A
1
1A101
REFERENCE SYMBOLS
IDENTITY SYMBOLS
LINE SYMBOLS
CENTER LINE
DEMOLISHED
HIDDEN
OVERHEAD
PROPERTY LINE
1 HOUR RATING
EXIT SEPARATION
MATCH LINE
COLUMN GRID
BLOWUP DETAIL
ABBREVIATIONS
DRAWING CONVENTIONS
View Name1/8" = 1'-0"
1 VIEW INDICATOR
LEVEL NAMEELEVATION
1
ELEVATION INDICATOR
REVISION CLOUD
1A101
1
A101
A101
1
2
3
4
2' -
0"
2' -
0"
WALL SECTION
ELEVATION
INTERIOR ELEVATION
DIMENSION CONVENTIONS
@ ATAFF ABOVE FINISH FLOORAPC ACOUSTICAL PANEL CEILINGARCH ARCHITECTURALBLDG BUILDINGCL CENTERLINECO CASED OPENINGCJ CONTROL JOINTCPT CARPETCTR CENTERCONC CONCRETECMU CONCRETE MASONRY UNITDN DOWNDS DOWNSPOUTDWG DRAWINGEIFS EXTERIOR INSULATION AND FINISH
SYSTEMEJ EXPANSION JOINTEL ELEVATIONELEC ELECTRICALELEV ELEVATOREQUIP EQUIPMENTES EDGE STRIPEWC ELECTRIC WATER COOLEREXP EXPOSEDEXT EXTERIOREXPT EXTERIOR PAINTEXTG EXISTINGFD FLOOR DRAINFE FIRE EXTINGUISHERFEC FIRE EXTINGUISHER CABINETGC GENERAL CONTRACTORGL EXTERIOR GLAZINGGR GROUTGT GLASS TILEGWB GYPSUM BOARDHM HOLLOW METALHVAC HEATING, VENTILATION, AIR-
CONDITIONING INSUL INSULATIONLVT LUXURY VINYL TILEMAX MAXIMUM
MECH MECHANICALMFR MANUFACTURERMIN MINIMUMMP METAL PANELMTL METAL COPINGNIC NOT IN CONTRACTNOM NOMINALNTS NOT TO SCALEOC ON CENTEROPP OPPOSITEOPNG OPENINGP PAINTPEMB PRE ENGINEERED METAL BUILDINGPL PLASTIC LAMINATEPT PORCELAIN TILEPTB PORCELAIN TILE BASEPTW PRESSURE TREATED WOODPWDR POWDER ROOMRB RUBBER BASEREQD REQUIREDRD ROOF DRAINRMA RESILIENT MOLDING ACCESSORIESSC SEALED CONCRETESF SQUARE FEETSIM SIMILARSPEC SPECIFICATIONSSS SOLID SURFACESST STUCCOSTD STANDARDSTW STAIN WOODSTR STRUCTURALTOS TOP OF STEELTYP TYPICALUNO UNLESS NOTED OTHERWISEVIF VERIFY IN FIELDVWC VINYL WALLCOVERINGW/ WITHWWF WELDED WIRE FABRICXTR EXISTING TO REMAIN
NOTE: 3-D VIEW SHOWN FOR REPRESENTATION ONLY. REFER TO DRAWINGS AND DETAILS FOR ALL MATERIALS, DIMENSIONS, AND CONSTRUCTION DETAILS.
30"W X 52"D
KNEE CLEARANCE
27"
MIN
11" MIN
8" MIN
9" M
IN
6" MAX
TOE CLEARANCE 9"30
" M
IN
17" - 25"
30"
MIN
25" MAX
>27
"
80"
4" MAX
>
60"D X DOOR + 18"W
52"D X DOOR W
52"D XDOOR + 12"W (W/ LATCH & CLOSER)
54"D X DOOR + 42"W
54"D X DOOR + 42"W
42"D X DOOR + 22"W
48"D X DOOR + 24"W
54"D X DOOR + 24"W (W/ CLOSER)
TURNING SPACE
KNEE AND TOE CLEARANCE PROTRUDING OBJECTS
DOOR CLEARANCECLEAR FLOOR SPACE
67" MIN
64" MIN
11" MIN
42" MIN
11" MIN
38"
MIN
60"
MIN
52"
MIN
30" MIN
REQUIRED AT ALL ACCESSIBLE LAVATORIES AND COUNTERS
SECTION VIEW SECTION VIEW
PLAN VIEW PLAN VIEW
KNEE CLEARANCE
TOE CLEARANCE
REQUIRED WITHIN ALL ACCESSIBLE RESTROOMS REQUIRED AT ALL ACCESSIBLE LAVATORIES, TOILET COMPARTMENTS AND URINAL COMPARTMENTS
SECTION VIEW
REQUIRED FOR ALL WALL-MOUNTED OBJECTS LOCATED ALONG CIRCULATION PATHS
PROTRUSION LIMITS FOR LEADING EDGE OF OBJECT
REQUIRED AT ALL ACCESSIBLE DOORS. ARROW INDICATES APPROACH.
60"
18"
12" (W/ LATCH & CLOSER)
52"
54"
42"
60"
36"
42"
48"
54"
(W/ C
LOSE
R)
24"
22"
48"D X DOOR + 22"W (W/CLOSER)
48"
(W/ C
LOSE
R)
22"
MIN
11"
48"D X DOOR W
48"D XDOOR + 12"W (W/ LATCH & CLOSER)
12" (W/ LATCH & CLOSER)
48"
42"D X DOOR + 24"W
48"D X DOOR + 24"W (W/ CLOSER)
42"
48"
(W/ C
LOSE
R)
24"NEW BUILDING
EXISTING BUILDING
NEW BUILDING
EXISTING BUILDING
ANSI 2017
COLLEGE ST.
ASS
EMB
LY S
T.
TOILETS
DUMPSTERS
PROJECT ACCESS
DUST CONTROL
ENSURE PRESENCE OF FIRE EXTINGUISHERS
PROJECT LOCATION
UNIVERSITY OF SOUTH CAROLINAPHRC- RENOVATION PROJECT 2ND FLOOR SUITE
921 ASSEMBLY STREET, COLUMBIA SC 29208DRAWING LIST
SHEET NO. Sheet NameGENERALCVR COVERG101 BUILDING CODE SUMMARYARCHITECTURALA101 FLOOR PLANSA201 REFLECTED CEILING PLANA801 DOOR/FINISH SCHEDULESMECHANICALM101 SECOND FLOOR PLANSELECTRICALE001 ELECTRICAL NOTES & LEGENDSE101 ELECTRICAL DEMOLITION PLANSE102 ELECTRICAL RENOVATION PLANS
DATE
221 PICKENS STREET (29205)POST OFFICE BOX 5875
COLUMBIA, SOUTH CAROLINA29250
803.834.4048 p803.834.4082 f
WWW.1X1DESIGN.COM
SHEET NUMBER
PROJECT NUMBER
REVISIONS
SHEET NAME
CLIE
NT
NA
ME
PRO
JECT
NA
ME
PRO
JECT
AD
DRE
SS
This
dra
win
g an
d th
e in
form
atio
n sh
own
ther
eon
are
prop
erty
of
1x1
Des
ign,
Inc.
Thi
s dr
awin
g m
ay n
ot b
e pu
blis
hed,
rep
rodu
ced,
cop
ied,
mod
ifie
d, u
ploa
ded,
tra
nsm
itte
d, p
oste
d, t
rans
ferr
ed o
r ot
herw
ise
used
wit
hout
the
pri
or w
ritt
en c
onse
nt o
f 1x
1 D
esig
n,In
c. L
egal
act
ion
will
be
purs
ued
agai
nst
all v
iola
tion
s an
d in
frin
gem
ents
to
the
full
exte
nt p
ossi
ble.
12/1
8/20
18 1
:05:
07 P
M
CVRCOVER
U-17-039-1
12.20.18
PHRC
- REN
OV
ATI
ON
PRO
JECT
2N
D F
LOO
R SU
ITE
Uni
vers
ity
Proj
ect
No:
FP0
0000
192
UN
IVER
SITY
OF
SOU
TH C
ARO
LIN
A
921
ASS
EMBL
Y S
TREE
T, C
OLU
MBI
A, S
C 29
208
RELE
ASE
D F
OR
BID
DIN
G -
DEC
EMBE
R 20
, 201
8
UNIVERSITY PROJECT NUMBER: FP00000192
STATE MAP CITY MAP 1/32" = 1'-0"1 SECOND FLOOR- CONSTRUCTION PLAN
No. Description Date
BUILDING CODE SUMMARY
ACTUAL AREA OF OCCUPANCY A
ALLOWABLE AREA OF OCCUPANCY A
ACTUAL AREA OF OCCUPANCY B
ALLOWABLE AREA OF OCCUPANCY B+ < 1
PROJECT DESCRIPTIONTHIS PROJECT CONSISTS OF AN INTERIOR RENOVATION TO A SECOND FLOOR OFFICE SUITE IN AN EXISTING BUILDING. MODIFICATIONS TO THE LAYOUT, MECHANICAL AND ELECTRICAL SYSTEMS ARE ANTICIPATED. MINOR MODIFICATIONS TO THE FSS SYSTEM ARE ANTICIPATED.
PROJECT INFORMATIONNAME OF PROJECT: UNIVERISTY OF SOUTH CAROLINA PHRC- RENOVATION PROJECT 2ND FLOOR SUITE
ADDRESS: 921 ASSEMBLY ST, COLUMBIA, SC, 29208
EXISTING OR PREVIOUS USE: OFFICE
PROPOSED USE: OFFICE
OWNER OR AUTH.. AGENT: UNIVERSITY OF SOUTH CAROLINA
CONTACT INFO: HATICE HIKMET, [email protected]
OWNED BY: STATE
CODE ENFORCEMENT JURISDICTION:
STATE
PROJECT DESIGN TEAM INFORMATIONLEAD DESIGN PROFESSIONAL:
DESIGNER FIRM CONTACT LICENSE # PHONE #
1X1 DESIGN, INC.
ARCHITECTURAL: 1X1 DESIGN, INC. ASHELEY SCOTT ST. JOHN 7937 (803) 834-4048
CIVIL: -- -- -- --
STRUCTURAL: -- -- -- --
MECHANICAL: SWYGERT & ASSOCIATES BILL LIVINGSTON 17994 (803) 791-9300
PLUMBING: -- -- -- --
FIRE-PROTECTION/STANDPIPE: -- -- -- --
ELECTRICAL: BELKA ENGINEERING JASON AREHEART 26181 (803) 731-2880
FIRE ALARM: -- -- -- --
OTHER: -- -- -- --
GENERAL CONTRACTOR: -- -- -- --
CODE COMPLIANCEINTERNATIONAL BUILDING CODE: 2015 EDITION
INTERNATIONAL MECHANICAL CODE: 2015 EDITION
INTERNATIONAL PLUMBING CODE: 2015 EDITION
NATIONAL ELECTRICAL CODE: 2014 EDITION
ICC/ANSI - 117.1: 2009 EDITION
AMERICAN WITH DISABILITIES ACT (ADA)
BASIC BUILDING DATACONSTRUCTION TYPE: EXISTING
SPRINKLERS: YES
STANDPIPES: EXISTING FSS SYSTEM
FIRE DISTRICT: NO
FLOOD HAZARD AREA: NO
BUILDING HEIGHT: EXISTING
GROSS BUILDING AREA:EXISTING (SQ FT) NEW (SQ FT) SUB-TOTAL (SQ FT)FLOOR
EXISTING, UNCHANGED 0 EXISTING, UNCHANGEDBUILDING
-- -- EXISTING, UNCHANGEDTOTAL
ALLOWABLE AREAPRIMARY OCCUPANCY: BUSINESS (B)
SECONDARY OCCUPANCY: NONE
INCIDENTAL USE (TABLE 509): NONE
SPECIAL USE (CHAPTER 4): NONE
SPECIAL PROVISIONS: NONE
MIXED OCCUPANCY: NO SEPARATION: EXCEPTION: --NA
INCIDENTAL USE SEPARATION (509):NA
THIS AREA IS NOT EXEMPT AS A NON-SEPARATED USE (SEE EXCEPTIONS)
NON-SEPARATED MIXED OCCUPANCY (508.3) The required type of construction for the building shall be determined by applying the height and area limitations for each of the applicable occupancies for the entire building. The most restrictivetype of construction, so determined shall apply to the entire building.
SEPARATED MIXED OCCUPANCY (508.4) See chart below for area calculation for each story, the area of the occupancy shall be such that the sum of the ratios for the actual floor area of each use divided by the allowable floor area for each use shall not exceed 1.
