POWER GRID COMPANY OF BANGLADESH LIMITED BIDDING …
Transcript of POWER GRID COMPANY OF BANGLADESH LIMITED BIDDING …
POWER GRID COMPANY OF BANGLADESH LIMITED BIDDING DOCUMENT
FOR Design, Supply, Erection, Testing & Commissioning of 400/230kV Meghnaghat AIS
Substation on Turnkey Basis (Bid Identification No.: PGCB/DCMPGSP/BD-P81/SS/01)
Addendum No. 2
Following revisions/changes are made in the bidding documents which will form part of the bidding documents:
1. Volume 3, Schedule A, top of the page 5SA is modified and in Schedule B pages were missing. The attachment 1 contains these modifications.
2. Volume3, Schedule I Drawings and Documents SI-6, Item 2.5 is modified as follows:
2.5 Following type test certificates of the equipment of similar or higher specifications (higher voltage & capacity) as per relevant IEC with the bid (i) Power Transformer / Shunt Reactor (a) Test of temperature rise (b) Lightning impulse test, Long duration induced AC voltage test (ACLD) and Separate source AC withstand voltage test (c) Short-circuit tests or Short-circuit Calculations (Not applicable for Shunt Reactors) (The calculation shall be verified by independent certified authority.)
3. Volume 3, APPENDIX A8SCHEDULE OF TECHNICAL REQUIREMENTS OF
SUBSTATION AUTOMATION SYSTEM Item 2. Detailed requirements, Dimensions of cubicle, Floor load N/m2 max.600 is changed to: max. 6000
SA- Introduction & preamble to the price & technical schedules 1
ADDENDUM 2 – ATTACHMENT 1
POWER GRID COMPANY OF BANGLADESH LIMITED
BIDDING DOCUMENT FOR
DESIGN, SUPPLY, ERECTION, TESTING, EXPANSION& COMMISSIONING OF 400/230 kV AIR INSULATED SWITCHGEAR (AIS) SUBSTATION AND EXISTING SWITCHING STATION AT NEW MEGHNAGHAT ON TURNKEY BASIS
SCHEDULE A
INTRODUCTION & PREAMBLE TO THE PRICE & TECHNICAL SCHEDULES
BRIEF DESCRIPTION OF THE WORKS
The bidder shall be deemed to have visited site, inspected, gathered data and verified details of the as-built system in order to design, supply and interface their new equipment. All necessary materials, adjustments, dismantling, re-routing, temporary, remedial and tiding-up work in order to complete the work specified shall be included in the contract price. The contractor is responsible for ensuring that all and/or and any item(s) of work required for the safe, efficient and satisfactory completion and functioning of the works, are included in the Bid Price whether they be described in the specification or not. The scope of work comprises the following: - DESCRIPTION OF WORKS
The brief description of works under this contract is as follows:
1. Meghnaghat 400/230kV Air insulated Substation
The scope of works under this turnkey contract is design, supply, delivery, installation, testing & commissioning of outdoor type AIS 400/230kV substation by expanding the existing Meghnaghat 230kV switching station. The following is a brief description of the scope of works, and details are described in the subsequent sections of the Bidding Documents. 1) 400kV Switchyard (1 and 1/2 circuit breaker scheme)
— Four (4) overhead line bays to connect two (2) 400 kV double circuit lines (Madunaghat-1 & 2 and Aminbazar-1 & 2 ),
— Two (2) transformer bays for two (2) sets of 3-phase 400/235/33kV, 750MVA auto transformers,
— Two (2) 400kV IPP (Independent Power Producer) line bays — Space for future extension of four (4) 400kV diameters, comprising:
SA- Introduction & preamble to the price & technical schedules 2
Space for future extension of four (4) 400kV overhead line bays & Space for future extension of two (2) 400kV transformer bays Space for future extension of two (2) 400kV IPP line bays.
— Two (2) shunt reactor bays with two (2) sets of 3-phase 400kV, 40MVAR shunt reactors, connected on the line side.
2) Transformer Yards
— Two (2) sets of 3-phase , 400/235/33kV, 750MVA auto transformers with 33kV switchgears,
— Space for two (2) 400/235/33kV, 750MVA auto transformers yard for future provision,
— Two (2) station transformers with the capacity of 3-phae, 33/0.415kV, 500kVA.
3) 230kV Switchyard (1 and 1/2 circuit breaker scheme)
— Two (2) 230 kV line bays to connect two (2) 230 kV overhead lines (Shyampur-1 &2),
— Two (2) transformer bay for 230kV side of 400/235/33kV, 750MVA auto transformers,
— Space for future extension of six (6) 230kV overhead/underground line bays and two (2) transformer bays for 230kV side of 400/235/33kV, 750MVA auto transformer,
— Two (2) bus section bays connecting the new and the existing 230kV switching station,
— 230kV busbar interconnection to the existing 230kV Switching Station, and re-configuration of entire 230kV busbar protection,
The scope of work also includes associated control, protection, fiber optic multiplexer equipment for communication & protection, substation automation, digital fault & disturbance recorder (DFDR), station power facilities, including towers and gantry structures, relocation of transmission lines and relevant accessories , re-configuration of existing 230kV Switching station operation and protection function, and associated civil works for switchyards, two storied Main Control Building, two (2) 400kV Switchyard Panel Rooms (SPR) and two (2) 230kV SPRs to accommodate protection and control IED and associated equipment, local control kiosks, 33kV tertiary equipment, cable trenches, water supply & sewerage, security wall, fences, access road & internal roads, security guard stations, and all other necessary substation facilities and supply of mandatory spare parts and maintenance & special tools. The scope of works shall also include two (2) Three-Phase Shunt Reactors with its capacity size for each line and associated air-insulated switchgears including all necessary works and services if the EMTP study result confirms the shunt reactors are necessary. The details of EMTP study that shall be performed by the Contractor is specified in section 16, Volume 2 of 3 of the Bidding Documents. The scope of work may also include the insulation co-ordination based on EMTP study with surge arrestors, Point-on-Wave device, and PIRs for each busbar and associated gas- and air-insulated switchgears. The scope of works includes all
SA- Introduction & preamble to the price & technical schedules 3
necessary works and services if the EMTP study result confirms surge arresters, Point-on-Wave, and PIR are necessary to mitigate surges to transmission lines, busbars, and transformers. The “Schedule of Requirements” for equipment, materials and services and the detailed technical specifications of equipment and materials of the Bidding Documents shall be read in conjunction with the scope of work described herein. The drawings provided in the Bidding Documents are indicative only and hence the entire scope of work is not fully reflected in those drawings.
The Programme of Works shall be as shown in Schedule C of Times for Delivery and Completion. Within one month of the signing of the Contract, the Contractor shall submit a programme chart detailing times required for the design, manufacture, testing, delivery and erection for the complete contract. The Contractor is responsible for ensuring that all and any items of work required for the safe, efficient and satisfactory completion and functioning of the works, are included in the Bid price whether they be described in the Specifications or not.
2. Training and Inspection:
The Contract Price shall include all costs of training & inspection of Employers and the instruction of staff on site for the following:
(a) International Training: the following engineers nominated by the Employer shall be
provided with training at specialist manufacturer's works as follows: SN description No/
engineer Duration (Week)
1 Control, protection & SAS 2 2 2 SCADA, telecommunication system
including multiplexer and PABX 2 2
3 HV AIS substation & equipment design 4 2 4 Operation and maintenance of HVAIS
substation equipment 8 2
(b) International Witnessing: the following engineers nominated by the Employer shall
participate in the inspection and witnessing of factory acceptance tests at manufacturers' works as follows* SN description No/ engineer Consultant Duration
(working days) 1 Transformers 2 1 10 2 Shunt reactor 2 1 7 3 Circuit breaker 2 - 5 4 disconnector 2 - 5 5 Instrument transformer 2 (1 for CT
& 1 for PT) - 5
6 lightning arrester 2 - 5 7 Control, Protection & SAS system 2 1 5 8 DC system 1 - 3
SA- Introduction & preamble to the price & technical schedules 4
(c) Local Training: On-site instruction by the manufacturer’s engineer on operations
and maintenance of the (i) Substation facilities including HV AIS Substation equipment & transformers (ii) control, protection & Substation automation system (iii) fiber optic multiplexer & digital PABX for a period of two (2) weeks and for fifteen (15) PGCB engineers in each program.
The Contractor shall be responsible for bearing all costs for the trainees (for item (a)), including but not limited to air fares, accommodation, meal, healthcare, transportation, visa fees together with payment of a daily allowance of US$ 70 for each of the Employer's trainee. The Employer's engineer & consultant attending the Pre-shipment inspection (as mentioned in item (b) shall be provided with the same facilities except the payment of daily allowance which is to be US$ 100.
3. Employer’s Engineer’s Site Office
The Contractor shall provide office accommodation as per clause 12.1.9 of Section 12, Volume 2 during the Contract period. The Employer’s Engineer’s Office at site or nearest town shall be an independent house or building with 2000ft^2 , three (3) bed rooms, a meeting room (20 attendants), kitchen, sanitary facilities (toilet, bathroom etc.) and car parking for three (3) vehicles at the adequate place of the office. The Office shall also be provided with air conditioners, three (3) sets of desks and chairs, a bookshelf, a meeting table with twenty (20) chairs. Security guard services for the Employer’s Engineer’s Office for full-date basis shall also be provided. This Bidding Documents is for the design, manufacture, quality assurance, new packing for export, insurance, shipment, custom clearance, inland transportation to site, complete construction and installation, jointing, terminating, bonding, earthing, painting, setting to work, site testing and commissioning including civil work and building services, warranty for a period of three-hundreds and sixty-five (365) days for all equipment, including all civil works.
SA- Introduction & preamble to the price & technical schedules 5
SCHEDULE A REQUIREMENTS Section-I 400/230kV AIS Substation
The equipment to be designed, supplied, installed, tested & commissioned as stipulated in bid specification and shown in bid drawings (volume 2 of 3):
1) PGCB SCOPE WITHOUT EQUIPMENT FOR IPP POWER PLANTS
Item Description 1A 420 kV Air Insulated Switchgear (AIS)
The 420kV AIS shall comply with the particular requirements as detailed in the Schedule of Technical Requirements included as Appendix A1 to this section and shall comprise the following:-
1A1 Six (6) sets of 420kV, 4000A, 50kA/1sec, 50Hz, 1425kVp BIL, gang operated SF6 gas circuit breakers with spring-stored energy operating mechanism or spring-hydraulic operating mechanism.
CSD (Control Switching Device) is required for transformer switching. The breaker shall be either live tank type or dead tank type. In case of dead tank type breaker the bidder need not to quote against the item 1A7 below (CT), In case of live tank type breaker the bidder shall quote against the item 1A7 below (CT).
1A2 Four (4) sets of 420kV, 4000A, 50kA/1sec, 50Hz, 1425kVp BIL, single-
phase operation, SF6 gas circuit breakers with spring-stored energy operating mechanism or spring-hydraulic operating mechanism.
CSD or Pre insertion resistor (PIR) is required for line circuit breaker. In the case where one diameter consists one line with PIR and transformer bay with CSD, the Mid. Breaker shall be equipped with PIR & also shall be controlled by CSD. In the case where one diameter consists one line with only CSD and transformer bay with CSD, the Mid. Breaker shall be controlled by CSD.
The breaker shall be either live tank type or dead tank type. In case of dead tank type breaker the bidder need not to quote against the item 1A7 below (CT), In case of live tank type breaker the bidder shall quote against the item 1A7 below (CT).
1A3 Four (4) sets of 420kV, 4000A, 50kA/1sec, 50Hz, 1425kVp BIL,
horizontal double side break, post type, motor operated disconnectors with motor-operated earthing switch.
1A4 Twenty (20) sets of 420kV, 4000A, 50kA/1sec, 50Hz, 1425kVp BIL,
horizontal double side break, post type, motor operated disconnectors without
SA- Introduction & preamble to the price & technical schedules 6
earthing switch. 1A5 Two (2) sets of 420kV, 2000A, 50kA/1sec, 50Hz, 1425kVp BIL, horizontal double side break, post type, motor operated disconnectors without earthing switch. 1A6 Two (2) sets of 420kV, 50Hz, 1425kVp BIL, post type, motor operated
busbar grounding switches. 1A7 Forty two (42) nos. of single-phase, 6-core, 420kV, 50kA/1sec,
4000A/1A, 50Hz, 1425kVp BIL, post type current transformer. 1A8 Twenty four (24) nos. of single-phase, 3 secondary windings, 420kV,
50kA/1sec, 50Hz, 1425kVp BIL, capacitor type voltage transformers. 1A9 Thirty (30) nos. of 390kV rated voltage, 303kV(rms) continuous
operating voltage at 50oC, 10kA nominal discharge current, 50Hz, Heavy duty station class, gapless metal oxide type, single phase surge arresters.
1A10 Eight (8) nos. of wave trap (single phase, 420kV, 4000A, 1mH). 1A11 Three (3) nos of 420kV post type support insulators required for
completing 420kV busbar and switchgear as specified in the technical specifications and bid drawings.
1A12 One (1) lot of Rigid tubular bus [Aluminum of grade 63401 WP], for
completing 420kV busbar as specified in the technical specifications and bid drawings. Bus capacity shall be 4000A and calculation is required for the confirmation of the above bus capacity during execution. Any busbar supporting insulator shall be included.
1A13 One (1) lot of Rigid tubular bus [Aluminum of grade 63401 WP], flexible
conductors, insulators, fittings including all necessary clamps and connectors required for completing 420kV switchgear connection as specified in the technical specifications and bid drawings. 400kV line bay shall have the capacity of 4000A, transformer bay shall have the capacity of 2000A and diameter (switchgear) connection shall have the capacity of 4000A. Calculation is required for the confirmation of the above connector capacity during execution.
1A14 One (1) lot of Steel structures for gantry and equipment supports
required for completing 420kV busbar and switchgear as specified in the technical specifications and bid drawings.
1B 245kV Air Insulated Switchgear (AIS)
The 245kV AIS shall comply with the particular requirements as detailed in the Schedule of Technical Requirements included as Appendix A1 to this section and shall comprise the following:-
1B1 Six (6) sets 245kV, 3000A, 50kA/1sec, 50Hz, 1050kVp BIL, gang
SA- Introduction & preamble to the price & technical schedules 7
operated, SF6 gas circuit breakers with spring-stored energy operating mechanism for diameter.
The breaker shall be either live tank type or dead tank type. In case of dead tank type breaker the bidder need not to quote against the item 1B7 & 1B8 below (CT), In case of live tank type breaker the bidder shall quote against the item 1B7 below (CT).
1B2 Two (2) sets of 245kV, 3000A, 50kA/1sec, 50Hz, 1050kVp BIL, single-
pole operation, SF6 gas circuit breakers with spring-stored energy operating mechanism for bus sectionalizing. The breaker shall be either live tank type or dead tank type. In case of dead tank type breaker the bidder need not to quote against the item 1B7 & 1B8 below (CT), In case of live tank type breaker the bidder shall quote against the item 1B8 below (CT).
1B3 Two (2) sets of 245kV, 2000A, 50kA/1sec, 50Hz, 1050kVp BIL, double
side break, post type, motor operated disconnectors with motor-operated earthing switch.
1B4 Sixteen (16) sets of 245kV, 3000A, 50kA/1sec, 50Hz, 1050kVp BIL,
double side break, post type, motor operated disconnectors without earthing switch.
