© Copyright 2015 OSIsoft, LLC Presented by Power Generation Automatic Dispatch System for Energy Trading Justin Bagley, PG&E Adam Hankins, PG&E Jim Kaiser, PG&E Greg Dumas, DST Controls Wednesday, April 29, 2015

Transcript of Power Generation Automatic Dispatch System for...

Page 1: Power Generation Automatic Dispatch System for …cdn.osisoft.com/corp/en/media/presentations/2015/UsersConference... · Automatic Dispatch System for Energy ... • Inter-Control

•© Copyright 2015 OSIsoft, LLC

Presented by

Power Generation Automatic Dispatch System for Energy

Trading

Justin Bagley, PG&E

Adam Hankins, PG&E

Jim Kaiser, PG&E

Greg Dumas, DST Controls

Wednesday, April 29, 2015

Page 2: Power Generation Automatic Dispatch System for …cdn.osisoft.com/corp/en/media/presentations/2015/UsersConference... · Automatic Dispatch System for Energy ... • Inter-Control

•© Copyright 2015 OSIsoft, LLC Wednesday, April 29, 2015

Generation Statistics

• 15 million customers

• > 18% renewables since 2012

• > 51% carbon free since 2012

•2

Page 3: Power Generation Automatic Dispatch System for …cdn.osisoft.com/corp/en/media/presentations/2015/UsersConference... · Automatic Dispatch System for Energy ... • Inter-Control

•© Copyright 2015 OSIsoft, LLC Wednesday, April 29, 2015

PG&E in 2020: 33% Renewables

•3

Solar PV, Solar Thermal, Wind, Small Hydro, Biogas, Biomass, Geothermal

Total Retail Sales 2002: 11% 2011: 19.4% 2020: 33%

Page 4: Power Generation Automatic Dispatch System for …cdn.osisoft.com/corp/en/media/presentations/2015/UsersConference... · Automatic Dispatch System for Energy ... • Inter-Control

•© Copyright 2015 OSIsoft, LLC Wednesday, April 29, 2015

• Balances supply and

demand for 38MM people

• Daily range is 22 to 44

GW-hrs

• Plans to reduce Green

House Gas to 1990

levels by 2020

• Plans for 33% of load

served by renewable

generation by 2020

CA ISO Balancing Responsibility

•4

Page 5: Power Generation Automatic Dispatch System for …cdn.osisoft.com/corp/en/media/presentations/2015/UsersConference... · Automatic Dispatch System for Energy ... • Inter-Control

•© Copyright 2015 OSIsoft, LLC Wednesday, April 29, 2015

Current Technology: ICCP plus AGC

• Automatic Generation Control

• Direct connect,

• AGC signal updated every 4 seconds

• Inter-Control Center Comm Protocol

Automatic Dispatching: Historical View Automatic Generation Control System

CA ISO signal goes directly to a

Generator Control System

•5

Page 6: Power Generation Automatic Dispatch System for …cdn.osisoft.com/corp/en/media/presentations/2015/UsersConference... · Automatic Dispatch System for Energy ... • Inter-Control

•© Copyright 2015 OSIsoft, LLC Wednesday, April 29, 2015

Real Time Market Today

Many Small Generators

Utility Scale Renewable Production 2010 – 2014

•6

Page 7: Power Generation Automatic Dispatch System for …cdn.osisoft.com/corp/en/media/presentations/2015/UsersConference... · Automatic Dispatch System for Energy ... • Inter-Control

•© Copyright 2015 OSIsoft, LLC Wednesday, April 29, 2015

Automatic Dispatch System supplements AGC

ADS sends power instructions, not control signals

Instructions are Power Levels for short time horizons – day, hour, 5 minutes

•7

•Day Ahead

•Hour Ahead

•Actual

Page 8: Power Generation Automatic Dispatch System for …cdn.osisoft.com/corp/en/media/presentations/2015/UsersConference... · Automatic Dispatch System for Energy ... • Inter-Control

•© Copyright 2015 OSIsoft, LLC Wednesday, April 29, 2015

•PG&E Operator •Running ADS Displays

•Generator •Control System

Forecasts are sent as Dispatch Packets

Dispatch Packet

Start time: 2006-10-13T14:10:00Z

Dispatch Operating Target: 12.0

•8

Page 9: Power Generation Automatic Dispatch System for …cdn.osisoft.com/corp/en/media/presentations/2015/UsersConference... · Automatic Dispatch System for Energy ... • Inter-Control

•© Copyright 2015 OSIsoft, LLC Wednesday, April 29, 2015

•CA ISO Generation Dispatcher •Running ADS Client

•PG&E Operator •Running ADS Displays

•Generator •Control System

•PI

•CA ISO ADS

•PG&E ADS

•1

•2

•3

•4

•5

•6

Typical Command Sequence 1. CA ISO Dispatcher instructs CA ISO ADS to send new power instruction

2. CA ISO ADS sends instruction to PG&E.

3. PG&E ADS web service requests the batch information.

4. PG&E ADS server periodically polls the CA ISO, requests the batch, interprets the batch, and

stores the batch data into the PI Server. Poll rate is currently every 10 seconds.

