Potential for Fire, Smoke and Asphyxiation Hazards Incorrect installation, adjustment, or misuse of this burner could result in death, severe personal injury, or substantial property damage. To the Homeowner or Equipment Owner: Please read and carefully follow all instructions provided in this manuah'egarding your responsibilities in caring for your heating equipment. Contact a professional, qualified service agency for installation, start-up or service work. Save this manual for future reference. To the Professional, Qualified installer or Service Agency: Please read and carefully follow all instructions provided in this manual before installing, starting, or servicing this burner or heating system. The Installation must be made in accordance with all state and local codes having jurisdiction. 6104 BCF10 R04 II

Transcript of Potential Hazards - usermanual.wiki · Potential for Fire, Smoke and Asphyxiation Hazards Incorrect...

Page 1: Potential Hazards - usermanual.wiki · Potential for Fire, Smoke and Asphyxiation Hazards Incorrect installation, adjustment, or misuse of this burner could result in death, severe

Potential for Fire, Smoke and Asphyxiation Hazards

Incorrect installation, adjustment, or misuse of this burner could result in death, severepersonal injury, or substantial property damage.

To the Homeowner or EquipmentOwner:• Please read and carefully follow all instructions

provided in this manuah'egarding your responsibilitiesin caring for your heating equipment.

• Contact a professional, qualified service agency forinstallation, start-up or service work.

• Save this manual for future reference.

To the Professional, Qualified installer

or Service Agency:• Please read and carefully follow all instructions provided

in this manual before installing, starting, or servicing thisburner or heating system.

• The Installation must be made in accordance with all state

and local codes having jurisdiction.

6104 BCF10 R04 II

Page 2: Potential Hazards - usermanual.wiki · Potential for Fire, Smoke and Asphyxiation Hazards Incorrect installation, adjustment, or misuse of this burner could result in death, severe

follOW the appliance manufaCturer's instruCti6nsfor burner installation; equipment and set, up i

1-800-OIL-BURN' BecketVs technical services

hot, linelwww.beekettcorp;COm. Beckett s website.

To the Owner:

Thank you for purchasing a Beckett burnerfor use with your heating appliance. Please payattention to the Safety Warnings contained withinthis instruction manual. Keep this manual for yourrecords and provide it to your qualified serviceagency for use in professionally setting up andmaintaining your oil burner.

Your Beckett burner wilt provide years of efficientoperation if it is professionally installed andmaintained by a qualified service technician. If atany time the burner does not appear to be operatingproperly, immediately contact _ualifiedservice aemcnc_Xfor consultation.

We recommend annual inspection/service of

your oil heating system by a qualified service

agency.

1"able of Contents

General Information .............................................. 3-4Hazard Definitions ............................................................... 3

Agency approvals ................................................................ 3General Specifications ........................................................ 3Owner's Responsibility ........................................................ 4Installer/Service Agency Responsibility ............................... 4Pre-installation checklist ..................................... 4-7Combustion air supply ......................................................... 4Clearances .......................................................................... 4Fuel supply .......................................................................... 5Nozzle pressure .................................................................. 5Vent system ......................................................................... 5Electrical supply .................................................................. 5Verify burner components ................................................... 6Verify firing input range ........................................................ 6Verify air tube ...................................................................... 6Stray Light ........................................................................... 7Dust and moisture ............................................................... 7

Mount the burner .................................................. 7-10Mount flanges on air tubes .................................................. 7Mount air tube to burner ...................................................... 7Install Nozzle ....................................................................... 8Check Electrodes ................................................................ 8Install Nozzle Line Assembly ............................................... 8Set Dimension Z .................................................................. 8Insert Burner ........................................................................ 9Fuel unit By-pass plug ......................................................... 9Oil supply/return lines .......................................................... 9Burner fuel flow ................................................................. 10

Wire the burner .......................................................... 10

Sequence of Operation-Typical .......................... 11

Prepare the burner for start-up ..................... 11-13Start-up checklist ............................................................... 12Z Dimension ...................................................................... 12

Adjusting plate Assembly .................................................. 12Initial head position ............................................................ 13Initial air settings ................................................................ 13Set appliance limit controls ................................................ 13Prepare the fuel unit for air venting ................................... 13Start the burner ...................................................14-15Start burner and vent air ................................................... 14Set air adjusting plate ........................................................ 15Maintenance and Service ............................... 16Annual Service .................................................................. 16Monthly maintenance ........................................................ 16

Replacement Parts .............................................18-19Warranty ....................................................Back Cover

_. 6104 BCFIO R04

Page 3: Potential Hazards - usermanual.wiki · Potential for Fire, Smoke and Asphyxiation Hazards Incorrect installation, adjustment, or misuse of this burner could result in death, severe

indicates an imminentlyhazardous situation,

which, if not avoided, will result in death,

serious injury, or property damage.

indicates a potentiallyhazardous situation,

which, if not avoided, could result in death,

severe personal injury, and/or substantialproperty damage.

indicates a potentiallyhazardous situation,

which, if not avoided, may result in person=al injury or property damage.

Intended to bring special attention to information,but not related to personal injury or property

damage.

Firing range

Motor

Ignition Trans.

Housing

Fuel unit

4.0 to 10.0 GPH

½ HP 3450 RPM

t 20/60 hz standard

6.5 amps _ 120 VAC

Optional voltages:(60 hz or 50 hz)- 240 VAC 1-PH

,208/240/480 VAC!3-PH

Continuous Duty,120V/12,000V

cast aluminum

100 - 300 PSIG

Shipping wt. 75 lbs.

Dimensions .........................see Figure 7

See NOTICE on 50 hz motor applications.)

Note. Within the boundaries of the hazaM warning, there

will be #_f!)rmation presented describing consequences

if the warning is not heeded and instructions on how toavoid the hazard.

Agency approvalls

C

[2] UL certified to comply with ANSI/UL296 and tested toCSAB140.0.

[2] Accepted by N.Y.C.M.E.A.Other approvals may be available and must be specified attime of order.

61 04 BCF1 0 R04 3

Page 4: Potential Hazards - usermanual.wiki · Potential for Fire, Smoke and Asphyxiation Hazards Incorrect installation, adjustment, or misuse of this burner could result in death, severe

Owner's Responsibility:

Follow These instructions

ExactlyFailure to follow these instructions,misuse, or incorrect adjustment ofthe burner could lead to equipmentmalfunction and result in asphyxia-tion, explosion or fire.