1B5 Two(2) sets of 245kV, 2000A, 50kA/1sec, 50Hz, 1050kVp BIL, double
side break, post type, motor operated disconnectors without earthing switch. 1B6 Two (2) sets of 245kV, 50Hz, 1050kVp BIL, post type, motor operated
busbar grounding switches. 1B7 Twenty four (24) nos. of single-phase, 5-core, 245kV, 3000/1A,
50kA/1sec, 50Hz, 1050kVp BIL, post type current transformer. 1B8 Twelve (12) nos. of single-phase, 2-core, 245kV, 3000/1A, 50kA/1sec,
50Hz, 1050kVp BIL, post type current transformer. 1B9 Eighteen (18) nos. of single-phase, 3 secondary windings, 245kV,
50kA/1sec, 50Hz, 1050kVp BIL, capacitor type voltage transformers. 1B10 Eighteen (18) nos. of 196kV rated voltage, 160kV(rms) continuous
operating voltage at 50oC 10kA nominal discharge current, 50Hz, Heavy duty station class, gapless metal oxide type, single phase surge arresters.
1B11 Deleted 1B12 Three (3) nos. of 245kV post type support insulators required for
completing 245kV busbar and switchgear as specified in the technical specifications and bid drawings.
1B13 One (1) lot of Rigid tubular bus [Aluminum of grade 63401 WP], for
completing 245kV busbar as specified in the technical specifications and bid
SA- Introduction & preamble to the price & technical schedules 8
drawings. Bus capacity shall be 3000A and calculation is required for the confirmation of the above bus capacity during execution. Any busbar supporting insulator shall be included.
1B14 One (1) lot of Rigid tubular bus [Aluminum of grade 63401 WP],
flexible conductors, insulators, fittings including all necessary clamps and connectors required for completing 245kV switchgear connection and for completing interconnection between existing 230kV switchyard and new 230kV switchyard, as specified in the technical specifications and bid drawings. 230kV line bay shall have the capacity of 3000A, transformer bay shall have the capacity of 2000A and diameter (switchgear) & bus section connection shall have the capacity of 3000A. Calculation is required for the confirmation of the above connector capacity during execution.
1B15 One (1) lot of Steel structures for gantry and equipment supports
required for completing 245kV busbar and switchgear including interconnection between existing 2230kV switchyard and new 230kV switchyard, as specified in the technical specifications and bid drawings.
1B16 One (1) lot of complete design, supply and construction including
necessary overhead lines, fittings, gantry structures, intermediate 2-circuit and 4-circuit towers, and conductors for interconnection between auto transformer & newly built 230kV bus.
1C Deleted 1D 36kV Air Insulated Switches and Connection for Earthing /
Auxiliary Transformers
The 36kV Switchgear shall comply with the particular requirements as detailed in the Schedule of Technical Requirements included as Appendix A1 to this section and shall comprise the following:-
1D1 Two (2) sets of 36kV, 630A, 31.5kA/1sec, 50Hz, 170kVp BIL, SF6 gas or
vacuum circuit breakers with spring-stored energy operating mechanism. 1D2 Four (4) sets of 36kV, 630A, 31.5kA/1sec, 50Hz, 170kVp BIL, single vertical
break, post type, motor operated disconnectors. 1D3 Six (6) nos. of single-phase, 2-secondary windings (33/√3kV / 110/√3V /
110/√3V), 36kV, 31.5kA/1sec, 50Hz, 170kVp BIL, inductive voltage transformers.
1D4 Six (6) nos. of 30kV rated voltage, 10kA nominal discharge current, 50Hz,
Heavy duty station class, single phase surge arresters. 1D5 Tertiary side connection between 36kV terminal to switches including
necessary fittings, structures, conductors and 36kV XLPE cable etc. for 2 sets of 400/235/33kV Auto transformer and 33/0.415kV Earthing/Auxiliary transformer.
SA- Introduction & preamble to the price & technical schedules 9
1E Power Transformers & Earthing/Auxiliary Transformers 1E1 Deleted 1E2 Two (2) nos. of 400/235/33 kV, 500/750 MVA (ONAN/ONAF), three
phase outdoor type auto transformer, equipped with the delta connected 33 kV tertiary winding (brought out to terminal bushings) for the purpose of supplying the substation auxiliary power requirements.
1E3 Two (2) nos. of 33/0.415 kV, 500kVA three phase outdoor type
earthing/auxiliary Zig-Zag transformers with associated steel support structures including all necessary connections.
1F Control, Protection, Substation Automation & Metering
400 kV Circuits
The equipment to be supplied, installed and commissioned is shown in bid drawings are comprising of:-
1F1 Control, Monitoring, Protection & Substation Automation System
including event recording function for four (4) sets of overhead line circuits to Ashuganj (Aminbazar-1 & 2 and Madunaghat-1 & 2).
1F2 Control, Monitoring, Protection & Substation Automation System
including event recording function for two (2) sets of 400/235/33kV three phase, auto transformer circuits including transformer tap changer control, fan control & AVR as per 4.15 of section 4 and 5.12.12 of section 5 in volume 2 of 3.
1F3 One (1) set of Busbar protection for 400kV system. 1F4 Tariff metering panel to accommodate programmable & recordable
digital 3-phase, 4 wire import and export MWh and MVArh meters (accuracy class 0.2) for each 400kV line and transformer feeders. For each feeder minimum two meters (main & check) including one set software and communication cord. Substation Automation System shall include monitoring of the metering for all the bays. Tariff Metering is to be supplied from Europe, USA or Japan origin. Printed catalogue, operation and service manual are to be provided.
1F5 Independent standalone Digital Fault and Disturbance recorder (DFDR)
to monitor complete substation including all bays & shunt reactor section as per drawing.
230 kV Circuits
The equipment to be supplied, installed and commissioned is shown in bid drawings are comprising of:-
1F6 Control, Monitoring, Protection & Substation Automation System
SA- Introduction & preamble to the price & technical schedules 10
including event recording function for Two (2) sets of overhead line circuits of Shyampur line 1&2.
1F7 Control, Monitoring, Protection & Substation Automation System
including event recording function for two (2) sets of 400/235/33 kV three phase, auto transformer circuits as per 5.12.12 of section 5 in volume 2 of 3.
1F8 One (1) set of Busbar protection for new 230kV system considering
sectionalizer and busbar synchronizers, including secondary wiring in the existing 230kV SS.
1F9 Tariff metering panel to accommodate programmable & recordable
digital 3-phase,4wire import and export MWh and MVArh meters (accuracy class 0.2) for each 230 kV line and transformer feeders. For each feeder minimum two meters (main & check). Substation Automation System shall include the metering for all the bays. Tariff Metering is to be supplied from Europe, Canada, USA or Japan origin. Printed catalogue, operation and service manual are to be provided.
1F10 Independent standalone Digital Fault and Disturbance recorder (DFDR)
to monitor complete substation including all bays section and shunt reactor section as per specification & drawing.
33kV Station Power System
1F11 Control, Monitoring, Protection & Substation Automation System
including event recording function for 33kV station power system. Substation Automation System shall include 33kV side control & protection and tariff metering for 0.415kV side. Tariff Metering for 0.415kV side is to be supplied from Europe, Canada, USA or Japan origin. Printed catalogue, operation and service manual are to be provided.
1G Multicore Cables 1G1 One (1) lot of complete set of multicore low voltage XLPE insulated
power and control cables (IEC 60502) shall be supplied, installed, glanded, terminated and have individual cores identified to be used for connection of all equipment supplied under the Contract. The overall substation cable routing and core schedules shall also be provided.
1H Earthing and Lightning Protection 1H1 One (1) lot of design, supply and installation of earthing system and
lightning protection screen including connections, connectors and clamps, to suit the substation overall arrangement and provide supporting design calculations.
1H2 Two (2) sets of 3-phase portable (maintenance) earthing equipment
devices with connectors and telescopic glass fibre operating pole suitable for plant supplied. (400kV and lower voltages)
SA- Introduction & preamble to the price & technical schedules 11
1I Batteries, Chargers and DC Distribution 1I1 110V substation alkaline batteries complete with chargers and
distribution switchboard to be supplied, installed and commissioned to provide all DC supplies to equipment being supplied.
The system shall generally be as shown in bid drawing and shall include:
a) The following battery sets shall be under this contract:
i. Two (2) sets of 100% batteries complete, each capacity shall not be less than 330Ah at the 5-hour rate of discharge for 400kV & 33kV side to be located in one 400kV Switchyard Panel Room (SPR).
ii. Two (2) sets of 100% batteries complete, each capacity shall not be less than 250Ah at the 5-hour rate of discharge for 230kV side to be located in one 230kV SPR.
During execution stage the capacity shall be confirmed with calculation by the contractor considering the bays under scope of work and future bays as per clause 8.4.3 of section 8 of Volume 2 of 3 of the biding document. The battery with higher capability if required after calculation shall be supplied within the same price.
b) The following battery charger sets shall be under this contract:
i. Two (2) sets of battery chargers complete, each float charge shall not be less than 110A rating and input voltage three phase 50Hz, 415V AC for 400kV & 33kV side battery to be located in one 400kV SPR.
ii. Two (2) sets of battery chargers complete, each float charge shall not be less than 80A rating and input voltage three phase 50Hz, 415V AC for 230kV side battery to be located in one 230kV SPR.
The rating shall be on the load and boost charging rate and the higher charging charger after calculation shall be supplied within the same price.
c) The following DC distribution boards shall be under this contract:
i. Two (2) sets of DC distribution boards complete for 400kV and 33kV systems, one will be located at 400kV SPR #1 with chargers and the other will be located at #2.
ii. Two (2) sets of DC distribution boards complete for 230kV system, one will be located at 230kV SPR #1 with chargers and the other will be located at #2.
The DC distribution board shall be with 50% overall spare switches for future use. All DC status excluding control & protection (DC voltage status for each bus including coupling breaker on/off status, fail with alarm) shall be
SA- Introduction & preamble to the price & technical schedules 12
incorporated in substation automation system.
1I2 48V DC system and distribution equipment to be supplied, installed and commissioned in the main control building for the new fibre optic multiplexer equipment for communication, protection and powering two 240V, 50Hz, 1.5kVA UPS for 30 minutes. One set shall be used as standby supply.
The system shall generally be as shown in bid drawing and shall include:
(i) Two (2) sets of 100% batteries complete, each capacity shall not be less than 250 Ah at the 5-hour rate of discharge
(ii) Two (2) sets of battery chargers of output 48V DC, 70A and input
voltage three phase 50Hz, 415 V AC.
(iii) DC distribution board. The DC distribution board shall be suitable to connect the new fibre optic multiplexer equipment for communication and protection with 50% overall spare switches for future use.
(iv) Two(2) sets of online UPS 240V, 50Hz, 1.5kVA powered from 48V DC
distribution board and AC distribution board as bypass circuit for Substation Automation system panels at itself.
48V DC system and distribution equipment shall be located in the Main Control Building.
All DC status excluding control & protection (DC voltage status for each bus including coupling breaker on/off status, fail with alarm) shall be incorporated in substation automation system.
1J LVAC Distribution 1J1 One (1) lot of LVAC switchboard for substation services to be supplied,
installed and commissioned, to provide the 415/240V supplies to all equipment being supplied under this turnkey Bid.
All AC status excluding control & protection (AC voltage status for each bus including coupling breaker on/off status, fail with alarm) shall be incorporated in substation automation system.
1J2 One (1) lot of Tariff metering panel to accommodate programmable & recordable digital 3-phase, 4-wire import and export MWh and MVArh meters (accuracy class 0.2) for two 33/0.415 kV station auxiliary transformer feeder circuits. For each feeder minimum two meters (main & check). Substation Automation System shall include the metering for all incoming LVAC source feeder.
The system and requirements shall generally be as shown in Bid drawing and technical specification of Volume 2 and shall include one 125A outdoor weather proof 3-phase with neutral and earth switched socket outlet and plug as per IEC 60309; to be installed, cabled and connected adjacent to the auxiliary
SA- Introduction & preamble to the price & technical schedules 13
transformers. 1K Civil Works, Building and Foundation 1K1 One (1) lot of Land development, including but not limited to the
formation and elevation of approximate 2.5m height, is included in the scope of works. One (1) lot of complete design, supply and construction of all civil items required for the outdoor works including but not limited to filling / cutting soil and leveling up to finished level and within the property line suitable for 400kV and 230kV switchyards and 230kV 4-circuit dead end towers.
1K2 One (1) lot of complete design, supply and construction of outdoor civil
works, including 400kV and 230kV and 33kV gantry foundation, 400kV and 230kV and 33kV equipment foundation, power transformers and auxiliary transformers foundations, oil pit, blast walls, substation main gate, security boundary walls and internal fencing, access road, internal roads and parking, concrete culvert, surface and switchyard drainage system including outfall, cable trench including soak pit, PVC pipes etc., switchyard surface finishing and gravel surfacing.
1K3 One (1) lot of complete design, supply and construction of all civil items
and facilities required for the two storied main control building in 400kV switchyard area.
1K4 One (1) lot of complete design, supply and construction of all civil items
and facilities required for two new one storied switchyard panel room buildings (SPR) with batteries and chargers, one located in 400kV switchyard and one in 230kV switchyard.
1K5 One (1) lot of complete design, supply and construction of all civil items
and facilities required for two new one storied switchyard panel room buildings (SPR) without batteries and chargers, one located in 400kV switchyard and one in 230kV switchyard.
1K6 One (1) lot of design, supply and construction of fire fighting system for
400kV auto transformers including water pipe network and reservoir at normal pressure
1K7 One (1) lot of complete design, supply and construction of fire alarm &
fire fighting system for other areas. Fire extinguishers shall be supplied as per Section 12.7 of Volume 2 of 3, for 400kV and 230kV switchyards buildings and outdoors.
1L Lighting, Small Power, Air Conditioning and Ventilation 1L1 One (1) lot of complete design, supply, installation and commissioning of
equipment to provide lighting, LV power supply, air conditioning system, ventilation system and emergency DC lighting for the main control building and switchyard panel rooms.
SA- Introduction & preamble to the price & technical schedules 14
1L2 One (1) lot of design, supply, installation and commissioning of equipment to provide lighting (flood light; LED type) for security, roadway, switchyard and emergency DC lighting at strategic locations for equipment operation and inspection.
1M Fibre Optic Multiplexer Equipment and PLC Equipment for
Communication and Protection 1M1 Multiplexer:
The equipment to be supplied, installed and commissioned shall be as shown on bid drawing. One (1) lot complete set of design, supply, installation and commissioning of fibre optic multiplexer equipment covering five (5) related substation optical interfaces with necessary works to interface with existing system is to be provided for:
- 21 relay for each transmission line protection (through fibre cores) - 21 relay carrier signal (main and back-up) - 87 (current differential) relay for each transmission line protection - SCADA data from switchgear and control system - Hot-line telephone system - Substation LAN system Additionally, if any Optical Interfaces are required for system configuration at
each remote end substation, then interface devices shall be installed in each existing system.
1M2 PABX:
Extension of existing digital PABX with subscriber telephone sets for the complete substation including necessary works to interface with existing system.
1M3 Optical Fiber: Underground optical fibre cables (48 cores for 400kV) from terminal
box gantry structure at each 400kV double circuit transmission line termination point to MDF (Main distribution Frame) to be installed in control room. The Contract includes supply and installation of MDF and pig-tail cables with adequate length.
1M4 PLC Equipment:
The equipment to be supplied, installed and commissioned shall be as per the SLD.
The scope of supply is summarised as follows:-
400kV 2 sets:- Indoor PLC equipment including teleprotection at Madunaghat for (direction Meghnaghat-1 & 2) 400 kV line and 2 sets:- Indoor PLC equipment including teleprotection at Aminbazar for (direction Meghnaghat-1 & 2) 400 kV line. 8 nos.:-Line traps and line matching units for phase to phase circuit coupling for 400kV lines.
