PI 825P/50Hz PI 825P/60Hz · 1500 50Hz 400 750 600 825 660 1800 60Hz 480 750 600 825 660 Engine...
Transcript of PI 825P/50Hz PI 825P/60Hz · 1500 50Hz 400 750 600 825 660 1800 60Hz 480 750 600 825 660 Engine...
-
PI 825P/50HzPI 825P/60Hz
Output Power Ratings Prime* Standby** rpm Frequency Voltage Kva kW Kva kW 1500 50Hz 400 750 600 825 660 1800 60Hz 480 750 600 825 660
Engine Technical Data Engine Make and Model Perkins 4006-23TAG2A Cylinders 6 Vertical In-Line Aspiration Turbocharged Air- to- Air Charge Cooled Combustion System Direct Injection Displacement 22.9liters Governor Electronic Emissions Regulations ½ TA Luft Electrical Starting System 24 Volt Starter Motor And 24 Volt 70 Amp Battery Charging Alternator
Air Systems Air Filter Type Dry-Paper (Replaceable)
Combustion Air Flow m3/min (cfm)
Prime
Standby
50 Hz 60 Hz 2260.13) 64) 2295.45) 65) 2507.34) 71) 2577.97) 73)
Maximum Air Filter Intake Restriction 3.7 kPa 3.7 kPa
Fuel System Fuel Filter Type Changeover (Optional) Recommended Fuel Class A2 Diesel
Fuel
Consumption l/hr (US gal/hr)
Engine speed 1500 rpm 1800 rpm Standby 45.7) 173) 52.6) 199) Prime Power 41.5) 157) 46.8) 177) %75 of Prime Power 32.0) 121) 34.1) 129) %50 of Prime Power 21.9) 83) 23.8) 90)
Fuel Tank Capacity: Open / Close 1630L / 1800 L
Lubrication System Lube Oil API-CG4, SAE 15W-40 (-°10 C to °50 C Ambient Temperature) Lube Oil Capacity 113.4 L Oil Pan 90.7 L Oil Filter Type Changeover (Optional) Oil Cooling Method Water
Cooling System Coolant Capacity 105 L Cooling System Mounted Radiator, Water Cooled Cooling Fan Air Flow m3/min (cfm) 42377.6) 1200) 46615.3) 1320)
Heat Radiation to Room 50 Hz 60 Hz
Prime 55kW 73kW Standby 76kW 81kW
Exhaust System Silencer
Grade Industrial Size 6” Qty 2
Exhaust Gas Flow m3/min (cfm)
Prime 6356.64) 180) 6709.78) 190) Standby 6356.64) 180) 6709.78) 190)
Maximum Allowable Backpressure 6 kPa 6 kPa
Exhaust Gas Maximum Temp
50 Hz 60 Hz Prime °430C °430C Standby °430C °430C
Alternator Technical Data Stamford Model Number HCI 634G No. of Poles 4 Number of Terminals (Leads) 6 A.V.R. & Excitation MX321 ( PMG) Regulation ±0.5% Ingress Protection IP-23 Insulation Class H Total Harmonic TGH / THC
-
PI 825P/50HzPI 825P/60Hz
Notes:*Prime power rating of the generating set is where a variable load and unlimited hours usage are applied on the generating set with an average load factor of 80% of the prime rating over each 24 hour period. Noting that a 10% overload is available for 1 hour in every 12 hours operation
**Standby power rating of the generating set is where a variable load limited to an annual usage upto 500 hours is applied, with 300 hours of which may be continuous running. Noting that no overload is permitted
All generators carry a one year or (1000) hours’ manufacturer’s warranty
In line with our policy of continuous development, PI reserves the right to change specification without notice
Controller Features Deep Sea 4520 or Eq.
