Page 1: Pneg-010 - Vane Axial Fan - WordPress.com · 8 PNEG-010 Vane Axial Fan Safety Alert Decals DC-1225 Stay clear of rotating blade. Blade could start automatically. Can cause serious

PNEG-010

Vane Axial Fan Installation and Operation

Model #: ____________

Owner’s Manual

PNEG-010Date: 03-21-14

Page 2: Pneg-010 - Vane Axial Fan - WordPress.com · 8 PNEG-010 Vane Axial Fan Safety Alert Decals DC-1225 Stay clear of rotating blade. Blade could start automatically. Can cause serious

2 PNEG-010 Vane Axial Fan

Fan Check List

1. All wire connections.

2. Tip clearance on blade.

3. Fan blade torqued to torque specs.

4. Grill guard in place and tight.

5. Fuse in place, extra fuse provided.

6. Motor rotation correct.

7. Contactor engages properly.

8. Running amperage.

9. Vibration.

10. All fasteners tight.

11. Indicator light.

12. All decals and serial number tag.

13. Aesthetic appearance.

14. Manual.

Tester Signature: __________________________

Date: ____________________________________

Record in the space provided below the Model # and Serial # of this product. These numbers are found on the Model and Serial Tags located on the outside of the unit.

Model #: ___________________________________________

Serial #: ___________________________________________

Keep these numbers for future reference.

Page 3: Pneg-010 - Vane Axial Fan - WordPress.com · 8 PNEG-010 Vane Axial Fan Safety Alert Decals DC-1225 Stay clear of rotating blade. Blade could start automatically. Can cause serious

Table of Contents

PNEG-010 Vane Axial Fan 3

ContentsChapter 1 Safety .....................................................................................................................................................4

Safety Guidelines .................................................................................................................................. 4Safety Instructions ................................................................................................................................. 5

Chapter 2 Decals ....................................................................................................................................................7Roof Damage Warning and Disclaimer ................................................................................................. 7Safety Alert Decals ................................................................................................................................ 8

Chapter 3 Installation Instructions .....................................................................................................................10Vane Axial Fan Pad ............................................................................................................................ 10

Chapter 4 Fan Installation ...................................................................................................................................11Pre-Installation Requirements ............................................................................................................. 11Machine to Earth Ground .................................................................................................................... 14Previously Installed Units .................................................................................................................... 14Proper Installation of the Ground Rod ................................................................................................. 14

Chapter 5 Fan Specifications ..............................................................................................................................15

Chapter 6 Fan Operation .....................................................................................................................................18Fan Start-Up ........................................................................................................................................ 18Fan Shut Down ................................................................................................................................... 18Maintaining Grain Quality .................................................................................................................... 18Grain Storage ...................................................................................................................................... 19Fan Blade Removal and Installation ................................................................................................... 20Removing the Fan Blade Assembly .................................................................................................... 21Installing the Fan Blade Assembly ...................................................................................................... 21

Chapter 7 Fan Service .........................................................................................................................................24Fan Blade Inspection and Maintenance .............................................................................................. 24Fan Motor ............................................................................................................................................ 24

Chapter 8 User Servicing Instructions and Troubleshooting ..........................................................................27Fan Troubleshooting Flow Chart ......................................................................................................... 28

Chapter 9 Parts List .............................................................................................................................................2912''-14'' Fan Parts ................................................................................................................................ 2918''-28'' Fan Parts ................................................................................................................................ 30

Chapter 10 Wiring Diagrams ...............................................................................................................................311 Phase 230 Volt Schematic ............................................................................................................. 321 Phase 230 Volt Wiring Diagram and Parts ..................................................................................... 333 Phase 230 Volt Schematic ............................................................................................................. 343 Phase 230 Volt Wiring Diagram and Parts ..................................................................................... 353 Phase 460 Volt Schematic ............................................................................................................. 363 Phase 460 Volt Wiring Diagram and Parts ..................................................................................... 373 Phase 575 Volt Schematic ............................................................................................................. 383 Phase 575 Volt Wiring Diagram and Parts ..................................................................................... 39

Chapter 11 Warranty ............................................................................................................................................41

Page 4: Pneg-010 - Vane Axial Fan - WordPress.com · 8 PNEG-010 Vane Axial Fan Safety Alert Decals DC-1225 Stay clear of rotating blade. Blade could start automatically. Can cause serious

4 PNEG-010 Vane Axial Fan

1. Safety

Safety Guidelines

This manual contains information that is important for you, the owner/operator, to know and understand. This information relates to protecting personal safety and preventing equipment problems. It is the responsibility of the owner/operator to inform anyone operating or working in the area of this equipment of these safety guidelines. To help you recognize this information, we use the symbols that are defined below. Please read the manual and pay attention to these sections. Failure to read this manual and its safety instructions is a misuse of the equipment and may lead to serious injury or death.

DANGER

WARNING

CAUTION

NOTICE

This is the safety alert symbol. It is used to alert you to potential personal injury hazards. Obey all safety messages that follow this symbol to avoid possible injury or death.

WARNING indicates a hazardous situation which, if not avoided, could result in death or serious injury.

CAUTION, used with the safety alert symbol, indicates a hazardous situation which, if not avoided, could result in minor or moderate injury.

NOTICE is used to address practices not related to personal injury.

DANGER indicates a hazardous situation which, if not avoided, will result in death or serious injury.

Page 5: Pneg-010 - Vane Axial Fan - WordPress.com · 8 PNEG-010 Vane Axial Fan Safety Alert Decals DC-1225 Stay clear of rotating blade. Blade could start automatically. Can cause serious

1. Safety

PNEG-010 Vane Axial Fan 5

Safety Instructions

Our foremost concern is your safety and the safety of others associated with this equipment. We want to keep you as a customer. This manual is to help you understand safe operating procedures and some problems that may be encountered by the operator and other personnel.

As owner and/or operator, it is your responsibility to know what requirements, hazards, and precautions exist, and to inform all personnel associated with the equipment or in the area. Safety precautions may be required from the personnel. Avoid any alterations to the equipment. Such alterations may produce a very dangerous situation where SERIOUS INJURY or DEATH may occur.

This equipment shall be installed in accordance with the current installation codes and applicable regulations, which should be carefully followed in all cases. Authorities having jurisdiction should be consulted before installations are made.

Follow Safety Instructions

Carefully read all safety messages in this manual and safety signs on your machine. Keep signs in good condition. Replace missing or damaged safety signs. Be sure new equipment components and repair parts include the current safety signs. Replacement safety signs are available from the manufacturer.

Learn how to operate the machine and how to use controls properly. Do not let anyone operate without instruction.

Keep your machinery in proper working condition. Unauthorized modifications to the machine may impair the function and/or safety and affect machine life.

If you do not understand any part of this manual or need assistance, contact your dealer.

Read and Understand Manual

Install and Operate Gas-Fired Equipment Properly

Fuel supply should be installed by a qualified gas technician and must meet local and state codes for gaseous fuel supplies.

Disconnect and lock out all fuel sources before servicing equipment. Explosive Gases

Page 6: Pneg-010 - Vane Axial Fan - WordPress.com · 8 PNEG-010 Vane Axial Fan Safety Alert Decals DC-1225 Stay clear of rotating blade. Blade could start automatically. Can cause serious

1. Safety

6 PNEG-010 Vane Axial Fan

Install and Operate Electrical Equipment Properly

Electrical controls should be installed by a qualified electrician and must meet the standards set by the National Electrical Code and all local and state codes.

Disconnect and lock out all power sources before installing wires/cables or servicing equipment.

Electric Shock Hazard

Prepare for Emergencies

Be prepared if fire starts.

Keep a first aid kit and fire extinguisher handy.

