senses thevoltage, steps it down, and provides a proportional output. Thestepped down voltage reduces the risk of injury to personnel.

The format used to express the ratio between the primary andsecondary voltage places the primary voltage as the first numberand the secondary (stepped down) voltage as the second number.For example, 480:120 represents the ratio of a PT that steps down

Another way to measure a three-phase four-wire system is with a 2-1/2 element transducer, but some accuracy will be sacrificed if thesystem is not completely balanced. A 2-1/2 element transduceruses all three current and only two voltage inputs. About the onlyfacility which might have balanced loads is a utility transmission site.(Unbalanced loads result from the variations in load drawn byequipment on the various phases of the circuit.)

Figure 8 shows a Moore Industries PWT 2-1/2 element transducerconnected to a balanced three-phase four-wire circuit. An examplemodel number for this unit is:

PWT/120AC,5A/4-20MA/2.5E/-120AC[SM]

Figure 8.

Taking Watt and VAR Measurements

Page 22 Page 15

1 2 3 4 5 6

PAV0-150 ac Input, 4-20mA Output

Digital Meter

115.00

Input115VAC

250 Ohm Resistor

FIGURE 1

VOLTS

Output

120 ACAuxiliaryPower

1 2 3 4 5 6

7 98 10 11 121b

– +

OUTPUT

Output+–

LINE

LOAD

N Va

A B C

Ia Ic Ia Ic

Vc N

12A

EXTPWRIb

6 A EXTPWR

ExternalPower ifApplicable

N

PWTWATTTRANSDUCER

Page 23: Power Transducer User’s Guide · 2018-12-26 · Reference Charts and Information A. Transducer output calculations ... Resistance is represented by the letter symbol “R.” One

© 1991 Moore Industries-International, Inc.

This matrix shows some typical applications for power transducers:

Transducer # of Elements Type of Circuit Typical Applications

PWT Watt 1 1-phs 2-w Heating elements,Convenience outlets

PWT Watt 1-1/2 3-phs 3-w Single motor load

PWT Watt 2 3-phs 3-w Motors, conveyorspumps

PWT Watt 2-1/2 3-phs 4-w Balanced circuit

PWT Watt 3 3-phs 4-w Factory substation

PAC Current 1 1-phs Phase current

PAV Voltage 1 1-phs Phase voltage

Page 14 Page 23

Taking Watt and VAR Measurements

Page 24: Power Transducer User’s Guide · 2018-12-26 · Reference Charts and Information A. Transducer output calculations ... Resistance is represented by the letter symbol “R.” One

© 1991 Moore Industries-International, Inc.

Three-Phase Three-WireMost industrial motors and other equipment within the processindustries operate with this type of system, commonly called a deltasystem.

The voltage values are expressed as line to line values becauseno neutral is present. Monitoring this type of system requires a two-element transducer.

Three-Phase Four-WireYou will find this type of system, consisting of three wires and aneutral, providing the entrance power to an industrial building.Common names for it include “wye” or “Y connected.”

Because the system has a neutral leg the voltages may bemeasured line to line or line to neutral. The proper description ofthis circuit uses both values (i.e. 208Y/120). Although commonlyonly the first value is used (208) for the purpose of power measure-ment we must use the line to neutral value (120ac)

Common Ac Power Systems

Page 12 Page 25

VII. Glossary

Ampere —A unit of electrical current or rate of flow of electrons.One volt across one ohm of resistance causes a current flow of oneampere. A flow of one coulomb per second equals one ampere.Apparent Power —The product of voltage and current in a circuit inwhich the two reach their peaks at different times, or, in other words,there is a phase angle between voltage and current. Units are VA.

