POWER-LINKER GROUP CO’s RELAY STABILITY … 2.pdf4 POWER-LINKER GROUP CO’s GROUP POWER- LINKER...
Transcript of POWER-LINKER GROUP CO’s RELAY STABILITY … 2.pdf4 POWER-LINKER GROUP CO’s GROUP POWER- LINKER...
![Page 1: POWER-LINKER GROUP CO’s RELAY STABILITY … 2.pdf4 POWER-LINKER GROUP CO’s GROUP POWER- LINKER FIG : TYPICAL HIGH IMPEDANCE GENERATOR DIFFERENTIAL PROTECTION SCHEME B1 B2 B1 B2](https://reader030.fdocuments.in/reader030/viewer/2022013014/5ada4e727f8b9a137f8d4bef/html5/thumbnails/1.jpg)
1
POWER-LINKER GROUP CO’s
GROUP
POWER- LINKER
wisdom is not virtue but necessity
GROUP
POWER-LINKER
AT1ST INDIA DOBLE PROTECTION AND AUTOMATION
CONFERENCE, NOV 2008
BYMR. H. C. MEHTA & MR. JAY MEHTA
GENERATOR DIFFERENTIAL PROTECTION RELAY STABILITY VIS-A VIS SELECTION OF CTS
[email protected] www.powerlinker.org
![Page 2: POWER-LINKER GROUP CO’s RELAY STABILITY … 2.pdf4 POWER-LINKER GROUP CO’s GROUP POWER- LINKER FIG : TYPICAL HIGH IMPEDANCE GENERATOR DIFFERENTIAL PROTECTION SCHEME B1 B2 B1 B2](https://reader030.fdocuments.in/reader030/viewer/2022013014/5ada4e727f8b9a137f8d4bef/html5/thumbnails/2.jpg)
2
POWER-LINKER GROUP CO’s
GROUP
POWER- LINKER
GENERATOR DIFFERENTIAL
PROTECTION
RELAY STABILITY
VIS-À-VIS
SELECTION OF CTS
![Page 3: POWER-LINKER GROUP CO’s RELAY STABILITY … 2.pdf4 POWER-LINKER GROUP CO’s GROUP POWER- LINKER FIG : TYPICAL HIGH IMPEDANCE GENERATOR DIFFERENTIAL PROTECTION SCHEME B1 B2 B1 B2](https://reader030.fdocuments.in/reader030/viewer/2022013014/5ada4e727f8b9a137f8d4bef/html5/thumbnails/3.jpg)
3
POWER-LINKER GROUP CO’s
GROUP
POWER- LINKER
• GENERATOR DIFFERENTIAL PROTECTION (87G)
o SIMPLEST BALANCE CURRENT DIFFERENTIAL
PROTECTION :
UNTIL IT IS MESSED UP BY EXPERTS
o SIMPLE SYSTEM :
GENERALLY, HIGH IMPEDANCE SCHEME.
INSTANTANEOUS OVER CURRENT RELAY WITH STABILIZING RESISTOR
CT’S WITH CLASS-PS SPECIFICATIONS.
SCHEME PROVIDES HIGH SENSITIVITY AND SECURITY.
![Page 4: POWER-LINKER GROUP CO’s RELAY STABILITY … 2.pdf4 POWER-LINKER GROUP CO’s GROUP POWER- LINKER FIG : TYPICAL HIGH IMPEDANCE GENERATOR DIFFERENTIAL PROTECTION SCHEME B1 B2 B1 B2](https://reader030.fdocuments.in/reader030/viewer/2022013014/5ada4e727f8b9a137f8d4bef/html5/thumbnails/4.jpg)
4
POWER-LINKER GROUP CO’s
GROUP
POWER- LINKER
FIG : TYPICAL HIGH IMPEDANCE GENERATOR DIFFERENTIAL PROTECTION SCHEME
B1 B2
B1 B2
B2
Instantaneous Over Current Relay
External or Internal RStab87
B1
![Page 5: POWER-LINKER GROUP CO’s RELAY STABILITY … 2.pdf4 POWER-LINKER GROUP CO’s GROUP POWER- LINKER FIG : TYPICAL HIGH IMPEDANCE GENERATOR DIFFERENTIAL PROTECTION SCHEME B1 B2 B1 B2](https://reader030.fdocuments.in/reader030/viewer/2022013014/5ada4e727f8b9a137f8d4bef/html5/thumbnails/5.jpg)
5
POWER-LINKER GROUP CO’s
GROUP
POWER- LINKER
• PRESENT SCENARIO, & CASE STUDY
SIMPLE, RELIABLE, SENSITIVE AND SECURED
PROTECTION MADE COMPLEX AND UNRELIABLE,
BY USING :
o GENERAL PROTECTION CLASS CT’S
o LOW IMPEDANCE TYPE BIASED DIFFERENTIAL PROTECTION SCHEME.