Controller Make and Model Auto Mains Failure (AMF) applications including remote communication , User configuration and complete gen-set monitoring and protection. Ready for generators with 3 ph 4 wires / 3 ph 3 wires / Mono ph
Engine Protections Oil pressure Coolant temperature
Fuel level (Optional) Coolant level (Optional)
Generator Protections Over / Under voltage Over/Under frequency Phases Sequence
Over current Charging Alternator Fault
Inputs and Outputs 3 No’s Configurable analog inputs 4 No’s binary inputs
6 No’s binary outputs D + Pre-Excitation terminal
Event and Performance Log Gen-set text alarm log For More Features We Can Use Higher Controller
Engine hours history log
Genset Enclosure Specification (optional) Enclosure Type Acoustic and Weather Proof Anticorrosive Protection Polyester Powder Coated Galvanized Sheet Access Doors 6 Drainage Fuel & Water Drainage Provision Transportation Tested Double Point Lifting Facility & Forklift Pockets Noise Level (@ Free-Field Conditions) 77 dBA @ 7 meter Water Fill Radiator Water Filling Provision Cable Access Cable Inlet and Outlet Provision Emergency Stop External Emergency Push Button Canopy RAL Color RAL 2000 Chassis RAL Color RAL 9011
Shipping Data Type Length (mm) Width (mm) Height (mm) Weight (kg) Open 4520 2000 2450 5393 Enclosed 5965 2065 3110 7330
-
4000 Series 4006-23TAG2A Diesel Engine – ElectropaK695 kWm @ 1500 rpm
www.perkins.com
Photographs are for illustrative purposes only and may not reflect final specification.All information in this document is substantially correct at time of printing and may be altered subsequently. Final weight and dimensions will depend on completed specification. Publication No. PN1738A/12/14 Produced in England ©2014 Perkins Engines Company Limited
Specification
Number of cylinders 6 vertical in-line
Bore and stroke 160 x 190 mm 6.3 x 7.5 in
Displacement 22.921 litres 1397 in3
Aspiration Turbocharged and air-to-air charge cooled
Cycle 4 stroke
Combustion system Direct injection
Compression ratio 13.6:1
Rotation Anti-clockwise, viewed on flywheel
Total lubricating capacity 113.4 litres 29.5 US gal
Cooling system Water-cooled
Total coolant capacity 105 litres 27.7 US gal
The Perkins® 4000 Series is a family of 6, 8, 12 and 16 cylinder diesel engines, designed to address today’s uncompromising demands within the power generation industry with particular aim at the standby market sector. Developed from a proven engine range that offers superior performance and reliability.
The 4006-23TAG2A is a turbocharged and air-to-air charge cooled, 6 cylinder diesel engine offered with either temperate or tropical cooling. Its premium features and design provide economic and durable operation as well as an exceptional power to weight ratio, excellent load acceptance and improved gaseous emissions, plus the overall performance and reliability characteristics essential to the power generation market.
-
www.perkins.com
Photographs are for illustrative purposes only and may not reflect final specification.All information in this document is substantially correct at time of printing and may be altered subsequently. Final weight and dimensions will depend on completed specification. Publication No. PN1738A/12/14 Produced in England ©2014 Perkins Engines Company Limited
4000 Series 4006-23TAG2A Diesel Engine – ElectropaK695 kWm @ 1500 rpm
Features and benefits
Economic powerl Individual 4 valve cylinder heads giving optimised gas flowsl Unit fuel injectors ensure ultra fine fuel atomisation and hence controlled rapid combustionl Commonality of components with other engines in the 4000 Series family for reduced stocking levels
Reliable powerl Developed and tested using the latest engineering techniquesl Piston temperatures controlled by an advanced gallery jet cooling systeml Tolerant of a wide range of temperature without derate
Compact, clean and efficient powerl Exceptional power to weight ratio and compact size give optimum power density for easier transportation and
installationl Designed to provide excellent service access for ease of maintenancel Engines to comply with major international standardsl Low gaseous emissions that will satisfy the requirements of ½ TA Luft (1986)
Product supportl Perkins actively pursues product support excellence by ensuring our distribution network invest in their territory –
strengthening relationships and providing more value to you, our customerl Through an experienced global network of distributors and dealers, fully trained engine experts deliver total
