Magneto hydro dynamic power generation (mhd power generation)
Power Generation Clyde
-
Upload
johncoberra -
Category
Documents
-
view
229 -
download
0
Transcript of Power Generation Clyde
-
8/2/2019 Power Generation Clyde
1/31
Power Generation
-
8/2/2019 Power Generation Clyde
2/31
Faradays Law
An electrical current flowing in a conductor will induce
a magnetic field around the conductor Right hand rule
Changing the magnetic flux around a conductor willgenerate an electrical current
-
8/2/2019 Power Generation Clyde
3/31
Electromagnet
Remember the days from elementary school where
you took wire and wrapped it around a nail, hooked itto a 6 volt lantern battery to produce a simpleelectromagnet
Think about how a magnetic pickup for speedmeasurement works. It is a simple permanent magnetwith a coil of wire wrapped around it.
The gear teeth change the magnetic flux whichresults in voltage being generated in the coil ofwires
-
8/2/2019 Power Generation Clyde
4/31
How Does a Generator Work
A simple AC generator consists of two parts:
Rotor
- Turned by the driver and consists of a coil of wireswound around a magnetic material to produce arotating magnetic field
Stator or Armature
- Rotating magnetic field induces a voltage in this coil ofwires
-
8/2/2019 Power Generation Clyde
5/31
Multiple Pole Generator
Adding additional magnets or poles will change the
frequency for a given speed
RPM = FrequencyPairs of Poles
60 *
-
8/2/2019 Power Generation Clyde
6/31
Generator Field
The generator field provides the power for the rotating
electromagnet The voltage regulator adjusts the DC voltage that is
used for the field
If the unit is not synchronized with another generator,
increasing the field voltage increases the outputvoltage of the generator
If the unit is synchronized with another generator,increasing the field voltage lowers the power factor ofthe generator
The field must operate within set limits to assure thatthere is sufficient magnetic field to produce the voltage
-
8/2/2019 Power Generation Clyde
7/31
3 Generators
3 generators have 3 windings in the stator that arespaced 120 apart to produce 3 independent outputs
Time
VoltagePhase
A
Phase
B
Phase
C
-
8/2/2019 Power Generation Clyde
8/31
Frequency or Isochronous Control
The output frequency is controlled by changing the
speed of the generator As the load changes, the turbine controller will
change the energy input to hold the speed constant
A simple PID controller could be used for this purpose
PIDSpeed Setpoint
Speed
Control Outputto Valve
-
8/2/2019 Power Generation Clyde
9/31
Load or Droop Control
In some of the older control systems, droop control
was the standard mode of control Droop control is Proportional control only
The speed/load curve for a droop controller looks likethe following:
Speed
Load
Setpoint=3600 rpm
25% 100%75%50%
3420 rpm
Frequency
60 Hz
57 Hz
Droop settingof 5%
-
8/2/2019 Power Generation Clyde
10/31
Droop Control
Generator control system has been refined to allow
other control variables to be used for the loadreference
Allows linear control through out the operatingrange
PIDSpeed
Speed Setpoint
Control Outputto Valve
+-
Sync Speed * Droop *% Output Selector PCD
Power
-
8/2/2019 Power Generation Clyde
11/31
Droop Control Curve
Increasing the setpoint will increase the load with the
modified control configuration
Speed
Load
Setpoint=3600 rpm
25% 100%75%50%
Frequency
60 Hz
57 Hz
Droop settingof 5%
Setpoint=3780 rpm
-
8/2/2019 Power Generation Clyde
12/31
Droop / Isochronous Control
The control system monitors the status of the breakers
in the system to determine whether operation shouldbe as an isochronous unit or as a droop control unit
Also monitors breakers to determine is load rejectionshave occurred so that a feed-forward response can beinitiated to prevent undesirable actions such as a trip
-
8/2/2019 Power Generation Clyde
13/31
Load Sharing
With multiple generators connected to the grid, it may
be desirable to have the generators sharing the loadproportional to their size
accomplished by monitoring the load of allmachines and taking the average
- this average becomes the setpoint for eachgenerator
-
8/2/2019 Power Generation Clyde
14/31
Parallel Isochronous Control
In some systems, it may be desirable for all of the
generators to operate collectively to control thefrequency of the system. This is called ParallelIsochronous control
-
8/2/2019 Power Generation Clyde
15/31
Infinite Buss Theory
The Infinite Buss theory was used to simplify the
control of generators. It stated that the power grid wasso large and inflexible that no single generator couldaffect the frequency of the system
good in theory, but not in reality
-
8/2/2019 Power Generation Clyde
16/31
Power Factor
Power factor is the phase relationship between the voltageand current
Voltage leading current is a lagging power factor
Voltage lagging current is a leading power factor
Power factor is the cosine of the angle between the voltageand current
Time
Voltage
Current
60PF = cosine (60)PF = .5
-
8/2/2019 Power Generation Clyde
17/31
Power Factor Control
Power factor of the installed electrical system isdetermined by the installed equipment
induction motors lagging power factor
capacitors leading power factor
Generator can be used to supply vars (imaginary powerthat is used to generate the magnetic field in motors,etc.)