Contact a professional, qualified service agency for theinstallation, adjustment and service of your oil burningsystem. Thereafter, have your equipment adjusted andinspected at least annually to ensure reliable operation.This work requires technical training, trade experience,licensing or certification in some states and the properuse of special combustion test instruments.

Please carefully read and comply with the followinginstructions:

* Never store o1"use gasoline or other flammable liquidsor vapors near this burner or appliance.

* Never attempt to burn garbage or refuse in thisappliance.

* Never attempt to light the burner by throwing burningmaterial into the appliance.

* Never attempt to burn any fuel not specified andapproved for use in this burner.

* Never restrict the air inlet openings to the burner or thecombustion air ventilation openings in the room.

Professional Installer/Service AgencyResponsibility:

Follow These

instructions ExactlyFailure to follow these instructions

could lead to equipment malfunc-tion and result in asphyxiation,explosion or fire.

* Please read all instructions before proceeding. Followall instructions completely.

* This equipment must be installed, adjusted and startedby a qualified service agency that is experienced withall applicable codes and ordinances and responsible forthe installation and commission of the equipment.

* The installation must comply with all local codes andordinances having jurisdiction and the latest editions ofthe NFPA 31 and CSA-B139 & B140 in Canada.

50 Hz motors -- The burner ratings, air settings and nozzleratings are based on standard 60 hz motors (at 3450 rpm). Derateall ratings 20% when using 50 hz motors. Consult factory forspecific application data.

High altitude installations -- Accepted industry practicerequires no derate of burner capacity tip to 2,000 feet above sealevel. For altitudes higher than 2,000 feet, derate burner capacity2% for each 1000 feet above sea level.

@@@@@@@@@@@@@@@@@@@@@@@@@@@@@@@@@@@@@@@@@@@@@@@@@@@@@@@@@@@@@@@@@@

Pre-installation check|ist[3 Combustion air supply

Adequate Combustionand Ventilation Air SupplyRequired

Failure to provide adequate air supply could se-riously affect the burner performance and result

®

in damage to the equipment, asphyxiation, ex-plosion or fire hazards.

* The burner cannot properly burn the fuel if it is not sup-plied with a reliable combustion air source.

* Follow the guidelines in the latest editions of the NFPA31 and CSA-B139 regarding providing adequate air for

combustion and ventilation. ®

® The burner requires combustion air and ventilation airfor reliable operation. Assure that the building and/orcombustion air openings comply with National Fire

4

Protection Standard for Oil-Burning Equipment, NFPA 31.For appliance/burner units in confined spaces, the roommust have an air opening near the top of the room plus onenear the floor, each with a free area at least one square inchper 1,000 Bm/hr input of all fuel burning equipment in themorn. For other conditions, refer to NFPA 31 (CSAB1139-Mgl in Canada).

If there is a risk of the space being under negative pressureor of exhaust fans or other devices depleting availableair for combustion and ventilation, the appliance/burnershould be installed in an isolated room provided withoutside combustion air.

Clearances

With the burner installed in the appliance, there must beadequate space in front of and on the sides of the burnerto allow access and operation. Verify that the clearancedimensions comply with all local codes and with theappliance mamffacturer's recommendations.

6104 BCFIO R04

Page 5: Potential Hazards - usermanual.wiki · Potential for Fire, Smoke and Asphyxiation Hazards Incorrect installation, adjustment, or misuse of this burner could result in death, severe

[] Fuel supply [] Nozzle pressure

Oil Supply Pressure

Control RequiredDamage to the pump, filter or othercomponent seals could cause possible oil

leakage and potential fire hazard.* The oil supply inlet pressure to the fuel unit cannot

exceed 3 psig.* Do NOT install valves in return line.

* Ensure that a pressure-limiting device is installed inaccordance with the latest edition of the NFPA 31.

* Gravity Feed Systems: Always install an anti-siphonvalve in the oil supply line or a solenoid valve (RWBPart #21789) in the pump/nozzle discharge tubing toprovide backup oil flow cut-off protection.

The fuel supply piping and tank must provide #1 or #2 fueloil at pressure or vacuum conditions suitable for the fuelunit (oil pump) on the burner. Refer to fuel unit literature inthe literature envelope in the burner carton to verify allow-able suction pressure.

If fuel supply is level with or higher than fuel unit --

* When the fuel unit is not required to lift the oil, the instal-lation is usually suitable for either a one-pipe or two-pipeoil system. The oil pressure at the inlet of the fuel trait mustnot exceed 3 psig.

* See Figure 8 for one-pipe fuel supply installations. SeeFigure 9 for two-pipe fuel supply installations.

If fuel supply is below the fuel unit --

Use a two-pipe oil system when the fuel trait must lift theoil more than 8 feet if burner is equipped with a B fuel unit,or more than 2 feet if burner is equipped with an H fuelunit. The return line provided by the two-pipe system isneeded to purge the air from the fuel lines and minimize thelikelihood of air-related problems during operation.

Correct Nozzle and Flow

Rate RequiredIncorrect nozzles and flow rates could

result in impaired combustion, under-firing, over=firing, sooting, puff-back

of hot gases, smoke and potential fireor asphyxiation hazards.

Use only nozzles having the brand, flow rate (gph),

spray angle and pattern specified by the appliancemanufacturer.

Follow the appliance manufacturer's specifications for

the required pump outlet pressure for the nozzle, sincethis affects the flow' rate.

* Nozzle manufacturers calibrate nozzle flow rates at 100

psig.* This burner utilizes pressures higher than 100 psig, so

the actual nozzle flow rate will be greater than the gphstamped on the nozzle body. (Example: A 5.00 gph noz-zle at 150 psig = 6.12 gph and at 300 psig = 8.66 gph)

For typical nozzle flow rates at various pressures see ac-

companying chart.

The fuel unit nozzle port pressure is factory set at 300 psig.Some original equipment manufacturer burner applicationsmay call for a lower pressure to obtain a required firingrate. Do not change this pressure unless directed to do soby the appliance manufacturer.

[]®

[]

®

E|ectrical supplyVerify that the power connections available are correct forthe burner. Refer to Figure !.All power must be suppliedthrough fused disconnect switches.

Vent system

The flue gas venting system must be in good condition andnmst comply with all applicable codes.

