SCALE DESIGN CHECKED DATE DRAWN APPROVED REVISION/ISSUE NO. DATE SEAL JOB NO. SHEET OF DRAWING NO. G-1 1 3 Job #1904 NONE 7/11/18 PJH PJH VJB VJB RED BUD, ILLINOIS REPLACEMENT OF FIVE SUBSTATION FEEDER UNDERGROUND EXITS 0 Client Review 7/11/18 1 Manhole updates 9/5/18 2 Bid Set 3/25/20 BID SET COVER SHEET SPRINGFIELD, IL RED BUD, IL PROJECT: REPLACEMENT OF FIVE SUBSTATION FEEDER UNDERGROUND EXITS FOR: CITY OF RED BUD 200 EAST MARKET STREET RED BUD, ILLINOIS 62278 WWW.CITYOFREDBUD.ORG LOCATION MAP STATE LOCATION PLAN INDEX OF DRAWINGS GENERAL G-1 COVER SHEET ELECTRICAL E-1 REPLACEMENT OF FIVE SUBSTATION FEEDER UNDERGROUND EXITS - SITE PLAN E-2 REPLACEMENT OF FIVE SUBSTATION FEEDER UNDERGROUND EXITS - MANHOLE DETAILS HWY 154 (W. MARKET ST) RTE 159 MADISON ST. POWER ST. SUBSTATION POWER PLANT DUCT BANK ROESLEIN PROPOSED

Transcript of POWER PLANT POWER ST. - City of Red Bud, IL › uploads › 3 › 8 › 4 › 1 › ...2 Bid Set...

Page 1: POWER PLANT POWER ST. - City of Red Bud, IL › uploads › 3 › 8 › 4 › 1 › ...2 Bid Set 3/25/20 BID SET COVER SHEET SPRINGFIELD, IL RED BUD, IL PROJECT: REPLACEMENT OF FIVE

SCALE

DESIGN

CHECKED

DATE

DRAWN

APPROVED

RE

VIS

IO

N/IS

SU

E

NO

.D

AT

E

SEAL

JOB NO.

SHEET OF

DRAWING NO.

G-1

1 3

Job #1904

NONE7/11/18

PJH PJH

VJB VJB

RE

D B

UD

, IL

LIN

OIS

RE

PL

AC

EM

EN

T O

F F

IV

E S

UB

ST

AT

IO

N

FE

ED

ER

U

ND

ER

GR

OU

ND

E

XIT

S

0C

lie

nt R

evie

w7

/1

1/1

8

1M

an

ho

le

u

pd

ate

s9

/5

/1

8

2B

id

S

et

3/2

5/2

0

BID SET

CO

VE

R S

HE

ET

SPRINGFIELD, IL

RED BUD, IL

PROJECT:

REPLACEMENT OF FIVE

SUBSTATION FEEDER

UNDERGROUND EXITS

FOR:

CITY OF RED BUD

200 EAST MARKET STREET

RED BUD, ILLINOIS 62278

WWW.CITYOFREDBUD.ORG

LOCATION MAP

STATE LOCATION PLAN

INDEX OF DRAWINGS

GENERAL

G-1 COVER SHEET

ELECTRICAL

E-1 REPLACEMENT OF FIVE SUBSTATION FEEDER

UNDERGROUND EXITS - SITE PLAN

E-2 REPLACEMENT OF FIVE SUBSTATION FEEDER

UNDERGROUND EXITS - MANHOLE DETAILS

HWY 154 (W. MARKET ST)

RT

E 159

MA

DIS

ON

S

T.

PO

WE

R S

T.

SUBSTATION

POWER PLANT

DUCT BANK

ROESLEIN

PROPOSED

Page 2: POWER PLANT POWER ST. - City of Red Bud, IL › uploads › 3 › 8 › 4 › 1 › ...2 Bid Set 3/25/20 BID SET COVER SHEET SPRINGFIELD, IL RED BUD, IL PROJECT: REPLACEMENT OF FIVE

JB-1

Existing 12KV #4/0 AWG AL in existing

conduit. Circuit I

MH5

MH4

MH2

MH3

MH6

Circuits A,B,D,E & I

Ex. poles/structures

to be removed

Circuits A,B,E,D

Str. #5

MH-1

Circuits A,B,D & E

Str. #3

Str. #4

Ex. Str.

to remain.

