PMAC801 Motor Protection Controller Instruction Manual...
Transcript of PMAC801 Motor Protection Controller Instruction Manual...
PMAC801 Motor Protection Controller Instruction Manual
V2.0
Zhuhai Pilot Electronics Co., Ltd.
Address: Building A3, Chuangruan Science & Technology Park, First Chuangxin Road, High-tech
Zone, Tangjia, Zhuhai, Guangdong, P.R. China
Post Code: 519080
Tel: +86-756-3629699/673
Fax: +86-756-3629600/700 INSTRUCTION
The objective of this instruction manual is to provide the technical and operation information of PMAC801.
This manual should be studied carefully before installing, parameterzing or operating the motor protection
controller. It’s expected that the users have a basic knowledge of physical and electrical fundamentals, electrical
wiring practices and electrical components.
This manual can’t include all changing of details and equipments, and can’t provide all occasional things about
installation, operation and maintenance. If users need more details information or have special questions,
please contact with us.
TABLE of CONTENTS
TABLE OF CONTENTS
1. DESCRIPTION...........................................................................................................................................................1
2. TECHNICAL PARAMETERS..................................................................................................................................2
2.1 SYSTEM PARAMETERS .................................................................... 2
2.2 SYMBOL INSTRUCTION ................................................................... 2
2.3 RANGE OF MEASUREMENT AND PRECISION.................................................. 3
2.4 EMC ................................................................................... 3
2.5 ENVIRONMENTAL CONDITIONS ............................................................ 3
3. SIZE AND INSTALLATION.....................................................................................................................................4
3.1 SIZE OF MAIN MODULE................................................................... 4
3.2 SIZE OF DISPLAY MODULE AND INSTALLATION............................................... 5
3.3 SIZE OF CT ............................................................................. 6
3.4 SIZA OF EXTENDED MODULE .............................................................. 7
3.5 SIZE OF POWER SUPPLY MODULE .......................................................... 8
3.6 CONNECTION SKETCH MAP................................................................ 8
4. FUNCTION CONFIGURATION............................................................................................................................10
5. CONTROL AND OTHER FUNCTIONS ...............................................................................................................12
5.1 RUN STATES OF MOTOR ................................................................. 12
5.2 OPERATION PERMISSION ................................................................ 12
5.3 PROTECTION/CONTROL.................................................................. 12
5.4 FAULT INFORMATION OUTPUT ............................................................ 12
5.5 POWER DIAGNOSIS ..................................................................... 12
5.6 RESET ................................................................................ 13
5.7 EMERGENT STOP ....................................................................... 13
5.8 RESTART FUNCTION..................................................................... 13
6. DISPLAY AND KEY FUNCTIONS ........................................................................................................................14
6.1 LEDS.................................................................................. 14
6.2 KEYPADS OPERATION ................................................................... 15
6.3 DISPLAY PORTS:........................................................................ 15
6.4 DISPLAY CONTENTS..................................................................... 15
7. TERMINALS AND OTHERS .................................................................................................................................18
7.1 MAIN MODULE ......................................................................... 18
7.2 CT MODULE............................................................................ 20
7.3 EXTENDED DIGITAL MODULE ............................................................. 22
7.4 EXTENDED ANALOG MODULE ............................................................. 24
7.5 POWER SUPPLY MODULE................................................................. 25
8. PROTECTION FUNCTIONS .................................................................................................................................26
8.1 PROTECTION VALUES ................................................................... 26
8.2 PROTECTION EXPLANATION .............................................................. 27
TABLE of CONTENTS
9. SYSTEM PARAMETERS .......................................................................................................................................34
10. DI AND DO CONFIGURATION ..........................................................................................................................37
11. TYPICAL CONNECTIONS ..................................................................................................................................41
11.1 PROTECTION MODE .................................................................... 41
11.2 DIRECT STARTER ...................................................................... 42
11.3 REVERSING DIRECT STARTER ........................................................... 43
11.4 STAR/DELTA STARTER .................................................................. 44
11.5 LOOP-OPEN STAR/DELTA STARTER WITH 3 RELAYS ......................................... 45
11.6 LOOP-CLOSE STAR/DELTA STARTER WITH 3 RELAYS ........................................ 46
11.7 AUTOTRANSFORMER STARTER ........................................................... 47
11.8 LOOP-OPEN AUTOTRANSFORMER STARTER WITH 3 RELAYS .................................. 48
11.9 LOOP-CLOSE AUTOTRANSFORMER STARTER WITH 3 RELAYS ................................. 49
11.10 BREAKE DIRECTOR ................................................................... 50
APPENDIX A BASIC SETTING AND EVER-PRESENT QUESTIONS ...............................................................51
APPENDIX B ORDER INFORMATION ..................................................................................................................52
DESCRIPTION
1
1. DESCRIPTION
PMAC801 intelligent motor protection controller is designed on the basis of PMAC800. And it is used to control
the contactor in the AC circuit (rated voltage up to 660V). It integrates the measurement, protection, and
control functions. It replaces the dispersive equipments in MCC and predigests the control circuit of motor to
improve the reliability.
PMAC801 uses the design of module framework. It has the characteristics of small size, compact configuration,
and extendibility. It is composed of main module, current measurement module (CT module), display module, extended digital module, extended analog module, and power supply module. The basic components are main module and CT module. The size of CT module is different in several
current levels. The other modules can be selected according to the requirements.
Features:
■ Use module framework. Several modules can be selected flexibly.
■ PMAC801 provides 17 protection functions such as start overtime protection, overload
protection, overcurrent protection, phase failure protection, current unbalance
protection, earth fault/leakage current protection, short circuit protection,
underload protection, external fault protection, overvoltage protection,
undervoltage protection, under power protection, phase sequence error
protection, EEx e overload protection, temperature (PTC/NTC) protection, analog
input protection.
■ Provides measurements of three phases current, three phase /phase voltage, zero phase sequence current,
active power, reactive power, power factor, frequency, and active energy measurements.
■ Provides protection, direct starter, reversing direct starter, star/delta starter, and
autotransformer starter etc motor starting control modes.
■ Main module provides 9 DIs for start, stop and reset etc. signals input. If more DIs are needed, an
extended digital module can be selected. Some of the DIs are programmable.
■ Main module provides 5 DOs to meet varies of starting control modes and protection action. If more DOs
are needed, an extended digital module can be selected. Some of the DOs are programmable.
■ Provides 4~20mA analog output for DCS.
■ 8 trip events can be stored in non-volatile memory.
■ Through an extended analog module, 2 analog input or 1 analog and 1 hot resistance input can be added.
■ Small size and compact configuration.
■ Easy installation. Proper for 35mm DIN rail.
TECHNICAL PARAMETERS
2
2. TECHNICAL PARAMETERS
2.1 SYSTEM PARAMETERS
2.1.1 Rated voltage of Motor: AC 380V or 660V.
2.1.2 Rated current:
Rated current of motor Rated current of controller
0.5A~2A 2A
1.6A~6.3A 6.3A
6.3A~25A 25A
25A~100A 100A
100A~250A 250A
250A~500A 500 A
500A~820A 820A
Note: Users can choose proper type of controller for motors according to the form above.
2.1.3 Power supply: 85~265V AC or DC.
2.1.3 Type of status input: Controller provides internal low voltage power supply for status circuit.
2.1.4 Output capacity of control relay:
AC type: 250V/12A, 380V/5A.
DC type: 220VDC/3A.
Output capacity of signal relay: 250VAC/5A or 30VDC/5A.
Note: PMAC801 has 5 relays, the front 3 are control relays, and the others are signal relays.
2.2 SYMBOL INSTRUCTION In the manual and display module, some symbols are used. The following list shows their definition.
