Placas Planas

download Placas Planas

of 141

description

Análisis y armado de placas planas.

Transcript of Placas Planas

  • Flat Slab Design

  • Resources used for compiling this presenta4on are acknowledged

  • Flat Slab with drop panels

    Flat slab with column head

    Flat slab with drop panel and column head

    Flat Slab resting directly on columns 1. What is a flat slab?

    31.1 General The term flat slab means a reinforced concrete slab with or without drops, supported generally without beams, by columns with or without flared column heads A flat slab may be solid slab or may have recesses formed on the soffit so that the soffit comprises a series of ribs in two directions. The recesses may be formed by removable or permanent filler blocks.

  • 2. Types of flat slab Flat Slab with drop panels

    Flat slab with column head Flat slab with drop panel and column head

    Flat Slab resting directly on columns

    Drop is a local thickening of the slab in the region of column Structural Advantages increase shear strength of slab increase nega5ve moment capacity of slab

    s5en the slab and hence reduce deec5on

    Column head is a local enlargement of the column at the junc5on with the slab Structural Advantages increase shear strength of slab

    (punching shear) reduce the moment in the slab by

    reducing the clear or effective span

  • A at slab may have recesses formed on the sot so that the sot comprises a series of ribs in two direc5ons ( wae Slabs).

  • Flat slabs with capitals, drop panels, or both. These slabs are very sa4sfactory for heavy loads and long spans. Although the formwork is more expensive than for at plates, at slabs will require less concrete and reinforcing than would be required for at plates with the same loads and spans. They are par4cularly economical for warehouses, parking and industrial buildings, and similar structures, where exposed drop panels or capitals are acceptable.

  • vFlexibility in room layout Introduce partition walls anywhere required Change the size of room layout Omit false ceiling

    v Saving in building height Lower storey height will reduce building weight approx. saves 10% in vertical members reduce foundation load

    vShorter construction time flat plate design will facilitate the use of big table formwork to increase productivity

    vEase of installation of M&E services all M & E services can be mounted directly on

    the underside of the slab instead of bending them to avoid the beams

    avoids hacking through beams

    3. Benefits of flat slab

  • The main disadvantage is their lack of resistance to lateral loads due to wind and earthquakes. Lateral load resis4ng systems such as shear walls are oDen necessary When the loads or spans or both become quite large, the slab thickness and column sizes required for at plates or at slabs are of such magnitude that it is more economical to use two-way slabs with beams, despite the higher formwork costs.

  • 4. Behaviour of Slab supported on Stiff , Flexible and no beams

    Case Study:

    Panel Size = 4 m x 4m Slab Thickness = 125 mm Load = 5 kN/m2

    S5 Supports ( Bearing wall) Flexible Supports (Beam) : 300 x 300 , 300 x 450 , 300 x 600 , 300 x 1000 mm Column supports at corners

  • A. Two way Slab on Rigid Supports (bearing Walls)

    Mx = 3.616 kNm/m My = 3.616 kNm/m

    IS 456 Values (Table 27): 0.062 x 5 x 16 = 4.96

    Slab Deec6on = 1.4 mm

  • B. Two way Slab on Flexible Supports (Beams on all sides) 1. Beam Size : 300 x300 mm

    Mx = 4.45 kNm/m My = 4.45 kNm/m

    IS 456 Values (Type 9): 0.056 x 5 x 16 = 4.48

    Mxy = 0.37 kNm/m

    Beam Moment = 12.2 kNm Beam Deec6on = 1.33 mm Slab deec6on= 2.9 mm

  • 2. Beam Size : 300 x450 mm

    Mx = 3 kNm/m My = 3 kNm/m IS 456 Values (Type 9): 0.056 x 5 x 16 = 4.48

    Mxy = 0.73 kNm/m

    Beam Moment = 15.6 kNm Beam Deec6on = 0.5 mm

    Slab deec6on= 1.5 mm

  • 3. Beam Size : 300 x 600 mm

    Mx = 2.43 kNm/m My = 2.43 kNm/m

    IS 456 Values (Type 9): 0.056 x 5 x 16 = 4.48

    Mxy = 0.8 kNm/m

    Beam Moment = 17 kNm Beam Deec5on = 0.24 mm Slab Deec5on = 0.98 mm

  • 4. Beam Size : 300 x 1000 mm

    Mx = 2 kNm/m My = 2 kNm/m IS 456 Values (Type 9): 0.056 x 5 x 16 = 4.48

    Mxy = 0.8 kNm/m

    Beam Moment = 18 kNm

  • 5. Beam Size : 300 x 125 mm (Concealed Beams)

    Mx = 9.8 kNm/m My = 9.8 kNm/m

    IS 456 Values (Type 9): 0.056 x 5 x 16 = 4.48

    Mxy = 3 kNm/m

    Beam Moment = 2.9 kNm Slab Deec6on = 7.0 mm

  • B. Two way Slab on Point Supports at corners (Flat Slab)

    Mx = 9.075 kNm/m (Middle) =12.4 kNm/m (Edge Strip)

    Mxy = 7.76 kNm/m My = 9.075 kNm/m (Middle) =12.4 kNm/m (Edge Strip)

    Slab Deec6on = 8.67 mm

  • Type of Support Mx My Mxy

    Beam Moment

    Deec4on Slab Beam

    Rigid 3.616 3.616 2.6 - 1.4 -

    300 x125 (Concealed Beams)

    9.84 9.85 3.0 2.88 7.0 4.3

    300 x300 4.45 4.45 0.37 12.2 2.9 1.33

    300 x450 3 3 0.73 15.6 1.5 0.50

    300 x600 2.43 2.43 0.8 17.0 0.98 0.24

    300x1000 2 2 0.8 18.0 0.60 0.05

    Flat Slab 9.0 9.0 7.76 - 8.676 -

    Results Summary

  • Two way Rectangular Slab supported on stiff beams, the shorter spans (stiffer portion of the slab) carry larger load and subjected to larger moments. The longer spans

    carry less load and subjected to less moment.

    Results indicate that decrease in supporting beams stiffness leads to an increase in bending moments of slabs and decrease in bending moment of the beams (behavior that is not captured using code recommendations).

    If the slab is supported on bearing walls, slab moments are distributed in similar way.

    If the slab is supported only by the columns, the slab behaves like a two way slab with an essential difference that all the load is carried in both directions to accumulate it

    at the columns. With Concealed beams it is reveled that the behaviour is close to Flat slabs rather than any useful

    beam action.

    Observa4ons

  • 4. Structural Behaviour of Flat Slab

    Deected Shape

    Column Strip Column Strip

    Middle Strip

    Column Strip Middle Strip

  • A Zone of ve BM (Hogging) in both direc7ons B Zone of +ve BM(Sagging) and ve BM C Zone of -ve BM and +ve BM D Zone of +ve BM in both direc7ons

    -m4

    -m2

    -m4

    m3

    m1

    m3

    m5 m7

    -m8

    -m4

    -m2

    -m4

    m7

    A A

    A A

    C

    C

    B

    B

    D

    Column Strip

    Middle Strip

    Column Strip

    Column Strip

    Middle Strip Column Strip

    -m6

    -m6 -m8 -m8

    -m8

    5. Distribution of Total Panel Moment in different zones

  • A Zone of ve BM (Hogging) in both direc7ons B Zone of +ve BM(Sagging) and ve BM C Zone of -ve BM and +ve BM D Zone of +ve BM in both direc7ons

    -m4

    -m2

    -m4

    m3

    m1

    m3

    m5 m7

    -m8

    -m4

    -m2

    -m4

    m7

    A A

    A A

    C

    C

    B

    B

    D

    Column Strip

    Middle Strip

    Column Strip

    Column Strip

    Middle Strip Column Strip

    -m6

    -m6 -m8 -m8

    -m8

    m1

    -m2 -m2 D C C

    m3

    -m4 -m4 B A A

    m5

    -m6

    -m6

    D

    B B

    m7

    -m8

    -m8

    C

    A A

  • 6. Definitions

    L2

    L1

    Moment Direc5on

    MIDDLE STRIP COLUMN STRIP 0.25L2 0.25L1

    COLUMN STRIP 0.25L1 0.25L2

    MIDDLE STRIP

    COLUMN STRIP 0.25L1 0.25L2

    Mom

    ent D

    irec5on

    SPAN Region

    SPAN Region: Bounded on all the four sides by middle strips

  • 7. General Design Considerations CL 31.2 Proportioning 31.2.1 Thickness of Flat Slab The thickness of the flat slab shall be

    generally controlled by considerations of span to effective depth ratios given in 23.2.