o TRANSFORMER DIFFERENTIAL PROTECTION RELAY IN PLACE OF GENERATOR DIFFERENTIAL PROTECTION RELAY.
o RESULT : SCHEME LESS SECURED AND LESS SENSITIVE.
![Page 6: POWER-LINKER GROUP CO’s RELAY STABILITY … 2.pdf4 POWER-LINKER GROUP CO’s GROUP POWER- LINKER FIG : TYPICAL HIGH IMPEDANCE GENERATOR DIFFERENTIAL PROTECTION SCHEME B1 B2 B1 B2](https://reader030.fdocuments.in/reader030/viewer/2022013014/5ada4e727f8b9a137f8d4bef/html5/thumbnails/6.jpg)
6
POWER-LINKER GROUP CO’s
GROUP
POWER- LINKER
o LOW IMPEDANCE PROTECTION SCHEME
o GENERAL PROTECTION CLASS CTS.
?THEN WHY DO WE USE
![Page 7: POWER-LINKER GROUP CO’s RELAY STABILITY … 2.pdf4 POWER-LINKER GROUP CO’s GROUP POWER- LINKER FIG : TYPICAL HIGH IMPEDANCE GENERATOR DIFFERENTIAL PROTECTION SCHEME B1 B2 B1 B2](https://reader030.fdocuments.in/reader030/viewer/2022013014/5ada4e727f8b9a137f8d4bef/html5/thumbnails/7.jpg)
7
POWER-LINKER GROUP CO’s
GROUP
POWER- LINKER
• CASE STUDY : CHEMICAL PLANT
∆
P20
ProposedGenerator
18MW11kV
100A63.5Ω10 Sec
66kV GRID INCOMER
GTG3 Nos X 5.4MW
11kV
GEG2 Nos X 6.329MW
11kV
TR-17.5MVA66/11kV
TR-27.5MVA66/11kV
P1 P4 P6 P21
100A63.5Ω10 Sec
100A63.5Ω10 Sec
∼
100A63.5Ω10 Sec
100A63.5Ω10 Sec
∼ ∼∆
66 kV BUS
P13
2 x 9.8 MVARECTIFIER TRANSFORMER
∆
IM
11 kV BUS
6.6 kV BUS
730 kW
TR-33.5MVA
11/6.6kV
IL IL IL
293A14 Ω
10Sec
NO
FIG. : PLANT SINGLE LINE DIAGRAM
∼ ∼ ∼
![Page 8: POWER-LINKER GROUP CO’s RELAY STABILITY … 2.pdf4 POWER-LINKER GROUP CO’s GROUP POWER- LINKER FIG : TYPICAL HIGH IMPEDANCE GENERATOR DIFFERENTIAL PROTECTION SCHEME B1 B2 B1 B2](https://reader030.fdocuments.in/reader030/viewer/2022013014/5ada4e727f8b9a137f8d4bef/html5/thumbnails/8.jpg)
8
POWER-LINKER GROUP CO’s
GROUP
POWER- LINKER
∼
87
100A63.5 ohms10 Sec
400/1CL:5P1015VA
400/1CL:5P1020VA
GTG-15.4MW11kV0.8PF
FIG. : GENERATOR DIFFERENTIAL PROTECTION SCHEME
CT SPECIFICATION & SETTING RANGE
11 kV SWITCHGEAR
LOW IMPEDANCE TYPETRANSFORMER DIFFERENTIAL PROTECTIONIpu = Id>= 0.15 To 2.0 In
Slope1 = 0 – 50%, Slope2 = 0 – 100%Turn Point1 = 0 – 20 In ( Break Point)Id >> = 0.5 – 20 In
5th Harmonic Blocking = 10 to 80% Id2nd Harmonic Blocking = 10 to 80% Id
Tested ValuesVk = 275 V; Iex = 10 mAIex at Vk/2 = 4.5 mA
at Vk/4 = 2.5 mA
Tested ValuesVk = 181.5 V; Iex = 75 mAIex at Vk/2 = 14 mA
at Vk/4 = 5.5 mA
Vendor : ADesign : Vk = 200 V app
Vendor : BDesign : Vk = 150 V App
Ifl = 354 A
Cable1= 100m
Cable2
![Page 9: POWER-LINKER GROUP CO’s RELAY STABILITY … 2.pdf4 POWER-LINKER GROUP CO’s GROUP POWER- LINKER FIG : TYPICAL HIGH IMPEDANCE GENERATOR DIFFERENTIAL PROTECTION SCHEME B1 B2 B1 B2](https://reader030.fdocuments.in/reader030/viewer/2022013014/5ada4e727f8b9a137f8d4bef/html5/thumbnails/9.jpg)
9
POWER-LINKER GROUP CO’s
GROUP
POWER- LINKER
o DIFFERENT VENDOR HAVE SUPPLIED CTS FOR TWO
ENDS OF DIFFERENTIAL PROTECTION.
