Pipeline Valve Spacing - Comparison of Codes

download Pipeline Valve Spacing - Comparison of Codes

of 10

Transcript of Pipeline Valve Spacing - Comparison of Codes

  • 7/21/2019 Pipeline Valve Spacing - Comparison of Codes

    1/10

    TABLE D1. PIPELINE VALVE SPACING AND DESIGN REQUIREMENTS IN GAS TRANSMISSION PIPELINE CODES

    No. Pipeline Code Code Approach Valve Spacing

    Basis

    Valve spacing Reqts...... Val

    1 US B31.8-1995 Edition Design is based on a class

    location concept with valve

    spacing, and allowable

    stress levels based on theclass location.

    Building Density/

    class location.Class 1. Para. 846.11, "the

    spacing between valves on

    a new transmission line

    shall not exceed 20 mi.inLocation Class 1."

    Class 2.Para.846.11, "the

    spacing between valves on

    a new transmission line

    shall not exceed 15 mi.inLocation Class 2.

    Class 3.Para.846.11, "the

    spacing between valves on

    a new transmission line

    shall not exceed 10 mi.inLocation Class 3 ."

    Class 4.Para.846.11, "the

    spacing between valves on

    a new transmission line

    shall not exceed 5 mi.inLocation Class 4"

    846.2

    not re

    autom

    the Cof au

    prese

    provid

    piping

    Their

    shall

    the o

    UNIF

    LOCA

    HISTORICAL DATA 1955-1968

    CODES

    Class 1, 20 mile spacing Class 2, 15 mile spacing Class 3, 8 mile spacing Class 4, 5 mile spacing

    2 US 49CFR Part 192 Based on ASME B31.8.

    Design rules are based on

    a class location concept.

    The class location concept

    was modified from that in

    the B31.8 Code in 1968 to

    a specific number ofhouses in a 1/4 mile width,

    one mile long with only

    one density index .

    Building Density 192.179(4) Each point on a

    pipeline in a Class 1

    location must be within 10

    miles of a sectionalizing

    block valve.

    192.179 (3) Each point on

    a pipeline in a Class 2

    location must be within 7.5

    miles of a sectionalizing

    block valve.

    192.179 (2) Each point on

    a pipeline in a Class 3

    location must be within 4

    miles of a sectionalizing

    block valve.

    192.179 (1) Each point on

    a pipeline in a Class 4

    location must be within 2.5

    miles of a sectionalizing

    block valve.

    192.1

    and t

    open

    must

    and p

    tamp

    UNIF

    LOCA

    HISTORICAL DATA-1968

    D1

  • 7/21/2019 Pipeline Valve Spacing - Comparison of Codes

    2/10

    TABLE D1. PIPELINE VALVE SPACING AND DESIGN REQUIREMENTS IN GAS TRANSMISSION PIPELINE CODES

    No. Pipeline Code Code Approach Valve Spacing

    Basis

    Valve spacing Reqts...... Val

    3 Canadian Z662-94, Oil and

    Gas Pipeline Systems Note,

    a revision is due out in 1997 but

    the areas of interest hereinhave not changed.

    Based on ASME B31.8 .

    Specified design rules

    based on a class location

    concept.

    4.4.3, Valves shall

    be located

    upstream and

    downstream of anypipeline segment at

    a spacing not

    greater than the

    applicable value

    given in Table 4.6

    Table 4.6 shown in

    valve spacing

    reqts... columns

    Table 4.6 as follows: For

    gas pipelines in Class 1

    Location, valves are not

    required.

    Table 4.6 as follows: For

    gas pipelines in Class 2

    Location, 25 km (15.6

    miles) valve spacing.

    Table 4.6 as follows: Class

    3 Location, 13 km (8.1

    miles) valve spacing.

    Table 4.6 as follows: Class

    4 Location, 8 km (5miles)

    valve spacing.

    There

    for va

    on ga

    lines requir

    autom

    autom

    shall

    UNIF

    LOCA

    4 Australian SAA AS 2885-1987 Based on a class location

    concept where the classes

    are based on individual

    size and not number of

    houses, similar in some

    respects to IGE TD/1.

    Class Location Table 3.4, Location Class

    R1, as required

    Table 3.4, Location Class

    R2, 30 km. max. (18.8

    mi.)

    Table 3.4, Location Class

    T1 and T2, 15 km. max.

    (9.4 mi.)