Keep emergency numbers for doctors, ambulance service, hospital, and fire department near your telephone.

Keep Emergency Equipment Quickly Accessible

Wear Protective Clothing

Wear close-fitting clothing and safety equipment appropriate to the job.

Remove all jewelry.

Tie long hair up and back.

Wear safety glasses at all times to protect eyes from debris.

Wear gloves to protect your hands from sharp edges on plastic or steel parts.

Wear steel-toed boots to help protect your feet from falling debris. Tuck in any loose or dangling shoestrings.

A respirator may be needed to prevent breathing potentially toxic fumes and dust.

Wear a hard hat to help protect your head.

Wear appropriate fall protection equipment when working at elevations greater than six feet (6').

Eye Protection

Gloves

Steel-Toed Boots

Respirator

Hard Hat

Fall Protection

Page 7: Pneg-010 - Vane Axial Fan - WordPress.com · 8 PNEG-010 Vane Axial Fan Safety Alert Decals DC-1225 Stay clear of rotating blade. Blade could start automatically. Can cause serious

PNEG-010 Vane Axial Fan 7

2. Decals

Roof Damage Warning and Disclaimer

The manufacturer does not warrant any roof damage caused by excessive vacuum or internal pressure from fans or other air moving systems. Adequate ventilation and/or “makeup air” devices should be provided for all powered air handling systems. The manufacturer does not recommend the use of downward flow systems (suction). Severe roof damage can result from any blockage of air passages. Running fans during high humidity/cold weather conditions can cause air exhaust or intake ports to freeze.

Excessive vacuum (or pressure) may damage roof. Use positive aeration system. Make sure all roof vents are open and unobstructed. Start roof fans when supply fans are started. Do not operate when conditions exist that may cause roof vent icing.

DC-969

CAUTION

GSI Group, Inc. 217-226-4421

Page 8: Pneg-010 - Vane Axial Fan - WordPress.com · 8 PNEG-010 Vane Axial Fan Safety Alert Decals DC-1225 Stay clear of rotating blade. Blade could start automatically. Can cause serious

2. Decals

8 PNEG-010 Vane Axial Fan

Safety Alert Decals

DC-1225

Stay clear of rotatingblade. Blade could startautomatically. Can causeserious injury. Disconnectpower before servicing.

DC-1225GSI Group 217-226-4421

WARNING

Page 9: Pneg-010 - Vane Axial Fan - WordPress.com · 8 PNEG-010 Vane Axial Fan Safety Alert Decals DC-1225 Stay clear of rotating blade. Blade could start automatically. Can cause serious

2. Decals

PNEG-010 Vane Axial Fan 9

DANGERHIGH VOLTAGEWill cause injuryor death.Lockout powerbefore servicing.

DC

-889

GSI Group Inc. 217-226-4421

Page 10: Pneg-010 - Vane Axial Fan - WordPress.com · 8 PNEG-010 Vane Axial Fan Safety Alert Decals DC-1225 Stay clear of rotating blade. Blade could start automatically. Can cause serious

10 PNEG-010 Vane Axial Fan

3. Installation Instructions

Vane Axial Fan Pad

Placement of the Fan Pad: Transitions/Fans/Heaters Only

If a fan or fan and heater is to be installed, refer to Figure 3A to determine the concrete pad size.

1. The top of this pad should be level with the top of the bin’s foundation.

2. Recommended pad thickness is 4" minimum.

3. Front of pad should be perpendicular to bin wall.

4. Pad for heater not required, but if it is to added, pour the pad to cover both locations.

For fans and transitions used in aeration duct system applications, refer the transition and aeration installation instructions.

IMPORTANT: Fan pad and fan must be level and smooth for proper operation. Vibration problems can result from improper fan leveling.

Figure 3A

TR-4734A = 20" for fans without heatersA = 44'' for fans with heaters

TR-6918 and TR-6919A = 32" for fans without heatersA = 56" for fans with heaters

TR-7048A = 45" for fans without heatersA = 69" for fans with heaters

Page 11: Pneg-010 - Vane Axial Fan - WordPress.com · 8 PNEG-010 Vane Axial Fan Safety Alert Decals DC-1225 Stay clear of rotating blade. Blade could start automatically. Can cause serious

PNEG-010 Vane Axial Fan 11

4. Fan Installation

Pre-Installation Requirements

Foundation

Use the dimension Figure 5A on Page 15 in the specifications section of this manual to determine the physical size of the fan to be installed. Use the dimensions shown to determine the position of the fan installation with respect to other equipment.

For proper operation of the fan, the unit is to be mounted on a level pad. The fan should not be anchored to the pad, but it should be allowed to “float” on the pad. Refer to Figure 5A on Page 15 for fan pad location in the specifications section of this manual for recommendations of pad placement with respect to various catalog transition ducts.

Transition

The transition duct should be all metal construction, with a gradual angle to the rectangular opening in the bin wall. The duct should allow for a smooth transition with minimal resistance of the airflow from the fan discharge to the bin plenum. Keep the entrance of the plenum as clear as possible from obstructions by floor support.

Roof Exhaust

Adequate exhaust air openings in the roof are required to prevent any additional back pressure from building in the bin. See roof damage warning and disclaimer on Page 7.

Power Supply

Adequate power must be supplied to the fan for reliable operation. Consult the local power company and have a representative survey the installation. Only the power company can ensure that their system is sized properly to provide adequate service to the installation and new equipment.

Wire Size

Undersized wire can lead to voltage drop which causes motor overheating and shortened motor life. Use the electrical specifications chart on Page 16 in this manual to size the supply wire according to the horsepower of the fan and the distance to the power supply. Refer to fan specifications section on Page 15 of this manual to find the full load current of the motor for a given fan size. The full load current can also be found on the motor nameplate.

Service Disconnect

Each fan motor must be supplied with an independent power circuit, equipped with a fused disconnect switch. Locate this switch near the unit, as the power should be shut off before servicing the fan.

It is the customer’s responsibility to provide a fused disconnect and motor overload protection. These must be properly sized and connected to allow proper motor operation. Failure to provide these components could cause severe motor damage and void the manufacturer’s warranty.

Page 12: Pneg-010 - Vane Axial Fan - WordPress.com · 8 PNEG-010 Vane Axial Fan Safety Alert Decals DC-1225 Stay clear of rotating blade. Blade could start automatically. Can cause serious

4. Fan Installation

12 PNEG-010 Vane Axial Fan

Fan Installation

1. Remove packaging materials and inspect fan for any shipping damages. Report these at once to the shipper.

2. Check all fasteners on the fan to make sure they are tight (fasteners may loosen during shipment). Tighten any loose fasteners, check for proper clearance and re-tighten.

3. Check all electrical connections that may have loosened during shipment.

4. Rotate the fan blade. Blade should rotate freely and should not make contact with the housing sides or venturi.

5. Place fan in proper location on the fan pad. Attach fan to transition duct and seal connection with caulk.

6. Check all joints and seams around the lower part of the bin. Verify that these are well sealed to prevent air leakage from the bin plenum. Inspect the transition duct as well. Seal any leaks that may be present to prevent air losses that reduce fan efficiency.

7. Level fan. Fan pad should be poured flat and level, however, it may be necessary to shim the legs provided on the fan housing to level the fan. Fans not resting on support legs may have excess vibration which can lead to premature wear and tear on fan components.

IMPORTANT: Electrical installation must be performed by a qualified electrician, in accordance with National and Local Electrical Codes. Any violation of electrical wiring codes could jeopardize the warranty.

Electrical Installation

1. Verify that the incoming power supply has been deemed adequate by the local power company.

2. Verify that the wiring supplying power to the fan is sized correctly for the distance away from supply and fan horsepower. (See tables in specification section on Page 16 of this manual.)