Symbol Definition Symbol Definition
Ie Rated current of motor I un Current unbalance rate
Ue Rated voltage of motor Uab, Ubc, Uca Three phase/phase voltage
Ia, Ib, Ic Phase current Ia, Ib, Ic Uav Average phase/phase voltage
Iav Average current f Frequency
Ig Neutral current PF Power factor
I△ Leakage current P Active power
Q Reactive power I△n
Primary rated current of leakage
current CT E Active energy
TECHNICAL PARAMETERS
3
2.3 RANGE of MEASUREMENT and PRECISION
2.4 EMC
Electrostatic discharge EN 61000-4-2, Level 3
Electromagnetic field immunity EN 61000-4-3, Level 3
Fast transient/burst immunity EN 61000-4-4, Level 4
Surge immunity EN 61000-4-5, Level 3
Conducted Emission EN 55022, Class B
Radiated Emission EN 55022, Class B
2.5 ENVIRONMENTAL CONDITIONS
Ambient temperature of work -10~+55℃
Ambient temperature of storage -25~+70℃
Humidity ≤95%
Item Range Precision Item Range Precision
10%~200% ±0.5% Current
200%~800% ±3% Power factor 0~1 ±1%
Leakage
current 10%~100% I△n ±1% Active power 0~600.0KW ±2%
PTC/NTC 10R~10K ±5% Active energy 99,999,999.9kWh ±2%
Voltage 50%~150%Ue ±0.5% Analog output 4mA~20mADC ±2%
Frequency 45HZ~65HZ ±1% Analog input 4mA~20mADC ±2%
SIZE and INSTALLATION
4
3. SIZE and INSTALLATION
3.1 SIZE of MAIN MODULE
Picture 3-1 Front, side, and planform
The main module can be installed on the DIN rail wide 35mm.
SIZE and INSTALLATION
5
3.2 SIZE of DISPLAY MODULE and INSTALLATION
Picture 3-2 Front, side, and planform
Picture 3-3 Installation sketch map
SIZE and INSTALLATION
6
3.3 SIZE of CT
Picture 3-4 Front, side, and planform of CT (Ie <= 100A)
The CT can be installed on the DIN rail wide 35mm. 5.5mm
40
74
172
182
196
3× 35
38
2×R3mm
(OUT)green*(OUT)yellow* red*(OUT)
black(OUT)
Yellow * Green * Red *
BA C
12 29
56 56mm mm
mm
mm
mm
mm
mm
mmmm
mm
mm
Picture 3-5 Size of CT (100A < Ie<= 250A)
The CT can be installed in the switchgear and controlgear with screws.
The yellow, green, red lines from the CT indicate the phase current Ia, Ib, Ic.
SIZE and INSTALLATION
7
Brown Blue
mmmm
mm mm
mm
mm
Picture 3-6 Size of CT (500A or 820A)
3.4 SIZE of EXTENDED MODULE
Picture 3-7 Front, side, and pictorial
The extended module can be installed on the DIN rail wide 35mm.
SIZE and INSTALLATION
8
3.5 SIZE of POWER SUPPLY MODULE
Picture 3-8 Front, side, and pictorial
The module can be installed on the DIN rail wide 35mm.
3.6 CONNECTION SKETCH MAP
Picture 3-9 Connection of main module and display module
SIZE and INSTALLATION
9
Picture 3-10 Connection of main module, extended digital module, extended analog module and display
module
The special connection cables will be provided with the modules.
FUNCTION CONFIGURATION
10
4. FUNCTION CONFIGURATION
Configuration
Basic Optional
Start overtime √
Overload √
Overcurrent √
Phase failure √
Current unbalance √
Short circuit √
Earth fault √
Underload √
External fault √
Leakage current √
Overvoltage
Undervoltage
Under power
Phase sequence error
√
(Voltage
function)
EEx e overload √
Temperature (PTC/NTC) √(Extended
analog module)
Protection
Analog input √(Extended
analog module)
Protection mode
Direct starter
Reversing direct starter (Rev_DS)
Star/delta starter with 2 relays (S/D Starter)
Loop-open star/delta starter with 3 relays
(S/D_3R_Open)
Loop-close star/delta starter with 3 relays
(S/D_3R_Close)
Autotransformer starter with 2 relays
(Autotf starter)
Loop-open autotransformer starter with 3 relays
(Autotf_3R_Open)
Loop-close autotransformer starter with 3 relays
(Autotf_3R_Close)
Motor starting
control mode
Breaker direct starter
√
(The mode can
be set.)
Protocol:MODBUS-RTU √ Communication
Protocol:PROFIBUS-DP or The other Modbus-RTU √
FUNCTION CONFIGURATION
11
9 DIs have different configurations under different
motor starting control modes; √
DI Extended digital module can provide Max 11 DI.
√(Extended
digital module)
5 DOs have different configurations under
different motor starting control modes; √
DO Extended digital module can provide Max 4 DO
√(Extended
digital module)
Analog output 4~20mA analog output; Analog parameter can be
programmed. √
Analog input Extended analog module can provide Max 2 route
of 4~20mA analog input.
√(Extended
analog module)
Three phases current
Neutral/Leakage current
Current unbalance rate
√
Measurements
Three phase/phase voltage
Frequency
Power factor
Active power
Reactive power
Active energy
PTC/NTC
√
Trip events 8 trip events including the trip reasons and the
trip time can be stored. √
Statistic
information
Total running time
Total stopped time
Total stop operation times
Total trip times
√
Restart function In case of a voltage dip, motor can be restart after
the voltage recovery. √
CONTROL and OTHER FUNCTIONS
12
5. CONTROL and OTHER FUNCTIONS
5.1 RUN STATES OF MOTOR PMAC801 divides motor running process into five status in order to provide perfect protection for motors:
“Ready”: in this state, motor can be started immediately.
“Starting”: From motor start to operate till running smoothly
“Running”: Motor running smoothly.
“Stopping”: Motor start to run till hot capacitor decrease to 15% of rated after receive stop command.
“Stopped”: After its hot capacity less than 15% of rated, the controller indicates that the motor comes into
stopped state. In this state, if there isn’t fault information of motor, the run state will be changed from stopped
state to ready state automatically. If there is fault information of motor, the state won’t be changed, and the
controller doesn’t implement start command. If a reset signal is given to the controller, the fault information
will be eliminated. Stopped state is finished and ready state comes.
5.2 OPERATION PERMISSION
Motor can be controlled through display module, remote DI or communication respectively.
Local control means that only commands from the keypads of display module are active.
Remote DI control means that only commands from DIs are active.
Remote communication control means that only commands from communication are active.
Operation permission of the controller can be set as local or remote via DI6. If status of DI6 is open, it means
local permission. If DI6 is closed, permission will be changed to remote DI. Through communication software,
permission can be changed from remote DI to communication.
Under protection mode there isn’t the difference of operation permission and only reset command is active.
5.3 PROTECTION/CONTROL Relays in controller have double functions of control and protection.
Via keypads, DI or communication, motor can be started and stopped normally.
When a fault takes place and the corresponding protection action mode is trip, controller will send signal to the
control relay, and trip will take place. The motor will be stopped. The reason of trip can be got from display
module and communication software.
There is an overflow relay in the controller, when the current of motor is bigger than the cut ability of contactor,
the relay will give a pulse to breaker to stop motor.
5.4 FAULT INFORMATION OUTPUT PMAC801 provides a relay output for fault information. Its contact is open normally. When alarm or trip
protection takes place, the contact will be closed. After the fault is eliminated, the contact is opened again.
5.5 POWER DIAGNOSIS PMAC801 provides a relay for power diagnosis output. Its contact is closed normally. When PMAC801 is
powered on, the contact will be opened. And if PMAC801 is powered off, the contact returns to be closed.
CONTROL and OTHER FUNCTIONS
13
5.6 RESET If PMAC801 stopped the motor because of the motor’s fault, when the motor comes into stopped state, the
controller should be reset to clear fault indication before restarting motor. Reset operation can be implemented
via reset keypad of display module, DI4 of controller or communication.
Reset operation can clear hot capacity. If user needs to restart motor peremptorily, you don’t need to wait until
motor comes into stopped state; when motor is in stopping state, users pressing reset key can clear hot
capacity and fault information to make motor come to ready state.
Note: In order to avoid starting a hot motor, please don’t reset the controller in motor’s stopping state, unless
emergency.
5.7 EMERGENT STOP
PMAC801 provides an emergent stop operation input. If the input is active, the motor will be stopped
immediately and hot capacity will be cleared at the same time. Motor won’t be allowed to start unless the input
is eliminated.
5.8 RESTART FUNCTION
In case of a voltage dip, PMAC801 will restart the motor in certain cases according to the length of the dip, after
the voltage restores. The function needs the power supply module to ensure the controller works for a period
of time after the voltage dips. In the period of time, if the voltage can’t restore, the restart function will be
noneffective.
DISPLAY and KEY FUNCTIONS
14
6. DISPLAY and KEY FUNCTIONS
The main function of the display module include: displaying measurement values and fault information, setting
parameters and controlling motor.