Str. #1

Str. #1A

Ex. Str.

to remain.

Str. #2

Circuit I

Circuits E & I

Circuits B & D

1

3

2

3

3

4 Circuit D

4 Circuit I

4

4

4

Circuit D

Circuit B

4

Circuit I

4Circuit E

Circuit A

6

6

6Circuit A

6Circuit A

6

6

270'

140'

340'

300'

Ex. Switchgear to remain

150'

955'-0"

Str. #9

Str. #10

Str. #7A

Str. #8A

Str. #8B

Str. #7B

5

5

Str. #6

6

Str. #2A

7 Circuit B & D

Str. #3A

Str. #4A

60'

90'100'

Str. #2B

JB-2

Circuit D

100'

115'

Circuit D390' 4

4

Switchgear Note:

The existing 4-5kV circuits in 4" GRS conduit

exiting the switchgear, will transition to new

6" Sch 40 PVC conduit to MH-5. One (1)

existing spare 4" GRS conduit will transition to

new 6" Sch 40 PVC conduit to JB-2. Expose all

existing conduit as required.

SCALE

DESIGN

CHECKED

DATE

DRAWN

APPROVED

RE

VIS

IO

N/IS

SU

E

NO

.D

AT

E

SEAL

JOB NO.

SHEET OF

DRAWING NO.

E-1

2 3

Job #1904

AS NOTED7/11/18

PJH PJH

VJB VJB

RE

D B

UD

, IL

LIN

OIS

RE

PL

AC

EM

EN

T O

F F

IV

E S

UB

ST

AT

IO

N

FE

ED

ER

U

ND

ER

GR

OU

ND

E

XIT

S

0C

lie

nt R

evie

w7

/1

1/1

8

1M

an

ho

le

u

pd

ate

s9

/5

/1

8

2B

id

S

et

3/2

5/2

0

SCALE: 1/64"=1'-0"

64' 32' 0 100' 200'

Str. #1

Existing: 50' pole with double circuit-3Ø tangent (N/S)

Install: 50'-2

C7A (S) (Circuit I)

UC5-1 w/ GOAB (12kV riser)

2-E1-2 L=35'N

TA-2H

M2-11

Transfer: Existing primary conductor (top - Circuit I) (S).

Remove: Existing pole, pole top units, double circuit

primary conductor (top & bottom - Circuits E & I) (N)

and all attachments.

Str. #1A

Existing: 50' pole with double circuit-3Ø tangent (N/S)

Install: 50'-2

C1-2 (no neutral) (top - Circuit I)

C7A (S) (bottom - Circuit E)

UC5-1 w/GOAB (4kV riser)

2-E1-2 L=35'N

TA-2H

M2-11

Transfer: Existing primary conductor (top - Circuit I) (N/S) &

(bottom - Circuit E) (S)

Remove: Existing pole, pole top units, primary conductor

(bottom - Circuit E) (N) and all attachments.

Str. #2

Existing: 40' pole with 3Ø tangent (N/S) and 3Ø deadend (W)

COs, down guy & anchor.

Install: 40'-2

C7A (SE)(low neutral)

C7A (W)

2-E1-2 L=35' (NW)

2-E1-2 L=35' (E)

2-TA-2H

M2-11

Transfer: Existing primary conductor (W/S) & COs.

Remove: Existing pole, pole top units, primary conductor (N),

down guy, andchor and all attachments.

Str. #2A

Existing: 40' pole with 3Ø double deadend (E/W), xfmr, CO

LA, bracket, street light, secondary, down guy

& anchor.

Install: 40'-2

C7A (E)

3-M5-24 (W)

1-M5-25 (W)

4-M42-13 (W)

UC5-1 w/ GOAB (4kV riser)

100' of #1/0 AWG triplex to Str. #2B

K14C

M2-11

Transfer: Existing primary conductor (E/W),street light &

secondary. Transfer xfmr, bracket, CO, LA to Str. #2B.

Remove: Existing pole, pole top unit, down guy, anchor and all

attachments.

Str. #2B

Existing: 40' pole with 3Ø tangent (E/W).

K14C

Str. #3

Existing: 45' pole with double circuit-3Ø tangents (E/W), area

light and secondary.