ALLOWABLE HEIGHT
TYPE OF CONSTRUCTION
ALLOWABLE (TABLE 504.3, 504.4, 506.2)
BUILDING HEIGHT (FT)
BUILDING HEIGHT (STORIES)
SHOWN ON PLANS CODE REFERENCE
EXISTING EXISTING --
--
--
EXISTING
EXISTING
N/A
5
DESIGN OCCUPANT LOAD (TABLE 1004.1.2) - 2ND FLOOR (AFFECTED)
FUNCTION OF SPACE FLOOR AREA IN SQ FT PER OCCUPANT AREA PER PLANS TOTAL OCCUPANTS PER FUNCTION
100 GROSS
2ND FLOOR (AFFECTED) TOTAL 7,639.74 SF 45.6 OCC = 46 OCC
FIRE PROTECTION REQUIREMENTS
BUILDING ELEMENT FIRE SEPARATION DISTANCE (FEET)
STRUCTURAL FRAMES, INCLUDING COLUMNS, GIRDERS, TRUSSES
--
RATING
REQ'D PROVIDED WITH --* REDUCTION
DETAIL # AND SHEET #
DESIGN # FOR RATED ASSEMBLY
DESIGN # FOR RATED PENETRATION
DESIGN # FOR RATED JOINTS
BEARING WALLS:
EXTERIOR
NORTH
EAST
WEST
SOUTH
INTERIOR
NONBEARING WALLS AND PARTITIONS
EXTERIOR WALLS
NORTH
EAST
WEST
SOUTH
INTERIOR WALLS & PARTITIONS
FLOOR CONSTRUCTION INCLUDING SUPPORTING BEAMS AND JOISTS
ROOF CONSTRUCTION INCLUDING SUPPORTING BEAMS AND JOISTS
SHAFT ENCLOSURES-EXIT
SHAFT ENCLOSURES-OTHER
CORRIDOR SEPARATION
OCCUPANCY SEPARATION
PARTY/FIRE WALL SEPARATION
SMOKE BARRIER SEPARATION
TENANT SEPARATION
INCIDENTAL USE SEPARATION
FIRE PROTECTION REQUIREMENTSEMERGENCY LIGHTING: XTR
EXIT SIGNS: XTR
FIRE ALARM: XTR
SMOKE DETECTION SYSTEMS: XTR
PANIC HARDWARE XTR
LIFE SAFETY PLAN REQUIREMENTSLIFE SAFETY PLAN SHEET #: G101
LIFE SAFETY PLAN INFORMATION:
N/A FOR PROJECTINCLUDED
PLUMBING FIXTURE REQUIREMENTS (TABLE 2902.1)
REQUIRED:
WATER CLOSETS
--
NOTE: FIXTURE COUNTS BASED UPON DESIGN OCCUPANT LOAD
EXIT REQUIREMENTS - 2ND FLOOR (AFFECTED)
MINIMUM NUMBER OF EXITS
2ND FLOOR (AFFECTED)
TRAVEL DISTANCE ARRANGEMENTS MEANS OF EGRESS (SECTION 1007.1.1)
NUMBER AND ARRANGEMENT OF EXITS
FLOOR, ROOM OR SPACE
REQ'D SHOWN ON PLANS
ALLOWABLE TRAVEL DISTANCE (TABLE 1017.1)
ACTUAL TRAVEL DISTANCE SHOWN ON PLANS
REQUIRED DISTANCE BETWEEN EXIT DOORS
ACTUAL DISTANCE SHOWN ON PLANS
2 3 300'-0" 82'-3" 44'-4" 116'-0"
1 Corridor dead ends (section 1020.4)2 Single exits (from spaces - table 1006.2.1; from story - tables 1006.3.1 and 1006.3.2(2))3 Common path of travel (table 1006.2.1)
21,3
EGRESS WIDTH PER OCCUPANT (SECTION 1005)
2ND FLOOR (AFFECTED)
REQUIRED WIDTH ACTUAL EXIT WIDTH SHOWN ON PLANS
EXIT WIDTH - 2ND FLOOR (AFFECTED)
USE GROUP OR SPACE DESIGNATION
STAIRS OTHER ELEMENTS STAIRS OTHER ELEMENTS
46 0.2"/0.15" NA 6.9" 34" 72"
OCCUPANT LOAD BASED ON 1004.1.2
URINALS LAVATORIES SHOWERS/TUBS
DRINKING FOUNTAINS
MALE: FEMALE: MALE: FEMALE: REGULAR: ANSI/ADA:
PROVIDED:
-- -- -- -- -- -- -- --
---- -- -- -- -- -- -- --
---- -- -- -- -- -- -- --
---- -- -- -- -- -- -- --
IECC: 2009 EDITION CLIMATE ZONE: 3
ACCESSORY OCCUPANCY: NONE
-- -- -- -- -- --
-- -- -- -- -- -- --
-- -- -- -- -- -- --
-- -- -- -- -- -- --
-- -- -- -- -- -- --
-- -- -- -- -- -- --
-- -- -- -- -- -- --
-- -- -- -- -- -- --
-- -- -- -- -- -- --
-- -- -- -- -- -- --
-- -- -- -- -- -- --
-- -- -- -- -- -- --
-- -- -- -- -- -- --
-- -- -- -- -- -- --
-- -- -- -- -- -- --
-- -- -- -- -- -- --
-- -- -- -- -- -- --
-- -- -- -- -- -- --
-- -- -- -- -- -- --
-- -- -- -- -- -- --
-- -- -- -- -- -- --
-- -- -- -- -- -- --
-- -- -- -- -- -- --
-- -- -- -- -- -- --
-- -- -- -- -- -- --
BUILDING DESCRIPTION& USE
(f)ACTUAL BUILDING AREA
(a)(A ) TABLE 506.2 AREASM
(c)(I ) SECTION 506.3 FACTOR INCREASE FOR OPEN SPACE
(d)(S ) BUILDING STORIES
(e)(A ) MAXIMUM BUILDING AREA OR UNLIMITED
--BUILDING, B (BUSINESS), MULTIFLOOR, SPRINKLERED
-- 4
t f a
--
I = [F / P - 0.25]W/30f
F =
P =
W =
XX'-X"
XX'-X"
XX'-X"
I = [XX - 0.25]XX/30f
A = [XX + (XX x XX)] x XX
A = [A + (NS x I )] x Sa t f a
a
A = [XXX] x XXa
A = XXXa
(b)(NS) TABLE 506.2 NON-SPRINKLERED BUILDING AREA
-- N/A
I = XXf
a
Building perimeter fronting public way or open space having 20ft min width:
Total building perimeter:
Minimum width of public way:
FIRE AND/OR SMOKE RATED WALL LOCATIONS (CHAPTER 7)
ASSUMED AND REAL PROPERTY LINES LOCATIONS
EXTERIOR WALL OPENING AREA WITH RESPECT TO DISTANCE TO ASSUMED PROPERTY LINES (705.8)
EXISTING STRUCTURES WITHIN 30' OF PROPOSED BUILDING
OCCUPANCY TYPES FOR AREA AS IT RELATES TO OCCUPANT LOAD CALCULATIONS (TABLE 1004.1.2)
OCCUPANT LOADS FOR EACH AREA
EXIT ACCESS TRAVEL DISTANCES (1017)
COMMON PATH OF TRAVEL DISTANCES (1006.2.1 & 1029.8)
DEAD END LENGTHS (1020.4)
CLEAR EXIT WIDTH FOR EACH EXIT DOOR
MAXIMUM OCCUPANT LOAD CAPACITY EACH EXIT DOOR CAN ACCOMMODATE BASED ON EGRESS WIDTH (1005.1)
ACTUAL OCCUPANT LOAD FOR EACH EXIT DOOR
SEPARATE SCHEMATIC PLAN INDICATING WHERE FIRE RATED FLOOR/CEILING AND/OR ROOF STRUCTURE IS PROVIDED FOR PURPOSES OF OCCUPANCY SEPARATION
LOCATION OF DOORS WITH PANIC HARDWARE (1010.1.10)
LOCATION OF DOORS WITH DELAYED EGRESS LOCKS AND AMOUNT OF DELAY (1010.1.10)
LOCATION OF DOORS WITH ELECTROMAGNETIC EGRESS LOCKS (1010.1.9.7)
LOCATION OF DOORS EQUIPPED WITH HOLD-OPEN DEVICES
LOCATION OF EMERGENCY ESCAPE WINDOWS (1030)
THE SQUARE FOOTAGE OF EACH FIRE AREA (901.7, 903)
THE SQUARE FOOTAGE OF EACH SMOKE COMPARTMENT (407.5)
NOTE ANY CODE EXCEPTIONS OR TABLE NOTES THAT MAY HAVE BEEN UTILIZED REGARDING THE ITEMS ABOVE:
---
NOTE: PER 2015 INTERNATIONAL FIRE CODE SECTION 509.1, DOORS TO ROOMS CONTAINING FIRE PROTECTION EQUIPMENT, CONTROLS FOR AIR CONDITIONING SYSTEMS, SPRINKLER RISERS, AND VALVES, OR OTHER FIRE DETECTION, SUPPRESSION, OR CONTROL ELEMENTS, SHALL BE IDENTIFIED FOR THE USE OF THE FIRE DEPARTMENT WITH DURABLE MATERIALS, PERMANENTLY INSTALLED, AND READILY VISIBLE. INSTALL "SPRINKLER RISER ROOM" AND "FIRE ALARM CONTROL PANEL" SIGNS.
*NOTE: EXISTING BULDING PLUMBING FIXTURES XTR
BUSINESS AREAS
ACCESSORY STORAGE AREAS, MECHANICAL EQUIPMENT ROOMS
NON-OCCUPIED
300 GROSS
--
4509.25 SF
169.84 SF
2960.65 SF
45
0.6
1 PARTITIONSCALE: 1 1/2" = 1'-0"
STUD RUNNER
3-5/8" METALSTUDS @ 16" O.C.
STUD RUNNER ATTACHED TO CONCRETE SLAB
CONCRETE SLAB
STRUCTURE ABOVE
5/8" GYPSUM BOARD
ACOUSTICAL BATT INSULATION
BASE - SEE FINISH SCHEDULE
FINISH FLOOR MATERIAL -SEE FINISH SCHEDULE
SEE A201
FOR CEILING HEIGHT
4 7/8"
3/4"
NOTE:
BASIS OF DESIGN:ACOUSTICAL BATT INSULATION FOR INTERIOR PARTITION WALLS SHALL BE:
1) CertainTeed Corporation2) Knauf Insulation3) Owens Corning
OR APPROVED EQUAL
CEILING AS SHOWN ONREFLECTED CEILING PLANSWHERE OCCURS
EXT'G STAIR
OFFICE
OFFICE
OFFICE
TELE/COMM
OFFICE
OFFICE
OFFICE
OFFICE
OFFICE
OFFICE
STORAGE
OFFICE
OFFICE
OFFICE
OFFICE
OFFICE
RECEPTION
BREAKROOM
OFFICE
OFFICE
OFFICE
OFFICE
OFFICE
OFFICE
OFFICE
OFFICE
OFFICEOFFICE
OFFICE
OFFICE
OFFICE
OFFICE
OFFICE
OFFICE
STORAGEWORK/FILE
AREA
VESTIBULE
DENOTES EXIT DOOR WITH EXISTING PANIC HARDWARE
DENOTES EXIT DOOR WITH EXISTING HOLD OPEN DEVICE
P
HO
MAX EXIT TRAVEL: 82'-3"
REQD EXIT DOOR: 32"MAX OCC LOAD: 213ACTUAL OCC LOAD: 26
LIFE SAFETY PLAN KEY
EXISTING FIRE EXTINGUISHER CABINETFEC-X
P
P
PHO
FEC-X
FEC-X
NOT IN SCOPE OF WORK
REQD EXIT DOOR: 68"MAX OCC LOAD: 453ACTUAL OCC LOAD: 26
EXIT DOOR: 32"MAX OCC LOAD: 213ACTUAL OCC LOAD: 26
BUSINESS AREAS
ACCESSORY STORAGE AREAS, MECHANICAL EQUIPMENT ROOMS
NON- OCCUPIED AREAS
OCCUPANT LOAD KEY
ACTUAL EXIT SEPARATION: 116'-0"
REQD EXIT SEPARATION: 132' - 10"/3 = 44' - 4"
DATE
221 PICKENS STREET (29205)POST OFFICE BOX 5875
COLUMBIA, SOUTH CAROLINA29250
803.834.4048 p803.834.4082 f
WWW.1X1DESIGN.COM
SHEET NUMBER
PROJECT NUMBER
REVISIONS
SHEET NAME
CLIE
NT
NA
ME
PRO
JECT
NA
ME
PRO
JECT
AD
DRE
SS
This
dra
win
g an
d th
e in
form
atio
n sh
own
ther
eon
are
prop
erty
of
1x1
Des
ign,
Inc.
Thi
s dr
awin
g m
ay n
ot b
e pu
blis
hed,
rep
rodu
ced,
cop
ied,
mod
ifie
d, u
ploa
ded,
tra
nsm
itte
d, p
oste
d, t
rans
ferr
ed o
r ot
herw
ise
used
wit
hout
the
pri
or w
ritt
en c
onse
nt o
f 1x
1 D
esig
n,In
c. L
egal
act
ion
will
be
purs
ued
agai
nst
all v
iola
tion
s an
d in
frin
gem
ents
to
the
full
exte
nt p
ossi
ble.
12/1
8/20
18 1
:05:
08 P
M
G101BUILDING CODE SUMMARY
U-17-039-1
12.20.18
UN
IVER
SITY
OF
SOU
TH C
ARO
LIN
A
921
ASS
EMBL
Y S
TREE
T, C
OLU
MBI
A, S
C 29
208
RELE
ASE
D F
OR
BID
DIN
G -
DEC
EMBE
R 20
, 201
8
NOT REQUIRED BY PROJECT SCOPE
NOT REQUIRED BY PROJECT SC
OPE
NOT APPLICABLE
NOT REQUIRED BY PROJECT SCOPE
1/16" = 1'-0"3 SECOND FLOOR- LIFE SAFETY
No. Description Date
PHRC
- REN
OV
ATI
ON
PRO
JECT
2N
D F
LOO
R SU
ITE
Uni
vers
ity
Proj
ect
No:
FP0
0000
192
GENERAL FLOOR PLAN NOTES1. EXISTING CONDITIONS BASED ON INFORMATION PROVIDED BY EXISTING PLANS,
OWNER, AND INFORMATION GATHERED DURING GENERAL FIELD OBSERVATION. IFGC DISCOVERS EXISTING CONDITIONS DIFFER FROM THOSE SHOWN, CONTACTOWNER OR ARCHITECT IMMEDIATELY.
2. ALL DIMENSIONS ARE TO FACE OF EXISTING ELEMENT OR FACE OF NEW STUDUNLESS NOTED OTHERWISE. ANY DISCREPANCIES SHALL BE BROUGHT TO THEARCHITECT'S ATTENTION IMMEDIATELY.
3. SEE A800S FOR FINISH SELECTION AND DETAILS.4. GENERAL CONTRACTOR TO COORDINATE ALL A/V REQUIREMENTS WITH TENANT.5. SEE G101 FOR PARTITION TYPES AND NOTES.
NEW WALL, SEE PARTITION TYPES
NEW DOOR, SEE DOOR SCHEDULE
ROOM TAG, SEE PLAN AND FINISH SCHEDULE
FLOOR PLAN LEGEND
Room name
101
101
1i
DOOR TAG, SEE PLAN AND DOOR SCHEDULE
INTERIOR WALL TAG, SEE PARTITION TYPES
FIRE EXTINGUISHER CABINETSFIRE EXTINGUISHER CABINET (FEC-X): EXISTING TO REMAIN
RENOVATION KEY NOTE LEGENDALIGN FINISHED FACE OF WALLS
INFILL WALL TO MATCH EXISTING
R1
R2
ALIGN WALL TO CENTER OF EXISTING ELEMENTR3
NEW PARTITION TO FOLLOW JOG IN EXISTING CEILING.R4
EXT'G STAIR
OFFICE
214
OFFICE
215
OFFICE
216A
TELE/COMM
217
OFFICE
218
OFFICE
219
OFFICE
220
OFFICE
221
OFFICE
222
OFFICE
223
STORAGE
240
OFFICE
239
OFFICE
238
OFFICE
237
OFFICE
236
OFFICE
235
RECEPTION
212
BREAKROOM
234
OFFICE
233
OFFICE
232
OFFICE
231
OFFICE
230
OFFICE
229
OFFICE
228
OFFICE
227
OFFICE
226
OFFICE
225
OFFICE
224
OFFICE
216F
OFFICE
216E
OFFICE
216D
OFFICE
216C
OFFICE
216B
OFFICE
241
R1
R1
R1
R2
216A.1
216B.1
216C.1
216D.1
216E.1
223.1 241.1
216F.1
STORAGE
213
1
1
1
1
1
1
11
1 1
1
1
11' -
8 1
/4"
3' -
1 7/
8"
2' -
8"
WORK/FILEAREA
212A
VESTIBULE
V203
CORRIDOR
H207
CORRIDOR
H209
CLEAR
6' - 6"
NO WORKANTICIPATED
13' - 11 5/8"
FEC-X
FEC-X
EQ EQ INFILL WITH LIKE CONSTRUCTION
INFILL WITH LIKE CONSTRUCTION
R1
R2
R3
R3
R3
R1
R1
7' - 10"
GENERAL DEMOLITION NOTES1. EXISTING CONDITIONS BASED ON INFORMATION PROVIDED BY EXISTING PLANS AND
INFORMATION GATHERED DURING GENERAL FIELD OBSERVATION. IF GC DISCOVERS EXISTINGCONDITIONS DIFFER FROM THOSE SHOWN, CONTACT OWNER OR ARCHITECT IMMEDIATELY.