service support around the clock, 365 days a year. They have a comprehensive suite of web based tools at their disposal covering technical information, parts identification and ordering systems, all dedicated to maximising the productivity of your engine
l Throughout the entire life of a Perkins engine, we provide access to genuine OE specification parts and service. We give 100% reassurance that you receive the very best in terms of quality for lowest possible cost .. wherever your Perkins powered machine is operating in the world
-
www.perkins.com
Photographs are for illustrative purposes only and may not reflect final specification.All information in this document is substantially correct at time of printing and may be altered subsequently. Final weight and dimensions will depend on completed specification. Publication No. PN1738A/12/14 Produced in England ©2014 Perkins Engines Company Limited
4000 Series 4006-23TAG2A Diesel Engine – ElectropaK695 kWm @ 1500 rpm
Technical information
Air inletl Mounted air filter
Fuel systeml Direct fuel injection system, fuel lift pumpl Fuel cooler
Governingl Heinzmann digital governor – governing to ISO 8528-5 Class G2
Lubrication systeml Wet sump with filler and dipstickl Lubrication oil filtersl Oil cooler with separate filter header
Cooling systeml Twin thermostats, water pumpl System designed for ambients up to 35ºC or 50ºCl Radiator supplied loose incorporating air-to-air charge cooler
Electrical equipmentl 24 volt starter motor, 24 volt 70 amp battery charging alternator with integral voltage regulator and activating switchl High coolant temperature switchl Low oil pressure switch
Flywheel and housingl SAE J620 size 18 flywheel l SAE ‘0’ flywheel housing
Literaturel User’s Handbook and Parts Manual
Optional equipmentl Heavy-duty air cleaners – paper element with pre-cleanerl Changeover lubrication oil filterl Changeover fuel filterl Immersion heater with thermostatl Additional manualsl 4 metre wiring harnessl Tropical or temperate radiator kitl Temperate fan
-
3027 mm 1706 mm
1964 mm
2414 mm
www.perkins.com
Photographs are for illustrative purposes only and may not reflect final specification.All information in this document is substantially correct at time of printing and may be altered subsequently. Final weight and dimensions will depend on completed specification. Publication No. PN1738A/12/14 Produced in England ©2014 Perkins Engines Company Limited
4000 Series 4006-23TAG2A Diesel Engine – ElectropaK695 kWm @ 1500 rpm
Engine package weights and dimensions
Length 3027 mm 119 in
Width 1706 mm 67 in
Height 1964 mm 77 in
Weight (dry) 2524 kg 5564 lb
-
www.perkins.com
Photographs are for illustrative purposes only and may not reflect final specification.All information in this document is substantially correct at time of printing and may be altered subsequently. Final weight and dimensions will depend on completed specification. Publication No. PN1738A/12/14 Produced in England ©2014 Perkins Engines Company Limited
4000 Series 4006-23TAG2A Diesel Engine – ElectropaK695 kWm @ 1500 rpm
Percent of prime powerFuel consumption at 1500 rpm
g/kWhFuel consumption at 1500 rpm
l/hr
Standby power 210 173
Prime power 209 157
Baseload power 210 127
75% 211 121
50% 213 83
Speedrpm
Type of operationTypical generator
output (Net) Engine power
Gross Net
kVA kWe kWm hp kWm hp
1500
Continuous baseload 600 480 531 712 505 677
Prime power 750 600 658 882 632 847
Standby (maximum) 825 660 721 967 695 932
The above ratings represent the engine performance capabilities to conditions specified in ISO 8528/1, ISO 3046/1:1986, BS 5514/1. Derating may be required for conditions outside these; consult Perkins Engines Company Limited.
Generator powers are typical and are based on an average alternator efficiency and a power factor (cos. θ) of 0.8. Fuel specification: BS 2869: Part 2 1998 Class A2 or ASTM D975 D2. Lubricating oil: 15W40 to API CG4.
Rating definitions Baseload power: Power available for continuous full load operation. No overload is permitted on baseload power. Prime power: Power available at variable load with a load factor not exceeding 80% of the prime power rating. There is no overload permitted on baseload power. Standby power: Power available in the event of a main power network failure up to a maximum of 500 hours per year of which up to 300 hours may be run continuously. Load factor may be up to 100% of standby power. No overload is permitted.
-
HCI634G - Technical Data Sheet
-
HCI634GSPECIFICATIONS & OPTIONS
STANDARDS
Newage Stamford industrial generators meet therequirements of BS EN 60034 and the relevantsection of other international standards such asBS5000, VDE 0530, NEMA MG1-32, IEC34, CSAC22.2-100, AS1359.Other standards and certifications can be consideredon request.