Balanced load —An alternating current power system consisting ofmore than two current-carrying conductors in which these current-carrying conductors all carry the same current.Billing demand —The demand level which a utility uses to calculatethe demand charges on the current month’s bill. If the rate sched-ule includes a ratchet clause or minimum demand charge, billingdemand may or may not be the actual average demand for thecurrent month.Burden —The electrical load an instrument or meter places on acurrent or potential transformer. All current and potential transform-ers have a rated burden which should not be exceeded or thetransformer accuracy will deteriorate.

Capacitor —A device consisting essentially of two conductingsurfaces separated by an insulating material or dielectric such asair, paper, mica, plastic, film, or oil. A capacitor stores electricalenergy, blocks the flow of direct current, and permits the flow ofalternating current to a degree dependent upon the capacitanceand frequency.Capacitive Reactance —Component of impedance due to capaci-tance. Symbol is “XC.”Clamp-on CT —A current transformer which clamps around acurrent-carrying conductor so that the conductor does not have tobe opened for insertion of the transformer primary. Particularlysuited for making energy surveys where current must be sensed atmany points for relatively short periods.Connected load —The total load which a customer can impose onthe electrical system if everything is connected at one time. Con-nected load can be measured in horsepower, watts, or volt-am-peres. Some rate schedules establish a minimum demand chargeby imposing a fee per unit of connected load.

208 VAC

L1

N

L2

L3

120 VAC

120 VAC120 VAC

L1

L2

L3

480VAC

480 VAC480 VAC

Page 25: Power Transducer User’s Guide · 2018-12-26 · Reference Charts and Information A. Transducer output calculations ... Resistance is represented by the letter symbol “R.” One

© 1991 Moore Industries-International, Inc.

zero and apparent power = real power.IV. Common Ac Power SystemsAc power systems offer a number of configurations for using power.In most instances, you will encounter the four arrangements de-scribed in this section.

Single-Phase Two-WireThe most recognizable ac power system is the single-phase two-wire system. This configuration provides power within your home foroperating domestic appliances like toasters and refrigerators.

The voltage on this type of circuit is measured and written as aline to line value. This illustration shows a 120 volt system. Measur-ing power on this system requires one voltage and one currentmeasurement, or a one element transducer.

Single-Phase Three-WireThis type of system provides electricity to homes in the UnitedStates and you will rarely encounter it in an industrial situation. Thetwo wires and neutral leg comprise a single phase system. Thissystem can be monitored with either a 1-1/2 or two element trans-ducer so that the voltage and current on each phase may bemeasured.

Contract load capacity —A load capacity contracted with a utilityand related to connected load. The minimum monthly demandcharge is sometimes established by applying the demand rate tosome specified percentage of the contracted capacity.Coulomb —The unit of electric charge equal to the quantity ofelectricity transferred by a current of one ampere in one second.Current Transformer (CT) —An instrument transformer, intended formeasuring or control purposes, designed to have its primarywinding connected in series with a conductor carrying the current tobe measured or controlled. Also see clamp-on CT, where theconductor itself acts as the primary. CT’s step down high currentsto lower values which can be used as input signals to measuringinstruments. They must be used with caution.Current transformer ratio –The ratio of primary amperes divided bysecondary amperes.

Demand —A measure of the customer load connected to theelectrical power system at any given time. Units are usually watts orvolt-amperes.Demand-hours —The equivalent number of hours in a month duringwhich the peak average demand is fully utilized. In other words, ifenergy consumption for the current month is X kwhr and the peakaverage demand is Y kw, then the demand-hours is equal to X/Yhours.

The higher the number of demand-hours the better the demandleveling situation and the more efficiently demand is being used.Many rate schedules have demand-hour based energy rate breakswhere the higher the demand-hour figure the lower the energyconsumption rate in $/kwhr.Demand interval —Demand charges are based on peak averagedemand over a utility-specified time interval, not on the instantane-ous demand (or connected load) at any given moment. This periodof time is called the demand interval. Demand intervals typicallyrange from 15, 20, to 30 minutes, although they can drop as low afive minutes.Demand-utilization efficiency —Related to demand-hours andreally a measure of how successful demand leveling procedureshave been. Calculated by dividing demand hours by 720, thenumber of hours in a 30 day billing period. Although demand-utilization efficiency heavily depends on the type of facility, ingeneral an efficiency of 50% is considered average, 40% and lowerpoor, and 60% and higher good.