• DEFICIENCY IN ENGINEERED SCHEME
• BOTH CT’S HAVE GOT DIFFERENT CHARACTERISTIC.
o CT SPECIFICATION ARE INADEQUATE
o RELAY CONNECTED IS LOW IMPEDANCE TYPE,
TRANSFORMER DIFFERENTIAL PROTECTION
INSTEAD OF
GENERATOR DIFFERENTIAL PROTECTION.
![Page 10: POWER-LINKER GROUP CO’s RELAY STABILITY … 2.pdf4 POWER-LINKER GROUP CO’s GROUP POWER- LINKER FIG : TYPICAL HIGH IMPEDANCE GENERATOR DIFFERENTIAL PROTECTION SCHEME B1 B2 B1 B2](https://reader030.fdocuments.in/reader030/viewer/2022013014/5ada4e727f8b9a137f8d4bef/html5/thumbnails/10.jpg)
10
POWER-LINKER GROUP CO’s
GROUP
POWER- LINKER
• DIFFERENTIAL PROTECTION SCHEME OPERATION :
o SCHEME IS STABLE FOR STEADY STATE CONDITION
AND GENERATORS EVACUATE 100% POWER.
o SCHEME MAL – OPERATES DURING
SUDDEN LOAD THROW IN
SUDDEN LOAD THROW OFF
SWITCHING IN OF A LARGE MOTOR
o MAL – OPERATIONS ARE IN CONSISTENT.
![Page 11: POWER-LINKER GROUP CO’s RELAY STABILITY … 2.pdf4 POWER-LINKER GROUP CO’s GROUP POWER- LINKER FIG : TYPICAL HIGH IMPEDANCE GENERATOR DIFFERENTIAL PROTECTION SCHEME B1 B2 B1 B2](https://reader030.fdocuments.in/reader030/viewer/2022013014/5ada4e727f8b9a137f8d4bef/html5/thumbnails/11.jpg)
11
POWER-LINKER GROUP CO’s
GROUP
POWER- LINKER
• SCHEME TESTING :
o SIMULATED SCHEME TESTING WAS CARRIED
OUT FOR,
o EXTERNAL FAULT STABILITY AND
o INTERNAL FAULT SENSITIVITY
o TEST RESULTS WERE FOUND SATISFACTORY.
![Page 12: POWER-LINKER GROUP CO’s RELAY STABILITY … 2.pdf4 POWER-LINKER GROUP CO’s GROUP POWER- LINKER FIG : TYPICAL HIGH IMPEDANCE GENERATOR DIFFERENTIAL PROTECTION SCHEME B1 B2 B1 B2](https://reader030.fdocuments.in/reader030/viewer/2022013014/5ada4e727f8b9a137f8d4bef/html5/thumbnails/12.jpg)
12
POWER-LINKER GROUP CO’s
GROUP
POWER- LINKER
• GENERATOR DIFFERENTIAL PROTECTION RELAY
CHARACTERISTICS & SETTING RANGE :
o RELAY INSTALLED AND COMMISSIONED
o MULTIFUNCTION DIGITAL PERCENTAGE BIASED
DIFFERENTIAL PROTECTION RELAY FOR TRANSFORMER
OR GENERATOR TRANSFORMER UNIT ? ? ?
WRONG APPLICATION FOR GENERATOR DIFFERENTIAL
PROTECTION. ? ? ?
