PL-1 SERIES II Thermostat Installation Guide

12
PL-1 SERIES II Thermostat Installation Guide Version 2.1 Acrolon Technologies, Inc. 19201 SONOMA HIGHWAY, SONOMA, CALIFORNIA 95476 Phone +1 (707) 938-1300, Fax: +1 (707) 938-1342 http://www.acrolon.com

Transcript of PL-1 SERIES II Thermostat Installation Guide

Page 1: PL-1 SERIES II Thermostat Installation Guide

PL-1 SERIES II ThermostatInstallation Guide

Version 2.1

Acrolon Technologies, Inc.19201 SONOMA HIGHWAY, SONOMA, CALIFORNIA 95476

Phone +1 (707) 938-1300, Fax: +1 (707) 938-1342 http://www.acrolon.com

Page 2: PL-1 SERIES II Thermostat Installation Guide
Page 3: PL-1 SERIES II Thermostat Installation Guide

Table of Contents

Chapter 1: Overview................................................................................ 1

Chapter 2: Installation..............................................................................2

Mounting.........................................................................2

Internal Wiring................................................................4

Installing the LID............................................................7

Applying Power..............................................................8

Chapter 3: Specifications.........................................................................

.

TC

Page 4: PL-1 SERIES II Thermostat Installation Guide

OverviewThis manual covers installation of Acrolon's PL-1 thermostat., an industrial-grade temperature controller designed specifically for use wine tanks.

The PL-1 should be mounted onto a protective ice shield on the tank and wired to the cooling and/or heating valves via 16-18AWG 300V wire run inside flex conduit

Key Features:

• Calibration-Free Temperature Sensing

• Two Internal Relays (5A @ 120VAC)

• Easy-to-Use Front Panel Controls and Display

• Industrial-Grade Power Line Communications

• NEMA-4X Rated for Indoor and Outdoor Use

1

1

NO USER SERVICEABLE PARTS INSIDE

ONLY AUTHORIZED, LICENSED PERSONNEL MAY INSTALL OR SERVICE THIS PRODUCT

TO PRESERVE THE PROTECTION AFFORDED BY THIS EQUIPMENT, CLOSE ADHERENCE TO THE PROCEDURES AND INSTRUCTIONS CONTAINED IN THIS DOCUMENT IS REQUIRED. FAILURE TO FOLLOW THE INSTRUCTIONS GIVEN HERE MAY CAUSE FIRE, PERSONAL INJURY OR VOID OR VOID PRODUCT WARRANTY.

Page 5: PL-1 SERIES II Thermostat Installation Guide

Installation

Mounting:1. Install the four mounting brackets supplied with the thermostat per Figure 2.

2. Fasten the PL-1 thermostat to the ice shield per Figure 3 using four #10 x 3/8” long stainless steel self-tapping screws. Note that pilot holes might be required depending upon the material used for the ice shield. Hand tighten each screw to between 8 and 12 inch pounds. DO NOT OVER TORQUE

3. With the thermostat securely fastened to the the ice shield, install 1/2” flexible conduit between the thermostat's leftmost bottom inlet and the power source. Secure conduit with liquid-tight fittings. See Figure 1.

4. Fully install temperature probe into thermowell of tank and run the probe cable through the liquid-tight strain-relief inlet at bottom right of the thermostat. Tighten to 8 and 12 inch pounds or until cable is secure.

Figure 1

2

2

PL-1 Therostat

Flexible Conduit(Power/Solenoid Wiring)

Temperature Probe Installed in probe-well w/ water-tight

cable grip

Ice Shield

HAZARDOUS VOLTAGE. Contact may cause electric shock, burn or result in death. Turn off and lock out system power before servicing or installing.

Liquid -tight ½ Contuit Fitting

Page 6: PL-1 SERIES II Thermostat Installation Guide

Figure 2 (above) Figure 3 (below)

3

Page 7: PL-1 SERIES II Thermostat Installation Guide

Internal Wiring

4

CAUTION: For continued protection against risk of fire, replace only with same type and rating of fuse.

F3: Little fuse, 218P Series, 6.3A/250V time delay, 5 x 20 mm

F1, F2: Wickmann, TE5 Series, 5.0A Time Delay, short pin

Notes:

1. This product must be connected to mains supply only by permanent field wiring using the following wire type: THWN, 18 AWG - 250 KCMIL 300 V, Nylon jacketed w/ high dielectric PVC insulation (UL-83, UL-1063 and UL-758).

2. All electrical connection and conduits are to be made per National Electric Code ANSI/NFPA70, or per the applicable code in the country of installation. Use only conduit and conduit fittings that meet UL 797 safety standard.

3. All wire terminal splice connectors must be UL and CSA rated up to 300 V per UL 486 and temperature rated per UL Flammability UL 94V-2/HB.

This product is intended for use single phase power distribution systems and relies on the building's installation for short-circuit (over current) protection and line voltage disconnect. Protective device (circuit-breaker) rating must not exceed 20 Amps. The installer of this equipment is responsible for provisioning this circuit-breaker, which must be located in the electrical distribution panel (breaker-panel) of the building, in close proximity to the PL-1 thermostat(s) and clearly labeled as being the disconnect for the product.

Compliance is checked by inspection.

ELECTRICAL SHOCK HAZARD: DISCONNECT BREAKERS BEFORE SERVICING OR INSTALLING THIS PRODUCT!

Page 8: PL-1 SERIES II Thermostat Installation Guide

Internal Wiring (continued)Mains Wiring:

1. Pull one each of the following wires colors from the source power through the conduit to the inside of thePL-1 power supply: GREEN (Earth), WHITE (NEUTRAL), BLACK (LINE), RED (cool output), PURPLEor BLUE (heat output). Leave only enough extra length of wire inside the thermostat to allow for easy wirepreparation and termination. USE ONLY THWN, 18 AWG 300V WIRE.