A special cable can connect the display module and the main module. If the main module is powered on, the
display module will be powered on.
The display module uses a 2 X 7 font LCD. After the module is powered on, its backlight will be turn on for 10s.
If keypads operation takes place, the backlight will be turn on for 10s again.
6.1 LEDs Display module has 5 LEDs ”Start”, “Run”, ”Alarm”, “Trip” and “Communication”.
Start:
Run:
Alarm:
Trip:
State Definition
OFF No starting state
ON Starting state
State Definition
OFF No running state
ON Running state
State Definition
OFF No alarm state
ON Alarm
State Definition
OFF Not trip state
ON Trip
DISPLAY and KEY FUNCTIONS
15
COMMUNICATION:
6.2 KEYPADS OPERATION
Display module has 2 groups of keypads. One group is control keypads, and the other is set keypads.
Control keypads: “Start A”: Start motor in direction CW. “Start B”: Start motor in direction CCW. “Stop”: Stop motor. “Reset”: In the stopping or stopped state, pressing the key 2s can eliminate fault information..
Set keypads: “←”: Switch the display interface and the setting interface to the control interface, or return to the previous
menu. “↑”: Switch display interface or increase setting value. “↓”: Switch display interface or decrease setting value.
“ ”: Enter button or press for 3s. Interface will switch to setting interface
6.3 PORTS:
There are two ports in the display module. The port in the front is reserved for debugging. Through a special
cable, the controller can communicate with PC.
The port in the back is used to connect with main module or extended module.
6.4 DISPLAY CONTENTS The display module has three kinds of operation modes: motor control mode, read mode and setting
mode.
Motor control mode:
After the display module is powered on, the default operation mode is the control mode.
Under the control mode interface, if the run state of motor is “Ready”, the motor starting control mode will be
displayed instead. If the run states of motor are “Starting”, ”Running”, ”Stopping”, or “Stopped”, characters
“Starting”, ”Running”, ”Stopping”, or “Stopped” will be displayed separately.
If the operation permission is local, under the control mode, operating keypads of the display module can start,
stop and reset motor.
Operating “←” can switch the other modes to the control mode. If there is no operation on the keypads for 1
minute, the modes return to the control mode automatically.
Read mode:
Pressing any of set keypads shortly can switch the control mode to the read mode.
State Definition
OFF No communication state
Flash Communication is normal.
ON Communication is abnormal.
DISPLAY and KEY FUNCTIONS
16
Under the read mode interface, values of three phases of current, zero phase sequence/leakage current,
current unbalance rate, state of DI and DO, hot resistance, three phase/phase voltage, power, frequency,
power factor, active energy, last stop reason, operation permission, trip events, statistic information can be
inquired through operating “↑” or “↓” keypads.
I a 0.0 AI b 0.0 A
I c 0.0 AI g 0.0 A
Unbalance 0.0 %
DI123456789 - - - - - - - - -
DO 12345 - - - - +
Uab 0.0 V
Uca 0.0 V
R 0
F 0.00 HzPF 0.0 %
P 0.00 kWQ 0.00 kvar
E 0.0 kWh
Stop reason Local
Permission Local
Trip events
Statistic
No.1
No.8 Trip reason overload
2007-02-01 08:23:24
Total running t 0 h
Total stopped t 0 h
Stop times 0
Trip times 0
Ubc 0.0 V
For state of DI/DO, “-” means there is no digital signal inputs or relay output. If there is digital signal input or
relay output, the corresponding “-”changes to be “+”.
The display items correspond to the function configuration of the controller.
DISPLAY and KEY FUNCTIONS
17
Setting mode:
Pressing “ ” for 3s can switch the other modes to the setting mode.
Under the setting mode interface, varies of protection and system parameters can be set. Operating “↑” or
“↓”can switch the setting items. Pressing “ ” can switch the current degree item to the sub degree item or
make the current item into programmable state. If “ ” appears, the parameter can be programmed. If a
parameter can be programmed, pressing “↑” or “↓” can modify the value up and down, pressing for long
time can accelerate the modification. Pressing “ ” can confirm the modification.
Only under the ready state of the motor, the modification is acceptable.
Protection Setting
System Setting
Start Overtime Overload Overcurrent Phase Failure ↙ ↓ ↓ ↓
Unbalance Short Circuit
UnderloadTemperature
Rated current
100A
CT
1
Earth/Leakage
Earth 1000mA
↙
↓↓
↓↓↓↓
↓
↓
Overvoltage↓
↓
Baudrate 1
9600
↓↓↓ ↓
↓
↓Underpower
↓Phase failure
↓
Undervoltage
Address
1
↓
↓EExe Overlaod
↓
Earth/Leakage
↓
↓
Analog input External Fault
Rated voltage
380V
8.0 Ie
Cut abilityControl Mode
Direct starter
Analog type
Ia
Analog multiple
1
Baudrate 2
9600
↓Feedback
Disabled
Restart
↓
↓
↓
↓↓
↓
↓
↓
↓
↓ ↓
↓ ↓
↓
↓
↓
↓↓↓
↓ ↓ ↓ ↓ ↓
↓↓↓↓
↓
↓
↓
Rated power
52.58 kW
↓
↓
Programmable DI↓
↓
The display items correspond to the function configuration of the controller.
TERMINALS and OTHERS
18
7. TERMINALS and OTHERS
7.1 MAIN MODULE
LEDs:
OFF Lighten Flicker
Run No power Ready The motor is started.
Com No communication - Communication is built with display module,
extended module, or PC.
Fault No fault Trip Alarm
The DB9 marked with Profibus – DP is the port for profibus network.
The RJ45 marked with External port is for connection with the display module or extended module.
Terminals:
No. Definition Remark Initialization
1 DC Common terminal of DIs -
2 DI1 DI1 -
3 DI2 DI2 -
4 DI3 DI3 -
5 DI4 DI4 -
6 DI5 DI5 -
7 DI6 DI6 -
8 DI7 DI7 -
TERMINALS and OTHERS
19
9 DI8 DI8 -
10 DI9 DI9 -
11 IA Phase A current -
12 IB Phase B current -
13 IC Phase C current -
14 IN Common Current -
15 RS1+ RS485+/1 -
16 RS1- RS485-/1 -
17 SHLD RS485 shield -
18 RS2+ RS485+/2 -
19 RS2- RS485-/2 -
20 UA Phase A voltage -
21 - - -
22 UB Phase B voltage -
23 - - -
24 UC Phase C voltage -
25 Ln1 Input + of leakage current -
26 Ln2 Input - of leakage current -
27 NA+ Output+ of 4~20mA analog -
28 NA- Output- of 4~20mA analog -
29 R11 DO1 Normally open
30 R12/R21 Common terminal of DO 1 & 2 -
31 R22 DO2 Normally open
32 R31
33 R32 DO3 Normally open
34 R41
35 R42
R41, R42 (Normally close)
36 R43
DO4
R43, R42 (Normally open)
37 R51
38 R52 DO5 Normally close
39 L/+ Power supply + -
40 N/- Power supply - -
41 FG Ground -
Note:
1. The inputs of phase current should be connected with the special CT module provided. 5A or 1A input isn’t
allowed.
2. 1 extended digital module and 1 extended analog module can be connected with main module at the same
time.
TERMINALS and OTHERS
20
7.2 CT MODULE CT (Ie <= 100A)
Primary side:
L1: phase A current
L2: phase B current
L3: phase C current
Terminals of secondary side: Definition Remark
IA Output of phase A current
IB Output of phase B current
IC Output of phase C current
IN Common current
Connection:
The terminals of secondary side should be connected with the corresponding terminals in the main module
with cables. The length of the cables should be limited in 1m.
TERMINALS and OTHERS
21
CT (Ie <= 250A)
(OUT)Green*(OUT)Yellow* Red*(OUT)
Black(OUT)
Yellow * Green * Red *
BA C
Primary side
Secondary side
Connection: The yellow, green, red lines of secondary side from the CT indicate the phase current Ia, Ib, Ic. The black line
is common line. They should be connected with the corresponding terminals in the main module.
CT (500A or 820A)
Connection:
The CT (500A or 820A) is separate. Three phases current need three CTs. If the primary lines are transited from
A to B, the brown lines of the three CTs should be connected with the corresponding current terminals in the
main module, and all the three blue lines should be connected with the common current terminal in the main
module.