![Page 13: POWER-LINKER GROUP CO’s RELAY STABILITY … 2.pdf4 POWER-LINKER GROUP CO’s GROUP POWER- LINKER FIG : TYPICAL HIGH IMPEDANCE GENERATOR DIFFERENTIAL PROTECTION SCHEME B1 B2 B1 B2](https://reader030.fdocuments.in/reader030/viewer/2022013014/5ada4e727f8b9a137f8d4bef/html5/thumbnails/13.jpg)
13
POWER-LINKER GROUP CO’s
GROUP
POWER- LINKER
• SETTINGS FOR USER SELECTION :
o ABSOLUTE VALUE DIFFERENTIAL UNIT Ib.
o PERCENTAGE BIASED DIFFERENTIAL UNIT WITH TWO
SLOPES P1 AND P2.
o OVERCURRENT PROTECTION UNIT Id >>.
o TIME DELAY OF 20 m SEC TO 99.99 SEC PROVIDED
FOR ALL THRESHOLD VALUES ???
RELAY MANUAL INDICATES THAT THIS TIME DELAY IS
PROVIDED TO AVOID TRIPPING COMMAND TO
SWITCHGEAR IF CT SATURATES ???
![Page 14: POWER-LINKER GROUP CO’s RELAY STABILITY … 2.pdf4 POWER-LINKER GROUP CO’s GROUP POWER- LINKER FIG : TYPICAL HIGH IMPEDANCE GENERATOR DIFFERENTIAL PROTECTION SCHEME B1 B2 B1 B2](https://reader030.fdocuments.in/reader030/viewer/2022013014/5ada4e727f8b9a137f8d4bef/html5/thumbnails/14.jpg)
14
POWER-LINKER GROUP CO’s
GROUP
POWER- LINKER
DELAYING TRIP COMMAND
TO PREVENT MALOPERATION
DUE TO
CT SATURATION
IS IT CORRECT CONCEPT
? ? ?
![Page 15: POWER-LINKER GROUP CO’s RELAY STABILITY … 2.pdf4 POWER-LINKER GROUP CO’s GROUP POWER- LINKER FIG : TYPICAL HIGH IMPEDANCE GENERATOR DIFFERENTIAL PROTECTION SCHEME B1 B2 B1 B2](https://reader030.fdocuments.in/reader030/viewer/2022013014/5ada4e727f8b9a137f8d4bef/html5/thumbnails/15.jpg)
15
POWER-LINKER GROUP CO’s
GROUP
POWER- LINKER
• DIFFERENTIAL PROTECTION RELAY TRIPPING CHARACTERISTICS
P2
Where:|Id| : Differential current, |Ia|: Restraining currentIb > : Minimum differential current, In : Relay rated currentDI : Break point for slope : 2
(Intersection of P2 straight line with Id/In axis)
Non Operating Zone
Ib >
Ia /In
DI
P1
0
Relay Operates : when,Threshold : |Id|≥ Id >>Threshold Id > - Any of the following equations,|Id|≥ Ib, |Id| ≥ (P1 . |Ia|), |Id| ≥ (P2 . |Ia|-DI)
Operating ZoneSlope 2
Slope 1
|Id|
![Page 16: POWER-LINKER GROUP CO’s RELAY STABILITY … 2.pdf4 POWER-LINKER GROUP CO’s GROUP POWER- LINKER FIG : TYPICAL HIGH IMPEDANCE GENERATOR DIFFERENTIAL PROTECTION SCHEME B1 B2 B1 B2](https://reader030.fdocuments.in/reader030/viewer/2022013014/5ada4e727f8b9a137f8d4bef/html5/thumbnails/16.jpg)
16
POWER-LINKER GROUP CO’s
GROUP
POWER- LINKER
• MAL-OPERATION OF SCHEME EXPERIENCED
DURING
o SWITCHING IN OR OFF
9.8 MVA RECTIFIER TRANSFORMER.
o SWITCHING IN OF
730 KW INDUCTION MOTOR.
• TYPICAL EVENT RECORDING :
o MAL – OPERATION OF THIS DIFFERENTIAL
PROTECTION WAS RECORDED FOR A TYPICAL CASE
![Page 17: POWER-LINKER GROUP CO’s RELAY STABILITY … 2.pdf4 POWER-LINKER GROUP CO’s GROUP POWER- LINKER FIG : TYPICAL HIGH IMPEDANCE GENERATOR DIFFERENTIAL PROTECTION SCHEME B1 B2 B1 B2](https://reader030.fdocuments.in/reader030/viewer/2022013014/5ada4e727f8b9a137f8d4bef/html5/thumbnails/17.jpg)
17
POWER-LINKER GROUP CO’s
GROUP
POWER- LINKER
R-PHASE : % Slope ( P1) set at 20%
|Id| = 0.2 In , |Id| ≥ P1 X |Ia|
|Id| ≥ 0.2 X (1.07 + 0.82)2
, |Id| ≥ 0.2 X 0.945
|Id| ≥ 0.189,
Since, Id actual (0.36) ≥ 0.189
RELAY OPERATES.