SA- Introduction & preamble to the price & technical schedules 15
1 set: - Digital Type telephone exchange and must be compatible with existing network scheme. Additionally, if any Interfaces are required for system configuration at each remote end substation, then interface devices shall be installed in each existing system as a lot.
1N SCADA system for Telecontrol and Telemetering 1N1 Design, supply, delivery, installation, testing & commissioning of hardware and
software to provide the telecontrol & telemetering facilities required at the existing National Load Despatch Center (NLDC) at Rampura and back up station at Biddyut Bhaban for integration of complete new 400/230kV substation. All required electrical signals shall be transmitted to the NLDC through the Industrial Gateway of the substation automation system. All HV breakers, motorized disconnectors, tap changer, etc. shall be controlled form NLDC through the Gateway of the substation automation system using IEC 60870-5-104 protocol. All necessary modification works in the software of master station of NLDC at Rampura & Biddyut Bhaban are to be carried out.
Section-II Mandatory Spares, Erection & Test Equipment
Supply of complete spares and spare parts of transformer, switchgear,
control equipment, protection relays, meters, erection & test equipment as per quantity mentioned in Schedule B. The materials shall have to be handed over to the designated store as per instruction of the Employer.
Section-III EMTP Study, Shunt Reactor and associated bay considering both
Meghnaghat 400kv & Madunaghat 400kV sides Requirement of Shunt reactor and associated shall be determined by EMTP study which shall be carried out under this scope of work. The clause related to change of facilities (no. 39 of General Condition of Contracts-GCC) shall not be applicable for the works under this section-III.
3A Works and Equipment for Shunt Reactor Installation
The works for shunt reactor shall comply with Section 16 of the Technical Specification and the particular requirements as detailed in the Schedule of Technical Requirements included as Appendix A1 to this section and shall comprise the following:-
3A1 EMTP study shall be done by the contractor to determine the requirement & the size of the shunt reactor and to determine the requirement & the number of lighting arrester at 400kV switchyard. EMTP study shall also include the insulation co-ordination for surge arrestors and requirements for Point-on-Wave device and PIRs for each busbar.
SA- Introduction & preamble to the price & technical schedules 16
3A2 Two (2) sets of 400 kV, 40MVAR, three phase outdoor type Shunt Reactor (ONAN) as specified in the technical specifications of this Section as per the EMTP study to be done by the Contractor.
3A3 Two (2) sets of 420kV, 2000A, 50kA/1sec, 50Hz, 1425kVp BIL, live tank type or dead tank type, gang operated, SF6 gas circuit breakers with spring-stored energy operating mechanism or spring-hydraulic operating mechanism as specified in the technical specifications, Section 3, Volume 2 of 3 of the Bidding Documents.
3A4 Two (2) sets of 420kV, 2000A, 50kA/1sec, 50Hz, 1425kVp BIL, horizontal centre break, post type, motor operated disconnectors with earthing switch as specified in the technical specifications, Section 3, Volume 2 of 3 of the Bidding Document.
3A5 Control, Protection, Monitoring & Substation Automation System
including event recording function for two (2) sets of Shunt Reactor line circuits as specified in the technical specifications and bid drawings.
3A6 One (1) lot of rigid tubular bus [Aluminum of grade 63401 WP], flexible conductors, insulators, fittings including all necessary clamps and connectors required for completing switchgear connection for Shunt Reactor bay as specified in the technical specifications and bid drawings.
3A7 One (1) lot of steel structures for gantry, equipment supports and civil works required for completing 420kV busbar and switchgear for Shunt Reactor bay as specified in the technical specifications and bid drawings.
(In case of any item will be supplied from within the Employer's Country, please select these items and indicate their prices in the Scledule No.2.)
Unit CurrencyForeign Local (Taka) Foreign Local (Taka)
(1) (2) (3) (1) x (2) (1) x (3)
1A 420 kV Air Insulated Switchgear (AIS)
1A.1 420kV, 4000A, 50kA/1sec, 50Hz, 1425kVp BIL, gang operated, SF6 gas circuit breakers with support structure 6 sets
1A.2 420kV, 4000A, 50kA/1sec, 50Hz, 1425kVp BIL, single-pole operation, SF6 gas circuit breakers with support structure 4 sets
1A.3420kV, 2000A, 50kA/1sec, 50Hz, 1425kVp BIL, motor operated disconnectors with motor operated earthing switch (for Transmission Lines) with support structure
4 sets
1A.4 420kV, 4000A, 50kA/1sec, 50Hz, 1425kVp BIL, motor operated disconnectors without earthing switch with support structure 20 sets
1A.5 420kV, 2000A, 50kA/1sec, 50Hz, 1425kVp BIL, motor operated disconnectors (for Transformers) with support structure 2 sets
1A.6 420kV, 50kA/1sec, 50Hz, 1425kVp BIL, motor operated busbar earthing switch with support structure 2 sets
1A.7 Single-phase, 6-core, 420kV, 50kA/1sec, 4000A/1A, 50Hz, 1425kVp BIL, current transformer with support structure 42 nos.
1A.8 Single-phase, 3-winding, 420kV, 50kA/1sec, 50Hz, 1425kVp BIL, capacitive voltage transformers with support structure 24 nos.
1A.9390kV rated voltage, 303kV(rms) continuous operating voltage at 50oC, 10kA, 50Hz, Heavy duty station class, metal oxide type, single phase surge arresters with support structure
30 nos.
1A.10 wave trap (single phase, 420kV, 4000A, 1mH) with support structure and insulators 8 nos.
1A.11 Post type support insulators for busbar and switchgear with support structures for 400kV diameters 3 nos.
Code1Qty.
CIP
Schedules of Rates and Prices 1) PGCB SCOPE WITHOUT EQUIPMENT FOR IPP POWER PLANTS
Schedule No. 1. Plant and Mandatory Spare Parts Supplied from Abroad
CIP
Total Price2Unit Price2
FOB Price
Clause No of Scope of WorksItem Description
SB-4
(In case of any item will be supplied from within the Employer's Country, please select these items and indicate their prices in the Scledule No.2.)
Unit CurrencyForeign Local (Taka) Foreign Local (Taka)
(1) (2) (3) (1) x (2) (1) x (3)
Code1Qty.
CIP
Schedule No. 1. Plant and Mandatory Spare Parts Supplied from Abroad
CIP
Total Price2Unit Price2
FOB Price
Clause No of Scope of WorksItem Description
1A.12Rigid tubular bus, flexible conductors, insulators, fittings including all necessary clamps and connectors for completing 420kV, 4000A, 50kA/1sec, 50Hz, 1425kVp BIL, busbar
1 lot
1A.13Rigid tubular bus, flexible conductors, insulators, fittings including all necessary clamps and connectors for completing 420kV switchgear connection
1 lot
1A.14 Steel structures for gantry, equipment support, accessories and fittings for 420kV busbar and switchgear 1 lot
Sub-total 1A
1B 245kV Air Insulated Switchgear
1B.1 245kV, 3000A, 50kA/1sec, 50Hz, 1050kVp BIL, gang operated, SF6 gas circuit breakers with support structure 6 sets
1B.2 245kV, 3000A, 50kA/1sec, 50Hz, 1050kVp BIL, single-pole operation, SF6 gas circuit breakers with support structure 2 sets
1B.3245kV, 2000A, 50kA/1sec, 50Hz, 1050kVp BIL, motor operated disconnectors with motor operated earthing switch (for Transmission lines) with support structure
2 sets
1B.4 245kV, 3000A, 50kA/1sec, 50Hz, 1050kVp BIL, motor operated disconnectors without earthing switch with support structure 16 sets
1B.5245kV, 2000A, 50kA/1sec, 50Hz, 1050kVp BIL, motor operated disconnectors without earthing switch (for Transformers) with support structure
2 sets
1B.6 245kV, 50kA/1sec, 50Hz, 1050kVp BIL, motor operated busbar grounding switches with support structure 2 sets
1B.7 Single-phase, 5-core, 245kV, 3000A/1A, 50kA/1sec, 50Hz, 1050kVp BIL, current transformer with support structure 24 nos.
1B.8Single-phase, 2-core, 245kV, 3000A/1A, 50kA/1sec, 50Hz, 1050kVp BIL, current transformer (for Bus sectionalizers) with support structure
12 nos.
SB-5
(In case of any item will be supplied from within the Employer's Country, please select these items and indicate their prices in the Scledule No.2.)
Unit CurrencyForeign Local (Taka) Foreign Local (Taka)
(1) (2) (3) (1) x (2) (1) x (3)
Code1Qty.
CIP
Schedule No. 1. Plant and Mandatory Spare Parts Supplied from Abroad
CIP
Total Price2Unit Price2
FOB Price
Clause No of Scope of WorksItem Description
1B.9 Single-phase, 3-winding, 245kV, 50kA/1sec, 50Hz, 1050kVp BIL, capacitor type voltage transformers with support structure 18 nos.
1B.10196kV rated voltage, 160kV(rms) continuous operating voltage at 50oC 10kA, 50Hz, Heavy duty station class, metal oxide type, single phase surge arresters with support structure.
18 nos.
1B.11 Deleted
1B.12 Post type support insulators for busbar and switchgear with support structures for 245kV busbar and switchgear 3 nos.
1B.13Rigid tubular bus, flexible conductors, insulators, fittings including all necessary clamps and connectors for completing 245kV, 3000A, 50kA/1sec, 50Hz, 1050kVp BIL, busbar
1 lot
1B.14
Rigid tubular bus, flexible conductors, insulators, fittings including all necessary clamps and connectors for completing 245kV switchgear connection, including interconnection between new and existing 230kV switchyards
1 lot
1B.15Steel structures for gantry, accessories and fittings for 245kV busbar and switchgears, including interconnection between new and existing 230kV switchyards
1 lot
1B.16Equipment and material for interconnection between auto transformer side gantry and newly built 230kV switchyard bus side gantry
iEquipment and material for interconnection between auto transformer side gantry and newly built 230kV switchyard bus side gantry except intermediatetwo and four circuit 230kV towers
1 lot
ii Intermediate two-circuit 230kV tower 1 no.
iii Intermediate four-circuit 230kV tower 2 nos.
Sub-total 1B
1C Deleted
Sub-total 1C
SB-6
(In case of any item will be supplied from within the Employer's Country, please select these items and indicate their prices in the Scledule No.2.)
Unit CurrencyForeign Local (Taka) Foreign Local (Taka)
(1) (2) (3) (1) x (2) (1) x (3)
Code1Qty.
CIP
Schedule No. 1. Plant and Mandatory Spare Parts Supplied from Abroad
CIP
Total Price2Unit Price2
FOB Price
Clause No of Scope of WorksItem Description
1D 33kV Switches & connection
1D.1 36kV, 630A, 31.5kA/1sec, 50Hz, 170kVp BIL, SF6 gas or Vacuum circuit breaker with support structure 2 sets
1D.2 36kV, 630A, 31.5kA/1sec, 50Hz, 170kVp BIL, motor operated disconnectors with support structure 4 sets
1D.3Single-phase, 2-secondary winding, 36kV, 31.5kA/1sec, 50Hz, 170kVp BIL, inductive voltage transformers with support structure
6 nos.
1D.430kV rated voltage, 10kA nominal discharge current, 50Hz, Heavy duty station class, single phase surge arresters with support structure
6 nos.
1D.5
Tertiary side connection between 33kV terminal to switches/switchgear including necessary fittings, structures, conductors and 36kV XLPE cables for 2 sets of 400/235/33kV Auto transformer and 33/0.415kV Earthing/Auxiliary transformer
i
Tertiary side connection between 33kV terminal to switches/switchgear including necessary fittings, structures and conductors excluding 36kV XLPE cables for 2 sets of 400/235/33kV Auto transformer and 33/0.415kV Earthing/Auxiliary transformer
1 lot
ii 36kV XLPE cables 1 x 185mm2 240 meter
Sub-total 1D
1E Power Transformers and Earthing/Auxiliary Transformers
1E.1 Deleted
1E.2 400/235/33 kV, 500/750MVA (ONAN/ONAF), three phase Auto Transformer 2 nos.
1E.3 33/0.415kV, 500kVA, three phase Earthing/Auxiliary Transformer 2 nos.
Sub-total 1E
1F Control, Protection, Substation Automation and Metering
SB-7
(In case of any item will be supplied from within the Employer's Country, please select these items and indicate their prices in the Scledule No.2.)
Unit CurrencyForeign Local (Taka) Foreign Local (Taka)
(1) (2) (3) (1) x (2) (1) x (3)
Code1Qty.
CIP
Schedule No. 1. Plant and Mandatory Spare Parts Supplied from Abroad
CIP
Total Price2Unit Price2
FOB Price
Clause No of Scope of WorksItem Description
1F.1 Control, Monitoring, Protection & Substation Automation System for four (4) sets of 400kV overhead line circuits 4 sets
1F.2 Control, Monitoring, Protection & Substation Automation System for two (2) sets of 400kV auto transformer circuits 2 sets
1F.3 Control, Monitoring, Protection & Substation Automation System for 400kV busbar system 1 set
1F.4 Tariff metering for 400kV system 1 lot
1F.5 Digital Disturbance Recorder with Analysis Computor for 400kV system 1 lot
1F.6 Control, Monitoring, Protection & Substation Automation System for two (2) sets of 230kV overhead line circuits 2 sets
1F.7 Control, Monitoring, Protection & Substation Automation System for two (2) sets of 230kV auto transformer circuits 2 sets
1F.8 Control, Monitoring, Protection & Substation Automation System for 230kV busbar system 1 lot
1F.9 Tariff metering for 230kV system 1 lot
1F.10 Digital Disturbance Recorder with Analysis Computor for 230kV system 1 lot
1F.11Control, Monitoring, Protection & Substation Automation System for 33kV station power system including tariff metering for 0.415kV side
1 lot
Sub-total 1F
1G Multicore Cables
1G.1 Multicore low voltage power and control cables for control, protection, metering, monitoring and L/V power circuits 1 lot
Sub-total 1G
1H Earthing and Lightning Protection
1H.1 Earthing and Lightning Protection 1 lot
1H.2 Portable(maintenance) earthing equipment device 2 sets
Sub-total 1H
1I Batteries, chargers & DC distribution
SB-8
(In case of any item will be supplied from within the Employer's Country, please select these items and indicate their prices in the Scledule No.2.)
Unit CurrencyForeign Local (Taka) Foreign Local (Taka)
(1) (2) (3) (1) x (2) (1) x (3)
Code1Qty.
CIP
Schedule No. 1. Plant and Mandatory Spare Parts Supplied from Abroad
CIP
Total Price2Unit Price2
FOB Price
Clause No of Scope of WorksItem Description
1I.1 110V Ni-cad Batteries with chargers and distribution boards
a) Batteries
i 110V Ni-cad Batteries, 330Ah @ 5h for 400kV and 33kV systems at 400kV Swtichyard Panel Room #1 2 sets
ii 110V Ni-cad Batteries, 250Ah @ 5h for 230kV system at 230kV Switchyard Panel Room #1 2 sets
b) Battery chargers
i Battery chargers for 400kV and 33kV systems at 400kV Switchyard Panel Room #1 2 sets
ii Battery chargers for 230kV system at 230kV Switchyard Panel Room #1 2 sets
c) Distributuon boards
i Distribution boards for 400kV and 33kV systems at 400kV Switchyard Panel Room #1 & #2 2 sets
ii Distribution boards for 230kV system at 230kV Switchyard Panel Room #1 & #2 2 sets
1I.248V Ni-cad Batteries 250Ah including chargers (each 2 sets) and distribution board and 240V, 1.5kVA UPS for SAS (2 sets) at Main Control Building
i 48V Ni-cad Batteries, 250Ah @ 5h 2 sets
ii 48V Battery chargers 2 sets
iii DC Distribution boards 2 sets
iv 1.5kVA, 240V, 50Hz UPS powered from 48V DC distribution board for Substation Automation System 2 sets
Sub-total 1I
1J LVAC Distribution
1J.1 LVAC switchboard for substation services 1 lot
1J.2 Tariff metering panel for LV system 1 lot
Sub-total 1J
SB-9
(In case of any item will be supplied from within the Employer's Country, please select these items and indicate their prices in the Scledule No.2.)