2. GENERAL CONTRACTOR TO PROTECT ALL ADJACENT SURFACES TO REMAIN FROM DAMAGEDURING CONSTRUCTION. GENERAL CONTRACTOR TO REPAIR/REPLACE ANY ADJACENTSURFACES DAMAGED DURING CONSTRUCTION TO MATCH ORIGINAL CONDITIONS.
3. GENERAL CONTRACTOR TO FIELD VERIFY CONDITIONS PRIOR TO START OF CONSTRUCTION.4. ALL EXISTING EXTERIOR ALUMINUM STOREFRONT TO REMAIN.5. SECURE ALL INTERIOR BLINDS DURING CONSTRUCTION FOR REUSE. INVENTORY ANY DAMAGED
ROLLERSHADES, AND REPORT TO ARCHITECT.
DEMOLITION KEY NOTE LEGENDREMOVE EXISTING DOOR, STORE FOR OWNER REUSE IN FUTURE PROJECT. OWNER TO PACKAGE AND RELOCATE FROM PROJECT SITE.
REMOVE WALL ENTIRELY. CEILING TO REMAIN.
D1
D2
REMOVE EXISTING ROLLERSHADE AND SALVAGE FOR OWNER'S REUSE IN FUTURE PROJECT. OWNER TO PACKAGE AND RELOCATE FROM PROJECT SITE.
D3 REMOVE EXISTING FLOORING AND RUBBER BASE.
D4
REMOVE EXISTING LIGHTING THIS AREA, SEE ELECTRICAL FOR EXACT LOCATIONS.D5
GC TO PROTECT EXISTING ROLLER SHADES, OPTION TO REMOVE, PROTECT AND REINSTALL AT COMPLETION OF PROJECT.
D6
REMOVE EXISTING FLOORING AND RUBBER BASE. SCORE RUBBER BASE SO IT'S REMOVAL FROM THE EXISTING WALL CREATES MINIMAL DAMAGE/REQUIRED TOUCH-UP. EXISTING FURNITURE TO REMAIN.
D7
DEMOLITION LEGENDNOTE: SEE DEMOLITION TAGS AND NOTES FOR MORE DETAILS.
EXISTING WALL TO REMAIN
EXISTING WALL TO BE REMOVED
EXISTING DOOR TO BE REMOVED
EXISTING STOREFRONT, TO BE REMOVED
EXISTING ELEMENT TO BE REMOVED
D2
D1
D1
D2
D2 D2
D1
EXTG STAIR VESTIBULE
OFFICE243
OFFICE242
OFFICE239
OFFICE238
OFFICE235
OFFICE234
OFFICE232
OFFICE231
OFFICE230
OFFICE229
BREAK ROOM245
RECEPTIONH206
OFFICE216
OFFICE217
STORAGE215
OPEN OFFICE220
OPEN OFFICE224
OFFICE244
OFFICE241
OFFICE219
OFFICE221
OFFICE240
OFFICE237
OFFICE222
OFFICE223
OFFICE236
OFFICE225
CONFERENCE227
STORAGE228
STORAGE226
TELE/COMM244
CORRIDORH209
CORRIDORH207
D3
D3
D3
D3D3
D3
D3
D4
D4
D5
D5
D3 D7 D7
D7
D7
D7
D7
D7
D7
D7
D7D7
D7D7
D7 D7
D7D7
D7 D7
D7
D3
D7
D7
D7
D3
D3
D3
D3
FEC-X
FEC-X
STORAGE
240
DATE
221 PICKENS STREET (29205)POST OFFICE BOX 5875
COLUMBIA, SOUTH CAROLINA29250
803.834.4048 p803.834.4082 f
WWW.1X1DESIGN.COM
SHEET NUMBER
PROJECT NUMBER
REVISIONS
SHEET NAME
CLIE
NT
NA
ME
PRO
JECT
NA
ME
PRO
JECT
AD
DRE
SS
This
dra
win
g an
d th
e in
form
atio
n sh
own
ther
eon
are
prop
erty
of
1x1
Des
ign,
Inc.
Thi
s dr
awin
g m
ay n
ot b
e pu
blis
hed,
rep
rodu
ced,
cop
ied,
mod
ifie
d, u
ploa
ded,
tra
nsm
itte
d, p
oste
d, t
rans
ferr
ed o
r ot
herw
ise
used
wit
hout
the
pri
or w
ritt
en c
onse
nt o
f 1x
1 D
esig
n,In
c. L
egal
act
ion
will
be
purs
ued
agai
nst
all v
iola
tion
s an
d in
frin
gem
ents
to
the
full
exte
nt p
ossi
ble.
12/1
8/20
18 1
:05:
03 P
M
A101FLOOR PLANS
U-17-039-1
12.20.18
UN
IVER
SITY
OF
SOU
TH C
ARO
LIN
A
921
ASS
EMBL
Y S
TREE
T, C
OLU
MBI
A, S
C 29
208
RELE
ASE
D F
OR
BID
DIN
G -
DEC
EMBE
R 20
, 201
8
1/8" = 1'-0"2 SECOND FLOOR RENOVATION PLAN1/8" = 1'-0"
1 SECOND FLOOR - DEMOLITION PLAN
No. Description Date
PHRC
- REN
OV
ATI
ON
PRO
JECT
2N
D F
LOO
R SU
ITE
Uni
vers
ity
Proj
ect
No:
FP0
0000
192
REFLECTED CEILING PLAN LEGEND
2'x4' LIGHTING FIXTURE
2'x2' ACOUSTICAL PANEL CEILING (APC) (EXISTING). HEIGHT VARIES.
2'x2' LIGHTING FIXTURE
RETURN REGISTER, SEE MECHANICAL.
SUPPLY DIFFUSER, SEE MECHANICAL.
GENERAL REFLECTED CEILING PLAN NOTES1. EXISTING CONDITIONS BASED ON INFORMATION PROVIDED BY EXISTING PLANS
AND INFORMATION GATHERED DURING GENERAL FIELD OBSERVATION. IF GCDISCOVERS EXISTING CONDITIONS DIFFER FROM THOSE SHOWN, CONTACTOWNER OR ARCHITECT IMMEDIATELY.
2. ALL CEILING TILE TO BE CENTERED IN SPACE EXACTLY AS SHOWN UNLESS NOTEDOTHERWISE. ALL APC TO BE INSTALLED PER SEISMIC REQUIREMENTS. SEE SPECS.
3. SEE ELECTRICAL FOR ALL LIGHT FIXTURES AND ELECTRICAL REQUIREMENTS.4. SEE ELECTRICAL FOR ALL EMERGENCY AND EGRESS FIXTURE LOCATIONS.5. SEE MECHANICAL FOR ALL MECHANICAL ELEMENTS.6. COORDINATE WITH ELECTRICAL AND MECHANICAL FOR ALL FIXTURES AND
EQUIPMENT SPECIFICATIONS. REFER TO ARCHITECTURAL DRAWINGS FORLOCATION. WHERE ENGINEERING DRAWINGS CALL FOR ROOF PENETRATIONSWITH EXISTING ROOFING SYSTEM OR ROOF SYSTEM TO BE REPLACED, FLASHAND SEAL AS REQUIRED.
OFFICE
216C
OFFICE
216D
OFFICE
216E
OFFICE
216F
OFFICE
223
OFFICE
241
VESTIBULE
V203
OFFICE
224
OFFICE
225
OFFICE
226
OFFICE
227
OFFICE
228
OFFICE
222
OFFICE
221
OFFICE
239
STORAGE
240
OFFICE
229
OFFICE
220
OFFICE
216B
OFFICE
216A
TELE/COMM
217
OFFICE
215
OFFICE
214
STORAGE
213
OFFICE
235
OFFICE
233
RECEPTION
212
WORK/FILEAREA
212A
BREAKROOM
234
OFFICE
232
OFFICE
236
OFFICE
218
CORRIDOR
H209OFFICE
237
OFFICE
219
OFFICE
238
OFFICE
230
OFFICE
231
CORRIDOR
H207
24' - 0"23' - 0"
23' - 0"
23' - 0"24' - 0"
23' - 0"24' - 0"
23' - 0"24' - 0"
23' - 0"
24' - 0"
23' - 0"24' - 0"
23' - 0"24' - 0"
ALTERNATE 1: SEE SHEET E102
R4
R4
EXTG STAIR VESTIBULE
OFFICE243
OFFICE242
OFFICE239
OFFICE238
OFFICE235
OFFICE234
OFFICE232
OFFICE231
OFFICE230
OFFICE229
BREAK ROOM245
RECEPTIONH206
OFFICE216
OFFICE217
STORAGE215
OPEN OFFICE220
OPEN OFFICE224
OFFICE244
OFFICE241
OFFICE219
OFFICE221
OFFICE240
OFFICE237
OFFICE222
OFFICE223
OFFICE236
OFFICE225
CONFERENCE227
STORAGE228
STORAGE226
TELE/COMM244
CORRIDORH209
CORRIDORH207
ALTERNATE 1: SEE SHEET E101
DEMOLITION KEY NOTE LEGENDREMOVE EXISTING DOOR, STORE FOR OWNER REUSE IN FUTURE PROJECT. OWNER TO PACKAGE AND RELOCATE FROM PROJECT SITE.
REMOVE WALL ENTIRELY. CEILING TO REMAIN.
D1
D2
REMOVE EXISTING ROLLERSHADE AND SALVAGE FOR OWNER'S REUSE IN FUTURE PROJECT. OWNER TO PACKAGE AND RELOCATE FROM PROJECT SITE.
D3 REMOVE EXISTING FLOORING AND RUBBER BASE.
D4
REMOVE EXISTING LIGHTING THIS AREA, SEE ELECTRICAL FOR EXACT LOCATIONS.D5
GC TO PROTECT EXISTING ROLLER SHADES, OPTION TO REMOVE, PROTECT AND REINSTALL AT COMPLETION OF PROJECT.
D6
REMOVE EXISTING FLOORING AND RUBBER BASE. SCORE RUBBER BASE SO IT'S REMOVAL FROM THE EXISTING WALL CREATES MINIMAL DAMAGE/REQUIRED TOUCH-UP. EXISTING FURNITURE TO REMAIN.
D7
RENOVATION KEY NOTE LEGENDALIGN FINISHED FACE OF WALLS
INFILL WALL TO MATCH EXISTING
R1
R2
ALIGN WALL TO CENTER OF EXISTING ELEMENTR3
NEW PARTITION TO FOLLOW JOG IN EXISTING CEILING.R4
DEMOLITION REFLECTED CEILING PLAN LEGEND
EXISTING LIGHTING FIXTURE
EXISTING LIGHTING FIXTURE
RETURN REGISTER, SEE MECHANICAL.
SUPPLY DIFFUSER, SEE MECHANICAL.
DATE
221 PICKENS STREET (29205)POST OFFICE BOX 5875
COLUMBIA, SOUTH CAROLINA29250
803.834.4048 p803.834.4082 f
WWW.1X1DESIGN.COM
SHEET NUMBER
PROJECT NUMBER
REVISIONS
SHEET NAME
CLIE
NT
NA
ME
PRO
JECT
NA
ME
PRO
JECT
AD
DRE
SS
This
dra
win
g an
d th
e in
form
atio
n sh
own
ther
eon
are
prop
erty
of
1x1
Des
ign,
Inc.
Thi
s dr
awin
g m
ay n
ot b
e pu
blis
hed,
rep
rodu
ced,
cop
ied,
mod
ifie
d, u
ploa
ded,
tra
nsm
itte
d, p
oste
d, t
rans
ferr
ed o
r ot
herw
ise
used
wit
hout
the
pri
or w
ritt
en c
onse
nt o
f 1x
1 D
esig
n,In
c. L
egal
act
ion
will
be
purs
ued
agai
nst
all v
iola
tion
s an
d in
frin
gem
ents
to
the
full
exte
nt p
ossi
ble.
12/1
8/20
18 1
:05:
04 P
M
A201REFLECTED CEILING PLAN
U-17-039-1
12.20.18
UN
IVER
SITY
OF
SOU
TH C
ARO
LIN
A
921
ASS
EMBL
Y S
TREE
T, C
OLU
MBI
A, S
C 29
208
RELE
ASE
D F
OR
BID
DIN
G -
DEC
EMBE
R 20
, 201
8
1/8" = 1'-0"3 SECOND FLOOR- RENOVATION RCP
1/8" = 1'-0"1 SECOND FLOOR- DEMOLITION RCP
NO CEILING WORKANTICIPATED
No. Description Date
PHRC
- REN
OV
ATI
ON
PRO
JECT
2N
D F
LOO
R SU
ITE
Uni
vers
ity
Proj
ect
No:
FP0
0000
192
GENERAL INTERIOR FINISH NOTES1. FOR FINISH LOCATIONS, REFER TO PLAN NORTH, SOUTH, EAST AND WEST FOR
FINISH PLACEMENT.2. FIELD VERIFY ALL LOCATIONS FOR CASEWORK PLACEMENT, PRIOR TO
FABRICATION. ENSURE ALL CLEARANCES ARE MET AND ACCOUNTED FOR.NOTIFY CONTRACTOR OF ANY DISCREPANCIES IMMEDIATELY.
3. ALL INTERIOR WALL AND CEILING FINISH MATERIALS SHALL BE CLASSIFIED INACCORDANCE WITH ASTM E 84 OR UL 723. FINISHES SHALL BE MEET CLASS AREQUIREMENTS, UNLESS NOTED OTHERWISE.
4. INSTALL ALL MATERIALS PER MANUFACTURER'S SPECIFICATIONS ANDRECOMMENDATIONS.
5. ALL APC TO BE INSTALLED PER SEISMIC REQUIREMENTS.6. PROVIDE PROPER MATERIAL TRANSITION STRIPS WHERE NEEDED.7. <PER PROJECT AS REQD> GENERAL CONTRACTOR TO COORDINATE ACOUSTICAL
CEILING INSTALLATION WITH MILLWORK PROFILES.8. <PER PROJECT AS REQD> ALL PRODUCTS SELECTED ARE FOR BASIS OF DESIGN
PURPOSES AND "APPLES TO APPLES" PRICING EXERCISE. PLEASE ENSURE ANY SUBSTITUTIONS/ALTERNATES ARE REVIEWED WITH OWNER PRIOR TO INSTALLATION.
INTERIOR FINISH SPECIFICATION LEGEND (BASIS OF DESIGN)FLOORING:
RB 1 - RUBBER COVE BASE
MFR: JOHNSONITE OR APPROVED EQUALSTYLE: BASIS OF DEISGN, PERCEPTIONS WALL BASE CONTOURCOLOR: TBDSIZE: 4 1/4"
PAINT:
P 1 - (GENERAL FIELD COLOR)
MFR: SHERWIN WILLIAMS OR APPROVED EQUALCOLOR: TBDFINISH: EG-SHEL
CPT 1 - CARPET TILE
MFR: MANNINGTON COMMERCIAL OR APPROVED EQUALDESIGN: HUSKCOLOR: TBDSIZE: 24 in x 24 inINSTALLATION: ASHLAR OR AS RECOMMENDED BY MANUFACTURER
* ALL FINISHES TO MEET FLAME SPREAD REQUIREMENTS. INSTALL ALL MATERIALS PER MANUFACTURER RECOMMENDATIONS.