400/15P10, 20VA
400/15P10, 15VA
G
Id 0.36A
Ib1 1.07A Ib2 0.82A
FIG : GTG-1 87G RELAY MAL-OPERATION
CASE : SWITCHING IN OF 9.8 MVA RECTIFIER TRANSFORMER
![Page 18: POWER-LINKER GROUP CO’s RELAY STABILITY … 2.pdf4 POWER-LINKER GROUP CO’s GROUP POWER- LINKER FIG : TYPICAL HIGH IMPEDANCE GENERATOR DIFFERENTIAL PROTECTION SCHEME B1 B2 B1 B2](https://reader030.fdocuments.in/reader030/viewer/2022013014/5ada4e727f8b9a137f8d4bef/html5/thumbnails/18.jpg)
18
POWER-LINKER GROUP CO’s
GROUP
POWER- LINKER
Y PHASE RELAY IS STABLE BECAUSE NO SPILL CURRENT FLOWS.
400/15P10, 20VA
400/15P10, 15VA
G
Id0A
Ib1 0.63A Ib2 0.64A
Y-PHASE :FIG : GTG-1 87G RELAY MAL-OPERATION
CASE : SWITCHING IN OF 9.8 MVA RECTIFIER TRANSFORMER
![Page 19: POWER-LINKER GROUP CO’s RELAY STABILITY … 2.pdf4 POWER-LINKER GROUP CO’s GROUP POWER- LINKER FIG : TYPICAL HIGH IMPEDANCE GENERATOR DIFFERENTIAL PROTECTION SCHEME B1 B2 B1 B2](https://reader030.fdocuments.in/reader030/viewer/2022013014/5ada4e727f8b9a137f8d4bef/html5/thumbnails/19.jpg)
19
POWER-LINKER GROUP CO’s
GROUP
POWER- LINKER
B PHASE RELAY IS STABLE BECAUSE NO SPILL CURRENT FLOWS.
400/15P10, 20VA
400/15P10, 15VA
G
Id 0A
Ib1 0.95A Ib2 0.96A
B-PHASE :FIG : GTG-1 87G RELAY MAL-OPERATION
CASE : SWITCHING IN OF 9.8 MVA RECTIFIER TRANSFORMER
![Page 20: POWER-LINKER GROUP CO’s RELAY STABILITY … 2.pdf4 POWER-LINKER GROUP CO’s GROUP POWER- LINKER FIG : TYPICAL HIGH IMPEDANCE GENERATOR DIFFERENTIAL PROTECTION SCHEME B1 B2 B1 B2](https://reader030.fdocuments.in/reader030/viewer/2022013014/5ada4e727f8b9a137f8d4bef/html5/thumbnails/20.jpg)
20
POWER-LINKER GROUP CO’s
GROUP
POWER- LINKER
• ANALYSIS
o SEQUENCE OF EVENT RECORDING INDICATES :
UNDER TRANSIENT CONDITION CURRENT
TRANSFORMERS ARE SATURATING.
RESULTING INTO,
• CAUSING RELAY MAL-OPERATION.
o THIS REQUIRES CHECKING DEFICIENCY IN CT
RATING SPECIFICATION.
• UNBALANCE CURRENT IN THE DIFFERENTIAL
RELAY OPERATING COIL.
![Page 21: POWER-LINKER GROUP CO’s RELAY STABILITY … 2.pdf4 POWER-LINKER GROUP CO’s GROUP POWER- LINKER FIG : TYPICAL HIGH IMPEDANCE GENERATOR DIFFERENTIAL PROTECTION SCHEME B1 B2 B1 B2](https://reader030.fdocuments.in/reader030/viewer/2022013014/5ada4e727f8b9a137f8d4bef/html5/thumbnails/21.jpg)
21
POWER-LINKER GROUP CO’s
GROUP
POWER- LINKER
• SPECIFICATION OF CURRENT TRANSFORMER INSTALLED AND COMMISSIONED:
FIELD TEST VALUESDESIGN VALUE
FIELD TEST VALUESDESIGN VALUE
Vk = 181.5 V, Iex = 75 mA
Iex at Vk/2 = 14 mAIex at Vk/4 = 5.5 mA
CTR: 400/1
CL: 5P10, 15VA
Design Vk = 150V App.