    Valve

    that in

    the va

    exped

    Wher

    valve

    opera

    UNIF

    LOCA

    D2

  • 7/21/2019 Pipeline Valve Spacing - Comparison of Codes

    3/10

    TABLE D1. PIPELINE VALVE SPACING AND DESIGN REQUIREMENTS IN GAS TRANSMISSION PIPELINE CODES

    No. Pipeline Code Code Approach Valve Spacing

    Basis

    Valve spacing Reqts...... Valv

    5 UK Pipelines Safety

    Regulations 1996

    A risk based approach that

    requires that the lines be

    designed, operated and

    maintained so that the riskto the public is acceptable.

    No specified

    spacing

    requirements.

    Emergency shut-down valves are

    required.

    Sched. 3 requires

    emergency shut-down

    valves to be normally

    closed valves, be capableof being closed, be able to

    pass equipment for

    inspecting and testing, be

    protected from damage

    arising from fire, explosion

    or impact and be

    maintained .

    Sched

    emerg

    valve s

    of beinperson

    (b) aut

    operat

    emerg

    system

    installa

    pipelin

    6 Institute of Gas Engineers

    TD/1 Edition 3, 93

    Design basis based on

    class location concept

    defined on the basis of

    number of persons / unit

    area.

    Judgment and

    operational

    considerations

    6.13.1 In a cross-country

    pipeline, valves should be

    provided at periodic

    intervals and may be hand-

    operated, automatic or

    remotely controlled.

    6.13.1 In built-up areas,

    the spacing of valves

    should be reduced. In

    determining the spacing of

    valves, consideration

    should also be given to

    operating pressure,

    pipeline diameter, time

    taken to arrive at the valve

    site, (cont.)

    6.13.1

    hand o

    or rem

    probability of leakage, theneed for valves for

    operational purposes, the

    position of the nearest

    offtakes and other existing

    valves. 6.13.2 The valves

    should be installed in

    readily accessible

    positions.

    UNIFO

    LOCA

    D3

  • 7/21/2019 Pipeline Valve Spacing - Comparison of Codes

    4/10

    TABLE D1. PIPELINE VALVE SPACING AND DESIGN REQUIREMENTS IN GAS TRANSMISSION PIPELINE CODES

    No. Pipeline Code Code Approach Valve Spacing

    Basis

    Valve spacing Reqts...... Val

    7 ISO 13623, Draft 9/7/96 Design is based on a class

    location concept.

    6.11 Place where

    required for

    operation,

    maintenance, and

    control of

    emergencies

    No specific requirements. 6.11

    opera

    isolat

    estab

    deter

    UNIFLOCA

    8 NEN 3650 (Netherlands) Code specifies two design

    approaches; 1) a risk

    approach that assures that

    each transport pipeline is

    designed, constructed and

    operated such that the

    additional risk to the

    surrounding area is

    acceptable, i.e., 2.5- 10 MPa

    (363-1450 psi) and 2

    (pressure >1.2 - 2.5 MPa

    (174-363 psi). In addition,

    there are 5 Categories, B,

    I, II, III, IV (cont.)

    No specific

    requirements

    presented

    Not more than 30 km (18.6 mi) apart. They are to be on both sides of water obstacles crossed by pipelines that

    are crossed by two or more lines.

    No m

    The gas design categories

    are a function of : gas

    versus oil, diameter and

    pressure; buried, on

    ground, or above ground;

    road crossings, railroad

    crossings, river crossings;

    distances to valves,

    compressor stations and

    gas treatment plants,

    (cont.)

    and stability of the ground.

    10 Euro Norm p EN 1594

    (CEN/TC 234)

    Design requirements are

    specified for buried piping,

    piping in a tunnel

    continuously supported

    and in stations. No class

    locations are defined

    No specific valve spacing requirements 6.5 P

    sectio

    which

    autom

    contr

    D4

  • 7/21/2019 Pipeline Valve Spacing - Comparison of Codes

    5/10

    TABLE D1. PIPELINE VALVE SPACING AND DESIGN REQUIREMENTS IN GAS TRANSMISSION PIPELINE CODES

    No. Pipeline Code Code Approach Valve Spacing

    Basis

    Valve spacing Reqts...... Valv

    This is a code that has

    minimum requirements for gas

    pipelines. If it is more stringent

    than a countries code it wouldapply (European countries.) It

    is weighted on the maintenance

    and operation of pipelines.