CPT 2 - CARPET TILE
MFR: MANNINGTON COMMERCIAL OR APPROVED EQUALDESIGN: HUSKCOLOR: TBDSIZE: 24 in x 24 inINSTALLATION: ASHLAR OR AS RECOMMENDED BY MANUFACTURER
P 2 - (HOLLOW METAL FRAME PAINT)
MFR: SHERWIN WILLIAMS OR APPROVED EQUALCOLOR: TBDFINISH: SEMI-GLOSS
* REFER TO PROJECT MANUAL FOR ADDITIONAL INFORMATION ON OTHER ACCEPTABLE MANUFACTURERS.
P 3 - (ACCENT COLOR)
MFR: SHERWIN WILLIAMS OR APPROVED EQUALCOLOR: TBDFINISH: EG-SHEL
EXT'G STAIR
OFFICE
214
OFFICE
215
OFFICE
216A
TELE/COMM
217
OFFICE
218
OFFICE
219
OFFICE
220
OFFICE
221
OFFICE
222
OFFICE
223
STORAGE
240
OFFICE
239
OFFICE
238
OFFICE
237
OFFICE
236
OFFICE
235
RECEPTION
212
BREAKROOM
234
OFFICE
233
OFFICE
232
OFFICE
231
OFFICE
230
OFFICE
229
OFFICE
228
OFFICE
227
OFFICE
226
OFFICE
225
OFFICE
224
OFFICE
216F
OFFICE
216E
OFFICE
216D
OFFICE
216C
OFFICE
216B
OFFICE
241
216A.1
216B.1
216C.1
216D.1
216E.1
223.1 241.1
216F.1
STORAGE
213
WORK/FILEAREA
212A
VESTIBULE
V203
CORRIDOR
H207
CORRIDOR
H209
NO WORKANTICIPATED
P1
PAINT TO MATCH EXISTING
PAINT TO MATCH EXISTING ADJACENT WALL
P3
P1
A B
10"
DR
HEI
GH
T
DR WIDTH
DR
HEI
GH
T
DR WIDTH
6"
6" 6"EQ EQ
GL-1GL-1
HOLLOW METAL FRAME
2"
2"
1
1' -
0"
1' - 6"
GL-2
GL-3
DR WIDTHHOLLOW METAL FRAME
2"
2"
2
GENERAL DOOR NOTES1. DOOR TYPE INDICATES DOOR TYPE, DOOR WIDTH (IN INCHES), DOOR HEIGHT (IN
INCHES) AND RATING (IN MINUTES). FOR EXAMPLE, DOOR TYPE A.36.84.00 IS A DOORTYPE "A", 36" IN WIDTH, 84" IN HEIGHT, WITH A "0" MINUTE FIRE RATING.
2. ALL DOORS TO BE LOCATED 6" FROM ADJACENT PERPENDICULAR WALL TO INSIDEFACE OF FRAME, UNLESS NOTED OTHERWISE. THIS DOES NOT APPLY TO STOREFRONTITEMS.
3. HEAD, JAMB AND SILL DETAILS ARE NOT SHOWN. COORDINATE WITHMANUFACTURER'S REQUIREMENTS, STRUCTURAL DRAWINGS, AND PARTITION TYPESFOR EXACT PRODUCT SELECTED AND APPROVED FOR USE. GC SHALL BE RESPONSIBLEFOR COORDINATING DETAILS AS REQUIRED .
4. DOOR HARDWARE ALLOWANCE: $600 PER NEW LEAF, MATCH EXISTING HARDWAREIF APPLICABLE AND COORDINATE WITH OWNER. SEE SPECS.
5. REFER TO THIS SHEET FOR FINISH DESIGNATIONS.
GENERAL STOREFRONT NOTESGL 1 - BASIS OF DESIGN
MFR: GUARDIAN INDUSTRIES CORP OR EQUALPRODUCT: CLEAR LAMINATED GLASSNOTE: PROVIDE SAFETY GLAZING LABEL
GL 2 - BASIS OF DESIGNMFR: GUARDIAN INDUSTRIES CORP OR EQUALPRODUCT: CLEAR TEMPERED GLASSTHICKNESS: 1/4" MINNOTE: PROVIDE SAFETY GLAZING LABEL
GL 3 - BASIS OF DESIGNMFR: GUARDIAN INDUSTRIES CORP OR EQUALPRODUCT: CLEAR MONOLITHIC GLASS
EXT'G STAIR
OFFICE
214
OFFICE
215
OFFICE
216A
TELE/COMM
217
OFFICE
218
OFFICE
219
OFFICE
220
OFFICE
221
OFFICE
222
OFFICE
223
STORAGE
240
OFFICE
239
OFFICE
238
OFFICE
237
OFFICE
236
OFFICE
235
RECEPTION
212
BREAKROOM
234
OFFICE
233
OFFICE
232
OFFICE
231
OFFICE
230
OFFICE
229
OFFICE
228
OFFICE
227
OFFICE
226
OFFICE
225
OFFICE
224
OFFICE
216F
OFFICE
216E
OFFICE
216D
OFFICE
216C
OFFICE
216B
OFFICE
241
216A.1
216B.1
216C.1
216D.1
216E.1
223.1 241.1
216F.1
STORAGE
213
WORK/FILEAREA
212A
VESTIBULE
V203
CORRIDOR
H207
CORRIDOR
H209
NO WORKANTICIPATED
PAINT EXTENTS
DATE
221 PICKENS STREET (29205)POST OFFICE BOX 5875
COLUMBIA, SOUTH CAROLINA29250
803.834.4048 p803.834.4082 f
WWW.1X1DESIGN.COM
SHEET NUMBER
PROJECT NUMBER
REVISIONS
SHEET NAME
CLIE
NT
NA
ME
PRO
JECT
NA
ME
PRO
JECT
AD
DRE
SS
This
dra
win
g an
d th
e in
form
atio
n sh
own
ther
eon
are
prop
erty
of
1x1
Des
ign,
Inc.
Thi
s dr
awin
g m
ay n
ot b
e pu
blis
hed,
rep
rodu
ced,
cop
ied,
mod
ifie
d, u
ploa
ded,
tra
nsm
itte
d, p
oste
d, t
rans
ferr
ed o
r ot
herw
ise
used
wit
hout
the
pri
or w
ritt
en c
onse
nt o
f 1x
1 D
esig
n,In
c. L
egal
act
ion
will
be
purs
ued
agai
nst
all v
iola
tion
s an
d in
frin
gem
ents
to
the
full
exte
nt p
ossi
ble.
12/1
8/20
18 1
:05:
05 P
M
A801DOOR/FINISH SCHEDULES
U-17-039-1
12.20.18
UN
IVER
SITY
OF
SOU
TH C
ARO
LIN
A
921
ASS
EMBL
Y S
TREE
T, C
OLU
MBI
A, S
C 29
208
RELE
ASE
D F
OR
BID
DIN
G -
DEC
EMBE
R 20
, 201
8
ROOM FINISH SCHEDULE
NO. NAMEFLOOR BASE CEILING WALL FINISH (PLAN ORIENTATION)
COMMENTSFINISH FINISH FINISH NORTH SOUTH EAST WEST
212 RECEPTION CPT 1 RB 1 XTR P 3 XTR P 1 XTR212A WORK/FILE AREA CPT 1 RB 1 XTR -- P 1 P 1 P 1213 STORAGE CPT 2 RB 1 XTR XTR XTR XTR XTR214 OFFICE CPT 2 RB 1 XTR XTR XTR XTR XTR EXISTING FURNITURE TO REMAIN IN SPACE
WHILE WORK IS ONGOING.215 OFFICE CPT 2 RB 1 XTR XTR XTR XTR XTR EXISTING FURNITURE TO REMAIN IN SPACE
WHILE WORK IS ONGOING.216A OFFICE CPT 2 RB 1 XTR P 1 P 1 P 1 P 1216B OFFICE CPT 2 RB 1 XTR P 1 P 1 P 1 P 1216C OFFICE CPT 2 RB 1 XTR P 1 P 1 P 1 P 1216D OFFICE CPT 2 RB 1 XTR P 1 P 1 P 1 P 1216E OFFICE CPT 2 RB 1 XTR P 1 P 1 P 1 P 1216F OFFICE CPT 2 RB 1 XTR P 1 P 1 P 1 P 1217 TELE/COMM XTR RB 1 XTR XTR XTR XTR XTR EXISTING FURNITURE TO REMAIN IN SPACE
WHILE WORK IS ONGOING.218 OFFICE CPT 2 RB 1 XTR XTR XTR XTR XTR EXISTING FURNITURE TO REMAIN IN SPACE
WHILE WORK IS ONGOING.219 OFFICE CPT 2 RB 1 XTR XTR XTR XTR XTR EXISTING FURNITURE TO REMAIN IN SPACE
WHILE WORK IS ONGOING.220 OFFICE CPT 2 RB 1 XTR XTR XTR XTR XTR EXISTING FURNITURE TO REMAIN IN SPACE
WHILE WORK IS ONGOING.221 OFFICE CPT 2 RB 1 XTR XTR XTR XTR XTR EXISTING FURNITURE TO REMAIN IN SPACE
WHILE WORK IS ONGOING.222 OFFICE CPT 2 RB 1 XTR XTR XTR XTR XTR EXISTING FURNITURE TO REMAIN IN SPACE
WHILE WORK IS ONGOING.223 OFFICE CPT 2 RB 1 XTR P 1 P 1 P 1 P 1224 OFFICE CPT 2 RB 1 XTR XTR XTR XTR XTR EXISTING FURNITURE TO REMAIN IN SPACE
WHILE WORK IS ONGOING.225 OFFICE CPT 2 RB 1 XTR XTR XTR XTR XTR EXISTING FURNITURE TO REMAIN IN SPACE
WHILE WORK IS ONGOING.226 OFFICE CPT 2 RB 1 XTR XTR XTR XTR XTR EXISTING FURNITURE TO REMAIN IN SPACE
WHILE WORK IS ONGOING.227 OFFICE CPT 2 RB 1 XTR XTR XTR XTR XTR EXISTING FURNITURE TO REMAIN IN SPACE
WHILE WORK IS ONGOING.228 OFFICE CPT 2 RB 1 XTR XTR XTR XTR XTR EXISTING FURNITURE TO REMAIN IN SPACE
WHILE WORK IS ONGOING.229 OFFICE CPT 2 RB 1 XTR XTR XTR XTR XTR EXISTING FURNITURE TO REMAIN IN SPACE
WHILE WORK IS ONGOING.230 OFFICE CPT 2 RB 1 XTR XTR XTR XTR XTR EXISTING FURNITURE TO REMAIN IN SPACE
WHILE WORK IS ONGOING.231 OFFICE CPT 2 RB 1 XTR XTR XTR XTR XTR EXISTING FURNITURE TO REMAIN IN SPACE
WHILE WORK IS ONGOING.232 OFFICE CPT 2 RB 1 XTR XTR XTR XTR XTR EXISTING FURNITURE TO REMAIN IN SPACE
WHILE WORK IS ONGOING.233 OFFICE CPT 2 RB 1 XTR XTR XTR XTR XTR EXISTING FURNITURE TO REMAIN IN SPACE
WHILE WORK IS ONGOING.234 BREAK ROOM XTR XTR XTR XTR XTR XTR P 1 EXISTING FURNITURE TO REMAIN IN SPACE
WHILE WORK IS ONGOING.235 OFFICE CPT 2 RB 1 XTR XTR XTR XTR XTR EXISTING FURNITURE TO REMAIN IN SPACE
WHILE WORK IS ONGOING.236 OFFICE CPT 2 RB 1 XTR XTR XTR XTR XTR EXISTING FURNITURE TO REMAIN IN SPACE
WHILE WORK IS ONGOING.237 OFFICE CPT 2 RB 1 XTR XTR XTR XTR XTR EXISTING FURNITURE TO REMAIN IN SPACE
WHILE WORK IS ONGOING.238 OFFICE CPT 2 RB 1 XTR XTR XTR XTR XTR EXISTING FURNITURE TO REMAIN IN SPACE
WHILE WORK IS ONGOING.239 OFFICE CPT 2 RB 1 XTR XTR XTR XTR XTR EXISTING FURNITURE TO REMAIN IN SPACE
WHILE WORK IS ONGOING.240 STORAGE XTR XTR XTR XTR XTR XTR XTR241 OFFICE CPT 2 RB 1 XTR P 1 P 1 P 1 P 1H207 CORRIDOR CPT 1 RB 1 XTR XTR XTR XTR XTRH209 CORRIDOR CPT 1 RB 1 XTR XTR XTR XTR XTRV203 VESTIBULE CPT 1 RB 1 XTR XTR XTR XTR XTR
1/8" = 1'-0"3 SECOND FLOOR- FINISH PLAN
DOOR SCHEDULE
NUMBER
SIZE DOOR FIRERATIN
G
FRAMEHARDWARECOMMENTS COMMENTSWIDTH HEIGHT TYPE MATERIAL FINISH TYPE MATERIAL FINISH
216A.1 6' - 0" 7' - 0" A.72.84.00 WOOD STAINED 0 2 HOLLOW METAL P2 A,B216B.1 4' - 6" 7' - 0" A.36.84.00 WOOD STAINED 0 1 HOLLOW METAL P2 A,B216C.1 4' - 6" 7' - 0" A.36.84.00 WOOD STAINED 0 1 HOLLOW METAL P2 A,B216D.1 4' - 6" 7' - 0" A.36.84.00 WOOD STAINED 0 1 HOLLOW METAL P2 A,B216E.1 4' - 6" 7' - 0" A.36.84.00 WOOD STAINED 0 1 HOLLOW METAL P2 A,B216F.1 4' - 6" 7' - 0" A.36.84.00 WOOD STAINED 0 1 HOLLOW METAL P2 A,B223.1 3' - 0" 7' - 0" A.36.84.00 WOOD STAINED 0 1 HOLLOW METAL P2 A,B241.1 3' - 0" 7' - 0" A.36.84.00 WOOD STAINED 0 1 HOLLOW METAL P2 A,B
DOOR SCHEDULE COMMENTS:
A: SEE FINISH SCHEDULE FOR PAINT DESIGNATIONSB: STAINED WOOD FINISH SHALL BE SELECTED FROM MANUFACTURERS' FULL RANGE
1/4" = 1'-0"1 DOOR TYPES
1/4" = 1'-0"2 FRAME TYPES
1/8" = 1'-0"4 SECOND FLOOR- FINISH PLAN- ALTERNATE #2
ALTERNATE #2:PAINT ALL COMMON AREA WALLS NOT IN THE BASE BID INCLUDED IN AREAS H207, H209, 212, V203 TO EXTENTS SHOWN ON THIS DRAWING. PAINT COLOR TO BE DETERMINED IF ALTERNATE IS ACCEPTED.
