PLUMBING RISER DIAGRAMS - MDM Construction · 2017. 4. 24. · 343 fountains parkway suite 100...
Transcript of PLUMBING RISER DIAGRAMS - MDM Construction · 2017. 4. 24. · 343 fountains parkway suite 100...
EXISTING 4"SANITARY STACK
EXISTING 2"VENT STACK
1 1/2" V
1 1/2" V
1 1/2" V
1 1/2" V
EXISTEWC
1 1/2" V
1 1/2" V 1 1/2" V
2" V
3" V
3" V
4" SS
3" V
2" SS
CO
4" SS
EXISTING 4"SANITARY STACKEXISTING 3"VENT STACK
2" SS
3" V
4" SS
4" SS
2" SS
2" V
3" V
P-513
RI
1 1/2" V
P-401
FD
P-101
2" SS
2" V
P-413
P-101FD
P-401
P-502
EXISTFD
2" SS
2" SS
RELOCATED VTR
EXISTING 1-1/2"COLD WATER RISER
EXISTING 3/4"HOT WATER RISER
EXISTING 1/2"HOT WATER RECIRCULATION RISER
1" CW
3/4" HW
1/2" CHW
1" CW
3/4" HW
1/2" CHW 1/2" CHW
3/4" HW
1" CW
3/4" HW
1/2" CHW
EXISTING 2"COLD WATERAND 1"HOT WATER PIPING
EXISTING 2"COLD WATERAND 1"HOT WATER PIPING
EXISTING 2"COLD WATERAND 1"HOT WATER PIPING
1/2" HW
1/2" CW
1/2" CW
1/2" HW 1 1/4" CW
1/2" CW 1/2" HW
1 1/4" CW
1/2" CW 1/2" HW
1/2" CW 1/2" HW
1/2" CHW
1/2" HW
1/2" CW
EXISTING 1/2"HOT WATER RECIRCULATION RISER
EXISTING 3/4"HOT WATER RISER
EXISTING 2"COLD WATER RISER
RI
P-513 P-413
P-401
P-101
P-101
P-401
P-502
1/2" CW
1/2" HW
1/2" CW
1" CW
3/4" HW
1" CW
HB
Drawn
THE ARCHITECT EXPRESSLY RESERVESHIS COMMON LAW AND STATUTORY LAWCOPYRIGHTS AND OTHER PROPERTYRIGHTS FOR THESE "ARCHITECTURALWORKS" AND "TECHNICAL DOCUMENTS"AND ANY DERIVITIVES THEREOF. THESEDRAWINGS AND DOCUMENTS ARE NOTTO BE REPRODUCED, CHANGED ORCOPIED IN ANY MANNER WHATSOEVERFOR ANY USE WITHOUT FIRST OBTAININGTHE EXPRESS WRITTEN CONSENT OFLOUIS G. CHIODINI, CHIODINI ASSOCIATES,NOR ARE THEY TO BE ASSIGNED TO ANYPARTY WITHOUT FIRST OBTAINING SAIDWRITTEN PERMISSION AND CONSENT.
C COPYRIGHT PENDING
Architecture / Interior Design / Graphics
1401 S. Brentwood Blvd. / Suite 575 / St. Louis, Missouri 63144
314-725-5588 / [email protected]
©
Revisions: Date
ENGINEERS/CONSULTANTS:
CheckedDate
Location
Project Title Project Number
Building Number
Drawing NumberApproved: Project Director
Drawing Title
5
ARCHITECT:SEAL
WOOLPERT, INC.343 FOUNTAINS PARKWAYSUITE 100FAIRVIEW HEIGHTS, IL 62208314-436-0865314-436-0884 fax
SCI ENGINEERING, INC130 POINT WEST BLVD.ST. CHARLES, MO 63301636-949-8200636-949-8269 fax
VA FORM 08-6231
one e
ighth
inch =
one foot
one q
uart
er
inch =
one foot
thre
e e
ighth
s inch =
one foot
one h
alf inch =
one foot
thre
e q
uart
ers
inch =
one foot
one inch =
one foot
one a
nd o
ne h
alf inches =
one foot
thre
e inches =
one foot
6"
10
6"
20
6"
20
6"
40
40
84
016
84
0
438-16-104
1 2 3 4 5 6 7 8 9
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
A
B
C
D
E
F
FINAL SUBMITTALFOR CONSTRUCTION
Department ofVeterans Affairs
C:\_Local R
evit F
iles\7
6966_S
ioux F
alls
VA
Chapel_
MP
_C
entr
al_
2016_m
ark
.buttim
er@
woolp
ert
.com
.rvt
Scale:
3/1
3/2
017 8
:36:3
3 A
M
P901
PLUMBING RISER DIAGRAMS VA HEALTH CARE SYSTEM
MFB2017.03.13
2016.052
VAS 438-16-104 BLDG. 5 CHAPELSIOUX FALLS, SD 57105
Approver
VAA
OWNER
8' 16'4'0P901
1 WASTE & VENT RISER DIAGRAM
8' 16'4'0P901
2 DOMESTIC WATER RISER DIAGRAM
S
S
S
S
DA
RD
M
PA
F
S
S
WAP
SB
VC
m
D,3,4,K,OS
EF
1
PA
SP
PA
CR
J
OS
AMPEREA
LEGEND
QUAD RECEPTACLE , NEMA 5-20R
MANUAL MOTOR STARTER SWITCH WITH THERMAL OVERLOADS
FUSED DISCONNECT SWITCH, NEMA 1, NF,
JUNCTION BOX
PANELBOARD
TELEPHONE/DATA OUTLET - (4) CAT6 CABLES
CLOSE CIRCUIT TV (CCTV) OUTLET
DATA/COMMUNICATIONS IN FLOOR BOX
CONDUIT BELOW GRADE OR IN FLOOR SLAB
POWER ABBREVIATIONS
LIGHTING
LED LIGHT FIXTURE
WALL MOUNTED LIGHT FIXTURE
EXIT SIGN - UNIVERSAL MOUNT ON UNSWITCHED CIRCUIT
EMERGENCY FIXTURE ON UNSWITCHED CIRCUIT
SPECIAL SYSTEMS
EQUIPMENT TAG
CEILING MOUNTED P.A. SPEAKER
MOTORIZED DAMPER
EXISTING DEVICES
EXISTING DUPLEX RECEPTACLE
EXISTING LIGHT SWITCH TO REMAIN
EXISTING PA SPEAKER
EXISTING TELEPHONE OUTLET
EXISTING DATA OUTLET
COPPER
SWITCH
WALL MOUNTED OUTLET
HOT WATER BOILER
HOT WATER PUMP
MINIMUM CIRCUIT AMPS
FULL LOAD AMPS
ELECTRIC HEATER
UNIT VENTILATOR
UNIT HEATER
UV
UH
HWP
HWB
S
FLA
EH
MCA
CU
W
ABOVE FINISHED FLOOR
TIME CLOCK #1
ELECTRIC METALLIC TUBING
PLUMBING CONTRACTOR
WEATHERPROOF
EMERGENCY LIGHT
NIGHT LIGHT
POLYVINYL CHLORIDE
FAX MACHINE OUTLET
RIGID GALVANIZED STEEL
HEATING CONTRACTORH.C.