3. Verify that the safety disconnect is installed and sized correctly for the fan size. (See tables in specification section on Page 16 of this manual.)

4. Install a machine to earth ground for each individual fan. Refer to ground rod installation on Page 14 in this manual.

5. The following wires must be supplied to each fan. Units without control transformers require a separate neutral and earth ground connection.

6. The starter controls require 115 VAC power to operate. On 230 volt 3 phase units, this power is supplied by L1 to neutral.

1 PH 230V L1, L2, N, G

3 PH 230V L1, L2, L3, N, G

3 PH 230V with optional transformer kit L1, L2, L3, G

3 PH 460V/575V L1, L2, L3, G

DANGERAlways disconnect and lock out power before working on or around fan.

Page 13: Pneg-010 - Vane Axial Fan - WordPress.com · 8 PNEG-010 Vane Axial Fan Safety Alert Decals DC-1225 Stay clear of rotating blade. Blade could start automatically. Can cause serious

4. Fan Installation

PNEG-010 Vane Axial Fan 13

Check this voltage before starting unit. If voltage is not within 105 VAC-125 VAC, check for proper voltage on L2 or L3 and move to appropriate leg. If voltage is not acceptable, install a 1/4 KVA step-down transformer. (NOTE: Grounded B and some open delta power supplies will require this transformer kit.)

Final Check

Check to make sure all safety guards are in place and not damaged. Replace damaged parts. Check to make sure all decals are visible and not damaged. Replace damaged decals. Check to make sure all control boxes are closed and no wiring is exposed.

Test Run

When the fan is completely installed, the unit will need to be checked for proper rotation. Provide power to the fan controls and start the fan momentarily. Make sure that the fan blade rotation is in the direction that the decal on the fan housing illustrates. If the blade is rotating the wrong direction, have the electrician correct the wiring.

Figure 4A

CAUTIONThe voltage between L1 and N must be 115 VAC. Any other voltage will cause damage to equipment.

Use a #6 or approved size bare copper ground wire. Install a 5/8" diameter 8' long copper-clad ground rod, 2' away from the foundation and 1' below the surface of the ground or in accordance with local requirements.

Page 14: Pneg-010 - Vane Axial Fan - WordPress.com · 8 PNEG-010 Vane Axial Fan Safety Alert Decals DC-1225 Stay clear of rotating blade. Blade could start automatically. Can cause serious

4. Fan Installation

14 PNEG-010 Vane Axial Fan

Machine to Earth GroundIt is very important that a machine to earth ground rod be installed at the fan. This is true even if there is a ground at the pole 15' away. This ground needs to be as close to the fan as possible, but no more than 8' away. The ground rod should be connected to the fan control panel with at least a #6 solid bare copper ground wire or in accordance with local requirements. The machine to earth ground provides additional safety if there is a short. It also provides the grounding necessary for long life and operation of the solid state circuit boards used on control circuits and the electronic ignition systems.

Previously Installed Units

It is recommended that previously installed units be checked to see that a machine to earth ground has been installed by an electrician.

Proper Installation of the Ground RodGround rods and wires are not supplied. It is recommended that the rod not be driven into dry ground. The following steps ensure proper ground rod installation:

1. Dig a hole large enough to hold 1 to 2 gallons of water.

2. Fill hole with water.

3. Insert rod through water and jab it into the ground.

4. Continue jabbing the rod up and down, the water will work its way down the hole, making it possible to work the rod completely into the ground. This method of installing the rod gives a good conductive bond with the surrounding soil.

5. Connect the bare copper ground wire to the rod with the proper ground rod clamp.

6. Connect the bare ground wire to the fan control boxes with a grounding lug.

7. Ground wire must not have any breaks or splices. Insulated wire is not recommended for grounding.

Figure 4B

Dig a hole large enough to hold 1 or 2 gallons of water. Work the ground rod into the earth until it is completely in the ground.

Page 15: Pneg-010 - Vane Axial Fan - WordPress.com · 8 PNEG-010 Vane Axial Fan Safety Alert Decals DC-1225 Stay clear of rotating blade. Blade could start automatically. Can cause serious

PNEG-010 Vane Axial Fan 15

5. Fan Specifications

NOTE: All dimensions in inches.

Figure 5A Fan Dimensions

Fan 12'' Diameter

1 HP12'' Diameter

0.75 HP14'' Diameter

18'' Diameter1.5 HP/3 HP

24'' Diameter 26'' Diameter 28'' Diameter

A (Bolt circle) 13-1/2" 13" 15-1/4" 19-1/4" 25-3/4" 27-3/4" 30"

B (Inside diameter) 12-1/4" 11-7/8" 14-1/4" 18-1/4" 24-1/4" 26-5/16" 28-1/4"

C (CL to bottom of leg) 7-9/16" 7-9/16" 10-7/8" 11-7/8" 15-7/16" 16-7/8" 18-1/8"

D (Length) 16-1/8" 16-1/8" 16-3/16" 17/20" 24" 24" 24"

E - - - - 26-3/4" - 26-3/4"

Page 16: Pneg-010 - Vane Axial Fan - WordPress.com · 8 PNEG-010 Vane Axial Fan Safety Alert Decals DC-1225 Stay clear of rotating blade. Blade could start automatically. Can cause serious

5. Fan Specifications

16 PNEG-010 Vane Axial Fan

Fan Electrical Specifications

Fan Horsepower 3/4 1

RPM 3450 3450

Phase 1 3 1 3

Volts 230 230 460 575 230 230 460 575

Full Load Amps 5.5 2.6 1.3 1 5.5 3 1.5 1.2

Minimum Wire Size Copper Wire Copper Wire

50' Run 14 14 14 14 14 14 14 14

100' Run 14 14 14 14 14 14 14 14

200' Run 12 14 14 14 12 14 14 14

300' Run 10 14 14 14 10 14 14 14

Minimum Wire Size Aluminum Wire Aluminum Wire

50' Run 14 14 14 14 14 14 14 14

100' Run 14 14 14 14 14 14 14 14

200' Run 10 14 14 14 10 14 14 14

300' Run 8 12 14 14 8 12 14 14

Fuse Size (Slow Blow) 15 10 5 5 15 10 5 5

Breaker Size 20 15 10 10 20 15 10 10

Fan Horsepower 1-1/2 3

RPM 3450 3450

Phase 1 3 1 3

Volts 230 230 460 575 230 230 460 575

Full Load Amps 7.5 4.6 2.3 1.8 15 7.4 3.7 3

Minimum Wire Size Copper Wire Copper Wire

50' Run 14 14 14 14 12 12 14 14

100' Run 12 14 14 14 10 12 12 12

200' Run 8 12 14 14 8 10 12 12

300' Run 6 10 12 12 6 8 10 10

Minimum Wire Size Aluminum Wire Aluminum Wire

50' Run 12 12 14 14 12 12 12 12

100' Run 10 12 12 14 8 10 12 12

200' Run 6 10 12 12 6 10 10 10

300' Run 4 10 12 12 4 8 10 10

Fuse Size (Slow Blow) 15 10 5 5 30 15 10 10

Breaker Size 20 15 10 10 40 20 15 15

Page 17: Pneg-010 - Vane Axial Fan - WordPress.com · 8 PNEG-010 Vane Axial Fan Safety Alert Decals DC-1225 Stay clear of rotating blade. Blade could start automatically. Can cause serious