No. Description Date
PHRC
- REN
OV
ATI
ON
PRO
JECT
2N
D F
LOO
R SU
ITE
Uni
vers
ity
Proj
ect
No:
FP0
0000
192
T
T
T
T
T
T
T
2 207
2
209
T
1
2
2
2
2 2
2
2 3
32
205
2 2
2
2
2
2
2
3
VESTIBULEH208
OFFICE229
OFFICE230
CORRIDORH207
OFFICE224D
OFFICE224C
OFFICE224B
OFFICE224A
OFFICE224
OFFICE220
OFFICE217
OFFICE216
STORAGE215
RECEPTIONH206
WORK/FILEAREA228
BREAKROOM
245
OFFICE243
OFFICE242
OFFICE239
OFFICE238
OFFICE235
OFFICE234
OFFICE232
OFFICE231
OFFICE227
OFFICE226
STORAGE233
OFFICE236
OFFICE237
OFFICE225
OFFICE223
OFFICE222
OFFICE221
OFFICE240
OFFICE241
OFFICE219
TELE/COMM218
OFFICE244
CORRIDORH209
T
T
T
T
T
T
207
T
205
3
2
2
2073
1 2
22
A 100
A 100
PROVIDE END CAP
1
2
1
2
1
12
3205
2
1
1
1
GENERAL NOTESALL WORK SHALL BE IN ACCORDANCE WITH THE 2015 INTERNATIONAL MECHANICAL CODE, 2015 INTERNATIONAL FUEL GAS CODE, 2009 INTERNATIONAL ENERGY CONSERVATION CODE, AND 2005 SMACNA HVAC DUCT CONSTRUCTION STANDARD. ALL LOCAL CODES OR REQUIREMENTS STILL APPLY.
VISIT SITE PRIOR TO BIDDING. THIS CONTRACTOR SHALL DETERMINE DIFFICULTY OF INSTALLATION AND REFLECT THIS IN HIS BIDDING.
DO NOT SCALE DRAWINGS. SEE ARCHITECTURAL DRAWINGS AND REFLECTED CEILING PLANS FOR EXACT LOCATIONS OF DOORS, WINDOWS, AIR DISTRIBUTION, ETC.
DO NOT SCALE DRAWINGS. THIS CONTRACTOR SHALL VERIFY ALL EXISTING ITEMS AND LOCATIONS IN THE FIELD.
ALL PIPING AND DUCTWORK LOCATIONS SHALL BE COORDINATED WITH WORK UNDER OTHER DIVISIONS OF THE SPECIFICATIONS TO AVOID INTERFERENCE.
SPACE ABOVE CEILING TO BE USED AS RETURN AIR PLENUM WHERE DUCT IS NOT INDICATED ABOVE RETURN AIR GRILLES.
THIS CONTRACTOR SHALL PROVIDE ALL ITEMS OF MISCELLANEOUS STEEL AS REQUIRED FOR INSTALLATION OF ALL MECHANICAL ITEMS.
REMOVAL AND REPLACEMENT OF CEILING, AS REQUIRED FOR INSTALLATION OF NEW WORK, SHALL BE DONE BY GENERAL CONTRACTOR.
THIS CONTRACTOR SHALL INCLUDE THE COST FOR ALL CONTROL WIRING AND RELOCATION OF THERMOSTATS. CONTROLS SHAL LBE BY JOHSNONS CONTROLS.
LOCATE ALL SPACE CONTROL INSTRUMENTS 4'-0" ABOVE FINISHED FLOOR. COORDINATE LOCATIONS WITH ARCHITECTURAL ELEVATIONS TO AVOID ITEMS INCLUDING BUT NOT LIMITED TO CUSTOM FINISHES, FIXED CASEWORK, FURNITURE, AND DOOR SWINGS. IN THE EVENT OF CONFLICTS IN THE FIELD, THE CONTRACTOR SHALL BRING THIS TO THE ATTENTION OF THE A/E FOR FINAL APPROVAL OF LOCATION.
THIS CONTRACTOR SHALL BE RESPONSIBLE FOR ANY NECESSARY DISMANTLING OF EQUIPMENT TO BE REMOVED.
ITEMS REMOVED UNDER THIS CONTRACT SHALL BECOME THE PROPERTY OF THE CONTRACTOR AND SHALL BE DISPOSED OF PROPERLY.
THIS CONTRACTOR SHALL PATCH ALL WALLS AND FINISHES TO MATCH EXISTING WHERE ALL ITEMS OR EQUIPMENT ARE REMOVED.
THE HVAC SYSTEMS SHALL NOT BE OPERATED DURING HEAVY CONSTRUCTION OPERATIONS INCLUDING MASONRY, GYPSUM BOARD SANDING, HEAVY CLEANUP ACTIVITIES, OR OTHER ACTIVITIES THAT CREATE AIRBORNE PARTICLES OR DEBRIS. ALL SYSTEMS SHALL BE CLEAN OF CONSTRUCTION DEBRIS, DUST AND DIRT AT FINAL COMPLETION. DUCT CLEANING AND UNIT/COIL CLEANING SHALL BE PERFORMED IF REQUIRED. IF EQUIPMENT OPERATES DURING CONSTRUCTION PROVIDE FILTER MEDIA OVER ALL RETURN GRILLES AND RETURN DUCT OPENINGS TO PROTECT DUCTS AND EQUIPMENT.
1.
2.
3.
4.
5.
6.
7.
8.
9.
10.
11.
12.
13.
14.
100A
LEGEND
T THERMOSTAT
TYPE "A" DIFFUSER, 100 CFM
SYMBOL DESCRIPTION
RETURN AND FRESH AIR DUCTWORK
RECTANGULAR SUPPLY DUCTWORK
CONNECTION POINT OF NEW TO EXISTING
TAG
A
NECK SIZE
UNI-FLOW SUPPLY
DESCRIPTION
PRICE
MANUFACTURER
ASPD
MODEL
LAY-IN
FRAME
126-250
CFM
8"ø
MAX NC
3024"x24"
FACE SIZE REMARKS
1, 2
AIR DISTRIBUTION SCHEDULE
1. PROVIDE WITH STANDARD WHITE FINISH.2. PROVIDE ALUMINUM OR ALUMINIZED STEEL CONSTRUCTION.
DEMOLITION NOTES
REMOVE EXISTING CEILING GRILLE AND DUCTWORK BACK TO TRUNK DUCT. PATCH TRUNK DUCT WITH SHEET METAL AND DUCT SEALER. PATCH INSULATION TO MATCH EXISTING.
RELOCATE EXISTING GRILL AS SHOWN ON RENOVATION PLAN.
RELOCATE EXISTING THERMOSTAT AS SHOWN ON RENOVATION PLAN.
1
2
3
NOTES TO SHEET
RELOCATE EXISTING SUPPLY DIFFUSER TO THIS LOCATION. PROVIDE ADDITIONAL ROUND METAL DUCT AND FLEXIBLE DUCT AS REQUIRED.
RELOCATE EXISTING GRILLE TO THIS LOCATION.
RELOCATE EXISTING THERMOSTAT TO THIS LOCATION.
1
2
3
REGISTERED
PROFES
SI O
N A L E N G I N E E R
W I L L I A MC
.LI
VIN
GSTON
SOUTHCA
R OL I N A
No. 1
7994
C E R T I F I C A T EOF
AUT
HORIZATION
SOUTHCA
R OL I N A
SWYG
ERT A
NDAS
SOCIA
TES,
LTD.
NO. C
00227
DATE
221 PICKENS STREET (29205)POST OFFICE BOX 5875
COLUMBIA, SOUTH CAROLINA29250
803.834.4048 p803.834.4082 f
WWW.1X1DESIGN.COM
SHEET NUMBER
PROJECT NUMBER
REVISIONS
SHEET NAME
CLIE
NT
NA
ME
PRO
JECT
NA
ME
PRO
JECT
AD
DRE
SS
This
dra
win
g an
d th
e in
form
atio
n sh
own
ther
eon
are
prop
erty
of
1x1
Des
ign,
Inc.
Thi
s dr
awin
g m
ay n
ot b
e pu
blis
hed,
rep
rodu
ced,
cop
ied,
mod
ifie
d, u
ploa
ded,
tra
nsm
itte
d, p
oste
d, t
rans
ferr
ed o
r ot
herw
ise
used
wit
hout
the
pri
or w
ritt
en c
onse
nt o
f 1x
1 D
esig
n,In
c. L
egal
act
ion
will
be
purs
ued
agai
nst
all v
iola
tion
s an
d in
frin
gem
ents
to
the
full
exte
nt p
ossi
ble.
C O N S U L T I N G E N G I N E E R S
Swygert & Associates
DBA Swygert & Assoc., Ltd.Post Office Box 11686Columbia, S.C. 29211
Telephone: (803) 791-9300Facsimile: (803) [email protected]
M101SECOND FLOOR PLANS
12.20.18
UN
IVER
SITY
OF
SOU
TH C
ARO
LIN
A
921
ASS
EMBL
Y S
TREE
T, C
OLU
MBI
A, S
C 29
208
RELE
ASE
D F
OR
BID
DIN
G -
DEC
EMBE
R 20
, 201
8
12−20−18
1/8" = 1'-0"M1011 SECOND FLOOR DEMOLITION PLAN
1/8" = 1'-0"M1012 SECOND FLOOR RENOVATION PLAN
No. Description Date
U-17-039-1
PHRC
- REN
OV
ATI
ON
PRO
JECT
2N
D F
LOO
R SU
ITE
Uni
vers
ity
Proj
ect
No:
FP0
0000
192
ELECTRICAL SYMBOL LEGEND
DESCRIPTIONSYMBOL SYMBOL
SINGLE RECEPTACLE (WALL MOUNTED @ 18"AFF)
DUPLEX RECEPTACLE (WALL MOUNTED @ 18"AFF)
PHONE OR DATA OUTLET (WALL MOUNTED @ 18"AFF)
MOTOR CONNECTION (AS NOTED)
J JUNCTION BOX (WALL MTD)
J JUNCTION BOX (FLOOR MOUNTED)
DUPLEX RECEPTACLE (FLOOR MOUNTED)
QUADPLEX RECEPTACLE (FLOOR MOUNTED)
DISCONNECT SWITCH, (REFER TO EQUIPMENT
CONNECTION SCHEDULE)
DISCONNECT SWITCH, (NON PROTECTED)
SP SPEAKER (CEILING MOUNTED)
SP SPEAKER (WALL MOUNTED)
DUPLEX RECEPTACLE (CEILING MOUNTED)
QUADPLEX RECEPTACLE (CEILING MOUNTED)
TV TELEVISION / CATV OUTLET (WALL MOUNTED @ 18"
AFF)
R SECURITY CARD READER
S SMOKE DETECTOR (WALL MOUNTED)
D SMOKE DETECTOR (DUCT MOUNTED)
A FIRE ALARM AUDIBLE DEVICE (WALL MOUNTED @ 7'-
6" AFF)
WF Wi-Fi ACCESS POINT (CEILING MOUNTED)
AIUADDRESSABLE INTERFACE UNIT (MONITOR OR
CONTROL TYPE)
HANDHOLEHH
DESCRIPTION
FSD FIRE / SMOKE DAMPER
W CCTV CAMERA (WALL MOUNTED)
C CCTV CAMERA (CEILING MOUNTED)
PUSH BUTTON CONTROL
H HEAT DETECTOR (CEILING MOUNTED)
SPD SURGE PROTECTION DEVICE
CABLE TRAY
KITCHEN EQUIPMENT CALLOUT (REFER TO SCHEDULE)#
DUPLEX RECEPTACLE (@ 6" ABOVE COUNTER)
DUPLEX RECEPTACLE (GFI TYPE @ 18"AFF)
DUPLEX RECEPTACLE (USB TYPE @ 18"AFF)
QUAD RECEPTACLE (WALL MOUNTED @ 18"AFF)
QUAD RECEPTACLE (GFI TYPE @ 18"AFF)
QUAD RECEPTACLE (USB TYPE @ 18"AFF)
QUAD RECEPTACLE (@ 6" ABOVE COUNTER)
J JUNCTION BOX (CEILING)
PHONE OR DATA OUTLET (MTD ABOVE COUNTER)
PHONE OR DATA OUTLET (FLOOR MOUNTED)
V FIRE ALARM VISUAL DEVICE (WALL MOUNTED @ 7'-6"
AFF)
A/V FIRE ALARM AUDIBLE/VISUAL DEVICE (WALL MOUNTED @
7'-6" AFF)
FIRE ALARM AUDIBLE DEVICE (CEILING MOUNTED)
FIRE ALARM VISUAL DEVICE (CEILING MOUNTED)
FIRE ALARM AUDIBLE/VISUAL DEVICE (CEILING MOUNTED)
A
V
A/V
S SMOKE DETECTOR (CEILING MOUNTED)
FIRE ALARM PULL STATION (WALL MOUNTED @ 48"
AFF TOP OF BOX)F
T FIRE ALARM TAMPER SWITCH
P FIRE ALARM PRESSURE SWITCH
H HEAT DETECTOR (WALL MOUNTED)
F FIRE ALARM FLOW SWITCH
TV TELEVISION / CATV OUTLET (CEILING MOUNTED)
MULTI-PHASE RECEPTACLE (AS NOTED ON PLAN)
CONDUIT CALLOUT (# INDICATES DIAMETER)#" C.
LIGHTING CONTROL CALLOUT (REFER TO SCHEDULE)#
K SECURITY KEY PAD
PANELBOARD (SURFACE MOUNTED)
PANELBOARD (RECESS MOUNTED)
PIV PRESSURE INDICATING VALVE
#
LIGHT SWITCH, SINGLE POLE
LIGHT SWITCH, 3 WAY TYPE
LIGHT SWITCH, 4 WAY TYPE
LIGHT SWITCH, AUTOMATIC (CONNECT TO LCS)
LIGHT SWITCH, DIGITALLY TIMED (0-30 MINUTES)
LIGHT SWITCH, DIMMER TYPE
LOWER CASE SUBSCRIPT INDICATES SWITCH-LEGa
T
D
A
4
3
OS OCCUPANCY SENSOR (CEILING MOUNTED)
OS OCCUPANCY SENSOR (WALL MOUNTED)
PC PHOTOCELL LIGHTING CONTROL
KEY NOTE CALLOUT (REFER TO KEY NOTES ON SHEET)#
CONTROL PANEL (SURFACE MOUNTED)
CONTROL PANEL (RECESS MOUNTED)
REMOTE TEST STATION FOR DUCT MOUNTED DETECTORS
(WALL MOUNTED)
REMOTE TEST STATION FOR DUCT MOUNTED DETECTORS
(CEILING MOUNTED)
T
T
MMOTOR RATED SNAP SWITCH IN NEMA 1 ENCLOSURE
ELECTRICAL METERING DEVICE
ELECTRICAL UTILITY METER & C/T CABINET
M
M
DUPLEX REC/DATA COMBINATION (FLOOR MOUNTED)
QUADPLEX REC/DATA COMBINATION (FLOOR
MOUNTED)
MULTI-LEVEL SWITCHING CONFIGURATION
DUPLEX RECEPTACLE (GFI TYPE @ 6" ABOVE
COUNTER)
DUPLEX RECEPTACLE (USB TYPE @ 6" ABOVE
COUNTER)
QUAD RECEPTACLE (GFI TYPE @ 6" ABOVE
COUNTER)
QUAD RECEPTACLE (USB TYPE @ 6" ABOVE
COUNTER)
REMOTE FEED-THRU GFCI DEVICE WITH
INDICATOR LIGHT. (NO RECEPTACLE)HH
WAP WIRELESS ACCESS POINT (CEILING MOUNTED)
(803) 731-0650 p | (803) 731-2880 f
ENGINEERING
7 CLUSTERS COURT, SUITE 201 | COLUMBIA, SC | 29210
ASSOCIATES, INC.