PVC
RGS
WP
F
NL
EM
P.C.
TC-1
EMT
AFF
CONDUIT
ROOFTOP UNIT
EXHAUST FAN
AIR HANDLING UNIT
WATER HEATER
REMOTE INDICATING LIGHT
ELECTRIC WATER COOLER
WH
RMI
RTU
EF
EWC
C
AHU
E.C. ELECTRICAL CONTRACTOR
G.C. GENERAL CONTRACTOR
GROUNDGND
MCB MAIN CIRCUIT BREAKER
MAIN LUG ONLYMLO
EXISTING FLUORESCENT LIGHT FIXTURE
EXISTING EXIT LIGHT
EXISTING EMERGENCY FIXTURE
EXISTING DOWNLIGHT
EXISTING PANELBOARD
EXISTING DISCONNECT SWITCH
MOTOR
GROUND
OCCUPANCY SENSOR
EXISTING TELE/DATA OUTLET
GENERAL PURPOSE RECEPTACLEGPR
DEMOLITION
EXISTING TO BE DEMOLISHED DUPLEX RECEPTACLE
EXISTING TO BE DEMOLISHED LIGHT SWITCH TO REMAIN
EXISTING TO BE DEMOLISHED F.A. STROBE TO BE REMOVED
EXISTING TO BE DEMOLISHED F.A. HORN/STROBE TO BE REMOVED
EXISTING TO BE DEMOLISHED PA SPEAKER
EXISTING TO BE DEMOLISHED TELEPHONE OUTLET
EXISTING TO BE DEMOLISHED FIRE ALARM MANUAL PULL STATION
EXISTING TO BE DEMOLISHED DUCT DETECTOR
EXISTING TO BE DEMOLISHED SMOKE DETECTOR
EXISTING TO BE DEMOLISHED DATA OUTLET
EXISTING TO BE DEMOLISHED FLUORESCENT LIGHT FIXTURE
EXISTING TO BE DEMOLISHED EXIT LIGHT
EXISTING TO BE DEMOLISHED DOWNLIGHT
EXISTING TO BE DEMOLISHED DISCONNECT SWITCH
EXISTING TO BE DEMOLISHED TELE/DATA OUTLET
CEILING MOUNTED SPEAKER
WIRELESS ACCESS POINT (1) CAT6 CABLE
SMARTBOARD CONNECTION
EXISTING CARD READER
DURESS ANTENNA
ROBOTIC DELIVERY ANTENNA
MICROPHONE JACK
PA SPEAKER VOLUME CONTROL
C
WP
F P W
A 2b
OR
DEMOLITION NOTES:
1. THE DEMOLITION DRAWINGS ARE DERIVED FROM FIELD OBSERVATIONS AND EXISTING DRAWINGS. THIS CONTRACTOR SHALL BE
RESPONSIBLE FOR ALL ELECTRICAL DEMOLITION WORK REQUIRED FOR THE INSTALLATION OF NEW ELECTRICAL WORK AND WORK
REQUIRED BY OTHER TRADES.
2. THE ELECTRICAL CONTRACTOR SHALL NOTE ANY EXISTING DAMAGE ON CEILING TILES, LIGHT FIXTURES, WALLS, FLOORS, FURNITURE,
PAVING, ETC. PRIOR TO THE START OF ANY WORK. THE CONTRACTOR SHALL PHOTOGRAPH THESE ITEMS AND SUBMIT THEM TO THE
ENGINEER BEFORE BEGINNING WORK.
3. ALL EXISTING CEILING TILES TO REMAIN WHICH ARE DAMAGED BY THIS CONTRACTOR DURING CONSTRUCTION SHALL BE REPLACED WITH
NEW CEILING TILES (MATCHING EXISTING) AT THIS CONTRACTOR'S EXPENSE.
4. ALL LIGHT FIXTURES, RECEPTACLES, FIRE ALARM DEVICES, ETC. TO BE REMOVED SHALL HAVE OPENINGS PATCHED TO MATCH EXISTING
CONDITIONS. ALL CUTTING AND PATCHING OF ELECTRICAL WORK SHALL BE BY THE ELECTRICAL CONTRACTOR.
5. ALL DEMO'D CIRCUITS WITH NO REMAINING LOAD SHALL BE RE-LABELED "SPARE" IN EXISTING PANELS.
6. THE ELECTRICAL CONTRACTOR SHALL BE RESPONSIBLE FOR MOVING AND PROTECTING ALL OWNER OWNED FURNITURE, EQUIPMENT ETC.
AS REQUIRED TO PERFORM THE WORK OF THIS PROJECT.