5. Fan Specifications

PNEG-010 Vane Axial Fan 17

Fan Horsepower 5 7

RPM 3450 3450

Phase 1 3 1 3

Volts 230 230 460 575 230 230 460 575

Full Load Amps 30 18 9 6.9 30 18 9 6.9

Minimum Wire Size Copper Wire Copper Wire

50' Run 10 10 12 12 10 10 12 12

100' Run 8 10 12 12 8 10 12 12

200' Run 4 8 10 12 4 8 10 12

300' Run 4 6 8 10 4 6 8 10

Minimum Wire Size Aluminum Wire Aluminum Wire

50' Run 8 8 12 12 8 8 12 12

100' Run 6 8 10 12 6 8 10 12

200' Run 3 6 10 10 3 6 10 10

300' Run 2 4 8 10 2 4 8 10

Fuse Size (Slow Blow) 40 25 15 15 40 25 15 15

Breaker Size 60 30 15 15 60 30 15 15

Fan Horsepower 10 15

RPM 3450 3450

Phase 1 3 1 3

Volts 230 230 460 575 230 230 460 575

Full Load Amps 47 25 13 9.6 57 32 16 14

Minimum Wire Size Copper Wire Copper Wire

50' Run 8 8 12 12 6 6 10 10

100' Run 6 6 10 12 4 4 10 10

200' Run 4 4 10 10 2 2 10 10

300' Run 2 2 8 8 0 0 8 10

Minimum Wire Size Aluminum Wire Aluminum Wire

50' Run 6 6 12 12 4 4 8 8

100' Run 4 4 10 10 2 2 8 8

200' Run 2 2 8 10 0 0 6 8

300' Run 0 0 6 8 0 0 4 6

Fuse Size (Slow Blow) 60 30 20 15 75 40 20 20

Breaker Size 80 40 20 20 100 60 30 20

Page 18: Pneg-010 - Vane Axial Fan - WordPress.com · 8 PNEG-010 Vane Axial Fan Safety Alert Decals DC-1225 Stay clear of rotating blade. Blade could start automatically. Can cause serious

18 PNEG-010 Vane Axial Fan

6. Fan Operation

After initial installation and also prior to using the unit each season, check the operation to ensure proper functioning, adjustment and reliability.

Fan Start-Up

1. Make certain the unit is properly installed and connected, as described within the installation section of this manual. All air passage joints and seams must be well sealed.

2. With main power supply turned OFF, rotate the blade by hand to make certain it turns freely without contacting the housing or venturi.

3. Open roof doors to allow airflow at all times when fan is operating.

IMPORTANT: Refer to roof damage disclaimer in the safety section on Page 7 of this manual.

4. Turn ON main power disconnect switch.

5. Press the fan Start button and check the following:

a. Check direction of blade rotation. Correct if needed by following the instructions on the motor.

b. Check to make sure the blade comes to full operating speed in less than 10 seconds. If there is any doubt as to proper operation, check the current draw of the motor. The motor amperage should not exceed the maximum full load amps listed on the motor nameplate.

Fan Shut Down1. Press the fan Stop button on units equipped with motor controls.

2. Shut off electrical power at main and at disconnect.

3. Close the roof openings and cover fan inlet to prevent harmful back-draft air currents from passing through the grain and to avoid grain infestation from rodents and insects.

Maintaining Grain QualityTo properly maintain the quality of stored grain, it is necessary to keep the grain dry, cool and insect free. Any one of these problems can contribute to spoilage. Wet, warm grain promotes insect growth as well as grain spoilage. Cool, dry grain can keep for long periods of time. (See Chart on Page 19.)

It is recommended that the grain be kept cool (avoid freezing as freezing can reduce quality). Grain should be cooled through the fall and winter, warmed in the spring and summer.

WARNINGMake certain all guards and covers are securely in place.

Page 19: Pneg-010 - Vane Axial Fan - WordPress.com · 8 PNEG-010 Vane Axial Fan Safety Alert Decals DC-1225 Stay clear of rotating blade. Blade could start automatically. Can cause serious

6. Fan Operation

PNEG-010 Vane Axial Fan 19

Grain Storage

IMPORTANT: Conditions and requirements may vary from area to area. Contact the local agriculture extension office or state agriculture university for more exact guidelines.

Average grain temperature should be above 35°F in the winter and below 65°F in the summer. Always try to keep the grain within 10°F-15°F of the average monthly outside temperature. This means grain may need to be aerated on warm days during the winter to stay above 35°F when freezing temperatures are predominate. During the summer it may be necessary to aerate the grain on cool nights, so the 65°F temperature is not exceeded during the hot days of summer.

If the grain is to be stored more than 1 year, it has to be recooled the following fall and winter, repeating the process as long as the grain is in storage. Frequent and regular inspection (at least weekly during fall and spring) is the best prevention against grain spoilage.

Equilibrium Moisture Chart

Approximate Allowable Holding Time for Field-Shelled Corn, to Maintain Grade*

Air Temperature

Percentage Relative Humidity

35 40 45 50 55 60 65 70 75 80 85 90 95 100

20°F 11.2 11.7 12.7 13.7 14.5 15.1 16.2 17.1 18.0 19.6 21.2 23.5 25.8 29.1

30°F 10.8 11.3 12.2 13.1 13.9 14.6 15.5 16.4 17.4 18.7 20.2 22.5 25.0 28.3

40°F 10.5 11.0 11.7 12.5 13.3 14.0 14.8 15.5 16.6 17.8 19.4 21.5 24.2 27.5

50°F 10.1 10.6 11.3 12.0 12.7 13.3 14.1 14.8 15.8 16.9 18.6 20.5 23.4 26.7

60°F 9.7 10.2 10.9 11.6 12.1 12.7 13.4 14.2 15.0 16.0 17.8 19.5 22.6 25.9

70°F 9.0 9.7 10.4 11.1 11.5 12.0 12.8 13.5 14.5 15.4 16.8 18.5 21.3 24.5

80°F 8.3 9.1 9.8 10.5 10.8 11.2 12.1 13.0 13.9 14.8 15.8 17.4 20.0 22.8

Grain Temperature

15% Days

18% Days

20% Days

22% Days

24% Days

26% Days

28% Days

30% Days

40°F 898 195 85 54 38 28 24 20

50°F 451 102 46 28 19 16 13 11

60°F 242 63 26 16 10 8 6.5 5.5

70°F 147 37 13 8 5 4 3.5 3

80°F 109 27 10 6 4 3 2.5 2

*Allowable holding time for field-shelled corn at various grain temperatures and moisture.

Safe moisture for normal winter storage of shelled corn is about 15%. Grain to be stored through the summer or long term, needs to be 1 to 3 points dryer.

Page 20: Pneg-010 - Vane Axial Fan - WordPress.com · 8 PNEG-010 Vane Axial Fan Safety Alert Decals DC-1225 Stay clear of rotating blade. Blade could start automatically. Can cause serious

6. Fan Operation

20 PNEG-010 Vane Axial Fan

Approximate Hours of Fan Time to Change Bin Temperature

1. Bushels are rounded and approximate.

2. The hours required are based on clean grain. High moisture grain and grain containing fines or foreign material will require more time to complete the air change.

3. Not Recommended: Bins in the NR range, may require fan(s) of a different size to get the cool time into the accepted range.

4. Bins requiring more than 100 hours of aeration to totally change the temperature may require continuous aeration at about 1/10th CFM per bushel or some other acceptable method.

Fan Blade Removal and Installation

The fan blade is secured to the motor shaft by the use of a taper-lock bushing, motor shaft key and cap screws. The size, quantity and torque of cap screws required will depend on the model of the fan.