Brown * Blue
Secondary side
Primary side
TERMINALS and OTHERS
22
7.3 EXTENDED DIGITAL MODULE
LED:
Run
The two RJ45 ports are used to connect the extended module and the main module. The functions of them
are identical.
ED1: Provides 4 DIs and 4 DOs.
Terminals:
No. Definition Remark Initialization
1 R61 DO6
2 R62/R71 Common terminal of DO 6 & 7 Normally open
3 R72 DO7 Normally open
4 DI10 DI10 -
5 DI11 DI11 -
6 DI12 DI12 -
7 - - -
8 DC1 Common terminal of DIs -
9 DI13 DI13 -
State Definition
OFF No power
Lighten Communication isn’t built.
Flicker Communication is built with main module.
TERMINALS and OTHERS
23
10 R81 DO8
11 R82/R91 Common terminal of DO 8 & 9 Normally open
12 R92 DO9 Normally open
ED2: Provides 8 DIs and 2 DOs.
Terminals: No. Definition Remark Initialization
1 DI10 DI 10 -
2 DI11 DI 11 -
3 DI12 DI 12 -
4 DI13 DI 13 -
5 DI14 DI 14 -
6 DI15 DI 15 -
7 DI16 DI 16 -
8 DI17 DI 17 -
9 DC1 Common terminal of DIs -
10 R61 DO6
11 R61/R71 Common terminal of DO 6 & 7 Normally open
12 R72 DO7 Normally open
ED3: Provides 11 DIs.
Terminals: No. Definition Remark
1 DI10 DI 10
2 DI11 DI 11
3 DI12 DI 12
4 DI13 DI 13
5 DI14 DI 14
6 DI15 DI 15
7 DI16 DI 16
8 DI17 DI 17
9 DI18 DI 18
10 DI19 DI 19
11 DI20 DI 20
12 DC1 Common terminal of DIs
All DIs and DOs are programmable.
TERMINALS and OTHERS
24
7.4 EXTENDED ANALOG MODULE
LED:
Run
The two RJ45 ports are used to connect the extended module and the main module. The functions of them are
identical.
EA1: Provides 1 route of analog input and 1 route of hot resistance input
Terminals: No. Definition Remark
1 AIN+ Analog input +
2 AIN- Analog input -
3 RT+ Input + of hot sense resistance
4 - -
5 - -
6 RT- Input - of hot sense resistance
State Definition
OFF No power
Lighten Communication isn’t built.
Flicker Communication is built with main module.
TERMINALS and OTHERS
25
EA2: Provides 2 routes of analog input. Terminals:
No. Definition Remark
1 AIN1+ Analog input +/1
2 AIN1- Analog input -/1
3 - -
4 AIN2+ Analog input +/2
5 AIN2- Analog input -/2
6 - -
7.5 POWER SUPPLY MODULE
The power supply module can support 1 route of AC power input, 1 route of DC power input and 1 route of DC
power output. If a system has AC and DC power supply at the same time or the restart function is needed, the
power supply module can be selected.
PL-1: Suit for 220VAC and 220VDC inputs; In case a voltage dip, the module can support the controller
about 3~6s;
PL-2:Suit for 380VAC input;
PL-3: Suit for 220VAC input; in case a voltage dip, the module can support the controller about 6~9s.
Terminals: No. Definition Remark
1 DC+
2
3 DC-
DC output
4 L
5
6 N
AC input
7 DC+
8
9 DC-
DC input
PROTECTION FUNCTIONS
26
8. PROTECTION FUNCTIONS
8.1 PROTECTION VALUES Function Items Setting range
Start time 2s~60s Start overtime
protection Protection action mode Trip/alarm
Curve speed K 10 16 24 40 60 80 100 130 180
280 400 600 800 1000 1200 1300
Hot/Cold curve rate 20%~99%
Cool time 5min~1000min, step 1min
Fault reset mode Manual/automatic
Overload protection
Protection action mode Trip/alarm
Protection action value 100%Ie~600%Ie; 0 means protection is
disabled.
Delay time 0.5s~60.0s; step 0.1s Overcurrent protection
Protection action mode Trip/alarm
Delay time 1 cycle~250 cycles; step 1 cycle. Phase failure
protection Protection action mode Trip/alarm
Protection action value 20%~60%; 0 means protection is disabled.
Delay time 0.5s~5.0s; step 0.1s Unbalance protection
Protection action mode Trip/alarm
Protection action value 400%Ie~ allowed cut current of contactor;
0 means protection is disabled.
Delay time 5 cycle~250 cycles, step 1 cycle. Short circuit protection
Protection action mode Trip/alarm
Protection action value (20%~100%) Ie;
0 means protection is disabled.
Delay time 1 cycle~3000 cycles; step 1 cycle.
Earth fault protection
Protection action mode Trip/alarm
Protection action value (20%~100%) I△n;
0 means protection is disabled.
Delay time 1 cycle~3000 cycles; step 1 cycle.
Leakage current
protection*
(It can’t coexist with
earth fault protection.) Protection action mode Trip/alarm
Protection action value (20%~100%)Ie; 0 means protection is
disabled.
Delay time 0.5s~60.0s; step 0.1s. Underload protection
Protection action mode Trip/alarm
Delay time 0.1s~60.0s; step 0.1s. External fault
protection Protection action mode Trip/alarm
PROTECTION FUNCTIONS
27
Protection action value (105%~150%)Ue; 0 means protection is
closed.
Delay time 0.5s~60.0s; step 0.1s.
Overvoltage protection
﹡
Protection action mode Trip/alarm
Protection action value (45%~95%)Ue; 0 means protection is disabled.
Delay time 0.5s~60.0s; step 0.1s. Undervoltage
protection﹡ Protection action mode Trip/alarm
Protection action value (20%~95%)Pn; 0 means protection is disabled.
Delay time 0.5s~60.0s; step 0.1s. Under power
protection﹡ Protection action mode Trip/alarm
Phase sequence error
protection﹡ Function Disable /Enable
EEx e motor overload
protection* Function Disable /Enable
Protection action value 4.0~20.0mA; 0 means protection is disabled.
Delay time 0.5s~60.0s; step 0.1s. Analog input
protection* Protection action mode Trip/alarm
Hot sense resistance PTC/NTC/ Disable
Action resistance 0.1kΩ~10.0 kΩ(For PTC, action value should
be bigger than return value. For NTC, reverse.)
Return resistance 0.1kΩ~10.0 kΩ
Delay time 1s
Temperature
protection﹡
Protection action mode Trip/alarm
Note:
1. ”﹡” means optional protection function.
2. If users decrease protection action value to 0, the protection function will be disabled.
8.2 PROTECTION EXPLANATION Protection parameters of PMAC801 can be set through display module or communication software.
Only start overtime, overload, phase failure, and short circuit protection functions are primarily enabled. Users
can enable the other protection functions according to requirements. Please be cautious when setting
protection parameters, in case of bringing controller’s mis-protection or motor’s damage.
Additionally, during motor’s starting state, only start overtime, phase failure, unbalance (if enabled),
earth/leakage (if enabled), short circuit (if enabled), external fault (if programmed), phase sequence error (if
enabled) and EEx e overload (if enabled) protections are active, the other protections won’t be active until
motor comes into running state.
◆ START OVERTIME PROTECTION
Start overtime protection is active just during motor’s starting state. The protection function can’t be disabled.
Users can set the start time according to the motor’s actual start time i.e. the time from when motor starts to
PROTECTION FUNCTIONS
28
when motor comes to rated speed. Usually the time can be set as 1.2 times of actual start time.
During motor’s starting state, after the set start time is expired, if Iav ≥1.2 times of Ie or Iav≤0.1 time of Ie,
start overtime protection will act immediately.
Default parameters:
Start time 5s
Action mode Alarm
◆ OVERLOAD PROTECTION
Overload protection prevents motor from running over rated current for long time and being damaged. The
controller simulates heating characteristic of motor to protect it. The protection function can’t be disabled. And
it is just active during running state.
The curve speed K should be set according to the motor’s overload level. The following is the relation of K and
overload level.
K Overload level Times of rated current 1.2 1.5 7.2
130,180 10A ≤2min 2s<t≤10s
280 10 ≤4min 4s<t≤10s
400,600 20 ≤8min 6s<t≤20s
800,1000 30
Delay time Less than an hour
≤12min 9s<t≤30s
Hot/Cold is used to calculate the motor’s hot capacity. It is achieved from the following formula.