    Applies to pipelines operated at

    >16 bar.

    11 German DIN 2470, 2413, and

    Construction Code 463

    Bases design on the

    elongation properties of the

    steel. No class locations

    are included.

    German Standard 463 , Par.. 3.2.2 , indicates that the distance between two main shut-off devices is determined

    by the local conditions and requirements for supply; a distance of 10 to 18 km (6 to 11.3 mi) is generally

    adequate.

    N

    12 Algerian Pipeline Code -

    Safety Regulations

    Concerning Transportation'

    Pipelines of Combustible Gas

    Based on Class Locations

    which are defined on the

    basis of population

    Based on Class

    Locations

    Article 31, Spacing

    between two gate valves in

    Zones 1 and 1a will not

    exceed 10 Km (6.1 mi.). Inurban areas, the volume of

    gas measured under

    normal conditions, between

    two successive valves shall

    not exceed 90,000 cu.

    meters.

    Article 31, Spacing

    between two gate valves in

    Zones 2 and 3 will not

    exceed 20 km (12.2 mi.).In urban areas, the volume

    of gas measured under

    normal conditions, between

    two successive valves shall

    not exceed 90,000 cu.

    meters.

    Article

    other

    rapidly

    flow, eautom

    comm

    install

    on the

    13 French Pipeline Design Code Based on Class Locations

    which are defined on the

    basis of population

    Based on three

    Class Locations

    20 km in Class 1 20 km in Class 2 10 km in Class 3 None

    Information is based on verbal

    information obtained from Gas

    de France.

    All class locations have a requirement for the gas volume between valves to be 90,000 cu. meters or less. UNIFO

    LOCA

    14 Regulations Concerning

    Transportation of Petroleum

    in Onshore Pipelines, 1986-

    Norway Directorate for Fireand Explosion Prevention

    Based on the Canadian Z

    183 and Z 184.

    Class Location 32 km (20 mi) in Class 1 24 km (15 mi) in Class 2 12 km (7.5 mi) in Class 3 8 km (5 mi) in Class 4 None

    UNIFO

    LOCA

    D5

  • 7/21/2019 Pipeline Valve Spacing - Comparison of Codes

    6/10

    No. Pipeline Code

    1 US B31.8-1995 Edition

    2 US 49CFR Part 192

    Pipeline Corridor for

    Class Location

    Retroactive

    Application?

    Discussion Design Basis

    220 yds (200 m) on either

    side of the pipeline

    Yes, with regard to the

    design stress (Class

    Location change). No,

    with regard to valvespacing.

    846.21c Spacing may be

    adjusted slightly to permit a

    valve to be installed in a

    more accessible location,with continuous accessibility

    being the primary

    consideration.

    Building Density (population

    density) with the design

    factors based on nominal

    wall thickness and outsidediameter.

    Class 1, Div. 1, 0.80 de

    factor for new constructi

    table 841.114A; Div. 2,

    design factor, per Table

    841.114A for new const

    (Div. 2.) for all API 5L pip

    except furnace butt weld

    0.43 design factor for fu

    (contd)

    846.21d, Automatic valve

    closures are not required.

    butt weld pipe. 0.60 des

    factor for (1) crossing of

    unimproved public roads

    highways, or public stree

    hard surfaces, and railro

    without casings and (2)

    encroachment of pipelin

    mains on roads, (cont.)

    highways or public stree

    hard surfaces and railro

    Also at fabricated assem

    and pipelines on bridges

    0.72 design factor for all

    road and railroad crossin

    0.50 design factor for

    compressor station pipin

    near concentration of pe

    One mile density index,

    count the number of

    buildings in a zone one-halfmile on each side of the

    pipeline and one mile long.

    The 10 mile density index is

    the sum of the one mile

    density indexes for any 10

    mile length of line.

    Class location is the basis

    for design.

    Class 1, 0.72 design fac

    220 yds (200 m) on either

    side of the pipeline

    Yes, per Par... 192.609

    and 192.611. with regard

    to design factor. No with

    regard to valve spacing.

    Building Density with the

    design factors based on

    nominal wall thickness and

    outside diameter.

    Class 1, 0.72design fac

    192.111.

    0.60 design factor or les

    steel pipe in Class 1 loca

    that: (1) Crosses the rig

    way of an unimproved p

    road, with a casing; (con

    (2) Crosses without a ca

    makes a parallel encroa

    on, the right-of-way of ei

    hard surfaced road, a hig

    a public street , or a railr

    (cont.)