Unit CurrencyForeign Local (Taka) Foreign Local (Taka)
(1) (2) (3) (1) x (2) (1) x (3)
Code1Qty.
CIP
Schedule No. 1. Plant and Mandatory Spare Parts Supplied from Abroad
CIP
Total Price2Unit Price2
FOB Price
Clause No of Scope of WorksItem Description
1K Civil Works, Building and Foundation
1K.1 The land development of two substation areas: 400kV and 230kV 1 lot
1K.2 Complete outdoor civil works excluding Main Control Building and SPR buildings
i) Outdoor gantry foundation 400kV switchyard 1 lot
ii) Outdoor equipment foundation 400kV switchyard 1 lot
iii) Outdoor gantry foundation 230kV switchyard
iii) a Gantry foundation for new 230kV switchyard 1 lot
iii) b Gantry foundation for interconnection of new and existing 230kV switchyard 1 lot
iv) Outdoor equipment foundation 230kV switchyard 1 lot
v) Outdoor gantry foundation 33kV switchyard 1 lot
vi) Outdoor equipment foundation 33kV switchyard 1 lot
vii) Transformer foundation including oilpit & carrage way 1 lot
viii) Blast wall 1 lot
ix) Secutiry boundary wall for 400kV and 230kV switchyards *3 2200 meter
x) Two (2) substation main gates (400kV and 230kV switchyards) 1 lot
xi) Chain link fencing *3 including three (3) personel gates 1000 meter
xii) Approach road 1 lot
xiii) Internal road 1 lot
xiv) Surface draing 1 lot
SB-10
(In case of any item will be supplied from within the Employer's Country, please select these items and indicate their prices in the Scledule No.2.)
Unit CurrencyForeign Local (Taka) Foreign Local (Taka)
(1) (2) (3) (1) x (2) (1) x (3)
Code1Qty.
CIP
Schedule No. 1. Plant and Mandatory Spare Parts Supplied from Abroad
CIP
Total Price2Unit Price2
FOB Price
Clause No of Scope of WorksItem Description
xv) Cable trench 1 lot
xvi) Switchyard surface finishing, drainage system including surface drain 1 lot
xvii) Gravel laying 1 lot
xviii) Septic tank, soakaway 1 lot
xix) Pump house including deep tubewell, motor, pump, water reservaoir, water pipe line, etc. 1 lot
xx) Guard house, sentry post, car port 1 lot
xxi) Foundations for two (2) intermediate 4-circuit 230kV towers 2 nos.
xxii) Foundations for one (1) intermediate 2-circuit 230kV tower 1 no.
1K.3 Main Control Building
i) Foundation works 1 lot
ii) Super structures 1 lot
iii) All finish works 1 lot
1K.4 Switchyard panel rooms with batteries and chargers
i) Foundation works 1 lot
ii) Super structures 1 lot
iii) All finish works 1 lot
1K.5 Switchyard panel rooms without batteries and chargers
i) Foundation works 1 lot
ii) Super structures 1 lot
SB-11
(In case of any item will be supplied from within the Employer's Country, please select these items and indicate their prices in the Scledule No.2.)
Unit CurrencyForeign Local (Taka) Foreign Local (Taka)
(1) (2) (3) (1) x (2) (1) x (3)
Code1Qty.
CIP
Schedule No. 1. Plant and Mandatory Spare Parts Supplied from Abroad
CIP
Total Price2Unit Price2
FOB Price
Clause No of Scope of WorksItem Description
iii) All finish works 1 lot
1K.6 Fire fighting system for Transformers 1 lot
1K.7 Fire alarm & fire fighting system 1 lot
Sub-total 1K
1L Lighting, small power, air conditioning and Ventilation
1L.1Lighting, small power, air conditioning and Ventilation and emergency DC lighting for Main Control Building and Switchyard Panel Rooms
1 lot
1L.2Lighting for ouside buildings and relay houses for security, roadway, switchyard and emergency DC lighting including steel poles (H=6m)
1 lot
Sub-total 1L
1M Fibre Optic Multiplexer Equipment and PLC Equipment for Communication and Protection
1M.1 Indoor Fibre Optic Multipexer Equipment 1 lot
1M.2 PABX 1 lot
1M.3 Fibre Optic cable and termination box 1 lot
1M.4 PLC Equipment 1 lot
Sub-total 1M
1N SCADA system for Telecontrol and Telemetering
1N1 Complete SCADA hardware & software 1 lot
Sub-total 1N
3A Shunt Reactor
3A.2400 kV, 40MVAR (ONAN), three phase outdoor type shunt reactor *4 2 sets
3A.3 420kV, 2000A, 50kA/1sec, 50Hz, 1425kVp BIL, gang operated, SF6 gas circuit breakers with support structure 2 sets
SB-12
(In case of any item will be supplied from within the Employer's Country, please select these items and indicate their prices in the Scledule No.2.)
Unit CurrencyForeign Local (Taka) Foreign Local (Taka)
(1) (2) (3) (1) x (2) (1) x (3)
Code1Qty.
CIP
Schedule No. 1. Plant and Mandatory Spare Parts Supplied from Abroad
CIP
Total Price2Unit Price2
FOB Price
Clause No of Scope of WorksItem Description
3A.4420kV, 2000A, 50kA/1sec, 50Hz, 1425kVp BIL, motor operated disconnectors with motor operated earthing switch with support structure
2 sets
3A.5 Control, Protection, Monitoring & Substation Automation System for 2 (2) sets of shunt reactor circuits 1 lot
3A.6Rigid tubular bus, flexible conductors, insulators, fittings including all necessary clamps and connectors for completing switchgear connection for Shunt Reactor bay
1 lot
3A.7All Civil works, Steel structures for gantry, equipment support, accessories and fittings for 420kV busbar and switchgear for two (2) Shunt Reactor bays
1 lot
Sub-total 3A
2 Mandatory Spares
2.1 400kV AIS Equipment
2.1.1 420kV Circuit breaker
2.1.1.1 Operating mechanism for circuit breaker 2 nos.
2.1.1.2 Each type of closing coils and opening coils 15 nos.
2.1.1.3 Each type of auxiliary contacts unit 3 nos.
2.1.1.4 SF6 gas cylinders – 45kg 3 nos.
2.1.2 Disconnector and earthing switch parts
2.1.2.1 Operating mechanism for disconnector 2 nos.
2.1.2.2 Mechnical Drive for high speed earthing switch 1 no.
2.1.3 420 kV current transformer 1 no. each
2.1.4 420 kV voltage transformer 1 no. each
2.1.5 420kV complete set of Surge Arrester 1 no.
2.1.6 420kV Special Tool/Instrument for Operation and maintenance(To be listed up by bidder) 1 set
2.2 230kV AIS Equipment
SB-13
(In case of any item will be supplied from within the Employer's Country, please select these items and indicate their prices in the Scledule No.2.)
Unit CurrencyForeign Local (Taka) Foreign Local (Taka)
(1) (2) (3) (1) x (2) (1) x (3)
Code1Qty.
CIP
Schedule No. 1. Plant and Mandatory Spare Parts Supplied from Abroad
CIP
Total Price2Unit Price2
FOB Price
Clause No of Scope of WorksItem Description
2.2.1 245kV Circuit breaker
2.2.1.1 Operating mechanism for circuit breaker 1 no.
2.2.1.2 Each type of closing coils and opening coils 15 nos.
2.2.1.3 Each type of auxiliary contacts unit 3 nos.
2.2.2 245kV Disconnector and earthing switch parts
2.2.2.1 Operating mechanism for disconnector 1 no.
2.2.2.2 Mechnical Drive for high speed earthing switch 1 no.
2.2.3 245 kV current transformer 1 no. each
2.2.4 245 kV voltage transformer 1 no. each
2.2.5 245kV Complete set of Surge Arrester 1 no.
2.2.6 245kV Special Tool/Instrument for Operation and maintenance(To be listed up by bidder) 1 set
2.3 36kV Switchgears
2.3.1 36 kV Circuit breaker
2.3.1.1 Operating mechanism for circuit breaker 1 no.
2.3.1.2 Each type of closing coils and opening coils 10 nos.
2.3.1.3 Each type of moving contacts and stationary contacts 3 nos.
2.3.1.4 Vacume interupter chambers (in case of vacume breakers) 2 nos.
2.3.2 36kV Disconnecting switch
2.3.2.1 Set (3-phase) of moving & stationary contacts for each rating of36 kV disconnector 1 no.
2.3.2.2 Set (3-phase) of moving & stationary contact for each rating of 36kV earthing switch. 1 no.
2.3.2.3 Operating mechanism for disconnecting switch 1 no.
2.3.2.4 Auxiliary contacts for disconnectors 3 nos.
SB-14
(In case of any item will be supplied from within the Employer's Country, please select these items and indicate their prices in the Scledule No.2.)
Unit CurrencyForeign Local (Taka) Foreign Local (Taka)
(1) (2) (3) (1) x (2) (1) x (3)
Code1Qty.
CIP
Schedule No. 1. Plant and Mandatory Spare Parts Supplied from Abroad
CIP
Total Price2Unit Price2
FOB Price
Clause No of Scope of WorksItem Description
2.3.2.5 Auxiliary contacts for earth switch 3 nos.
2.3.3 36 kV current transformer 1 no. each
2.3.4 36kV voltage transformer 1 no. each
2.3.5 36kV Special Tool/Instrument for Operation and maintenance(To be listed up by bidder) 1 set
2.4 PROTECTION AND CONTROL
2.4.1 Each type of Protection Relay / AVR 1 set
2.4.2 Each type of Tripping relays 2 sets
2.4.3 Each type of Auxilliary relays 5 sets
2.4.4 Each type of Trip circuit supervision relays 1 set
2.4.5 Each type of Bay Control Unit 1 set
2.4.6 Each type of Switch (if applicable ) 1 set
2.4.7 Each type of MCB 1 set
2.4.8 Each type of lamps 10 sets
2.4.9 Industial PC 1 set
2.4.10 Gateway Terminal 1 set
2.4.11 Bay ethernet switches 2 nos.
2.4.12 Optical connectors (one from each category) 1 lot
2.5 DC & Charger EQUIPMENT
2.5.1 Each type of Printed Circuit Board used 1 lot
2.5.2 Minature circuit breakers of each type and rating(Bidders to list all types) 1 lot
SB-15
(In case of any item will be supplied from within the Employer's Country, please select these items and indicate their prices in the Scledule No.2.)
Unit CurrencyForeign Local (Taka) Foreign Local (Taka)
(1) (2) (3) (1) x (2) (1) x (3)
Code1Qty.
CIP
Schedule No. 1. Plant and Mandatory Spare Parts Supplied from Abroad
CIP
Total Price2Unit Price2
FOB Price
Clause No of Scope of WorksItem Description
2.6 LVAC EQUIPMENT
2.6.1 Miniature circuit breakers of each type and rating(Bidders to list all types) 1 lot
2.7 POWER, CONTROL AND AUXILIARY CABLES
2.7.1 Power cables (36kV) 100m of each type 1 lot
2.7.2 Control cables: 200m of each type 1 lot
2.7.3 LV cables: 200m of each type 1 lot
2.7.4 Other cables (communication, etc.): 100m of each type 1 lot
2.8 TRANSFORMERS and SHUNT REACTORS
2.8.1 Auto Transformer
2.8.1.1 420kV bushing 1 no.
2.8.1.2 245 kV bushing 1 no.
2.8.1.3 33 kV bushing 1 no.
2.8.1.4 Set of gaskets for each transformer 1 no.
2.8.1.5 Set of dial type thermometer with gaskets 1 no.
2.8.1.6 Set of thermal image type indicator with gaskets 1 no.
2.8.1.7 Set of Silica gel breather 1 no.
2.8.1.8 Buchholz relay 1 no.
2.8.1.9 Set of tap changer diverter switch 1 no.
2.8.1.10 Tap changer control mechanism motor 1 no.
2.8.1.11 Transformer oil 200 litter barrel. 20 nos.
2.8.2 Earthing/Auxiliary Transformer
2.8.2.1 33kV bushing 1 no.
SB-16
(In case of any item will be supplied from within the Employer's Country, please select these items and indicate their prices in the Scledule No.2.)
Unit CurrencyForeign Local (Taka) Foreign Local (Taka)
(1) (2) (3) (1) x (2) (1) x (3)
Code1Qty.
CIP
Schedule No. 1. Plant and Mandatory Spare Parts Supplied from Abroad
CIP
Total Price2Unit Price2
FOB Price
Clause No of Scope of WorksItem Description
2.8.2.2 0.415kV bushing 1 no.
2.8.2.3 Set of gaskets for each transformer 1 no.
2.8.2.4 Set of dial type thermometer with gaskets 1 no.
2.8.2.5 Set of thermal image type indicator with gaskets 1 no.
2.8.2.6 Set of Silica gel breather 1 no.
2.8.2.7 Buchholz relay 1 no.
2.8.2.8 Transformer oil 200 litter barrel. 5 nos.
2.8.3 Shunt Reactor
2.8.3.1 420kV bushing 1 no.
2.8.3.2 Set of gaskets for each transformer 1 no.
2.8.3.3 Set of dial type thermometer with gaskets 1 no.
2.8.3.4 Set of thermal image type indicator with gaskets 1 no.
2.8.3.5 Set of Silica gel breather 1 no.
2.8.3.6 Shunt reactor oil 200 litter barrel. 10 nos.
2.9 Instruments for Communication & SCADA Maintenance
2.9.1 Digital data ( Communication) analyzer. 1 lot
2.9.2
Generator and Receiver for the following interfaces:(1) V.24 / RS232 SYNC AND ASYNC(2) V.35(3) G.703 CO-DIR AND 2048kbps and 704kbps(4) Bit Error rate measuring facility
1 lot
2.9.3 Digital selective level meter (50Hz to 600 kHz) plus level generator ( 50hz to 2Mhz) 1 lot
2.9.4 Subscriber Module for DCS 255 Exchange 1 lot
2.1 Post Type Insulator
2.10.1 For 420kV 3 nos.
SB-17
(In case of any item will be supplied from within the Employer's Country, please select these items and indicate their prices in the Scledule No.2.)
Unit CurrencyForeign Local (Taka) Foreign Local (Taka)
(1) (2) (3) (1) x (2) (1) x (3)
Code1Qty.
CIP
Schedule No. 1. Plant and Mandatory Spare Parts Supplied from Abroad
CIP
Total Price2Unit Price2
FOB Price
Clause No of Scope of WorksItem Description
2.10.2 For 245kV 3 nos.
2.11 Disk Insulator
2.11.1 Each type of disc insulator 20 nos.each
2.12 Conductor
2.12.1 Bus Conductor for each size 100 m.each
2.12.2 Rigid Tubler Condactor for each size 20 m.each
2.13 Clamp and Fitting
2.13.1 Clamp and fitting for each type 10 nos.each
Sub-total 2
3 Length for security boundary wall and chain link fencing shall be finalized during execution stage and payment shall be based on actual one.