    For slabs with drops conforming to 31.2.2, span to effective depth ratios given in 23.2 shall be applied directly; otherwise the span to effective depth ratios obtained in accordance with provisions in 23.2 shall be multiplied by 0.9. For this purpose, the longer span shall be considered.

    The minimum thickness of slab shall be 125 mm.

    31.2.2 Drop The drops when provided shall be

    rectangular in plan, and have a length in each direction not less than one- third of the panel length in that direction.

    For exterior panels, the width of drops at right angles to the non continuous edge and measured from the centre-line of the columns shall be equal to one-half the width of drop for interior panels.

    Minimum thickness of Drop > of Slab thickness and > 100 mm

  • 31.2.3 Column Heads Where column heads are provided, that portion of a column head which lies within the largest right circular cone or pyramid that has a vertex angle of 900and can be included entirely within the outlines of the column and the column head, shall be considered for design purposes.

  • 8. Determination of Bending Moment CL 31.3

    31.3.1. Methods of Analysis and Design

    It shall be permissible to design the slab system by one of the following

    methods:

    a) The direct design method as specified in 31.4, and

    b) The equivalent frame method as specified in 31.5.

    In each case the applicable limitations given in 31.4 and 31.5 shall be met.

  • 9. Direct Design Method CL 31.4 A. Limitations : 31.4.1 Slab system designed by the direct design method shall fulfil the following conditions:

    a) There shall be minimum of three continuous spans in each direction, b) The panels shall be rectangular, and the ratio of the longer span to the shorter span within

    a panel shall not be greater than 2.0 c) It shall be permissible to offset columns to a maximum of 10percent of the span in the

    direction of the offset notwithstanding the provision in (b) d) The successive span lengths in each direction shall not differ by more than one-third of

    the longer span. The end spans may be shorter but not longer than the interior spans, and

    e) The design live load shall not exceed three times the design dead load.

    Note: Applicable to gravity loading condition alone (and not to the lateral loading condition)

  • 1 2 3

    2

    3

    Lx1 Lx2 Lx3

    Ly1

    Ly2

    Ly3

    0.1Ly2

    0.1Lx1 Lx1 Lx2 Lx3 Lx2

    Ly1 Ly2 Ly3 Ly2

    Lx1 2Lx2/3 Lx3 2Lx2/3

    Ly1 2Ly2/3 Ly3 2Ly2/3

    wuL/wuD 3

    For any Panel Longer Span/Shorter Span 2

  • B. Total Design Moment for a Span: CL31.4.2

    CL of Panel 1

    CL of Panel 2

    1

    2

    DESIGN STRIP

    31.4.2.1 In the direct design method, the total design moment for a span shall be determined for a strip bounded laterally by the centre-line of the panel on each side of the centre-line of the supports. 31.4.2.2 The absolute sum of the positive and average negative bending moments in each direction shall be taken as:

    1

    2

    M0x

    M0y

    lnx

  • wu kN/m

    L1

    L2 Ln Ln (L1)

    (L2) Note: 1. It is the same as the total moment that occurs in a

    simply supported slab

    2. The moment that actually occurs in such a slab has been shown by experience and tests to be somewhat less than the value determined by the Mo expression. For this reason, l1 is replaced with ln

  • It is next necessary to know what propor4ons of these total moments are posi4ve and what propor4ons are nega4ve.

    10.Distribution of Total Panel Moment M0

    If a slab was completely xed at the end of each panel, the division would be as it is in a xed-end beam, two-thirds nega4ve and one-third posi4ve, as shown in Figure.

    This division is reasonably accurate for interior

    panels where the slab is con4nuous for several spans in each direc4on with equal span lengths and loads.

    Interior Panel

  • The rela4ve s4nesses of the columns and slabs of exterior panels are of far greater signicance in their eect on the moments than is the case for interior panels.

    The magnitudes of the moments are very sensi4ve to the amount of torsional restraint supplied at the discon4nuous edges.

    This restraint is provided both by the exural s4ness of the slab and by the exural s4ness of the exterior column.

    Exterior Panel

  • Code Recommendations

  • Distribution of Bending Moments across panel width Code Recommendations

  • 11. Rebar Detailing - Code Recommendations

  • Bent bars are also used. There seems to be a trend among designers to use straight bars more than bent bars.

    ELEVATION

  • Rebar Detailing - Code Recommendations

    e e e e e

    b b b b b

    Ln greater of adjacent clear spans CL 31.7.3 (b)

  • Sec6on through Middle Strip

  • 12. Two way Shear in Flat Slab

    Flat plates present a possible problem in transferring the shear at the perimeter of the columns.

    There is a danger that the columns may punch through the slabs.

    As a result, it is frequently necessary to increase column sizes or slab thicknesses or to use shear heads. Shear heads consist of steel I or channel shapes placed in the slab over the columns

  • Note: Flat Slab with drop panel and capital, shear is required to be checked at two sec4ons 1. at a distance d/2 from the face of column capital 2. at a distance d/2 from the face of drop panel

  • Design Example #1

    Design by DDM at plate supported on columns 450 mm square, for a Live Load = 3 kN/m2, Floor Finish = 1 kN/m2 use M20 and Fe415. Assume clear cover = 20 mm. Eec6ve Column Height = 3.35m. Bay spacing in X and Y direc6on = 5m c/c Interior Panel P5 Corner Panel P7

    3 bays @ 5 m c/c

  • A. Interior Panel Design

    5 m

    5 m 2.5m

    2.5 m A A

    A A

    B

    B

    CCD

    Zone A Corner Strip

    Zone B Middle Strip along X

    Zone C Middle Strip along Y

    Zone D Interior Region Step 1: Panel Division into Strips 31.1.1(a)

    Moment direc6on Along

    L1 L2 Width of Column Strip on either side of Centre Line = 0.25L2 and 0.25 L1

    Middle Strip

    X 5 5 1.25 and 1.25 m Adopt 1.25 m 2.5m

    Y 5 5 1.25 and 1.25 m Adopt 1.25 m 2.5m

  • Step 2: Trial Depth CL 31.2.1

    L/d = 26 Modica5on Factor = 1.33, Assuming pt = 0.4%, FIG 4 IS 456 d = 5000/(26 x 1.33) = 145 mm > 125 CL 31.2.1 DS= 145 + 20 + 18 = 183 mm ( assume #12 bars, and bars in two layers) Provide Ds= 200 mm d = 200-20-18 = 162 mm

  • Step 3 Design Loads / m width of Slab

    wuD = 1.5(25x 0.2 + 1) = 9kN/m wuL = 1.5 x 3 = 4.5kN/m wu = 13.5 kN/m

    Step 4: Check for Applicability of DDM: CL 31.4.1

    No. of Con5nuous Spans in each direc5on = 3 ; OK 31.4.1(a) Long Span/Short Span = 5/5 = 1

  • Step 5: Check for punching shear around Column

    Assumed d = 162 mm Sec4on 1: Cri5cal Sec5on at d/2 around the column Perimeter of Cri5cal Sec5on = 4 x 0.612= 2.448 m Design Shear at cri5cal sec5on Vu Vu = 13.5 ( 52 0.6122) = 333kN c = 0.25fck = 1.12 MPa ks = 0.5 +1 = 1.5 333 kN OK