7. THE ELECTRICAL CONTRACTOR SHALL DISPOSE OF ALL DEMOLISHED EQUIPMENT EXCEPT WHERE NOTED OTHERWISE.
8. WHEN A DEVICE IS REMOVED THE ELECTRICAL CONTRACTOR SHALL PROVIDE ALL REQUIRED CIRCUITRY TO MAINTAIN CONTINUITY OF ALL
DOWNSTREAM DEVICES TO REMAIN.
DUPLEX RECEPTACLE, NEMA 5-20R (20A) (5362 SERIES) "C"DENOTES OVER COUNTER MOUNTING HEIGHT, SEE SPEC
C
GROUND FAULT PROTECTED DUPLEX RECEPTACLE (20A) NEMA5-20R WEATHERPROOF OUTLET BOX
30A DISCONNECT SWITCH, NEMA 1, NF, RATING
HOMERUN TO PANEL (ALL CONDUCTORS ARE #10, UNLESS NOTED) GROUND NEUTRAL HOT PARTIAL CIRCUIT
TELEPHONE OUTLET JACK WALL PHONE, 46" AFF PAY PHONE (PUBLIC), 44" AFF FAX
DATA/COMMUNICATIONS NUMBER INDICATES CABLE QUANTITY, PROVIDE (4) CAT6 CABLES IF NO NUMBER IS SHOWN LETTER DENOTES OVER COUNTER HEIGHT
CONCEALED CONDUIT TURNS UP TURNS DOWN
LAY-IN LED SHADING DENOTES EMERGENCY CIRCUITING AND NIGHT LIGHT REQUIREMENTS
DOWN LIGHT OR LED HIGH BAY SHADING DENOTES EMERGENCY CIRCUITING
LIGHTING CALLOUT DENOTES SWITCH LEG NO. DENOTES CIRCUIT LETTER DENOTES FIXTURE TYPE
MD
P.C.
OR
1. INSTALL ELECTRICAL SYSTEM IN ACCORDANCE WITH ALL STATE CODES, LOCAL CODES AND N.E.C. 2014 AND ITS APPENDICES, UNLESS
OTHERWISE DIRECTED SPECIFICALLY BY THESE PLANS.
2. FOR CLARITY, ONLY EXISTING LIGHT FIXTURES, SWITCHES, RECEPTACLES, ETC. ARE SHOWN WHICH ARE PERTINENT TO THIS WORK.
3. FOR CLARITY, THE QUANTITY OF BRANCH CIRCUIT CONDUCTORS ARE NOT SHOWN. CONTRACTOR SHALL BE RESPONSIBLE FOR
PROVIDING ALL BRANCH CIRCUITRY. RECORD AS-BUILT CIRCUIT PATHS AND PRESENT DRAWINGS FOR ENGINEER VERIFICATION WHEN
REQUESTED BY ENGINEER.
4. EXISTING CIRCUITS WITH NEW OR REVISED LOADS SHALL HAVE THE CIRCUIT DIRECTORY UPDATED TO REFLECT NEW LOAD.
5. EXACT HEIGHT OF DEVICES DESIGNATED AS OVER COUNTER SHALL BE COORDINATED WITH CASEWORK AND FURNITURE DRAWINGS.
6. REFER TO ARCHITECTURAL SHEETS FOR ALL FIRE-RATED PARTITION LOCATIONS AND RATINGS.
7. PROVIDE FIRE SEAL AROUND CONDUITS ON ALL CORE-DRILLED FLOOR AND FIRE-RATED WALL PENETRATIONS. CONTRACTOR IS
RESPONSIBLE FOR ALL CORE-DRILLS REQUIRED FOR INSTALLATION OF ELECTRICAL WORK.
8. PRIOR TO CORE DRILLING OR DESTRUCTIVE REMOVAL OF EXISTING FLOOR AREAS, THE ELECTRICAL CONTRACTOR SHALL COORDINATE
EXACT LOCATION WITH OWNER AND ELECTRONICALLY SCAN FLOOR FOR EXISTING CIRCUITRY, PIPING, ETC, WHICH MAY BE
ENCOUNTERED AND BRING POTENTIAL CONFLICTS TO THE ATTENTION OF THE ENGINEER WHERE IN CONFLICT WITH ELECTRICAL
INSTALLATION.
9. ROUTING OF CIRCUITRY INSTALLED IN CASEWORK, LAB TABLES, CABINETRIES, ETC. SHALL BE COORDINATED FOR PROPER
CONCEALMENT AND FUNCTION OF CASEWORK, LAB TABLES, CABINETRIES, ETC.
10. VERIFY THE LOCATION OF ALL UTILITIES PRIOR TO DRILLING OR CUTTING.
11. IN THE SPACE ABOVE THE CEILING USED AS A RETURN AIR PLENUM, THE ELECTRICAL CONTRACTOR SHALL ENSURE THAT ALL
ELECTRICAL WIRING, CABLES, BUSHINGS AND CABLE TIES ARE PLENUM RATED.
12. THE ELECTRICAL CONTRACTOR SHALL PROVIDE ALL ACCESS PANELS REQUIRED FOR ELECTRICAL WORK.
13. ALL PATCHING AND PAINTING REQUIRED FOR THE INSTALLATION OF NEW ELECTRICAL WORK SHALL BE BY THE ELECTRICAL
CONTRACTOR. PATCHING AND PAINTING SHALL MATCH ADJACENT CONDITIONS.
14. ALL EXPOSED METAL CONDUITS ARE TO BE PAINTED TO MATCH THE ADJACENT SURFACE. PAINTING OF CONDUIT IS TO BE BY THE
ELECTRICAL CONTRACTOR.