Glossary

Page 26 Page 11

N

120 VAC

120 VAC

240 VAC

L1

L2

120 VAC

L1

L2

Page 26: Power Transducer User’s Guide · 2018-12-26 · Reference Charts and Information A. Transducer output calculations ... Resistance is represented by the letter symbol “R.” One

© 1991 Moore Industries-International, Inc.

Glossary

Discretionary loads —Loads which may be removed from the linefor short periods of time without affecting business, plant operation,or personnel comfort. Typical are HVAC systems, hot water heaters,and snow-melt systems. These types of load provide the shed/restore capability required in power demand controller systems.

Efficiency —In general, the ratio of output power to input powerexpressed as a percentage. For electromechanical equipment,such as motors, it is very difficult to determine true efficiency underplant floor conditions. Electric input power can be easily measured,but accurately determining mechanical output power is difficult.Energy consumption charges —The charges a utility imposes forthe consumption of real power in watts. Units are usually dollars perkilowatt-hour.

Fuel-adjustment charges —Charges from a utility for changes inthe cost of the fuel they use and other utility-cost factors. Frequentlythese charges are based on complex formulas which include manyvariables related to the cost of delivering electrical energy. Unitsare usually $/kwhr.Frequency —The number of recurrences of a periodic phenomenonin a unit of time. In electrical terms, frequency is specified as somany Hertz (Hz) where one Hz equals one cycle per second.

Horsepower (hp) —A unit of power, or the capacity of a mechanismto do work. It is equivalent to raising 33,000 pounds one foot in oneminute. One horsepower equals 746 watts.

Inductive Reactance —Component of impedance due to induc-tance. Symbol is “XI.”Impedance —The total opposition (i.e. resistance and reactance) acircuit offers to the flow of alternating current at a given frequency.It is measured in ohms.Induction motor —An alternating current motor in which the primarywinding (usually the stator) is connected to the power source andinduces a current into a polyphase secondary (usually the rotor).Induction motors are the principal source of poor power factorproblems.Inducto r—Also called an inductance or retardation coil. A conduc-tor, wound into a spiral or coil to increase its inductive intensity, isused for introducing inductance into a circuit. An inductor retardsthe change of current flow through it.

Page 10 Page 27

Page 27: Power Transducer User’s Guide · 2018-12-26 · Reference Charts and Information A. Transducer output calculations ... Resistance is represented by the letter symbol “R.” One

© 1991 Moore Industries-International, Inc.

Drawing 7 shows that there is more positive power than negativepower, so the RMS value will be positive. P = EI cos60° = EI(0.5).

Real PowerSo far when we have referred to power we have meant useful or realpower, or power which does work. Real power = EI cosØ = I2R =I2ZcosØ. It is expressed in units of watts (watts = volts x amps xcosØ).

Apparent powerApparent power is the product of the voltage and current withoutregard to the applied load or the phase angle. Its measured valueis called “volt-amps” or VA. When a real world load is applied to thecircuit a combination of real power and reactive power results.

Reactive PowerReactive power is the result of the net reactance in the circuit.Rather than doing useful work, reactive power is stored in themagnetic and electric fields of the inductance and capacitance,then returned to the circuit. The unit for reactive power is VAR forvolt-amps-reactive. Reactive power = EIsinØ = I2ZsinØ.

Power TriangleA convenient method to display the relationship between apparent,reactive, and real power and the phase angle is with the powertriangle. The lengths of the sides of the triangle correspond to therelative values of the respective parameters.