Power factor is adjusted by changing the fieldexcitation
Generator has a defined operating area that must be
adhered to Control system can be used to protection the
generator from over/under excitation
-
8/2/2019 Power Generation Clyde
18/31
Generator Capacity Curve
Defines the operating area of
the generator Stability limit
Stator heating limit
MW limit
Rotor heating
Max excitation current
Rated MVA
Operating point
Power Factor
+MVAR
-MVAR
MW
Rotor Field Heating Limit
Maximum Excitation Limit
MW Limit
Rated MVA
Stator Heating Limit
Stability Limit
PF = Cos
Generator OperatingPoint
-
8/2/2019 Power Generation Clyde
19/31
Synchronization
Synchronization allows multiple generators to be
placed on line If the generators are not synchronized correctly, severe
damage can result to the generators
Synchronization is nothing more than the alignment of
the rotating magnetic fields in the generators Three conditions must be met for the synchronization
to be successful
Frequencies must be matched
Voltages must be matched Phase angles must be matched
-
8/2/2019 Power Generation Clyde
20/31
Synchronization Frequency
The units must be operating at the same relativefrequency for synchronization to be successful
Low generator frequency
- generator speeds up instantly on breaker closure
High generator frequency
- generator slows down instantly on breaker closure Units are not designed for the sudden speed changes if
not synchronized correctly
During synchronization, the speed of the generator isslightly higher than the buss frequency to allow currentto flow from the generator when the breaker closes
-
8/2/2019 Power Generation Clyde
21/31
Synchronization Voltage
Voltages must be matched prior to synchronization
Low generator voltage will result in an in-rush ofcurrent into the generator
- rotor heating
- may trip protection relays
Generator voltage slightly higher than bussrecommended to allow current flow into grid
On breaker closure, field controls Power Factor insteadof voltage
-
8/2/2019 Power Generation Clyde
22/31
Synchronization Phase
Synchroscope measures the voltage difference
between the buss and generator to determine thephase angle
Breaker should be closed when there is no phasedifference between the two signals
-
8/2/2019 Power Generation Clyde
23/31
Synchronization Phase Example
Time
Voltage Buss Gen
Time
Voltage
Buss
Gen
Generator out of phase
Generator in phase
-
8/2/2019 Power Generation Clyde
24/31
Automatic Synchronizers
Automatic synchronizers are often used to perform the
synchronization task Match the frequency, voltage, and phase but also have
some intelligence
generator frequency is slightly than buss and that
the phase angle is changing to assure that theunits are operating correctly
anticipate the closing speed of the breaker toassure that the breaker closes at 0 phasedifference
detect and close on dead busses
Require the use of a synch check relay
-
8/2/2019 Power Generation Clyde
25/31
Generator Metering and Synchronization
-
8/2/2019 Power Generation Clyde
26/31
Generator Relaying
Relaying is used to protect the generator from abnormal
conditions like over-current, voltage unbalance, currentdifferential, power, etc.
This can be a number of individual protective devicesor a single relay that is designed to incorporate all ofthe functions
-
8/2/2019 Power Generation Clyde
27/31
IEEE Numbering System
IEEE C37.2 defines device numbers
25 Sync Check Relay25A Automatic Synchronizing Relay
27 Undervoltage Relay
32 Power Relay
37 Undercurrent Relay
40 Loss of Field Relay
41 Field Relay
43 Manual Selector Switch49 Temperature Relay
50 Instantaneous Overcurrent Relay
51 Time Overcurrent Relay
52 AC Circuit Breaker
55 Power Factor Relay
59 Overvoltage Relay
65 Governor74 Alarm Relay
81 Frequency Relay
86 Lockout Relay
90 Voltage Regulator
-
8/2/2019 Power Generation Clyde
28/31
Typical One Line Diagram
-
8/2/2019 Power Generation Clyde
29/31
Generator and Voltage Regulator
-
8/2/2019 Power Generation Clyde
30/31
Relaying and Metering
-
8/2/2019 Power Generation Clyde
31/31
Synchronization