VOLTAGE REGULATORS
MX321 AVR - STANDARD
This sophisticated Automatic Voltage Regulator(AVR) is incorporated into the Stamford PermanentMagnet Generator (PMG) system and is fitted asstandard to generators of this type.The PMG provides power via the AVR to the mainexciter, giving a source of constant excitation powerindependent of generator output. The main exciteroutput is then fed to the main rotor, through a fullwave bridge, protected by a surge suppressor. TheAVR has in-built protection against sustained over-excitation, caused by internal or external faults. Thisde-excites the machine after a minimum of 5seconds.Over voltage protection is built-in and short circuitcurrent level adjustments is an optional facility.
WINDINGS & ELECTRICAL PERFORMANCE
All generator stators are wound to 2/3 pitch. Thiseliminates triplen (3rd, 9th, 15th …) harmonics on thevoltage waveform and is found to be the optimumdesign for trouble-free supply of non-linear loads.The 2/3 pitch design avoids excessive neutralcurrents sometimes seen with higher windingpitches, when in parallel with the mains. A fullyconnected damper winding reduces oscillationsduring paralleling. This winding, with the 2/3 pitchand carefully selected pole and tooth designs,ensures very low waveform distortion.
TERMINALS & TERMINAL BOX
Standard generators feature a main stator with 6ends brought out to the terminals, which are mountedon the frame at the non-drive end of the generator.A sheet steel terminal box contains the AVR andprovides ample space for the customers' wiring andgland arrangements. It has removable panels foreasy access.
SHAFT & KEYS
All generator rotors are dynamically balanced tobetter than BS6861:Part 1 Grade 2.5 for minimumvibration in operation. Two bearing generators arebalanced with a half key.
INSULATION/IMPREGNATION
The insulation system is class 'H'.All wound components are impregnated withmaterials and processes designed specifically toprovide the high build required for static windingsand the high mechanical strength required forrotating components.
QUALITY ASSURANCE
Generators are manufactured using productionprocedures having a quality assurance level to BSEN ISO 9001.
The stated voltage regulation may not be maintainedin the presence of certain radio transmitted signals.Any change in performance will fall within the limits ofCriteria 'B' of EN 61000-6-2:2001. At no time will thesteady-state voltage regulation exceed 2%.
NB Continuous development of our products entitlesus to change specification details without notice,therefore they must not be regarded as binding.
Front cover drawing typical of product range.
2
-
CONTROL SYSTEM SEPARATELY EXCITED BY P.M.G.
A.V.R. MX321
VOLTAGE REGULATION ± 0.5 %
SUSTAINED SHORT CIRCUIT
INSULATION SYSTEM
PROTECTION
RATED POWER FACTOR
STATOR WINDING
WINDING PITCH
WINDING LEADS
STATOR WDG. RESISTANCE
ROTOR WDG. RESISTANCE
EXCITER STATOR RESISTANCE
EXCITER ROTOR RESISTANCE
R.F.I. SUPPRESSION BS EN 61000-6-2 & BS EN 61000-6-4,VDE 0875G, VDE 0875N. refer to factory for others
WAVEFORM DISTORTION NO LOAD < 1.5% NON-DISTORTING BALANCED LINEAR LOAD < 5.0%
MAXIMUM OVERSPEED 2250 Rev/Min
BEARING DRIVE END
BEARING NON-DRIVE END
1 BEARING 2 BEARING
WEIGHT COMP. GENERATOR
WEIGHT WOUND STATOR
WEIGHT WOUND ROTOR
WR² INERTIA
SHIPPING WEIGHTS in a crate
PACKING CRATE SIZE
TELEPHONE INTERFERENCE
COOLING AIR
VOLTAGE STAR 380/220 400/231 415/240 440/254 416/240 440/254 460/266 480/277
VOLTAGE DELTA 220 230 240 254 240 254 266 277
kVA BASE RATING FOR REACTANCE VALUES
800 800 800 800 875 925 963 1000
Xd DIR. AXIS SYNCHRONOUS 3.14 2.83 2.63 2.34 3.53 3.34 3.18 3.03
X'd DIR. AXIS TRANSIENT 0.25 0.23 0.21 0.19 0.28 0.26 0.25 0.24
X''d DIR. AXIS SUBTRANSIENT 0.18 0.16 0.15 0.13 0.21 0.20 0.19 0.18
Xq QUAD. AXIS REACTANCE 1.88 1.70 1.58 1.40 2.10 1.98 1.89 1.80
X''q QUAD. AXIS SUBTRANSIENT 0.21 0.19 0.18 0.16 0.24 0.23 0.22 0.21
XL LEAKAGE REACTANCE 0.10 0.09 0.08 0.07 0.12 0.11 0.10 0.10
X2 NEGATIVE SEQUENCE 0.22 0.20 0.19 0.17 0.24 0.23 0.22 0.21
X0 ZERO SEQUENCE 0.03 0.03 0.03 0.02 0.03 0.03 0.03 0.03
REACTANCES ARE SATURATED VALUES ARE PER UNIT AT RATING AND VOLTAGE INDICATED
T'd TRANSIENT TIME CONST.