    Cri4cal Sec4on

    0.612m

    0.612m

    5m

    5m

    Contributory Area

  • Step 6:Design Moments CL 31.4.2.2

    Parameters Along X Along Y L1 (Span in direc4on of Mo) 5 5 m 0.65L1 3.25 3.25 m Ln (clear span extending from face to face of columns, capitals)

    (5-0.45) = 4.55 4.55 m

    Ln > 0.65L1 4.55 4.55 m L2 (Span transverse to L1) 5 5 m W = wu L2Ln 307.2 307.2 kN M0 = W Ln / 8 174.72 174.72 kNm

    wu = 13.5 kN /m

  • Step 7 : Distribution of Bending Moment across panel width ; CL: 31.4.3.2, 31.5.5

    Moment Direc5on along X Y Nega4ve Design Moment

    MN = - 0.65*M0 113.6 113.6 kNm 31.4.3.2

    Column Strip M1 = 0.75MN 85.2 85.2 kNm 31.5.5.1 Width of Column Strip resis4ng M1 (Csw) 2x1.25 =2.5 2x1.25 =2.5 m

    -m1 = M1/ Csw (Zone A) 34.1 34.1 kNm/m Middle Strip M2 = 0.25MN 28.4 28.4 kNm 31.5.5.4(a) Width of Middle Strip resis4ng M2 (Msw) 2.5 2.5 m

    -m2 = M2/Msw (Zone B & C) 11.4 11.4 kNm/m

  • Posi5ve Design Moment MP = 0.35*M0

    61.2 61.2 kNm 31.4.3.2

    Column Strip M1 = 0.6MP 36.7 36.7 kNm 31.5.5.3 +m1 = M1/ Csw (Zone B &C)

    14.7 14.7 kNm/m

    Mid Span M2 = 0.4MP 24.5 24.5 kNm 31.5.5.4(a) +m2 = M2/Msw (Zone D) 9.8 9.8 kNm/m

    -ve sign : Hogging Moment (tension at top) +ve sign : Sagging Moment (tension at borom)

    -34.1

    -11.4

    -34.1

    14.7

    9.8

    14.7

    -34.1 -11.4 -34.1

    9.8 14.7

    -11.4 -34.1 -34.1

    -34.1

    -11.4

    -34.1

    14.7

    A B A

    DC C

    AAB

    Step 8 : Check for adequacy of Depth Max Design Bending moment = 34.1 kNm/m Mu,lim = 72.41 kNm/m > 34.1, Depth is adequate G-1.1(c)

  • Loca6on Moment (kNm/m)

    Ast (mm2/m)

    Ast (prov) Bar dia Spacing

    mm

    Along X Zone A (-) 34.1 635 635 10 120 - T Zone B 14.7 260 260 8 190 - B Zone C (-)11.4 200 240 8 200 - T Zone D 9.8 171 240 8 200 - B

    Along Y Zone A (-)34.1 635 635 10 120 - T Zone B (-)11.4 200 240 8 200 - T Zone C 14.7 260 260 8 190 - B Zone D 9.8 171 240 8 200 - B

    7.5 Ast2 58490Ast + Mu = 0 G-1.1(b)

    Step 9 :Rebar Details Ast,min = 0.12 x 200 x 1000 /100 = 240 mm2/m 26.5.2.1 Minimum Eec5ve Depth of Slab = 162 mm

  • #8@19

    0 #8

    @20

    0 #8

    @19

    0

    #8@200 #8@190 #8@190

    0.15Ln

    0.15Ln 0.125Ln

    0.125Ln

    Borom Rebar Details in Interior Panel

    A B A

    A B A

    C D C

  • TOP Rebar Details in Interior Panel

    #10@120

    #10@

    120

    #8@200

    #8@200 #8

    @20

    0

    0.3Ln

    0.2Ln

    0.3Ln 0.2Ln

    Note: Distances for curtailment of rebars are measured from column face

    A B A

    C D C

  • B. Corner Panel Design

    Step 5: Check for punching shear around Column

    Assumed d = 162 mm Sec4on 1: Cri5cal Sec5on at d/2 around the column Perimeter of Cri5cal Sec5on = 2 x 0.531= 1.062 m Design Shear at cri5cal sec5on Vu Vu = 13.5 ( 2.52 0.5312) = 81kN c = 0.25fck = 1.12 MPa ks = 0.5 +1 = 1.5 81 kN OK

    450

    162/2 = 81 mm

  • Step 7 : Distribution of Bending Moment across panel width ; CL 31.4.3.3 , 31.5.5

    = / Assume Columns and Slab panels are with same modulus of elas5city

    5 m

    5 m

    1.25

    m

    1.25m A A

    A A

    B

    B

    CCD

    Step 6:Design Moments CL 31.4.2.2

    M0 = 174.72 kNm

  • Parameters Along X Along Y Sum o f co l umn s4ness above and below the slab 2 (4EcIc)/Lc

    (2 x 4 x Ec x 450 x 4503/12) /3350 = 8.16 Ec x 106

    Slab s4ness ks = 4EsIs/Ls

    (4 Es x 5000 x 2003/12)/5000 = 2.67Es x 106

    2.67Es x 106

    c = kc /ks 3.06 3.06

    = 1+ (1/c) 1.33 1.33

  • Moment Direc5on along X Y Nega4ve Design Moment

    MN = - 0.65*M0/ 85.4 85.4 kNm 31.4.3.3

    Column Strip M1 = MN 85.4 85.4 kNm 31.55.2(a) Width of Column Strip Csw resis4ng M1 2x1.25 = 2.5 2.5 m

    -m1 = M1/Csw 34.2 34.2 kNm/m Middle Strip M2=0 0 0 kNm 31.5.5.4(a)

    -m2 = 0 0 0 kNm/m

    A. Exterior nega4ve design moment: -m1 -m1

    -m1

    -m1

    Exterior

    Exterior

    Interior

    Interior 1.25

    1.25

    -m2

    -m2

    X

    Y

  • Moment Direc5on along X Y Nega4ve Design Moment

    MN = - (0.75 0.1/)Mo 118 118 kNm 31.4.3.3

    Column Strip M1 = 0.75 MN 88.5 88.5 kNm 31.5.5.1 Width of Column Strip Csw resis4ng M1 2x1.25 =2.5 2.5 m

    -m1 = M1/ Csw -35.4 -35.4 kNm/m Middle Strip M2 = 0.25 MN 22.12 22.12 kNm 31.5.5.4(a) Width of Middle Strip Msw resis4ng M2 2.5 2.5 m

    -m2 = M2/Msw -8.85 -8.85 kNm/m

    B. Interior nega4ve design moment:

    - m1

    - m1

    - m2

    m1 -m1 -m1 -m2

    X

    Y

    Exterior

    Exterior

    Interior

    Interior

  • Moment Direc5on along X Y Design Moment

    MP = (0.63 0.28/)Mo 73.29 73.29 kNm 31.4.3.3

    Column Strip M1 = 0.6 MP 43.98 43.98 kNm 31.5.5.3 Width of Column Strip Csw resis4ng M1 2x1.25 =2.5 2.5 m

    m1 = M1/ Csw 17.6 17.6 kNm/m Middle Strip M2 = 0.4 MP 29.32 29.32 kNm 31.5.5.4(a) Width of Middle Strip Msw resis4ng M2 2.5 2.5 m

    m2 = M2/Msw 11.73 11.73 kNm/m

    C. Posi4ve Moment in Mid Span:

    m1

    m1 m1

    m1

    m1

    m1

    m2 X

    Y

    Exterior

    Exterior

    Interior

    Interior

    m2

  • -ve sign : Hogging Moment (tension at top) +ve sign : Sagging Moment (tension at borom)

    17.6

    11.73

    17.6

    -8.85 -35.4

    11.73 17.6 17.6

    A B A

    DC C

    AAB

    -35.4

    -35.4

    -8.85

    -35.4

    -34.2

    -34.2

    0

    -34.2 -34.2 -0

    Exterior

    Exterior

    Interior

    Interior

    Step 7 : Check for adequacy of Depth Max Design Bending moment = 35.4 kNm/m Mu,lim = 72.41 kNm/m > 35.4, Depth is adequate G-1.1(c)