15. ELECTRICAL CONTRACTOR SHALL BE RESPONSIBLE FOR PROVIDING ALL REQUIRED JUNCTION BOXES, PULL BOXES, ETC. FOR A
COMPLETE INSTALLATION PER THE N.E.C. AND LOCAL CODES.
16. ALL CONDUCTORS AND EQUIPMENT LUGS SHALL BE RATED FOR 90 DEGREE CELSIUS.
17. ALL ITEMS INCLUDED ON THESE DRAWINGS AND THE SPECIFICATIONS SHALL BE INCLUDED IN THE CONTRACTORS BID. ANY ITEMS THAT
ARE UNCLEAR OR FOUND TO BE INCORRECT BY THE CONTRACTOR SHALL BE BROUGHT TO THE ATTENTION OF THE
ARCHITECT/ENGINEER AT LEAST 7 CALENDAR DAYS PRIOR TO THE BID DUE DATE.
18. COORDINATE WORK WITH OTHER TRADES. COORDINATION OR SCHEDULING SHALL BE THE RESPONSIBILITY OF THE INVOLVED
CONTRACTORS.
19. ALL CIRCUIT DIRECTORIES SHALL BE COORDINATED WITH OWNER FOR CORRECT CALL-OUT OF ROOM NUMBERS/ROOM NAMES.
20. IN AREAS WHERE SYSTEM CABLING GOES THROUGH CMU WALLS THE ELECTRICAL CONTRACTOR SHALL PROVIDE 3/4" CONDUIT STUB
(MINIMUM) FOR ROUTING OF CABLES. ELECTRICAL CONTRACTOR TO SEAL AROUND CONDUIT OPENING.
GENERAL NOTES:
LIGHTING AND POWER NOTES:
1. LIGHT FIXTURES DESIGNATED AS "NIGHT LIGHTS" SHALL BE ON UNSWITCHED CIRCUIT, UNLESS NOTED.
2. LIGHT FIXTURES DESIGNATED AS "EMERGENCY LIGHTS" SHALL BE SWITCHED AND PROVIDED WITH EMERGENCY BALLAST ON UNSWITCHED
CIRCUIT (SAME CIRCUIT AS SWITCH LEG), UNLESS NOTED.
3. EXIT SIGNS SHALL BE ON UNSWITCHED CIRCUIT, UNLESS NOTED.
4. ALL RECESSED DOWNLIGHTS MOUNTED IN GRID CEILING SHALL BE CENTERED IN CEILING TILE, UNLESS NOTED.
5. IN ALL MECHANICAL ROOMS COORDINATE EXACT LOCATION OF LIGHT FIXTURES WITH HVAC DUCTWORK.
6. CONDUCTORS FOR BRANCH CIRCUITRY ARE #12 AWG, UNLESS NOTED.
7. ALL HOMERUN CONDUCTORS BACK TO PANEL SHALL BE #10 AWG, UNLESS NOTED. ALL SWITCHES AND RECEPTACLES DESIGNATED TO BE
RELOCATED SHALL BE PROVIDED WITH NEW DEVICE AND COVER PLATE.
8. PROVIDE A GREEN GROUND CONDUCTOR IN ALL BRANCH CIRCUITRY. REFER TO SPECS FOR OTHER GROUNDING CONDUCTOR TYPES.
9. PROVIDE A DEDICATED NEUTRAL CONDUCTOR FOR ALL SINGLE PHASE CIRCUITS.
10. ALL CONDUIT DROPS FOR PLENUM RATED CABLES SHALL BE PROVIDED WITH A CONDUIT BUSHING ABOVE THE CEILING.
11. WHERE TERMINATED IN A J-BOX ALL SPARE CIRCUITRY SHALL BE LABELED WITH PANEL AND CIRCUIT NUMBER.
12. COORDINATE WITH MECHANICAL CONTRACTOR AND PROVIDE ALL NECCESSARY AUXILIARY CONTACTS, RELAY, ETC. IN MOTOR STARTERS
FOR REQUIRED CONTROL OF MECHANICAL EQUIPMENT.
13. WHEN A DEVICE IS REMOVED AND RE-INSTALLED, DEVICE SHALL BE CLEANED BEFORE RE-INSTALLATION.
14. ALL LIGHT FIXTURES TO BE SUPPORTED BY SUPPORT WIRES DIRECTLY FROM STRUCTURE ABOVE AND NOT FROM CEILING GRID SUPPORTS.
CONDUIT AND CIRCUITRY TO BE SUPPORTED INDEPENDANTLY AND NOT FROM LIGHT FIXTURE SUPPORT WIRES.
15. ALL GFI TYPE RECEPTACLES TO BE INSTALLED AS SEPARATELY CONNECTED RECEPTACLES. FEED-THROUGH OR GFI TYPE BREAKERS NOT
ALLOWED UNLESS NOTED OTHERWISE.
16. COORDINATE IN-FLOOR OUTLETS WITH SYSTEM PLANS. MANY FLOOR POWER OUTLETS TO HAVE TELE/DATA OUTLETS ADJACENT TO THEM.
USE DIVIDED MULTI-OUTLET ASSEMBLIES TO FACILITATE CLEANER INSTALLATION APPEARANCE.
17. ALL DASHED CIRCUITRY IS ROUTED BELOW FLOOR SLAB.
18. HEAT LOOPS (#18 GA. WITH GROUND) MAY BE USED FOR A FEED TO A SINGLE LIGHT FIXTURE UNIT ONLY. HEAT LOOPS FEEDING MULTIPLE
LIGHT FIXTURES MAY NOT BE USED.
MOUNTING HEIGHT - TO TOP OF DEVICE (UNLESS NOTED):COORDINATE MOUNTING HEIGHTS WITH ARCHITECTURAL PLANS AND ELEVATIONS.