Hot/Cold =(100×Hot rotor locked time∕Cold rotor locked time)*100%
Hot rotor locked time and cold rotor locked time can be found in motor’s technical specification. Or its typical
value is 85%. After motor stops, its cool speed is affected by the cool time set by users. Cool time can be set according to the
motor’s cool condition. The typical time is 30 minutes.
If the fault reset mode is manual, after motor stops because of overload fault, users should reset controller
manually to clear fault indication and hot capacity. If the fault reset mode is automatic, after motor stops,
manual operation is unnecessary. After hot capacity falls under 15%, fault indication will be cleared
automatically, and motor can be restarted.
During the motor’s running state, if Iav>1.05 times of Ie, overload protection function will start to calculate
delay time according to time-current curves, and act after delay time is expired. If Iav ≤ 1.05 times of Ie, the
protection won’t act. The error of delay time is ±10%.
Overload protection have 16 types of inverse time-limit time-current characteristics curves.
PROTECTION FUNCTIONS
29
Default parameters:
Curve speed K 10
Hot/Cold curve rate 85%
Cooling time 30min
Fault reset mode Manual
Protection action mode Alarm
◆ OVERCURRENT PROTECTION
Overload protection prevents the motor from being locked because of heavy overload or other mechanical
reasons.
Users can set the action value of overcurrent protection according to motor’s max locked current provided by
manufactures. The value can be set as half of motor’s max locked current, and usually it is 1.5~2.5 times Ie.
During the motor ‘s running state, if Iav≥1 time of the action value, overcurrent protection function will start
to calculate the delay time, and act after the delay time is expired. If Iav < 1 time of the action value, protection
won’t act.
The error of delay time is ±100ms.
PROTECTION FUNCTIONS
30
◆ PHASE FAILURE PROTECTION
If any phase < 5% of Ie, protection will act after the delay time is expired. The protection function can’t be
disabled.
The error of delay time is ±2 cycles.
Default parameters: Delay time 2 cycles
Action mode Alarm
◆ CURRENT UNBALANCE PROTECTION
Current unbalance is a main reason to lead to motor’s hot damage. When unbalance takes place, if unbalance
rate reaches the protection action value, controller will alarm or trip.
Once unbalance protection is active, if the current unbalance rate ≥1 time of the action value, the protection
will start to calculate the delay time, and act after the delay time is expired. If the unbalance rate < 1 time of
the action value, the protection won’t act.
The error of delay time is ±100ms.
◆ SHORT CIRCUIT PROTECTION
Short circuit current will generate mass of hot, and slow action will lead motor to burn out. The controller
provides prompt protection for motor.
If motor’s short circuit current is bigger than the cut ability of contactor and the protection action mode is trip,
the overflow relay of the controller will give a pulse to breaker to stop motor. The contactor will be cut after
the current falls down the cut ability.
During the motor’s running state, if any phase current ≥1 time of the action value, the protection will start to
calculate the delay time, and after the delay time is expired, if the current < the allowed cut current of contactor,
the protection will act to cut the contactor. If the current < 1 time of the action value, the protection won’t act.
The error of delay time is ±2 cycles. ◆ EARTH FAULT PROTECTION
Earth fault protection will work when rotor’s coil is short connection with ground. The connection point
determines the magnitude of earth current. Low action value will protect more coils.
After Earth fault protection is active, if Ig≥1 time of the action value, the protection will start to calculate
delay time, and act after delay time is expired. If Ig < 1 time of the action value, the protection won’t act.
The error of delay time is ±2 cycles.
Default parameters:
Action value 20%Ie
PROTECTION FUNCTIONS
31
Delay time 2 cycles
Action mode Alarm
◆ LEAKAGE CURRENT PROTECTION
Leakage current protection provides more precise check of earth current to prevent people from injury.
After leakage current protection is active, if I△≥1 time of the action value, the protection will start to calculate
the delay time, and act after the delay time is expired. If I△< 1 time of the action value, the protection won’t
act.
The error of delay time is ±2 cycles.
The leakage current protection is optional. If the function is selected, users can set the item ”earth or leakage”
to leakage.
◆ UNDERLOAD PROTECTION
Underload protection prevents motor from uneconomical energy spoilage.
During the motor’s running state, if Iav ≤ 1 time of the action value, the protection will start to calculate delay
time, and act after the delay time is expired. If Iav > 1 time of the action value, the protection won’t act.
The error of delay time is ±100ms.
◆ EXTERNAL FAULT PROTECTION If a DI is programmed as external fault input, the active input will touch off the external fault protection. After
the DI is cleared, the fault information will be cleared automatically.
◆ UNDERVOLTAGE PROTECTION
Low voltage may make motor’s rotate speed slow or motor stop.
During the motor’s running state, if any phase/phase voltage ≤ 1 time of the action value, the protection will
start to calculate the delay time, and act after the delay time is expired. If all phase/phase voltage >1 time of
the action value, the protection won’t act.
The error of delay time is ±100ms.
◆ OVERVOLTAGE PROTECTION
Overvoltage may make insulation damaged. Because motors can usually work under 1.2 times of Ue, the action
value can be set as 120% of Ue.
During the motor’s running state, if any phase/phase voltage ≥1 time of the action value, the protection will
start to calculate the delay time, and act after the delay time is expired. If all phase/phase voltage < 1 time of
the action value, the protection won’t act.
PROTECTION FUNCTIONS
32
The error of delay time is ±100ms.
◆ UNDER POWER PROTECTION
Under power protection provides motors with better underload protection.
During motor ‘s running state, if the total value of three phase active power ≤ 1 time of the action value, the
protection will start to calculate the delay time, and act after the delay time is expired. If the value > 1 time of
the action value, the protection won’t act.
The error of delay time is ±100ms.
◆ PHASE SEQUENCE ERROR PROTECTION
Wrong phase sequence can make motor run in wrong direction. The protection prevents motor from being
started in wrong direction.
◆ EEx e OVERLOAD PROTECTION (te time protection)
EEx e overload protection is for explosion proof three phase induction motors. The trip time of the protection
from the cold state motor must be less than the te time rated for the motor.
A trip time curve is provided to implement the protection in the controller. The trip time curve is below the curve
provided by GB3836.3-2000, and is suitable for the motors, which conform to GB3836.3-2000.
te characteristics curve:
① The curve is provided by GB3836.3-2000.
② The curve is provided by the controller. ◆ ANALOG CURRENT INPUT PROTECTION Analog current input protection is designed for non-electrical parameter. It can measure 4~20mA current input
and make a protection output according to the measurement.
PROTECTION FUNCTIONS
33
◆ OVERTEMPERATURE PROTECTION
Impedance of hot resistance imbedded in motor stator can change according to temperature’s change.
The te hot sense resistance can be connected with the controller, when the impedance reaches the action value,
the controller will trip or alarm.
PTC: If the real time impedance ≥the action value, then the controller will act after the delay time. If the
action mode is alarm, the alarm information will be cleared automatically when the impedance < the return
value.
NTC: If the real time impedance ≤the action value, then controller will act after the delay time. If the action
mode is alarm, the alarm information will be cleared automatically when the impedance >the return value.
The delay time is 1s. The error of delay time is ±100ms.
DI and DO CONFIGURATION
34
9. SYSTEM PARAMETERS
◆ RATED CURRENT of MOTOR
Range: 0.5 A~ 820.0A.
◆ RATED VOLTAGE of MOTOR
Range: 100 V~ 690 V.
◆ RATED POWER of MOTOR
Range: 0.5~600kW.
◆ RATE of EXTERNAL CT
Because PMAC801 has its special independent CT, and the rated current of the CT is up to 820A. Generally it
doesn’t need the other CTs. In case the other CTs are used, the rate of the CT should be set. For example, if the
other CT is 500A/5A, the rate is 100.
Range: 1~2000.
◆ EARTH/LEAKAGE
Range: Earth, leakage.
Earth fault protection and leakage current protection can’t exist at the same time. Users can select any of them
through display module or communication.
Earth fault protection uses three composite vector modes to calculate the Zero phase sequence current. Leakage
current protection needs external leakage CT.
◆ PRIMARY RATED CURRENT of LEAKAGE CURRENT CT Range: 1mA~1000mA.