Figure 1 - Typical Nameplate

General Model

Serial Number, Including Date

Rating Information

Approva Agency Symbo s

ForusewithGroup 8.. i

Primary Group and Fuel

_,_P//92 XXO00 RO0

R.W. Beckett Construc-tion & Setting Data

R.W. Beckett SpecificationNumber and Revision

Boiler Manufacturer andModel, When Applicable

Additional Codes

k002

61 04 8CF1 0 R04 5

Page 6: Potential Hazards - usermanual.wiki · Potential for Fire, Smoke and Asphyxiation Hazards Incorrect installation, adjustment, or misuse of this burner could result in death, severe

[] Verify burner components m Figure 2 - Min. Combustion Chamber Dimensions

, Burner nameplate (figure D, Model CF1000

* Air tube assembly

* Mounting flange kit

* Pedestal mounting assembly kit (recommended)

Oil nozzle, per Table 1 -- Only 45° to 70° solid patternnozzles are recommended unless otherwise specified byappliance manufacturer. (See specific appliance recom-mendation sheet or refer to OEM Spec Guide). Find therequired firing rate in the 300 psig column (factory-set fuelunit pressure). Select the corresponding nozzle from cot-unto 1 (Rated gph @ lOOpsig).

(Example: 5. O0 gph nozzle @ 300 psig = 8.66 gph)t405

Table 1 - Nozzle Capacities

2.00 2.24

2.52

2.50 2.80

2:753.00

3.50

4.00

5.00

8.00

2.45

3.06

3 37

7.00 7.83

3.35 3.67

391 429

4.474.90

5,045,5!5.59 6.12

61i56.71 7.35

7,27 7:96

8.57

9.19

2.65

3.31

3,64

3.97

4.63

5.29

5,956.61

7:28

7.94

8,60

9.26

9:92

2.83 3.16 3.32 3.46

3.54 3.95 4.15 4.33

3,90 4135 4.56 4176

4.24 4.74 4.97 5.20

5,80 61065.66 6.32

7.07 7.91

8.49 9.49

9:i9 i01289.90 11.07

1&6! !! 86

6.63 6.93

7,46 7,79

8.29 8.66

9.i2 9;53

9.95 10.39

i07s ii2 11.61 12.12

iZ44 iZ99

8.00 8194 9180 1 0158 11131 12165 13.27 13186

[] Verify firing rate* Refer to appliance manufacturer's instructions (if available)

for firing rate and nozzle selection. Otherwise, the maximumrecommended firing rate for the burner depends on thelength of the firing chamber and the distance from theburner center to the chamber floor. Verify that the chamberdimensions are at least as large as the mininmm valuesgiven in Figure 2. If the appliance dimensions are smallerthan recommended, reduce the firing rate accordingly.

Figure 3 -Air Tube Mounting Dimensions

G

E insertion depthG Air tube to inside of chamber

0.25" +/- 0.125

T Air tube lengthD Tube diameter

Note: Install the burner with a 2 deg. pitch as shown

6.75" CF66KD

t0;25" OF

t 3.7[$" CF136KD

t7:75" CF176KD

6 61 04 8CF10 RO4

Page 7: Potential Hazards - usermanual.wiki · Potential for Fire, Smoke and Asphyxiation Hazards Incorrect installation, adjustment, or misuse of this burner could result in death, severe

Verify air tube

Note: The information in this section may be disregarded if theair tube is supplied by the appliance manufacturer.

* Air tube arrangement -Tube A -- 4.0 to 10.0 GPH per Table 2

* Maximum firing capacity depends on the firebox pressure,see Table 2.

* See Figure 3 to verify the correct air tube length and airtube combination code.

Table 2 - Air Tube Capacity vs. Firebox Pressure

Air TubeCapacityvs. FireboxPressure

TubeFirebox

Pressure

(Inw.c.)0.0

0.2

0.4

0.6

0.8

1.0

No ReserveAir

**.0

10.5

"0.1

9.6

9.2

8.7

10%Turndown

(GPH)

10.00

9.45

9.10

8.84

8.30

7.83

Note: 10% turndown indicates sufficient reserve air to reduce the CO 2 in the flue to 90% of itsvalue.

oNote: The above ratings may vary 5 _/odue to variations in actual job conditions.

Stray Light

Protect Against Stray

Light LockoutFailure to follow these instructions could cause

loss of burner operation resulting in no heat, anunplanned process interruption, work stoppageand the potential for frozen plumbing or othercold weather property damage.

* The control must detect a dark, no-flame condition inorder to start the burner or it wilt hold in the stray lightlockout mode.

* Shield the burner view window from direct exposure tointense light.

[] 9ust and Moisture

Protect Against Dust andMoisture

Wet, dusty environments could lead to blockedair passages, corrosion damage to components,impaired combustion performance and result in

asphyxiation, explosion or fire.

* This burner is designed for clean, dry installations.* Electrical controls are not protected against rain or

sprayed water.* Keep the installation clear of dust, dirt, corrosive va-

pors, and moisture.* Protective covers and more frequent maintenance may

be required.

U e uFneF

I

Protect the Air Tube From

Overheating

Overheating could cause damage to the airtube and other combustion componentsleading to equipment malfunction and

impaired combustion performance.* The end of the air tube must not extend into the com-

bustion chamber unprotected unless it has been factory-tested and specified by the appliance manufacturer.

* Position the end of the air tube 1/4" back from flush

with the refractory inside entry wall to prevent damagefrom overheating.

[] Mount flange(s) on air tube

Note: This section does not apply to burners with weldedflanges.* Do not install air tube on burner.

* For non-pre.s'szn_efiring flange, refer to Figure 4: Installgasket (item a) and flange (item e). Ignore the nextparagraph.

* For pressure-/irhTgJlange, refer to Figure 4: Slide gasket(item a) onto the air tube, making sure the top of the air tubeis up. Pre-dritl holes in the pressure firing plate (item b) tomatch the appliance studs. Slide the pressure firing plate(item b) and flange (item e) onto the air tube as shown.Wrap ceramic fiber rope around the air tube and presstightly into the inside diameter of the flange (item e).

* Slide the air tube (item d) into position in the appliancefront. Tighten the flange-mounting-stud nuts. Set theinsertion of the air tube so dimension G is 1/4" nominal.

* Pitch the air tube at 2° from horizontal as shown and secure

the flange to the air tube.

Figure 4 - Mount flange(s) on air tube

G

1412 a b

61 04 BCFIO R04 '7

Page 8: Potential Hazards - usermanual.wiki · Potential for Fire, Smoke and Asphyxiation Hazards Incorrect installation, adjustment, or misuse of this burner could result in death, severe

[] Mount air tube to burner

* Remove the rear access door from the back of the burner

for improved access to the interior.* Attach the air tube to the burner with the bolts and acorn

nuts provided. The acorn nuts must go on the outside of theburner, with the bolts inserted from the inside.