2. Strip back insulation of each wire 1/8”.

3. Remove the power plug from P1 of the power supply and loosen the all screws terminals.

4. Cleanly install the conductor of each wire into Pl plug (with no stray strands) per wiring diagram shown inFigure 4. Tighten the screw terminal as each wire is installed. Torque all screw terminals of P1 to 6 inchpounds.

5. Install the power plug into the Pl receptacle on the power supply.

Probes Wiring: PL-1 Series II Controllers accept both TankNET 4-Wire and 2-Wire temperature probes. Series II PL-1s ship with 2-wire probes unless otherwise requested. Please identify your probe type as either 2-Wire or 4-Wire prior to reading and executing these probe wiring instructions.

4-WIRE PROBE WIRING:

1. Strip back insulation of each probe wire 1/8”.

2. Remove the probe plug from P2 of the power supply and loosen the all screws terminals.

3. Install the conductor of each probe wire into the P2 plug per wiring diagram shown in Figure 4, tighteningeach screw after installing each conductor. Torque all screw terminals of P2 to 6 inch pounds.

4. Install the probe plug into the P2 receptacle on the power supply.

WARNING: FAILURE TO CONNECT PROPER INPUT VOLTAGE MAY CAUSE FIRE OR DESTROY PRODUCT AND SHALL VOID PRODUCT WARRANTY!

5

Figure 4

6000-024-S2 = 24VAC INPUT VOLTAGE 6000-120-S2 = 120VAC INPUT VOLTAGE

pbegidio
Text Box
R2
pbegidio
Text Box
R2
pbegidio
Text Box
R2
Page 9: PL-1 SERIES II Thermostat Installation Guide

2-WIRE PROBE WIRING:

1. Install the PL-1 thermostat per Acrolon’s PL-1 Installation Guide while disregarding the 4-wire probe wiring information provided with in it.

2. Pull approximately 6” of probe cable through the liquid-tight cable gland located at bottom right of PL-1 power supply.

3. Strip back the outer jacket of the probe cable about 1” from the cut end of the cable. Take care not to breach the insulation of either of the two internal wires contained within the cable jacket.

4. Strip back approximately 1/8” of insulation from both the red and black wires of the probe cable.

5. Remove the 4-terminal “PROBE” plug from the PL-1 power supply.

6. Insert the RED wire into the leftmost terminal of the PROBE plug as shown in Figure 1, and secure by hand tightening the terminal screw using a 4mm x 2.5mm standard screw driver. Insert the BLACK wire into terminal immediately adjacent to the right of the RED wire per figure below, and secure as previously described above.

7. If the probe cable has been extended, be sure to use shielded cable and terminate the shield or drain-wire at JP8 per illustration below.

8. Install the PROBE plug into PL-1 display at “JP8” location.

9. Reduce excess probe cable from within the PL-1 by pulling the cable back through the cable gland of the power supply and then tighten the gland to ensure a water-proof seal around the probe cable.

6

Page 10: PL-1 SERIES II Thermostat Installation Guide

PL-1 Display Installation

1. Verify internal power and probe wiring

2. Hold the PL-1 display assembly with your right hand with front panel against your palm.

3. Align inside right edge of display assembly with the right edge of the power supply assembly.

4. With your left hand connect the 8-conductor ribbon cable from the power supply to the mating receptacle on the display assembly (see figure 5).

5. With your left hand connect the 4-conductor ribbon cable from the power supply to the mating connector on the display assembly (see figure 5).

6. Align the mounting screws of the display assembly with the threaded holes on the power supply assembly.

7. Using a Phillips screw driver tighten each mounting screw starting at upper left, then lower right, the upper right, and finally lower right. Tightening the LID screws in this fashion prevents binding between the PL-1 display and the power supply. Hand tighten ONLY to 10 to 12 inch pounds. DO NOT OVER TORQUE.

Figure 5

7

Page 11: PL-1 SERIES II Thermostat Installation Guide

Applying Power

The PL-1 thermostat connects to the mains supply through permanent field wiring via circuit-breaker located in the electrical distribution panel of the building. This circuit-breaker serves as the disconnect for the thermostat and should be clearly marked as such in the panel.

Apply power to the PL-1 thermostat(s) by switching ON (closing) the corresponding circuit-breaker inside the distribution panel to which the thermostat is connected. .

8

ELECTRICAL SHOCK HAZARD: BEFORE APPLYING POWER ENSURE THAT ALL WIRING IS CORRECT AND THAT THE PL-1 LID IS SECURELY FASTENED TO THE PL-1 POWER SUPPLY BASE.

Page 12: PL-1 SERIES II Thermostat Installation Guide

Specifications

Part Number:

The part number scheme for the PL-1 thermostat is as follows:

6000-XXX

Where: XXX: 120 or 024, indicates the power supply input voltage (120VAC or 24VAC) as measured between line and neutral

Specifications:

Input Voltage 6000-120: 120 Vac, 50/60 Hz, 0.05A

6000-024: 24 Vac, 50/60 Hz, 0.20A

Relay Contacts COOL RELAY (N.O / COM / N.C): 5A @ 120VACHEAT RELAY (N.O / COM / N.C): 5A @ 120VAC

Operating Temperature 0 to +50ºC

Storage Temperature -10 to +60ºC

Network Transceiver Power Line PL-20N (1A p-p)

Enclosure Polycarbonate, UL50, NEMA-4X Rated

Safety Agency Listing ETL

9