If users select the leakage current protection, a leakage current CT is needed. PMAC801 supports the CT, which’s
secondary rated current is 4mA. The primary rated current of the CT can be set according to real value.
◆ CUT ABILITY of CONTACTOR Range:6.0~10.0Ie
◆ STARTING CONTROL MODE
Range: protection mode, direct starter, reversing direct starter, star/delta starter, Loop-open star/delta starter
with 3 relays, Loop-close star/delta starter with 3 relays, autotransformer starter, Loop-open autotransformer
starter with 3 relays, Loop-close autotransformer starter with 3 relays, breaker direct starter.
The default mode is direct starter.
◆ ANALOG TYPE
Range: Ia, Ib, Ic, Ig UnI, Uab, Ubc, Uca. The parameters can be chosen to correspond to the analog current
output.
◆ ANALOG MULTIPLE
Range: 1.0~10.0.
DI and DO CONFIGURATION
35
When the multiple of analog is set 2, the relations of analog and corresponding current output 20mA are listed
as follow:
Sort Corresponding Value
of 20mA Sort
Corresponding Value
of 20mA
Ia 2 times of rated value UnIav 200%
Ib 2 times of rated value Uab 2 times of rated value
Ic 2 times of rated value Ubc 2 times of rated value
Ig 2 times of rated value Uca 2 times of rated value
◆ COMMUNICATION ADDRESS Range: 1~247(Modbus-RTU);
3~123(Profibus-DP).
◆ BAUDRATE
Range: 2400,4800,9600,19200.
The default is 9600.
◆ CHECK on FEEDBACK of CONTACTORS
Range: Disable/Enable.
If the function of check on feedback of contactors is enabled, the controller will check the state of contactor
firstly. If the state is error, “Feedback Error” will be displayed and the fault information relay will be closed. If the
state is right, the fault information will be cleared.
◆ OPERATION PERMISSION
Range: Remote DI/Communication.
After the DI6 is active, the operation permission is switched to remote. It includes remote and communication.
The parameter only can be set via communication.
◆ SYSTEM FREQUENCY
Range: 50HZ/60HZ. The default is 50HZ. The parameter just can be set via communication.
◆ RESTART FUNCTION
After a motor is started, if a undervoltage protection happens, or a voltage dip results in contactor to break and
the voltage drops down the undervoltage protection action value (undervoltage protection is enabled) or 70% of
rated voltage (undervoltage is disabled), the controller will open the control relay inside, and give a voltage dip
information.
In case a voltage dip, the controller start to cumulate the dip time till the voltage rises above the programmable
voltage restoration level (VRL). If the dip time isn’t over the programmable allowed dip time (ADT), the motor
will be restarted after the start delay time (SDT) is expired. If the dip time is over the allowed dip time, the motor
won’t be restarted, and all dip information will be cleared.
The function is noneffective under the Motor starting control mode of protection mode.
Parameter Range
DI and DO CONFIGURATION
36
Function Disabled/Enabled
Voltage restoration level 75%~100%
Allowed dip time 0.2s~10.0s
Start delay time 0.1s~60.0s
DI and DO CONFIGURATION
37
10. DI and DO CONFIGURATION
Protection mode
Terminal No. DI No. Function DO No. Function
2 DI1 Common DI DO1
Control relay A for
protect motor output
3 DI2 Common DI
4 DI3 Common DI DO2 /
5 DI4 Reset
6 DI5 Emergent stop DO3 Overflow relay output
7 DI6 Common DI
8 DI7 Programmable DI DO4 Fault information output
9 DI8 Programmable DI
10 DI9 Programmable DI DO5
Self-diagnose
information output
Direction starter
Terminal No. DI No. Function DO No. Function
2 DI1 Start in CW (start A) DO1
Control relay A to control and
protect motor
3 DI2 Common DI
4 DI3 Stop DO2 /
5 DI4 Reset
6 DI5 Emergent stop DO3 Overflow relay
7 DI6 Local/Remote switch
8 DI7
Contactor C1 status
information input
DO4 Fault information
9 DI8 Programmable DI
10 DI9 Programmable DI DO5 Self-diagnose information
Reversing direct starter
Terminal
No.
DI No. Function DO No. Function
2
DI1
Start in CW (start A)
DO1
Control relay A for
control and protect
motor status output
3 DI2 Start in CCW (start B)
4 DI3
Stop DO2
Control relay B for
control and protect
motor status output
5 DI4 Reset DO3 Overflow failure
DI and DO CONFIGURATION
38
6 DI5 Emergent stop output
7 DI6 Local/Remote switch
8 DI7 C1 Contactor’s status information DO4
Motor Fault
information
9 DI8 C2 Contactor’s status information
10 DI9 Programmable DI DO5
Self-diagnose
information
Star/delta starter or autotransformer starter with 2 relays
Terminal
No.
DI No. Function DO No. Function
2
DI1
Start in CW (start A)
DO1
Control relay A for
control and protect
motor status output
3 DI2 Common DI
4 DI3
Stop DO2
Control relay B for
control and protect
motor status output
5 DI4 Reset
6 DI5 Emergent stop DO3
Overflow failure
output
7 DI6 Local/Remote switch
8 DI7 C1 Contactor’s status information DO4
Motor Fault
information
9 DI8 C2 Contactor’s status information
10 DI9 Programmable DI DO5
Self-diagnose
information
Star/delta starter or autotransformer starter with 3 relays
Terminal
No.
DI No. Function DO No. Function
2
DI1 Start in CW (start A) DO1
Control relay A for
control and protect
motor status output
3 DI2 Common DI
4 DI3
Stop DO2
Control relay B for
control and protect
motor status output
5 DI4 Reset
6 DI5
Emergent stop DO3
Control relay C for
control and protect
motor status output
7 DI6 Local/Remote switch
8 DI7 C1 Contactor’s status information DO4
Motor Fault
information output
9 DI8 C2 Contactor’s status information
10
DI9
C3 Contactor’s status information DO5
Self-diagnose
information
output(Normal
close contactor)
DI and DO CONFIGURATION
39
Breaker direct starter
Terminal
No.
DI No. Function DO No. Function
2 DI1
Start in CW (start A) DO1
Control relay A for
closing breaker output
3 DI2 Common DI
4 DI3
Stop DO2
Control relay B to
opening breaker
output
5 DI4 Reset
6 DI5 Emergent stop DO3 -
7 DI6 Local/Remote
8 DI7 C1 Contactor’s status information DO4
Motor Fault
information
9 DI8 C2 Contactor’s status information
10
DI9
C3 Contactor’s status information DO5
Self-diagnose
information
output(Normal
close contactor)
◆ PROGRAMMABLE DIs and DOs
Programmable DI Comment
DI7~DI9 of main module
All DIs of extended digital module
General DI
External fault input
Start/stop A via remote DI
Start/stop B via remote DI
Programmable DO Comment
All DOs of extended digital module
General DO
Fault information output of start overtime
Fault information output of overload
Fault information output of overcurrent
Fault information output of phase failure
Fault information output of current unbalance
Fault information output of short circuit
Fault information output of earth fault
Fault information output of leakage
Fault information output of underload
Fault information output of external fault
Fault information output of overvoltage
Fault information output of undervoltage
Fault information output of underpower
Fault information output of phase sequence error
Fault information output of EEx e overload
Fault information output of temperature
DI and DO CONFIGURATION
40
Fault information output of analog current input
Alarm information output
Trip information output
Ready state information output
Starting/running state information output
Stop state information output
Note: If the function of check on feedback of contactors is enabled, some of DI7~DI9 will be used for feedback
input of contactors. If the function is disabled, the DIs can be programmed.
TYPICAL CONNECTIONS
41
11. TYPICAL CONNECTIONS
11.1 PROTECTION MODE
29 30
26
25 Ln1
Ln2
414039
1 5
FGN/-L/+
C
A
B
QF
C1
MOTOR
N
L
C1
C1
4~20mA
2827
+ -
UB22
UC24
UA20
IN
IB
IC
IA
CT
11
13
12
14
353332 36 3837
RS485
1615
+ -
RJ 45
DB9
1918
+ -
17
SHLD
StopStart
6
QF
9 108
DI
com
mon
Res
et
Em
ergen
t st
op
Pro
gra
m D
I
Pro
gra
m D
I
Pro
gra
m D
I
RS485/1Analog output RS485/2
Display port
Profibus portContro
l Relay A
Overflo
w relay
Fault in
form
ation
Self-d
iagnose in
fo
Under protection mode, contact of relay A is in series with coil circuit of contactor C1, after powering on
controller, the contact of relay A is closed immediately, then motor can be started via remote control switch. If
a protection action takes place, contact of relay A will be opened, then contactor C1 will be opened and motor
stops. After motor comes into stopped state, fault information can be cleared via reset operation. And then relay
A will be closed, motor can be restarted.