BELKA
CONTACT: CLIFF STRINGFIELD
(803) 731-0650 p | (803) 731-2880 f
ENGINEERING
7 CLUSTERS COURT, SUITE 201 | COLUMBIA, SC | 29210
ASSOCIATES, INC.
BELKA
CONTACT: CLIFF STRINGFIELD
(803) 731-0650 p | (803) 731-2880 f
ENGINEERING
7 CLUSTERS COURT, SUITE 201 | COLUMBIA, SC | 29210
ASSOCIATES, INC.
BELKA
CONTACT: CLIFF STRINGFIELD
OB21808OB21808OB21808
No. C00953
ASSOC. INC.
BELKA
ENGINEERING
A
NILORACHTU
O
S
CE
RT
I FI CATE OF AUTHOR
I ZA
TI O
N
No. C00953
ASSOC. INC.
BELKA
ENGINEERING
A
NILORACHTU
O
S
CE
RT
I FI CATE OF AUTHOR
I ZA
TI O
N
No. C00953
ASSOC. INC.
BELKA
ENGINEERING
A
NILORACHTU
O
S
CE
RT
I FI CATE OF AUTHOR
I ZA
TI O
N
No. 26181
R
A
NILORACHTU
O
S
J EE
NI
GN
E
LANOISSEF
OR
PD
ES
NE
CILA
S
ON E
AR
T
L.HERA
No. 26181
R
A
NILORACHTU
O
S
J EE
NI
GN
E
LANOISSEF
OR
PD
ES
NE
CILA
S
ON E
AR
T
L.HERA
No. 26181
R
A
NILORACHTU
O
S
J EE
NI
GN
E
LANOISSEF
OR
PD
ES
NE
CILA
S
ON E
AR
T
L.HERA
DATE
221 PICKENS STREET (29205)POST OFFICE BOX 5875
COLUMBIA, SOUTH CAROLINA
29250803.834.4048 p803.834.4082 f
WWW.1X1DESIGN.COM
SHEET NUMBER
PROJECT NUMBER
REVISIONS
SHEET NAME
CLIE
NT
NA
ME
PR
OJE
CT
NA
ME
PR
OJE
CT
AD
DR
ES
S
This
dra
win
g a
nd the info
rmation s
how
n there
on a
re p
ropert
y o
f B
elk
a E
ngin
eering &
Associa
tes, In
c. T
his
dra
win
g m
ay n
ot be p
ublis
hed, re
pro
duced, copie
d, m
odifie
d, uplo
aded, tr
ansm
itte
d, poste
d, tr
ansfe
rred o
r oth
erw
ise u
sed w
ithout th
e p
rior
written c
onsent of B
elk
a E
ngin
eering &
Associa
tes, In
c. L
egal action w
ill b
e p
urs
ued a
gain
st all
vio
lations a
nd infr
ingem
ents
to the full
exte
nt possib
le.
12-14-18
12
/17
/20
18
4:5
4:0
3 P
M
E001
ELECTRICAL NOTES &LEGENDS
U-17-039-1
12.20.18
UN
IVE
RS
ITY
OF
SO
UT
H C
AR
OL
INA
921 A
SS
EM
BLY
ST
RE
ET
, C
OLU
MB
IA,
SC
29208
RE
LE
AS
ED
FO
R B
IDD
ING
– D
EC
EM
BE
R 2
0,
20
18
GENERAL EXISTING CONDITION NOTES1 AREAS OF WORK EXIST FOR THIS PROJECT WHICH ARE NOT ACCESSIBLE OR HAVE LIMITED ACCESS DURING
DESIGN. AS SUCH CONTRACTOR SHALL VERIFY ALL UTILITIES IN AREA OF WORK BEFORE DEMOLITION OF ANY
SERVICE. ANY ELECTRICAL COMPONENTS NOT SHOWN SHALL BE IDENTIFIED AND THE ARCHITECT AND
ENGINEER SHALL BE NOTIFIED AS SOON AS POSSIBLE. NO ELECTRICAL REWORK SHALL BE COMMENCEDWITHOUT COORDINATION OF BOTH ARCHITECT AND ENGINEER.
2 IN AREAS WHERE THE EXISTING CEILINGS ARE NOT SLATED TO BE REMOVED, THE CONTRACTOR SHALL WORKTHRU THE EXISTING CEILINGS (SEE ARCHITECTURAL REFLECTED CEILING PLAN FOR AREA OF WORK). THE
CONTRACTOR SHALL BE RESPONSIBLE FOR REPLACING ANY DAMAGED TILE OR GRID THAT IS A RESULT OF
THEIR WORK.
3 REFER TO ARCHITECTURAL PLANS FOR PHASING OF CONSTRUCTION.
4 THE CONTRACTOR SHALL BE RESPONSIBLE FOR INSTALLING A FIRESTOP SYSTEM IN ALL PENETRATIONS OFFIRE-RATED WALLS CREATED BY THE REMOVAL OF EXISTING ELECTRICAL CONDUIT OR CABLES, AS WELL AS
THOSE CREATED BY NEWLY INSTALLED CONDUITS AND SLEEVES.
5 WHERE INSTALLATION REQUIRES CUTTING OR DRILLING OF THE EXISTING FLOOR SLAB, THE CONTRACTORSHALL X-RAY THE EXISTING SLAB PRIOR TO WORK TO ENSURE THAT NO EXISTING UTILITIES OR STRUCTURAL
ELEMENTS IN THE SLAB WILL BE COMPROMISED BY THE WORK. NOTIFY THE ARCHITECT/ENGINEER OF ANY
CONFLICTS THAT WILL REQUIRE RELOCATING THE PROPOSED SLAB WORK. THE CONTRACTOR SHALL BERESPONSIBLE FOR THE REPAIR OF ANY DAMAGED UTILITIES OR STRUCTURAL ELEMENTS CAUSED BY THE SLAB
DEMOLITION.
6 SUPPORT ALL EXISTING CONDUITS AND JUNCTION BOXES ABOVE THE CEILING PER NEC IN THECONSTRUCTION AREA.
7 REMOVE ALL ABANDONED CONDUIT, WIRE, AND COMMUNICATION CABLES ABOVE THE CEILING IN THECONSTRUCTION AREA.
8 PROVIDE JUNCTION BOX COVER PLATES ON ALL EXISTING JUNCTION BOXES ABOVE THE CEILING IN THECONSTRUCTION AREA.
9 SUPPORT ALL EXISTING COMMUNICATION CABLES ABOVE THE CEILING IN THE CONSTRUCTION AREA
10 WHERE INFORMATION SHOWN ON THESE DRAWINGS CONFLICTS WITH VERIFIED FIELD CONDITIONS, IT SHALL BEBROUGHT TO THE ATTENTION OF THE ENGINEER
GENERAL "ELECTRICAL" NOTES1 BRANCH CIRCUIT WIRING SHALL BE NO. 12 AWG UNLESS NOTED OTHERWISE. WHERE CONDUCTOR AND
RACEWAY SIZE ARE SHOWN AT HOMERUN, SUCH SIZE SHALL BE USED FOR THE ENTIRE CIRCUIT.
EXCEPTION: FINAL CONNECTION TO DEVICES, IN OUTLET BOXES, IS NOT REQUIRED TO BE LARGER THAN NO.
12 AWG.
2 20A/120V BRANCH CIRCUITS EXCEEDING 100' IN LENGTH FROM PANEL TO FARTHEST DEVICE OR FIXTURESHALL USE NO. 10 CONDUCTORS AND 3/4"C.
3 PRIOR TO ROUGH-IN, COORDINATE THE LOCATION AND MOUNTING HEIGHT OF ALL WALL AND CEILINGMOUNTED DEVICES WITH THE ARCHITECTURAL ELEVATIONS, MILLWORK SHOP DRAWINGS, AND EXISTING
CONDITIONS. IN THE EVENT OF A CONFLICT, NOTIFY THE ARCHITECT. MINOR ADJUSTMENTS IN DEVICE
LOCATION, I.E. 5'-0" IN ANY DIRECTION SHALL BE DONE AT NO ADDITIONAL COST TO THE OWNER.
4 WHEN A RECPTACLE IS INDICATED TO BE MOUNTED ADJACENT TO A COMPUTER/TELEPHONE/TELEVISIONOUTLET, THE DEVICE(S) SHALL BE MOUNTED WITHIN 6" CENTER-TO-CENTER.
5 PROVIDE FLEXIBLE CONDUIT FOR ALL CONDUITS CROSSING EXPANSION JOINTS. REFER TO ARCHITECTURALDRAWINGS FOR LOCATION OF EXPANSION JOINTS.
6 OUTLET BOXES FOR SWITCHES, RECEPTACLES, ETC MOUNTED ON OPPOSITE SIDES OF FIRE RATED PARTITIONSSHALL NOT BE MOUNTED IN THE SAME WALL CAVITY. SEPARATE WALL PENETRATIONS BY MOUNTING ON
OPPOSITE SIDES OF WALL STUDS OR OTHER VERTICAL STRUCTURAL MEMBER IN THE WALL.
7 ALL BRANCH CIRCUITS INDICATED ON THESE PLANS TO BE LARGER THAN NO. 12 AWG SHALL BE SIZED ASINDICATED FOR THE ENTIRE LENGTH OF THE CIRCUIT.
8 RACEWAYS SHALL BE INSTALLED CONCEALED IN NEW WALL CONSTRUCTION ABOVE CEILINGS, BELOW FLOOR,AND IN OTHER CAVITIES TO THE GREATEST EXTENT POSSIBLE. WHERE EXPOSED RACEWAYS MUST BE USED,
LAYOUT RACEWAYS TO MINIMIZE THE NUMBER OF VERTICAL RUNS.
9 BRANCH CIRCUIT ROUTING SHALL COMPLY WITH DETAILS ON DRAWINGS AND SHALL BE COORDINATED WITHTHE WORK OF OTHER TRADES BEFORE AND DURING CONSTRUCTION.
10 WHERE LIGHT SWITCH AND ABOVE COUNTER RECEPTACLES ARE INDICATED TO BE MOUNTED ADJACENT TOEACH OTHER, THE DEVICES SHALL BE MOUNTED AT THE SAME HEIGHT UNDER A COMMON DEVICE PLATE.
11 REFER TO THE ARCHITECTURAL DRAWINGS FOR PROJECT PHASING.
12 THE ARRANGEMENT, GROUPING, AND ROUTING OF BRANCH CIRCUITS SHALL BE PROVIDED AT THECONTRACTOR'S DISCRETION IN ACCORDANCE WITH GENERALLY ACCEPTED PRACTICE FOR ELECTRICAL WORK,
THE NATIONAL ELECTRICAL CODE REQUIREMENTS, LOCAL ORDINANCES, AND THE FOLLOWING:
12.1 A COMMON NEUTRAL SHALL NOT BE INSTALLED IN A HOMERUN FOR 2 OR 3 BRANCH CIRCUITS UNLESSDIRECTION IS PROVIDED BY THE ENGINEER IN WRITTING FOR A SPECIFIC APPLICATION.
12.2 MULTIPLE SINGLE-POLE BRANCH CIRCUITS (UP TO 3 HOTS, 3 NEUTRALS, 1 GROUND) RATED FOR 30-AMPSOR LESS MAY BE PULLED INTO A SINGLE RACEWAY. THE CONTRACTOR SHALL BE RESPONSIBLE FOR SIZING
THE RACEWAYS AND DERATING CONDUCTORS PER NEC ARTICLE 310.15.
12.3 A GROUND CONDUCTOR SHALL BE PROVIDED IN ALL RACEWAYS UNLESS NOTED OTHERWISE.
13 WHEREVER ON THE ELECTRICAL DRAWINGS THE WORD "PROVIDE" IS USED, IT SHALL BE INFERRED TO MEAN"FURNISH AND INSTALL".
14 THE USE OF MC CABLE IS NOT ALLOWED.
15 SEAL ALL EXISTING AND NEW FIRE RATED WALL AND FLOOR PENETRATIONS IN THE CONSTRUCTION AREA
16 SEE THE ARCHITECTURAL DRAWINGS FOR ALL LOCATIONS OF FIRE RATED WALLS.
GENERAL "SIGNAL" NOTES1 ALL COMMUNICATIONS OUTLET BOXES SHALL BE 2-1/2" DEEP.
2 PROVIDE 1" CONDUIT TO ABOVE THE LOCAL ACCESIBLE CEILING FOR ALL COMMUNICATION WALL MOUNTEDDEVICES. PROVIDE SLEEVES SIZED FOR 40% EXPANSION THROUGH CORRIDOR WALLS.
3 ALL FIRE ALARM CABLE SHALL BE INSTALLED IN METALLIC CONDUIT. COORDINATES WITH FIRE ALARM SYSTEMMANUFACTURER FOR CABLE ROUTING AND QUANTITIES.
GENERAL "LIGHTING" NOTES1 SEE ARCHITECTURAL REFLECTED CEILING PLAN FOR THE EXACT LOCATION OF ALL CEILING MOUNTED LIGHTING
FIXTURES.
2 LIGHTING FIXTURE CATALOG NUMBERS ARE INDICATIVE OF THE STYLE OF FIXTURE REQUIRED. CONTRACTORSHALL PROVIDE FIXTURES WITH THE PROPER TRIM, VOLTAGE AND OPTIONS NECESSARY FOR INSTALLATION.
3 DOUBLE-FACED EXIT FIXTURES SHALL BE OF THE SAME MANUFACTURER & SERIES AS THE SINGLE TYPESPECIFIED.
4 ALL EXIT SIGNS SHALL BE CONNECTED TO LOCAL LIFE SAFETY LIGHTING CIRCUIT AHEAD OF ALL SWITCHING.
5 REFER TO ARCHITECTURAL DRAWINGS FOR MOUNTING DETAILS OF LIGHT FIXTURE TO ACOUSTICAL CEILINGSYSTEM AND STRUCTURE.
GENERAL "DEMOLITION" NOTES1 ALL ELECTRICAL EQUIPMENT TO BE REMOVED SHALL REMAIN THE PROPERTY OF THE OWNER. THE
CONTRACTOR SHALL NOT DISPOSE OF ANY MATERIALS UNTIL RELEASED BY OWNER'S PROJECT MANAGER.