Fan Size HP

Bin Diameter Approximate 22' to Eave-Approximate Hours of Fan Time Required

Approximate 32' to Eave

18 21 24 27 30 33 36 42 48 36 42 48

1 73 79 90 NR NR NR NR NR NR NR NR NR

1.5 56 61 65 66 76 82 92 NR NR NR NR NR

3 44 51 52 57 63 69 78 93 NR NR NR NR

7 38 42 44 47 52 56 61 71 81 79 93 NR

10 35 37 41 42 45 49 53 62 71 72 82 92

15 30 32 35 39 40 42 45 54 63 62 70 80

Approximate BU 4500 6500 8500 11000 13500 16500 19500 27000 35500 28000 38500 50500

DANGERAlways disconnect and lock out power before working on or around fan.

CAUTION

Although the taper-lock method of retaining the blade onto the motor shaft is very simple and obvious, it is essential that the following points be read carefully and fully understood, as improper installation can result in serious or fatal injury caused by a loose, fast flying blade.

THREADED BUSHING HOLES: The threaded holes within the bushing are providedfor disassembly purposes only. Do not attempt to use these holes for re-assembly,as they will not allow the parts to become locked onto the shaft, thereby causing an extremely hazardous operating condition.

CLEARANCE HOLES: When re-assembling parts, the cap screws must be installedthrough the UNTAPPED CLEARANCE HOLES to cause the blade to be pulledforward onto the tapered bushing, thus locking the parts securely onto the motorshaft. Refer to Page 23 (under installation section) for assembly details.

NR

Page 21: Pneg-010 - Vane Axial Fan - WordPress.com · 8 PNEG-010 Vane Axial Fan Safety Alert Decals DC-1225 Stay clear of rotating blade. Blade could start automatically. Can cause serious

6. Fan Operation

PNEG-010 Vane Axial Fan 21

Removing the Fan Blade Assembly1. Lock out and tagout the main power to make sure the dryer cannot be started during servicing.

2. Remove the grill guard.

3. If there is a safety washer present, remove the bolt, lock washer and safety washer.

4. Remove the bolts from the unthreaded holes of the bushing. Do not use these bolts for bushing removal.

5. Using an allen wrench, undo the set screw (if present) and remove the key from the keyway.

6. Install grade 5 or stronger bolts into the threaded holes in the bushing and gradually apply torque to each bolt to loosen the bushing.

7. Remove the bushing and fan blade assembly.

Installing the Fan Blade Assembly1. Clean the motor shaft, key, bushing and the bore of the hub with a non-residual cleaner, such as

brake parts cleaner or electric parts cleaner. It is important that these mating surfaces be clean and dry and no grease or oil is present. The parts must be assembled dry for maximum friction.

2. Insert bolts into bushing holes and ensure the shoulder portion of the bolt is NOT protruding the hole.

3. Install the fan blade assembly onto the motor shaft.

4. Align the keyway in the bushing with the key and slide the bushing onto the motor shaft.

NOTE: Do not use excessive force to drive the bushing onto the shaft.

5. Align bushing and hub keyways with the key. Bushing should be flush with the end of the motor shaft.

6. Loosely install the bolts through the unthreaded holes in the bushing into the threaded holes of the hub.

7. Find the applicable torque for the bushing in the chart on Page 22. The bushing type is etched into the face of the bushing.

8. Torque the bushing gradually to evenly seat it inside the hub and onto the motor shaft. Set the torque wrench to 1/3 of the required torque setting and tighten each bolt in a circular pattern three (3) times. Increase the torque setting on the wrench to 2/3 of the required torque and tighten each bolt in a circular pattern three (3) times. Increase the setting on the torque wrench to the final required torque setting and tighten each bolt in a circular pattern three (3) times.

9. If there is a safety washer present, install the washer, lock washer and bolt.

10. Turn the fan blade assembly by hand to make sure there is freedom of movement and uniform clearance around the inlet.

11. Install the grill guard and turn ON the main power source.

CAUTIONDo not use any lubricant or thread locking compound during installation. The use of such products will cause improper bolt torque and will crack the fan hub.

Page 22: Pneg-010 - Vane Axial Fan - WordPress.com · 8 PNEG-010 Vane Axial Fan Safety Alert Decals DC-1225 Stay clear of rotating blade. Blade could start automatically. Can cause serious

6. Fan Operation

22 PNEG-010 Vane Axial Fan

Installing the Fan Blade Assembly (Continued)

12. Operate the fan for 30 minutes.

13. Stop the fan and lock out and tagout the main power to make sure the dryer cannot be started during servicing.

14. Remove the grill guard and re-tighten the bolts in a circular pattern one time at the final required torque setting.

15. Install the grill guard and turn ON the main power source.

Figure 6A Vane Axial Fan

Bushing Bolt ThreadBolt Torque

Foot - PoundsBushing Bolt Thread

Bolt Torque Foot - Pounds

JA 10-24 5 P-1 5/16"-18 13

G 1/4"-20 6 SK 5/16"-18 15

H 1/4"-20 6 SF 3/8"-16 23

SH 1/4"-20 8 Q-1 3/8"-16 29

SD 1/4"-20 9 R-1 3/8"-16 29

SDS 1/4"-20 9

CAUTIONDo not exceed the torque specifications listed on the bushing bolt torque chart. Exceeding the recommended torque will crack the fan hub.

Page 23: Pneg-010 - Vane Axial Fan - WordPress.com · 8 PNEG-010 Vane Axial Fan Safety Alert Decals DC-1225 Stay clear of rotating blade. Blade could start automatically. Can cause serious

6. Fan Operation

PNEG-010 Vane Axial Fan 23

Installing the Fan Blade Assembly (Continued)

Figure 6B Cutaway Drawing of Typical Propeller Installation

Figure 6C Cap Screw Arrangement for Disassembly

Figure 6D Cap Screw Arrangement for Resassembly

Cap screws installed through clearance holes of bushing. (See text on Page 22 for proper torque.)

Page 24: Pneg-010 - Vane Axial Fan - WordPress.com · 8 PNEG-010 Vane Axial Fan Safety Alert Decals DC-1225 Stay clear of rotating blade. Blade could start automatically. Can cause serious

24 PNEG-010 Vane Axial Fan

7. Fan Service

Fan Blade Inspection and Maintenance

Pre-season inspections should be done on the fan blade to look for the following:

1. Any debris (stalks, bees wings, mud, insects and insect nests) accumulated on the surfaces of the fan blade. Remove these items as they will likely disrupt airflow over the fan airfoils and can potentially cause vibration problems.

2. Inspect the fan blade for any broken, cracked or loose parts. Blade should NOT be operated with broken or loose parts. Contact dealer for determination of the repairs required.

Browning Taper-Lock Bushing Bolt Tightening Torque

Fan Motor

Removal and Installation

In the event of motor failure, remove the motor, as described and take it to the nearest Authorized Service Station. AUTHORIZED SERVICE STATIONS ARE THE ONLY PLACES THAT CAN PROVIDE MOTOR WARRANTY. Motor service and repair at other places will be at owner’s expense. If service station determines motor failure to be caused by faulty material or workmanship, repair will be under warranty when within the warranty period. Motor failure because of external causes will result in a charge to the owner for repair.

1. LOCK OUT THE MAIN POWER SUPPLY, then remove fan guard, venturi and blade as outlined earlier.

2. Open motor junction box cover and disconnect the motor lead wires from within the box.

NOTE: Tag or otherwise identify wires for ease of re-assembly.

3. Remove motor mount bolts. If there are any shims between the motor and its base, note their locations so they can be properly installed during re-assembly.

4. Disconnect the motor end of the motor conduit, if required, then carefully pull conduit and wires through hole in the motor junction box. Remove motor. If motor requires service, take it to an Authorized Service Station.

5. To re-install motor, slide onto motor base plate and replace shims (if required) between motor and base plate. Re-install motor mount bolts and washers and fully tighten them at this time. Re-install conduit and wires and carefully remake all electrical wiring connections.