Under this mode, the functions of check on feedback of contactors and restart are noneffective.
TYPICAL CONNECTIONS
42
11.2 DIRECT STARTER
MOTOR
1 2 54
IN
Ln1
Ln226
25
IB
IC
IA
3029
RS485/1
RS485
1615
+ -
FG
353332
L/+ N/-
4039 41
C1
BC
AN
C1
L
+
27
Analog output
28
-
4~20mA
20 UA
24 UC
22 UB
36
RJ 45
Display port CT
6 7
11
13
12
14
3837
DB9
Profibus port
1918
RS485/2
+ -
17
SHLD
QFQF
9 108
C1
DI
com
mon
Sta
rt A
Sto
p
Res
et
Em
ergen
t st
op
Loca
l/Rem
ote
Sta
tus
of C
1
Progra
m D
I
Progra
m D
I
Contro
l Relay A
Overflo
w relay
Fault in
formatio
n
Self-d
iagnose in
fo
Under direct starter mode, after powering on controller, “Direct Starter” will be displayed. Under the ready
state of motor, if command START A is given, the contact of relay A will be closed, and then the contact of C1
contactor will be closed; Motor is started. During the starting state, LED ”START” is lighten, and “Starting“ is
displayed. After started, LED ”START” is off, and LED ’’RUN” is lighten. “Running” is displayed. If command STOP
is given, the contact of relay A will be opened, and the contact of contactor C1 will be opened; Motor stops.
If a fault takes place, and protection action mode is trip, the controller will open the contact of relay A to stop
motor. After motor comes into stopped state, fault information can be cleared via reset operation; motor can be
restarted.
TYPICAL CONNECTIONS
43
11.3 REVERSING DIRECT STARTER
MOTOR
C1C2
Ln2
Ln125
26
2930 30 31
FGL/+ N/-
4039 41
C1QF
BC
A N
L
C1
C2
C2
UB22
24 UC
20 UA 35 33 3632 3837
RS485
1615
+ -
1918
+ -
17
SHLD
RJ 45
DB9
1 2 3 54
+
27 28
-
4~20mA
6 7
IN
IB
IC
IA
CT
11
13
12
14
QF
10
DI
com
mon
Sta
rt A
Sto
p
Res
et
Em
erg
ent
stop
Loca
l/Rem
ote
Sta
tus
of C1
Sta
tus
of C2
Progra
m D
I
Sta
rt B
Contro
l Rela
y A
Overflow
rela
y
Fault in
form
ation
Self-d
iagnose in
fo
Contro
l Rela
y BDisplay port
Profibus port
98
C1 C2
RS485/1Analog output RS485/2
Under reversing direct starter mode, after powering on controller, “Rev_DS” will be displayed. Under the
ready state of motor, if command START A is given, the contact of relay A will be closed, and then the contact of
C1 contactor will be closed. Motor is started in CW direction. During starting, LED ”START” is lighten, and
“Starting“ is displayed. After starting, motor runs at positive direction. LED ”START” is off, and LED ’’RUN” is
lighten. “Running” is displayed. If command STOP is given, the contact of relay A will be opened, and the contact
of contactor C1 will be opened. Motor stops. Giving command START B will start motor in CCW direction. The
contact of relay B will be closed and the contact of contactor C2 will be closed. During starting, LED ”START” is
lighten, and “ Starting” is displayed. After started, LED ”START” is off, and LED ’’RUN” is lighten. “Running” is
displayed.
If a fault takes place, and protection action mode is trip, the controller will open the contact of relay A or B to stop
motor. After motor comes into stopped state, fault information can be cleared via reset operation, motor can be
restarted.
TYPICAL CONNECTIONS
44
11.4 STAR/DELTA STARTER
MOTOR
Ln125
26 Ln2
QF
CA
A
N
L
C1
L/+ N/-
39 40
FG
41
C2
2V 2W 2U1U 1W1V
C2
C2
C1
C3
C2C1
UB
UC
UA20
22
24
C1
C3
IN
IB
IC
IA11
13
12
14
1615
+ -
1918
+ -
17
SHLD
4~20mA
2827
+ -
RJ 45
DB9
2930 30 31 35 33 3632 3837
QF
Display port
Profibus port
RS485
CT
RS485/1Analog output RS485/2
1 2 54 6 7 9 108
DI
com
mon
Sta
rt A
Sto
p
Res
et
Em
erg
ent
stop
Loca
l/Rem
ote
Sta
tus
of C
1
Sta
tus
of C
2
Pro
gra
m D
I
C1 C2
Con
trol R
elay A
Overflo
w rela
y
Fault in
formation
Self-d
iagnose in
fo
Con
trol R
elay B
Under star/delta mode, after powering on controller, “S/D Starter” will be displayed. Under the ready state of
motor, if command START A is given, the contact of relay A will be closed, and then the contacts of C1 and C3
contactors will be closed. Motor is started under Y mode. During starting, LED ”START” is lighten, and “Starting”
is displayed. When the start time elapses, the contact of relay A will be opened, and the contact of relay B will
be closed. Then the contact of C1 contactor will be opened, and the contact of C2 contactor will be closed. Motor
will run under △ mode. LED ”START” is off, and LED ’’RUN” is lighten. “Running” is displayed. If command STOP
is given, the contact of relay B will be opened, and the contacts of contactor C2 and C3 will be opened. Motor
stops.
If a fault takes place, and protection action mode is trip, the controller will stop motor. After motor comes into
stopped state, fault information can be cleared via reset operation, motor can be restarted.