Signature of Bidder
Name of Bidder
Foreign Currency (2)
4 If size of shunt reactor is increased/decreased from 40MVAr, the only foreign supply cost may be adjusted as "New price = Old price * 20% + Old price * 80% * (new size) / (old size)".
TOTAL OF SCHEDULE NO.1(To be indicated in Schedule No.6 Grand Summary)
Local Currency (Taka)
Foreign Currency (1)
1 Bidders shall enter a code representing the country of origin of all imported plant and equipment.
2 Specify currency in accordance with specifications in Bid Data Sheet under ITB 19.1 in Single-Stage Bid. Create and use as many columns for Unit Price and Total Price as there are curencies.
Foreign Currency (3)
SB-18
(In case of any item supplied from within the Employer's Country , please select the Items and indicate the prices)
Unit Currency(Taka) Local (Taka) Local (Taka)
(1) (3) (1) x (3)1A 420 kV Air Insulated Switchgear (AIS)
1A.1 420kV, 4000A, 50kA/1sec, 50Hz, 1425kVp BIL, gang operated, SF6 gas circuit breakers with support structure 6 sets
1A.2 420kV, 4000A, 50kA/1sec, 50Hz, 1425kVp BIL, single-pole operation, SF6 gas circuit breakers with support structure 4 sets
1A.3420kV, 2000A, 50kA/1sec, 50Hz, 1425kVp BIL, motor operated disconnectors with motor operated earthing switch (for Transmission Lines) with support structure
4 sets
1A.4 420kV, 4000A, 50kA/1sec, 50Hz, 1425kVp BIL, motor operated disconnectors without earthing switch with support structure 20 sets
1A.5 420kV, 2000A, 50kA/1sec, 50Hz, 1425kVp BIL, motor operated disconnectors (for Transformers) with support structure 2 sets
1A.6 420kV, 50kA/1sec, 50Hz, 1425kVp BIL, motor operated busbar earthing switch with support structure 2 sets
1A.7 Single-phase, 6-core, 420kV, 50kA/1sec, 4000A/1A, 50Hz, 1425kVp BIL, current transformer with support structure 42 nos.
1A.8 Single-phase, 3-winding, 420kV, 50kA/1sec, 50Hz, 1425kVp BIL, capacitive voltage transformers with support structure 24 nos.
1A.9390kV rated voltage, 303kV(rms) continuous operating voltage at 50oC, 10kA, 50Hz, Heavy duty station class, metal oxide type, single phase surge arresters with support structure
30 nos.
1A.10 wave trap (single phase, 420kV, 4000A, 1mH) with support structure and insulators 8 nos.
1A.11 Post type support insulators for busbar and switchgear with support structures for 400kV diameters 3 nos.
Schedules of Rates and Prices 1) PGCB SCOPE WITHOUT EQUIPMENT FOR IPP POWER PLANTS
Schedule No. 2. Plant and Mandatory Spare Parts Supplied from Within the Employer’s Country
Item Description Clause No of Scope of Works
EXW PriceCode
Unit PriceQty.
SB-19
(In case of any item supplied from within the Employer's Country , please select the Items and indicate the prices)
Unit Currency(Taka) Local (Taka) Local (Taka)
(1) (3) (1) x (3)
Schedule No. 2. Plant and Mandatory Spare Parts Supplied from Within the Employer’s Country
Item Description Clause No of Scope of Works
EXW PriceCode
Unit PriceQty.
1A.12Rigid tubular bus, flexible conductors, insulators, fittings including all necessary clamps and connectors for completing 420kV, 4000A, 50kA/1sec, 50Hz, 1425kVp BIL, busbar
1 lot
1A.13Rigid tubular bus, flexible conductors, insulators, fittings including all necessary clamps and connectors for completing 420kV switchgear connection
1 lot
1A.14 Steel structures for gantry, equipment support, accessories and fittings for 420kV busbar and switchgear 1 lot
Sub-total 1A1B 245kV Air Insulated Switchgear
1B.1 245kV, 3000A, 50kA/1sec, 50Hz, 1050kVp BIL, gang operated, SF6 gas circuit breakers with support structure 6 sets
1B.2 245kV, 3000A, 50kA/1sec, 50Hz, 1050kVp BIL, single-pole operation, SF6 gas circuit breakers with support structure 2 sets
1B.3245kV, 2000A, 50kA/1sec, 50Hz, 1050kVp BIL, motor operated disconnectors with motor operated earthing switch (for Transmission lines) with support structure
2 sets
1B.4 245kV, 3000A, 50kA/1sec, 50Hz, 1050kVp BIL, motor operated disconnectors without earthing switch with support structure 16 sets
1B.5245kV, 2000A, 50kA/1sec, 50Hz, 1050kVp BIL, motor operated disconnectors without earthing switch (for Transformers) with support structure
2 sets
1B.6 245kV, 50kA/1sec, 50Hz, 1050kVp BIL, motor operated busbar grounding switches with support structure 2 sets
1B.7 Single-phase, 5-core, 245kV, 3000A/1A, 50kA/1sec, 50Hz, 1050kVp BIL, current transformer with support structure 24 nos.
1B.8Single-phase, 2-core, 245kV, 3000A/1A, 50kA/1sec, 50Hz, 1050kVp BIL, current transformer (for Bus sectionalizers) with support structure
12 nos.
SB-20
(In case of any item supplied from within the Employer's Country , please select the Items and indicate the prices)
Unit Currency(Taka) Local (Taka) Local (Taka)
(1) (3) (1) x (3)
Schedule No. 2. Plant and Mandatory Spare Parts Supplied from Within the Employer’s Country
Item Description Clause No of Scope of Works
EXW PriceCode
Unit PriceQty.
1B.9 Single-phase, 3-winding, 245kV, 50kA/1sec, 50Hz, 1050kVp BIL, capacitor type voltage transformers with support structure 18 nos.
1B.10196kV rated voltage, 160kV(rms) continuous operating voltage at 50oC 10kA, 50Hz, Heavy duty station class, metal oxide type, single phase surge arresters with support structure.
18 nos.
1B.11 Deleted
1B.12 Post type support insulators for busbar and switchgear with support structures for 245kV busbar and switchgear 3 nos.
1B.13Rigid tubular bus, flexible conductors, insulators, fittings including all necessary clamps and connectors for completing 245kV, 3000A, 50kA/1sec, 50Hz, 1050kVp BIL, busbar
1 lot
1B.14
Rigid tubular bus, flexible conductors, insulators, fittings including all necessary clamps and connectors for completing 245kV switchgear connection, including interconnection between new and existing 230kV switchyards
1 lot
1B.15Steel structures for gantry, accessories and fittings for 245kV busbar and switchgears, including interconnection between new and existing 230kV switchyards
1 lot
1B.16Equipment and material for interconnection between auto transformer side gantry and newly built 230kV switchyard bus side gantry
i
Equipment and material for interconnection between auto transformer side gantry and newly built 230kV switchyard bus side gantry except intermediate two and four circuit 230kV towers
1 lot
ii Intermediate two-circuit 230kV tower 1 no.iii Intermediate four circuit 230kV tower 2 nos.
SB-21
(In case of any item supplied from within the Employer's Country , please select the Items and indicate the prices)
Unit Currency(Taka) Local (Taka) Local (Taka)
(1) (3) (1) x (3)
Schedule No. 2. Plant and Mandatory Spare Parts Supplied from Within the Employer’s Country
Item Description Clause No of Scope of Works
EXW PriceCode
Unit PriceQty.
Sub-total 1B1C Deleted
Sub-total 1C1D 33kV Switches & connection
1D.1 36kV, 630A, 31.5kA/1sec, 50Hz, 170kVp BIL, SF6 gas or Vacuum circuit breaker with support structure 2 sets
1D.2 36kV, 630A, 31.5kA/1sec, 50Hz, 170kVp BIL, motor operated disconnectors with support structure 4 sets
1D.3Single-phase, 2-secondary winding, 36kV, 31.5kA/1sec, 50Hz, 170kVp BIL, inductive voltage transformers with support structure
6 nos.
1D.430kV rated voltage, 10kA nominal discharge current, 50Hz, Heavy duty station class, single phase surge arresters with support structure
6 nos.
1D.5
Tertiary side connection between 33kV terminal to switches/switchgear including necessary fittings, structures, conductors and 36kV XLPE cables for 2 sets of 400/235/33kV Auto transformer and 33/0.415kV Earthing/Auxiliary transformer
i
Tertiary side connection between 33kV terminal to switches/switchgear including necessary fittings, structures and conductors excluding 36kV XLPE cables for 2 sets of 400/235/33kV Auto transformer and 33/0.415kV Earthing/Auxiliary transformer
1 lot
ii 36kV XLPE cables 1 x 185mm2 240 meterSub-total 1D
1E Power Transformers and Earthing/Auxiliary Transformers1E.1 Deleted
1E.2 400/235/33 kV, 500/750MVA (ONAN/ONAF), three phase Auto Transformer 2 nos.
SB-22
(In case of any item supplied from within the Employer's Country , please select the Items and indicate the prices)
Unit Currency(Taka) Local (Taka) Local (Taka)
(1) (3) (1) x (3)
Schedule No. 2. Plant and Mandatory Spare Parts Supplied from Within the Employer’s Country
Item Description Clause No of Scope of Works
EXW PriceCode
Unit PriceQty.
1E.3 33/0.415kV, 500kVA, three phase Earthing/Auxiliary Transformer 2 nos.
Sub-total 1E1F Control, Protection, Substation Automation and Metering
1F.1 Control, Monitoring, Protection & Substation Automation System for four (4) sets of 400kV overhead line circuits 4 sets
1F.2 Control, Monitoring, Protection & Substation Automation System for two (2) sets of 400kV auto transformer circuits 2 sets
1F.3 Control, Monitoring, Protection & Substation Automation System for 400kV busbar system 1 set
1F.4 Tariff metering for 400kV system 1 lot
1F.5 Digital Disturbance Recorder with Analysis Computor for 400kV system 1 lot
1F.6 Control, Monitoring, Protection & Substation Automation System for two (2) sets of 230kV overhead line circuits 2 sets
1F.7 Control, Monitoring, Protection & Substation Automation System for two (2) sets of 230kV auto transformer circuits 2 sets
1F.8 Control, Monitoring, Protection & Substation Automation System for 230kV busbar system 1 lot
1F.9 Tariff metering for 230kV system 1 lot
1F.10 Digital Disturbance Recorder with Analysis Computor for 230kV system 1 lot
1F.11Control, Monitoring, Protection & Substation Automation System for 33kV station power system including tariff metering for 0.415kV side
1 lot
Sub-total 1F 1G Multicore Cables
1G.1 Multicore low voltage power and control cables for control, protection, metering, monitoring and L/V power circuits 1 lot
Sub-total 1G1H Earthing and Lightning Protection
SB-23
(In case of any item supplied from within the Employer's Country , please select the Items and indicate the prices)
Unit Currency(Taka) Local (Taka) Local (Taka)
(1) (3) (1) x (3)
Schedule No. 2. Plant and Mandatory Spare Parts Supplied from Within the Employer’s Country
Item Description Clause No of Scope of Works
EXW PriceCode
Unit PriceQty.
1H.1 Earthing and Lightning Protection 1 lot1H.2 Portable(maintenance) earthing equipment device 2 sets
Sub-total 1H1I Batteries, chargers & DC distribution1I.1 110V Ni-cad Batteries with chargers and distribution boards
a) Batteries
i 110V Ni-cad Batteries, 330Ah @ 5h for 400kV and 33kV systems at 400kV Swtichyard Panel Room #1 2 sets
ii 110V Ni-cad Batteries, 250Ah @ 5h for 230kV system at 230kV Switchyard Panel Room #1 2 sets
b) Battery chargers
i Battery chargers for 400kV and 33kV systems at 400kV Switchyard Panel Room #1 2 sets
ii Battery chargers for 230kV system at 230kV Switchyard Panel Room #1 2 sets
c) Distributuon boards
i Distribution boards for 400kV and 33kV systems at 400kV Switchyard Panel Room #1 & #2 2 sets
ii Distribution boards for 230kV system at 230kV Switchyard Panel Room #1 & #2 2 sets
1I.248V Ni-cad Batteries 250Ah including chargers (each 2 sets) and distribution board and 240V, 1.5kVA UPS for SAS (2 sets) at Main Control Building
i 48V Ni-cad Batteries, 250Ah @ 5h 2 setsii 48V Battery chargers 2 sets
iii DC Distribution boards 2 sets
iv 1.5kVA, 240V, 50Hz UPS powered from 48V DC distribution board for Substation Automation System 2 sets
Sub-total 1I1J LVAC Distribution1J.1 LVAC switchboard for substation services 1 lot
SB-24
(In case of any item supplied from within the Employer's Country , please select the Items and indicate the prices)
Unit Currency(Taka) Local (Taka) Local (Taka)
(1) (3) (1) x (3)
Schedule No. 2. Plant and Mandatory Spare Parts Supplied from Within the Employer’s Country
Item Description Clause No of Scope of Works
EXW PriceCode
Unit PriceQty.
1J.2 Tariff metering panel for LV system 1 lotSub-total 1J
1K Civil Works, Building and Foundation
1K.1 The land development of two substation areas: 400kV and 230kV 1 lot
1K.2 Complete outdoor civil works excluding Main Control Building and SPR buildings
i) Outdoor gantry foundation 400kV switchyard 1 lotii) Outdoor equipment foundation 400kV switchyard 1 lot
iii) Outdoor gantry foundation 230kV switchyardiii) a Gantry foundation for new 230kV switchyard 1 lot
iii) b Gantry foundation for interconnection of new and existing 230kV switchyard 1 lot
iv) Outdoor equipment foundation 230kV switchyard 1 lotv) Outdoor gantry foundation 33kV switchyard 1 lot
vi) Outdoor equipment foundation 33kV switchyard 1 lotvii) Transformer foundation including oilpit & carrage way 1 lot
viii) Blast wall 1 lotix) Secutiry boundary wall for 400kV and 230kV switchyards *3 2200 meter
x) Two (2) substation main gates (400kV and 230kV switchyards) 1 lot
xi) Chain link fencing *3 including three (3) personel gates 1000 meterxii) Approach road 1 lot
xiii) Internal road 1 lotxiv) Surface draing 1 lotxv) Cable trench 1 lot
xvi) Switchyard surface finishing, drainage system including surface drain 1 lot
xvii) Gravel laying 1 lotxviii) Septic tank, soakaway 1 lot
SB-25
(In case of any item supplied from within the Employer's Country , please select the Items and indicate the prices)
Unit Currency(Taka) Local (Taka) Local (Taka)
(1) (3) (1) x (3)
Schedule No. 2. Plant and Mandatory Spare Parts Supplied from Within the Employer’s Country
Item Description Clause No of Scope of Works
EXW PriceCode
Unit PriceQty.
xix) Pump house including deep tubewell, motor, pump, water reservaoir, water pipe line, etc. 1 lot
xx) Guard house, sentry post, car port 1 lotxxi) Foundations for two (2) intermediate 4-circuit 230kV towers 2 nos.
xxii) Foundations for one (1) intermediate 2-circuit 230kV tower 1 no.1K.3 Main Control Building
i) Foundation works 1 lotii) Super structures 1 lot
iii) All finish works 1 lot1K.4 Switchyard panel rooms with batteries and chargers
i) Foundation works 1 lotii) Super structures 1 lot
iii) All finish works 1 lot1K.5 Switchyard panel rooms without batteries and chargers
i) Foundation works 1 lotii) Super structures 1 lot
iii) All finish works 1 lot1K.6 Fire fighting system for Transformers 1 lot1K.7 Fire alarm & fire fighting system 1 lot
Sub-total 1K1L Lighting, small power, air conditioning and Ventilation
1L.1Lighting, small power, air conditioning and Ventilation and emergency DC lighting for Main Control Building and Switchyard Panel Rooms
1 lot
1L.2Lighting for ouside buildings and relay houses for security, roadway, switchyard and emergency DC lighting including steel poles (H=6m)
1 lot
Sub-total 1L
1M Fibre Optic Multiplexer Equipment and PLC Equipment for Communication and Protection
1M.1 Indoor Fibre Optic Multipexer Equipment 1 lot
SB-26
(In case of any item supplied from within the Employer's Country , please select the Items and indicate the prices)
Unit Currency(Taka) Local (Taka) Local (Taka)
(1) (3) (1) x (3)
Schedule No. 2. Plant and Mandatory Spare Parts Supplied from Within the Employer’s Country
Item Description Clause No of Scope of Works
EXW PriceCode
Unit PriceQty.