  • Strip Loca6on Moment (kNm/m)

    Ast (mm2/m)

    Ast (prov) Bar dia Spacing

    mm

    Along X Zone A(Exterior) (-)34.2 637 637 10 120(T) Zone A(Interior) (-)35.4 662 662 10 115(T) Zone B 17.6 314 314 8 160(B) Zone C(Interior) (-)8.85 155 240 8 200(T) Zone D 11.73 206 240 8 200(B)

    Along Y Zone A (Exterior) (-)34.2 637 637 10 120(T) Zone A(Interior) (-)35.4 662 662 10 115(T) Zone B (Interior) (-)8.85 155 240 8 200(T) Zone C 17.6 314 314 8 160(B) Zone D 11.73 206 240 8 200(B)

    Step 8 :Rebar Details Ast,min = 0.12 x 200 x 1000 /100 = 240 mm2/m 26.5.2.1

    7.5 Ast2 58490Ast + Mu = 0

  • 17.6

    11.73

    17.6

    11.73 17.6 17.6

    A B A

    D C C

    A A B

    Exterior

    Exterior

    Interior

    Interior

  • -8.85 -35.4

    A B A

    DC C

    AAB

    -35.4

    -35.4

    -8.85

    -35.4

    -34.2

    -34.2

    0

    -34.2 -34.2 -0 Exterior

    Exterior

    Interior

    Interior #8

    @20

    0

    #10@

    120

    #10@

    115

    #10@120 #10@120

    #8@200

    #8@200 #10@115

    #10@

    115

    #8@20

    0

    TOP Rebar details in Corner Panel

  • Design Example #2

    Design by DDM at plate supported on columns 500 mm square, for a Live Load = 4 kN/m2, Floor Finish = 1 kN/m2 use M25 and Fe415. Floor slab is exposed to moderate environment. Column Height = 3.5m (c/c). Bay spacing in X and Y direc6on = 5.5m c/c. Assume that building is not restrained against sway Interior Panel P5 Corner Panel P7

    3 bays @ 5.5 m c/c

  • A. Interior Panel Design

    5.5 m

    5.5 m 2.75m

    2.75 m A A

    A A

    B

    B

    CCD

    Zone A Corner Strip

    Zone B Middle Strip along X

    Zone C Middle Strip along Y

    Zone D Interior Region Step 1: Panel Division into Strips 31.1.1(a)

    Moment direc6on Along

    L1 L2 Width of Column Strip on either side of Centre Line = 0.25L2 and 0.25 L1

    Middle Strip

    X 5 5 1.375 and 1.375 m Adopt 1.375 m 2.75m

    Y 5 5 1.375 and 1.375 m Adopt 1.375 m 2.75m

  • Step 2: Trial Depth CL 31.2.1

    L/d = 26 Modica5on Factor = 1.33, Assuming pt = 0.4%, FIG 4 IS 456 d = 5500/(26 x 1.33) = 160 mm > 125 CL 31.2.1 DS= 160 + 30 + 18 = 208 mm ( assume #12 bars, and bars in two layers) Provide Ds= 225 mm d = 225-30-18 = 177 mm

  • Step 3 Design Loads / m width of Slab

    wuD = 1.5(25x 0.225 + 1) = 9.94kN/m wuL = 1.5 x 4 = 6kN/m wu = 15.94 16 kN/m

    Step 4: Check for Applicability of DDM: CL 31.4.1

    No. of Con5nuous Spans in each direc5on = 3 ; OK 31.4.1(a) Long Span/Short Span = 5.5/5.5 = 1

  • Step 5: Check for punching shear around Column

    Assumed d = 177 mm Sec4on 1: Cri5cal Sec5on at d/2 around the column Perimeter of Cri5cal Sec5on = 4 x 0.677= 2.708 m Vu = 16 ( 5.52 0.6772) = 477kN c = 0.25fck = 1.25 MPa ks = 0.5 +1 = 1.5 477 kN OK

    Cri4cal Sec4on

    0.677m

    0.677m

    5.5m

    5.5m

    Contributory Area

  • Step 6:Design Moments CL 31.4.2.2

    Parameters Along X Along Y L1 (Span in direc4on of Mo) 5.5 5.5 m 0.65L1 3.575 3.575 m Ln (clear span extending from face to face of columns, capitals)

    (5.5-0.5) = 5 5 m

    Ln > 0.65L1 5 5 m L2 (Span transverse to L1) 5.5 5.5 m W = wu L2Ln 440 440 kN M0 = W Ln / 8 275 275 kNm

    wu = 16 kN /m

  • Step 7 : Distribution of Bending Moment across panel width ; CL: 31.4.3.2, 31.5.5

    Moment Direc5on along X Y Nega4ve Design Moment

    MN = - 0.65*M0 179 179 kNm 31.4.3.2

    Column Strip M1 = 0.75MN 134.3 134.3 kNm 31.5.5.1 Width of Column Strip resis4ng M1 (Csw) 2.75 2.75 m

    -m1 = M1/ Csw (Zone A) 48.8 48.8 kNm/m Middle Strip M2 = 0.25MN 44.8 44.8 kNm 31.5.5.4(a) Width of Middle Strip resis4ng M2 (Msw) 2.75 2.75 m

    -m2 = M2/Msw (Zone B & C) 16.3 16.3 kNm/m

  • Posi5ve Design Moment MP = 0.35*M0

    96.3 96.3 kNm 31.4.3.2

    Column Strip M1 = 0.6MP 57.8 57.8 kNm 31.5.5.3 +m1 = M1/ Csw (Zone B &C)

    21 21 kNm/m

    Mid Span M2 = 0.4MP 38.5 38.5 kNm 31.5.5.4(a) +m2 = M2/Msw (Zone D) 14 14 kNm/m

    -ve sign : Hogging Moment (tension at top) +ve sign : Sagging Moment (tension at borom)

    -48.8

    -16.3

    -48.8

    21

    14

    21

    -48.8 -16.3 -48.8

    14 21

    -16.3 -48.8 -48.8

    -48.8

    -16.3

    -48.8

    21

    A B A

    DC C

    AAB

    Step 8 : Check for adequacy of Depth Max Design Bending moment = 48.8 kNm/m Mu,lim = 108 kNm/m > 48.8 Depth is adequate G-1.1(c)

  • Loca6on Moment (kNm/m)

    Ast (mm2/m)

    Ast (prov) Bar dia Spacing

    mm

    Along X Zone A (-) 48.8 828 828 10 90 - T Zone B 21 340 340 8 145 - B Zone C (-)16.3 262 270 8 180 - T Zone D 14 224 270 8 180 - B

    Along Y Zone A (-) 48.8 828 828 10 90 - T Zone B -16.3 262 270 8 180 - T Zone C 21 340 340 8 145 - B Zone D 14 224 270 8 180 - B

    6 Ast2 63906Ast + Mu = 0 G-1.1(b)

    Step 9 :Rebar Details Ast,min = 0.12 x 225 x 1000 /100 = 270 mm2/m 26.5.2.1 Minimum Eec5ve Depth of Slab = 177 mm

  • #8@14

    5 #8

    @18

    0 #8

    @14

    5

    #8@180 #8@145 #8@145

    0.15Ln

    0.15Ln 0.125Ln

    0.125Ln

    Borom Rebar Details in Interior Panel

    A B A

    A B A

    C D C

  • TOP Rebar Details in Interior Panel

    #10@90

    #10@

    90

    #8@180

    #8@200 #8

    @18

    0

    0.3Ln

    0.2Ln

    0.3Ln 0.2Ln

    Note: Distances for curtailment of rebars are measured from column face

    A B A

    C D C

  • B. Corner Panel Design

    Step 5: Check for punching shear around Column

    Assumed d = 177 mm Sec4on 1: Cri5cal Sec5on at d/2 around the column Perimeter of Cri5cal Sec5on = 2 x 0.5885= 1.177 m Vu = 16 ( 2.752 0.58852) = 115.5kN c = 0.25fck = 1.25 MPa ks = 0.5 +1 = 1.5 115.5 kN OK