Install: 45'-2

C7A (E) (no neutral) (top - Circuit B)

3-M5-24 (W)

3-M42-13 (W)

C7A (E) (bottom - Circuit D)

3-M5-24 (W)

1-M5-25 (W)

4-M42-13 (W)

M2-11

Transfer: Existing double circuit conductor (E), area light and

secondary.

Remove: Existing pole,pole top units, double circuit primary

conductors (W) and all attachments.

Str. #3A

Install: 45'-2

C7A (E) (Circuit B)

UC5-1 w/ GOAB (4kV riser)

2-E1-2 L=35' (W)

TA-2H

M2-11

Str. #4

Existing: 45' pole with double circuit-3Ø tangent (E/W), COs

& capacitor bank.

Install: 45'-2

C1-2 (Circuit B) (no neutral)

C9-2 (E) (Circuit D)

M2-11

Transfer: Existing conductor (E/W). capacitor bank & COs.

Remove: Existing pole, pole top units and all attachments.

Str. #4A

Install: 45'-2

C1-2 (Circuit B) (no neutral)

C7A (E) (Circuit D)

UC5-1 w/ GOAB (4kV riser) (Circuit D)

2-E1-2 L=35' (W)

TA-2H

M2-11

Str. #5

Existing: 45' pole with 3Ø tangent (E/W)

Install: 45'-2

C7A (W) (Circuit D)

UC5-1 w/GOAB (4kV riser)

2-E1-2 L=35' (E)

TA-2H

M2-11

Transfer: Existing conductor (W)

Remove: Existing pole, pole top unit, primary conductor (E)

and all attachments.

Str. #6

Install: 45'-2

C7A (E) (Circuit D)

UC5-1 w/GOAB (4kV riser)

2-E1-2 L=35' (W)

TA-2H

M2-11

Str. #7A

Existing: 40' pole with 3Ø tangent (E/W)

Remove: Existing pole, primary conductor (E/W) and

all attachments.

Str. #7B

Existing: 40' pole with 3Ø tangent (E/W)

Remove: Existing pole, primary conductor (E/W) and

all attachments.

Str. #8A

Existing: 50' pole with double circuit-3Ø deadend (N/W),

down guys and anchors.

Remove: Existing pole, pole top units, primary conductor (N/W),

down guys, anchors and all attachments.

Str. #8B

Existing: 50' pole with double circuit-3Ø deadend (N/W),

3Ø deadend (E), down guys and anchors.

Transfer: Existing primary conductor (E) to Str. #9.

Remove: Existing pole, pole top units, primary conductor (N/W/E),

down guys, anchors and all attachments.

Str. #9

Existing: 40' pole with 3Ø tangent (E/W), 3Ø primary

riser, pole mount xfmr, COs, LAs, 1Ø

service riser, meter & street light.

No Change

Str. #10

Existing: 45' pole with 3Ø deadend (W), 3Ø primary

riser, down guy & anchor.

No Change

Breaker Connection inside Switchgear

Install: 9 - Terminations (3 for each breaker) for #4/0 AL UG to

NEMA 2 hole pad (Circuits A,B & E)

6 - Terminations for #4/0 AL UG to NEMA 2 hole pad (Circuit D)

(3 breaker terminations to MH-5 & 3 breaker

terminations to JB-2)

Note: Tape each breaker connection as required.

BID SET

LEGEND:

3ɸ Junction Box

New pole

Existing pole - Not being moved or replaced.

Existing pole - Being removed

New Manhole - Refer to Dwg. E-2 for Details

Existing Manhole

KEY NOTES:

1

2

Install 4-5kV feeders, (Circuits A,B,D & E), each w/ 3 phase

#4/0 AWG AL from existing breaker. Install an additional

5kV feeder (using existing spare conduit) (from Circuit D breaker),

w/ 3 phase #4/0 AWG AL, to JB-2. Abandon (1) existing spare

conduit in place.

Refer to "Switchgear Note" on drawing for conduit information.

Install new duct bank w/ 4-5kV feeders (Circuits A,B,D & E)

and 1-15kV feeder (Circuit I), each w/ 3 phase #4/0 AWG AL

in 6" conduit) and 1- spare 6" conduit.