MATERIALS THAT OWNER'S PROJECT MANAGER CHOOSES TO RETAIN SHALL BE DELIVERED BY THE
CONTRACTOR TO A LOCATION DESIGNATED BY THE PROJECT MANAGER. ALL OTHER MATERIALS SHALL BEPROPERLY DISPOSED OF BY THE CONTRACTOR.
2 ELECTRICAL DEVICES NOT SHOWN ON WALLS TO BE DEMOLISHED SHALL BE DEMOLISHED AT NO ADDITIONALCOST TO OWNER.
3 ELECTRICAL DEVICES NOT SHOWN ON CEILINGS OR WALLS TO REMAIN SHALL REMAIN IN PLACE. PROTECTFROM DAMAGE DURING CONSTRUCTION
4 ELECTRICAL DEVICES NOT SHOWN ON CEILINGS TO BE REMOVED SHALL BE TEMPORARILY DISCONNECTED ANDREMOVED DURING DEMOLITION AND RE-INSTALLED ON NEW CEILING IN SAME LOCATION.
ABBREVIATIONS
ABR DESCRIPTION(E) EXISTING
AFC ABOVE FINISHED CEILING
AFF ABOVE FINISHED FLOOR
AFG ABOVE FINISHED GRADE
AHU AIR HANDLING UNIT
BAS BUILDING AUTOMATION SYSTEM
BFC BELOW FINISHED CEILING
BFG BELOW FINISHED GRADE
BOD BOTTOM OF DEVICE
CBB COMMUNICATIONS BACK BOARD
cd CANDELA
CLG CEILING
ECB ENCLOSED CIRCUIT BREAKER
EF EXHAUST FAN
FACP FIRE ALARM CONTROL PANEL
FCU FAN COIL UNIT
FDS FUSED DISCONNECT SWITCH
FSD FIRE/SMOKE DAMPER
GBB GROUND BUSS BAR
GFCI GROUND-FAULT CIRCUIT-INTERRUPTING
GFI GROUND-FAULT INTERRUPTING
GP GENERAL PURPOSE
HP HEAT PUMP
ICP IRRIGATION CONTROL PANEL
IG ISOLATED GROUND
J-BOX JUNCTION BOX
LCS LIGHTING CONTROL SYSTEM
NEC NATIONAL ELECTRIC CODE
NFDS NON-FUSED DISCONNECT SWITCH
OC ON CENTER
RFAP REMOTE FIRE ALARM ANNUNCIATOR PANEL
RTU ROOF TOP UNIT
SD SMOKE DETECTOR
SPD SURGE PROTECTION DEVICE
TGB TELEPHONE GROUNDING BUSS BAR
UNO UNLESS OTHERWISE NOTED
UTP UNSHIELDED TWISTED PAIR
VFD VARIABLE FREQUENCY DRIVE
W/ WITH
WH WATER HEATER
WP WEATHERPROOF
XFMR TRANSFORMER
ELECTRICAL DRAWING INDEX
# SHEET NAMEE001 ELECTRICAL NOTES & LEGENDS
E101 ELECTRICAL DEMOLITION PLANS
E102 ELECTRICAL RENOVATION PLANS
DEMOLITION/RENOVATION NOTATIONIF NO ANNOTATION IS SHOWN ASSUME EXISTING TO REMAIN INPLACE FOR SOLID LINES AND DEMOLISH FOR DASHED LINES.
DEVICES AND EQUIPMENT NOT SHOWN SHALL BE ASSUMED TOBE EXISTING TO REMAIN IN PLACE.
E EXISTING FIXTURE OR DEVICE TO REMAIN IN PLACE. REPLACEANY BROKEN DEVICES OR PLATES; COLOR TO MATCH EXISTING.
R EXISTING FIXTURE OR DEVICE TO BE REMOVED BY THEELECTRICAL CONTRACTOR. MAINTAIN CONTINUITY OF REMAINING
PORTIONS OF BRANCH CIRCUIT.
RE EXISTING DEVICE TO BE REMOVED BY THE ELECTRICALCONTRACTOR. EXISTING CIRCUIT SHALL BE RETAINED. PROVIDE
NEW DEVICE AS SHOWN ON RENOVATION PLANS.
RN RELOCATED FIXTURE (NEW LOCATION).
RR EXISTING FIXTURE TO BE RELOCATED BY THE ELECTRICALCONTRACTOR TO NEW LOCATION SHOWN ON RENOVATION PLAN.
LIGHT FIXTURE SCHEDULE
SYMBOL
FIXTURE SPECIFICATIONS LAMPING ELECTRICAL
MOUNTING REMARKS NOTESTYPE
FIXTUREDESCRIPTION MANUFACTURER CAT. # NO. LAMP TYPE
FIXT.LOAD VOLTS
A 2x4 VOLUMETRIC LEDLIGHTING FIXTURE
HUBBELL (COLUMBIA) LCAT24-35-ML-G-ED-U - 5000 LUMENS3500K
39 277 V RECESS MTD IN GRIDCEILING
B 2x2 VOLUMETRIC LEDLIGHTING FIXTURE
HUBBELL (COLUMBIA) LCAT22-35-LW-G-ED-U - 2800 LUMENS3500K
23 277 V RECESS MTD IN GRIDCEILING
BE 2x2 VOLUMETRIC LEDLIGHTING FIXTURE WITH
CONNECTION TO
EMERGENCY GENERATOR
HUBBELL (COLUMBIA) LCAT22-35-LW-G-ED-U - 2800 LUMENS3500K
23 277 V RECESS MTD IN GRIDCEILING
X EXIT SIGN HUBBELL (COLUMBIA) CCES(D)R - LED 1 277 V CEILING MTD
LIGHT FIXTURE SCHEDULE NOTES1 LUMENS LISTED IN SCHEDULE REPRESENT DELIVERED LUMENS OF FIXTURES.
2 THREE DIGIT NUMBERS LISTED IN LAMP COLUMN REPRESENT CRI AND COLOR TEMPERATURE. FIRST DIGITINDICATES MINIMUM CRI AND LAST TWO DIGITS INDICATE COLOR TEMPERATURE. EXAMPLE: 830 INDICATES
MINIMUM CRI OF 80 AND A COLOR TEMPERATURE OF 3000K.
3 SEE ARCHITECTURAL RCP AND ELEVATIONS FOR EXACT LOCATION AND MOUNTING HEIGHTS.
4 CONFIRM QUANTITIES OF FIXTURES SHOWN IN RCP MATCH QUANTITIES SHOWN ON ELECTRICAL PLANS PRIORTO BID. IF NO DISCREPANCIES ARE NOTED PRIOR TO BID THE HIGHEST QUANTITY OF EACH FIXTURE TYPE
SHOWN SHALL BE PROVIDED.
LIGHTING CONTROL SCHEME LEGEND
MARKMANUAL / WALL
STATION(S)MULTI-LEVEL
SWITCHED/ZONEDOCCUPANCYSENSOR
VACANCYSENSOR
SCHEDULEDAUTO-ON
SCHEDULEDAUTO-OFF
DAYLIGHT CONTROLPLUGLOADCONTROL
NOTESDAYLIGHTON / OFF
DAYLIGHTDIMMED
1 Yes No No Yes No No No No No 1,2,3
2 No No Yes No No No No No No 3
# LIGHTING CONTROL SCHEME NOTES1 MANUAL WALL SWITCH SHALL BE PART OF THE LIGHTING CONTROL SYSTEM. REFER TO PLANS FOR MANUAL
WALL STATION LOCATION(S) IN EACH SPACE.
2 ROOMS WITH DIMMING TYPE SWITCHES SHOWN IN PLAN WILL REQUIRE DIMMING CONTROL
3 SET DELAYS FOR ALL OCCUPANCY AND VACANCY SENSORS TO 20-MINS.
NOT TO SCALEE001
1 KEYPLAN
No. Description Date
PHRC
- REN
OV
ATI
ON
PRO
JECT
2N
D F
LOO
R SU
ITE
Uni
vers
ity
Proj
ect
No:
FP0
0000
192
JJ
JJ
JJ
JJ
JJ
J
F
S
S
S
S
S
SS
C
S
A/V
A/V
A/V
A/V
A/V
A/V
A/V
A/V
R
RR
R
R R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R E
R
R
RRR
RRR
RRR
RR
E
R
R
R
R
R
R
R
R
R
R
V203
VESTIBULE 224
OFFICE 225OFFICE
226
OFFICE
227
OFFICE
228OFFICE
240STORAGE
222OFFICE
H207CORRIDOR
221OFFICE 239
OFFICE 229OFFICE
230OFFICE
231
OFFICE
237
OFFICE
238OFFICE
220OFFICE
219
OFFICE
236
OFFICE 232
OFFICE
H209CORRIDOR
218
OFFICE
217TELE/COMM
235OFFICE 233
OFFICE
234
BREAK
ROOM
212A
WORK/FILE
AREA
213
STORAGE
214
OFFICE
215OFFICE
H209
CORRIDOR
ALTERNATE NO.1 - REPLACE
CORRIDOR LIGHTING
FIXTURES (TYP.)
E
R
R
E
RRR
E
E
R
E
R
E
RR
REEEEEE
R
R
R
R
R
R
E
E
ERR
EE
E
RR
E
R
R
E
RR
EE
RR
E
E
E
E
E
E
EE
R
E
E
R
R
R E
E
E
E
E
E
E
EE
RR
EXISTING PANEL "PLNC2"
EXISTING PANEL "PLND2"
E
1
1
1
11
22
3
3
3
1
1
1
E
WAPE 1
WAP
E
1
V203VESTIBULE
224OFFICE
225
OFFICE
226
OFFICE
227OFFICE
222
OFFICE 240STORAGE
228
OFFICE
239OFFICE
H209
CORRIDOR
229OFFICE
230OFFICE
238OFFICE
220OFFICE
221OFFICE
219OFFICE
237OFFICE
231OFFICE
232OFFICE
236OFFICE218
OFFICE
217TELE/COMM
235OFFICE
233OFFICE
234
BREAK
ROOM212A
WORK/FILE
AREA
212
RECEPTION
H209CORRIDOR
213STORAGE
214OFFICE
215
OFFICE
(803) 731-0650 p | (803) 731-2880 f
ENGINEERING
7 CLUSTERS COURT, SUITE 201 | COLUMBIA, SC | 29210
ASSOCIATES, INC.
BELKA
CONTACT: CLIFF STRINGFIELD
(803) 731-0650 p | (803) 731-2880 f
ENGINEERING
7 CLUSTERS COURT, SUITE 201 | COLUMBIA, SC | 29210
ASSOCIATES, INC.
BELKA
CONTACT: CLIFF STRINGFIELD
(803) 731-0650 p | (803) 731-2880 f
ENGINEERING
7 CLUSTERS COURT, SUITE 201 | COLUMBIA, SC | 29210
ASSOCIATES, INC.
BELKA
CONTACT: CLIFF STRINGFIELD
OB21808OB21808OB21808
No. C00953
ASSOC. INC.
BELKA
ENGINEERING
A
NILORACHTU
O
S
CE
RT
I FI CATE OF AUTHOR
I ZA
TI O
N
No. C00953
ASSOC. INC.
BELKA
ENGINEERING
A
NILORACHTU
O
S
CE
RT
I FI CATE OF AUTHOR
I ZA
TI O
N
No. C00953
ASSOC. INC.
BELKA
ENGINEERING
A
NILORACHTU
O
S
CE
RT
I FI CATE OF AUTHOR
I ZA
TI O
N
No. 26181
R
A
NILORACHTU
O
S
J EE
NI
GN
E
LANOISSEF
OR
PD
ES
NE
CILA
S
ON E
AR
T
L.HERA
No. 26181
R
A
NILORACHTU
O
S
J EE
NI
GN
E
LANOISSEF
OR
PD
ES
NE
CILA
S
ON E
AR
T
L.HERA
No. 26181
R
A
NILORACHTU
O
S
J EE
NI
GN
E
LANOISSEF
OR
PD
ES
NE
CILA
S
ON E
AR
T
L.HERA
0
DATE
221 PICKENS STREET (29205)POST OFFICE BOX 5875
COLUMBIA, SOUTH CAROLINA
29250803.834.4048 p803.834.4082 f
WWW.1X1DESIGN.COM
SHEET NUMBER
PROJECT NUMBER
REVISIONS
SHEET NAME
CLIE
NT
NA
ME
PR
OJE
CT
NA
ME
PR
OJE
CT
AD
DR
ES
S
This
dra
win
g a
nd the info
rmation s
how
n there
on a
re p
ropert
y o
f B
elk
a E
ngin
eering &
Associa
tes, In
c. T
his
dra
win
g m
ay n
ot be p
ublis
hed, re
pro
duced, copie
d, m
odifie
d, uplo
aded, tr
ansm
itte
d, poste
d, tr
ansfe
rred o
r oth
erw
ise u
sed w
ithout th
e p
rior
written c
onsent of B
elk
a E
ngin
eering &
Associa
tes, In
c. L
egal action w
ill b
e p
urs
ued a
gain
st all
vio
lations a
nd infr
ingem
ents
to the full
exte
nt possib
le.
GENERAL NOTES
8 16 24 32
SCALE: 1/8" = 1'-0"
12-14-18
12
/17
/20
18
4:5
4:0
3 P
M
E101
ELECTRICAL DEMOLITIONPLANS
U-17-039-1
12.20.18
UN
IVE
RS
ITY
OF
SO
UT
H C
AR
OL
INA
921 A
SS
EM
BLY
ST
RE
ET
, C
OLU
MB
IA,
SC
29208
RE
LE
AS
ED
FO
R B
IDD
ING
– D
EC
EM
BE
R 2
0,
20
18
KEY NOTES
1 REMOVE EXISTING FIRE ALARM & SECURITY DEVICES FROM EXISTINGCEILING. BAG DURING RENOVATION AND RE-INSTALL IN NEW CEILINGS.
2 REMOVE EXISTING RECEPTACLES AND DATA OUTLETS FROM FLOORBOXAND PROVIDE BLANK COVERS.
3 AT COLUMNS, REMOVE DATA J-BOXES THAT CONFLICT WITH NEW WALLS.
1 REMOVE EXISTING LIGHTING AS INDICATED AND TURN OVER TO OWNER.EXISTING LIGHTING CIRCUITS (PHN2-5, PHN2-7 AND PHN2-11) SHALL
BE REUSED FOR PROVIDED LIGHTING SHOWN ON RENOVATION PLAN.
2 REMOVE EXISTING RECEPTACLES AND ASSOCIATED CONDUIT/CONDUCTORSAS INDICATED. MAINTAIN CONTINUITY OF EXISTING CIRCUITS. EXISTING
CIRCUITS ORIGINAL IN EXISTING PANELS "PLN2C" AND "PLN2D."
3 PROVIDE BLANK COVER PLATES ON ALL UNUSED BOXES.
DEMOLITION/RENOVATION NOTATIONIF NO ANNOTATION IS SHOWN ASSUME EXISTING TO REMAIN INPLACE FOR SOLID LINES AND DEMOLISH FOR DASHED LINES.