You can easily see that if the phase angle is zero, then the VARs are

Basic Concepts of Ac Power

Initiator pulses —Electrical impulses generated by pulse-initiatormechanisms installed in utility revenue meters. Each pulse indi-cates the consumption of a specific number of watts. These pulsescan be used to measure energy consumption and demand.Installed load—Equivalent to connected load.

Joule —Unit of measure. One joule of work is accomplished when avoltage of one volt causes one coulomb of electrons to pass througha circuit.

Kilowatt-hour (kwhr) —A unit of electrical measurement indicatingthe expenditure of 1,000 watts for one hour. Higher quantities areexpressed in megawatt hours, or the expenditure of one millionwatts for one hour.

Lagging current —The current flowing in a circuit which is mostlyinductive. If a circuit contains only inductance the current lags theapplied voltage by 90°. Lagging current means lagging powerfactor of less than unity.Leading current —The current flowing in a circuit which is mostlycapacitive. If a circuit contains only capacitance the current leadsthe applied voltage by 90°. Leading current means leading powerfactor of less than unity.Load —Any device or circuit which consumes power in an electricalsystem.Load restoring —The energization of loads that were previouslyremoved from the line to limit the load and control demand level.Load shedding —The removal of loads from the line to limit loadand control demand level.

Neutral —The conductor chosen as the return path for the currentfrom the load to the source in power measurement procedures. Theneutral is frequently, but not necessarily, grounded.

Ohm—The unit of electrical resistance. One ohm is the value ofresistance through which a potential difference of one volt willmaintain a current flow of one ampere.Ohms’ Law —The voltage across an element of a direct currentcircuit is equal to the current in amperes through the elementmultiplied by the resistance of the element in ohms.

Glossary

Page 28 Page 9

Apparent Power(VA)

Reactive Power(VARs)

Real Power (watts)

Phase Angle (ø)

Page 28: Power Transducer User’s Guide · 2018-12-26 · Reference Charts and Information A. Transducer output calculations ... Resistance is represented by the letter symbol “R.” One

© 1991 Moore Industries-International, Inc.

Capacitive LoadWhen the applied load is a pure capacitance, the current will leadthe voltage by 90°. Phase angle = 90°. P = EI cos90 = 0. Again,RMS power is zero (Drawing 6).

Drawing 6. Capacitive load

Real LoadsIn actual practice loads are never purely resistive, inductive, orcapacitive. For an example, let’s consider a circuit whose loadsresult in a small amount of inductive reactance. In this example(Drawing 7) the current lags the voltage by 60°.

Drawing 7. Inductive and reactive loads

Basic Concepts of Ac Power Glossary

Peak average demand —The highest average load over a utility-specified time interval during a billing period. If there is no ratchetclause in the rate schedule then the peak average demand is alsothe billing demand.Polyphase —Having or utilizing several phases. A polyphasealternating current power circuit has several phases of alternatingcurrent with a fixed phase angle between phases.Potential transformer (PT) —An instrument transformer of which theprimary winding is connected in parallel with the circuit whosevoltage is to be measured or controlled. PT’s normally are used tostep down high voltage potentials to levels acceptable to measuringinstruments.Potential transformer ratio —The ratio of primary voltage dividedby secondary voltage.Power demand controllers —Control devices designed to minimizeand level average demand by maintaining it below some pre-selected level. This is normally accomplished by shedding andrestoring discretionary loads. There are many basic principles ofoperation of power demand controllers.Power factor —The ratio of real power (in watts) of an alternatingcurrent circuit to the apparent power in volt-amperes. Also thecosine of the phase angle between the voltage applied to a loadand the current passing through it.Power factor correction —Steps taken to raise the power factor bybringing the current more nearly in phase with the applied voltage.Most frequently this consists of increasing the lagging power factorof inductive circuits by adding capacitance.Power factor penalty —The charge utilities impose for operating atpower factors below some rate-schedule-specified level. This levelranges from a lagging power factor of 0.80 to unity. Utilities calcu-late power factor penalties in countless ways.Pulse initiator —An assemblage added to a revenue meter whichgenerates pulses proportional to meter disk rotation. Each pulserepresents a discrete quantity of energy consumed. Most frequentlythe pulses are generated photoelectrically and output throughmercury-wetted relays.