[] Install nozzle

* See Figure 5. Install the oil nozzle in the nozzle adapter.Use a 3/4" open-end wrench to steady the nozzle adapterand a 5/8" open-end wrench to turn the nozzle. Tightensecurely but do not over-tighten.

, Check, and adjust if necessa17, the critical dimensions P,Q, R and S shown in the drawing. Verify that the oil tubeassembly and electrodes are in good condition, with nocracks or damage.

[] Check electrode settings

Maintain Electrode

SpecificationsFailure to properly maintain these specificationscould cause ignition malfunction, puff-back of

hot gases, heavy smoke, asphyxiation, explosionand fire hazards.

* Adjust the electrode gap and position in relation to thenozzle to the specifications shown in Figure 5.

Check, and adjust if necessary, the critical dimensions RQ, R and S shown in the drawing. Verify that the oil tubeassembly and electrodes are in good condition, with nocracks or damage.

Figure 5 - Nozzle and nozzle line assembly

* Slide the secondary adjusting plate (item f) completely tothe left on the indicator adjusting plate (item e). Fingertighten acorn nut c to secure the two plates together. Slideboth plates completely to the left on the primary adjustingplate (item g) and finger-tighten acorn nut d.

* Slide the completed adjusting plate assembly over the nozzleline end. Move the plate assembly and the nozzle line so theplate assembly fits into position as shown in Figure 6.

* Install the spline nut (Figure 6, item b) on the end of thenozzle line, leaving the nut loosely placed so the plates canbe moved.

, Connect the high-voltage leads from the ignition transformerto the electrodes.

Figure 6 - Nozzle line assembly in burnerMeasure dimension Z from

g

Measure dimension Z from the flat

surface between (not on) the raised fins.

Z = 1-3/4"+ 1/16"

Legend {Figures 6 & 7)

a adjustingplateassembly

b splinenut

c Bottomacornnut

d Topacornnut (forsettingdim.Z only

e Indicatoradjustingplate

f Secondaryadjustingplate

g Primaryadjustingplate

[] Set dimension Z

Legend

P Nozzle centerline to electrode tip 14"

Q Nozzle to head 1/4"

R Nozzle face to electrode tip 1/8"

S Electrode spacing 3/32"

[] Install nozzle line assembly

* Insert the nozzle line assembly into the burner air tube asin Figure 6.

* See Figures 6 and 7. Assemble the adjusting plate assemblyper the instructions in the assembly packet.

8

* Replace the rear access door on the burner, making surethat the adjusting plate assembly is now securely held inplace.

* Loosen acorn nut d in Figure 6. Slide the nozzle line andplate assembly until dimension Z (from end of air tube toflat area of front Pace of head) is 1-314" -4-1116". When

dimension Z is correctly set, tighten acorn nut d. Verifythat the adjusting plate assembly is properly seated in theadjusting groove.

* Attach the oil line from the oil valve to the nozzle line end.

Tighten securely.* Before proceeding, check dimension Z once again. Loosen

acorn nut d if necessary to reposition the nozzle line. Oncedimension Z is set, do not loosen acorn nut d again. Forthe setting of acorn nut c, refer to Page 13.

6104 13CF10 FI04

Page 9: Potential Hazards - usermanual.wiki · Potential for Fire, Smoke and Asphyxiation Hazards Incorrect installation, adjustment, or misuse of this burner could result in death, severe

Figure 7 - Adiustinq plate assv.

g

121insert burner

* Position the burner in the fi'ont of the appliance and looselytighten the nuts on the mounting studs. The burner shouldbe pitched downward 2 ° as shown in Figures 3 and 4.

See Figure 8. Install the pedestal support kit (recommend-ed) by attaching the 3/4"NPT flange (item a) to the bottomof the burner using the (4) #10 screws provided. Cut andthread (one end only) a 3A"pipe nipple (item b) with length10 inches less than dimension D in Figure 8. Thread thepipe into the flange. Then slip the pipe end into the floorflange (item c).

* Secure the burner to the appliance by tightening the nuts onthe burner flange mounting studs. Then secure the pedestalsupport floor flange set screw to the pipe.

Figure 8 - Burner installed in appliance front

LegendH Housing totallength 18"

J Center to bottomofhousing 10-7/8"

K Overall housing height 13-3/8"

KJ

b

121Oil supply/return lines

install Oil Supply To

Specifications

Failure to properly install the oilsupply system could cause oilleakage, equipment malfunction,puff=back of hot gases, heavy smoke,

asphyxiation, explosion and firehazards.

* Carefully install the oil supply lines, fittings and conl-ponents using the guidelines provided in this section.

* The oil supply must comply with the latest editionof NFPA 31 (Canada CSA B139) and all applicablecodes.

* Do not install valves in return line.

* If the oil supply inlet pressure to the pump exceeds 3psig or for gravity feed systems, install an oil safety orpressure reducing valve (Webster OSV, Suntec PRV orequivalent).

* Install the oil tank and oil lines in accordance with all

applicable state and local codes.* Size the oil supply and return lines using the guidelines

given in the fuel unit literature included in the literatureenvelope. Oil line flow rate wilt equal the burner rate forone-pipe systems. For two-pipe systems, refer to Table 3for the fl_el unit gear set capacity - the rate at which fl_elis recircutated when connected to a two-pipe system. Sizetwo-pipe oil lines based on this flow rate.

* Use continuous lengths of heavy-wail copper tubing, routedunder the floor where possible. Do not attach fl_el lines tothe appliance or to floor joists if possible. This will reducevibration and noise transmission problems.

* Install an oil filter sized to handle the fl_etunit gearset flowcapacity (Table 3) for two-pipe systems. Size the filterfor the firing rate for one-pipe systems. Locate the filterimmediately adjacent to the burner fuel unit.

* Install two high-quality shut-off valves in accessiblelocations on the oil supply line. Locate one valve closeto the tank. Locate the other valve close to the burner,

upstream of the fllel filter.

[] Fuel unit by-pass plug

Do Not install By-passPlug with 1=Pipe System

Failure to comply could cause immediate pumpseal failure, pressurized oil leakage and thepotential for a fire and injury hazard.

* The burner is shipped without the by-pass plug installed.® Intall the by-pass plug in two-pipe oil supply systems ONLY.

