Transcript of Plc analog input output programming
![Page 2: Plc analog input output programming](https://reader031.fdocuments.in/reader031/viewer/2022013117/587054541a28aba2118b4f69/html5/thumbnails/2.jpg)
IntroductionThe G7F-ADHA is A/D-D/A Combination module for use with the GLOFA GM7and MASTER-K80S series. This module is to convert an analog input signal(voltage or current) from external sensors into a 12-bit signed Binary digitalvalue, and convert digital internal data to analog value (Voltage or Current)
![Page 3: Plc analog input output programming](https://reader031.fdocuments.in/reader031/viewer/2022013117/587054541a28aba2118b4f69/html5/thumbnails/3.jpg)
Input Specifications
![Page 4: Plc analog input output programming](https://reader031.fdocuments.in/reader031/viewer/2022013117/587054541a28aba2118b4f69/html5/thumbnails/4.jpg)
Output Specifications
![Page 5: Plc analog input output programming](https://reader031.fdocuments.in/reader031/viewer/2022013117/587054541a28aba2118b4f69/html5/thumbnails/5.jpg)
Names of parts and functions
![Page 6: Plc analog input output programming](https://reader031.fdocuments.in/reader031/viewer/2022013117/587054541a28aba2118b4f69/html5/thumbnails/6.jpg)
Special Data Register
A/D conversion value stores special data register as following.The table which is shown below is possible to use under the same or greater than K80S CPU ROM V1.3.
![Page 7: Plc analog input output programming](https://reader031.fdocuments.in/reader031/viewer/2022013117/587054541a28aba2118b4f69/html5/thumbnails/7.jpg)
parameter setting
![Page 8: Plc analog input output programming](https://reader031.fdocuments.in/reader031/viewer/2022013117/587054541a28aba2118b4f69/html5/thumbnails/8.jpg)
Wiring of voltage/current input
![Page 9: Plc analog input output programming](https://reader031.fdocuments.in/reader031/viewer/2022013117/587054541a28aba2118b4f69/html5/thumbnails/9.jpg)
Wiring of voltage/current Output
![Page 10: Plc analog input output programming](https://reader031.fdocuments.in/reader031/viewer/2022013117/587054541a28aba2118b4f69/html5/thumbnails/10.jpg)
ADC Characteristics (voltage input)
In voltage input, digital amount 0 is output by 0V input and 4,000 is output by 10V input. Therefore input 2.5mV equals to digital amount 1, but value less than 2.5mV can’t be converted.
![Page 11: Plc analog input output programming](https://reader031.fdocuments.in/reader031/viewer/2022013117/587054541a28aba2118b4f69/html5/thumbnails/11.jpg)
ADC Characteristics (Current input)
Current input 0mA becomes output 0, 10mA does 2000 and 20mA does 4000. Therefore input 5 ㎂ equals to digital amount 1, but value less tan 5 ㎂ can’t be converted. So abandon it.
![Page 12: Plc analog input output programming](https://reader031.fdocuments.in/reader031/viewer/2022013117/587054541a28aba2118b4f69/html5/thumbnails/12.jpg)
DAC Characteristics (Voltage Output)
Input of digital amount 0 outputs analog amount 0V, 4000 does 10V. Digital input 1 equals to 2.5mV of analog amount.
![Page 13: Plc analog input output programming](https://reader031.fdocuments.in/reader031/viewer/2022013117/587054541a28aba2118b4f69/html5/thumbnails/13.jpg)
DAC Characteristics (Current Output)
In current output, digital amount 0 exchanges to 0mA, and 4,000 does 20mA. Analogamount of digital input 1 equals to 5 ㎂.
![Page 14: Plc analog input output programming](https://reader031.fdocuments.in/reader031/viewer/2022013117/587054541a28aba2118b4f69/html5/thumbnails/14.jpg)
Examples
![Page 15: Plc analog input output programming](https://reader031.fdocuments.in/reader031/viewer/2022013117/587054541a28aba2118b4f69/html5/thumbnails/15.jpg)
Examples
![Page 16: Plc analog input output programming](https://reader031.fdocuments.in/reader031/viewer/2022013117/587054541a28aba2118b4f69/html5/thumbnails/16.jpg)
Examples (0-10VDC TO INVERTER)
Control an Induction motor/Inverter from HMI using PLC:
1. Interfacing PLC and Inverter with HMI2. Operation (ON/OFF the Inverter) Mode Selection3. Frequency Reference Selection (0-10VDC from PLC)4. Writing PLC Program for Analog output (0-10VDC/4-20mA)5. HMI Design for operation
Use Frequency Ref: 0-10VDC from G7F-ADHAUse Frequency Ref: 0-10VDC from G7F-ADHA
![Page 17: Plc analog input output programming](https://reader031.fdocuments.in/reader031/viewer/2022013117/587054541a28aba2118b4f69/html5/thumbnails/17.jpg)
Examples (0-10VDC TO INVERTER)