Q—A phantom quantity used by power companies to calculate volt-ampere-reactive (VAR) when there are both leading and laggingpower factors. A Q-hour meter will determine VAR-hr’s when thepower factors vary from 30° leading to 90° lagging.Q-hour meter —Similar to a watt-hour meter except that the voltageapplied to each potential coil lags the voltage supplied to the

Page 8 Page 29

P

ØPhaseAngle

360°

I E

E

I

360°180°

P

Average Power

Page 29: Power Transducer User’s Guide · 2018-12-26 · Reference Charts and Information A. Transducer output calculations ... Resistance is represented by the letter symbol “R.” One

© 1991 Moore Industries-International, Inc.

Basic Concepts of Ac Power

The power is defined as P = EI cosØ, where Ø is the phase anglebetween the voltage and current. Here (Drawing 4) the angle iszero. CosØ = 1, so P = EI and alternates between some positivevalue and zero.

Drawing 4 shows instantaneous values of the voltage, current,and power. The quantities used in the equations and in the applica-tions are the RMS (root mean squared) values.

Drawing 4. Current, voltage and power values of a resistive load

Inductive LoadWhen the applied load is a pure inductance, the current will lag thevoltage by 90°. Phase angleØ = 90°. The resulting power: P = EIcos(–90°) = 0. The product of E and I varies between equalamounts of positive and negative values resulting in an RMS valueof zero power (Drawing 5).

Drawing 5. Inductive Load

Glossary

respective watt-hour meter potential coil by 60°. This is generallyaccomplished by cross-phasing, thus eliminating the need for aphase-shifting transformer. The VAR-hr information can be calcu-lated as follows: VAR-hr= (2Q hr - whr)/ sqrt3

Ratchet clause —A rate schedule clause which states that billingdemand may be based on current month peak average demand oron historical peak average demand, depending on relative magni-tude.

Usually the historical period is the past eleven months, althoughit can be for the life of the contract. Billing demand is either thecurrent month’s peak average demand or some percentage (75% istypical) of the highest historical peak average demand, dependingon which is largest.Reactance —The opposition to the flow of alternating current.Capacitive reactance is the opposition offered by capacitors andinductive reactance is the opposition offered by an inductive load.Both reactances are measured in ohms.Reactive power —Also called a watt-less power and measured involt-amperes-reactive. Reactive power increases with decreasingpower factor and is the component of apparent power which doesno real work in a system.Real power —The component of apparent power that representstrue work in an alternating current circuit. It is expressed in wattsand is equal to the apparent power times the power factor.Resistance —The property of a substance which impedes currentflow and results in the dissipation of power in the form of heat. Theunit of resistance is the ohm. One ohm is the resistance throughwhich a difference of potential of one volt will produce a current ofone ampere.Revenue meter —A meter used by a utility to generate billinginformation. Many types of meters fall in this category dependingon the rate structure.Root mean square (RMS) —The effective value of alternatingcurrent or voltage. The RMS value of voltage and current can beused for the accurate computation of power in watts. The RMSvalue is the same value as if continuous direct current were appliedto a pure resistance.

Single-phase —An alternating current circuit in which only onephase of current is available in a two-conductor or three-conductorsystem where the load lines are 0° or 180° out of phase.

Page 30 Page 7

E

360°

I

P

ØPhaseAngle

E

Ø = 0

P

I

360°

Page 30: Power Transducer User’s Guide · 2018-12-26 · Reference Charts and Information A. Transducer output calculations ... Resistance is represented by the letter symbol “R.” One

© 1991 Moore Industries-International, Inc.