1M.2 PABX 1 lot1M.3 Fibre Optic cable and termination box 1 lot1M.4 PLC Equipment 1 lot
Sub-total 1M1N SCADA system for Telecontrol and Telemetering1N1 Complete SCADA hardware & software 1 lot
Sub-total 1N
3A Shunt Reactor
3A.2400 kV, 40MVAR (ONAN), three phase outdoor type shunt reactor *4 2 sets
3A.3 420kV, 2000A, 50kA/1sec, 50Hz, 1425kVp BIL, gang operated, SF6 gas circuit breakers with support structure 2 sets
3A.4420kV, 2000A, 50kA/1sec, 50Hz, 1425kVp BIL, motor operated disconnectors with motor operated earthing switch with support structure
2 sets
3A.5 Control, Protection, Monitoring & Substation Automation System for 2 (2) sets of shunt reactor circuits 1 lot
3A.6Rigid tubular bus, flexible conductors, insulators, fittings including all necessary clamps and connectors for completing switchgear connection for Shunt Reactor bay
1 lot
3A.7All Civil works, Steel structures for gantry, equipment support, accessories and fittings for 420kV busbar and switchgear for two (2) Shunt Reactor bays
1 lot
Sub-total 3A
2 Mandatory Spares2.1 400kV AIS Equipment 2.1.1 420kV Circuit breaker2.1.1.1 Operating mechanism for circuit breaker 2 nos.2.1.1.2 Each type of closing coils and opening coils 15 nos.2.1.1.3 Each type of auxiliary contacts unit 3 nos.
SB-27
(In case of any item supplied from within the Employer's Country , please select the Items and indicate the prices)
Unit Currency(Taka) Local (Taka) Local (Taka)
(1) (3) (1) x (3)
Schedule No. 2. Plant and Mandatory Spare Parts Supplied from Within the Employer’s Country
Item Description Clause No of Scope of Works
EXW PriceCode
Unit PriceQty.
2.1.1.4 SF6 gas cylinders – 45kg 3 nos.2.1.2 Disconnector and earthing switch parts2.1.2.1 Operating mechanism for disconnector 2 nos.2.1.2.2 Mechnical Drive for high speed earthing switch 1 no.2.1.3 420 kV current transformer 1 no. each2.1.4 420 kV voltage transformer 1 no. each2.1.5 420kV complete set of Surge Arrester 1 no.
2.1.6 420kV Special Tool/Instrument for Operation and maintenance(To be listed up by bidder) 1 set
2.2 230kV AIS Equipment2.2.1 245kV Circuit breaker 2.2.1.1 Operating mechanism for circuit breaker 1 no.2.2.1.2 Each type of closing coils and opening coils 15 nos.2.2.1.3 Each type of auxiliary contacts unit 3 nos.2.2.2 245kV Disconnector and earthing switch parts2.2.2.1 Operating mechanism for disconnector 1 no.2.2.2.2 Mechnical Drive for high speed earthing switch 1 no.2.2.3 245 kV current transformer 1 no. each2.2.4 245 kV voltage transformer 1 no. each2.2.5 245kV Complete set of Surge Arrester 1 no.
2.2.6 245kV Special Tool/Instrument for Operation and maintenance(To be listed up by bidder) 1 set
2.3 36kV Switchgears2.3.1 36 kV Circuit breaker2.3.1.1 Operating mechanism for circuit breaker 1 no.2.3.1.2 Each type of closing coils and opening coils 10 nos.2.3.1.3 Each type of moving contacts and stationary contacts 3 nos.2.3.1.4 Vacume interupter chambers (in case of vacume breakers) 2 nos.2.3.2 36kV Disconnecting switch
SB-28
(In case of any item supplied from within the Employer's Country , please select the Items and indicate the prices)
Unit Currency(Taka) Local (Taka) Local (Taka)
(1) (3) (1) x (3)
Schedule No. 2. Plant and Mandatory Spare Parts Supplied from Within the Employer’s Country
Item Description Clause No of Scope of Works
EXW PriceCode
Unit PriceQty.
2.3.2.1 Set (3-phase) of moving & stationary contacts for each rating of36 kV disconnector 1 no.
2.3.2.2 Set (3-phase) of moving & stationary contact for each rating of36 kV earthing switch. 1 no.
2.3.2.3 Operating mechanism for disconnecting switch 1 no.2.3.2.4 Auxiliary contacts for disconnectors 3 nos.2.3.2.5 Auxiliary contacts for earth switch 3 nos.2.3.3 36 kV current transformer 1 no. each2.3.4 36kV voltage transformer 1 no. each
2.3.5 36kV Special Tool/Instrument for Operation and maintenance(To be listed up by bidder) 1 set
2.4 PROTECTION AND CONTROL 2.4.1 Each type of Protection Relay / AVR 1 set2.4.2 Each type of Tripping relays 2 sets2.4.3 Each type of Auxilliary relays 5 sets2.4.4 Each type of Trip circuit supervision relays 1 set2.4.5 Each type of Bay Control Unit 1 set2.4.6 Each type of Switch (if applicable ) 1 set2.4.7 Each type of MCB 1 set2.4.8 Each type of lamps 10 sets2.4.9 Industial PC 1 set2.4.10 Gateway Terminal 1 set2.4.11 Bay ethernet switches 2 nos.2.4.12 Optical connectors (one from each category) 1 lot2.5 DC & Charger EQUIPMENT 2.5.1 Each type of Printed Circuit Board used 1 lot
2.5.2 Minature circuit breakers of each type and rating(Bidders to list all types) 1 lot
2.6 LVAC EQUIPMENT
2.6.1 Miniature circuit breakers of each type and rating(Bidders to list all types) 1 lot
SB-29
(In case of any item supplied from within the Employer's Country , please select the Items and indicate the prices)
Unit Currency(Taka) Local (Taka) Local (Taka)
(1) (3) (1) x (3)
Schedule No. 2. Plant and Mandatory Spare Parts Supplied from Within the Employer’s Country
Item Description Clause No of Scope of Works
EXW PriceCode
Unit PriceQty.
2.7 POWER, CONTROL AND AUXILIARY CABLES 2.7.1 Power cables (36kV) 100m of each type 1 lot2.7.2 Control cables: 200m of each type 1 lot2.7.3 LV cables: 200m of each type 1 lot2.7.4 Other cables (communication, etc.): 100m of each type 1 lot2.8 TRANSFORMERS and SHUNT REACTORS 2.8.1 Auto Transformer2.8.1.1 420kV bushing 1 no.2.8.1.2 245 kV bushing 1 no.2.8.1.3 33 kV bushing 1 no.2.8.1.4 Set of gaskets for each transformer 1 no.2.8.1.5 Set of dial type thermometer with gaskets 1 no.2.8.1.6 Set of thermal image type indicator with gaskets 1 no.2.8.1.7 Set of Silica gel breather 1 no.2.8.1.8 Buchholz relay 1 no.2.8.1.9 Set of tap changer diverter switch 1 no.2.8.1.10 Tap changer control mechanism motor 1 no.2.8.1.11 Transformer oil 200 litter barrel. 20 nos.2.8.2 Earthing/Auxiliary Transformer2.8.2.1 33kV bushing 1 no.2.8.2.2 0.415kV bushing 1 no.2.8.2.3 Set of gaskets for each transformer 1 no.2.8.2.4 Set of dial type thermometer with gaskets 1 no.2.8.2.5 Set of thermal image type indicator with gaskets 1 no.2.8.2.6 Set of Silica gel breather 1 no.2.8.2.7 Buchholz relay 1 no.2.8.2.8 Transformer oil 200 litter barrel. 5 nos.2.8.3 Shunt Reactor2.8.3.1 420kV bushing 1 no.2.8.3.2 Set of gaskets for each transformer 1 no.2.8.3.3 Set of dial type thermometer with gaskets 1 no.
SB-30
(In case of any item supplied from within the Employer's Country , please select the Items and indicate the prices)
Unit Currency(Taka) Local (Taka) Local (Taka)
(1) (3) (1) x (3)
Schedule No. 2. Plant and Mandatory Spare Parts Supplied from Within the Employer’s Country
Item Description Clause No of Scope of Works
EXW PriceCode
Unit PriceQty.
2.8.3.4 Set of thermal image type indicator with gaskets 1 no.2.8.3.5 Set of Silica gel breather 1 no.2.8.3.6 Shunt reactor oil 200 litter barrel. 10 nos.2.9 Instruments for Communication & SCADA Maintenance 2.9.1 Digital data ( Communication) analyzer. 1 lot
2.9.2
Generator and Receiver for the following interfaces:(1) V.24 / RS232 SYNC AND ASYNC(2) V.35(3) G.703 CO-DIR AND 2048kbps and 704kbps(4) Bit Error rate measuring facility
1 lot
2.9.3 Digital selective level meter (50Hz to 600 kHz) plus level generator ( 50hz to 2Mhz) 1 lot
2.9.4 Subscriber Module for DCS 255 Exchange 1 lot2.1 Post Type Insulator2.10.1 For 420kV 3 nos.2.10.2 For 245kV 3 nos.2.11 Disk Insulator2.11.1 Each type of disc insulator 20 nos.each2.12 Conductor2.12.1 Bus Conductor for each size 100 m.each2.12.2 Rigid Tubler Condactor for each size 20 m.each2.13 Clamp and Fitting2.13.1 Clamp and fitting for each type 10 nos.each
Sub-total 2
TOTAL OF SCHEDULE NO.1(To be indicated in Schedule No.6 Grand Summary)
Foreign Currency (2)
Foreign Currency (1)
Foreign Currency (3)
Local Currency (Taka)
SB-31
(In case of any item supplied from within the Employer's Country , please select the Items and indicate the prices)
Unit Currency(Taka) Local (Taka) Local (Taka)
(1) (3) (1) x (3)
Schedule No. 2. Plant and Mandatory Spare Parts Supplied from Within the Employer’s Country
Item Description Clause No of Scope of Works
EXW PriceCode
Unit PriceQty.
Name of Bidder
1 Length for security boundary wall and chain link fencing shall be finalized during execution stage and payment shall be based on actual one.
Signature of Bidder
SB-32
Schedules of Rates and PricesCountry of Origin Declaration Form
Name of CountryCountry Code1 DescriptionSl.No
SB-33
CurrencyForeign
CurrencyPortion
LocalCurrencyPortion
Foreign Local
(1) (2) (3) (1) x (2) (1) x (3)
3.1 Project Managing/Engineering Fees 1 lot
3.2 EMTP Study 1 lot
Foreign Currency (2)
Description
TOTAL OF SCHEDULE NO.3(To be indicated in Schedule No.6 Ground Summary)
Signature of Bidder
Schedule No. 3. Design Services
Unit Price1
Name of Bidder __________________________________________________________
Total Price1
Qty.
(Special Notes)1) The Design Services, shall include Project managing/ engineering fees such as, Liaison, overall substation design, project schedule & control , drawings/ documentation handling, contract issues, cash flows, periodical reporting, Project progress meeting and etc., which are not including in equipment, installation, site testing and civil works for the Package SS-1 Contract.
2) The design fees for plant and mandatory spare parts shall be included in Schedule No .1 or 2.
3) The design fees for erection/Installation, commissioning and Civil works shall be including in related items of Schedule No.4.
Unit
Foreign Currency (1)
__________________________________________________________
Foreign Currency (3)
Local Currency (Taka)
Item
1 Specify currency in accordance with specifications in Bid Data Sheet under ITB 19.1 in Single-Stage Bid. Create and use as many columns for Unit Price and Total Price as there are currencies.
SB-34
Schedule No. 4.1 Civil Works, Installation and Site tests / Commissioning of Equipment
Unit CurrencyForeign Local (Taka) Foreign Local (Taka)
(1) (2) (3) (1) x (2) (1) x (3)
1A 420 kV Air Insulated Switchgear (AIS)
1A.1 420kV, 4000A, 50kA/1sec, 50Hz, 1425kVp BIL, gang operated, SF6 gas circuit breakers with support structure 6 sets
1A.2 420kV, 4000A, 50kA/1sec, 50Hz, 1425kVp BIL, single-pole operation, SF6 gas circuit breakers with support structure 4 sets
1A.3420kV, 2000A, 50kA/1sec, 50Hz, 1425kVp BIL, motor operated disconnectors with motor operated earthing switch (for Transmission Lines) with support structure
4 sets
1A.4 420kV, 4000A, 50kA/1sec, 50Hz, 1425kVp BIL, motor operated disconnectors without earthing switch with support structure 20 sets
1A.5 420kV, 2000A, 50kA/1sec, 50Hz, 1425kVp BIL, motor operated disconnectors (for Transformers) with support structure 2 sets
1A.6 420kV, 50kA/1sec, 50Hz, 1425kVp BIL, motor operated busbar earthing switch with support structure 2 sets
1A.7 Single-phase, 6-core, 420kV, 50kA/1sec, 4000A/1A, 50Hz, 1425kVp BIL, current transformer with support structure 42 nos.
1A.8 Single-phase, 3-winding, 420kV, 50kA/1sec, 50Hz, 1425kVp BIL, capacitive voltage transformers with support structure 24 nos.
1A.9390kV rated voltage, 303kV(rms) continuous operating voltage at 50oC, 10kA, 50Hz, Heavy duty station class, metal oxide type, single phase surge arresters with support structure
30 nos.
1A.10 wave trap (single phase, 420kV, 4000A, 1mH) with support structure and insulators 8 nos.
1A.11 Post type support insulators for busbar and switchgear with support structures for 400kV diameters 3 nos.
Unit Price1 Total Price1
Schedules of Rates and Prices 1) PGCB SCOPE WITHOUT EQUIPMENT FOR IPP POWER PLANTS
Schedule No. 4. Installation and Other Services
Item Description Clause No of Scope of Works
Qty.
SB-35
Schedule No. 4.1 Civil Works, Installation and Site tests / Commissioning of Equipment
Unit CurrencyForeign Local (Taka) Foreign Local (Taka)
(1) (2) (3) (1) x (2) (1) x (3)
Unit Price1 Total Price1
Schedule No. 4. Installation and Other Services
Item Description Clause No of Scope of Works
Qty.