* Use a two-pipe system, one-pipe system with by-pass loop,or remove the by-pass plug when using with a one-pipe

system and no by-pass loop

Table 3 - Fuel unit gearset capacities

Fuel Unit i Gearset capacity i

' model number (gallons per hour) i

B2TA8245 21

61 04 BCF1 0 NO4 9

Page 10: Potential Hazards - usermanual.wiki · Potential for Fire, Smoke and Asphyxiation Hazards Incorrect installation, adjustment, or misuse of this burner could result in death, severe

Burner fuel flow

®

®

One-pipe systems - See Figure 9 for the fuel flow path.* Oil supply connects to one of the fuel unit inlet ports.Two-pipe systems - See Figure 10 for the fuel flow pathsfor two-pipe oil systems.* Oil supply connects to one of the fuel unit inlet ports. Oil

return connects to the fuel unit return port. (Install theby-pass plug in the fuel unit for two-pipe systems.)

Figure 9 - One-pipe oil flow with "B" pump

_ 300 psig

300 psig

Figure 10 - Two-pipe oil flow with "B" pump

@

300 psig

Legend

a Return port

b Nozzle porte Oil valve

d Nozzle & adapter

g Inlet portk Return line to oil tank

p Air bleed valve

300 psig

Wire the burner -- R7184

Electrical Shock Hazard

Electrical shock can cause severe personal in-jury or death.

* Disconnect electrical power before installing or servic-ing the burner.

* Provide ground wiring to the burner, metal control en-closures and accessories. (This may also be required toaid proper control system operation)

* Perform all wiring in compliance with the NationalElectric Code ANSI/NFPA 70 (Canada CSA C22.1).

Install the burner and all wiring in accordance with the NationalElectrical Code and all applicable local codes or requirements.

Wire the burner in compliance with all instructions provided bythe appliance manufacturer. Verify operation of all controls inaccordance with the appliance manufacturer's guidelines.

See Figure 11 for a typical wiring diagram, with R7184 oil

primary, for reference purposes only.

Figure 11 - Typical Wiring

H N G PowersupNy

; i 12o_/6oh_

Nozzle pressure - The fuel unit nozzle port pressureis factory set at 300 psig. Some original equipmentmanufacturer burner applications may call for a lowerpressure to obtain a required firing rate. Do not changethis pressure unless directed to do so by the appliancemanufacturer.

CC

||

Legend

FD Fused Disconnect, by others

LM Limit controls, by others

OP Operating controls, by others

PR Oil primal T control, R7184 typ.

CC Flame sensor, cad cell typical

!_ i_

81

m_ _ _ Ftekt WifiO_

A_ othe__irO 16 ga

TR Ignition transformer

M 1 Burner motor

$1 Oil valve

T-T 24-volt thermostaglimit terminals

F-F Cad cell flame sensor terminals

11O 6104 BCF10 R04

Page 11: Potential Hazards - usermanual.wiki · Potential for Fire, Smoke and Asphyxiation Hazards Incorrect installation, adjustment, or misuse of this burner could result in death, severe

Sequence(typical)

of Operation

1. Standby -- The burner is idle, waiting for a call for heat.When a call for heat is initiated, there is a 3-10 second delaywhile the control performs a safe start check.

2. Valve-on delay--As applicable, the ignition and motor areturned on for a 15-second prepurge.

3. Trial for ignition (TFI) -- The fuel valve is opened, asapplicable. A flame should be estalished within the 15-second lockout time.

Lockout -- If flame is not sensed by the end of the TFI,the contmt shuts down on safety lockout and must bemanually reset. If the control locks out tbxee times in a row,the contmt enters restricted lockout. Call a qualified servicetechnician.

Ignition carryover -- Once flame is established, theignition remains on for 10 seconds to ensure flame stability.It then turns off.

6. Run -- The burner runs until the call for heat is satisfied.

The burner is then sent to burner motor-off delay, asapplicable, or it is shut down and sent to standby.

7. Recycle -- If the flame is lost while the burner is firing, thecontrol shuts down the burner, enters a 60-second recycledelay, and then repeats the ignition steps outlined above. Ifthe flame is lost three times in a row, the control locks out

to prevent continuous cycling with repetitious flame losscaused by poor combustion.

8. Burner motor-off delay -- If applicable, the fuel valveis closed and the burner motor is kept on for the selectedpostpurge time before the control returns the burner tostandby.

Resetting to OHM

If the control locks out tbxee times in a row without a con>

ptete heat cycle between attempts, the lockout becomes re-stricted. A qualified service technician should be called toinspect the burner.

the burner for

Professional installation

and Service Required

Incorrect installation and mishandling of start=upcould lead to equipment malfunction and result

in asphyxiation, explosion or fire.

* This burner must be installed and prepared for start-upby a qualified service technician who is trained and ex-perienced in commercial oil burner system installationand operation.

* Do not attempt to start the burner unless you are fullyqualified.

* Do not continue with this procedure until all items inthe "Prepare the burner for start-up" section have beenverified.

* Carefully follow the wiring diagrams, control instruc-tion sheets, flame safeguard sequence of operation, testprocedures and all appliance manufacturer's directionsthat pertain to this installation.

* If any of these items are not clear or are unavailable,call Beckett at 1-800-645-2876 for assistance.

Do Not Bypass SafetyControls

or bypassing safety controlscould lead to equipment malfunction and result

in asphyxiation, explosion or fire.

* Safety controls are designed and installed to provideprotection.

* Do not tamper with, or bypass any safety control.* If a safety control is not functioning properly, shut off

all main electrical power and fuel supply to the burnerand call a qualified service agency immediately.

Tampering with,

C{..................................

F m e-on .....

[ delay

)Standby

?

ignitionLockout

61 04 BCF1 0 NO4 '1 '1

Page 12: Potential Hazards - usermanual.wiki · Potential for Fire, Smoke and Asphyxiation Hazards Incorrect installation, adjustment, or misuse of this burner could result in death, severe

Keep Service AccessCovers Securely installed

These covers must be securely in place toprevent electrical shock, damage from exter-

nal elements, and protect against injury frommoving parts.

, All covers or service access plates must be in place atall times except during maintenance and service.

* This applies to all controls, panels, enclosures, switch-es, and guards or any component with a cover as partof its design.

El Adjusting plate assembly (Figure 12)

Make sure spline nut (item b) and bottom acorn nut(item c) are loose.

Figure 12 - Adjusting plate initial setting, typical

El Start=up checklist

Combustion air supply and venting have been inspectedand verified to be free of obstructions and installed in ac-

cordance with all applicable codes.