    500

    177/2 = 88.5 mm

    2.75m

    2.75m

  • Step 7 : Distribution of Bending Moment across panel width ; CL 31.4.3.3 , 31.5.5

    = / Assume Columns and Slab panels are with same modulus of elas5city

    5 m

    5 m

    1.25

    m

    1.25m A A

    A A

    B

    B

    CCD

    Step 6:Design Moments CL 31.4.2.2

    M0 = 275 kNm

  • Parameters Along X Along Y Sum o f co l umn s4ness above and below the slab 2 (4EcIc)/Lc

    Le = 1.2 Lc (CL E1) Lc = 3.5-0.225 = 3.275

    (2 x 4 x Ec x 500 x 5003/12) /1.2*3275 = 10.6 Ec x 106

    Slab s4ness ks = 4EsIs/Ls

    (4 Es x 5500 x 2253/12)/5500 = 2.67Es x 106

    3.8Es x 106

    c = kc /ks 2.8 2.8

    c min (Table 17) (0.7/0.5)*0.1 =0.14 < c. Adopt c = 2.8

    = 1+ (1/c) 1.36 1.36

  • Moment Direc5on along X Y Nega4ve Design Moment

    MN = - 0.65*M0/ 131.4 131.4 kNm 31.4.3.3

    Column Strip M1 = MN 131.4 131.4 kNm 31.55.2(a) Width of Column Strip Csw resis4ng M1 2.75 2.75 m

    -m1 = M1/Csw 47.8 47.8 kNm/m Middle Strip M2=0 0 0 kNm 31.5.5.4(a)

    -m2 = 0 0 0 kNm/m

    A. Exterior nega4ve design moment: -m1 -m1

    -m1

    -m1

    Exterior

    Exterior

    Interior

    Interior 1.25

    1.25

    -m2

    -m2

    X

    Y

    M0 = 275 kNm

  • Moment Direc5on along X Y Nega4ve Design Moment

    MN = - (0.75 0.1/)Mo 186 186 kNm 31.4.3.3

    Column Strip M1 = 0.75 MN 139.5 139.5 kNm 31.5.5.1 Width of Column Strip Csw resis4ng M1 2.75 2.75 m

    -m1 = M1/ Csw 50.73 50.73 kNm/m Middle Strip M2 = 0.25 MN 46.5 46.5 kNm 31.5.5.4(a) Width of Middle Strip Msw resis4ng M2 2.75 2.75 m

    -m2 = M2/Msw 17 17 kNm/m

    B. Interior nega4ve design moment:

    - m1

    - m1

    - m2

    m1 -m1 -m1 -m2

    X

    Y

    Exterior

    Exterior

    Interior

    Interior

  • Moment Direc5on along X Y Design Moment

    MP = (0.63 0.28/)Mo 116.6 116.6 kNm 31.4.3.3

    Column Strip M1 = 0.6 MP 70 70 kNm 31.5.5.3 Width of Column Strip Csw resis4ng M1 2.75 2.75 m

    m1 = M1/ Csw 25.5 25.5 kNm/m Middle Strip M2 = 0.4 MP 46.7 46.7 kNm 31.5.5.4(a) Width of Middle Strip Msw resis4ng M2 2.75 2.75 m

    m2 = M2/Msw 17 17 kNm/m

    C. Posi4ve Moment in Mid Span:

    m1

    m1 m1

    m1

    m1

    m1

    m2 X

    Y

    Exterior

    Exterior

    Interior

    Interior

    m2

  • -ve sign : Hogging Moment (tension at top) +ve sign : Sagging Moment (tension at borom)

    25.5

    17

    25.5

    -17 -50.73

    17 25.5 25.5

    A B A

    DC C

    AAB

    -50.73

    -50.73

    -17

    -50.73

    -47.8

    -47.8

    0

    -47.8 -47.8 -0

    Exterior

    Exterior

    Interior

    Interior

    Step 7 : Check for adequacy of Depth Max Design Bending moment = 50.73 kNm/m Mu,lim = 108 kNm/m > 50.73, Depth is adequate G-1.1(c)

  • Strip Loca6on Moment (kNm/m)

    Ast (mm2/m)

    Ast (prov) Bar dia Spacing

    mm

    Along X Zone A(Exterior) (-)47.8 810 810 10 90(T) Zone A(Interior) (-)50.73 864 864 10 90(T) Zone B 25.5 415 415 10 180(B) Zone C(Interior) (-)17 273 273 8 180(T) Zone D 17 273 273 8 180(B)

    Along Y Zone A (Exterior) (-)47.8 810 810 10 90(T) Zone A(Interior) (-)50.73 864 864 10 90(T) Zone B (Interior) (-)17 273 273 8 180(T) Zone C 25.5 415 415 10 180(B) Zone D 17 273 273 8 180(B)

    Step 8 :Rebar Details Ast,min = 0.12 x 225 x 1000 /100 = 270 mm2/m 26.5.2.1

    6 Ast2 63906Ast + Mu = 0

  • 7.2m 7.2m 7.2m

    6.4m

    6.4m

    6.4m

    Design Example #3

    Design by DDM at plate supported on columns of dia = 450 mm, Column head = 1.5 m dia, Drop panel size = 3.2 x 3.2 m, for a Live Load = 4 kN/m2, Floor Finish = 1 kN/m2 use M20 and Fe415. Assume clear cover = 20 mm. Column Height = 3.35m Interior Panel P5 Exterior Panel P2/P4 Corner Panel P1

  • Step 1: Panel Division into Strips 31.1.1(a)

    Moment direc6on Along

    L1 L2

    Width of Column Strip on either side of

    Centre Line = 0.25L2 and 0.25 L1

    Middle Strip

    X 7.2 6.4 1.6 < 1.8 m; 1.6 m 4m Y 6.4 7.2 1.8 > 1.6 m; 1.6 m 3.2m

    Lx = 7.2

    L y = 6.4 1.6

    1.6

    1.6 1.6

    CSx CSx MSx

    CSy

    MSy

    CSy A. Interior Panel Design

    Zone A Corner Strip

    Zone B Middle Strip along X

    Zone C Middle Strip along Y

    Zone D Interior Region

  • Step 2: Trial Depth CL 31.2.1

    L/d = 26 Modica5on Factor = 1.4, Assuming pt 0.4%, FIG 4 IS 456 d = 7200/(26 x 1.4) = 198 mm > 125 CL 31.2.1 DS= 198+20+18= 236 mm ( assume #12 bars) Provide Ds= 240 mm , d = 198mm

  • Step 3: Design Loads / m width of Slab

    wuD = 1.5(25 x 0.24 + 1) = 10.5kN wuL = 1.5 x 4 = 6.0kN wu = 16.5 kN

    Step 4: Check for Applicability of DDM: CL 31.4.1

    No. of Con5nuous Spans in each direc5on = 3 ; OK 31.4.1(a) Long Span/Short Span = 7.2/6.4 = 1.125

  • Step 5: Drop Panel Size : CL 31.2.2

    Length along X Lx/3 = 2.4 m Length along Y Ly/3 = 2.13 m Generally Drop Panel Size is set equal to Width of Column Strip Proposed size 3.2 x 3.2 meets all the requirements. Minimum thickness = DS = 60 mm or 100 mm; Adopt 100 mm

    Step 6:Column Head

    1/4 to 1/5 of average span = 7.2/5 = 1.44 m Provided = 1.5 m ; Ok Equivalent Square Capital =0.89D = 1.335 m

