Power Generation Clyde

download Power Generation Clyde

of 31

Transcript of Power Generation Clyde

  • 8/2/2019 Power Generation Clyde

    1/31

    Power Generation

  • 8/2/2019 Power Generation Clyde

    2/31

    Faradays Law

    An electrical current flowing in a conductor will induce

    a magnetic field around the conductor Right hand rule

    Changing the magnetic flux around a conductor willgenerate an electrical current

  • 8/2/2019 Power Generation Clyde

    3/31

    Electromagnet

    Remember the days from elementary school where

    you took wire and wrapped it around a nail, hooked itto a 6 volt lantern battery to produce a simpleelectromagnet

    Think about how a magnetic pickup for speedmeasurement works. It is a simple permanent magnetwith a coil of wire wrapped around it.

    The gear teeth change the magnetic flux whichresults in voltage being generated in the coil ofwires

  • 8/2/2019 Power Generation Clyde

    4/31

    How Does a Generator Work

    A simple AC generator consists of two parts:

    Rotor

    - Turned by the driver and consists of a coil of wireswound around a magnetic material to produce arotating magnetic field

    Stator or Armature

    - Rotating magnetic field induces a voltage in this coil ofwires

  • 8/2/2019 Power Generation Clyde

    5/31

    Multiple Pole Generator

    Adding additional magnets or poles will change the

    frequency for a given speed

    RPM = FrequencyPairs of Poles

    60 *

  • 8/2/2019 Power Generation Clyde

    6/31

    Generator Field

    The generator field provides the power for the rotating

    electromagnet The voltage regulator adjusts the DC voltage that is

    used for the field

    If the unit is not synchronized with another generator,

    increasing the field voltage increases the outputvoltage of the generator

    If the unit is synchronized with another generator,increasing the field voltage lowers the power factor ofthe generator

    The field must operate within set limits to assure thatthere is sufficient magnetic field to produce the voltage

  • 8/2/2019 Power Generation Clyde

    7/31

    3 Generators

    3 generators have 3 windings in the stator that arespaced 120 apart to produce 3 independent outputs

    Time

    VoltagePhase

    A

    Phase

    B

    Phase

    C

  • 8/2/2019 Power Generation Clyde

    8/31

    Frequency or Isochronous Control

    The output frequency is controlled by changing the

    speed of the generator As the load changes, the turbine controller will

    change the energy input to hold the speed constant

    A simple PID controller could be used for this purpose

    PIDSpeed Setpoint

    Speed

    Control Outputto Valve

  • 8/2/2019 Power Generation Clyde

    9/31

    Load or Droop Control

    In some of the older control systems, droop control

    was the standard mode of control Droop control is Proportional control only

    The speed/load curve for a droop controller looks likethe following:

    Speed

    Load

    Setpoint=3600 rpm

    25% 100%75%50%

    3420 rpm

    Frequency

    60 Hz

    57 Hz

    Droop settingof 5%

  • 8/2/2019 Power Generation Clyde

    10/31

    Droop Control

    Generator control system has been refined to allow

    other control variables to be used for the loadreference

    Allows linear control through out the operatingrange

    PIDSpeed

    Speed Setpoint

    Control Outputto Valve

    +-

    Sync Speed * Droop *% Output Selector PCD

    Power

  • 8/2/2019 Power Generation Clyde

    11/31

    Droop Control Curve

    Increasing the setpoint will increase the load with the

    modified control configuration

    Speed

    Load

    Setpoint=3600 rpm

    25% 100%75%50%

    Frequency

    60 Hz

    57 Hz

    Droop settingof 5%

    Setpoint=3780 rpm

  • 8/2/2019 Power Generation Clyde

    12/31

    Droop / Isochronous Control

    The control system monitors the status of the breakers

    in the system to determine whether operation shouldbe as an isochronous unit or as a droop control unit

    Also monitors breakers to determine is load rejectionshave occurred so that a feed-forward response can beinitiated to prevent undesirable actions such as a trip

  • 8/2/2019 Power Generation Clyde

    13/31

    Load Sharing

    With multiple generators connected to the grid, it may

    be desirable to have the generators sharing the loadproportional to their size

    accomplished by monitoring the load of allmachines and taking the average

    - this average becomes the setpoint for eachgenerator

  • 8/2/2019 Power Generation Clyde

    14/31

    Parallel Isochronous Control

    In some systems, it may be desirable for all of the

    generators to operate collectively to control thefrequency of the system. This is called ParallelIsochronous control

  • 8/2/2019 Power Generation Clyde

    15/31

    Infinite Buss Theory

    The Infinite Buss theory was used to simplify the

    control of generators. It stated that the power grid wasso large and inflexible that no single generator couldaffect the frequency of the system

    good in theory, but not in reality

  • 8/2/2019 Power Generation Clyde

    16/31

    Power Factor

    Power factor is the phase relationship between the voltageand current

    Voltage leading current is a lagging power factor

    Voltage lagging current is a leading power factor

    Power factor is the cosine of the angle between the voltageand current

    Time

    Voltage

    Current

    60PF = cosine (60)PF = .5

  • 8/2/2019 Power Generation Clyde

    17/31

    Power Factor Control

    Power factor of the installed electrical system isdetermined by the installed equipment

    induction motors lagging power factor

    capacitors leading power factor

    Generator can be used to supply vars (imaginary powerthat is used to generate the magnetic field in motors,etc.)