1. RECEPTACLES MOUNTED AT 18" AFF, UNLESS NOTED.
2. SWITCHES MOUNTED AT 48" AFF, UNLESS NOTED.
3. TELEPHONE OUTLETS MOUNTED AT 18" AFF, UNLESS NOTED.
4. WALL TELEPHONE OUTLETS MOUNTED AT 48" AFF, UNLESS NOTED.
5. DATA OUTLETS MOUNTED AT 18" AFF, UNLESS NOTED.
6. OUTLETS MOUNTED AT 80" AFF, UNLESS NOTED.
7. "C" DEVICES TO BE MOUNTED ABOVE COUNTER AND BACKSPLASH. COORDINATE WITH ARCHITECTURAL DRAWINGS AND APPROVED SHOP
DRAWINGS FOR CASEWORK.
OR
TOGGLE SWITCH OCCUPANCY SENSOR KEYED 4-WAY 3-WAY DIMMER
2
Drawn
THE ARCHITECT EXPRESSLY RESERVESHIS COMMON LAW AND STATUTORY LAWCOPYRIGHTS AND OTHER PROPERTYRIGHTS FOR THESE "ARCHITECTURALWORKS" AND "TECHNICAL DOCUMENTS"AND ANY DERIVITIVES THEREOF. THESEDRAWINGS AND DOCUMENTS ARE NOTTO BE REPRODUCED, CHANGED ORCOPIED IN ANY MANNER WHATSOEVERFOR ANY USE WITHOUT FIRST OBTAININGTHE EXPRESS WRITTEN CONSENT OFLOUIS G. CHIODINI, CHIODINI ASSOCIATES,NOR ARE THEY TO BE ASSIGNED TO ANYPARTY WITHOUT FIRST OBTAINING SAIDWRITTEN PERMISSION AND CONSENT.
C COPYRIGHT PENDING
Architecture / Interior Design / Graphics
1401 S. Brentwood Blvd. / Suite 575 / St. Louis, Missouri 63144
314-725-5588 / [email protected]
©
Revisions: Date
ENGINEERS/CONSULTANTS:
CheckedDate
Location
Project Title Project Number
Building Number
Drawing NumberApproved: Project Director
Drawing Title
5
ARCHITECT:SEAL
WOOLPERT, INC.343 FOUNTAINS PARKWAYSUITE 100FAIRVIEW HEIGHTS, IL 62208314-436-0865314-436-0884 fax
SCI ENGINEERING, INC130 POINT WEST BLVD.ST. CHARLES, MO 63301636-949-8200636-949-8269 fax
VA FORM 08-6231
one e
ighth
inch =
one foot
one q
uart
er
inch =
one foot
thre
e e
ighth
s inch =
one foot
one h
alf inch =
one foot
thre
e q
uart
ers
inch =
one foot
one inch =
one foot
one a
nd o
ne h
alf inches =
one foot
thre
e inches =
one foot
6"
10
6"
20
6"
20
6"
40
40
84
016
84
0
438-16-104
1 2 3 4 5 6 7 8 9
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
A
B
C
D
E
F
100% SUBMITTAL
Department ofVeterans Affairs
C:\_R
evit L
ocal F
iles\0
76966_S
ioux F
alls
VA
Chapel_
ELE
C_C
entr
al_
2016_lu
ke.k
istn
er@
woolp
ert
.com
.rvt
Scale: 12" = 1'-0"
3/1
3/2
017 8
:49:0
3 A
M
E-001
LEGEND AND GENERALNOTES
VA HEALTH CARE SYSTEM
LIK2017.03.13
2016.052
VAS 438-16-104 BLDG. 5 CHAPELSIOUX FALLS, SD 57105
Approver
KMM
Owner
WAP
WAP
J
JJ
4
4
J
WAP
4
OS4
4
J
4
CATV
WAP
PA
PA
PA
4
PA
15
PA
SP SP
SP SP
SP SP
M M
M M
M M
J
J
J
PA
PA
24
WAP
F
J
RT
LR
TL
RT
LR
TL
RT
L
DA
DA
DA
PA
CR
J M
M
PA
SB
SB SB
V
SP
DH
DH
WAP
4
4
24
4
2
2
2
2
2
2
2
24
2
44
2 42
4
44
44
24
4
2 2
44
4
RD
RS
RS
2
2
4
2
G
C
D01
D02
P5
EC
D03
D03
D03
D03
D03
D06
D06
D04
D04
D05
D05
D06
D04
D06
EXISTINGEXHAUST FANTO REMAIN
CU
-1
CU
-2
AHU
-
AHU
1
VAV
DEMO
VAV
DEMO
VAV
DEMO
VAV
DEMO
VAV
DEMO
RF
1
D07
D06
D06
D08
D06
D07
D14
D07 D07
UH
DEMO
D09
D11
D13
(TYP)
D12
D16
D15
D17
D10
D05
1. CUT OFF 1" BELOW FLOOR SURFACE AND GROUT IN ANY EXISTING CONDUITPENETRATIONS THROUGH FLOORS WHERE WALLS ARE REMOVED.
2. REFER TO THE GENERAL CONTRACTOR'S "DEMOLITION PLAN" FOR PROCESS ANDPROCEDURES RELATED TO DEMOLITION, SAFETY, AND EMERGENCYPROCEDURES.
3. REFER TO MECHANICAL DEMOLITION PLANS FOR EQUIPMENT TO BEDISCONNECTED AND MADE SAFE BY ELECTRICAL CONTRACTOR, FOR REMOVALBY MECHANICAL CONTRACTOR OR DEMOLITION CONTRACTOR.
4. EXISTING MECHANICAL, ELECTRICAL, AND PLUMBING SYSTEMS WHICH SERVEPORTIONS OF THE BUILDING WHICH ARE OUTSIDE THE SCOPE OF WORK OF THISCONTRACT SHALL REMAIN ACTIVE AT ALL TIMES. IF IT IS DEEMED NECESSARY TOTEMPORARILY DISRUPT ANY ELECTRICAL, PLUMBING, OR MECHANICALSERVICES, IT SHALL BE THE CONTRACTOR'S RESPONSIBILITY TO COORDINATETHE SCHEDULE FOR DISRUPTION OF SERVICE WITH THE OWNER. THE OWNER'SSCHEDULES WILL DICTATE THE CONTRACTOR'S SCHEDULE FOR SYSTEMS SHUT-DOWN.