  • Step 7 : Check for Shear around Column Capital

    Minimum Eec5ve Depth of Slab = 198 mm Eec5ve Depth at Drop loca5on = 298 mm Sec4on 1: Cri5cal Sec5on at d/2 around the column capital Perimeter of Cri5cal Sec5on = ( 1.5 + 0.298) = 5.65 m Weight of Drop Projec5on below slab = 0.1x 25 x 1.5 = 3.75 kN/m2 Design Shear at cri5cal sec5on around capital Vu Vu = 16.5 ( 7.2 x 6.4 - x 1.7982/4) + 3.75(3.2 x 3.2 - x 1.7982/4) = 747 kN c = 0.25fck = 1.12 MPa ks = 0.5 +1 = 1.5 747 kN OK

    1.5

    Cri4cal Sec4on

    DROP3.2 m

    3.2 m

    1.798

    Capital

  • Sec4on 2 : Check for Shear around drop 1.5

    Cri4cal Sec4on

    DROP3.2 m

    3.2 m

    Capital

    3.2 + 0.198 = 3.4

    Cri5cal Sec5on at d/2 around the drop d = 198mm Perimeter of Cri5cal Sec5on = 4 x 3.4 = 13.6m Design Shear at cri5cal sec5on Vu = 16.5 ( 7.2 x 6.4 3.42) = 569 kN Shear Resistance of Concrete = 1.12 x 13600 x 198 =

    3015kN > 569 kN

  • Step 8:Design Moments CL 31.4.2.2

    Parameters Along X Along Y L1 (Span in direc4on of Mo) 7.2 6.4 m 0.65L1 4.68 4.16 m Ln (clear span extending from face to face of columns, capitals)

    (7.2-1.335) =

    5.865

    (6.4-1.335) =

    5.065 m

    Ln > 0.65L1 5.865 5.065 m L2 (Span transverse to L1) 6.4 7.2 m W = wu L2Ln 619.34 601.72 kN M0 = W Ln / 8 454 381 kNm

    wu = 16.5 kN /m

  • Step 9 : Distribution of Bending Moment across panel width ; CL: 31.4.3.2, 31.5.5

    Moment Direc5on along X Y Nega4ve Design Moment

    MN = - 0.65*M0 295.1 247.65 kNm 31.4.3.2

    Column Strip M1 = 0.75MN 221.33 185.74 kNm 31.5.5.1 Width of Column Strip Csw 2x1.6 =3.2 2x1.6 =3.2 m

    -m1 = M1/ Csw 69.17 58.04 kNm/m Middle Strip M2 = 0.25MN 73.78 61.91 kNm 31.5.5.4(a) Width of Middle Strip Msw 3.2 4

    -m2 = M2/Msw 23.06 15.48 kNm/m

  • Posi5ve Design Moment MP = 0.35*M0

    158.9 133.35 kNm 31.4.3.2

    Column Strip M1 = 0.6MP 95.34 80.01 kNm 31.5.5.3 +m1 = M1/ Csw 29.79 25 kNm/m

    Middle Strip M2 = 0.4MP 63.56 53.34 kNm 31.5.5.4(a) +m2 = M2/Msw 19.86 13.34 kNm/m

    -ve sign : Hogging Moment (tension at top) +ve sign : Sagging Moment (tension at borom) -69.17

    -23.06

    -69.17

    29.79

    19.86

    29.79

    -58.04 -15.48 -58.04

    13.34 25

    -15.48 -58.04 -58.04

    -69.17

    -23.06

    -69.17

    25

    A B A

    DC C

    AAB

    Step 10 : Check for adequacy of Depth

    Max Design Bending moment = 69.17 kNm/m Mu,lim = 126.36 kNm/m > 69.17, G-1.1(c) Depth is adequate

  • Moment Direc4on

    Mom

    ent

    Direc4

    on

    CS

    MS

    CS

    FE Results from ETAB

  • Strip Loca6on Moment (kNm/m)

    Ast (mm2/m)

    Ast (prov) Bar dia Spacing

    mm

    Along X Zone A (-) 69.17 1093 1093 10 70 - T Zone B 29.79 437 437 8 110 - B Zone C (-)23.06 334 334 8 150 -T Zone D 19.86 286 288 8 170 - B

    Along Y Zone A (-)58.04 896 896 10 85 - T Zone B (-)15.48 222 288 8 170-T Zone C 25 364 364 8 135 -B Zone D 13.34 190 288 8 170 - B

    7.5 Ast2 71488Ast + Mu = 0 G-1.1(b)

    Step 11 :Rebar Details Ast,min = 0.12 x 240 x 1000 /100 = 288 mm2/m 26.5.2.1 Minimum Eec5ve Depth of Slab = 198 mm

  • #8@170 #8@135 #8@135

    #8@17

    0 #8

    @11

    0 #8

    @11

    0

    7.2 m

    6.4 m 0.15Ln

    0.15Ln

    Borom Rebar Details in Interior Panel

    LAP ZONE

    A A

    A A

    B

    B

    C D C

    0.125Ln

    0.125Ln

  • #8@170 #10@85

    #8@15

    0 #1

    0@ 70

    0.22Ln 0.22Ln

    0.22Ln

    0.22Ln

    0.33

    Ln

    0.33

    Ln

    0.2Ln

    0.2Ln

    0.33Ln

    0.2Ln

    Top Rebar Details in Interior Panel

    Note: Distances for curtailment of rebars are measured from column face

    A B A

    0.33Ln

    0.2Ln

  • Sec6on Through Middle Strip - CDC

    #8@170

    7.2 m

    #8@340

    #8@150

    #8@135

    Sec6on Through Column Strip - ABA

    #10@70

    #10@140

    #10@85

    #8@170 #8@340 #8@170

  • Step 7 : Check for Shear around Column Capital

    Minimum Eec5ve Depth of Slab = 198 mm Eec5ve Depth at Drop loca5on = 298 mm Sec4on 1: Cri5cal Sec5on at d/2 around the column capital Perimeter of Cri5cal Sec5on = ( 1.5 + 0.298)/4 = 1.412 m Weight of Drop Projec5on below slab = 0.1x 25 x 1.5 = 3.75 kN/m2 Design Shear at cri5cal sec5on around capital Vu Vu = 16.5 ( 3.6x 3.2 ( x 1.7982/4)/4) + 3.75(1.6 x 1.6 ( x 1.7982/4)/4)) = 187 kN c = 0.25fck = 1.12 MPa ks = 0.5 +1 = 1.5 187 kN OK

    2. Corner Panel Design

  • Sec4on 2 : Check for Shear around drop

    Cri5cal Sec5on at d/2 around the drop d = 198mm Perimeter of Cri5cal Sec5on = 2 (1.7)=3.4m Design Shear at cri5cal sec5on Vu = 16.5 ( 3.6 x 3.2 1.72) = 143 kN Shear Resistance of Concrete = 1.12 x 3400 x 198 = 754kN > 143 kN

    CRITICAL SECTION

    drop

    free edge

    free edge

    =1.6 + 0.198/2 = 1.7 m

    Step 8:Design Moments CL 31.4.2.2

    Along X Along Y

    M0 = W Ln / 8 454 381 kNm

  • Step 9 : Distribution of Bending Moment across panel width ; CL 31.4.3.3 , 31.5.5

    = / Equivalent side of circular column = 0.89D = 0.89x 450 = 400 mm Assume Ec = Es

  • Parameters Along X Along Y Sum o f co l umn s4ness above and below the slab 2 (4EcIc)/Lc

    (2 x 4 x Ec x 400 x 4003/12) /3350 = 5.09 Ec x 106

    Slab s4ness ks = 4EsIs/Ls

    (4 Es x 6400 x 2403/12)/7200 = 4.1Es x 106

    (4 Es x 7200 x 2403/12)/6400 = 5.184Es x 106

    c = kc /ks 1.24 0.98

    c min (Table 17) l2/l1 = 6.4/7.2 = 0.89, WuL/WuD = 0.571

    (0.7/0.5)*0.071 = 0.1

  • Moment Direc5on along X Y Nega4ve Design Moment

    MN = - 0.65*M0/ 164 122.6 kNm 31.4.3.3

    Column Strip M1 = MN 164 122.6 kNm 31.55.2(a) Width of Column Strip Csw resis4ng M1 2x1.6 =3.2 2x1.6 =3.2 m