    (3) Is supported by a veh

    pedestrian, railroad, or pbridge; or

    (4) Is used in a fabricate

    assembly, or is used wit

    pipe diameters in any dir

    from the last fitting of (co

    a fabricated assembly, o

    than a transition piece o

    elbow used in place of a

    bend which is not assoc

    with a fabricated assemb

    0.50 design factor for ste

    in a compressor station,

    regulating station, or me

    station; and steel pipe, a pipe riser, on a platfor

    located offshore or in inla

    navigable waters.

    D6

  • 7/21/2019 Pipeline Valve Spacing - Comparison of Codes

    7/10

    No. Pipeline Code

    3 Canadian Z662-94, Oil and

    Gas Pipeline Systems Note,

    a revision is due out in 1997 but

    the areas of interest hereinhave not changed.

    4 Australian SAA AS 2885-1987

    Pipeline Corridor for

    Class Location

    Retroactive

    Application?

    Discussion Design Basis

    Class Location areas shall

    extend 200 m (220 yds.) on

    both sides of the centerline

    of any continuous 1.6 km (1mi.) length of pipeline

    except as defined at the

    ends.

    Yes, Par. 10.7.1.

    indicates that where class

    locations change as a

    result of changes inpopulation density or

    location development, an

    engineering assessment

    shall be made to

    determine if the pipeline

    is satisfactory for the

    changed class location.

    4.4.4 It shall be permissible

    to adjust the valve spacing

    and location specified in

    Clause 4.4.3 based onfactors such as operational,

    maintenance, access, and

    system design

    considerations. Note: Valve

    spacing adjustments should

    not (cont.)

    Population Density using a

    Class Location factor, a

    proximity factor and a

    design factor of 0.8. Wallthickness is the design wall

    thickness and the diameter

    is the outside diameter of

    the pipe. (cont.)

    Class 1, Table 4.1, Gen

    and cased crossings hav

    allowable stress of 0.8

    (1.00*0.8) SMYS. and Other* have an allow

    stress of 0.6 (0.75*0.8)

    Railways and stations ha

    allowable stress of 0.5

    (0.625*0.8) SMYS.

    exceed 25 % of the

    applicable distances listed in

    Table 4.6.

    Nominal wall thickness

    equals the design thickness

    plus the corrosion

    allowance, plus the

    threading and groove

    allowances. Nominal wallcannot be less than the

    design wall thickness.

    Outside diameter of the pipe

    and the SMYS are used

    *Other: Piping that is (a)

    assembly; or with five

    4.4.9 For gas pipeline

    systems, blowdown valves

    shall be located so that the

    sections of transmission

    lines between sectionalizing

    valves can be blown down.

    Sizes and capacities of the

    connections for blowing

    down transmission lines

    shall be (cont.)

    in pla

    such that, under emergency

    conditions, the section can

    be blown down as rapidly as

    practicable. Locations of

    blowdown valves shall be

    such that the gas can be

    blown to the atmosphere

    without undue hazard.

    There is no specificdefinition of Corridor width

    for determining Location

    Types. Par. 3.5.2.9 states"

    Where a point on a pipeline

    in a Class R1 location or a

    Class R2 location is within

    100 m of a location where

    the average daily

    congregation is (cont.)

    3.5.2.8Yes at intervalsnot exceeding 5 years,

    and where necessary,

    appropriate corrective

    action shall be taken.

    Concentration of thepopulation without specific

    building density

    requirements. Outside

    diameter is used with the

    nominal wall thickness which

    cannot be less than 10 mm

    (0.393 inch) where wall

    thickness and depth of

    cover provide third party

    protection.

    3.6 & 3.7 Class R1. Desfactor is 0.72 with a third

    damage factor of 1 resu

    design factor of 0.72. (A

    the SMYS of a published

    specification unless the a

    yield strength is determin

    field test.) Min. w.t.=10 m

    (3.7.2.2)

    more than 20 people, the

    pipeline shall be considered

    to be in a Class t1 locationfor a distance of 100 m in

    both directions from that

    point. It appears that 100 m

    is the corridor width.

    3.1.5.2 Required wall

    thickness cannot be less

    than pressure designthickness (PD/2sigma y)

    plus manufacturing under

    tolerance if greater than

    12.5%, plus corrosion,

    threading and machining

    tolerance.