Drawing 2. One rotation of an ac motor

Resistive LoadWhen this coil is wired to a purely resistive load, the voltage and theresulting current occur simultaneously. In other words, they arerotating “in phase” (Drawing 3).

Drawing 3. Resistive Load

Sliding demand interval —A method of calculating average de-mand by averaging the demand over several successive short timeintervals, advancing one short time interval each time. Updatingaverage demand at short time intervals gives the utility a muchbetter measure of true demand and makes it difficult for the cus-tomer to obscure high short-term loads.Subsidiary billing factors —Secondary billing factors in a rateschedule, including such things as fuel-adjustment costs, multiplemetering points, interruptible service provisions, and transformerownership benefits.

Time-dependent clauses —Rate schedule provisions which varyrates depending on the time of day or time of year when energy isconsumed. Frequently these clauses cover both demand andenergy charges. There is money to be saved by operating highloads and consuming high amounts of energy during off-peakperiods when rates are lower.True power —Same as real power.

Unbalanced loads —A situation existing in an alternating currentsystem using more than two current-carrying conductors whereuneven loading of the phases results in unequal current in thecurrent-carrying conductors.

Volt-ampere (VA) —The unit of apparent power. It equals volts xamperes, regardless of the power factor.Volt-ampere demand —Where peak average demand is measuredin volt-amperes rather than watts. In this case the customer isautomatically penalized for operating at any power factor less thanunity.Volt-ampere-reactive (VAR) —The unit of reactive power, asopposed to real power, in watts. One VAR is equal to one reactivevolt-ampere.Volt-ampere-reactive demand —Measuring VAR demand is amethod of penalizing for poor power factor. Multiplying by somerate ($/VAR) penalizes for operating at any power less than unity.

Frequently there is a quantity of “free” VAR which is determinedas some percentage of the peak average watt demand. All excessVAR over this quantity is then billed at this $/VAR rate. Effectively,this penalizes for operating below some specified power factor lessthan unity.

Page 6

Basic Concepts of Ac Power Glossary

Page 31

E

I

E

0

One Rotation–

+

360°

Page 31: Power Transducer User’s Guide · 2018-12-26 · Reference Charts and Information A. Transducer output calculations ... Resistance is represented by the letter symbol “R.” One

© 1991 Moore Industries-International, Inc.

III. Basic Concepts of Ac PowerThis material should give non-electrical engineers a feel for some ofthe basic characteristics of electrical systems. Ideally, this informa-tion will help you implement and work with an energy monitoring andmanagement system.

Power—Direct Current CircuitIn a direct current circuit voltage and current are constant. Thereare only resistive loads. The relationship between voltage, currentand resistance is E = IR. Power is defined P = EI = I2R. A watt isone volt times one amp. 1W = (1V) (1A).

Power—Alternating Current CircuitAlternating current is created by rotating a coil of conductive wirethrough a magnetic field (Drawing 1). Drawing 2 represents theresults of the rotating action through the magnetic field. In an accircuit, voltage and current vary in amplitude in a sinusoidal fashion.

Drawing 1. Typical ac motor

Glossary

Volt-ampere-reactive-hour —The measure of the number of VAR’sused in one hour. VAR-hr and whr are frequently used to calculateaverage power factor during a billing period.Voltage (V) —The force which causes current to flow through aconductor. One volt equals the force required to produce a currentflow of one ampere through a resistance of one ohm.

Watt (W)—A measure of real power. The unit of electric powerrequired to do work at the rate of one joule per second. It is thepower expended when one ampere of direct current flows through aresistance of one ohm.Watt demand —The usual demand billing factor where peak aver-age demand is measured in watts or real power.Watt-hour (whr) —A unit of electrical work indicating the expendi-ture of one watt of electrical power for one hour.Wattmeter —An instrument for measuring the real power in anelectric circuit. Its scale is usually graduated in watts, kilowatts, ormegawatts.