Existing duct bank to be abandoned. Remove existing

4-5kV feeders.

Install new 6" conduit w/ 3-15kV #4/0 AWG AL.

Existing overhead conductor to be removed.

Existing overhead primary conductor to remain.

Install new 7 - 336.4kcmil ACSR conductor (double circuit).

3

4

5

6

JB-1 (field verify location)

Install: ND-450 junction box

3-600A 4pt junctions

6-600A elbows #4/0 AWG AL

6-600A insulating caps

2-UM48-2 ground

Transfer: Existing underground conductor

(Circuit I) and terminate in JB-1.

JB-2 (field verify location)

Install: ND-450 junction box (Circuit D)

3-600A 4pt junctions

9-600A elbows #4/0 AWG AL

3-600A insulating caps

2-UM48-2 ground

MH-1

Existing: Manhole location.

Remove: Existing poles, above ground conduit,

OH conductor, UG cable and

all attachments.

Note: Abandon manhole in place

MH-2

Existing: Manhole location.

Remove: UG cable.

Note: Abandon manhole in place

MH-3

Existing: Manhole location.

Remove: UG cable.

Note: Abandon manhole in place

MH-4

Existing: Manhole location.

Remove: Existing poles, above ground conduit,

OH conductor, UG cable and

all attachments.

Note: Abandon manhole in place

MH-5

Install: Precast vault (Circuits A,B,D,E & I)

15-600A 2pt junctions (Circuits A,B,D,E & I)

30-600A elbows #4/0 AWG AL

2-UM48-2 ground

MH-6

Install: Precast vault (Circuits A,B,D,E,I)

2-UM48-2 ground

SIT

E P

LA

N

7

Page 3: POWER PLANT POWER ST. - City of Red Bud, IL › uploads › 3 › 8 › 4 › 1 › ...2 Bid Set 3/25/20 BID SET COVER SHEET SPRINGFIELD, IL RED BUD, IL PROJECT: REPLACEMENT OF FIVE

ELECTRICAL

TOP VIEW

MATCH EXISTING LANDSCAPE

CONDUIT

LADDER

CONDUIT

MATCH EXISTING LANDSCAPE

PEA GRAVEL

PULL IRONS

PULL IRONS

LADDER

COMPACTED FILL

PEA GRAVEL

CAST IRON MANHOLE

CONDUIT

PULL IRON

PULL IRON

CAST IRON MANHOLE

(4) DUCT BANK KNOCKOUTS

DUCT BANK

SECTION VIEW

SECTION VIEW

2'-9"

4'

A/6'

PVC SUMP

2'

6'

6'

A/12'

CONDUIT

A/13'-4"

A/7'-4"

OPENING

OPENING

B/17'-4"

B/9

'-4"

B/8'

B/16'

1'-6"

1'-6"

2'

3'-6"

3'-6"

CONCRETE

ENCASED

SCALE

DESIGN

CHECKED

DATE

DRAWN

APPROVED

RE

VIS

IO

N/IS

SU

E

NO

.D

AT

E

SEAL

JOB NO.

SHEET OF

DRAWING NO.

E-2

3 3

Job #1904

AS NOTED7/11/18

PJH PJH

VJB VJB

RE

D B

UD

, ILLIN

OIS

RE

PL

AC

EM

EN

T O

F F

IV

E S

UB

ST

AT

IO

N

FE

ED

ER

U

ND

ER

GR

OU

ND

E

XIT

S

0C

lie

nt R

evie

w7

/1

1/1

8

1M

an

ho

le

u

pd

ate

s9

/5

/1

8

2B

id

S

et

3/2

5/2

0

BID SET

MA

NH

OL

E #

5 &

#

6 D

ET

AIL

S

NOTES:

1. DIMENSIONS MARKED WITH 'A' FOR MANHOLE #6.

DIMENSIONS MARKED WITH 'B' FOR MANHOLE #5.

2. MANHOLE #5 TO HAVE ADDITIONAL CABLE RACKING

NOT SHOWN.

AutoCAD SHX Text
3"
AutoCAD SHX Text
(TYP)
AutoCAD SHX Text
9"
AutoCAD SHX Text
3"
AutoCAD SHX Text
6" nominal conduit (6.625" actual)