{221Oil nozzle has been selected correctly and securely in-stalled in the nozzle adapter.

Fuel unit by-pass plug has not been installed for one-pipeoil system.

{21By-pass plug has been installed for two-pipe oil system.

Fuel connection to nozzle line assembly is secure.

Dimension Z has been set per the 'Set Z Dimension'

instructions detailed earlier in this manual. The top acornnut (figure 12, item d) should never be loosened once the Zdimension in initially set.

Fuel supply line is correctly installed, the oil tank is suf-

ficiently filled, and shut-off valves are open.

Burner is securely mounted in appliance, with pressure fir-

ing plate and gasket installed for pressurized chamber ap-plication.

Appliance has been filled with water (boilers) and controlshave been operationally checked.

Burner has been installed in accordance with appliancemamKacturer's instructions (when available).

Also refer to appliance manufacturer's instructions (when

available) for start-up procedures.

I3 Z dimension

Should be set per these instructions (see page 9). The topacorn nut (Figure 12, item d) should never be loosenedonce the Z dimension is initially set.

Legend

b Sptine nut for securing nozzle line

C Bottom acorn nut (for head adjustment)

d Top Acorn nut (for setting dimension Z only)-do not loosen after setting dimension Z

e Indicator adjusting plate

tF Secondary adjusting plate

9 Primary adjusting plate

h Copper oil line from oil valve to nozzle line

112 6104 BCFIO R04

Page 13: Potential Hazards - usermanual.wiki · Potential for Fire, Smoke and Asphyxiation Hazards Incorrect installation, adjustment, or misuse of this burner could result in death, severe

initial head position (Figure 12)

• The indicator plate assembly (item e) markings correspondto head position settings. Slide the secondary adjustingplate (item f) toward the rear of the burner until the numberon the indicator plate corresponds to the initial head settinggiven in Table 4 for the desired firing rate.

• Fig,re 12 shows a typical example, with a head settingof 6.

• When the head position has been set, tighten the bottomacorn nut (item e) and the sptine nut (item b).

Table 4 - initial indicator adjustment platesettings (head position)

adjustingplate setting Tube !W'

4

6

7:12

NOTE

4.00

7.00

i i iii i - ii i iii

7.00

10.00 10.00; i

These settings are approximate, andcan vary depending on actual job con-ditions and overfire pressure.

®

initial air settings (Figure 12)

Loosen the screw holding the air adjusting plate (item m).Set the air to the desired rate. (The numbers on this platecorrespond to the approximate firing rate settings given inTable 5.)

* Rotate the air adjusting plate until the lower edge of thepointer is opposite the number from Table 5 correspondingto the desired firing rate.

* This initial setting should be adequate for starting the burner.Tighten the screw to secure the adjusting plate. Once theburner is in operation, the air setting will be adjusted forbest performance as discussed later in this manual.

* Follow the procedures given later in this manual for fine-tuning the air settings.

Table 5 - Initial air adjusting plate settings(damper position)

head settings Tube !!A, Tube "B,

0 4.00 4.00

2 5.00 8.00

6100 9100

4 7.00 10.00

r.506 8.00

10100 ;

These settings are approximate, andNOTE can vary depending on actual job con-

ditions and overfire pressure.

Set appliance limit controls

, Set the appliance limit controls in accordance with theappliance manufacturer's recommendations.

®

Prepare the fuel unit for air venting

To vent air fron_lone-pipe oil systems, attach a clear hoseto the pump air bleed valve (figure 10) on the fuel unit.Provide a container to catch the oil. Loosen the pump airbleed valve.Vent the air as described under Start the b,rner.

61 04 BCF1 0 R04 113

Page 14: Potential Hazards - usermanual.wiki · Potential for Fire, Smoke and Asphyxiation Hazards Incorrect installation, adjustment, or misuse of this burner could result in death, severe

Start the Burner

IExplosion and FireHazard

®

®

®

®

Failure to follow these instructions

could lead to equipment malfunction

and result in heavy smoke emission,soot-up, hot gas puff-back, fire andasphyxiation hazards.

Do not attempt to start the burner when excess oil hasaccunmtated in the appliance, the appliance is full ofvapor, or when the combustion chamber is very hot.Do not attempt to re-establish flame with the burnernmning if the flame becomes extinguished during start-up, venting, or adjustment.Vapor-Filled Appliance: Allow the unit to coot offandall vapors to dissipate before attempting another start.Oil-Flooded Appliance: Shut off the electrical powerand the oil supply to the burner and then clear all ac-cumulated oil before continuing.If the condition still appears unsafe, contact the Fire De-partment. Carefully follow their directions.Keep a fire extinguisher nearby and ready for use.

Professional ServiceRequired

incorrect installation, adjustment,and use of this burner could resultin severe personal injury, death, orsubstantial property damage fromfire, carbon monoxide poisoning,soot or explosion.

Please read and understand the manual supplied with thisequipment. This equipment nmst be installed, adjusted and putinto operation only by a qualified individual or service agencythat is:

o Licensed or certified to install and provide technicalservice to oil heating systems.

o Experienced with all applicable codes, standards andordinances.

o Responsible for the correct installation and commissionof this equipment.

o Skilled in the adjustment ofoit burners using combustiontest instruments.

The installation must strictly comply with all applicablecodes, authorities having jurisdiction and the latest revisionof the National Fire Protection Association Standard for the

installation of Oil-burning Equipment, NFPA 3 ! (or CSA B !39and B140 in Canada).

Regulation by these authorities take precedence over the generalinstructions provided in this installation manual.

Do not proceed unless all prior steps in this manual have beencompleted.

13 Starting the burner and venting air

Priming the pump

Hot Gas Puff=back and

Heavy Smoke Hazard

Failure to bleed the pump properlycould result in unstable combustion,

hot gas puff-back and heavy smoke.

® Do not allow oil to intermittently spray into a hot com-bustion chamber while bleeding.

• Install a gauge in the nozzle discharge port tubing orfully open the pump bleed valve to prevent oil sprayfrom accunmtating in the combustion chamber whenventing air from the fuel pump.

• Ensure that all bubbles and froth are purged from theoil supply system before tightening the pump air bleedvalve.

1. Verify that the air adjusting plate (Figure 12, item m) hasbeen set to the initial air position as described on page 13tinder Initial air settings.

2. Open the oil shut-off valves in the oil supply (and return)line(s) to the burner.

3. Set the thermostat (or operating control) to call for heat.

4. Close the line switch to the burner. The burner motor should

start immediately.