Page 32 Page 5

Slipring

Brush

Rotating Conductor

Directionof rotation

UniformMagneticField

Load

Page 32: Power Transducer User’s Guide · 2018-12-26 · Reference Charts and Information A. Transducer output calculations ... Resistance is represented by the letter symbol “R.” One

© 1991 Moore Industries-International, Inc.

VIII. Reference Charts and Information

A. Transducer Output CalculationsMost transducers you need will be standard calibration units. Howthen, do you determine what the output represents for both potentialand current transformers?

The output of a transducer represents the standard calibrationof the unit (from the data contained within the Specifications sectionon the unit’s data sheet) multiplied by the transformer ratios.You determine the output with this formula:

Transducer Cal x Potential Transformer Ratio x Current Transformer Ratio

Standard Transducer CalibrationsExample 1: You have a 480:120 ratio potential transformer, 100:5ratio current transformer and are monitoring a three-phase three-wire system. For this example we will use a two element transducer.

The ratios show us that the secondary of the PT is 120 volts andthe secondary of the CT is 5 amps. We therefore would use a 120volt 5 amp input watt transducer. Looking to the Specificationssection of the PWT Watt Transducer data sheet (table 4) with 120ac,5a, we find the standard output would be 500 watts per element.

We can now determine what the output would represent bymultiplying the transformer ratios by the full scale calibration of thetransformer:

This is what the output (i.e. 0-1mA) would equal (0-80,000 watts).This type of calculation is true of any of the watt or VAR transduc-

ers. There will be rare times that the transducer will need to becustom calibrated to meet the customer’s specific needs. Anexample of this would be if the customer had a meter alreadyscaled to a specific value.

Page 4 Page 33

500 WATTSPER ELEMENT

2 ELEMENTS480

120

100

580,000 WATTSX X X =

Page 33: Power Transducer User’s Guide · 2018-12-26 · Reference Charts and Information A. Transducer output calculations ... Resistance is represented by the letter symbol “R.” One

© 1991 Moore Industries-International, Inc.

B. Full-Load Motor CurrentsUse this chart to determine the full-load motor current of three-phase induction-type Squirrel Cage and Wound Rotor motors.Using the known horsepower of the motor (left column) and goingacross to the appropriate voltage (from the nameplate) you canestimate the motor current, in amps, at that voltage.

Motor Current in amps; Translating horsepower to voltage

hp 115V 200V 230V 460V 575V 2300V 4160V

0.5 4 2.3 2 1 0.80.75 5.6 3.2 2.8 1.4 1.11 7.2 4.15 3.6 1.8 1.41.5 10.4 6 5.2 2.6 2.12 13.6 7.8 6.8 3.4 2.73 11 9.6 4.8 3.95 17.5 15.2 7.6 6.17.5 25 22 11 9

10 32 28 14 1115 48 42 21 1720 62 54 27 2225 78 68 34 2730 92 80 40 3240 120 104 52 4150 150 130 65 5260 177 154 77 62 16 8.975 221 192 96 77 20 11

100 285 248 124 99 26 14.4125 368 312 156 125 31 17150 415 360 180 144 37 20.5200 550 480 240 192 49 27

Over 200, appx. amps/hp2.75 2.4 1.2 0.96 0.24 0.13

Page 2 Page 35

Reference Charts and Information

Page 34: Power Transducer User’s Guide · 2018-12-26 · Reference Charts and Information A. Transducer output calculations ... Resistance is represented by the letter symbol “R.” One

© 1991 Moore Industries-International, Inc.

I. Why Monitor Power?With ac power consumption and measurement drawing ever-moreattention throughout the process industries, an understanding ofbasic ac parameters becomes increasingly important.

This simple reference guide uses illustrations and simple defini-tions to explain the basics of ac power and its uses in the processindustries. This comparison shows the relationship between theterms used in measuring electrical current and standard processflow concepts:

Electrical Term Flow Term

Current FlowVoltage Pressure

Resistance Pressure Drop

Keeping this simple analogy in mind should help you understandand apply the basic principles needed to use power transducers.