1A.12Rigid tubular bus, flexible conductors, insulators, fittings including all necessary clamps and connectors for completing 420kV, 4000A, 50kA/1sec, 50Hz, 1425kVp BIL, busbar
1 lot
1A.13Rigid tubular bus, flexible conductors, insulators, fittings including all necessary clamps and connectors for completing 420kV switchgear connection
1 lot
1A.14 Steel structures for gantry, equipment support, accessories and fittings for 420kV busbar and switchgear 1 lot
Sub-total 1A1B 245kV Air Insulated Switchgear
1B.1 245kV, 3000A, 50kA/1sec, 50Hz, 1050kVp BIL, gang operated, SF6 gas circuit breakers with support structure 6 sets
1B.2 245kV, 3000A, 50kA/1sec, 50Hz, 1050kVp BIL, single-pole operation, SF6 gas circuit breakers with support structure 2 sets
1B.3245kV, 2000A, 50kA/1sec, 50Hz, 1050kVp BIL, motor operated disconnectors with motor operated earthing switch (for Transmission lines) with support structure
2 sets
1B.4 245kV, 3000A, 50kA/1sec, 50Hz, 1050kVp BIL, motor operated disconnectors without earthing switch with support structure 16 sets
1B.5245kV, 2000A, 50kA/1sec, 50Hz, 1050kVp BIL, motor operated disconnectors without earthing switch (for Transformers) with support structure
2 sets
1B.6 245kV, 50kA/1sec, 50Hz, 1050kVp BIL, motor operated busbar grounding switches with support structure 2 sets
1B.7 Single-phase, 5-core, 245kV, 3000A/1A, 50kA/1sec, 50Hz, 1050kVp BIL, current transformer with support structure 24 nos.
1B.8Single-phase, 2-core, 245kV, 3000A/1A, 50kA/1sec, 50Hz, 1050kVp BIL, current transformer (for Bus sectionalizers) with support structure
12 nos.
1B.9 Single-phase, 3-winding, 245kV, 50kA/1sec, 50Hz, 1050kVp BIL, capacitor type voltage transformers with support structure 18 nos.
SB-36
Schedule No. 4.1 Civil Works, Installation and Site tests / Commissioning of Equipment
Unit CurrencyForeign Local (Taka) Foreign Local (Taka)
(1) (2) (3) (1) x (2) (1) x (3)
Unit Price1 Total Price1
Schedule No. 4. Installation and Other Services
Item Description Clause No of Scope of Works
Qty.
1B.10196kV rated voltage, 160kV(rms) continuous operating voltage at 50oC 10kA, 50Hz, Heavy duty station class, metal oxide type, single phase surge arresters with support structure.
18 nos.
1B.11 Deleted
1B.12 Post type support insulators for busbar and switchgear with support structures for 245kV busbar and switchgear 3 nos.
1B.13Rigid tubular bus, flexible conductors, insulators, fittings including all necessary clamps and connectors for completing 245kV, 3000A, 50kA/1sec, 50Hz, 1050kVp BIL, busbar
1 lot
1B.14
Rigid tubular bus, flexible conductors, insulators, fittings including all necessary clamps and connectors for completing 245kV switchgear connection, including interconnection between new and existing 230kV switchyards
1 lot
1B.15Steel structures for gantry, accessories and fittings for 245kV busbar and switchgears, including interconnection between new and existing 230kV switchyards
1 lot
1B.16Equipment and material for interconnection between auto transformer side gantry and newly built 230kV switchyard bus side gantry
iEquipment and material for interconnection between auto transformer side gantry and newly built 230kV switchyard bus side gantry except intermediate two and four circuit 230kV towers
1 lot
ii Intermediate two-circuit 230kV tower 1 no.iii Intermediate four circuit 230kV tower 2 nos.
Sub-total 1B1C Deleted
Sub-total 1C1D 33kV Switches & connection
1D.1 36kV, 630A, 31.5kA/1sec, 50Hz, 170kVp BIL, SF6 gas or Vacuum circuit breaker with support structure 2 sets
SB-37
Schedule No. 4.1 Civil Works, Installation and Site tests / Commissioning of Equipment
Unit CurrencyForeign Local (Taka) Foreign Local (Taka)
(1) (2) (3) (1) x (2) (1) x (3)
Unit Price1 Total Price1
Schedule No. 4. Installation and Other Services
Item Description Clause No of Scope of Works
Qty.
1D.2 36kV, 630A, 31.5kA/1sec, 50Hz, 170kVp BIL, motor operated disconnectors with support structure 4 sets
1D.3Single-phase, 2-secondary winding, 36kV, 31.5kA/1sec, 50Hz, 170kVp BIL, inductive voltage transformers with support structure
6 nos.
1D.430kV rated voltage, 10kA nominal discharge current, 50Hz, Heavy duty station class, single phase surge arresters with support structure
6 nos.
1D.5
Tertiary side connection between 33kV terminal to switches/switchgear including necessary fittings, structures, conductors and 36kV XLPE cables for 2 sets of 400/235/33kV Auto transformer and 33/0.415kV Earthing/Auxiliary transformer
i
Tertiary side connection between 33kV terminal to switches/switchgear including necessary fittings, structures and conductors excluding 36kV XLPE cables for 2 sets of 400/235/33kV Auto transformer and 33/0.415kV Earthing/Auxiliary transformer
1 lot
ii 36kV XLPE cables 1 x 185mm2 240 meterSub-total 1D
1E Power Transformers and Earthing/Auxiliary Transformers1E.1 Deleted
1E.2 400/235/33 kV, 500/750MVA (ONAN/ONAF), three phase Auto Transformer 2 nos.
1E.3 33/0.415kV, 500kVA, three phase Earthing/Auxiliary Transformer 2 nos.
Sub-total 1E1F Control, Protection, Substation Automation and Metering
1F.1 Control, Monitoring, Protection & Substation Automation System for four (4) sets of 400kV overhead line circuits 4 sets
1F.2 Control, Monitoring, Protection & Substation Automation System for two (2) sets of 400kV auto transformer circuits 2 sets
1F.3 Control, Monitoring, Protection & Substation Automation System for 400kV busbar system 1 set
1F.4 Tariff metering for 400kV system 1 lot
SB-38
Schedule No. 4.1 Civil Works, Installation and Site tests / Commissioning of Equipment
Unit CurrencyForeign Local (Taka) Foreign Local (Taka)
(1) (2) (3) (1) x (2) (1) x (3)
Unit Price1 Total Price1
Schedule No. 4. Installation and Other Services
Item Description Clause No of Scope of Works
Qty.
1F.5 Digital Disturbance Recorder with Analysis Computor for 400kV system 1 lot
1F.6 Control, Monitoring, Protection & Substation Automation System for two (2) sets of 230kV overhead line circuits 2 sets
1F.7 Control, Monitoring, Protection & Substation Automation System for two (2) sets of 230kV auto transformer circuits 2 sets
1F.8 Control, Monitoring, Protection & Substation Automation System for 230kV busbar system 1 lot
1F.9 Tariff metering for 230kV system 1 lot
1F.10 Digital Disturbance Recorder with Analysis Computor for 230kV system 1 lot
1F.11Control, Monitoring, Protection & Substation Automation System for 33kV station power system including tariff metering for 0.415kV side
1 lot
Sub-total 1F 1G Multicore Cables
1G.1 Multicore low voltage power and control cables for control, protection, metering, monitoring and L/V power circuits 1 lot
Sub-total 1G1H Earthing and Lightning Protection1H.1 Earthing and Lightning Protection 1 lot1H.2 Portable(maintenance) earthing equipment device 2 sets
Sub-total 1H1I Batteries, chargers & DC distribution1I.1 110V Ni-cad Batteries with chargers and distribution boards
a) Batteries
i 110V Ni-cad Batteries, 330Ah @ 5h for 400kV and 33kV systems at 400kV Swtichyard Panel Room #1 2 sets
ii 110V Ni-cad Batteries, 250Ah @ 5h for 230kV system at 230kV Switchyard Panel Room #1 2 sets
b) Battery chargers
i Battery chargers for 400kV and 33kV systems at 400kV Switchyard Panel Room #1 2 sets
SB-39
Schedule No. 4.1 Civil Works, Installation and Site tests / Commissioning of Equipment
Unit CurrencyForeign Local (Taka) Foreign Local (Taka)
(1) (2) (3) (1) x (2) (1) x (3)
Unit Price1 Total Price1
Schedule No. 4. Installation and Other Services
Item Description Clause No of Scope of Works
Qty.
ii Battery chargers for 230kV system at 230kV Switchyard Panel Room #1 2 sets
c) Distributuon boards
i Distribution boards for 400kV and 33kV systems at 400kV Switchyard Panel Room #1 & #2 2 sets
ii Distribution boards for 230kV system at 230kV Switchyard Panel Room #1 & #2 2 sets
1I.248V Ni-cad Batteries 250Ah including chargers (each 2 sets) and distribution board and 240V, 1.5kVA UPS for SAS (2 sets) at Main Control Building
i 48V Ni-cad Batteries, 250Ah @ 5h 2 setsii 48V Battery chargers 2 sets
iii DC Distribution boards 2 sets
iv 1.5kVA, 240V, 50Hz UPS powered from 48V DC distribution board for Substation Automation System 2 sets
Sub-total 1I1J LVAC Distribution1J.1 LVAC switchboard for substation services 1 lot1J.2 Tariff metering panel for LV system 1 lot
Sub-total 1J1K Civil Works, Building and Foundation
1K.1 The land development of two substation areas: 400kV and 230kV 1 lot
1K.2 Complete outdoor civil works excluding Main Control Building and SPR buildings
i) Outdoor gantry foundation 400kV switchyard 1 lotii) Outdoor equipment foundation 400kV switchyard 1 lot
iii) Outdoor gantry foundation 230kV switchyardiii) a Gantry foundation for new 230kV switchyard 1 lot
iii) b Gantry foundation for interconnection of new and existing 230kV switchyard 1 lot
iv) Outdoor equipment foundation 230kV switchyard 1 lotv) Outdoor gantry foundation 33kV switchyard 1 lot
vi) Outdoor equipment foundation 33kV switchyard 1 lot
SB-40
Schedule No. 4.1 Civil Works, Installation and Site tests / Commissioning of Equipment
Unit CurrencyForeign Local (Taka) Foreign Local (Taka)
(1) (2) (3) (1) x (2) (1) x (3)
Unit Price1 Total Price1
Schedule No. 4. Installation and Other Services
Item Description Clause No of Scope of Works
Qty.
vii) Transformer foundation including oilpit & carrage way 1 lotviii) Blast wall 1 lot
ix) Secutiry boundary wall for 400kV and 230kV switchyards *3 2200 meter
x) Two (2) substation main gates (400kV and 230kV switchyards) 1 lot
xi) Chain link fencing *3 including three (3) personel gates 1000 meterxii) Approach road 1 lot
xiii) Internal road 1 lotxiv) Surface draing 1 lotxv) Cable trench 1 lot
xvi) Switchyard surface finishing, drainage system including surface drain 1 lot
xvii) Gravel laying 1 lotxviii) Septic tank, soakaway 1 lot
xix) Pump house including deep tubewell, motor, pump, water reservaoir, water pipe line, etc. 1 lot
xx) Guard house, sentry post, car port 1 lotxxi) Foundations for two (2) intermediate 4-circuit towers 2 nos.
xxii) Foundations for one (1) intermediate 2-circuit tower 1 no.1K.3 Main Control Building
i) Foundation works 1 lotii) Super structures 1 lot
iii) All finish works 1 lot1K.4 Switchyard panel rooms with batteries and chargers
i) Foundation works 1 lotii) Super structures 1 lot
iii) All finish works 1 lot1K.5 Switchyard panel rooms without batteries and chargers
i) Foundation works 1 lotii) Super structures 1 lot
iii) All finish works 1 lot1K.6 Fire fighting system for Transformers 1 lot1K.7 Fire alarm & fire fighting system 1 lot
SB-41
Schedule No. 4.1 Civil Works, Installation and Site tests / Commissioning of Equipment
Unit CurrencyForeign Local (Taka) Foreign Local (Taka)
(1) (2) (3) (1) x (2) (1) x (3)
Unit Price1 Total Price1
Schedule No. 4. Installation and Other Services
Item Description Clause No of Scope of Works
Qty.
Sub-total 1K1L Lighting, small power, air conditioning and Ventilation
1L.1Lighting, small power, air conditioning and Ventilation and emergency DC lighting for Main Control Building and Switchyard Panel Rooms
1 lot
1L.2Lighting for ouside buildings and relay houses for security, roadway, switchyard and emergency DC lighting including steel poles (H=6m)
1 lot
Sub-total 1L
1M Fibre Optic Multiplexer Equipment and PLC Equipment for Communication and Protection
1M.1 Indoor Fibre Optic Multipexer Equipment 1 lot1M.2 PABX 1 lot1M.3 Fibre Optic cable and termination box 1 lot1M.4 PLC Equipment 1 lot
Sub-total 1M1N SCADA system for Telecontrol and Telemetering1N1 Complete SCADA hardware & software 1 lot
Sub-total 1N3A Shunt Reactor
3A.2400 kV, 40MVAR (ONAN), three phase outdoor type shunt reactor *4 2 sets
3A.3 420kV, 2000A, 50kA/1sec, 50Hz, 1425kVp BIL, gang operated, SF6 gas circuit breakers with support structure 2 sets
3A.4420kV, 2000A, 50kA/1sec, 50Hz, 1425kVp BIL, motor operated disconnectors with motor operated earthing switch with support structure
2 sets
3A.5 Control, Protection, Monitoring & Substation Automation System for 2 (2) sets of shunt reactor circuits 1 lot
3A.6Rigid tubular bus, flexible conductors, insulators, fittings including all necessary clamps and connectors for completing switchgear connection for Shunt Reactor bay
1 lot
SB-42
Schedule No. 4.1 Civil Works, Installation and Site tests / Commissioning of Equipment
Unit CurrencyForeign Local (Taka) Foreign Local (Taka)
(1) (2) (3) (1) x (2) (1) x (3)
Unit Price1 Total Price1
Schedule No. 4. Installation and Other Services
Item Description Clause No of Scope of Works
Qty.
3A.7All Civil works, Steel structures for gantry, equipment support, accessories and fittings for 420kV busbar and switchgear for two (2) Shunt Reactor bays
1 lot
Sub-total 3A
2 Length for security boundary wall and chain link fencing shall be finalized during execution stage and payment shall be based on actual one.
Local Currency (Taka)
1 Specify currency in accordance with specifications in Bid Data Sheet under ITB 19.1 in Single-Stage Bid. Create and use as many columns for Unit Price and Total Price as there are currencies.
Signature of Bidder
Name of Bidder
TOTAL OF SCHEDULE NO. 4.1(To be indicated in Schedule No.6 Grand Summary)
Foreign Currency (3)
Foreign Currency (1)
Foreign Currency (2)
SB-43
Schedule No. 4.2 –Other Services
Unit CurrencyForeign Local (Taka) Foreign Local (Taka)
(1) (2) (3) (1) x (2) (1) x (3)
4.2.1 International Training
(a)Control, protection & Substation Automation System (SAS) at Manufactuerer's WorksTwo (2) Engineers, Two (2) weeks
1 lot
(b)SCADA telecommunication system including multiplexer and PABX at Manufacturer's WorksTwo (2) Engineers, Two (2) weeks
1 lot
(c)Design for HV AIS Substation at International Reputed Training CenterFour (4) Engineers, Two (2) weeks
1 lot
(d)Operation and Maintenance for HV AIS Substation at International Reputed Training CenterEight (8) Engineers, Two (2) weeks
1 lot
Sub-total 4.2.1
4.2.2 Witness of Factory Acceptance Tests of Equipment
(a) 400/235/33kV, Three (3) Phase, 750MVA Auto TransformersTwo (2) Engineers with one (1) Consultant, Ten (10) days 1 lot
(b) 400kV, 40MVAr, Shunt ReactorTwo (2) Engineers with one (1) Consultant, Seven (7) days 1 lot
(c ) 420kV and 245kV Gas Insulated Circuit Breakers (GCB)Two (2) Engineers, Five (5) days 1 lot
(d) 420kV and 245kV Disconnector with Earthing SwitchesTwo (2) Engineers, Five (5) days 1 lot
Unit Price1 Total Price1
Schedules of Rates and PricesSchedule No. 4. Installation and Other Services
Item Description Clause No of Scope of Works
Qty.