NOTE: Make sure to install and tighten the blade in accordance with earlier instructions.

Bushing Size Hex Bolt Size Torque (inch. lbs.)

H 1/4"-20 x 3/4" 95

P 5/16"-18 x 1" 192

WARNING

Do not attempt to pull the flange of the bushing flush with the blade hub. A clearance of 1/8'' to 1/4'' must be maintained between bushing flange and blade hub surface. Blade will loosen and cause damage or injury.

Page 25: Pneg-010 - Vane Axial Fan - WordPress.com · 8 PNEG-010 Vane Axial Fan Safety Alert Decals DC-1225 Stay clear of rotating blade. Blade could start automatically. Can cause serious

7. Fan Service

PNEG-010 Vane Axial Fan 25

General Inspection

Inspect the motor at regular intervals, approximately every 500 hours of operation or every three (3) months, whichever occurs first. Keep the motor clean and the ventilation openings clear. The following steps should be performed at each inspection:

1. Check that the motor is clean. Check that the interior and exterior of the motor is free of dirt, oil, grease, water, etc. Oily vapor, paper pulp, textile lint, etc., can accumulate and block motor ventilation. If the motor is not properly ventilated, over heating can occur and cause early motor failure.

2. Check all electrical connectors to be sure that they are tight.

Lubrication and Bearings

Bearing grease will lose its lubricating ability over time, not suddenly. The lubricating ability of a grease (over time) depends primarily on the type of grease, the size of the bearing, the speed at which the bearing operates and the severity of the operating conditions. Good results can be obtained if the following recommendations are used in the maintenance program. Type of grease: A high grade ball or roller bearing grease should be used.

Recommended grease for standard service conditions:

1. Polyrex EM (Exxon Mobil)

Equivalent and compatible greases include:

1. Texaco polystar

2. Rykon premium #2

3. Pennzoil pen 2 lube

4. Chevron SRI

Lubrication Procedure

Be sure that the grease you are adding to the motor is compatible with the grease already in the motor.

With Grease Outlet Plug

1. Clean all grease fittings.

2. Remove grease outlet plug.

3. Add the recommended amount of grease.

4. Re-install grease outlet plug.

DANGER

Do not touch electrical connections before you first ensure that power has been disconnected. Electrical shock can cause serious or fatal injury. Only qualified personnel should attempt the installation, operation and maintenance of this equipment.

CAUTIONTo avoid damage to motor bearings, grease must be free of dirt.

Page 26: Pneg-010 - Vane Axial Fan - WordPress.com · 8 PNEG-010 Vane Axial Fan Safety Alert Decals DC-1225 Stay clear of rotating blade. Blade could start automatically. Can cause serious

7. Fan Service

26 PNEG-010 Vane Axial Fan

Without Grease Outlet Plug

This requires disassembly of the motor. Contact local motor shop for assistance.

Volume of Grease to Relubricate Bearings (Teaspoons)

Lubrication Intervals - Ball Bearing Motors

NEMA Frame Size

Up to 210 incl. 2

Over 210 to 280 incl. 3.9

Over 280 to 360 incl. 5.2

Over 360 to 449 incl. 13.4

Type of Annual Usage

1800 RPM - NEMA Frame Size 3600 RPM - NEMA Frame Size

Up to 280 incl.

Over 280 to 360 incl.

Over 360Up to 280

incl.Over 280 to

360 incl.Over 360

Continuous Normal Duty * 9500 Hrs 7400 Hrs 3500 Hrs 3600 Hrs 2200 Hrs 2200 Hrs

Continuous Severe Duty ** 4750 Hrs 3700 Hrs 1750 Hrs 1800 Hrs 1100 Hrs 1100 Hrs

Seasonal Service Motor(idle 6 months)

Lubrication at beginning of season and then follow the appropriate duty interval above.

* Clean, little corrosion with 40°C maximum temperature.

** Moderate dirt, corrosion with 50°C maximum temperature.

Average hours per month = 730.

Page 27: Pneg-010 - Vane Axial Fan - WordPress.com · 8 PNEG-010 Vane Axial Fan Safety Alert Decals DC-1225 Stay clear of rotating blade. Blade could start automatically. Can cause serious

PNEG-010 Vane Axial Fan 27

8. User Servicing Instructions and Troubleshooting

Important Information Regarding Fuse Replacement

This product employs overload protection (fuse). A blown fuse indicates an overload or short circuit situation. If the fuse blows, disconnect all power to the product. Replace the fuse as per the user servicing instructions (follow product marking for proper fuse rating) and check the product. If the replacement fuse blows, a short circuit may be present and the user should discontinue use of the product until customer service can be contacted for further assistance.

Fan Troubleshooting Chart

Symptom Possible Cause Solution

1. Fan does not run.

1. Blown fuse or breaker in disconnect switch.

1. To replace blown fuse, grasp centerof fuse securely and pull carefullyoutward to remove fuse from fuse holder.RISK OF FIRE. Replace fuse only withequally rated fuse shown on panel label.

2. Main power not turned ON.2. Turn power ON at all disconnects ahead of

the unit.

3. Defective wiring or loose connection.3. Follow wiring diagram and tighten any

loose connections.

4. Incorrect wire size.4. See wire size charts on Page 16 for proper

wire size and change if needed.

5. Overload kicked out. 5. Check manual reset, push in to reset.

6. Defective motor. 6. Replace motor.

7. Defective magnetic contactor. 7. Check the magnetic contactor.

2. Fan runs for a short period of time then shuts off.

1. Undersize wiring.1. Check to see that power supply wires

are the proper size, contact the local power company.

2. Low line voltage at the installation power failure.

2. Call power company after making sure wire size is correct.

3. Magnetic contactor malfunctioning. 3. Change magnetic contactor.

4. Defective start/stop button. 4. Replace necessary part.

5. Overload setting incorrect. 5. Adjust overload to proper setting.

3. Fan makes ticking noise.1. Fan blade hitting housing.

1. Stop fan and turn OFF power. Remove fan guard and check to see if fan blade is hitting the housing. Adjust motor or fan blade position to obtain proper clearance.

2. Motor bearing bad. 2. Replace motor bearing.

4. Fan vibrates.

1. Fan not level. 1. Level fan.

2. Fan has dirt deposit on blade. 2. Clean blade.

3. Motor shaft is bent. 3. Replace motor.

4. Blade not mounted properly on shaft. 4. Mount blade properly on shaft.

5. Blade out of balance. 5. Replace or have blade rebalanced.

Page 28: Pneg-010 - Vane Axial Fan - WordPress.com · 8 PNEG-010 Vane Axial Fan Safety Alert Decals DC-1225 Stay clear of rotating blade. Blade could start automatically. Can cause serious

8. User Servicing Instructions and Troubleshooting

28 PNEG-010 Vane Axial Fan

Fan Troubleshooting Flow Chart

Page 29: Pneg-010 - Vane Axial Fan - WordPress.com · 8 PNEG-010 Vane Axial Fan Safety Alert Decals DC-1225 Stay clear of rotating blade. Blade could start automatically. Can cause serious

PNEG-010 Vane Axial Fan 29

9. Parts List

12''-14'' Fan Parts

Ref #Part #

Description12" 0.75 HP 12'' 1 HP 14'' 1 HP

1 F-7359 F-7225 F-7230 VA Housing Assembly

2 - MTR-0145 MTR-0145 Motor 1 HP 1 PH 3400 RPM

2 FH-5579 - - Motor 1 HP 1 PH 3500 RPM

3 F-7124 F-7252 F-7301 GRP - VA Blade

4 F-7233 F-7233 F-7233 GRP - Safety Washer

5 F-7177 F-7177 F-7178 Grill Guard

6 S-3611 S-6606 S-6606 Flange Bolt 5/16"-18 x 3/4" ZN Grade 5

7 S-845 S-3611 S-3611 Flange Nut 5/16"-18 ZN YDP

8 S-6606 S-845 S-845 Flat Washer 5/16" USS SAE YDP Grade 2

Page 30: Pneg-010 - Vane Axial Fan - WordPress.com · 8 PNEG-010 Vane Axial Fan Safety Alert Decals DC-1225 Stay clear of rotating blade. Blade could start automatically. Can cause serious