5. PG&E Generator Control System receives the new Power target..

ADS Protocol

•9

Page 10: Power Generation Automatic Dispatch System for …cdn.osisoft.com/corp/en/media/presentations/2015/UsersConference... · Automatic Dispatch System for Energy ... • Inter-Control

•© Copyright 2015 OSIsoft, LLC Wednesday, April 29, 2015

ADS Data Flow

•10

•Retrieval Security

•X.509 V3 cert

•Encrypted transport

•ADSToPIService

•Heartbeat to monitor

connectivity

•Configurable

•Polls Data

•Multiple Sites

•PI System

•Secure Transfer

•Historical Data

•Generator Control

Page 11: Power Generation Automatic Dispatch System for …cdn.osisoft.com/corp/en/media/presentations/2015/UsersConference... · Automatic Dispatch System for Energy ... • Inter-Control

•© Copyright 2015 OSIsoft, LLC Wednesday, April 29, 2015

What is stored in the PI System?

Batch arrives

HH:MM:SS

Batch start

time (PI

Point)

Dispatch

Power

Level

(PI Point)

Pre-

goto

(Pi

Point)

13:06:34 13:10:00 483 483

13:11:34 13:15:00 483 483

13:16:34 13:20:00 480 483

13:21:36 13:25:00 480.11 480

13:26:36 13:30:00 483 480.11

13:31:36 13:35:00 480 483

13:36:36 13:40:00 480 480

•BatchUID

•BatchType

•BatchStartTime

•InstructionType

•InstructionStartTime

•DOT (target generation for next start time)

•PreGoTo (DOT from last dispatch)

• Information for power

generation purposes

• Information needed for

historical reference

•11

•All dispatch fields can be stored in PI by

adjusting configuration of the service

Page 12: Power Generation Automatic Dispatch System for …cdn.osisoft.com/corp/en/media/presentations/2015/UsersConference... · Automatic Dispatch System for Energy ... • Inter-Control

•© Copyright 2015 OSIsoft, LLC Wednesday, April 29, 2015

End Result

•12

Page 13: Power Generation Automatic Dispatch System for …cdn.osisoft.com/corp/en/media/presentations/2015/UsersConference... · Automatic Dispatch System for Energy ... • Inter-Control

•© Copyright 2015 OSIsoft, LLC Wednesday, April 29, 2015

Automatic Dispatch for Renewable Generation

•13

Power

generated

MW vs.

time of day

Not at all

like

conventional

fuel

generation

Page 14: Power Generation Automatic Dispatch System for …cdn.osisoft.com/corp/en/media/presentations/2015/UsersConference... · Automatic Dispatch System for Energy ... • Inter-Control

•© Copyright 2015 OSIsoft, LLC Wednesday, April 29, 2015

Forecast info: Demand, Supply Curves

•14

Page 15: Power Generation Automatic Dispatch System for …cdn.osisoft.com/corp/en/media/presentations/2015/UsersConference... · Automatic Dispatch System for Energy ... • Inter-Control

•© Copyright 2015 OSIsoft, LLC Wednesday, April 29, 2015

Net Load Forecast

•15

Page 16: Power Generation Automatic Dispatch System for …cdn.osisoft.com/corp/en/media/presentations/2015/UsersConference... · Automatic Dispatch System for Energy ... • Inter-Control

•© Copyright 2015 OSIsoft, LLC Wednesday, April 29, 2015

Schedule Generation using Forecasts

Solar and Wind

Forecasts @

Generating Station

Demand

Forecasts

PI Server Future Data

Net Load

Calculation

AF

GeoThermal

Hydro

Control Rooms

•16

Page 17: Power Generation Automatic Dispatch System for …cdn.osisoft.com/corp/en/media/presentations/2015/UsersConference... · Automatic Dispatch System for Energy ... • Inter-Control

•© Copyright 2015 OSIsoft, LLC Wednesday, April 29, 2015

PI Server Future Data manages Forecast vs. Actual

Now

Line

Actual

Power

Output Level

Real time,

updated

every 5

seconds

Forecast, 5

minute intervals

(Blue line)

•17

Page 18: Power Generation Automatic Dispatch System for …cdn.osisoft.com/corp/en/media/presentations/2015/UsersConference... · Automatic Dispatch System for Energy ... • Inter-Control

•© Copyright 2015 OSIsoft, LLC

A. Generation staff is concerned with reliability and cost rather than micro-managing supply with Demand

Solution Result

Summary

Business Challenges

A. Minimize manual intervention in power generation

PG&E delivers some of the nation's cleanest energy to our customers.

More than 50% of our portfolio is from sources that are renewable and/or have no greenhouse gas emissions.

•18 •1

8

Page 19: Power Generation Automatic Dispatch System for …cdn.osisoft.com/corp/en/media/presentations/2015/UsersConference... · Automatic Dispatch System for Energy ... • Inter-Control

•© Copyright 2015 OSIsoft, LLC

Questions?

•19

•Please wait for the

microphone

•State your

name & company

Justin Bagley

[email protected]

Greg Dumas

[email protected]

Page 20: Power Generation Automatic Dispatch System for …cdn.osisoft.com/corp/en/media/presentations/2015/UsersConference... · Automatic Dispatch System for Energy ... • Inter-Control

•© Copyright 2015 OSIsoft, LLC

Take-away:

“Create a good forecast and put it in PI Server Future Data”

Thank

You