5. THE BUILDING'S FIRE ALARM SYSTEM SHALL REMAIN OPERATIONAL THROUGHOUTTHE PROJECT. COORDINATE WITH OWNER FOR BRIEF PERIODS WHEN REQUIREDMODIFICATIONS REQUIRE DEACTIVATION OF THE SYSTEM. UPON REMOVAL OFFIRE ALARM DEVICES, PROVIDE MODIFICATION OF FIRE ALARM SYSTEMPROGRAMMING TO REFLECT CHANGES.
6. ALL EXISTING LAMPS AND BALLASTS ARE TO BE REMOVED AND DISPOSED OFPROPERLY PER EPA REQUIREMENTS FOR MERCURY AND PCB'S.
7. ALL EXISTING ELECTRICAL PANELS ARE TO REMAIN UNLESS OTHERWISE NOTED,EVEN WITHIN WALLS RECEIVING NEW FINISHES.
Drawn
THE ARCHITECT EXPRESSLY RESERVESHIS COMMON LAW AND STATUTORY LAWCOPYRIGHTS AND OTHER PROPERTYRIGHTS FOR THESE "ARCHITECTURALWORKS" AND "TECHNICAL DOCUMENTS"AND ANY DERIVITIVES THEREOF. THESEDRAWINGS AND DOCUMENTS ARE NOTTO BE REPRODUCED, CHANGED ORCOPIED IN ANY MANNER WHATSOEVERFOR ANY USE WITHOUT FIRST OBTAININGTHE EXPRESS WRITTEN CONSENT OFLOUIS G. CHIODINI, CHIODINI ASSOCIATES,NOR ARE THEY TO BE ASSIGNED TO ANYPARTY WITHOUT FIRST OBTAINING SAIDWRITTEN PERMISSION AND CONSENT.
C COPYRIGHT PENDING
Architecture / Interior Design / Graphics
1401 S. Brentwood Blvd. / Suite 575 / St. Louis, Missouri 63144
314-725-5588 / [email protected]
©
Revisions: Date
ENGINEERS/CONSULTANTS:
CheckedDate
Location
Project Title Project Number
Building Number
Drawing NumberApproved: Project Director
Drawing Title
5
ARCHITECT:SEAL
WOOLPERT, INC.343 FOUNTAINS PARKWAYSUITE 100FAIRVIEW HEIGHTS, IL 62208314-436-0865314-436-0884 fax
SCI ENGINEERING, INC130 POINT WEST BLVD.ST. CHARLES, MO 63301636-949-8200636-949-8269 fax
VA FORM 08-6231
one e
ighth
inch =
one foot
one q
uart
er
inch =
one foot
thre
e e
ighth
s inch =
one foot
one h
alf inch =
one foot
thre
e q
uart
ers
inch =
one foot
one inch =
one foot
one a
nd o
ne h
alf inches =
one foot
thre
e inches =
one foot
6"
10
6"
20
6"
20
6"
40
40
84
016
84
0
438-16-104
1 2 3 4 5 6 7 8 9
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
A
B
C
D
E
F
100% SUBMITTAL
Department ofVeterans Affairs
C:\_R
evit L
ocal F
iles\0
76966_S
ioux F
alls
VA
Chapel_
ELE
C_C
entr
al_
2016_lu
ke.k
istn
er@
woolp
ert
.com
.rvt
Scale:As indicated
3/1
3/2
017 8
:49:1
2 A
M
ED-001
THIRD FLOOR ELECTRICALDEMOLITION PLAN
VA HEALTH CARE SYSTEM
LIK2017.03.13
2016.052
VAS 438-16-104 BLDG. 5 CHAPELSIOUX FALLS, SD 57105
Approver
KMM
Owner
1/8" = 1'-0"
THIRD FLOOR ELECTRICAL DEMOLITION PLAN
D01 ALL ELECTRICAL ITEMS WITHIN BORDERED AREA TO BE REMOVEDIN THEIR ENTIRETY AND CIRCUITRY REMOVED BACK TO SOURCEUNLESS NOTED OTHERWISE. POWER AND VARIOUS LOWVOLTAGE CABLING WHICH SERVES FLOOR ABOVE OR SPACEOTHERWISE OUTSIDE THE ARE OF WORK MAY BE PRESENT INTHE AREA AND MUST REMAIN IN SERVICE AND PROTECTED ATALL TIMES DURING CONSTRUCTION.
D02 NO WORK IN HATCHED AREA, UNLESS CIRCUITRY OR CABLINGSERVING DEMOLISHED AREA PASSES THROUGH IT. REMOVESUCH CIRCUITRY WITH CARE TO NOT CAUSE DISTURBANCE OFTHE FINISHED SPACE.
D03 EXISTING REAL TIME LOCATOR ANTENNA. REMOVE AND RETURNTO OWNER.
D04 EXISTING DURESS SYSTEM ANTENNA TO BE REMOVED BY VA.COORDINATE WITH VA.
D05 EXISTING WIRELESS ACCESS POINT. REMOVE FROM CEILING ANDTEMPORARILY SUPPORT IN CEILING SPACE DURINGCONSTRUCTION. PROTECT CABLING SERVING IT.
D06 EXISTING PA SYSTEM SPEAKER TO BE TIED UP IN CEILING SPACEDURING CONSTRUCTION FOR REINSTALLATION IN NEW CEILING.
D07 DISCONNECT EXISTING MECHANICAL EQUIPMENT AND REMOVECIRCUITRY BACK TO SOURCE.