![Page 18: Plc analog input output programming](https://reader031.fdocuments.in/reader031/viewer/2022013117/587054541a28aba2118b4f69/html5/thumbnails/18.jpg)
Examples (0-10VDC TO INVERTER)Inverter Configuration (3/1)Inverter Configuration (3/1)
![Page 19: Plc analog input output programming](https://reader031.fdocuments.in/reader031/viewer/2022013117/587054541a28aba2118b4f69/html5/thumbnails/19.jpg)
Examples (0-10VDC TO INVERTER)Inverter Configuration (3/2)Inverter Configuration (3/2)
![Page 20: Plc analog input output programming](https://reader031.fdocuments.in/reader031/viewer/2022013117/587054541a28aba2118b4f69/html5/thumbnails/20.jpg)
Examples (0-10VDC TO INVERTER)Inverter Configuration (3/3)Inverter Configuration (3/3)
![Page 21: Plc analog input output programming](https://reader031.fdocuments.in/reader031/viewer/2022013117/587054541a28aba2118b4f69/html5/thumbnails/21.jpg)
Examples (0-10VDC TO INVERTER)PLC Program (Both for 0-10VDC/4-20mA)PLC Program (Both for 0-10VDC/4-20mA)
![Page 22: Plc analog input output programming](https://reader031.fdocuments.in/reader031/viewer/2022013117/587054541a28aba2118b4f69/html5/thumbnails/22.jpg)
HMI Design (Both for 0-10VDC/4-20mA)HMI Design (Both for 0-10VDC/4-20mA)
Examples(0-10VDC TO INVERTER)
![Page 23: Plc analog input output programming](https://reader031.fdocuments.in/reader031/viewer/2022013117/587054541a28aba2118b4f69/html5/thumbnails/23.jpg)
Examples(4-20mA TO INVERTER)
Control an Induction motor/Inverter from HMI using PLC:
1. Interfacing PLC and Inverter with HMI2. Operation (ON/OFF the Inverter) Mode Selection3. Frequency Reference Selection (4-20mA from PLC)4. Writing PLC Program for Analog output (0-10VDC/4-20mA)5. HMI Design for operation
Use Frequency Ref: 4-20mA from G7F-ADHAUse Frequency Ref: 4-20mA from G7F-ADHA
![Page 24: Plc analog input output programming](https://reader031.fdocuments.in/reader031/viewer/2022013117/587054541a28aba2118b4f69/html5/thumbnails/24.jpg)
Examples(4-20mA TO INVERTER)
![Page 25: Plc analog input output programming](https://reader031.fdocuments.in/reader031/viewer/2022013117/587054541a28aba2118b4f69/html5/thumbnails/25.jpg)
Examples(4-20mA TO INVERTER)Inverter Configuration (3/1)Inverter Configuration (3/1)
![Page 26: Plc analog input output programming](https://reader031.fdocuments.in/reader031/viewer/2022013117/587054541a28aba2118b4f69/html5/thumbnails/26.jpg)
Examples(4-20mA TO INVERTER)Inverter Configuration (3/2)Inverter Configuration (3/2)
![Page 27: Plc analog input output programming](https://reader031.fdocuments.in/reader031/viewer/2022013117/587054541a28aba2118b4f69/html5/thumbnails/27.jpg)
Examples(4-20mA TO INVERTER)Inverter Configuration (3/3)Inverter Configuration (3/3)
![Page 28: Plc analog input output programming](https://reader031.fdocuments.in/reader031/viewer/2022013117/587054541a28aba2118b4f69/html5/thumbnails/28.jpg)
Examples(4-20mA TO INVERTER)PLC Program (Both for 0-10VDC/4-20mA)PLC Program (Both for 0-10VDC/4-20mA)
![Page 29: Plc analog input output programming](https://reader031.fdocuments.in/reader031/viewer/2022013117/587054541a28aba2118b4f69/html5/thumbnails/29.jpg)
HMI Design (Both for 0-10VDC/4-20mA)HMI Design (Both for 0-10VDC/4-20mA)
Examples(4-20mA TO INVERTER)
![Page 30: Plc analog input output programming](https://reader031.fdocuments.in/reader031/viewer/2022013117/587054541a28aba2118b4f69/html5/thumbnails/30.jpg)
Topic-1. RESET DATA REGISTER DxxxTopic-1. RESET DATA REGISTER Dxxx
ADDITIONAL
When the Stop switch is pressed stop button then inverter goes stop but set frequency in last command does not reset.
Please find the below program in which Register D000 is reset by pressing T000 3S.
Think Clear !!!!
![Page 31: Plc analog input output programming](https://reader031.fdocuments.in/reader031/viewer/2022013117/587054541a28aba2118b4f69/html5/thumbnails/31.jpg)
????? QUESTIONS ?????
ADDITIONAL
1. Why G7F-ADHA is 12 bit?2. Why D4983 max value 4000?3. How can we got analog output from Inverter?4. How to interface Inverter output to PLC?5. How to Program PLC for Analog Input?
What is sol…. !!!!
![Page 32: Plc analog input output programming](https://reader031.fdocuments.in/reader031/viewer/2022013117/587054541a28aba2118b4f69/html5/thumbnails/32.jpg)
ATTACHMENT
ADDITIONAL
Documents AttachmentPLC Program (Both for 0-10VDC/4-20mA)
HMI Design (Both for 0-10VDC/4-20mA)New.PRJ
Inverter user Manual
G7F-ADHA user Manual
My Special Inverter Manual