T''d SUB-TRANSTIME CONST.
T'do O.C. FIELD TIME CONST.
Ta ARMATURE TIME CONST.SHORT CIRCUIT RATIO
814 kg
17.8009 kgm2
183 x 92 x 140(cm)
18.3482 kgm2
2029kg
766 kg
1/Xd
DOUBLE LAYER LAP
1.75 Ohms at 22°C
0.003 Ohms PER PHASE AT 22°C STAR CONNECTED
6
TWO THIRDS
934 kg
1965 kg
934 kg
BALL. 6224 (ISO)
REFER TO SHORT CIRCUIT DECREMENT CURVES (page 7)
WINDING 312
With 4% ENGINE GOVERNING
0.8
IP23
CLASS H
BALL. 6317 (ISO)
17 Ohms at 22°C
0.079 Ohms PER PHASE AT 22°C
HCI634G
1.614 m³/sec 3420 cfm 1.961 m³/sec 4156 cfm
50 Hz
THF
-
Winding 312HCI634G
THREE PHASE EFFICIENCY CURVES
50Hz
4
-
Winding 312HCI634G
THREE PHASE EFFICIENCY CURVES
60Hz
5
-
HCI634GWinding 312
Locked Rotor Motor Starting Curve
0
5
10
15
20
25
30
0 200 400 600 800 1000 1200 1400 1600 1800 2000 2200LOCKED ROTOR kVA
PE
R C
EN
T T
RA
NS
IEN
T V
OL
TA
GE
DIP
.
346V 380V 400V 415V 440V
0
5
10
15
20
25
30
0 200 400 600 800 1000 1200 1400 1600 1800 2000 2200 2400 2600LOCKED ROTOR kVA
PE
R C
EN
T T
RA
NS
IEN
T V
OL
TA
GE
DIP
.
380V 416V 440V 460V 480V
60Hz
50Hz
6
-
3-phase 2-phase L-L 1-phase L-NVoltage Factor Voltage Factor x 1.00 x 0.87 x 1.30
380v X 1.00 416v x 1.00 x 1.00 x 1.80 x 3.20400v X 1.07 440v x 1.06 x 1.00 x 1.50 x 2.50415v X 1.12 460v x 1.12 10 sec. 5 sec. 2 sec.440v X 1.18 480v x 1.17
HCI634G
50Hz 60Hz
The sustained current value is constant irrespectiveof voltage level
Three-phase Short Circuit Decrement Curve. No-load Excitation at Rated SpeedBased on star (wye) connection.