D08 REMOVE EXISTING CARD READER AND REQUEST TO EXIT DEVICEWITHIN CLOSET AND RETURN TO OWNER.
D09 EXISTING ROBOTIC DELIVERY ANTENNA SYSTEM. REMOVE FROMWALL AND TEMPORARILY SUPPORT IN CEILING SPACE DURINGCONSTRUCTION. PROTECT CABLING SERVING IT.
D10 EXISTING 12"X4" CABLETRAY IN CORRIDOR CEILING TO REMAIN.CABLING WITHIN TO BE REPLACED PER NOTE D11. CABLETRAYNOT SHOWN FOR CLARITY PURPOSES.
D11 EXISTING DATA AND TELEPHONE CABLING SERVINGRESPIRATORY CARE CLINIC TO BE REPLACED AND REROUTED TOEXISTING 2ND FLOOR IT ROOM. SEE SHEET E-301.
D12 COORDINATE REPAIR OF EXTERIOR WALL WHERE CONDUITS ANDDISCONNECTS SERVING CONDENSING UNITS ARE REMOVED.
D13 REMOVE EXISTING LIGHTING FIXTURES FROM CEILING ASREQUIRED FOR VAV HEATING COIL REPLACEMENT. REINSTALLLIGHTS.
D14 EXISTING SMARTBOARD SYSTEM, SPEAKERS, AND MICROPHONESTO BE REMOVED IN ITS ENTIRETY BY OWNER'S CURRENTSMARTBOARD SERVICE CONTRACTOR AS A SUBCONTRACT TOELECTRICAL CONTRACTOR. TURN ALL COMPONENTS OVER TO VAFOR STORAGE.
D15 EXISTING COMMUNICATIONS CABLING AND EQUIPMENT TO BEREMOVED AND RELOCATED/RE-ROUTED TO EXISTING IT ROOM ONFLOOR BELOW. COORDINATE RE-ROUTING AND RELOCATINGWITH VA IT DEPARTMENT.
D16 IDENTIFY AND TRACE EXISTING CABLING WHICH TRANSMITS THECHAPEL BROADCAST TO THE VA FACILITY - WIDE TVDISTRIBUTION SYSTEM UP TO WHERE IT LEAVES THE THIRDFLOOR WEST WING. PROTECT THE CABLING THROUGHOUT THECONSTRUCTION PROCESS FOR REUSE WITH NEW A/VEQUIPMENT. REARRANGE/RE-ROUTE CABLING AS NEEDED TOACCOMMODATE DEMOLITION AND NEW EQUIPMENTINSTALLATION.
D17 POWER CONNECTION FOR ELECTRIC WATER COOLER TO REMAIN.
GENERAL NOTES
KEYED NOTES
PLANNORTH
4'0 8' 16'
REF.
D
OS
D
D
D
D
D
D
D
OS
OS
OS
OS
OS
OS
OS
OS
D D
D
OS
OS
OS
D
OS
OS
OS
OS
OS
OS
OS
OS
OS
OS
OSOS
OS
RACK
VENDOR VENDOR
RACK
S4
A
UPD
N
J
J
RACK
VENDOR VENDOR
RACK
S4
A
UPD
N
J
J
1 2 3 4
A
B
C
D
E
F
G
H
KK.2
1.3 1.9 3.1 3.9
H.9
G.5
5
PULM. FUNC.LAB
348A
EXAM348
EXAM345
WAITING346
ELEV.EQUIP.
350
VIRT. TELE349G
EXAM346A
VIEW347A
OFFICE349H
GROUPCPAP
351E
OFF.346B
OFF.346C
STAIR #6348D
CONFERENCE351
ADA BATH351D
OFFICE349F
OFFICE349E
STORAGE349A
GRIEVE349B
CORRIDOR397
ADA BATH351A
OPENOFFICE
349C
LOCKER/BREAK351C
PULM./ RTWORK
351B
2A
2A
2A
2A
2A
6A
6A
6AB
6A
6A
6A
6A
6A
6A
8AA
12A 6
A 6A
12A
12A
8AA
12A
12A
8AA
12A
8AA
2A
2A
4B 4
B 4B
4B
4B
4B 4
B 4B
4B
4B
4B
4B
2A
6A
6A
6A
2A
2A
2AC
2A
2AC
2A
2AC
2A
2A
2A
6A
6A
6A
6A
12A
8E
8E
8E
8E
P5
EC
C
G
8E
4B
4B
4B
4B
4B 4
B
6AB
4B
2AB
6AB
- 4C
- 2C
- 6G
4C
4C
4C
4C 4
C
4C
abc
111
103
101
aa
aa
a
a
a
a
aa a a
a
b
b b bd
d
c
c c
c
c c
CHECK IN347
WAIT301B
d
4C
b
104
12D
12A
- 8EC
- 12C
STORAGE348B
EMS348C
CHAPEL349
A/V EQUIP.349D
CPAPOFFICE
351F
HOMEOXYGEN
351G
4C 4
Cb
b
d c b a
102
(TYP)
1. #10 AWG CONDUCTORS SHALL BE USED THROUGHOUT THE HOMERUNCONDUIT UNTIL THE FIRST LIGHTING LOAD FOR EACH CIRCUIT IS CONNECTED TO THEHOMERUN CONDUCTORS.
2. LIGHTING SWITCHES ON OPPOSITE SIDE OF PARTITIONS TO BE SEPARATEDLATERALLY WITH A STUD BETWEEN THEM TO CONTROL SOUND TRANSMISSION.
3. ALL PENETRATIONS THROUGH FIRE-RATED WALLS OR FLOORS TOPRESERVE RATING OF THE WALL OR FLOOR.
4. SHADED FIXTURES (2x4's, DOWNLIGHTS) IN CORRIDORS TO BE ONEMERGENCY POWER CIRCUIT AND TO FUNCTION AS A NIGHT LIGHT.
5. MOUNT EXIT SIGNS TO WALLS WHENEVER POSSIBLE. CEILING- MOUNTINGOF EXIT SIGNS SHOULD BE BY EXCEPTION, WHERE THERE IS NO PRACTICAL WALLAVAILABLE.