    Power factor is adjusted by changing the fieldexcitation

    Generator has a defined operating area that must be

    adhered to Control system can be used to protection the

    generator from over/under excitation

  • 8/2/2019 Power Generation Clyde

    18/31

    Generator Capacity Curve

    Defines the operating area of

    the generator Stability limit

    Stator heating limit

    MW limit

    Rotor heating

    Max excitation current

    Rated MVA

    Operating point

    Power Factor

    +MVAR

    -MVAR

    MW

    Rotor Field Heating Limit

    Maximum Excitation Limit

    MW Limit

    Rated MVA

    Stator Heating Limit

    Stability Limit

    PF = Cos

    Generator OperatingPoint

  • 8/2/2019 Power Generation Clyde

    19/31

    Synchronization

    Synchronization allows multiple generators to be

    placed on line If the generators are not synchronized correctly, severe

    damage can result to the generators

    Synchronization is nothing more than the alignment of

    the rotating magnetic fields in the generators Three conditions must be met for the synchronization

    to be successful

    Frequencies must be matched

    Voltages must be matched Phase angles must be matched

  • 8/2/2019 Power Generation Clyde

    20/31

    Synchronization Frequency

    The units must be operating at the same relativefrequency for synchronization to be successful

    Low generator frequency

    - generator speeds up instantly on breaker closure

    High generator frequency

    - generator slows down instantly on breaker closure Units are not designed for the sudden speed changes if

    not synchronized correctly

    During synchronization, the speed of the generator isslightly higher than the buss frequency to allow currentto flow from the generator when the breaker closes

  • 8/2/2019 Power Generation Clyde

    21/31

    Synchronization Voltage

    Voltages must be matched prior to synchronization

    Low generator voltage will result in an in-rush ofcurrent into the generator

    - rotor heating

    - may trip protection relays

    Generator voltage slightly higher than bussrecommended to allow current flow into grid

    On breaker closure, field controls Power Factor insteadof voltage

  • 8/2/2019 Power Generation Clyde

    22/31

    Synchronization Phase

    Synchroscope measures the voltage difference

    between the buss and generator to determine thephase angle

    Breaker should be closed when there is no phasedifference between the two signals

  • 8/2/2019 Power Generation Clyde

    23/31

    Synchronization Phase Example

    Time

    Voltage Buss Gen

    Time

    Voltage

    Buss

    Gen

    Generator out of phase

    Generator in phase

  • 8/2/2019 Power Generation Clyde

    24/31

    Automatic Synchronizers

    Automatic synchronizers are often used to perform the

    synchronization task Match the frequency, voltage, and phase but also have

    some intelligence

    generator frequency is slightly than buss and that

    the phase angle is changing to assure that theunits are operating correctly

    anticipate the closing speed of the breaker toassure that the breaker closes at 0 phasedifference

    detect and close on dead busses

    Require the use of a synch check relay

  • 8/2/2019 Power Generation Clyde

    25/31

    Generator Metering and Synchronization

  • 8/2/2019 Power Generation Clyde

    26/31

    Generator Relaying

    Relaying is used to protect the generator from abnormal

    conditions like over-current, voltage unbalance, currentdifferential, power, etc.

    This can be a number of individual protective devicesor a single relay that is designed to incorporate all ofthe functions

  • 8/2/2019 Power Generation Clyde

    27/31

    IEEE Numbering System

    IEEE C37.2 defines device numbers

    25 Sync Check Relay25A Automatic Synchronizing Relay

    27 Undervoltage Relay

    32 Power Relay

    37 Undercurrent Relay

    40 Loss of Field Relay

    41 Field Relay

    43 Manual Selector Switch49 Temperature Relay

    50 Instantaneous Overcurrent Relay

    51 Time Overcurrent Relay

    52 AC Circuit Breaker

    55 Power Factor Relay

    59 Overvoltage Relay

    65 Governor74 Alarm Relay

    81 Frequency Relay

    86 Lockout Relay

    90 Voltage Regulator

  • 8/2/2019 Power Generation Clyde

    28/31

    Typical One Line Diagram

  • 8/2/2019 Power Generation Clyde

    29/31

    Generator and Voltage Regulator

  • 8/2/2019 Power Generation Clyde

    30/31

    Relaying and Metering

  • 8/2/2019 Power Generation Clyde

    31/31

    Synchronization