    D7

  • 7/21/2019 Pipeline Valve Spacing - Comparison of Codes

    8/10

    No. Pipeline Code

    5 UK Pipelines Safety

    Regulations 1996

    6 Institute of Gas Engineers

    TD/1 Edition 3, 93

    Pipeline Corridor for

    Class Location

    Retroactive

    Application?

    Discussion Design Basis

    Not applicable Yes, requires that

    modification,

    maintenance or other

    work on a pipeline iscarried out in such a way

    that its soundness and

    fitness for the purpose for

    which it has been

    designed will not be

    prejudiced.

    Reg. 5, that a pipeline shall

    be designed to withstand

    the expected strains and

    processes. Reg. 8, that apipeline be constructed of

    suitable materials. Reg. 9,

    that it be constructed and

    installed that it is sound and

    fit for its purpose.

    No specific requirements

    than that it suitable for th

    intended usage.

    Reg. 11, that the safe

    operating limits of a pipeline

    be established and not

    exceeded, save for testing.

    Reg. 12 that adequate

    arrangements be made for

    dealing with incidents andemergencies involving a

    pipeline.

    6.8.2 Population density,

    expressed as the number of

    persons per unit hectare,

    should be the average for

    each 1.6 km (1 mi.) of

    pipeline in a strip centered

    on the pipeline of a width 8

    times the minimum building

    proximity distance (BPD) for

    a (cont.)

    1) Min. wall; 2) Outside

    diameter of pipe, 3)

    Population density; 4)

    Fatigue cycles and 5)

    specified minimum yield

    stress.

    6.8.4.1 Design factor s

    not exceed 0.72and de

    pressure should not exc

    bar (1500 psi). (cont.)

    Type R area pipeline as

    defined in Figure 2. (Figure

    2 presents BPD that range

    from 10 to 110 m. For 508

    mm (20 inch) diameter lines

    at 66.7 bar (1000 psi), the

    BPD ranges from 50 to 90

    m.

    6.8.4.2 If wall thickness

    exceeds 19.1 mm (0.75

    then 19.1 mm will suffice

    provided the design fact

    less than 0.5. Also, if ris

    analysis justifies it, the B

    from Table 3 S Type are

    be used (Appendix 3 pro

    guidelines.)

    6.8.4.2 When design fac

    less than 0.3, BPD in Ta

    may be used, other wise

    values.

    TRAFFIC: 6.11.1 Pipeli

    which either cross, or en

    with, the appropriate pro

    distance of a high densit

    route, should have a nom

    thickness of not less tha

    mm (0.469-in). The des

    factor should not exceed

    (cont.)

    However, when this calls

    pipe with a nom. wall thi

    of 19.1 mm (0.75 in) , th

    mm pipe is acceptable,

    that it does not result in t

    design factor exceeding

    higher design factor may

    justified by risk analysis.

    6.11.2 Pipelines crossin

    running within the bound

    other traffic routes shoul

    a nom. wall thickness of

    than 9.52 mm (0.375-in)

    should have impact prot

    The design factor should

    exceed 0.30. (cont.)

    D8

  • 7/21/2019 Pipeline Valve Spacing - Comparison of Codes

    9/10

    No. Pipeline Code

    7 ISO 13623, Draft 9/7/96

    8 NEN 3650 (Netherlands)

    9 SNIP 2.05.06-85 Russian

    Pipeline Code

    10 Euro Norm p EN 1594

    (CEN/TC 234)

    Pipeline Corridor for

    Class Location

    Retroactive

    Application?

    Discussion Design Basis

    However, when this calls

    pipe with a nom. wall thi

    of 19.1 mm (0.75 in) , th

    mm pipe is acceptable, that it does not result in

    design factor exceeding

    higher design factor may

    justified by risk analysis.

    Annex B. Class 5,

    multistory buildings, traffic

    is heavy or dense, and

    numerous underground

    utilities.

    400 m (440 yds) in width

    centered on the pipeline and

    for a sliding length of 1.5 km

    (0.94 mi).

    Outside diameter minus t

    min., t min, and P int. - P

    ext., Sigma y is SMYS at

    max. design temp.

    Class 1. 0.83

    Same as US, Can. Class4.