Max. sustained durationAll other times are unchanged
Instantaneous
SustainedMinimum
Sustained Short Circuit = 2,900 Amps
Sustained Short Circuit = 3,500 AmpsNote 1The following multiplication factors should beused to adjust the values from curve betweentime 0.001 seconds and the minimum currentpoint in respect of nominal operating voltage :
Note 2The following multiplication factor should be used to convert thevalues calculated in accordance with NOTE 1 to those applicableto the various types of short circuit :
Note 3Curves are drawn for Star (Wye) connected machines. For Deltaconnection multiply the Curve current value by 1.732
50Hz
60Hz
1000
10000
100000
0.001 0.01 0.1 1 10TIME (secs)
CU
RR
EN
T (A
mp
s)
SYMMETRICAL
ASYMMETRICAL
1000
10000
100000
0.001 0.01 0.1 1 10TIME (secs)
CU
RR
EN
T (A
mp
s)
SYMMETRICAL
ASYMMETRICAL
7
-
Class - Temp Rise
Star (V) 380 400 415 440 380 400 415 440 380 400 415 440 380 400 415 440
Delta (V) 220 230 240 254 220 230 240 254 220 230 240 254 220 230 240 254
kVA 750 760 750 750 800 810 800 800 820 830 820 820 850 860 850 850
kW 600 608 600 600 640 648 640 640 656 664 656 656 680 688 680 680
Efficiency (%) 94.5 94.6 94.8 95.0 94.2 94.4 94.6 94.8 94.1 94.3 94.5 94.7 93.9 94.2 94.4 94.6
kW Input 635 643 633 632 679 686 677 675 697 704 694 693 724 730 720 719
Star (V) 416 440 460 480 416 440 460 480 416 440 460 480 416 440 460 480
Delta (V) 240 254 266 277 240 254 266 277 240 254 266 277 240 254 266 277
kVA 813 844 888 913 875 925 963 1000 913 969 1008 1046 950 1000 1044 1088
kW 650 675 710 730 700 740 770 800 730 775 806 837 760 800 835 870
Efficiency (%) 94.6 94.7 94.8 94.8 94.4 94.5 94.5 94.6 94.2 94.3 94.4 94.4 94.1 94.2 94.3 94.3
kW Input 688 713 749 770 742 783 815 846 775 822 854 886 808 849 886 923
14 18 21 24
25.4 15.87 0 0
TD_HCI634G.GB_12.03_03_GB
SAE
AN
DIMENSIONS
HCI634G
Cont. F - 105/40°C Cont. H - 125/40°C Standby - 150/40°C Standby - 163/27°C
Winding 312 0.8 Power Factor
RATINGS
50Hz
60Hz
Barnack Road • Stamford • Lincolnshire • PE9 2NBTel: 00 44 (0)1780 484000 • Fax: 00 44 (0)1780 484100Website: www.newage-avkseg.com
© 2004 Newage International Limited.Reprinted with permission of N.I. only.Printed in England.
-
InteliLiteNT AMF 9SINGLE SET GEN-SET CONTROLLER
ComAp is a member of AMPS (The Association of Manufacturers of Power generating Systems).
ComAp products meet the highest standards, with every stage of production undertaken in accordance with the ISO certifi cation obtained in 1998.
DescriptionThe InteliLiteNT AMF 9 is integrated controller for gen-sets operating in single standby mode.
The controller meets all requirements for Auto Mains Failure (AMF) applications including remote communication and internet control, user confi guration and complete gen-set monitoring and protection.
InteliLiteNT AMF 9 is easy to use with a simple intuitive user interface and graphic display. Unit is designed for quick and cost saving commissioning and bring seamless integration with the latest breed of EFI diesel engines from all major manufacturers. This offers a higher level of functionality with users able to display a comprehensive range of values from the EFI engine on standard analog gauges and true RMS measurement of electric values.
Benefi ts Less wiring and components Less engineering and programming Cost saving commissioning Remote monitoring reduced call-out
costs of service engineers History 100+ records based
on running hours Hybrid binary inputs and outputs
module – simple way of extension the unit performance
SMS on alarm/event Direct communication
with EFI engines Perfect price / performance ratio
InteliLiteNT AMF 9 supports J1939 for all major brands:
• Caterpillar• Cummins• Detroit Diesel• Deutz
• GM• Isuzu• Iveco• John Deere
• MAN• MTU• Perkins• Scania
• Sisu• VM Motori• Volvo Penta and others
-
Customer satisfaction is our mission. We continuously develop the best people to succeed in our mission.
