Power Factor Correction Most domestic loads (such as washing machines, air conditioners, and...
-
Upload
prudence-cummings -
Category
Documents
-
view
225 -
download
2
Transcript of Power Factor Correction Most domestic loads (such as washing machines, air conditioners, and...
Power Factor Correction
Most domestic loads (such as washing machines, air conditioners, and refrigerator) and industrial loads (such as induction motors) are inductive and operate at a low lagging power factor. Although the inductive nature of the load can not be changed, but the power factor can be increased.
The process of increasing the power factor without altering the voltage or current to the original load is known as power factor correction
LI
V
LI
VInductiveload
Inductiveload C
CI
I
)(a )(bFigure Power factor correction: (a) original inductive load, (b) inductive load with improved power factor
Most loads are inductive, as shown in figure below (a) which has a power factor of cos , a load’s power factor is improved or corrected by installing a capacitor in parallel with load, as shown in Figure below (b) which has a power factor of cos .
1
2
The effect of adding the capacitor can be illustrated using power triangle or the phasor diagram of the current involved.
CI
1 2
LI
CI
V
I
The original load has power factor and the inductive load with improved power factor has
11 cospf
22 cospf
The power factor correction can be looked from another perspective. Consider the power triangle in Figure below.
1S
2S
1 2
1Q
2Q
CQ
P
If the original inductive load has apparent power S1, then
11 cosSP
1111 tansin PSQ
If desired to increase the power factor from to without altering the real power (i.e ), then the new reactive power is
11 cospf 22 cospf
22 cosSP
22 tanPQ
The reduction in the reactive power is caused by the shunt capacitor, that is
)tan(tan 2121 PQQQC
The value of the required shunt capacitance of capacitor C is determined by
; 22
rmsC
rmsC CV
X
VQ
221
2rmsrms
C
V
P
V
QC
)tan(tan
Although the most command situation in practice is that of an inductive load, it is also possible that the load is capacitive, that is, the load is operating at a leading power factor. In this case, an inductor should be connected across the load for power factor correction. The required shunt inductance L can be calculated from
L
rmsrms
L
rmsL Q
VL
L
V
X
VQ
222
Where , the difference between the new and old reactive powers.
21 QQQL
Example 1
When connected to a 120 V (rms), 60 Hz power line, a load absorbs 4 kW at a lagging power factor of 0.8. Find the value of capacitance necessary to rise the pf to 0.95.
Solution
Before improving power factor :
If the pf=0.8, than
011 873680 ..cos
The apparent power from the real power
VAP
S 50080
400
11
.cos
After improving power factor :
The pf is raised to 0.95
022 1918950 ..cos
The real power has not changed, but the apparent power has changed, its new value :
VAP
S 54210950
4000
22 .
.cos
The new reactive power is
VARSQ 41314191854210 0222 .).sin(.sin
The reactive power due to installation of capacitor is
VARQQQC 6168541314300021 ..
and
FxxV
QC
rms
C
5310120602
6168522
..
Example 2
The pf correction capacitor in a 240 V, 50 Hz fluorescent light unit has broken down and needs replacing. A test on the unit shows that, without the capacitor, the supply current is 0.86 A at pf of 0.5 lagging. The value quoted on the original capacitor have faded and the only other information is that the working pf of the unit should be 0.95. Determine the value of the capacitor needed (look in Figure below).
Pf=0.5
240 V50 Hz
Choke and lamp
0.86 A
Three phase system
The total average power P :
coscos LL IVIVP 33
The total reactive power Q :
sinsin LL IVIVQ 33
The total apparent power S :
LL IVjQPS 3
For a Y-connected load :
VVL 3 II L , but
For a - connected load :
II L 3 VVL , but
IandIVV LL ,, are all rms value and is the angle between the phase voltage
and the phase current
Example 3
A three-phase motor can be regarded as a balanced Y-load. A three-phase motor draws 5.6 kW when the line voltage is 220 V and the line current is 18.2 A. Determine the power factor of motor.
Solution
The power factor is :
807502182203
5600
3
3
..
cos
cos
xx
IV
P
pf
IVP
LL
LL
Example 4
A balanced three phase load draws 50 kW at a lagging power factor of 0.85 from a 480 V supply.
a. Find the apparent power S
b. Find the line current
c. Find the reactive power Q
LI
Example 5
A three phase industrial load consists of 136 kW at 0.8 power factor lagging. What size capacitor bank is required to correct the power factor to 0.95 lagging?