SB-44
Schedule No. 4.2 –Other Services
Unit CurrencyForeign Local (Taka) Foreign Local (Taka)
(1) (2) (3) (1) x (2) (1) x (3)
Unit Price1 Total Price1
Schedule No. 4. Installation and Other Services
Item Description Clause No of Scope of Works
Qty.
(e) 420kV and 245kV Instrument Transformers (CT, CVT)Two (2) Engineers, Five (5) days 1 lot
(f) 420kV and 245kV Lightning ArrestersTwo (2) Engineers, Five (5) days 1 lot
(g) Control, Protection & Substation Automation System (SAS)Two (2) Engineers with one (1) Consultant, Five (5) days 1 lot
(h) DC Chargers and distribution boardsOne (1) Engineer, Three (3) days 1 lot
Sub-total 4.2.2
4.2.3 O & M Training at Site
(a)
420kV and 245kV Air Insulated Switchgear, 400/235/33kV 750MVA Auto Transformer, Protection and Substation Automation System (SAS), Fibre Optic Multiplexer & PABX(Fifteen (15) Engineers x 2 Weeks)
1 lot
Sub-total 4.2.3
4.2.4 Employer's Engineer's Office Accomodation at Site
(a) Office accommodation with specified facilities and services during construction period 1 lot
(b) Security guard services for Engineer's Office at Site 1 lot
Sub-total 4.2.4
TOTAL OF SCHEDULE NO.4.2(To be indicated in Schedule No.6 Grand Summary)
Foreign Currency (1)
Foreign Currency (2)
Foreign Currency (3)
SB-45
Schedule No. 4.2 –Other Services
Unit CurrencyForeign Local (Taka) Foreign Local (Taka)
(1) (2) (3) (1) x (2) (1) x (3)
Unit Price1 Total Price1
Schedule No. 4. Installation and Other Services
Item Description Clause No of Scope of Works
Qty.
Name of Bidder
Signature of Bidder
1 Specify currency in accordance with specifications in Bid Data Sheet under ITB 19.1 in Single-Stage Bid. Create and use as many columns for Unit Price and Total Price as there are currencies.
Local Currency (Taka)
SB-46
Unit CurrencyForeign Local (Taka) Foreign Local (Taka)
(1) (2) (3) (1) x (2) (1) x (3)
5.1 Security Infrastructure
5.1.1 Perimeter Security Fence
5.1.1.1 Construction (Relocating Facility only)
5.1.1.2 Maintenance (Overall Lenghth of Road) (up to TOC)
5.1.2 Watch Tower with Security Alarms and Searchlights (including the payment of electricity bill)
5.1.2.1 Construction and Installation (Additional )
5.1.2.2 Relocation
5.1.2.3 Maintenance (Overall Lenghth of Road) (up to TOC)
5.1.3 Security Lighting along the Perimeter Fence
5.1.3.1 Construction and Installation (Relocating Facility only)
5.1.3.2 Maintenance (Overall Lenghth of Road) (up to TOC)
5.1.4 Security Barriers and Gates
5.1.4.1 Construction and Installation
5.1.4.2 Maintenance(up to TOC)
5.1.5 Security Command and Control Centre (SCCC)
5.1.5.1 SCCC Prefabricated Building with Utility Facilities
5.1.5.2 Equipment Furniture and Furnishing
Schedules of Rates and PricesSchedule of No.5 Provisional Sums
Item Description Clause No of Scope of Works
Qty.
FOB PriceCIP
Provisional sum of security module shall be as per Section 23 of Vol. 3 of Bidding Document, and the Bidder may insert more items in the below table but the total price shall not exceed the ceiling amount BDT 20,000,000. (This price is excluded from the price bid evaluation.)
CIP
Unit Price1 Total Price1
SB-47
Unit CurrencyForeign Local (Taka) Foreign Local (Taka)
(1) (2) (3) (1) x (2) (1) x (3)
Schedule of No.5 Provisional Sums
Item Description Clause No of Scope of Works
Qty.
FOB PriceCIP
Provisional sum of security module shall be as per Section 23 of Vol. 3 of Bidding Document, and the Bidder may insert more items in the below table but the total price shall not exceed the ceiling amount BDT 20,000,000. (This price is excluded from the price bid evaluation.)
CIP
Unit Price1 Total Price1
5.1.5.3 Maintenance
5.1.6 Redundant Power Supply for All Security Lighting, Watch Tower and Associated Equipment (inculding that provided
5.1.6.1 Supply and Installation
5.1.6.2 Maintenance
5.1.6.3 Fuel
5.1.7 Maintenance of helipad
5.2 Security Equipment
5.2.1 CCTV
5.2.1.1 Supply and Installation of CCTV Cameras(To install two camera associate with W/T)
5.2.1.2 Supply and Installation of CCTV Monitoring System
5.2.1.3 Maintenance of CCTV Cameras and Monitoring System
5.2.2 Security Alarm System
5.2.2.1 Supply and Installation
5.2.2.2 Maintenance
5.2.3 Security Equipment
5.2.3.1 Supply and Installation of Door Frame Metal Detector
5.2.3.1 Maintenance of Door Frame Metal Detector
5.2.3.3 Supply of Hand Held Metal Detector
SB-48
Unit CurrencyForeign Local (Taka) Foreign Local (Taka)
(1) (2) (3) (1) x (2) (1) x (3)
Schedule of No.5 Provisional Sums
Item Description Clause No of Scope of Works
Qty.
FOB PriceCIP
Provisional sum of security module shall be as per Section 23 of Vol. 3 of Bidding Document, and the Bidder may insert more items in the below table but the total price shall not exceed the ceiling amount BDT 20,000,000. (This price is excluded from the price bid evaluation.)
CIP
Unit Price1 Total Price1
5.2.3.4 Maintenance of Hand Held Metal Detector
5.2.3.5 Supply and Installation of PTZ Camera for main entry gates (including cabling)
5.2.3.6 Maintenance of PTZ Camera
5.2.3.7 Radio Sets
5.2.4 Communication Equipment
5.2.4.1 GPS Tracking, First-Aid-Kit and mobile Phone Communication fitted with vehicles and Boat
5.2.4.2 Communication Charge
5.2.5 Identification Bade / Card System
5.2.5.1 Supply and Maintenance
5.2.6 Consultation with security agencies in periodical review
5.2.7 Evacuation in case of Emergency
5.3 Security Personnel for Additional Security Module
5.3.1 Security Supervisors
5.3.2 Security Guards
Foreign Currency (1)
Foreign Currency (2)
Foreign Currency (3)
TOTAL OF SCHEDULE NO. 5(To be indicated in Schedule No.6 Grand Summary)
SB-49
Unit CurrencyForeign Local (Taka) Foreign Local (Taka)
(1) (2) (3) (1) x (2) (1) x (3)
Schedule of No.5 Provisional Sums
Item Description Clause No of Scope of Works
Qty.
FOB PriceCIP
Provisional sum of security module shall be as per Section 23 of Vol. 3 of Bidding Document, and the Bidder may insert more items in the below table but the total price shall not exceed the ceiling amount BDT 20,000,000. (This price is excluded from the price bid evaluation.)
CIP
Unit Price1 Total Price1
Name of Bidder
Signature of Bidder
1 Specify currency in accordance with specifications in Bid Data Sheet under ITB 19.1 in Single-Stage Bid. Create and use as many columns for Unit Price and Total Price as there are currencies.
Local Currency (Taka)
SB-50
Foreign Local (Taka)
Currency 1
Currency 2
Currency 3
Currency 1
Currency 2
Currency 3
Currency 1
Currency 2
Currency 3
Currency 1
Currency 2
Currency 3
Currency 1
Currency 2
Currency 3
Currency 1
Currency 2
Currency 3
6.5
Foreign Currency (1)
Foreign Currency (2)
Foreign Currency (3)
Local Currency (Taka)
Name of Bidder
Signature of Bidder
Description
Total Schedule No.1 (Plant and Equipment, Mandatory Spare Parts and Instrument supplied fromAbroad)
Schedules of Rates and Prices 1) PGCB SCOPE WITHOUT EQUIPMENT FOR IPP POWER PLANTS
Schedule of No.6 Grand Summary
Item
Not Applicable
6.2
1 Specify currency in accordance with specifications in Bid Data Sheet under ITB 19.1 in Single-Stage Bid. Create and use as many columns for Unit Price and Total Price as there are currencies.
Sub-totalSchedule No.4.2(Other Services)
Total Schedule No.4 (Installation and Other Services)
Sub-totalSchedule No.4.1(Civil Works, Installation, Site Tests and Commissioning of Plant)
Total Schedule No.5 (Provisional Sums)
Foreign Currency
Total Schedule No.2 (Plant and Equipment, Mandatory Spare Parts and Instrument supplied from Within the Employer's Country)
Total Schedule No.3 (Design Services)
Total Price1
6.3
6.1
6.6GRAND TOTAL (Schedule No.1 to Schedule No.4 to Letter of Price Bid)
Total(4.1 + 4.2)
6.4
SB-51
Code 1 Unit FOB Price
(Country) Foreign Currency Local Currency Foreign Currency Local Currency(1) (2) (3) (4) (1) x (3) (1) x (4)
Name of Bidder ________________________________________________
Signature of Bidder ________________________________________________
1 Bidder shall enter a code representing the country of origin of all imported plant and equipment.
2 Specify currency in accordance with specifications in Bid Data Sheet under ITB 19.1 in Single-Stage Bid. Create and use as many columns for Unit Price and Total Price as there are curencies.
Schedules of Rates and PricesSchedule No. 7. Recommended Spare Parts
Item DescriptionQty.
Unit Price2
Currency CIP PriceTotal Price2
CIP Price
Currency 1
Currency 2
Currency 3
Local Currency (Taka)
TOTAL SCHEDULE NO.7 Recommended Spare Parts
SB-52
SCHEDULE No. 8 - DAY WORKS
1)
LABOUR
2)
3)
4)
5)
6)
7)
No works whatsoever may be executed as day works, nor will payment be made for any Day works except in accordance with provisions of the Conditions of Contract, and with prior written authorization of the Engineer/ Employer.
The Contractor shall be entitled to the following payments in respect of labour employed on Day works:
The aggregate amount of wages for such labour calculated on the actual hours worked at the wage rate set out in this schedule up to the grade of charge hand or overseer working with the men.
The wages given in this schedule shall cover Contractor’s profit, on cost, superintendence, insurance and all allowances to labour, time keeping and all clerical and office work as well as the use of tools, timber, light equipment and non-mechanical equipment and all incidental charges whatever.
The “Normal working Day” as hereinafter referred to shall be taken to be of eight hours excluding meal breakers and rest periods.
Including the sums due to the Contractor for the execution of Day works, the hours for which payment shall be made for all personnel and the hire of all equipment shall be reckoned from the time of starting the particular item of day work, either at the beginning of or during the course of a normal working day to the end of the normal working day or the time of completion of the particular item of Day work, whichever maybe sooner. No payment shall be made for personnel or plant for hours outside the normal working day unless the said personnel and plant are employed on Day works outside the Normal Working Day on the written instruction of the Employer’s Representative, The same Day work rate shall apply for works done both during and outside the Normal Working Day.
On completion of any authorized Day works, a written statement shall be issued by the Employer’s Representative who shall sign it together with the Contractor and which shall state the number of workmen and their grades involved in the Day work, the number of hours worked and a detailed description of the Material used and the work carried out. A copy of this signed statement shall be retained by the Employer’s Representative and the Contractor and shall be the sole basis upon which payment for Day Works will be made.
Day Work Rate for Labour
Class of Labour Normal Working Day of 8 Hours Local Taka/Day
Local Labour
Unskilled Labourer
Skilled Labourer
Driver
Steel Erector
Surveyor (on survey work only)
Mason/ concrete work
Carpenter
Bar-bender/ Steel fixer
Welder
Welder’s assistant
Painter
Crane operator
Bulldozer/ grader operator
Expatriate Labour Normal Working Day of 8 Hours Foreign Currency - Per Day
Junior Engineer
Senior Engineer
Schedules of Rates and Prices
SB-53
8)
9)
10)
11)
12)
13)
14)
1
a. hr.
b. hr.
c. hr.
d. hr.
e. hr.
f. hr.
g. hr.
h. hr.
i. hr.
j. hr.
k. hr.
l. hr.
m. hr.
n. hr.
o. hr.
p. hr.
q. hr.
r. hr.
s. hr.
Any other class of labour envisaged by Contractors for the execution of any Day works, except that covered by Paragraph 3 above, i.e. superintendent, etc., shall be entered above together with the appropriate labour rates, and such rates shall be the only rates considered in any Day works claim.
The labour rates to be entered above shall include all other benefits or contributions made by the employer such as contributions to Social Insurance Schemes, Annual leave, Termination of Employment and Redundancy Law, Provident fund, Health Schemes, etc.; which are imposed either by Law or by agreement with Trade Unions.
EQUIPMENT AND TRANSPORT
The rates for hire of equipment and transport shall apply only to equipment, which the Contractor has on site, and are to apply for the actual running for which the equipment is employed on work.
The rates shall include service, operators and necessary attendants, fuel, lubricants and other consumable.
The Contractor may insert additional items.
MATERIALS
The rates for materials shall apply to the net amount of materials actually provided, erected and foaming part of the works and shall include for delivery to the site of operations.
The Contractor may insert additional items.
Equipment (with operator)
Rate
LocalForeignItem Description Unit
Mobile Welding set
Acetylene cutting equipment
Air compressor (180m3/hr. atmosphere) complete with hoses and toolsDump truck 6 Cu.m capacity
Crane up to 6 Tonnes lift
Drilling equipment
Compactor Machine
Water Pump
Vibrator Machine with porker
Small Generator and mobile Lighting Facility
Excarator
Vibrator Roller
Scaffoliding Sets
Tractor without winch
5- tonne lorry
2 - tonne lorry
5- seater saloon car (or similar)
Bulldozer (D6 or similar)
Pick-up Truck
SB-54
2a. tonb. m3
c. m3
d. ton
e. m3
f. m2
g. m2
h. m3
i. m2
j. m3
k. m3
l. m3
m. m3
MaterialCementSand
Crushed Stone
Reinforcing Steel
Imported material for backfilling
Timber shoring
Sheet piling
Gabion walls with mesh
Turfing of slopes
150mm-100mm Base course for roads
50mm-20mm Base for roads
150mm thick premix-Asphalt layer
Rubble stones for foundation work (150-300mm dia.)
SUPERVISORY STAFF RATES
The following rates shall apply where, by agreement with Employer’s Representative, supervisory staff are employed on Day works in a direct capacity, i.e. other in their normal supervisory capacity.
The rates also be used as a basis for assessing any legitimate claims for extra costs in accordance with the provision of the Conditions of Contract, where these have not been claimed as Day works.
No payment shall be made without the prior written authority of the Engineer, and the provisions of the Conditions of Contract shall apply to any claim for payment.
Local Currency/Taka./ DayLocal
The Contractor shall insert in the following schedule descriptions and rates for any class of supervisory staff envisaged which are not already included.
Class of supervisory staff Normal working Day of 8 Hours
Expatriate
Senior Engineer
Senior Engineer - Civil /Structural
Junior Engineer - Civil / Structural
Architect
Surveyor
Supervisor
Foreman
Junior Engineer
Foreign Currency/ Day
SB-55