+24V
STOP
ALARM
GENERATOR
DIESEL/GAS ENGI
NE
1
2
ENGINEANALOG
INPUTS
POWER SUPPLY
8 to 36 VDC
+ -
4 BINARY INPUTS
4 BINARY OUTPUT
S
(OPEN COLLECTO
R)
BINARYOUTPUT
S
(OPEN
COLLECTOR)
D+
Oil Pressure
J1939Start/Stop - Speed
Request
Values + Fault Cod
es
Aux Alternator
Preexcitation
Fuel Solenoid
Starter
GENERATOR
CURRENTVO
LTAGE
MEASUREM
ENT
ECU
InteliLiteNT AMF 9
oror
or
IL-NT S-USB
IL-NT RS232-485
IL-NT RS232
S-USB
IL-NT GPRS
COMMUNICATION
PLUG-IN MODULE
or
CAN - J1939
I/O EXTENSION
Possible to contec
t:
PC, MODEM,
IL-NT RD (SW),
SCADA/PLC, INTE
RNET
LOAD
3ph
3phG
ENERATOR C.B. CO
NTROL
MAINS C.B. CO
NTROL
3ph
MAINS
MAINS
VOLTAG
EM
EASUREMENT
EXTENSION
PLUG-IN MODULE
IL-NT AOUT8
IL-NT BIO8
or
IL-NT BIO8
IL-NT AOUT8
3 phase AMF function• Over/Under frequency• Over/Under voltage
3 phase generator protections• Over/Under frequency• Over / Under voltage• Over current
True RMS Voltage measurement• 3 phase generator voltages:
• Phase to neutralL1 – N, L2 – N, L3 – N
• Phase to phaseL1 – L2, L2 – L3, L3 – L1
• 3 phase mains voltages• Voltage range 277 V p-n, 480 V p-p• Maximal measured voltage 300 V p-n
True RMS current measurements• 3 generator phase currents• Current range 5 A• Maximal measured current 10 A• Ready for generators with
3 ph 4 wires / 3 ph 3 wires / Split ph / Mono ph
Event and performance log• Gen-set text alarm log• Engine hours history log• ECU text alarm log • Test Run scheduler
Power measurements• Apparent power per phase• Total apparent power
User interface• Graphic 128 × 64 pixels display• 2 languages, user changeable from PC• Setpoints adjustable via
controller buttons or PC• Buttons with mechanical feedback
Inputs and outputs• 3 fully confi gurable analog inputs• 4 binary inputs; 6 binary outputs• D+ preexcitation terminal• Optional 8 hybrid binary inputs/outputs• Optional 8 analog gauge drive outputs,
compatible with VDO, Datcon gauges
EFI engine support• Cummins Modbus• Engine specifi c J1939 for all major
manufacturers (see table on page 1)• Diagnostic messages in plain text
Engine protections• Oil pressure protection• Coolant temperature• Fuel level
Active calls• 1 channel• SMS alarm• Event SMS
Miscellaneous features• Operation mode
– AMF/MRS application switch• Maintenance – service time counter• Engine hours counter
Communication interfaces• Optional RS232, RS485
(including Modem support) or USB plug-in interface
• Optional GSM modem via IL-NT GPRS
Mechanicaland operation parameters• Unit dimension 120 × 180 mm• Sealed front face rated for IP65• Hard plexiglass LCD cover• Operation temperature:
• -20 °C to +70 °C standard version• -40 °C to +70 °C low temperature ver.
• Power supply voltage 8–36 V• Voltage drops shorter than
50 ms do not affect operation
2012-05/CPLEILA9
ComAp, spol. s r. o.
Czech RepublicPhone: + 420 246 012 111 Fax: + 420 266 316 647E-mail: [email protected]: www.comap.cz
MANUFACTURER: LOCAL DISTRIBUTOR / PARTNER:
© ComAp. Features and specifi cation are subject to change without prior notice.
Accessoriesand PC tools
IL-NT AOUT8 – Analog Outputs for PWM Gauges Module
IL-NT BIO8 – Binary Input/Output (PWM) Module
IL-NT RD (SW) – Remote Display Software for InteliLiteNT Controllers
IG-IB – InternetBridge support IL-NT GPRS – GSM Modem/
Wireless Internet Module IL-NT RS232 – RS232 Extension Board IL-NT RS232-485 – Dual
Port Extension Board IL-NT S-USB – Service USB Module InteliMonitor – PC Monitoring Tool WinScope – Special Graphical
Controllers’ Monitoring Software LiteEdit – PC Confi guration
and Monitoring Tool
Features
Schematic diagram
ANSI code Protection
59 Overvoltage
27 Undervoltage
81H Overfrequency
81L Underfrequency
50 + 51 Overcurrent*
47 Phase rotation**
71 Gas (Fuel) level
* Shortcurrent only / ** Fixed setting