5. If the burner motor does not start, reset the motor overloadswitch (if so equipped) and press the reset switch of theburner primary control.

6. Vent the fuel unit as soon as the burner motor starts rotating.To vent --

13 Attach a clear plastic tube to the air bleed valve (Figure8 or 9 as applies, itemp).

13 Place the end of the tube in a container to catch the oil.Then loosen the fuel unit air vent valve.

13 Tighten the air vent valve after all air has been purged.

13 IF burner stops during venting --

• The burner primary control will lockout if flame is notestablished within its time limit. This is typically 15seconds for R7184B primary controls, but may be lessfor other flame supervisory controls.

• The burner may lockout several times during the periodneeded to purge all the air. Press the red reset button

114. 6104 BCF10 NO4

Page 15: Potential Hazards - usermanual.wiki · Potential for Fire, Smoke and Asphyxiation Hazards Incorrect installation, adjustment, or misuse of this burner could result in death, severe

for 1/2second during the prepurge cycle to extend airventing time.

IF burner stops afier flame established --

* Additional venting is probably required. Repeat theair venting procedure.

Disable function

Any time the motor is running, press and hold the resetbutton to disable the burner. The burner will remain off as

long as the button is held and will return to standby whenreleased.

CAD cell resistance cheek

While the burner is firing, and after the ignition has beenturned off, press and release the reset button (hold 1/2 sec-ond or tess) to check the cad celt resistance. The LED wiltflash ! to 4 times, depending on the cad celt resistance (re-fer to the table below).

Number of LED Cad Cell Resistance(ohms)flashes

1 Strong (0 to 400)

2 Norton (400 to 800)

3 Weak (800 to 1600)

4 Poor (1600 and above)*

* Lockout is likely to occur.

CO 2 level as high as possible (lowest possible 02),

Example: 13.5% CO 2 (2.5% 02) with a trace ofsmoke.

b. Increase the air to reduce CO 2by 2 percentage pointsat a zero smoke level. (Increase 0 2 by 3 percentagepoints at a zero smoke level.)

Example: Reduce CO 2 from 13.5% to 11.5%, withzero smoke (or increase 0 2from 2.5% to 5.5%).

c. This procedure provides a margin of reserve air to ac-comlnodate variable conditions.

5.

6.

Check the breech draft pressure against the appliancemanufacturer's recommended setting (typically + 0.1"W.C.).

If the breech pressure is higher or lower than recommend-ed level, adjust the appliance breech damper to achieve

the specified setting. Recheck the smoke and CO2 (or 02)levels. Adjust burner air if necessary and tighten the airadjusting plate screw securely.

Figure 13 - Air damper assembly

-:777°Tt.E6/naic {;7 =:7 : ---on Flame sensed

Off Flame not sensed

Flashing (1/2 sec off - 1/2 Lockout/Restrictedsec on) Lockout

F!asNng (2 sec off _2 sec ReCYcleon)

Set air adjusting plate (Figure 12)

l. Allow the burner to run until the appliance has warmedsufficiently.

2. Visually check the flame. The flame should not be darkorange or smoky. If the flame appears to be smoking,increase the amount of air by re-adjusting the damperindicator to a higher number.

3. Once the appliance has warmed, the air setting can bechecked and adjusted.

4. Use combustion test instruments to adjust the burner.

a. Adjust the air tmtil a trace of smoke is achieved with

O_

d ©

Legend

H Damper label - position indicator for air adjustment plate

J Damper indicator - permanently attached to damper

L Air adjusting plate - sets air position

K Air adjusting plate screw - locks plate position

6104 BCF10 RO4 115

Page 16: Potential Hazards - usermanual.wiki · Potential for Fire, Smoke and Asphyxiation Hazards Incorrect installation, adjustment, or misuse of this burner could result in death, severe

Maintenance a Service

Annual Professional

Service Required

Tampering with or making incorrect

adjustments could lead to equipmentmalfunction and result in asphyxia-tion, explosion or fire.

• Do not tamper with the burner or controls or makeany adjustments unless you are a trained and qualifiedservice technician.

• To ensure continued reliable operation, a qualifiedservice technician must service this burner annually.

• More frequent service intervals may be required in dustyor adverse environments.

• Operation and adjustment of the burner requires technicaltraining and skillful use of combustion test instrumentsand other test equipment.

drops of SAE 20 nondetergent oil at each oil hole. DO NOTover oil motor. Excessive oiling can cause motor failure.

[] Check motor current. The amp draw should not exceed thenameplate rating.

[] Check all wiring for secure connections or insulationbreaks.

[] Check the pump pressure and cutoff function.[] Check primal T control safety lockout timing.[] Check ignition system for proper operation.[] Inspect the vent system and chinmey for soot accunmtation

or other restriction.

[] Clean the appliance thoroughly according to the manufac-turer's reconamendations.

[] Check the burner performance. Refer to the section "Setcombustion with test instruments".

[] It is good practice to make a record of the service performedand the combustion test results.

Monthly maintenance = by owner

Annual service = by qualified service techni=clan

Have the burner inspected, tested and started at least annuallyby a qualified service technician. This annual test/inspectionshould include at least the following:

[] Replace the oil supply line filter. The line filter cartridgemust be replaced to avoid contamination of the fuel unitand nozzle.

[] Inspect the oil supply system. All fittings should be leak-tight. The supply lines should be free of water, sludge andother restrictions.

[] Remove and clean the pump strainer if applicable.[] Replace the nozzle with the exact brand, pattern, gph, flow

rate and spray angle.[] Clean and inspect the electrodes for damage, replacing any

that are cracked or chipped.[] Check electrode tip settings. Replace electrodes if tips are

rounded.

[] Inspect the igniter spring contacts.[] Clean the cad cell lens surface, if necessary.[] Inspect all gaskets. Replace any that are damaged or would

fail to seal adequately.[] Inspect the combustion head and air tube. Remove any car-

bon or foreign matter. Replace all damaged units with exact

parts.[] Clean the blower wheel, air inlet, air guide, and burner

housing of any lint or foreign material.[] If motor is not permanently lubricated, oil motor with a few

Observe combustion air openings and vent system for

integrity. Openings must be clean and free of obstructions.

Check oil lines and fittings to verify there are no leaks.

Observe burner ignition and performance to verify smooth

operation.

Shut the system down if you observe abnormal or

questionable operation. Call a qualified service agency forprofessional inspection and service.