o VENDOR B : PHASE END
Vk = 275 V, Iex = 10 mA
Iex at Vk/2 = 4.5 mA
Iex at Vk/4 = 2.5 mA
CTR: 400/1
CL: 5P10, 20VA
Design Vk = 200V App.
o VENDOR A : NEUTRAL END
![Page 22: POWER-LINKER GROUP CO’s RELAY STABILITY … 2.pdf4 POWER-LINKER GROUP CO’s GROUP POWER- LINKER FIG : TYPICAL HIGH IMPEDANCE GENERATOR DIFFERENTIAL PROTECTION SCHEME B1 B2 B1 B2](https://reader030.fdocuments.in/reader030/viewer/2022013014/5ada4e727f8b9a137f8d4bef/html5/thumbnails/22.jpg)
22
POWER-LINKER GROUP CO’s
GROUP
POWER- LINKER
• REVIEW OF SPECIFICATION OF CTS & FIELD TEST
RESULTS
o DESIGNED CT SECONDARY VOLTAGES ARE WIDELY DIFFERENT
200 & 150 V FOR EITHER END CTS.
o TESTED VALUE OF KNEE POINT VOLTAGE FOR EITHER END CT’S HAVE HIGH DIFFERENCE.
275 V AND 181 V FOR EITHER END CTS.
o EXCITATION CURRENT ALSO HAS LARGE DIFFERENCE
AT VK/2 – 4.5 mA & 14 mA
AT VK/4 – 2.5 mA & 5.5 mA
![Page 23: POWER-LINKER GROUP CO’s RELAY STABILITY … 2.pdf4 POWER-LINKER GROUP CO’s GROUP POWER- LINKER FIG : TYPICAL HIGH IMPEDANCE GENERATOR DIFFERENTIAL PROTECTION SCHEME B1 B2 B1 B2](https://reader030.fdocuments.in/reader030/viewer/2022013014/5ada4e727f8b9a137f8d4bef/html5/thumbnails/23.jpg)
23
POWER-LINKER GROUP CO’s
GROUP
POWER- LINKER
• LARGE DIFFERENCE IN SATURATION
o VOLTAGE (KPV)
o EXCITATION CURRENT IEX , AT THE SATURATION
VOLTAGE IS THE REASON FOR,
DIFFERENTIAL CURRENT THROUGH OPERATING
COIL, THUS MAL-OPERATION OF RELAY.
![Page 24: POWER-LINKER GROUP CO’s RELAY STABILITY … 2.pdf4 POWER-LINKER GROUP CO’s GROUP POWER- LINKER FIG : TYPICAL HIGH IMPEDANCE GENERATOR DIFFERENTIAL PROTECTION SCHEME B1 B2 B1 B2](https://reader030.fdocuments.in/reader030/viewer/2022013014/5ada4e727f8b9a137f8d4bef/html5/thumbnails/24.jpg)
24
POWER-LINKER GROUP CO’s
GROUP
POWER- LINKER
• DESIRED CT SPECIFICATION :
SPECIFIC REQUIREMENT OF CURRENT TRANSFORMER
SECONDARY VOLTAGE
∼
87
63.5 ohm100A
400/1
GTG-1,2,36750 kVA
11kV, 50 Hz0.8PF
400/1
Maximum through fault current = 1.865 kA
FIG : ACTUAL REQUIREMENT OF C.T. SPECIFICATION
X’d = 30.4%X”d = 19%
IFL = 354.3A
![Page 25: POWER-LINKER GROUP CO’s RELAY STABILITY … 2.pdf4 POWER-LINKER GROUP CO’s GROUP POWER- LINKER FIG : TYPICAL HIGH IMPEDANCE GENERATOR DIFFERENTIAL PROTECTION SCHEME B1 B2 B1 B2](https://reader030.fdocuments.in/reader030/viewer/2022013014/5ada4e727f8b9a137f8d4bef/html5/thumbnails/25.jpg)
25
POWER-LINKER GROUP CO’s
GROUP
POWER- LINKER
• CT SPECIFICATIONS FOR 87 RELAY
FAULT MVA = 100 x 6.75
19
= 35.52 MVA
FAULT CURRENT = 1865 AMPS