    -m1 = M1/ 3.2 -51.3 -38.3 kNm/m Middle Strip M2=0 0 0 kNm 31.5.5.4(a) Width of Middle Strip Msw resis4ng M2 3.2 4

    -m2 = 0 0 0 kNm/m

    A. Exterior nega4ve design moment: -m1 -m1

    -m1

    -m1

    Exterior

    Exterior

    Interior

    Interior 1.6

    1.6

    -m2

    -m2

    X

    Y

  • Moment Direc5on along X Y Nega4ve Design Moment

    MN = - (0.75 0.1/)Mo 315.3 266.9 kNm 31.4.3.3

    Column Strip M1 = 0.75 MN 236.5 200.2 kNm 31.5.5.1 Width of Column Strip Csw resis4ng M1 2x1.6 =3.2 2x1.6 =3.2 m

    -m1 = M1/ Csw -73.9 -62.6 kNm/m Middle Strip M2 = 0.25 MN 78.83 66.7 kNm 31.5.5.4(a) Width of Middle Strip Msw resis4ng M2 3.2 4 m

    -m2 = M2/Msw -24.7 -16.7 kNm/m

    B. Interior nega4ve design moment:

    - m1

    - m1

    - m2

    m1 -m1 -m1 -m2

    X

    Y

    Exterior

    Exterior

    Interior

    Interior

  • Moment Direc5on along X Y Design Moment

    MP = (0.63 0.28/)Mo 215.4 187.2 kNm 31.4.3.3

    Column Strip M1 = 0.6 MP 129.3 112.3 kNm 31.5.5.3 Width of Column Strip Csw resis4ng M1 2x1.6 =3.2 2x1.6 =3.2 m

    m1 = M1/ Csw 40.4 35.1 kNm/m Middle Strip M2 = 0.4 MP 86.2 74.9 kNm 31.5.5.4(a) Width of Middle Strip Msw resis4ng M2 3.2 4 m

    m2 = M2/Msw 26.94 18.7 kNm/m

    C. Posi4ve Moment in Mid Span:

    m1

    m1 m1

    m1

    m1

    m1

    m2 X

    Y

    Exterior

    Exterior

    Interior

    Interior

    m2

  • -ve sign : Hogging Moment (tension at top) +ve sign : Sagging Moment (tension at borom)

    40.4

    26.94

    40.4

    -16.7 -62.6

    18.7 35.1 35.1

    A B A

    DC C

    AAB

    -73.9

    -73.9

    -24.7

    -62.6

    -51.3

    -51.3

    0

    -38.3 -38.3 -0

    Exterior

    Exterior

    Interior

    Interior

    Step 10 : Check for adequacy of Depth Max Design Bending moment = 73.9 kNm/m Mu,lim = 126.36 kNm/m > 73.9, Depth is adequate G-1.1(c)

  • Strip Loca6on Moment (kNm/m)

    Ast (mm2/m)

    Ast (prov) Bar dia Spacing

    mm

    Along X Zone A(Exterior) (-)51.3 782 782 10 100 - T Zone A(Interior) (-)73.9 1180 1180 10 65 - T Zone B 40.4 604 604 8 80 -B Zone C(Interior) (-)24.7 359 359 8 140 - T Zone D 26.94 393 393 8 125-B

    Along Y Zone A (Exterior) (-)38.3 570 570 10 135 Zone A(Interior) (-)62.6 976 976 10 80 Zone B (Interior) (-)16.7 240 288 8 170 Zone C 35.1 520 520 8 95 Zone D 18.7 270 288 8 170

    7.5 Ast2 71488Ast + Mu = 0 G-1.1(b)

    Step 11 :Rebar Details Ast,min = 0.12 x 240 x 1000 /100 = 288 mm2/m 26.5.2.1 Minimum Eec5ve Depth of Slab = 198 mm

  • Strip Loca6on Moment (kNm/m)

    Bar dia

    Spacing mm

    Along X Zone B 40.4 8 80 -B Zone D 26.94 8 125-B

    Along Y Zone C 35.1 8 95 Zone D 18.7 8 170

    #8@80

    #8

    @12

    5

    #8@95 #8@95 #8@170

    #8@80

  • 40.4

    26.94

    40.4

    -16.7 -62.6

    18.7 35.1 35.1

    A B A

    D C C

    A A B

    -73.9

    -73.9

    -24.7

    -62.6

    -51.3

    -51.3

    0

    -38.3 -38.3 -0 Exterior

    Exterior

    Interior

    Interior

    #10@

    100

    #10@

    100

    #10@

    65

    #10@

    65

    #8@14

    0

    #10@135 #10@80 #8@170(Min)*

    #10@135

    #8@170

    #8@17

    0(Min)*

    * Op4onal Top Rebars

    #10@80 Strip Loca6on Moment (kNm/m)

    Bar dia

    Spacing mm

    Along X Zone A(Exterior) (-)51.3 10 100 - T Zone A(Interior) (-)73.9 10 65 - T Zone C(Interior) (-)24.7 8 140 - T

    Along Y Zone A (Exterior) (-)38.3 10 135 Zone A(Interior) (-)62.6 10 80 Zone B (Interior) (-)16.7 8 170

  • Transfer of Moments and Shears between Slabs and Columns The maximum load that a at slab can support is dependent upon the strength of

    the joint between the column and the slab.

    Load is transferred by shear from the slab to the column along an area around the column

    In addi7on moments are also transferred.

    The moment situa7on is usually most cri7cal at the exterior columns.

    Shear forces resul7ng from moment transfer must be considered in the design of the lateral column reinforcement (i.e., 7es and spirals).

  • EXAMPLE Compute moment transferred to Interior and corner Column in example 2

    Interior Column As spans are same in both direc5ons M = 0.08 (0.5 wL L2 Ln2 /(1+1/c) = 0.08 x 0.5 x 6 x 5.5 x 52 / 1.36 = 24.3 kNm this moment is distributed to top and borom column at junc5on in propor5on to their

    s5ness. M = 24.3/2 = 12.2 kNm Corner Column M = 131.4 kNm

  • Equivalent Frame Method (EFM) CL 31.5 More Comprehensive and Logical method Used when limita7ons of DDM are not

    complied with Applicable when subjected to horizontal

    loads 31.5.1 (a) Idealizing the 3D slab column system to 2D frames along column Centre lines in both longitudinal and transverse direc6ons.

    Longitudinal Frame

    Transverse Frame Edge Frame

  • For ver6cal loads, each oor, together with the columns above and below, is analyzed separately. For such an analysis, the far ends of the columns are considered xed. If there are large number of panels, the moment at a par6cular joint in a slab beam can be sa6sfactorily obtained by assuming that the member is xed two panels away. This simplica6on is permissible because ver6cal loads in one panel only appreciably aect the forces in that panel and in the one adjacent to it on each side.

    31.5.1(b)

  • En6re Frame Analysis Gravity + Lateral Loads

    For lateral loads, it is necessary to consider an equivalent frame that extends for the en4re height of the building, because the forces in a par4cular member are aected by the lateral forces on all the stories above the oor being considered.