9. Parts List

30 PNEG-010 Vane Axial Fan

18''-28'' Fan Parts

Ref #Part #

Description18'' 1.5 HP 18'' 3 HP 24'' 7 HP 24'' 10 HP 28'' 15 HP

1 FH-5535 FH-3660 F-7199 F-7199 F-7199 Split Taper Bushing

2 F-7179 F-7179 014-1042-2-W 014-1042-2-W 014-1043-0-W Grill Guard

3 F-7248 F-7248 F-7513 F-7513 F-7516 Fan Housing without Controls

3 N/A F-7510 F-7513 F-7513 F-7516 Fan Housing with Controls

4 F-7254 F-7255 F-6920 F-6921 F-6923 Blade Assembly

5 MTR-0147 MTR-0141 MTR-0142 MTR-0143 MTR-0144 230V 1 PH Motor

5 MTR-0002 MTR-0003 MTR-0088 MTR-0089 MTR-0085 230V/460V 3 PH Motor

5 FH-6592 FH-6593 FH-6594 FH-6595 FH-6596 575V 3 PH Motor

6 PR-331 PR-331 PR-331 PR-331 PR-331 Handle

7 FH-6972 FH-6972 C-8824 C-8824 C-8824 Junction Enclosure

7 N/A C-8803 C-8803 C-8803 C-8803 Control Enclosure

8 N/A N/A F-7316 F-7316 F-7317 Venturi (Yellow)

8 N/A N/A 069-1306-5 069-1306-5 069-1307-3 Venturi (Orange)

9 FH-7518 FH-7518 FH-7519 FH-7519 FH-7521 Control Enclosure Mount

Page 31: Pneg-010 - Vane Axial Fan - WordPress.com · 8 PNEG-010 Vane Axial Fan Safety Alert Decals DC-1225 Stay clear of rotating blade. Blade could start automatically. Can cause serious

PNEG-010 Vane Axial Fan 31

10. Wiring Diagrams

1. 1 Phase 230 Volt Schematic

2. 1 Phase 230 Volt Wiring Diagram and Parts

3. 3 Phase 230 Volt Schematic

4. 3 Phase 230 Volt Wiring Diagram and Parts

5. 3 Phase 460 Volt Schematic

6. 3 Phase 460 Volt Wiring Diagram and Parts

7. 3 Phase 575 Volt Schematic

8. 3 Phase 575 Volt Wiring Diagram and Parts

Page 32: Pneg-010 - Vane Axial Fan - WordPress.com · 8 PNEG-010 Vane Axial Fan Safety Alert Decals DC-1225 Stay clear of rotating blade. Blade could start automatically. Can cause serious

10. Wiring Diagrams

32 PNEG-010 Vane Axial Fan

1 Phase 230 Volt Schematic

Page 33: Pneg-010 - Vane Axial Fan - WordPress.com · 8 PNEG-010 Vane Axial Fan Safety Alert Decals DC-1225 Stay clear of rotating blade. Blade could start automatically. Can cause serious

10. Wiring Diagrams

PNEG-010 Vane Axial Fan 33

1 Phase 230 Volt Wiring Diagram and Parts

Ref # Part # Description

1 C-8707 Mounting Plate

2 E160-1137 Ground Lug

3 C-8718 Single Pole Fuse Block

4 C-8719 2A Slow Blow Fuse

5 C-8715 Fuse Puller

6 C-8716 ON/OFF Switch Assembly

7 056-1941-6 3 HP 230V 1 PH Contactor

7 056-2078-7 5 HP 230V 1 PH Contactor

7 056-1994-6 7.5 HP 230V 1 PH Contactor

7 056-2030-7 10 HP 230V 1 PH Contactor

7 056-2030-7 15 HP 230V 1 PH Contactor

8 056-1944-0 3 HP 230V 1 PH Overload

8 CH-1070 5 HP 230V 1 PH Overload

8 CH-1073 7.5 HP 230V 1 PH Overload

8 CH-1059 10 HP 230V 1 PH Overload

8 CH-1060 15 HP 230V 1 PH Overload

9 C-8717 Cable Tie

10 S-1158 Screw, TCSF #8-32 x 1/2" PHP ZN

Page 34: Pneg-010 - Vane Axial Fan - WordPress.com · 8 PNEG-010 Vane Axial Fan Safety Alert Decals DC-1225 Stay clear of rotating blade. Blade could start automatically. Can cause serious

10. Wiring Diagrams

34 PNEG-010 Vane Axial Fan

3 Phase 230 Volt Schematic

Page 35: Pneg-010 - Vane Axial Fan - WordPress.com · 8 PNEG-010 Vane Axial Fan Safety Alert Decals DC-1225 Stay clear of rotating blade. Blade could start automatically. Can cause serious

10. Wiring Diagrams

PNEG-010 Vane Axial Fan 35

3 Phase 230 Volt Wiring Diagram and Parts

Ref # Part # Description

1 C-8707 Mounting Plate

2 E160-1137 Ground Lug

3 C-8716 ON/OFF Switch Assembly

4 C-8718 Single Pole Fuse Block

5 C-8719 2A Slow Blow Fuse

6 C-8717 Cable Tie

7 C-8715 Fuse Puller

8 056-1949-9 3 HP 230V 3 PH Contactor

8 056-1969-7 5 HP 230V 3 PH Contactor

8 056-2078-7 7.5 HP 230V 3 PH Contactor

8 056-2078-7 10 HP 230V 3 PH Contactor

8 056-1994-6 15 HP 230V 3 PH Contactor

9 056-2022-4 3 HP 230V 3 PH Overload

9 056-1944-0 5 HP 230V 3 PH Overload

9 CH-1070 7.5 HP 230V 3 PH Overload

9 CH-1071 10 HP 230V 3 PH Overload

9 CH-1073 15 HP 230V 3 PH Overload

10 S-1158 Screw, TCSF #8-32 x 1/2" PHP ZN

Page 36: Pneg-010 - Vane Axial Fan - WordPress.com · 8 PNEG-010 Vane Axial Fan Safety Alert Decals DC-1225 Stay clear of rotating blade. Blade could start automatically. Can cause serious

10. Wiring Diagrams

36 PNEG-010 Vane Axial Fan

3 Phase 460 Volt Schematic

Page 37: Pneg-010 - Vane Axial Fan - WordPress.com · 8 PNEG-010 Vane Axial Fan Safety Alert Decals DC-1225 Stay clear of rotating blade. Blade could start automatically. Can cause serious

10. Wiring Diagrams

PNEG-010 Vane Axial Fan 37

3 Phase 460 Volt Wiring Diagram and Parts

Ref # Part # Description

1 C-8707 Mounting Plate

2 C-8715 Fuse Puller

3 C-8716 ON/OFF Switch Assembly

4 C-8719 2A Slow Blow Fuse

5 C-8720 Class CC Slow Blow Fuse

6 E160-1137 Ground Lug

7 C-8717 Cable Tie

8 056-2110-7 Side Mount Contact

9 S-1158 Screw, TCSF #8-32 x 1/2" PHP ZN

10 056-1948-1 3 HP 460V 3 PH Contactor

10 056-1949-9 5 HP 460V 3 PH Contactor

10 056-1949-9 7.5 HP 460V 3 PH Contactor

10 056-1969-7 10 HP 460V 3 PH Contactor

10 056-2078-7 15 HP 460V 3 PH Contactor

11 CH-1053 3 HP 460V 3 PH Overload

11 CH-1054 5 HP 460V 3 PH Overload

11 056-1971-3 7.5 HP 460V 3 PH Overload

11 056-1944-0 10 HP 460V 3 PH Overload

11 CH-1070 15 HP 460V 3 PH Overload

12 C-8711 460V 3 PH Transformer

Page 38: Pneg-010 - Vane Axial Fan - WordPress.com · 8 PNEG-010 Vane Axial Fan Safety Alert Decals DC-1225 Stay clear of rotating blade. Blade could start automatically. Can cause serious