For help in controlling your ac power usage, or ordering powertransducers, please call your local representative. In addition, ourhelpful Sales Engineers are available during business hours. Pleaseconsult the back of this booklet for the phone number of the officenearest you.

C. Nameplate Voltage Ratings of StandardInduction Motors

Nominal System Voltage Nameplate Voltage

Single-Phase Motors:120 ........................................................... 115240 ........................................................... 230

Three-Phase Motors:208 ........................................................... 200240 ........................................................... 230480 ........................................................... 460600 ........................................................... 5752400 ....................................................... 23004160 ....................................................... 40004800 ....................................................... 46006900 ....................................................... 660013800 ................................................... 13200

Data taken from IEEE Std. 141-1976

Reference Charts and Information

Page 36 Page 1

Page 35: Power Transducer User’s Guide · 2018-12-26 · Reference Charts and Information A. Transducer output calculations ... Resistance is represented by the letter symbol “R.” One

© 1991 Moore Industries-International, Inc.

D. Nominal System VoltagesThe information on this page should correspond to the power yourfacility receives from the power company.

Maximum SystemNominal System Voltages Voltages

Single Phase Systems:

Two Wire Three Wire120AL 120/240...............................................127 or 127/254

Three Phase Systems:

Three Wire Four Wire208Y/120..............................220

(240).................240/120.................................254480....................480Y/277..............................508(600)...............................................................635(2400)...........................................................25404160.............................................................4400(4800)...........................................................5080(6900)...........................................................7260

12470Y/7200....................1320013200Y/7620....................13970

13800.................(13800Y/7970)................14520(23000).......................................................24340

24940Y/14400..................26400(34500)..............34500Y/19920..................36500(46000).......................................................4830069000..........................................................72500

* Those system voltages shown without parenthesis are preferred. Taken from IEEE Std. 141-1976.

Reference Charts and Information

Page 37

Page 36: Power Transducer User’s Guide · 2018-12-26 · Reference Charts and Information A. Transducer output calculations ... Resistance is represented by the letter symbol “R.” One

© 1991 Moore Industries-International, Inc.

Rugged Construction:Card guides running the entiredepth of the housing hold thePC boards securely in place.This reduces damage from shockand vibration by preventing the boardfrom flexing.

Instruments Designed with Users in Mind

Moore Industries' power transducers feature utility-grade designand construction to provide years of accurate operation. Eachmodel also features a low burden power requirement and a provenability to maintain stability. For the ultimate quality check, we burn-in test every single unit manufactured.

Easy Installation: Unique “keyhole slotted”mounting flanges eliminate mounting hassleby letting you set the screws,then slip the unit over them andtighten down. No more fumblingto hold a transducer whilesetting screws at the same time!

IX. Power Transducers Available from Moore Industries

PAC/PAV Ac Current/Voltage TransducersMeasures ac current or voltage drawn by a source of load, such asa motor or heater. This information can be used to to help schedulemotor maintenance, monitor viscosity within a process, or record amachine’s energy usage.

PDC Dc Voltage Transducer & Ground Fault DetectorMonitors ground faults on a battery back-up system to assure thatenergy doesn’t leak to ground, thus draining the system and leavingit useless.

PVT, PWT, PWV Ac Power TransducersThese units monitor demand and power usage, from which revenuebilling may be calculated.

PVW, PWH, PCV Ac Power/Energy TransducersThese units combine the function of the ac power transducerswith an integrator(s) to provide contact output indicating energy(KW-hours, KVAR-hours).

SM Surface Mount HousingEvery unit comes in this style of housing, which is rust-free alumi-num and has card guides running its entire depth to support the PCboards. Conforming to commonly accepted standards for wiringand footprint sizes makes this housing easy to install and work with.

Page 39