  • 31.5.1(C and d)

    I2 = moment of iner4a at the face of the column / column capital c2 = dimension of column capital in the transverse direc4on l2 = width of equivalent frame.

    varia6on of the exural moment of iner6a

    Varia4ons of moment of iner4a along the axis 0f the slab on account of provision of drops shall be taken into account

    The s4ening eect of ared column heads may be ignored

  • 31.5.2 Loading Paiern

    wu LL > wu,DL

  • Cri5cal Sec5on Interior Column Centre Line Column /Capital face

    C

    < = C/2

    Results in Signicant reduc4on of design moments

    Design Posi5ve Moment (Span region) M3 = M0 (M1+M2)/2

  • Distribu5on of Moment

    Similar to DDM

  • Example 3 : Compute moments in exterior/interior Panel along Longitudinal Span Longitudinal Span = 7.2m, Transverse Span = 6.4 m, Interior Column = 450mm dia, Column Capital = 1500mm dia, Exterior Column = 400x400mm, Column Capital = 870mm(square), Floor to Floor = 3.35 m, Slab Thickness = 240 mm, number of Panels = 4 in each direc6on

    7.2 m

    6.4m

    6.4m

    7.2 m 7.2 m 7.2 m

    6.4m

  • Step 1: S5ness Computa5ons

    Exterior Column (Kce) = 4E x (4004 /12) /3350 = 2.55E106 = 1 Interior Column (KcI) = 4E x (4504 /64) /3350 = 2.4E106 = 0.957 Slab(Ks) =4E x (6400 x 2403/12) /7200 = 4.1E106 = 1.608

    Step 2: Simplied frame for analysis 31.5.1 (b)

    7200 7200

    3350

    3350 1 2 3

    A B

    C D

    Joint Member Rela5ve S5ness Sum Distribu5on Factors

    1

    1-A 1

    3.608

    0.277

    1-2 1.608 0.446

    1-C 1 0.277

    2

    2-B 0.957

    5.13

    0.187

    2-1 1.608 0.314

    2-3 1.608 0.314

    2-D 0.957 0.187

    Fixed End Moments = (16.5 x 6.4) x 7.22/12 = 456.2 kNm

  • Joint 1 2 3

    Members FIXED 1A+1C 1-2 2-1 FIXED 2B+2D 2-3

    FIXED 3-2

    DF 0.554 0.446 0.314 0.374 0.314 - FEM 456.2 -456.2 456.2 -456.2

    Bal -252.74 -203.46 - - - -

    CO - - -101.73 - - -

    Bal - - 31.94 38.04 31.94 -

    CO - 15.97 - - - 15.97

    Bal -8.85 -7.12 - - - -

    CO - - -3.56 - - -

    Bal 1.12 1.33 1.12

    Final end Moments -261.6 261.6 -528.43 39.37 489.26 -440.23

    1 2 3

    261.6 528.43 489.26 440.23

    Counter Clockwise end moments are posi4ve

  • Step 3: Design Moments in Exterior Panel A. Design Nega6ve Moments at Cri6cal Sec6on

    At Exterior Support : CL 31.5.3.2

    870

    400 470

    235

    Cri6cal Sec6on from Column Centre line = 435 mm

    261.6 528.43 16.5 x 6.4 = 105.6 kN/m

    105.6 x 7.2/2 - (528.43-261.6)/7.2 = 343 kN

    0.435

    Design Moment = 343 x 0.435 -261.6 -105.6x0.4352/2 = -122.4 kNm (Hogging)

  • At Interior Support : CL 31.5.3.1

    Width of equivalent square = 0.89D = 1335 mm

    667.5 mm

    Cri4cal Sec4on loca4on is at capital face

    0.175x7200 = 1260mm

    261.6 528.43 16.5 x 6.4 = 105.6 kN/m

    343 kN 0.6675

    Design Moment = 417.32 x 0.6675 -528.3 -105.6x0.66752/2 = -273.26 kNm (Hogging)

    417.32

  • B. Design Posi4ve Moment

    M(+) = (16.5 x 6.4x7.2)7.2/8 ( 528.43 + 261.6)/2 = 289.3 kNm

    Moments DDM EFM Posi4ve Moment (Span) 215.4 289.3 Nega4ve Moment(Exterior Support) 164 122.4 Nega4ve Moment (Interior Support) 315.3 273.3

  • Step 4: Design Moments in Interior Panel A. Design Nega6ve Moments at Cri6cal Sec6on

    At Interior Support : CL 31.5.3.1

    16.5 x 6.4 = 105.6 kN/m

    387 kN

    0.6675

    Design Moment at A= 387 x 0.6675 - 489.26 -105.6x0.66752/2 = -254.5 kNm (Hogging)

    373.32

    489.26 440.23

    Design Moment at B = 373.32 x 0.6675 - 440.23 -105.6x0.66752/2 = -214.6 kNm (Hogging)

    0.6675

    A B

  • B. Design Posi4ve Moment

    M(+) = (16.5 x 6.4x7.2)7.2/8 ( 489.26 + 440.23)/2 = 219.5 kNm

    Moments DDM EFM Posi4ve Moment (Span) 158.9 219.5 Nega4ve Moment (Interior Support) 295.1 254.5/214.6

  • Need for Computer Analysis

    The equivalent frame method is not sa6sfactory for hand calcula6ons. It is possible, however, to use computers and plane frame analysis programs if the structure is modeled such that various nodal points in the structure can account for the changing moments of iner6a along the member axis.

    SLAB Drop Panel

    Column Head Column

    Column

  • FE Analysis of Slab

    At any point in the plate bending, there will generally be two bending moments Mx , My in two mutually perpendicular direc5ons coupled with a complimentary twis5ng moment Mxy Design for exure involves providing reinforcing steels in two orthogonal direc5ons to resist the moment eld. Mx, My and Mxy.

    Slab is idealized as an assembly of discrete plate bending elements joined at nodes

    Wood Armer equa4ons are used for this purpose.

  • Wood Armer equa5ons (1968) This method was developed by considering the normal moment yield

    criterion (Johansens yield criterion) aiming to prevent yielding in all direc4ons.

    At any point in the slab, the moment normal to a direc4on, resul4ng due to design moments Mx , My , and Mxy must not exceed the ul4mate normal resis4ng moment in that direc4on.

    Mx* cos2 + My* sin2 - exural strength of plate in the direc4on of with X axis.

    Mx cos2 + Mysin2 + 2 Mxy cos sin - normal bending moment in the direc4on of

  • A. For bomom steel ( Sagging Moment +ve, Hogging Moment ve)

    Compute : Mx* = Mx +|Mxy| and My* = My +|Mxy|

    Case 1: If Mx* 0 and MY* 0 then no change in computed values of Mx* and My*

    Case 2: If Mx* < 0 then Mx* = 0 and MY* = MY + | Mxy2/Mx|

    Case 3: If My* < 0 then My* = 0 and Mx* = Mx + | Mxy2/My|

    B. For Top steel ( Sagging Moment +ve, Hogging Moment ve)

    Compute : Mx* = Mx -|Mxy| and My* = My -|Mxy|

    Case 1: If Mx* 0 and MY* 0 then no change in computed values of Mx* and My*

    Case 2: If Mx* > 0 then Mx* = 0 and MY* = MY -| Mxy2/Mx|

    Case 3: If My* > 0 then My* = 0 and Mx* = Mx -| Mxy2/My|

  • Example 1 FE results at centre of a plate element are: Mx = 7 kNm, My = 23 kNm, Mxy = 9 kNm. Compute design moments using Wood - Armer equa4ons. A. Borom rebars (Sagging Moments)

    Mx* = Mx+|Mxy| = 16 > 0 , Mx* = 16 kNm My* = My+|Mxy| = 32 > 0 , My* = 32 kNm B. Top rebars (Hogging Moments) Mx* = Mx-|Mxy| = -2 < 0 , Mx* = 2 kNm My* = My-|Mxy| = 14 > 0 Set My* = 0 and compute Mx* = Mx -| Mxy2/My| = 7 |81/23| = 3.478 kNm

  • Example 2 FE results at centre of a plate element are: Mx = 7 kNm, My = -23 kNm, Mxy = 9 kNm. Compute design moments using Wood - Armer equa4ons. A. Borom rebars (Sagging Moments)

    Mx* = Mx+|Mxy| = 16 > 0 , Mx* = 16 kNm My* = My+|Mxy| = -14 < 0 , Set My* = 0 and compute Mx* = Mx + | Mxy2/My| = 7 + |81/23| = 10.52 kNm B. Top rebars (Hogging Moments) Mx* = Mx-|Mxy| = -2 < 0 , Mx* = 2 kNm My* = My-|Mxy| = -32 < 0 , MY* = 32 kNm