10. Wiring Diagrams

38 PNEG-010 Vane Axial Fan

3 Phase 575 Volt Schematic

Page 39: Pneg-010 - Vane Axial Fan - WordPress.com · 8 PNEG-010 Vane Axial Fan Safety Alert Decals DC-1225 Stay clear of rotating blade. Blade could start automatically. Can cause serious

10. Wiring Diagrams

PNEG-010 Vane Axial Fan 39

3 Phase 575 Volt Wiring Diagram and Parts

Ref # Part # Description

1 C-8707 Mounting Plate

2 C-8715 Fuse Puller

3 C-8716 ON/OFF Switch Assembly

4 C-8719 2A Slow Blow Fuse

5 C-8720 Class CC Slow Blow Fuse

6 E160-1137 Ground Lug

7 C-8717 Cable Tie

8 056-2110-7 Side Mount Contact

9 S-1158 Screw, TCSF #8-32 x 1/2" PHP ZN

10 056-1948-1 3 HP 575V 3 PH Contactor

10 056-1949-9 5 HP 575V 3 PH Contactor

10 056-1942-4 7.5 HP 575V 3 PH Contactor

10 056-1969-7 10 HP 575V 3 PH Contactor

10 056-1969-7 15 HP 575V 3 PH Contactor

11 CH-1052 3 HP 575V 3 PH Overload

11 CH-1054 5 HP 575V 3 PH Overload

11 056-2022-4 7.5 HP 575V 3 PH Overload

11 056-1971-3 10 HP 575V 3 PH Overload

11 056-1944-0 15 HP 575V 3 PH Overload

12 C-8712 575V 3 PH Transformer

Page 40: Pneg-010 - Vane Axial Fan - WordPress.com · 8 PNEG-010 Vane Axial Fan Safety Alert Decals DC-1225 Stay clear of rotating blade. Blade could start automatically. Can cause serious

40 PNEG-010 Vane Axial Fan

NOTES

Page 41: Pneg-010 - Vane Axial Fan - WordPress.com · 8 PNEG-010 Vane Axial Fan Safety Alert Decals DC-1225 Stay clear of rotating blade. Blade could start automatically. Can cause serious

PNEG-010 Vane Axial Fan 41

11. Warranty

GSI Group, LLC Limited WarrantyThe GSI Group, LLC (“GSI”) warrants products which it manufactures to be free of defects in materials and workmanship under normal usage and conditions for a period of 12 months after sale to the original end-user or if a foreign sale, 14 months from arrival at port of discharge, whichever is earlier. The end-user’s sole remedy (and GSI’s only obligation) is to repair or replace, at GSI’s option and expense, products that in GSI’s judgment, contain a material defect in materials or workmanship. Expenses incurred by or on behalf of the end-user without prior written authorization from the GSI Warranty Group shall be the sole responsibility of the end-user.

Warranty Extensions:The Limited Warranty period is extended for the following products:

GSI further warrants that the portable and tower dryer frame and basket, excluding all auger and auger drive components, shall be free from defects in materials for a period of time beginning on the twelfth (12th) month from the date of purchase and continuing until the sixtieth (60th) month from the date of purchase (extended warranty period). During the extended warranty period, GSI will replace the frame or basket components that prove to be defective under normal conditions of use without charge, excluding the labor, transportation, and/or shipping costs incurred in the performance of this extended warranty.

Conditions and Limitations:THERE ARE NO WARRANTIES THAT EXTEND BEYOND THE LIMITED WARRANTY DESCRIPTION SET FORTH ABOVE. SPECIFICALLY, GSI MAKES NO FURTHER WARRANTY OF ANY KIND, EXPRESS OR IMPLIED, INCLUDING, WITHOUT LIMITATION, WARRANTIES OF MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE OR USE IN CONNECTION WITH: (I) PRODUCT MANUFACTURED OR SOLD BY GSI OR (II) ANY ADVICE, INSTRUCTION, RECOMMENDATION OR SUGGESTION PROVIDED BY AN AGENT, REPRESENTATIVE OR EMPLOYEE OF GSI REGARDING OR RELATED TO THE CONFIGURATION, INSTALLATION, LAYOUT, SUITABILITY FOR A PARTICULAR PURPOSE, OR DESIGN OF SUCH PRODUCTS.

GSI shall not be liable for any direct, indirect, incidental or consequential damages, including, without limitation, loss of anticipated profits or benefits. The sole and exclusive remedy is set forth in the Limited Warranty, which shall not exceed the amount paid for the product purchased. This warranty is not transferable and applies only to the original end-user. GSI shall have no obligation or responsibility for any representations or warranties made by or on behalf of any dealer, agent or distributor.

GSI assumes no responsibility for claims resulting from construction defects or unauthorized modifications to products which it manufactured. Modifications to products not specifically delineated in the manual accompanying the equipment at initial sale will void the Limited Warranty.

This Limited Warranty shall not extend to products or parts which have been damaged by negligent use, misuse, alteration, accident or which have been improperly/inadequately maintained. This Limited Warranty extends solely to products manufactured by GSI.

Prior to installation, the end-user has the responsibility to comply with federal, state and local codes which apply to the location and installation of products manufactured or sold by GSI.

Product Warranty Period

AP Fans and Flooring

Performer Series Direct Drive Fan Motor 3 Years * Warranty prorated from list price:

0 to 3 years - no cost to end-user

3 to 5 years - end-user pays 25%

5 to 7 years - end-user pays 50%

7 to 10 years - end-user pays 75%

** Warranty prorated from list price:

0 to 3 years - no cost to end-user

3 to 5 years - end-user pays 50%

† Motors, burner components and moving parts not included. Portable dryer screens included. Tower dryer screens not included.

All Fiberglass Housings Lifetime

All Fiberglass Propellers Lifetime

Cumberland Feeding/Watering Systems

Feeder System Pan Assemblies 5 Years **

Feed Tubes (1-3/4" and 2.00") 10 Years *

Centerless Augers 10 Years *

Watering Nipples 10 Years *

Grain Systems Grain Bin Structural Design 5 Years

Grain SystemsFarm FansZimmerman

Portable and Tower Dryers 2 Years

Portable and Tower Dryer Frames and Internal Infrastructure †

5 Years

9101239_1_CR_rev7.DOC (revised July 2009)

Page 42: Pneg-010 - Vane Axial Fan - WordPress.com · 8 PNEG-010 Vane Axial Fan Safety Alert Decals DC-1225 Stay clear of rotating blade. Blade could start automatically. Can cause serious

This equipment shall be installed in accordance with the current installation codes and applicable

regulations, which should be carefully followed in all cases. Authorities having jurisdiction should be

consulted before installations are made.

GSI Group 1004 E. Illinois St.

Assumption, IL 62510-0020 Phone: 1-217-226-4421

Fax: 1-217-226-4420 www.gsiag.com

Copyright © 2014 by GSI GroupPrinted in the USA CN-310824

GSI is a worldwide brand of AGCO Corporation.