TYPICAL CONNECTIONS
45
11.5 LOOP-OPEN STAR/DELTA STARTER WITH 3 RELAYs
C2C1
2U
C3
2W2V
MOTOR
1V 1W1U
Ln2
Ln1
26
25
UB
UC
UA
22
24
20
FGL/+ N/-
414039
C
QF
A
A N
L
C2
C3
C1 C3
C1
IN
IB
IC
IA11
13
12
14
2930 30 31 35 33 3632 3837
RJ 45
DB9
Display port
Profibus port CT
1 2 54 6 7 1615
+ -
1918
+ -
17
SHLD
4~20mA
2827
+ -
RS485
RS485/1Analog output RS485/2
108 9
C1 C2 C3
DI
com
mon
Sta
rt A
Sto
p
Res
et
Em
ergen
t st
op
Loca
l/Rem
ote
Sta
tus
of C1
Sta
tus
of C2
Con
trol Relay A
Fault in
form
ation
Self-d
iagnose in
fo
Con
trol Relay B
Sta
tus
of C3
Con
trol Relay C
Sequence of contactors
Switch Contactor Start
1 2 Run
C1 ○ ○ ○ ● ●
C2 ○ ● ● ● ●
C3 ● ● ○ ○ ○
TYPICAL CONNECTIONS
46
11.6 LOOP-CLOSE STAR/DELTA STARTER WITH 3 RELAYs
25
22
24
26
C2
C1
2V 2U2W 1U 1V 1W
MOTOR
C3
Ln2
Ln1
UB
UC
20
QF
C
A
A
UA
N
L
C4C1
C2C2
N/-L/+
39
FG
4140
C3
RE
S
RE
S
RE
S
C2
C1
N
C4
IN
IB
IC
IA11
13
12
14
2930 30 31 35 33 3632 3837
RJ 45
DB9
Display port
Profibus port CT
1 2 54 6 7 1615
+ -
1918
+ -
17
SHLD
4~20mA
2827
+ -
RS485
RS485/1Analog output RS485/2
108 9
C1 C2 C3
DI
com
mon
Sta
rt A
Sto
p
Res
et
Em
ergen
t st
op
Loca
l/Rem
ote
Sta
tus
of C1
Sta
tus
of C2
Con
trol Relay A
Fault in
form
ation
Self-d
iagnose in
fo
Con
trol Relay B
Sta
tus
of C3
Con
trol Relay C
Sequence of contactors
Switch Contactor Start
1 2 3 Run
C1 ● ● ● ○ ○ ○
C2 ○ ○ ○ ● ● ●
C3 ○ ● ● ● ● ●
C4 ○ ○ ● ● ○ ○
TYPICAL CONNECTIONS
47
11.7 AUTOTRANSFORMER STARTER
MOTOR
C3
C1
C2
25
26
Ln1
Ln2
20 UA
22
24
UB
UC
N/-L/+ FG
39 4140
C
QF
A
A
NN
L
C1
C1
C2
C2
C1
C3
IN
IB
IC
IA11
13
12
14
2930 30 31 35 33 3632 3837
1 2 54 6 7 1615
+ -
1918
+ -
17
SHLD
4~20mA
2827
+ -
RJ 45
DB9
QF
10
Display port
Profibus port
RS485
CT
RS485/1Analog output RS485/2
DI
com
mon
Sta
rt A
Sto
p
Res
et
Em
ergen
t st
op
Loca
l/Rem
ote
Sta
tus
of C1
Sta
tus
of C2
Pro
gra
m D
I
C1 C2
8 9
Contro
l Relay A
Overflo
w relay
Fault in
form
atio
n
Self-d
iagnose in
fo
Contro
l Relay B
Sequence of contactors
Switch Contactor Start
1 2 Run
C1 ● ○ ○ ○
C2 ○ ○ ● ●
TYPICAL CONNECTIONS
48
11.8 LOOP-OPEN AUTOTRANSFORMER STARTER WITH 3 RELAYs
MOTOR
C3
C2
C1
CA
QF
A
Ln226
Ln125
UA20
UC24
UB22
40 4139
FGL/+ N/-
N
L
N
2930 30 31 35 33 3632 3837
IN
IB
IC
IA11
13
12
14
1 2 54 6 7 1615
+ -
1918
+ -
17
SHLD
4~20mA
2827
+ -
RJ 45
DB9
Display port
Profibus port
RS485
CT
RS485/1Analog output RS485/2
108 9
C1 C2 C3
DI
com
mon
Sta
rt A
Sto
p
Res
et
Em
ergen
t st
op
Loca
l/Rem
ote
Sta
tus
of C
1
Sta
tus
of C
2
Con
trol Relay A
Fault in
form
ation
Self-d
iagnose in
fo
Con
trol Relay B
Sta
tus
of C
3
C3
C2C1 C3
C3
C1
Con
trol Relay C
Sequence of contactor
Switch Contactor Start
1 2 3 Run
C1 ○ ○ ○ ○ ● ●
C2 ○ ● ○ ○ ○ ○
C3 ● ● ● ○ ○ ○
TYPICAL CONNECTIONS
49
11.9 LOOP-CLOSE AUTOTRANSFORMER STARTER WITH 3 RELAYs
C3
MOTOR
C2
C1
Ln226
UC
UB
Ln1
24
22
25
QF
A
A
C
UA20
L
N
40 41
FG
39
L/+ N/-
N
2930 30 31 35 33 3632 3837
IN
IB
IC
IA11
13
12
14
1 2 54 6 7 1615
+ -
1918
+ -
17
SHLD
4~20mA
2827
+ -
RJ 45
DB9
Display port
Profibus port
RS485
CT
RS485/1Analog output RS485/2
108 9
C1 C2 C3
Sta
tus
of C1
Sta
tus
of C2
DI
com
mon
Sta
rt A
Sto
p
Res
et
Em
ergen
t st
op
Loca
l/Rem
ote
Contro
l Relay A
Fault in
form
ation
Self-d
iagnose in
fo
Contro
l Relay B
Sta
tus
of C3
Contro
l Relay C
C2 C3C1
C3
C3
C1
C2
Sequence of contactor
Switch Contactor Start
1 2 3 Run
C1 ○ ○ ○ ● ● ●
C2 ○ ● ● ● ○ ○
C3 ● ● ○ ○ ○ ○
TYPICAL CONNECTIONS
50
11.10 BREAKE DIRECTOR
MOTOR
Ln2
Ln125
26
2930 30 31
FGL/+ N/-
4039 41
QF
BC
A
N
L
HC FC
UB22
24 UC
20 UA
35 33 3632 3837
1615
+ -
1918
+ -
17
SHLD
RJ 45
DB9
1 2 3 54
+
27 28
-
4~20mA
6 7
IN
IB
IC
IA11
13
12
14
HC: Close coil of QF
FC: Open coil of QF
8 9 10
Display port
Profibus port
RS485
CT
RS485/1Analog output RS485/2
DI
com
mon
Sta
rt A
Sto
p
Res
et
Em
ergen
t st
op
Loca
l/Rem
ote
Progra
m D
I
Progra
m D
I
Progra
m D
I
Control R
elay A
Fault in
form
ation
Self-d
iagnose in
fo
Control R
elay B
Under breaker director mode, if command START A is given, relay A will give a pulse to the close coil of break
to start motor. If command STOP is given, relay B will give a pulse to the open coil of break to stop motor.
Under this mode, the function of check on feedback of contactors is noneffective.
BASIC SETTING and EVER-PRESENT QUESTIONS
51
APPENDIX A BASIC SETTING and EVER-PRESENT QUESTIONS
Basic setting:
Before start the motor, please set the following parameters at least.
(1) The rated current of motor;
(2) The rated voltage of motor;
(3) The rated power of motor;
(4) The motor starting control mode;
(5) The values of every protection functions users need.
Ever-present questions: Question Resolvent
After powered on, the controller
doesn’t work. Check terminals L/+ and N/- to ensure proper input voltage.
The measurement value of current
isn’t right.
Check if the current is in the measurement range of the controller.
Check if the rated current of motor and CT are set properly.
The measurement value of power
isn’t right. Check the phase sequence of current and voltage.
Relays misact. Check the motor starting control mode.
Check the address.
Check the baudrate. No communication.
Check if the terminal resistance is missed.
The control commands are
noneffective Check the operation permission.
ORDER INFORMATION
52
APPENDIX B ORDER INFORMATION
Main module:
PMAC801
Note:
1. The basic protection function includes start overtime protection, overload protection, overcurrent protection,
phase failure protection, current unbalance protection, earth fault protection, short circuit protection,
underlaod protection, and external error input protection.
2. The function dedicated with italics can be selected together.
3. The leakage current protection function needs an additional leakage CT.
4. Voltage protection function includes overvoltage, undervoltage, underpower, phase sequence error
protection. If voltage protection function or restart function are selected, voltage measurement function will
be active automatically.
5. If temperature protection function or analog input protection function is needed, the extended analog
module EA1 should be selected.
6. If the control circuit is DC system, the “Z” item can be selected.
- * - * - * - * - *
2
6.3
25
100
250
500
820
Rated current of controller
2A
6.3A
25A
100A
250A
500A
820A
N
M
P
F
Communication protocol
No
MODBUS-RTU
PROFIBUS-DP
2 MODBUS-RTU
C
X
V
Other protection function
Leakage current protection
EEx e overload protection
Voltage protection
A
E
S
R
Accessorial function
4~20mA analog output
Events record
Statistic information
Restart function
Z
Control Relay type
220VDC/3A
ORDER INFORMATION
53
Accessorial modules
Name Type Function
Display module PMAC801D1 The main function of the display module is to display measurement values
and fault information, to set protection value and to control motor.
ED1 4DI, 4DO
ED2 8DI, 2DO Extended digital
module ED3 11DI
EA1 1 route of 4~20mA analog input,1 route of hot resistance input Extended analog
module EA2 2 routes of 4~20mA analog input
PL1
If the system has AC and DC power supply or restart function are needed,
the power supply module can be selected. It can supply PMAC801 to work
for 3~6s, when the system voltage is interrupted. It is proper for 220V AC
or 220V DC input.
PL2 It is proper for 380V AC input.
Power supply
module
PL3
If the restart function is needed, the module can be selected. It can supply
PMAC801 to work for 6~9s, when the system voltage is interrupted. It is
proper for 220V AC input.
LCT100 The hole size is 50mm. It is proper for motor with rated current 10~100A.
LCT250 The hole size is 75mm. It is proper for motor with rated current
100~250A.
LCT400 The hole size is 100mm. It is proper for motor with rated current
250~400A.
Leakage CT
LCT630 It is proper for motor with rated current > 400A.