DEVICES AND EQUIPMENT NOT SHOWN SHALL BE ASSUMED TOBE EXISTING TO REMAIN IN PLACE.
E EXISTING FIXTURE OR DEVICE TO REMAIN IN PLACE. REPLACEANY BROKEN DEVICES OR PLATES; COLOR TO MATCH EXISTING.
R EXISTING FIXTURE OR DEVICE TO BE REMOVED BY THEELECTRICAL CONTRACTOR. MAINTAIN CONTINUITY OF REMAINING
PORTIONS OF BRANCH CIRCUIT.
RE EXISTING DEVICE TO BE REMOVED BY THE ELECTRICALCONTRACTOR. EXISTING CIRCUIT SHALL BE RETAINED. PROVIDE
NEW DEVICE AS SHOWN ON RENOVATION PLANS.
RN RELOCATED FIXTURE (NEW LOCATION).
RR EXISTING FIXTURE TO BE RELOCATED BY THE ELECTRICALCONTRACTOR TO NEW LOCATION SHOWN ON RENOVATION PLAN.
SCALE: 1/8" = 1'-0"E101
1 LIGHTING DEMOLITION PLANSCALE: 1/8" = 1'-0"E101
2 POWER & SYSTEMS DEMOLITION PLAN
No. Description Date
PHRC
- REN
OV
ATI
ON
PRO
JECT
2N
D F
LOO
R SU
ITE
Uni
vers
ity
Proj
ect
No:
FP0
0000
192
JJ
JJ
JJ
J
S
S
SS
C
A/V
A/V
A/V
A/V
S
S
S
A/V
J
J
A/V
A/V
A/V
F
SHADING INDICATES EMERGENCY FIXTURE USED BY GENERATOR
AE = UPPERCASE LETTER / LETTERS INDICATE FIXTURE TYPEd = LOWERCASE LETTER INDICATES SWITCH IDENTIFICATION9 = DESIGNATES CIRCUIT NUMBER
NOTE:ALL "EM" FIXTURES INDICATED IN PLAN CONTAIN CONNECTION TO GENERATOR. ALL EMERGENCY BALLAST FIXTURES REQUIRE AN EXTRA CONSTANT POWER CONDUCTOR TO BE CONNECTED TO THE EMERGENCY BALLAST FOR CHARGING. CONDUCTOR MUST NOT BE CONTROLLED BY ANY LIGHTING SYSTEM OR HAVE POWER INTERUPTED AT ANY TIME.
CE
LIGHT FIXTURE PLAN KEY
LIGHTING CONTROL SYMBOL CORRELATES WITH DESIRED CONTROL SCHEME AS INDICATED IN THE LIGHTING CONTROL SCHEME SCHEDULE
LIGHT CONTROL SCHEME
d
9
V203VESTIBULE
224
OFFICE
225
OFFICE
226OFFICE
227OFFICE
241OFFICE
223OFFICE
H207CORRIDOR
216FOFFICE
216EOFFICE
216D
OFFICE
216C
OFFICE
222
OFFICE
240STORAGE
228
OFFICE
229OFFICE
H209
CORRIDOR
239
OFFICE
221OFFICE
216BOFFICE
220
OFFICE
219
OFFICE
237
OFFICE
238
OFFICE
230
OFFICE
231
OFFICE
232
OFFICE
236
OFFICE
218
OFFICE
233
OFFICE
235OFFICE
217
TELE/COMM
216AOFFICE
215OFFICE
213STORAGE
214OFFICE
212
RECEPTION
212A
WORK/FILE
AREA 234
BREAK
ROOM
H209
CORRIDOR
BEBBE
B
B
BE
AA
B
BE
B
BE
B
BE
AA
AA
AA
AA
AA
B B
B B
B B
B
B B
BE B
B
X
X
3
A
A
3
A
A A
A
DD
DD
DD
D
D
1
1
1
1 X
X
X
R
3
f
1
ddd
d
d
d
d
d
d
d
d
d
d
d
1
1
1
1
1
1
1
1
11
2
2
2
5 5
55
5 11 11
7
7 7
7
11
5
5
5
5 5
5
55
5
5
55
5 5
5
55
5 5
55
5
5
55 11 11
1111
11
11
11
11
1111
b
b b
bb
b
c
c
3 f
B
B
BE
B
BE
B
BE
B
BE
1
1
1
f
f
f
f
f
f
f
f
f
11
11
11
11
11
11
11
11
11
1
1
ALTERNATE NO. 1 - PROVIDE
LIGHTING FIXTURES IN THIS
CORRIDOR (TYP).
E
11
V203VESTIBULE 224
OFFICE225
OFFICE
226OFFICE
227OFFICE
228OFFICE
240STORAGE
241OFFICE
223OFFICE
222OFFICE216D
OFFICE
216EOFFICE
216F
OFFICE
H207
CORRIDOR
221OFFICE
216COFFICE
216BOFFICE
216AOFFICE
239OFFICE
H209
CORRIDOR
229
OFFICE
230
OFFICE
238
OFFICE
220
OFFICE
219
OFFICE
237
OFFICE
231
OFFICE
232OFFICE
236
OFFICE
218
OFFICE
217
TELE/COMM
235
OFFICE
233
OFFICE
234
BREAK
ROOM
212A
WORK/FILE
AREA212
RECEPTION
213
STORAGE
214OFFICE
215
OFFICE
RN
RN
RN
E
E
EE
E
E
E
E
E
E E
E
E
E
E
E
E E
E
E
E
E
E
E
EE
EE
E
E
E102
5
E
E
E
E EE E E
EE
EXISTING PANEL "PLNC2"
EXISTING PANEL "PLND2"
PLND2-1
PLND2-3
PLND2-3
PLND2-37
PLND2-37
PLND2-37
PLND2-35
PLND2-35
PLND2-35
PLNC2-31
PLNC2-31
PLNC2-31
PLNC2-31
PLNC2-23
PLNC2-23
PLNC2-23
PLNC2-23
PLNC2-25
PLNC2-25
PLNC2-19
PLNC2-19PLNC2-19
PLNC2-19
2
RN
E
WAPE
WAPE
E
PLNC2-25
PLNC2-25
PLNC2-31
PLNC2-23
15cd
RN
15cd
RN
15cd
RN
3
3
3
3
FIRE
12"
DOOR, OPENING
OR END OF
WALL
NOTE:
DEVICES SHOWN WITHIN 48" OF EACH OTHER ON ALL ELECTRICAL PLANS SHALL BE ALIGNED
PER THIS DETAIL. IF DEVICES ARE SHOWN IN MIDDLE OF WALL, THEN CENTER DEVICES ON
WALL.
18"
48"
SEE LEGEND
TELEVISION
DEVICE
RECEPTACLE
VOICE/DATA OUTLET
LIGHT
SWITCH
HVAC THERMOSTAT,
HUMIDISAT, CO
SENSOR, ETC.
FIRE ALARM ANNUNCIATION DEVICE
6"
CL
PHONE OUTLET
CARD
READER
6"
6"
6"
FLOOR 214' - 0"
PLNC2-19
216A
OFFICE
3/4" CONDUIT FOR POWER
1" CONDUIT FOR DATA
PLNC2-19
FLATSCREEN BACK BOX
18"
1 1/4"
CONDUIT
FOR DATA
3/4"
CONDUIT
FOR POWER
(803) 731-0650 p | (803) 731-2880 f
ENGINEERING
7 CLUSTERS COURT, SUITE 201 | COLUMBIA, SC | 29210
ASSOCIATES, INC.
BELKA
CONTACT: CLIFF STRINGFIELD
(803) 731-0650 p | (803) 731-2880 f
ENGINEERING
7 CLUSTERS COURT, SUITE 201 | COLUMBIA, SC | 29210
ASSOCIATES, INC.
BELKA
CONTACT: CLIFF STRINGFIELD
(803) 731-0650 p | (803) 731-2880 f
ENGINEERING
7 CLUSTERS COURT, SUITE 201 | COLUMBIA, SC | 29210
ASSOCIATES, INC.
BELKA
CONTACT: CLIFF STRINGFIELD
OB21808OB21808OB21808
No. C00953
ASSOC. INC.
BELKA
ENGINEERING
A
NILORACHTU
O
S
CE
RT
I FI CATE OF AUTHOR
I ZA
TI O
N
No. C00953
ASSOC. INC.
BELKA
ENGINEERING
A
NILORACHTU
O
S
CE
RT
I FI CATE OF AUTHOR
I ZA
TI O
N
No. C00953
ASSOC. INC.
BELKA
ENGINEERING
A
NILORACHTU
O
S
CE
RT
I FI CATE OF AUTHOR
I ZA
TI O
N
No. 26181
R
A
NILORACHTU
O
S
J EE
NI
GN
E
LANOISSEF
OR
PD
ES
NE
CILA
S
ON E
AR
T
L.HERA
No. 26181
R
A
NILORACHTU
O
S
J EE
NI
GN
E
LANOISSEF
OR
PD
ES
NE
CILA
S
ON E
AR
T
L.HERA
No. 26181
R
A
NILORACHTU
O
S
J EE
NI
GN
E
LANOISSEF
OR
PD
ES
NE
CILA
S
ON E
AR
T
L.HERA
0
DATE
221 PICKENS STREET (29205)POST OFFICE BOX 5875
COLUMBIA, SOUTH CAROLINA
29250803.834.4048 p803.834.4082 f
WWW.1X1DESIGN.COM
SHEET NUMBER
PROJECT NUMBER
REVISIONS
SHEET NAME
CLIE
NT
NA
ME
PR
OJE
CT
NA
ME
PR
OJE
CT
AD
DR
ES
S
This
dra
win
g a
nd the info
rmation s
how
n there
on a
re p
ropert
y o
f B
elk
a E
ngin
eering &
Associa
tes, In
c. T
his
dra
win
g m
ay n
ot be p
ublis
hed, re
pro
duced, copie
d, m
odifie
d, uplo
aded, tr
ansm
itte
d, poste
d, tr
ansfe
rred o
r oth
erw
ise u
sed w
ithout th
e p
rior
written c
onsent of B
elk
a E
ngin
eering &
Associa
tes, In
c. L
egal action w
ill b
e p
urs
ued a
gain
st all
vio
lations a
nd infr
ingem
ents
to the full
exte
nt possib
le.
GENERAL NOTES
8 16 24 32
SCALE: 1/8" = 1'-0"
12-14-18
12
/17
/20
18
4:5
4:0
6 P
M
E102
ELECTRICAL RENOVATIONPLANS
U-17-039-1
12.20.18
UN
IVE
RS
ITY
OF
SO
UT
H C
AR
OL
INA
921 A
SS
EM
BLY
ST
RE
ET
, C
OLU
MB
IA,
SC
29208
RE
LE
AS
ED
FO
R B
IDD
ING
– D
EC
EM
BE
R 2
0,
20
18
KEY NOTES
1 PROVIDE GENERATOR TRANSFER DEVICE (BODINE# GTD20 OR EQUAL) FORCORRIDOR EMERGENCY EGRESS FIXTURES. GTD SHALL BE CONNECTED
WITH NORMAL POWER CIRCUIT AND UNSWITCHED GENERATOR-BACK
CIRCUIT (PLS2-1).
2 IN CONFERENCE ROOM, PROVIDE TV ROUGH-IN BOX (CHIEF #PAC-526FOR EQUAL) WITH 20 AMP DUPLEX RECEPTACLE. FROM TV ROUGH-IN BOX
PROVIDE ONE 1-1/4"C. DOWN TO 4" SQUARE BOX MOUNTED ADJACENT
TO DUPLEX RECEPTACLE. SEE ELEVATION DETAIL ON THIS DRAWING.
3 FIRE ALARM DEVICE SHALL BE SET TO 15CD. (TYP. IN CORRIDORS)
1 PROVIDE LIGHTING FIXTURES AS INDICATED AND FEED WITH EXISTINGCIRCUITS FROM EXISTING PANEL "PHN2" (SEE KEY PLAN ON DRAWING
E-100 FOR PANEL LOCATION). EXISTING CIRCUITS CAN BE EXTENDED
FROM J-BOXES ABOVE CEILING. EMERGENCY EGRESS LIGHTING SHALLBE FED WITH EXISTING CIRCUIT "PLS2-1" (PANEL LOCATED IN SAME
ELECTRICAL ROOM AS "PHN2").
2 PROVIDE 20 AMP DUPLEX RECEPTACLES AS INDICATED AND FEED WITHEXISTING CIRCUITS FROM EXISTING PANELS "PLN2C" OR "PLN2D" AS
NOTED. ALL WIRING DEVICES AND PLATES SHALL MATCH EXISTING
(GRAY DEVICES WITH SMOOTH STAINLESS-STEEL DEVICE PLATES.
3 FOR DATA LOCATIONS, PROVIDE 4" SQUARE, 2-1/2" DEEP BOX WITHSINGLE GANG PLASTER RING AND 1" CONDUIT FROM BOX TO ABOVE
CEILING OUT INTO CORRIDOR. PROVIDE PULL STRING IN CONDUIT AND
PLASTIC GROMMET ON END OF CONDUIT.
4 RELOCATE EXISTING FIRE ALARM INDICATING DEVICES AS INDICATED ONDEMOLITION AND RENOVATION PLANS.
SCALE: 1/8" = 1'-0"E102
1 LIGHTING RENOVATION PLANSCALE: 1/8" = 1'-0"E102
2 POWER & SYSTEMS RENOVATION PLAN
NOT TO SCALEE102
4 DEVICE ALIGNMENT DETAIL
DEMOLITION/RENOVATION NOTATIONIF NO ANNOTATION IS SHOWN ASSUME EXISTING TO REMAIN INPLACE FOR SOLID LINES AND DEMOLISH FOR DASHED LINES.
DEVICES AND EQUIPMENT NOT SHOWN SHALL BE ASSUMED TOBE EXISTING TO REMAIN IN PLACE.
E EXISTING FIXTURE OR DEVICE TO REMAIN IN PLACE. REPLACEANY BROKEN DEVICES OR PLATES; COLOR TO MATCH EXISTING.
R EXISTING FIXTURE OR DEVICE TO BE REMOVED BY THEELECTRICAL CONTRACTOR. MAINTAIN CONTINUITY OF REMAINING
PORTIONS OF BRANCH CIRCUIT.
RE EXISTING DEVICE TO BE REMOVED BY THE ELECTRICALCONTRACTOR. EXISTING CIRCUIT SHALL BE RETAINED. PROVIDE
NEW DEVICE AS SHOWN ON RENOVATION PLANS.
RN RELOCATED FIXTURE (NEW LOCATION).
RR EXISTING FIXTURE TO BE RELOCATED BY THE ELECTRICALCONTRACTOR TO NEW LOCATION SHOWN ON RENOVATION PLAN.
NOT TO SCALEE102
5 CONFERENCE ROOM ELEVATION
No. Description Date
PHRC
- REN
OV
ATI
ON
PRO
JECT
2N
D F
LOO
R SU
ITE
Uni
vers
ity
Proj
ect
No:
FP0
0000
192