105
(TYP)
106
(TYP)107 109
108
110
Drawn
THE ARCHITECT EXPRESSLY RESERVESHIS COMMON LAW AND STATUTORY LAWCOPYRIGHTS AND OTHER PROPERTYRIGHTS FOR THESE "ARCHITECTURALWORKS" AND "TECHNICAL DOCUMENTS"AND ANY DERIVITIVES THEREOF. THESEDRAWINGS AND DOCUMENTS ARE NOTTO BE REPRODUCED, CHANGED ORCOPIED IN ANY MANNER WHATSOEVERFOR ANY USE WITHOUT FIRST OBTAININGTHE EXPRESS WRITTEN CONSENT OFLOUIS G. CHIODINI, CHIODINI ASSOCIATES,NOR ARE THEY TO BE ASSIGNED TO ANYPARTY WITHOUT FIRST OBTAINING SAIDWRITTEN PERMISSION AND CONSENT.
C COPYRIGHT PENDING
Architecture / Interior Design / Graphics
1401 S. Brentwood Blvd. / Suite 575 / St. Louis, Missouri 63144
314-725-5588 / [email protected]
©
Revisions: Date
ENGINEERS/CONSULTANTS:
CheckedDate
Location
Project Title Project Number
Building Number
Drawing NumberApproved: Project Director
Drawing Title
5
ARCHITECT:SEAL
WOOLPERT, INC.343 FOUNTAINS PARKWAYSUITE 100FAIRVIEW HEIGHTS, IL 62208314-436-0865314-436-0884 fax
SCI ENGINEERING, INC130 POINT WEST BLVD.ST. CHARLES, MO 63301636-949-8200636-949-8269 fax
VA FORM 08-6231
one e
ighth
inch =
one foot
one q
uart
er
inch =
one foot
thre
e e
ighth
s inch =
one foot
one h
alf inch =
one foot
thre
e q
uart
ers
inch =
one foot
one inch =
one foot
one a
nd o
ne h
alf inches =
one foot
thre
e inches =
one foot
6"
10
6"
20
6"
20
6"
40
40
84
016
84
0
438-16-104
1 2 3 4 5 6 7 8 9
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
A
B
C
D
E
F
100% SUBMITTAL
Department ofVeterans Affairs
C:\_R
evit L
ocal F
iles\0
76966_S
ioux F
alls
VA
Chapel_
ELE
C_C
entr
al_
2016_lu
ke.k
istn
er@
woolp
ert
.com
.rvt
Scale:As indicated
3/1
3/2
017 8
:49:0
6 A
M
E-101
SECOND & THIRD FLOORLIGHTING PLANS
VA HEALTH CARE SYSTEM
Author2017.03.13
2016.052
VAS 438-16-104 BLDG. 5 CHAPELSIOUX FALLS, SD 57105
Approver
Checker
Owner
1/8" = 1'-0"
THIRD FLOOR LIGHTING PLAN
101 ACTIVATION OF ANY OCCUPANCY SENSOR IN CORRIDOR TO TURNON ALL LIGHTS IN CORRIDOR.
102 PROVIDE (4) WALL BOX DIMMING SWITCHES IN CHAPEL FORLIGHTS, (A) FOR SEATING AREA, (B) FOR SEATING AREA SCONCES,(C) FOR ALTAR AREA, (D) FOR ALTAR SCONCES.
103 ACTIVATION OF ANY OCCUPANCY SENSOR IN CHAPEL TO TURNON ALL TYPE B LIGHTS IN CHAPEL. TYPE C LIGHTS TO BE ON 24/7FOR CHAPEL OPERATION.
104 REINSTALL EXISTING LIGHTS IN SAME LOCATIONS ANDRECONNECT TO EXISTING CIRCUITRY AFTER VAV COILS AREREPLACED IN RESPIRATORY CARE AREA.
105 REMOVE AND REINSTALL EXISTING LIGHTS TO FACILITATECEILING REMOVAL AND REINSTALLATION FOR PLUMBING WORK.TEMPORARILY SUPPORT LIGHTS IN PLACE WHILE CEILING ISGONE TO MAINTAIN FACILITY OPERATION.
106 REMOVE EXISTING LIGHTING FIXTURES AND REINSTALL INLOWERED CEILING IN DISHWASHING ROOM. EXTEND CIRCUITRYAS REQUIRED.
107 RELOCATE EXISTING EXIT SIGN ADJACENT TO DOORFRAME TOACCOMMODATE LOWERED CEILING. EXTEND CIRCUITRY ASREQUIRED.
108 RELOCATE EXISTING RECEPTACLE TO ACCOMMODATE LOWEREDCEILING. EXTEND CIRCUITRY AS REQUIRED.
109 ADJUST HEIGHT OF EXISTING JUNCTION BOX AS REQUIRED TOSUIT LOWERED CEILING. RE-SUPPORT BOX AND EXTENDCIRCUITRY AS REQUIRED.
110 REMOVE EXISTING LIGHT FIXTURE FOR REMOVAL OF CEILING.EXISTING CIRCUITRY TO REMAIN FOR REUSE. PROVIDE NEW TYPE'D' LIGHT FIXTURE CHAIN HUNG AT 10' AFF. CONNECT TO EXISTINGCIRCUITRY.
111 PROVIDE (4) 3-WAY SWITCHES FOR CONTROL OF CHAPEL LIGHTSIN CONJUNCTION WITH CEILING OCCUPANCY SENSORS ANDDIMMING SWITCHES.
GENERAL NOTES
KEYED NOTES
PLANNORTH
4'0 8' 16' 1/8" = 1'-0"
SECOND FLOOR LIGHTING PLAN
PLANNORTH
4'0 8' 16'