@ 11 kV BASE
![Page 26: POWER-LINKER GROUP CO’s RELAY STABILITY … 2.pdf4 POWER-LINKER GROUP CO’s GROUP POWER- LINKER FIG : TYPICAL HIGH IMPEDANCE GENERATOR DIFFERENTIAL PROTECTION SCHEME B1 B2 B1 B2](https://reader030.fdocuments.in/reader030/viewer/2022013014/5ada4e727f8b9a137f8d4bef/html5/thumbnails/26.jpg)
26
POWER-LINKER GROUP CO’s
GROUP
POWER- LINKER
o CRITERIA I :
CONSIDERING EXTERNAL THROUGH FAULT CURRENT
RLEAD = 0.8 Ω FOR 100 MTRS. (8Ω/KM)
OR
VK ≥ 2 IF (RCT + 2RL +RR)
CTR
≥ 2 X 1865 (RCT + 2X 0.8 +0)
400
≥ (9.325 RCT + 15 V)
![Page 27: POWER-LINKER GROUP CO’s RELAY STABILITY … 2.pdf4 POWER-LINKER GROUP CO’s GROUP POWER- LINKER FIG : TYPICAL HIGH IMPEDANCE GENERATOR DIFFERENTIAL PROTECTION SCHEME B1 B2 B1 B2](https://reader030.fdocuments.in/reader030/viewer/2022013014/5ada4e727f8b9a137f8d4bef/html5/thumbnails/27.jpg)
27
POWER-LINKER GROUP CO’s
GROUP
POWER- LINKER
o CRITERIA II : CHARGING CURRENT OF RECTIFIER TRANSFORMERFULL LOAD CURRENT = 9800 KVA = 514.4 A
√3 X 11X 103
CHARGING CURRENT, SAY MAX 12 X FULL LOAD = 6180 A
Vk ≥ 2 x 6180(RCT+ 2 x 0.8 + 0) 400
≥ 30.9 RCT + 49.44
Select Vk ≥ (31 RCT + 50)V,
Iex @VK /4 = 0.15 Min Pickup x 0.8 2
= 60 m Amp ≥ 60 m Amp.
![Page 28: POWER-LINKER GROUP CO’s RELAY STABILITY … 2.pdf4 POWER-LINKER GROUP CO’s GROUP POWER- LINKER FIG : TYPICAL HIGH IMPEDANCE GENERATOR DIFFERENTIAL PROTECTION SCHEME B1 B2 B1 B2](https://reader030.fdocuments.in/reader030/viewer/2022013014/5ada4e727f8b9a137f8d4bef/html5/thumbnails/28.jpg)
28
POWER-LINKER GROUP CO’s
GROUP
POWER- LINKER
• RECOMMENDED SPECIFICATION :
VK ≥ (31 RCT + 50)V,
IEX @ VK /4 = 60 m AMP.
o ESTABLISHED THAT DUE TO INADEQUACY OF
CURRENT TRANSFORMER RATING SPECIFICATION
THE CTS WERE SATURATING.
o RESULTING INTO MAL-OPERATION OF THE SCHEME.
![Page 29: POWER-LINKER GROUP CO’s RELAY STABILITY … 2.pdf4 POWER-LINKER GROUP CO’s GROUP POWER- LINKER FIG : TYPICAL HIGH IMPEDANCE GENERATOR DIFFERENTIAL PROTECTION SCHEME B1 B2 B1 B2](https://reader030.fdocuments.in/reader030/viewer/2022013014/5ada4e727f8b9a137f8d4bef/html5/thumbnails/29.jpg)
29
POWER-LINKER GROUP CO’s
GROUP
POWER- LINKER
• DEFICIENCY IN RELAY SELECTION AND RELAY PROGRAMMING :
o PERCENTAGE BIASED TRANSFORMER DIFFERENTIAL
(MIN BIAS 20%) PROTECTION RELAY IS UTILIZED.
o CHARACTERISTICS IS LOW IMPEDANCE TYPE.
o RELAY IS LESS SECURED, RELAY OPERATES FOR
SPILL CURRENT FLOWING THROUGH OPERATING
COIL UNDER TRANSIENT CONDITION DUE TO CT
SATURATION.
o RELAY IS LESS SENSITIVE.