    A1.2 The corridor width is

    based on a "critical

    distance" on either side of

    the pipeline. The length is

    also taken as the "critical

    distance". The critical

    distance is a function of the

    diameter and operating

    pressure. (cont.)

    Design factor based on

    location class and whether it

    is in a pipeline corridor. The

    design factors are; 1.39

    (0.72), 1.50 (.67), and 1.82

    (.55) applied to the hoop

    stress based on average

    diameter (D-t) and tmin.

    The allowable stress is the

    SMYS.

    Location class 1. In des

    pipeline corridors,DF

    (0.72) for mechanical da

    protection. Other pipelin

    = 1.39 (0.72).

    For dia... of 8 in (200 mm),the critical distance is 4, 5,

    and 5 m for 20-50, 50-80.

    and 80-110 bar pressures

    respectively. For 30 in (750

    mm) dia..., the critical

    distance is 30 and 35 m for

    50-80 and 80-110 bar

    pressures respectively.

    (Table A2-1)

    There is also a minimexample, 219.1 mm (8 i

    and for 914 mm (3

    crossings, canal cross

    Allowable stresses

    outside of a pipeline

    corridor.

    Location class 1. Outsid

    designated pipeline co

    Max. Allowable stress =0

    SMYS or ).72 x 0.75 SM

    which ever is lower.

    Category IV, below Grd.

    lines < 1200 mm (47.2 in)

    in dia..,

    None defined since class

    location does not include a

    width on the sides of the

    pipeline.

    Unknown The specified minimum

    ultimate stress is the basis.

    This is modified by the type

    of pipe and the location

    category of the pipe as well

    as the load factor (how well

    the load is known, i.e.,

    seismic/soil movementloads versus pressure

    loads).

    Category B, m=0.60, s

    allowable stress as 0.43

    (for welded steel pipe wi

    0.85 Y/U, this equals 0.5

    SMYS. However, they h

    load factor that ranges f

    to 1.15. Thus, the allow

    could be between 0.50 aSMYS.)

    Maximum stress is 0.72

    SMYS based on OD and

    min wall thickness for buried

    piping and piping

    continuously supported in a

    tunnel. In a station, the

    maximum stress is 0.67

    SMYS.

    D9

  • 7/21/2019 Pipeline Valve Spacing - Comparison of Codes

    10/10

    No. Pipeline Code

    This is a code that has

    minimum requirements for gas

    pipelines. If it is more stringent

    than a countries code it wouldapply (European countries.) It

    is weighted on the maintenance

    and operation of pipelines.

    Applies to pipelines operated at

    >16 bar.

    11 German DIN 2470, 2413, and

    Construction Code 463

    12 Algerian Pipeline Code -

    Safety Regulations

    Concerning Transportation'

    Pipelines of Combustible Gas

    13 French Pipeline Design Code

    Information is based on verbal

    information obtained from Gas

    de France.

    14 Regulations Concerning

    Transportation of Petroleum

    in Onshore Pipelines, 1986-

    Norway Directorate for Fire

    and Explosion Prevention

    Pipeline Corridor for

    Class Location

    Retroactive

    Application?

    Discussion Design Basis

    Not applicable No DIN 2470 defines allowable

    stress levels based on steel

    yield strength.

    200 m along the line, +/-

    100 m perpendicular to the

    line.

    Code does not appear to

    be retroactively applied

    when zones change.

    Thickness is based on the

    min. wall, OD. The

    allowable stress is limited to

    a percent of the yield stressand or the ultimate stress.

    Zone 3, 80 % minimum

    stress (SMYS), or 60 %

    ultimate stress (SMUS-s

    minimum ultimate stressBased on t, which is nom

    minus the under thickne

    tolerance and the outsid

    diameter.

    A second requirement is

    maximum operating pre

    cannot exceed .85 times

    test pressure which mus

    least 90 % of the SMYP

    A brief review indicated

    reducing the stress by

    200 m along the line, 100 m

    perpendicular to the line.

    Code does not appear to

    be retroactively applied

    when zones change.

    Class Location, however,

    information on use of min.

    wall and average dia. was

    not available.

    Class 1, 0.73 SMYS

    A route unit is determined

    continuously along a

    pipeline and is an area 1000

    m along the line, 200 m oneither side of the line.

    Class 1 and 2 locations

    are to be survey annually.

    Class 3 and 4 locations

    are to be surveyed every6 months.

    Class location Class 1, 0.72

    Desi

    D10