II 6 6104 BCFIO R04

Page 17: Potential Hazards - usermanual.wiki · Potential for Fire, Smoke and Asphyxiation Hazards Incorrect installation, adjustment, or misuse of this burner could result in death, severe

See next page for __ replacement parts

Page 18: Potential Hazards - usermanual.wiki · Potential for Fire, Smoke and Asphyxiation Hazards Incorrect installation, adjustment, or misuse of this burner could result in death, severe

Rep|acement partsfor best performance specify genuine __g_ replacement parts

1 Timer Nozzle valve delay 21295U

Oil Valve Box mounted 2!789U

3 Adjusting plate assembly CF10-2300 Kit 51213U

4 Knurled nut All models 3666

B2TA-8245 21313U5 Fuel pump H3PAN-C150H 21309U

P Ikitedesta All models 51193

7 Fuel lines Specify length

Damper spring All models H 4339

9 Sight glass All models 31346

HCast aluminum door 5994UJStamped sheet_metal door* 520i301U

11 Control SpecifyIi

12 Damper indicator All models . 5985BK

13 Coupling Hole Plug Use with threaded hole 32439UCoupling Access Door Use with rectangular opening 16703GY

14 Head assembly CF1000 combustion 51203P

15 Electrode assembly All models 51212

8'ii4' long 5990082

1i:3;4,,0ng '699oii6'gniti°n !eads 6990J62

I 19'1/4'long' 5990192

17 Nozzle line assembly Refer to Figure 2, Page 7

18 Air tube ......... Refer to Figure 2, Page7

19 Transformer 12,000 volt 51214

21 Blower wheel CF1000 5.50" x 3.09" 21268U

................................................ 21402u22 , lotor 208/230_460V three phase 21638U

120V single phase 7223Motor relay (not shown) 208V single phase 7300

three phase 21719

AdjuStable flange j See Figure13 on 0pposite page

* These doors are NOT interchangeable. Please specify what you are replacing.

118 6104 BCF10 RO4

Page 19: Potential Hazards - usermanual.wiki · Potential for Fire, Smoke and Asphyxiation Hazards Incorrect installation, adjustment, or misuse of this burner could result in death, severe

Figure 14 - AdjustableMounting Plates for CFIO00

Kit #51312

12¼"

Kit #5 i 629

61 04 BCF1 0 R04 119

Page 20: Potential Hazards - usermanual.wiki · Potential for Fire, Smoke and Asphyxiation Hazards Incorrect installation, adjustment, or misuse of this burner could result in death, severe

Limited Warranty information

Limited

RRANTYFor Residential, Commercial and Specialty Burners

The R. W. BECKETT CORPORATION ("Beckett") warrants to persons who purchase its Beckett burners fi'om Beckett fbr resale or fbr

incorporation into a product fbr resale ("Customers") that its equipment is fi'ee from defects in material and workmanship under normal use andservice f\_r 60 months from the date of manuf;acture fbr Residential Burners and 18 months from the date of manuf;acture fbr Commercial and

Specialty Burners. Residet_tial bz_rt_er models' inchMe: AF, AFG, AFII, NX, SF, SR and SMG. Commercial bw'ner models' mehMe: CF375,

CF500, CFS00, CF1400, CF2300A, CF2500, CF3500A, CG10, CG15, CG25 and CG50. 5_eeia[ O bzcrner models' inelzcde: ADC, ADCP, ARV,

SDC and SM. The provisions of this warranty are extended to individual major burner components as t\41ows:

a) 60 months from date of manuf=acture fbr all Beckett-branded major components, except f\_r 12 Vdc components.

b) 18 months from date ofmanuf;acture t\_r all non-Beckett-branded major components and Beckett branded 12 Vdc components.

Note: Normal service items t\mnd to be def_cti'_ e upon receipt by the customer are co'_ ered by this warranty.

THIS _\'ARRANTY DOES NOT EXTEND TO EQUIPMENT SUBJECTED TO MISUSE, NEGLECT, OR ACCIDENT: NOR DOES THIS Y_2kRRANTY APPLY

UNLESS THE PRODUCT COVERED BY IT IS PROPERLY INSTALLED BY A QUALIFIED, COMPETENT TE(:HNICIAN, WHO IS LICENSED WHERE

STATE AND LOCAL (:ODES REQ[ IRE, AND WHO IS EXPERIENCED IN MAKING SUCH INSTALLATIONS, IN ACCORDANCE _rlTH THE LATEST

EDITION OF NFPA NO. 31 OF THE NATIONAL FIRE PROTECTION ASSOCIATION, THE LATEST EDITION OF THE NATIONAL F[EL GAS CODE (NFPA

NO. 54) AND IN ACCORDANCE WITH ALL APPLICABLE LOCAL, STATE AND NATIONAL (:ODES HAVING JURISDICTIONAL AUTHORITY.

Equipment, which is de*_ctive in material or workmanship and within the warranty period, may be returned for credit as %llows:Beckett Burners, Beckett-branded major components and non-Beckett-branded major components that came as original equipment on a Beckett burner

or were sold as a replacement part by Beckett should be returned, freight prepaid, to Beckett's home office. Credit will be issued to the customer unlessthe returned equipment is determined by Beckett to be out of warranty or damaged by user, in which case the equipment will be scrapped.

Note: Beckett is not responsible for any labor cost fur removal and replacement of equipment.

THIS WARtL_NTY IS LIMITED TO THE PRECISE TERMS SET FORTH ABOVE. AND PROVIDES EXCLUSIVE REMEDIES EXPRESSLY IN LIEU OF ALL OTHER

REMEDIES, AND IN PARTICULAR THERE SHALL BE EXCLUDED THE IMPLIED WARI_NTIES OF MERCHANTABILITY AND FITNTSS FOR A PARTICULAR

PURPOSE. IN NO EVENT WILL BECKETT BE LIABLE FOR ANY INCIDENTAL OR CONSEQUI_NTIAL DAMAGE OF ANW NATURE Beckett neither assumes nor

authorizes any person to assmne _br Beckett any other liability or obligation in colmection with the sale of this equipment, Beckett's liability and Customer's

exclusive remedy being limited to credit as set fi, rth above.

Form No.61545 R72905

R,W, BECKETT CORPORATIONU.S.A.: P.O. Box '1289 • Elyria, Ohio 44036

www.beckettcorp,comCanada: R.W. Beckett Canada, Ltd. • Unit #3,430 Laird Road • Guelph, Ontario N1G 3X7

Printed in U.S.A. 12/2006 © R.W. Beckett Corporation