![Page 30: POWER-LINKER GROUP CO’s RELAY STABILITY … 2.pdf4 POWER-LINKER GROUP CO’s GROUP POWER- LINKER FIG : TYPICAL HIGH IMPEDANCE GENERATOR DIFFERENTIAL PROTECTION SCHEME B1 B2 B1 B2](https://reader030.fdocuments.in/reader030/viewer/2022013014/5ada4e727f8b9a137f8d4bef/html5/thumbnails/30.jpg)
30
POWER-LINKER GROUP CO’s
GROUP
POWER- LINKER
• CONCLUSION :
• SCHEME WAS MALOPERATING DUE TO
o GENERAL PROTECTION CLASS CT’S.
o LOW IMPEDANCE SCHEME PROTECTION RELAY NOT
PREFERRED FOR GENERATOR DIFFERENTIAL
PROTECTION TO ENSURE,
o HIGHER SENSITIVITY &
o HIGHER SECURITY AGAINST EXTERNAL FAULT.
![Page 31: POWER-LINKER GROUP CO’s RELAY STABILITY … 2.pdf4 POWER-LINKER GROUP CO’s GROUP POWER- LINKER FIG : TYPICAL HIGH IMPEDANCE GENERATOR DIFFERENTIAL PROTECTION SCHEME B1 B2 B1 B2](https://reader030.fdocuments.in/reader030/viewer/2022013014/5ada4e727f8b9a137f8d4bef/html5/thumbnails/31.jpg)
31
POWER-LINKER GROUP CO’s
GROUP
POWER- LINKER• RECOMMENDATIONS :
TO ENSURE STABILITY AND RELIABILITY
o CTS WITH CLASS PS SPECIFICATIONS FOR GENERATOR DIFFERENTIAL AND/OR FOR ANY DIFFERENTIAL (BALANCE CURENT PROTECTION) TO BE USED.
o EVEN IF RELAYS ARE PROVIDED WITH FEATURE TO DETECT CURRENT TRANSFORMER SATURATION AND BLOCK THE RELAY,
SELECT CT’S OF CLASS PS SPECIFICATIONS
o CONSIDER HIGH IMPEDANCE DIFFERENTIAL PROTECTION SCHEME TO ENSURE
HIGH SENSITIVITY OF PROTECTION
HIGH SECURITY FOR EXTERNAL FAULT AND TRANSIENT DISTURBANCES
![Page 32: POWER-LINKER GROUP CO’s RELAY STABILITY … 2.pdf4 POWER-LINKER GROUP CO’s GROUP POWER- LINKER FIG : TYPICAL HIGH IMPEDANCE GENERATOR DIFFERENTIAL PROTECTION SCHEME B1 B2 B1 B2](https://reader030.fdocuments.in/reader030/viewer/2022013014/5ada4e727f8b9a137f8d4bef/html5/thumbnails/32.jpg)
32
POWER-LINKER GROUP CO’s
GROUP
POWER- LINKER
B1 B2
B1 B2
B2
Instantaneous Over Current Relay
External or Internal RStab87
B1
GOOD OLD SECURED, RELIABLE HIGH IMPEDANCE DIFFERENTIAL PROTECTION SCHEME
![Page 33: POWER-LINKER GROUP CO’s RELAY STABILITY … 2.pdf4 POWER-LINKER GROUP CO’s GROUP POWER- LINKER FIG : TYPICAL HIGH IMPEDANCE GENERATOR DIFFERENTIAL PROTECTION SCHEME B1 B2 B1 B2](https://reader030.fdocuments.in/reader030/viewer/2022013014/5ada4e727f8b9a137f8d4bef/html5/thumbnails/33.jpg)
33
POWER-LINKER GROUP CO’s
GROUP
POWER- LINKER
![Page 34: POWER-LINKER GROUP CO’s RELAY STABILITY … 2.pdf4 POWER-LINKER GROUP CO’s GROUP POWER- LINKER FIG : TYPICAL HIGH IMPEDANCE GENERATOR DIFFERENTIAL PROTECTION SCHEME B1 B2 B1 B2](https://reader030.fdocuments.in/reader030/viewer/2022013014/5ada4e727f8b9a137f8d4bef/html5/thumbnails/34.jpg)
34
POWER-LINKER GROUP CO’s
GROUP
POWER- LINKER
GROUP
POWER-LINKER POWER - LINKERS
Times Square, 602B, “B” Wing,
Near Marol Metro Station,
Andheri (E), Mumbai-400 059, India.
E-Mail : [email protected]
Website : www.powerlinker.org